INSTALLATION MANUAL
VAM150FAVAM250FAVAM350FAVAM500FAVAM650FAVAM800FAVAM1000FAVAM1500FAVAM2000FA
Total Heat ExchangerHRV (Heat Reclaim Ventilation)
1
1
H H
K L
J
F41626
3
150-
250
600
153
90
263
2020
153
GC
ED
BA
34 19 2 5
7
8
612
11
10
24
14
1516
13
130 254 988 254 130
14.5
621
403.
5
403.
535
033
0
621
14.5
A
C
B
325
95
1140
315
252
568
222
199
421
898
2020
200-
300
650
912
380
380
34 19 2 5
7
8
612
11
10
2
4 14
13
15
16
A B C D E F G H J K LVAM150F
269 149 104 509 288 560 718145
76097
200VAM250F
132 146VAM350F
285 164 112 800 416 850 758 812VAM500F 84 197VAM650F
348204
140852 421 902
912137
988196 250
VAM800F89 246 263
VAM1000F 203 1140 568 1190VAM1500F 710 421 898 VAM2000F 710 568 1168
A B
2
2
VAM500F
280
415
758
850
150-
250
600-
415
280
112
2 318
11
9
1
18
10
10
17
4200
2
119
14
15
1
16
13
5
19
VAM150~2000FTotal Heat ExchangerHRV (Heat Reclaim Ventilation)4PW13545-1C
Installation manual
1
CONTENTS Page
Safety considerations ........................................................................1Dimensions........................................................................................1Installation .........................................................................................1System...............................................................................................4Electric wiring ....................................................................................6Test run............................................................................................17Wiring diagram ................................................................................18
The English text is the original instruction. Other languages aretranslations of the original instructions.
SAFETY CONSIDERATIONS
Please read these "Safety considerations" carefully before installingair conditioning equipment and be sure to install it correctly. Aftercompleting the installation, make sure that the unit operates properlyduring the start-up operation. Please instruct the customer on how tooperate the unit and keep it maintained.
Also, inform customers that they should store this installation manualalong with the operation manual for future reference.This air conditioner comes under the term appliances not accessibleto the general public.
Meaning of warning and caution symbols
DIMENSIONS
(See figure 1 (A = Models 150F~1000F, B = Models 1500F~2000F))
INSTALLATION
Installation position
Example of Installation, VAM500F (See figure 2), VAM800F(VAM1000F) (See figure 3), VAM2000F (See figure 4)
VAM150F VAM500F VAM1000FVAM250F VAM650F VAM1500FVAM350F VAM800F VAM2000F
Total Heat Exchanger HRV (Heat Reclaim Ventilation) Installation manual
HRV Heat Reclaim VentilationPlease read this installation manual carefully and installthe unit properly to keep it at full capacity for a long time.Please provide some necessary parts, for example roundhoods, air suction/discharge grilles etc., before theinstallation of the unit.
WARNINGDo not install HRV or an air suction/discharge grille in thefollowing places.
WARNING Place such as machinery plant and chemical plant
where gas, which contains noxious gas or corrosiveconponents of materials such as acid, alkali organicsolvent and paint, is generated.Place where combustible gas leakag is likely.Such gas can cause fire.
Place subjected to high temperature or direct flame.Avoid a place where the temperaure near the HRV unitand the air suction/discharge air grille exceeds 40C. If the unit is used at high temperature, defomed airfilter and heat exchange element or burned motorresult.
Place such as bathroom subjected to moisture.Electric leak or electric shock and other failure can becaused.
Place subjected to much carbon black.Carbon black attaches to air filter and heat exchangeelement, making them unable to use.
The equipment is not intended for use in a potentiallyexplosive atmosphere.
1 Maintenance space for the heat exchange elements, air filters and fans
2 Maintenance cover3 Inspection hole 450 mm4 Switch box5 4x 14x40 mm Ceiling hook (Oval hole)6 Exhaust air fan7 OA (Outdoor air) Fresh air from outdoors8 EA (Exhaust air) Exhaust air to outdoors9 Supply air fan
10 SA (Supply air) Supply air to room11 RA (Retun air) Return air from room12 Damper plate13 Heat exchange elements14 Air filters15 Applicable duct16 Nominal diameter
CAUTION1. Install the unit in a place strong enough to
support its weight.Poor installation is hazardous. It also causes vibrationsand usual operating noise.
2. Provide the service space and the inspection holes.(Be sure to provide the inspection holes to inspect theair filters, the heat exchange elements and fans.)
3. Do not install the unit directly against a ceiling or wall.(If the unit is in contact with the ceiling or wall, it cancause vibration.)
1 Air suction/discharge grille (option)2 Inspection hole 450 mm (field supply)3 Maintenance space for the heat exchange elements, air filters and
fans4 Duct (field supply)5 Duct (200) (field supply) or (*) Flexible duct (option)6 Branch duct (field supply) (only for VAM800~2000F)7 (*) Flexible duct (option)8 (*) Silencer (option)9 EA (Exhaust air to outdoors) 10 Heat Insulator (field supply)11 OA (Outdoor air) Fresh air from outdoors12 Metal suspension bracket for absorbing vibration (field supply)13 Suspension bolt (field supply)14 Gradient of down to outdoor 1/5015 SA (Supply air to room)16 RA (Return air from room)17 Round hood (field supply)18 Suspension bolt postion19 Additional external damper (field supply)
VAM150F, VAM250F, VAM350F, VAM500F, VAM650F,VAM800F, VAM1000F
CAUTIONS
Installation manual
2VAM150~2000F
Total Heat ExchangerHRV (Heat Reclaim Ventilation)
4PW13545-1C
The method of installation
VAM150F, VAM250F, VAM350F, VAM500F
VAM650F, VAM800F, VAM1000F, VAM1500F, VAM2000F
Installation of duct connecting flangesAttach the provided duct connecting flanges using screws(accessories).
