Download pdf - Seperator Logics

Transcript
  • 7/30/2019 Seperator Logics

    1/44

    Start up system and

    seperator logics 660MW

    (DHI make) boiler

  • 7/30/2019 Seperator Logics

    2/44

  • 7/30/2019 Seperator Logics

    3/44

    BOILER START-UP AND

    OPERATIONAL PROCEDURES

    Cold Start Up conditions Greater than 72 hours shutdown.

    Boiler pressure < 1 kg/cm2 (g)

    Preparation for BLU Chemical cleaning and steam blowing completion (for

    the first time)

    All interlocks and protections in service All instrumentation and associated mechanicalequipment has been checked out and is available forservice.

  • 7/30/2019 Seperator Logics

    4/44

    Oil firing equipment checked out to ensureproper functioning

    Warm-up oil guns have been inserted properly andcoupled.

    All oil guns quick connect couplings are properlyassembled.

    All manual valves are opened.

    All control valves are closed.

    Pulverisers and feeders are available forservice

    SADC checking complete & burner tilthorizontal

    Feedwater system is through and atleast onefeed water pump available.

  • 7/30/2019 Seperator Logics

    5/44

    The deaerator aux. steam supply is available

    and feedwater in deaerator is at 105C.

    BCP checked out completely Suction and discharge iso. Valves open

    All pump instrumentation available in service

    Pump diff. pressure transmitters in service

    Ensure proper trip settings have been made

    The steam generator start-up system valves

    are ready for operation (UG, WR, ZR valves),

    with isolation valves open. The separator levelcontrol for WR and ZR valves has been

    checked and is available for service.

  • 7/30/2019 Seperator Logics

    6/44

    The startup system drain transfer system is ready for

    operation. This system includes WR and ZR valves,

    the flash tank and connecting pipe to condenser.

    Steam supply isolating valves to the steam coil air

    pre-heaters are open.

    Cooling water system is in operation

    All air and gas handling equipment has been checked

    and is available for service.

    Air heater ready for service & means for extinguishing

    APH fire is available.

    The soot blowing equipment has been checked for

    proper operation and the system is in the start-up

    mode with all blowers retracted and the main steam

    supply valve closed.

  • 7/30/2019 Seperator Logics

    7/44

    All desuperheater spray water control and blockvalves valves are closed.

    All boiler, superheater, and reheater drain valves areopen, and all vent valves are closed. The economizerand furnace wall drain valves are closed, andeconomizer vent valves are open.

    The aux. steam isolation line from the superheater is

    isolated. The warming system of the boiler superheaters is

    isolated.

    The furnace gas temperature probe(s) is in workingorder and available for service.

    The HP and LP bypass stations are available forservice, and hydraulic stations are in operation. Thewater supply for desuperheating has beenestablished.

  • 7/30/2019 Seperator Logics

    8/44

    The condenser is available in service, with circulationwater flow and vacuum has been established toaccept water flow from Start-up flash tank and theSCAPH drain tank and LP bypass (condenserpressure set point interlock of LP bypass).

    The main steam stop cum control valves and the hotreheat stop and control valves are closed. Drainvalves on the main, cold reheat and hot reheat linesare open.

    The condensate polishing plant is available foroperation.

    The TG has been prepared and is available forservice

    Warm water filling The entire economizer, furnace wall and seperator

    system should be filled with warm deaerated water(105C)

  • 7/30/2019 Seperator Logics

    9/44

    The following procedure shall be carried out to ensurethat the water system is free of air :-

    The economiser outlet vent valve is open.

    BFP (M) is started at minimum speed and flow according tofeed pump operating procedures.

    Water system is to be filled with approx. 10 % BMCRfeedwater flow. When level in the seperator reaches set-pt.,the WR valve will begin to open. When the WR valve reaches

    > 30% open for approx. 1 min., feedwater flow set pt. isincreased to 30 % TMCR. As the drain flow increases, WRvalve will reach full open and ZR valve will begin to open.The water system is considered full when :-

    The seperator water level remains stable for two minutes.

