Page 1: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

11"

15.5"

11" 12"

16.75"

12"11" 12"

15.56"

6" 6"

6"

18"

12.5" 12"

6"

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details 6" Single Unit Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Tri-Plane Face Unit Deco Face Unit

Straight Face Unit

12"

6"

1.125"

Typical SectionDimensions May Vary by Region*

1 ofCDMRKM

Rock Face Unit

1212-19-174444 W 78th St, Minneapolis, MN 55435

952-897-1040

Page 2: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

17.25"

11" 10"

3"

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details Cap Unit Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Cap Units Inside Curve Cap Units Corner / Wall

Cap Units Wall Step PlanCap Units Wall StepIsometric

Cap Unit

Cap Units Outside Curve

Split Cap End

Split Cap Both Ends

Split Cap End

Cut Cap Unit as Required at End of Wall

Cut Cap Units as Requiredto Construct a Mitered 90 Degree Corner

Cut Cap Units to Fitas Required

Cut Cap Units to Fitas Required

2 ofCDMRKM 1212-19-174444 W 78th St, Minneapolis, MN 55435

952-897-1040

Page 3: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

18"

13.5"

3"

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details Rectangular Cap Unit Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Cap Units Inside Curve Cap Units Corner / Wall

Cap Units Wall Step PlanCap Units Wall StepIsometric

Cap Unit

Cap Units Outside Curve

Cut Cap Unit as Required at End of Wall

Cut Cap Units as Required toConstruct a Mitered 90 Degree Corner

Cut Cap Units to Fitas Required

Cut Cap Units to Fitas Required

3 ofCDMRKM 12

Double Cap at Step

12-19-174444 W 78th St, Minneapolis, MN 55435

952-897-1040

Page 4: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details Gravity Wall Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Gravity Wall Typical Section

Cap Unit

Regal Stone Unit

FinishedGrade

Total WallHeight

Embedment

24"

6"

12" (Min.) of FreeDraining Aggregate

4" Ø (Min) Drain Tile(Elevation Varies)(See Note)

4" Ø (Min) Drain Tile(Elevation Varies) - or -

6" (Min) CompactedGranular Base Leveling Pad

Note:Drain should be at bottom of wall whenpossible.Utilize raised drain location when bottomof wall drainage is not possible.

1 1/8"6"

Low Permeable Soil

4 ofCDMRKM 1212-19-174444 W 78th St, Minneapolis, MN 55435

952-897-1040

Page 5: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details Reinforced Wall Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Cap Unit

Regal Stone Unit

FinishedGrade

Total WallHeight

Embedment

24"

6"

4" Ø (Min) Drain Tile(Elevation Varies)

4" Ø (Min) Drain Tile(Elevation Varies) - or -

6" (Min) CompactedGranular Base Leveling Pad

12" (Min.) of FreeDraining Aggregate

GeosyntheticReinforcement(Typ)

Reinforced Soil

1 1/8"6"

Note:Drain should be at bottom of wall whenpossible.Utilize raised drain location when bottomof wall drainage is not possible.

Typical Reinforced Wall Section

Low Permeable Soil

5 ofCDMRKM 1212-19-174444 W 78th St, Minneapolis, MN 55435

952-897-1040

Page 6: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details Tiered Wall Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Regal Stone Unit

Finished Grade

24"

6" 6" (Min) CompactedGranular BaseLeveling Pad

12" (Min.) of FreeDraining Aggregate

GeosyntheticReinforcement(Typ)

Reinforced Soil

Varies

Cap Unit Total TierHeight

Embedment

Embedment

Typical Tiered Section

1 1/8"6"

1 1/8"6"

Rear Drain SytemWhen Required

6 ofCDMRKM 12

4" Ø (Min) Drain Tile(Elevation Varies)

4" Ø (Min) Drain Tile(Elevation Varies) - or -

12-19-17

Note:Drain should be at bottom of wall whenpossible.Utilize raised drain location when bottomof wall drainage is not possible.

4444 W 78th St, Minneapolis, MN 55435

952-897-1040

Page 7: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details Inside Corner Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Typical Base and / or OddNumbered Courses Plan

Inside Corner Isometric

Typical 2nd and / or EvenNumbered Courses Plan

Inside Corner Plan with Geogrid

Block Note:Cut units as required to maintain running bond pattern.

Grid

Str

engt

h Di

rect

ion

Grid Strength Direction

Free DrainingAggregate

Cut Unit

Additional Geogrid OverlapExtension (See Note)

H/4

H/4

Geogrid Note:Measure, cut and orient the geogrid, as per the engineers design andthe geogrid manufacturers specifications on correct strength direction.

Extend geogrid the wall height / 4 (H / 4) beyond the adjoining wallface at inside wall corners.

The reinforcement should not extend into the retaining wall units onthe perpendicular leg of the 90 degree corner.

Geogrid Reinforcement(Typ.)

3" of Backfill is RequiredBetween Overlapping Geogridfor Proper Anchorage (Typ.).