VAM1500F, VAM2000F
Installation of HRV
Install the anchor bolt (M10 to 12) in advance.Pass the metal suspension bracket through the anchor bolt andsecure the anchor bolt with washer and nut.(Before installation, check for foreign objects such as vinyl andpaper remaining inside the fan housing.)
The metal suspension bracket is fitted on top of the standardunit.If the anchor bolt is long, install it on the bottom of the unit.(Be sure to screw in the removed mounting screw on top toprevent air leakage.)Install the duct caution name plate property on the indoor side(SARA) and outdoor side (EAOA).
on installing the ducts The parts marked with (*) are effective in reducing
blowing noise. When using the unit at a quiet place, use the optional
silencer box and flexible duct at the part of the airdischarge outlet on the indoor side SA (supply air toroom) of the unit, to counter the noise.
When selecting installation materials, consider therequired volume of air flow and noise level in thatparticular installation.
When the outdoor air infiltrates into the ceiling and thetemperature and humidity in the ceiling become high,insulate the metal portions of the unit.
1 Screw (accessories)2 Duct connecting flange (accessories)
screws provided screws provided
VAM150 16 VAM650 24VAM250 16 VAM800 24VAM350 16 VAM1000 24VAM500 16 VAM1500 24
VAM2000 24
1 2
1
2 2
1 Ceiling hook2 Nut3 Washer4 Double nuts
NOTE Remove the two fixing metals for transportation if itprevents installation work. (Be sure to screw in theremoved mounting screw on the body side to preventair leakage.)
1
2
3
4
1
2
3
4
Duct connection
3VAM150~2000FTotal Heat ExchangerHRV (Heat Reclaim Ventilation)4PW13545-1C
Installation manual
3
Do not connect the ducts as follows
1 The minimal radius of bends for flexible ducts are as follows:300 mm duct: 200 mm diameter375 mm duct: 250 mm diameter
2 To prevent air leakage, wind aluminum tape round the sectionafter the duct connecting flange and the duct are connected.
3 Install the opening of the indoor air intake as far as from theopening of the exhaust suction.
4 Use the duct applicable to the model of unit used (Refer to theoutline drawing.)
5 Install the two outdoor ducts with down slope (slope of 1/50 ormore) to prevent entry of rain water. Also, provide insulation forboth ducts to prevent dew formation. (Material: Glass wool of25 mm thick)
6 If the level of temperature and humidity inside the ceiling isalways high, install a ventilation equipment inside the ceiling.
7 Insulate the duct and the wall electrically when a metal duct is tobe penetrated through the metal lattice and wire lattice or metallining of a wooden structure wall.
VAM150F, VAM250F, VAM350F, VAM500F, VAM650F,VAM800F, VAM1000F
VAM1500F, VAM2000F
Using 250 mm round ducts for the SA (supply air) and RA(return air) sides
1. Loosen the 12 screws off the SA (supply air) side and removethe connection chamber. Be sure to tighten up these screwsback in position in order not to allow any air leak from the unit.
2. Fix the duct connecting flanges (Option) with theiraccompanying 12 screws.
Introducing the silencers and other options.This model handles a high air flow rate.To reduce the blow-out noise, some optional attachments areavailable: silencer, flexible duct, thin air intake/exhaust grille, etc.
1. Remove the connection chamber off the SA (supply air) sideand attach the upper and lower silencers.
2. Now fix the duct connecting flanges (option) and connect the250 mm flexible ducts.
Extreme bendDo not bend the duct over 90 Multi bend
Reduce the diameter of the duct to be connected.Do not reduce the duct diameter halfway.
HRV
1
23
1
4
4 2
1
5
HRV
1 Aluminium tape (field supply)2 Insulation material (field supply)3 Duct connecting flange (option)4 Slope over 1/505 Duct connecting flange (option)6 SA (Supply air)7 RA (Return air)8 Connecting chamber9 Silencer (option)
6
8
7
7
8
9
6
3
S
YSTEM
Installation manual
4VAM150~2000F
Total Heat ExchangerHRV (Heat Reclaim Ventilation)
4PW13545-1C
Independent system
Air conditioner linked operation system
System Standard methodRelated items in Electric wiring
Independent system
Up to 16 units can be controlled with theremote controller for HRV. (A system withtwo remote controls can be created in themaster/slave switching.)
All HRV operations can be used andindicated.
Operation monitor output and humidifieroperation are possible using AdapterPCB.
Remote control cord should be procuredlocally.(Maximum cord length: 500 m)
"When connecting to Remote controller for
HRV" on page 13
Combined operation system with VRV systems and Sky-air series
1-group linked operation system
A combined total of up to 16 airconditioners and the HRV can becontrolled.
The HRV ventilation mode can beoperated independently when airconditioners are not being used.
Using the local seting of the remotecontroller for air conditioners, varioussettings such as precool/pre-heatreservation on/off, ventilation flow rate,ventilation mode, etc.
"Standard 1-group linked-control
system" on page 13
Multi-group (2 or more) linked operation system
Since all VRV units are connected to asingle line in view of installation, all VRVunits are subjects for operation.
If there are problems operating all VRVunits, do not use this system.
"Linked control with more than two
groups" on page 14
HRV HRV
1
2
1 Remote controller for HRV
2 2-wire cord (produced locally)
VRV HRV
1 2
1 Remote controller for air conditioner(Remote controller for HRV)
2 Remote controller for air conditioner
VRV VRV
VRV VRV
HRV HRV
1 2
5 5
5 5
3 4
6
1 Group 1 4 Group 42 Group 2 5 Remote controller
for HRV3 Group 3 6 Distant control
adapter
NOTE Adapter PCB: KPR50-2 ; Distant control adapter: KRP2A61: Installation box for adapter PCB: KRP50-2A90 Operation of two or more group is not possible with direct duct connection. With VAM types, the direct duct connection shown can also be selected for 1-group operation systems.