    And The WR valve is fully opened and ZR valve is >15 %

    opened for two (2) minutes. After filling of water system, the feedwater pump is stopped.

    Water level in deaerator must be re-established andmaintained and water temperature at 105C is reestablished.

  • 7/30/2019 Seperator Logics

    10/44

    Restart the feed water pump and establish feedwater flow of

    10 % BMCR to the boiler.

    Water recirculation for clean up

    Feed water clean up recirculation is required to

    ensure that feedwater quality at the o/l. of seperator

    and deaerator is within specified limits.

    During this time, a constant feedwater flow of 10 %

    BMCR is maintained.

    Feed water flows through

    Ecomomiser and Evaporator and discharges the boiler

    through the WR valve to the flash tank and via connecting

    pipe to the condenser. From condenser, water flows through

    the CPP, which is in service to remove impurities,then

    returns to the feedwater tank.

  • 7/30/2019 Seperator Logics

    11/44

    Start of Boiler Circulation Pump The following preparatory work needs to be completed :-

    Feed water quality within specified limits.

    Feed water flow set point at 10% BMCR.

    Seperator water level stable at normal level. Cooling water flow to the HP cooler of BCP adequate.

    Suction valves and discharge valves are open.

    Set the UG valve at min. position and start BCP as per pumpoperating instructions.

    As soon as pump is running, open the UG valve to establish min.

    water wall flow at 30% TMCR. With BCP in operation, flow through the economiser and water

    wall tubes increases substantially.

    Initial firing precautions

    Atleast 30% of the TMCR load air flow must be maintained toproduce the following conditions :- An air rich atmosphere to prevent accumulation of an explosive

    mixture

    High excess air through the APHs

  • 7/30/2019 Seperator Logics

    12/44

    Boiler Light Up Start the Secondary Air Preheater

    Start one ID fan, then the corresponding FD fan andadjust air flow to a max. of 30% TMCR

    Start the second draft group

    Start the selected scanner air fan.

    Adjust fan and SADC to permit a purge air flow of

    atleast 30% of TMCR and furnace draft of approx. -12.7 mmWC.

    When fans are started, SADC should modulate theaux. air dampers to maintain WB to furnace DP at 102

    mmWC(g). Check that all other purge permissives are satisfied.

    Place FTPs in service.

    Initiate a furnace purge.

  • 7/30/2019 Seperator Logics

    13/44

    After furnace purge check the followingconditions

    FW control is on auto maintaining FW flow rate ofapprox. 5% TMCR.

    Start-up system (BCP and UG valve) is onautomatic maintaining minimum waterwall flow.

    Seperator level control is on auto, i.e the WR and

    ZR level control valves are all in automatic. Furnace pressure control is on auto.

    Unit air flow is on auto maintaining 30% TMCR airflow.

    Place HP bypass valve in operation Place LP bypass valve in operation

    Place SH and RH temp. controls on auto. Withsetpoints of 350 C for SH and 320 C for RH.

  • 7/30/2019 Seperator Logics

    14/44

    Open SH division panel vent valves, SH backpassdrain valves and RH outlet vent valves.

    Initiate a light-up sequence of oil elevation AB warm-up oil guns.

    Set fuel oil flow control to auto and adjust the TMCRto 5 % of TMCR firing rate.

    When elevation AB is in service, close theeconomizer vent valves.

    After a 5 minute stabilization period, progressivelyincrease firing rate to 10 % TMCR at a rate of 0.5%per minute.

    To ensure stable operation of the water system and toensure sufficient steam flow through the superheater,firing rate shouldnot be further increased until 8kg/cm2 (g) is measured in the water seperator.

  • 7/30/2019 Seperator Logics

    15/44

    As the pressure is raised, first the WR and then the

    ZR valves will open when seperator water level

    increases due to boiler water swell. As the pressure

    further increases,the WR and ZR valves will start toclose as the water level decreases.