7 ofCDMRKM 12

Free DrainingAggregate

Cut Unit

12-19-174444 W 78th St, Minneapolis, MN 55435

952-897-1040

Page 8: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details Outside Corner Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Typical Base and / or OddNumbered Courses Plan

Outside Corner Isometric

Typical 2nd and / or EvenNumbered Courses Plan

Outside Corner Plan with Geogrid

Block Note:Cut units as required to maintain runningbond pattern.

Free DrainingAggregate

Corner Unit

Geogrid Reinforcement(Typ.)

3" of Backfill is RequiredBetween Overlapping Geogridfor Proper Anchorage (Typ.).

Corner Unit

H/2

H/2

H/2

H/2

Wall Corner AdditionalFree DrainingAggregate Fill Limits(See Notes)

Free DrainingAggregate

Wall Corner AdditionalFree DrainingAggregate Fill Limits(See Notes)

Geogrid Note:Measure, cut and orient the geogrid, as per theengineers design and the geogrid manufacturersspecifications on correct strength direction.

The reinforcement should not extend into theretaining wall units on the perpendicular leg of the90 degree corner.

Free Draining Aggregate Note:Place additional free draining aggregatefill at outside wall corners to extend backfrom wall face each way a distance equalto the wall height / 2 (H / 2).

8 ofCDMRKM 12

Grid Strength Direction

Grid

Str

engt

h Di

rect

ion

12-19-174444 W 78th St, Minneapolis, MN 55435

952-897-1040

Page 9: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details Inside Curve Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Typical Inside Curve Plan

Inside Curve IsometricInside Curve Plan with Geogrid

Block Note:Cut units as required to maintain running bond pattern.

Free DrainingAggregate

Regal Stone Unit

Place Additional Pieces of GeogridWhen Gap Angle Exceeds 20° onInside Wall Curves

Geogrid Reinforcement(Typ)

20°

Grid Strength Direction

Grid

Str

engt

h Di

rect

ion

9 ofCDMRKM 12

Geogrid Note:Measure, cut and orient the geogrid, as per theengineers design and the geogrid manufacturersspecifications on correct strength direction.

The reinforcement should not extend into theretaining wall units on the perpendicular leg of the90 degree corner.

12-19-174444 W 78th St, Minneapolis, MN 55435

952-897-1040

Page 10: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details Outside Curve Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Typical Outside Curve Plan

Outside Curve Isometric

Outside Curve Plan with Geogrid

Block Note:Cut units as required to maintain running bond pattern.

Free DrainingAggregateRegal Stone Unit

3" of Backfill is RequiredBetween Overlapping Geogridfor Proper Anchorage (Typ.)

H/2

H/2

Geogrid Reinforcement (Typ)

Additional Corner Free DrainingAggregate (See Notes)

10 ofCDMRKM 12

Geogrid Note:Measure, cut and orient the geogrid, as per theengineers design and the geogrid manufacturersspecifications on correct strength direction.

The reinforcement should not extend into theretaining wall units on the perpendicular leg of the90 degree corner.

Free Draining Aggregate Note:Place additional free draining aggregatefill at outside wall corners to extend backfrom wall face each way a distance equalto the wall height / 2 (H / 2).

Grid Strength Direction

Grid

Str

engt

h Di

rect

ion

12-19-174444 W 78th St, Minneapolis, MN 55435

952-897-1040

Page 11: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details Top of Wall Fence Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Cap Unit

Regal Stone Unit

Finished Grade

18" ±

Minimum Offset Fence Section

Note:Concrete filled tube or form to be set during the wallconstruction, not drilled through geogrid afterwardswhen directly behind units.

Steel Fence or Railing

36" M

in.

Geosynthetic Reinforcement(Typ)

Concrete Filled Tube orForm 8' o.c. Max.

Cap Unit

Regal Stone Unit

FinishedGrade

36"

Steel Fence or Railing

24" M

in.

Geosynthetic Reinforcement(Typ)

Concrete Filled Tube orForm 8' o.c. Max.

Fence Section

11 ofCDMRKM 1212-19-174444 W 78th St, Minneapolis, MN 55435

952-897-1040

Page 12: Sect-Swale · Regal Stone Details Inside Corner Details Designed By: Checked By: Revision: Date: Drawing No: No Scale Scale: Typical Base and / or Odd Numbered Courses Plan Inside

Title:

The suitability and/or manner of use of any detailscontained in this document is the sole responsibility of theuser.Final project specific designs shall be prepared by a licensedprofessional engineer.

Copyright 2017 Keystone Retaining Wall Systems, LLC Project:Regal Stone Details Top of Wall Swale Details

Revision: Date: Drawing No:Designed By: Checked By:

No Scale

Scale:

Cap Unit

Regal Stone Unit

Concrete or GrassDrainage Swale toIntercept and DivertSurface Water

Steel Fence or Railingas Required

Geosynthetic Reinforcement(Typ)

Concrete Filled Tube orForm 8' o.c. Max.

Drainage Swale Section

24" M

in.

Low Permeable soil

PlasticMembrane

Expansion Materialw/Concrete

FinishedGrade

36" Min.

8" Min.

12 ofCDMRKM 1212-19-174444 W 78th St, Minneapolis, MN 55435

952-897-1040


Recommended