System Standard methodRelated items in Electric wiring
Direct duct connection system
The HRV will operate only when the airconditioner fan is on.
When the air conditioner is not beingused, the HRV can be operated incirculation or ventilation modes.
Other specifications are the same asthose of the standard system.
"Direct duct connection system
for 1-group operation system" on page 14
VRV HRV
1 2 3
1 Remote controller for air conditioner(Remote controller for HRV)
2 Remote controller for air conditioner
3 Duct
Centralized control system (VRV system).VAM150~2000FTotal Heat ExchangerHRV (Heat Reclaim Ventilation)4PW13545-1C
Installation manual
5
System Standard methodRelated items in Electric wiring
Centralized control system
All/individual control system
Use of the on/off controller,Adapter PCB for remote controlor schedule timer enablescentralized control of the entiresystem.(maximum of 64 groups)
The on/off controller can turnon or off the individual units.
The schedule timer and on/offcontroller can be usedtogether. However, the AdapterPCB for remote control cannotbe used with anothercentralized control device.
"All/individual control" on page 15
Zone control system
Use of the centralizedcontroller enables zone controlvia the centralized control line.(maximum of 64 zones)
The central controller displaysthe Filter indication andabnormality warnings, andenables resetting.
The centralized controllerallows ventilation operation foreach zone independently.
"Zone control system" on page 16
HRV
HRV
VRV VRV
VRV VRV
1 1
1 1
2
1 Remote controller for for air conditioner
2 Adapter PCB for remote controller , Schedule timer, On/Off controller
VRV VRV
HRV HRV HRV
HRV
2
1
4
3 3
1 Zone 1 3 Remote controller for air conditioner
2 Zone 2 4 Central controller
NOTE Wiring adapter for remote contact: KRP50-2, Adapter PCB for remote control: KRP2A61, schedule timer. DST30B61, on/offcontroller. DCS301B61, controller: DCS302B61, BRC1C517
ELECTRIC WIRING Component electrical specificationsInstallation manual
6VAM150~2000F
Total Heat ExchangerHRV (Heat Reclaim Ventilation)
4PW13545-1C
Connection of wiring
Connect the wires in accordance with the diagram of eachsystem.
All wiring must be performaed by an authorized electrician. All field supplied parts and materials and electric works must
conform to local codes. Use copper wire only
Connection of wiring
A circuit breker capable of shutting down power supply to theentire system must be installed.
A single switch can be used to supply power to units on thesame system. However, branch switches and branch circuitbreakers must be selected carefully.
Fit the power supply wiring of each unit with a switch and fuse asshown in the drawing.
Be sure to give the electric grounding (earth) connection.Complete system example
Specifications for field supplied fuses and wire
Precautions
1 Do not connect wires of different gauge to the same powersupply terminal. Looseness in the connection may causeoverheating.When connecting more than one wire to the power supplywiring, use a 2 mm2 (1.6) gauge wire.
2 Keep total current of crossover wiring between indoor units lessthan 12 A.When using two power wiring of a gauge greater than 2 mm2(1.6), branch the line outside the terminal board of the unit inaccordance with electrical equipment standards.The branch must be sheathed so as to provide an equal orgreater degree of insulation as the power supply wiring itself.
3 Do not connect wires of different gauge to the same groundingterminal. Looseness in the connection may deteriorateprotection.
4 Keep the power supply wiring distant from other wires to preventnoise.
5 For remote controller wiring, refer to the Installation manual ofthe remote controller..
Before obtaining access to terminal devices, all powersupply circuits must be interrupted.
Power supply wiringTransmission wiringSwitch
Fuse
1 Outdoor unit2 Indoor unit3 Power supply4 Main switch5 Remote controller
VRV
VRV
VRVHRV
HRV
1
2
2
3
4
5
5
VAM 150F 250F 350F 500F 650F 800F 1000F 1500F 2000FUnitsType JVE, 5VE JVE, 5VE, 7VE50 Hz Power supply Max. 264 V/Min. 198 V60 Hz Power supply Max. 242 V/Min. 198 VPower supply (*)
(*) MCA: Min. Circuit Amps MFA: Max. Fuse Amps KW: Moter Rated Output FLA: Full Load Amps
MCA (A) 0.9 0.9 1.35 1.35 2.3 3.4 3.4 6.75 6.75MFA (A) 16 16 16 16 16 16 16 16 16Fan motor (*)KW (kW) 0.03x2 0.03x2 0.09x2 0.09x2 0.14x2 0.23x2 0.23x2 0.23x4 0.23x4FLA (A) 0.4x2 0.4x2 0.6x2 0.6x2 1.0x2 1.5x2 1.5x2 1.5x2 1.5x2
NOTE For details, refer to ELECTRICAL DATA.
VAM 150F 250F 350F 500F 650F 800F 1000F 1500F 2000FType JVE, 5VE JVE, 5VE, 7VEPower supply wiringField supplied fuses 16 A
Wire H05VV-U3GSize Wire size must comply with local codesTransmission wiringWire Shield wire (2 wire)Size 0.75-1.25 mm2
Same gauge wires Different gauge wires
View seen from VRV Wiring example VAM150~2000FTotal Heat ExchangerHRV (Heat Reclaim Ventilation)4PW13545-1C
Installation manual
7
All transmission wiring except for the remote controller wires ispolarized and must match the terminal symbol.