    During all start-ups, control the firing rate to keep the

    max. FEGT below 538 C, as measured by the

    furnace temperature probes until approx. 10% steamgeneration or the turbine is synchronized.

    The superheat backpass drain valve can be closed

    when seperator pressure reaches 5 kg/cm2 (g).

    Progressively increase LP bypass set point to 12kg/cm2(g).

    Close the RH o/l. vent valves when RH pressure

    reaches 5 kg/cm2.

  • 7/30/2019 Seperator Logics

    16/44

    Increase LP bypass set pt. to 12 kg/cm2(g). As theHP bypass opens, the reheater will be warmed andpressurized cas steam is passed through the LPbypass and reheater vents.

    Close the reheat outlet vent valves when RH pressurereaches 5 kg/cm2(g).

    When steam pressure at HP bypass reaches 12kg/cm2(g), the HP bypass valve is released topressure ramp mode

    Initiate an elevation start command for other oilelevations.

    After a 5 minute stabilization period, progressivelyincrease firing rate to 15% TMCR at a rat of 0.5% perminute.

    The rate of pressure rise should follow the prescribedstart up curves

    When boiler pressure reaches 90 kg/cm2(A), the HPbypass valve is released to pressure control modeand maintains a constant pressure during rolling.

  • 7/30/2019 Seperator Logics

    17/44

    After a pressure of 90 kg/cm2 is attained the firingrate can be adjusted to achieve the reqd. steamtemperature for turbine rolling. Target steamconditions are:- 10% TMCR steam flow, SH = 350 C,RH = 320 C.

    Maintain seperator water level at normal and checkthe boiler water concentrations and constituents asfrequently as necessary to maintain proper boilerwater conditions.

    Turbine rolling and synchronisation Confirm the steam conditions, i.e. pressure,

    temperature

    Roll turbine using reheat steam. During this time totalsteam passes through HP bypass while it remains onpressure control mode.

    SH and RH steam temperatures are maintained byadjusting firing rate and air flow.

  • 7/30/2019 Seperator Logics

    18/44

    Synchronize generator and put on initial load of app.10% according to TG start up instructions.

    After synchronization, all superheat and reheat vent

    and drain valves should be closed. As steam is transferred to the IP turbine during

    turbine loading, the LP bypass will close whilemaintaining reheat pressure at 12 kg/cm2.

    Increase firing rate to 20 % TMCR at a rate of 0.5%per minute.

    As turbine conditions permit, put feed water heatersinto service as per manufacturers instructions.

    The firing rate should never exceed the rate

    necessary to match the total steam generation. If the unit was started with one set of fans in service,

    start the second set of fans as required.

  • 7/30/2019 Seperator Logics

    19/44

    Introduction of coal Coal firing can commence when steam flow reaches

    approximately 20% TMCR and LP bypass is closed.

    Start the first pulverizer At a prescribed load as per turbine manufacturer, the

    HP turbine is transferred to forward flow. At first threeturbine control valves are opened until sufficient flowis established through the HP section of the turbine.

    The HP bypass valve compensates by closing tocontrol the steam pressure at set point.

    Continue the transfer to forward flow until the firstthree turbine valves are fully opened and HP bypassvalves are fully closed.

    Start the second pulverizer when the HP bypass isclosed.

    Increase the total firing rate to 30% TMCR at a rate of0.5% per minute by increasing each coal elevationloading.

  • 7/30/2019 Seperator Logics

    20/44

    Initial load increase The third pulverizer can be started after steam flow

    reaches 25-30% TMCR. Place additional pulverizers

    in service in a similar manner. Pre-warm thepulverizer initiate an elevation start command. Afterthe coal elevation is proven in service the feeder isput into automatic.

    Increase total firing rate to 35% TMCR.

    After reaching 30% TMCR load and firing is stable, oilelevation AB is issued an elevation stop command bythe operator

    After oil elevation AB is stopped ensure that coal el. Aor C shows flame through flame scanner indications.