Use shield wire in transmission wiring. Ground the shield of theshield wire to , at the grounding screw, with the C-cupwasher.
Sheathed wire materials may be used for transmission wiring,but they are not suitable for EMC (ElectromagneticCompatibility) (European Directive).When using sheathed wire, electromagnetic Compatibility mustconform to Japanese standards stipulated in the ElectricAppliance Regulatory Act.Transmission wiring need not be grounded when using sheathedwire.
Opening the switch box
1 2
5
3
46
7
8
A
B
C
1 Terminal board for transmission wiring2 Terminal board for power supply3 Grounding terminal4 Power supply wiring5 Clamp material (attached)6 Remote controller wiring7 Unit wiring8 Field supply wire/Earth terminal (attached)
Ground the shield part of shielded wire.A Earth screw (attached)B C-cup washer (attached)C Shield part
CAUTIONBefore opening the cover, be sure to turn off the powerswitches of the main units and other devices connectedwith the main units. Remove the screw securing the cover and open the
switch box. Secure the power cord control wires with the clamp,
as shown in the next figures.
VRVHRV
P1
P1
P1
P2 P2
P2
L N 1 2Out
VRV HRV
L N
L N 1 12 2 P1 P2 F1 F1 T1 T1 P2 P1 F1 F2 J2 JC L NJ1
12
5
3
44
6
7
6
1 Outdoor unit/BS unit2 Switch box3 Indoor unit4 Power supply 220-240 V~50 Hz5 Remote controller (VRV)6 Transmission wiring7 Remote controller (HRV)
VAM150F, VAM250F, VAM350F, VAM500F, VAM650F,VAM800F, VAM1000F Required electrical connections for possible additional field Installation manual
8VAM150~2000F
Total Heat ExchangerHRV (Heat Reclaim Ventilation)
4PW13545-1C
VAM1500F, VAM2000F
supplied external damper
The external damper prevents the intake of outdoor air if the HRV isswitched off. (Refer to figures 2, 3, and 4, item 19).1. The HRVs main unit PCB operates the HRV and supplies power
for the external damper.
Source voltage supply starts when HRV starts operating.Source voltage supply is stopped when HRV is switched off.
2. Required electrical connectionsConnect one end of the accessory harness to the X15Aconnector on the PCB and the other end to the harness leadingto the external damper via a insulated splices-closed barrelconnector (0.75 mm2).Make sure that the wire is released from strain.
3. Required settingsDefault setting of the X15A connector: Not in operationChange this default setting as follows by means of the remotecontroller for incorporating function of the external damper in thesystem: Mode No.: 18 (Group control) or 28 (Individual control) Setting switch No.: 3 Setting position No.: 03
How to install the optional adapter circuit board (KRP2A61, KRP50-2)When installing the optional adaptor circuit board, it is necessary toprepare the fixingbox (KRP50-2A90)1 Open the electrical compartment cover by following the
procedure described in the section "Opening the switch box" onpage 7.
2 Remove the securing screw, and install the adapter circuitboard.
3 After the wires are connected, fasten the electrical compartmentcover.
VAM150F, VAM250F, VAM350F, VAM500F, VAM650F,VAM800F, VAM1000F
1
29
7
6
4
1
4
5
PCB
1213
12
11
12
10
10
1
7
13
9
2
10
12
6
5
8
4
3
4
11
12
10
1 Electric component mounting base2 Printed circuit board3 Electrical compartment cover4 Securing screw5 Grounding terminal6 Terminal board7 Transmission wiring terminal board8 Slide9 X15A connector
10 Harness for connection of additional external damper (supplied accessory)
11 Insulated splices-closed barrel connector (0.75 mm2) (field supply)
12 Double or reinforced insulated flexible cable (0.75 mm2) to external damper (field supply)
13 Tie wrap (field supply)
Supply voltage Connected load capacity
220 V0.5 A230 V
240 V
KRP50-2A90 ComponentsFixing screw 3 pieces
Clamp 2 pieces
2
1PCB
X15A3
1 HRV main unit2 External damper3 Earth to external damper, if no
class II construction (EN60335-2-40)
Installation Install the heater control kit to the outside of the switch box of theHRV unit as shown below.VAM150~2000FTotal Heat ExchangerHRV (Heat Reclaim Ventilation)4PW13545-1C
Installation manual
9
How to install the optional heater control kit (BRP4A50)When operating the HRV units at or below 10C of the outdoor airtemperature, use a field supplied preheater to preheat outdoor air.
The BRP4A50 kit is required to have an ON/OFF delay control whena preheater is used (initial setting is required).
For more detailed information on how to install the BRP4A50 optionkit, see the installation manual delivered with the option kit.
Power cord connection, control wire terminals and switches on the electronic control unit (printed circuit board) Connect the power cord to the L and N terminals. Secure the power cord with the power cord clamp, as shown in
"Opening the switch box" on page 7 Be sure to give the electric grounding (earth) connection.
VAM150F, VAM250F, VAM350F, VAM500F, VAM650F,VAM800F, VAM1000F
CAUTION For electric heater, safety devices, and installation
location, follow the standards or regulations of eachcountry.
Use a nonflammable duct for the electric heater. Besure to keep a distance of 2 m between the heaterand HRV unit for safety.
Use a different power supply and different circuitbreaker for the HRV units and electric heaters.
For setting the initial setting on the remote controller,see 19(29)-8-03 or 19(29)-8-04 in chapter "List ofSettings" on page 11.
1
5
4
3
2
3
A
B
1 Fixing board2 PCB support (Attached to adapter PCB)3 Fixing screw4 Lid5 Switch box
Applicable adapter name Kit nameA Adapter PCB for Humidifier KRP50-2B Adapter PCB Remote controller KRP2A1
1 Switch box2 Heater control kit3 Fixing screw4 Lid
43 1
23
X3AX2AX1A
X7A
FuL
10A
X13A
X8A
X12A
X5A
X9A
KRP
50-2
SS1
X11A
X10A
L N
L N
HML
P2 P1 F1 F2 J1 J2 JC
P2 P1 F1 F2 J1 J2 JCSS1
HML
161514177
654
1
3 2
12
11
10
9
8
13
VAM1500F, VAM2000F Local settingInstallation manual
10VAM150~2000F
Total Heat ExchangerHRV (Heat Reclaim Ventilation)
4PW13545-1C
Using the remote controller of the VRV-system air conditioner tomake HRV unit settingsInitial setting
1 Mode nos. 17, 18 and 19: Group control of HRV units.2 Mode nos. 27, 28 and 29: Individual control
Operating procedure
The following describes the operating procedure and settings.
1 Press the INSPECTION/TRIAL button for more than fourseconds with the unit in the normal mode to enter the localsetting mode.
2 Use the TEMPERATURE ADJUSTMENT button to select thedesired mode number. (The code display will blink.)
3 To make settings for individual units under group control (whenmode No. 27, 28 or 29 is selected), press the TIMER SETTINGON/OFF button to select the unit No. for which the settings areto be made. (This process is not necessary when settings aremade for the entire group.)
4 Press the top section of the TIMER button to select the settingswitch No.
5 Press the lower section of the TIMER button to select settingposition No.
6 Press the PROGRAM/CANCEL button once to enter thesettings. (The code display will stop blinking and light up.)
7 Press the INSPECTION/TRIAL button to return to normal mode.
X3A X4AX2AX1A
X7A
FuL
10A
X13A
X8A
X12A
X5A
X6A
X9A
KRP
50-2
SS1
X11A
X10A
L N
L N
HML
P2 P1 F1 F2 J1 J2 JC
P2 P1 F1 F2 J1 J2 JC
SS1
HML
161514177
6 654
1
3 2
12
11
1010
9
8
13
1 Transformer 10 Damper2 Secondary 11 Indoor air thermistor3 Primary 12 Outdoor air thermistor4 Supply air fan 13 Air flow5 Exhaust air fan 14 Remote controller6 Damper 15 Centralized control7 Power supply 16 No-voltage external input8 Terminals 17 Factory setting
Be sure to give the electric grounding (earth) connection.
9 For KRP50-2 or BRP4A50
TEST
Chr
hrTEST
NOTAVAILABLE
L H
ExampleVAM150~2000FTotal Heat ExchangerHRV (Heat Reclaim Ventilation)4PW13545-1C
Installation manual
11
When adjusting the ventilation air flow to low setting in the groupsetting mode, enter the mode No., 19 setting switch No., 0 andsetting position No., 01.
List of Settings
Mode No.Setting
switch No. Description of Setting
Setting position No.(Caution *1.)Group
settingsIndividual settings 01 02 03 04 05 06
17 27
0 Filter cleaning time setting Approx. 2500 hoursApprox. 1250
hoursNo
counting
2 Precool/preheat on/off setting Off On 3 Precool/preheat time setting 30 min 45 min 60 min 4 Fan speed initial setting Normal Ultra high
5
Yes/No seting for direct duct connection with VRV system
No duct (Air flow setting)
With duct (fan off)
Setting for cold areas (Fan operation selection for heater thermo OFF)
No duct With duct
Fan off Fan L Fan off Fan L
7 Centralized/individual setting Centralized Individual
8 Centralized zone interlock setting No Yes
Priority on operation
9 Preheat time extension setting 0 min 30 min 60 min 90 min
18 28
0External signal JC/J2 Last
commandPriority on external
input
1 Setting for direct Power ON Off On 2 Auto restart setting Off On 3 Setting for external damper On
4 Indication of ventilation mode/Not indication IndicationNo
Indication
7Fresh up air supply/exhaust setting
No Indication
No Indication Indication Indication
Supply Exhaust Supply Exhaust
8 External input terminal function selection (between J1 and JC) Fresh-up Overall alarm
Overall malfunction Forced off
Fan forced off
Air flow increase
9 KRP50-2 output switching selection (between 1 and 3) Fan on/off Abnormal
19 29
0 Ventilation air flow setting Low Low Low Low High High2 Ventilation mode setting Automatic Exchange By pass 3 Fresh Up on/off setting Off On 8 Electric heater setting No delay No delay On, off delay On, off delay
CAUTION1. The setting positions are set at 01 at the factory.
The ventilation air flow, however, is set at 06(medium) in the HRV unit. When lower or highersetting is desired, change the setting after installation.
2. Group number setting for centralized controllerMode No. 00: Group controllerMode No. 30: Individual controllerRegarding the setting procedure, refer to the sectionGroup number setting for centralized control in theoperating manual of either the on/off controller or thecentral controller.
Operation with the remote control exclusively for Air For FRESH UP operation, If it is set to Fresh up air supply:The volumeInstallation manual
12VAM150~2000F
Total Heat ExchangerHRV (Heat Reclaim Ventilation)
4PW13545-1C
conditioning operation HRV units. (BRC301B61)For non-independent systems, starting/stopping operation and timeroperation may not be possible.
Use the air conditioner remote control or the Centralized controller insuch cases.
BRC301B61: Remote controller for VRV
BRC1C51, 61, 517: Remote controller for VRV
1. Operation lampThis pilot lamp (red) light up while the unit is in Operation.
2. Operation/Stop buttonWhen pushed once, the unit starts operating.When pushed twice, the unit stops.
3. Air flow rate changeover buttonAir flow rate can be changed over to [Low] mode or [High] mode, FRESH UP [LowFRESH UP] mode, FRESH UP [High FRESH UP] mode.For FRESH UP operationWhen this indication does not show: The volume of outdoor airsupplied into the room and that of the room air exhaustedoutdoors is equivalent.
of outdoor air supplied into the room is largerthan that of room air exhausted outdoors.(This operation prevents the odor and moisturefrom kitchens and toilets from flowing into therooms.)