    Reduce oil firing to minimum After stable firing is established, put into service the

    second BFP(T) as per manufacturers procedures.

    Start the ESP as per manufacturers instructions.

  • 7/30/2019 Seperator Logics

    21/44

    The steam temperature at the seperator inlet will

    reach a stable superheated condition at

    approximately 30% TMCR, causing the level in the

    seperator to decrease and eventually disappear. The

    boiler is now in once-through mode (dry mode). The

    BCP will be stopped automatically.

    When the BCP stops, the warm-keeping system of

    the start-up system should be put into operation.

  • 7/30/2019 Seperator Logics

    22/44

  • 7/30/2019 Seperator Logics

    23/44

  • 7/30/2019 Seperator Logics

    24/44

  • 7/30/2019 Seperator Logics

    25/44

  • 7/30/2019 Seperator Logics

    26/44

    Wet mode and Dry mode of operation

  • 7/30/2019 Seperator Logics

    27/44

    Operational Logics for Mixing Piece Upstream

    Valve orBCP circ. Shut-off MOV

    Open permissive If WET mode of operation is selected AND

    DRY mode is not selected

    Close permissive

    BCP off Auto opening

    Open permissives present AND any of the following conditionsare present

    MFT has operated OR

    Open command from start sequence for BCP circ. Shut off valve(Mixing piece upstream valve) OR

    System in wet mode of operation for 3 seconds

    Auto closing If system is in dry mode of operation for 3 seconds.

  • 7/30/2019 Seperator Logics

    28/44

    Operational logics for Boiler

    recirculation Pump

    Start permissive UG valve opening > min. (15 %)AND

    BCP circ. Shutoff MOV openedAND

    BCP inlet shut off MOV openedAND

    BCP outlet shut off MOV openedAND

    BCP inlet manual valve openedAND

    BCP cooling water flow not lowAND

    Seperator storage tank level > 1100 mm AND

    Economiser inlet flow > 111 T/hrAND

    No BCP trip override existsAND

    No BCP MCC disturbance exists

  • 7/30/2019 Seperator Logics

    29/44

    Trip permissives

    Dry mode of operation of the boiler

    Auto starting of BCP

    BCP will get auto started if either BCP auto

    start signal is present OR

    Start BCP FR. W & steam start seq. signalfrom Start seq. is present.

    BCP auto Start signal

  • 7/30/2019 Seperator Logics

    30/44

    Auto stopping of BCP

    BCP will stop on auto if either BCP auto stop

    signal OR BCP MCC disturbance signal ispresent.

  • 7/30/2019 Seperator Logics

    31/44

    BCP trip override logic

  • 7/30/2019 Seperator Logics

    32/44

    Operational logics for BCP Inlet

    Shut-off MOV Open permissive

    If WET mode of operation is selected OR

    BCP not tripped

    Close permissive

    BCP not running (stopped) Auto opening

    Open permissives presentAND any of the following conditionsare present

    MFT has operated OR

    Open command from start sequence for BCP inlet shut off MOV OR System in wet mode of operation for 3 seconds OR

    BCP auto start signal is present

    Auto closing BCP trip signal

  • 7/30/2019 Seperator Logics

    33/44

    Operational logics forBCP Outlet

    Shut-off MOV Open permissive

    If WET mode of operation is selected OR

    BCP not tripped

    Close permissive

    BCP not running (stopped) Auto opening

    Open permissives presentAND any of the following conditionsare present

    MFT has operated OR

    Open command from start sequence for BCP outlet shut off MOVOR

    System in wet mode of operation for 3 seconds OR

    BCP auto start signal is present

    Auto closing

    BCP trip signal

  • 7/30/2019 Seperator Logics

    34/44

    Operational logics forBCP

    Circulation Line Vent MOV Open permissive

    If Auto Dry Mode of operation is not selectedAND

    If BLI is less than 15 % BMCR OR BCP is notrunning

    Auto opening Open permissives present and also if any of thefollowing conditions are present

    MFT has operated OR

    Open command from start sequence for BCP circ. Line ventMOV OR

    BCP is not running

    Auto closing If Auto Dry Mode of operation is selected OR

    If BLI > 15 % BMCR and BCP running (proven for 20

    secs.