If it is set to Fresh up air exhust:The volumeof room air exhausted outdoors is larger thanthat of outdoor air suppied into the room.(This operation prevents the hospital odor andfloating bacteria from flowing out to thecorridors.)
4. Ventilation mode changeover button
(Automatic) modeThe temperature sensor of the unit automaticallychanges the ventilation of the unit in [Bypass]mode and [Heat Exchange] mode. (Heat Exchange) modeIn this mode, the air passes through the heatexchange element to effect [Total HeatExchanging] ventilation. (Bypass) modeIn this mode, the air does not pass through theheat exchange element but passes it to effect[Bypass] ventilation.
5. Indication of operation control method: When the operation of HRVs are linked with the air conditioners,this indication may be shown.While the indication is shown, the ON/OFF of HRVs cannot beoperated by the HRV remote controller.
6. Indication of operation standby:It indicates the precooling/preheating operation. This unit is atstop and will strat opration after the precooling/preheatingoperation is over.Precooling/prheating opration means the operation of HRVs isdelayed during the startup operation of linked air conditionerssuch a before the office hours.During this period the cooling or heating load is reduced to bringthe room temperature to the set temperature in a short time.
7. Indication of centralized control:When a remote controller for air conditioners or devices forcentralized control are connected to the HRVs, this indicationmay show.During this indication appears on the display, the ON/OFF andtimer operation may not be possible with the HRV remotecontrollers.
8. Indication of air filter cleaning
When the indication appears on the display, clean thefilter.
9. Filter signal reset button10. Inspection button
This button is to be used only for service. It is not to be usednormally.
How to operate with Timer
11. Push the button and select either one of or .
Each time the button is pushed, the indication changes asshown below.
( )
BRC301B61
A
HRV
TEST
FRESH UP
hr
hr
6
8
4
3
9
5 7 1 2
11
13
10
12
TEST
Chr
hrTEST
NOTAVAILABLE
L H
6 1 2
7
58
9
4
11
10 13 12 14
3
FRESH UP
FRESH UP
A
( (
( (
No indication
12. Push the button and set the time.Wiring and connections in combination with VRV-SYSTEMVAM150~2000FTotal Heat ExchangerHRV (Heat Reclaim Ventilation)4PW13545-1C
Installation manual
13
Each time when is pushed, the time advances one hour.Each time when is pushed, the time goes back one hour.
13. Push the button .Then, the reservation is finished.Either or changes from flashing to lighting.After the reservation is finished, the remaining time is indicatedin the display.
For cancelling the timer operation, push the button onceagain.The indication disappears.
14. If you press these buttons when using independent operation ofthe HRV unit, the message NOT AVAILABLE will appear on thedisplay for a few seconds.
Independant system
When connecting to Remote controller for HRV
For raising the remote-controlled ventilation air flow rate from Highto Ultra-High, connect the remote controller for the air-conditioner toHRV and make settings on site.(Refer to Initial setting under item "Local setting" on page 10.)Set the switches on the printed circuit board to the factory setting.
Standard 1-group linked-control system
The remote control of the air conditioner can be used to controlup to 16 air conditioner indoor units and HRV units.
Initial settings can be made for the functions of the HRV units(pre-cool/pre-heat, ventilation air flow, ventilation mode andFresh-Up).Use the remote controller of the air conditioner to make the initialsettings for the HRV units.Refer to Initial setting under Item "Local setting" on page 10
Pre-cool/pre-heat functionWhen the pre-cool/pre-heat function is set, the HRV unit switches onat the preset time (30, 45 or 60 minutes) after the VRV-system airconditioner begins cooling or heating operation. The function is setOFF at the factory. Therefore, to use this function, the initial settingmust be made using the remote controller of the air conditioner.If the air conditioner is re-started within two hours after the operationwas stopped, this function does not operate.
Example 1:To switch on the pre-cool/pre-heat function, and turn on the HRV unit60 minutes after the air conditioner is turned on.
Set the mode No. to 17 for group control, or 27 for individualcontrol, the setting switch No. to 2 and the setting position No.to 02
Set the mode No. to 17 for group control, or 27 for individualcontrol, the setting switch No. to 3 and the setting position No.to 03
Example 2:To switch the ventilation air flow to ultra high setting. (The units areset at the high air flow setting at the factory)
Set the mode No. to 17 for group control, or 27 for individualcontrol, the setting switch No. to 4 and the setting position No.to 02
Example 3:To switch the ventilation air flow to low setting.
Set the mode No. to 19 for group control, or 29 for individualcontrol, the setting switch No. to 0 and the setting position No.to 01
Factory setting
air flow rate
Factory setting
air flow rate
P1 P2 P1 P2
P1 P2P1 P2
HRV HRV
1 2
5
3 4
6
1 Master unit 4 Switch position: Master2 Slave unit 5 Remote controller for HRV3 Switch position: Slave 6 Maximum connection line length:
500 m
H M L
SS1
H M L
SS1
P1P2
P1P2 P1P2
P1 P2
VRV HRV
1 2
3
1 Remote controller for air conditioner
3 Connecting line can be extended up to 500 m maximum
2 Remote controller for HRV
Connecting the remote controller for HRV Direct duct connection system for 1-group operation systemInstallation manual
14VAM150~2000F
Total Heat ExchangerHRV (Heat Reclaim Ventilation)
4PW13545-1C
The remote controller for HRV cannot be used for starting/stoppingoperation or for timer operation. (The centralized control indicationwill be lit.)To set pre-cool/pre-heat function settings, change the remote controlair flow rate setting from medium (M) to high (H), etc., perform initialsettings from the remote controller for HRV.Since it will become a two-remote-control system, perform master/slave setting as shown below.
Refer to preforming initial settings in the remote control instructionmanual.
Example 4:To set the pre-cool/pre-heat reservation function to on and have theHRV start operating 60 minutes after the air conditioner has started,set the same numbers as shown in example 1 using the remotecontroller for HRV.
Example 5:To increase the remote control air ventilation rate setting fromMedium to High, set the same numbers as shown in example 2 usingthe remote controller for HRV.
Set the switches of the HRV unit PCB to the default factory settings.
Determination of heating/cooling selection rights for VRV-systems is performed using the remote controller for HRV.The heating/cooling selection rights can be enabled or disabledusing the ventilation mode button of the remote controller forHRV.This operation cannot be performed with the remote controllerfor air conditioner.
Line connections and the settings of the switches on the HRV unitPCB should be the same as for Standard system for 1-groupsystem.
Set the switches of the HRV unit PCB to the default factory settings.
1 Be sure to set the initial settings to Direct duct connection:Enabled. When the remote contoroller for HRV is not yet connected,
initial settings can be performed using the air conditionerremote control. Set the mode number to 17, the settingswitch number to 5, and the setting position number to 02according to the procedure in "Local setting" on page 10.
When the remote contoroller for HRV, initial settings shouldbe performed using the remote controller for HRV. Set thesame numbers as described above when using the remotecontroller for air conditioner according to the procedureMaking initial settings in the remote control instructionmanual.
2 Settings for other HRV functions should be made using thesame method as in Standard system for 1-group system.
Linked control with more than two groups
Mount the optionalKRP2A61 Adapter PCB forremote control on theelectric componentmounting base of one HRVunit.
A maximum of 64 airconditioners and HRVunits can be connected tothe F1 and F2 terminals.
Use the remote controllerof the air conditioner tomake the initial settings.
Remote control Master/slave settingRemote controller for air conditioner SlaveRemote controller for HRV Master
Air ventilation rate setting
using remote control Default factory settings
When set as in example 5
Low Low (L) air flow rate Low (L) air flow rateHigh Medium (M) air flow rate High (H) air flow rate
Default factory settings
air flow rate
Heating/cooling selection rights Operation switchover control displayEnabled Not litDisabled LitNot set Blinking
P1P2
P1P2 P1P2
P1 P2
VRV
1 2
5
3
4
1 Remote controller for air conditioner
4 Medium (M) air flow rate
2 Remote controller for HRV 5 When the remote controller for HRV is connected, set the switches on the HRV unit PCB to the default factory settings.
3 Maximum connection line length: 500 m
H M L
SS1
1 Remote controller for air conditioner
2 Connecting line can be extended up to 1000 m maximum
3 Optional distant control adapter KRP2A61
P1P2
P1P2 P1P2
P1 P2
VRV
1 2
3
4
1 Remote controller for air conditioner
3 Maximum connection line length: 500 m
2 Remote controller for HRV 4 Medium (M) air flow rate
VRV VRV
HRV 1
HRV 2
X11A
F1 F2 P1P2
P1 P2
F1 F2
F1 F2
1
2
3
Procedure The Adapter PCB for remote control and schedule timer cannotbe used together.VAM150~2000FTotal Heat ExchangerHRV (Heat Reclaim Ventilation)4PW13545-1C
Installation manual
15
1 Turn off the main power.2 Connect the air-conditioner remote controller.
3 Turn on the main power.4 Make the remote controller settings on site; Set the collective
zone interlock to ON. Mode number 17, setting switch number8 and setting position number 02.
5 Turn off the main power.6 Disconnect the remote controller.
Now the on-site settings are complete.For raising the remote-controlled ventilation air flow rate High toUltra-High, connect the remote controller for the air conditioner toHRV and make settings on site. (Refer to Initial setting under item"Local setting" on page 10.)
Centralized control system
All control
When using Adapter PCB for remote control (KRP2A61,62,63) orschedule timer (DST301B61)
A maximum of 64 air conditioners and HRV units can beconnected to the F1 and F2 terminals.
This system does not required group number setting forcentralized control. (auto-address system)
The Adapter PCB for remote control can be mounted on theelectric component mounting base of either the HRV unit or airconditioner. (The HRV unit can accept only the KRP2A61)
For raising the remote-controlled ventilation air flow rate fromHigh to Ultra-High, connect the remote controller for the air-conditioner to HRV and make settings on site.(Refer to Initial setting under item "Local setting" on page 10.)
All/individual control
When using the on/off controller (DCS301B61)
A maximum of 64 air conditioners and HRV units can beconnected to the F1 and F2 terminals.
This system allows connection of four on/off controllers. It is necessary to assign a central control group number to each
HRV unit and air conditioner.Regarding the setting of the group number, refer to the sectionon the centralized control group number setting in theoperating instructions of the On/off controller.
Use the remote controller of the air conditioner to make the initialsettings.
Example:Follow the procedure below to set the centralized group No. 2-05 toHRV 1.