    Operational logics for WR Line

  • 7/30/2019 Seperator Logics

    35/44

    Operational logics for WR Line

    Isolation MOV Open permissive

    If BLI is lesser than 1000 T/hrAND Either Main steam bottle up OFF OR

    All feedwater pumps not off.

    Close permissive BLI > 960 T/hrOR

    If all FW pumps are offAND BCP is offAND all scanners show no flame

    Auto opening Open permissives presentAND also if any of the following conditions are present MFT has operated OR

    Open command from start sequence for WR line isolation MOV OR

    Auto wet mode of operation OR

    Seperator storage tank level > 1100 mm OR

    BLI < 890 T/hr.

    Auto closing BLI >1000 T/hrOR Main steam bottle up ONAND All feedwater pumps off

    Manual close After manual control is enabled, this will take place

    If Manual close command is sent from LVS / OWSAND

    Seperator storage tank level is not greater than 1100 mm.

    Operational logics for ZR Line

  • 7/30/2019 Seperator Logics

    36/44

    Operational logics for ZR Line

    Isolation MOV Open permissive

    If BLI is lesser than 1000 T/hrAND Either Main steam bottle up OFF OR

    All feedwater pumps not off.

    Close permissive BLI > 960 T/hr OR

    If all FW pumps are offAND BCP is offAND all scanners show no flame

    Auto opening Open permissives presentAND also if any of the following conditions are present MFT has operated OR

    Open command from start sequence for ZR line isolation MOV OR

    Auto wet mode of operation OR

    Seperator storage tank level > 1100 mm OR

    BLI < 890 T/hr.

    Auto closing BLI >1000 T/hrOR Main steam bottle up ON AND All feedwater pumps off

    Manual close After manual control is enabled, this will take place

    If Manual close command is sent from LVS / OWSAND

    Seperator storage tank level is not greater than 1100 mm.

  • 7/30/2019 Seperator Logics

    37/44

    Operational logics forStorage tank drain MOV /

    Seperator water leg level control blocking MOV

    Open permissive

    Dry mode of operation

    Auto opening

    If seperator water leg control valve demand > 5 %.

    Auto closing

    Close seperator water leg CV demand from Start

    sequence. OR

    MFT operated OR

    BCP on and Wet mode of operation OR

    Seperator water leg CV demand < 2%AND

    Close position < 5 %.

  • 7/30/2019 Seperator Logics

    38/44

    Operational logics for Start up

    system warming MOV

    Open permissive Dry mode of operation

    Auto opening

    Open permissives presentAND also if any of thefollowing conditions are present Seperator storage tank level is less than 4000 mm

    Auto closing If wet mode of operation OR

    If MFT gets operated OR

    Close start up system warming valve command ispresent from Start up sequence. OR

    Seperator storage tank level > 1100 mmAND BCP

    On.

  • 7/30/2019 Seperator Logics

    39/44

    Operational logics for BCP Drain

    MOV

    Open permissive

    BCP not running

    Auto closing

    BCP running

    Operational logics for BCP outlet

    drain MOV Open permissive BCP not running

    Auto closing

    BCP runnin

  • 7/30/2019 Seperator Logics

    40/44

    Separator logic (Seperator storage tank wet leg level)

  • 7/30/2019 Seperator Logics

    41/44

    Separator logic (Seperator storage tank wet leg level)

    Separator logic (Seperator storage tank level)

  • 7/30/2019 Seperator Logics

    42/44

    Separator logic (Seperator storage tank level)

    Separator logic (Control of flow through BCP)

  • 7/30/2019 Seperator Logics

    43/44

    Separator logic (Control of flow through BCP)

  • 7/30/2019 Seperator Logics

    44/44