P1
P2
P1 P2
P1 P2
HRV 1 1
2
1 Remote controller for air conditioner
2 Remote controller for HRV
HRV 1
X11A
HRV 2
VRV 1
F1 F2
D1 D2
F1 F2
F1 F2
F1 F2 P1P2 P1 P2
P1P2
P1 P2
1
2
7
5
3
4
6
1 Remote controller for air conditioner
5 Adapter PCB for remote control (KRP2A61)
2 Remote controller for HRV 6 Distant control adapter3 Connecting line can be extended
up to 1000 m maximum7 On/Off signal
4 Schedule timer (DST301B61)
1 2 3 4
F1 F2 F1 F2 F1 F2 F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
P1
P2
P1P2
P1 P2
P1 P2
HRV 1
HRV 2
VRV 1
1
2
5
3
4
1 Remote controller for air conditioner
4 Schedule timer
2 Remote controller for HRV 5 On/Off controller3 Connecting line can be extended
up to 1000 m maximum
Procedure A maximum of 64 air conditioners and HRV units can beconnected to the F1 and F2 terminals.Installation manual
16VAM150~2000F
Total Heat ExchangerHRV (Heat Reclaim Ventilation)
4PW13545-1C
1 Turn off the main switch of the HRV-1 and On/off controller.2 Connect the air conditioners remote controller.
3 Turn on the main switch of the HRV-1 and On/off controller.4 Set the central control group number using the local setting on
the remote controller.Mode No.: 00Central control group No.: 2-05
5 Turn off the main switch of the HRV and On/off controller.6 Disconnect the remote controller.
The setting is now complete.For the ventilation air flow setting, follow the procedure described inthe section "All control" on page 15.
Zone control system
The HRV units will turn on and off in according with the zoneoperation command from the centralized controller.
Zone 2
The HRV units operate in the zone-linked mode, as described in thesection, "Linked control with more than two groups" on page 14. Forthe initial setting, follow the procedure described in that section. It is necessary to assign a central control group number to each
HRV unit and air conditioner.Regarding the setting of the group number, refer to the section onthe centralized control group number setting in the operatinginstructions of the Centralized controller. Refer to the section"All/individual control" on page 15 for the setting procedure.
For the ventilation air flow setting, follow the proceduredescribed in the section "All control" on page 15.
For the zone setting from the centralized controller, refer to theoperating instructions of the centralized controller.
The centralized controller can be used to control the individualunits in the zone for ventilation operation.
Remote control
Monitor of operation
The operation of the HRV can be monitored from the outside by theconnection of the adaptor PCB for remote control KRP50-2 (option).Be sure to connect the terminal strip on the adaptor PCB for remotecontrol KRP50-2 (option).
P1
P2
P1 P2
P1 P2
HRV 1 1
2
1 Remote controller for air conditioner
2 Remote controller for HRV
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
P1 P2
P1P2
P1 P2
P1P2
HRV 1
HRV 2
HRV 3
VRV
1
2
5
3
4
3
1 Zone 1 4 Connecting line can be extended up to 1000 m maximum
2 Zone 2 5 Centralized controller (DCS302B61
3 Remote controller for HRV
L L N
X10AX9A
KRP50-2
123
12
5
3
4
6
1 Operation lamp 4 2P connecter2 Power source 5 3P connecter3 Power source 6 Printed circuit board
Wiring adapter for remote contact KRP50-2 (option)(To be placed in the switch box of the HRV)
Fresh-up operation NOTESVAM150~2000FTotal Heat ExchangerHRV (Heat Reclaim Ventilation)4PW13545-1C
Installation manual
17
PurposesWhen Combined with a local ventilating fan (such as the one in toiletand kitchen), the air flow rate of HRV is balanced by either fanoperation or exhaust operation.
However, a circuit with voltaged and low current (16 V, 10 mA) isfromed between the JC and J1, so a relay with low-load contact pointmust be used.
Functions
The unit performs overcharged operation to prevent back flow ofodor.
Necessary partsOperation contact of exhaust ventilating fan (Field supply)Example of control wiring
System description
TEST RUN
After completing the installation of the system, check again to makesure that No error was made in wiring or switch setting on the printedcircuit boards of the HRV units.
Then, turn on the power of the HRV units. Refer to the manual of theremote controller of each unit (remote controller for air conditioner,central control unit, etc.) for conducting a trial operation.
The local setting by the remote controller for the air conditioner (Refer to "Local setting" on page 10)
J1, JC normal open
J1, JC normal close
Fresh-up OFF (Factory setting) Normal Fresh-upFresh-up ON Fresh-up Fresh-up
1
23
J1JC
HRV
1 Connecting line can be extended up to 50 m maximum
3 Printed circuit board
2 (Field supply)
1 2HRV
1 Local ventilating fan 2 Power supply
WIRING DIAGRAM VAM150, 250, 350, 500, 650, 800, 100FInstallation manual
18VAM150~2000F
Total Heat ExchangerHRV (Heat Reclaim Ventilation)
4PW13545-1C
Power supplySingle phase220-240/220 V50/60 Hz
External output terminals
Adapter for wiring(optional accessories) (KRP50-2)
Terminals for the input front outside
Terminals for the centralized control
Remote controller(Optional accessories)
L-RED N-BLUA1P Printed circuit board
C1R-C2R Capacitor (M1FM2F)F1U Fuse (250 V, 10 A)
K1R-K3R Magnetic relay(M1F)K4R-K6R Magnetic relay(M2F)
K7R Magnetic relay(M1D)M1D Motor (Damper motor)M1F Motor (Air supply Fan motor)M2F Motor (Exhaust Fan motor)
Q1L-Q2L Thermo switch (M1F-M2F Built-in)R1T Thermistor (Indoor air)R2T Thermistor (Outdoor air)S1W Limit switchT1R Transformer (Supply 220-240 V/22 V)X1M Terminal (Power supply)X2M Terminal (Control)
Optional AccessoriesAdapter for wiring (KRP50-2)
Ry1 Magnetic relay (On/Off)Ry2 Magnetic relay (Humifider operation)
X9A10 A Connector (KRP50-2)Remote controller
SS1 Selector switch (Main/Sub)Optional Connector
X11A Connector (Adaptor power supply)
NOTE Terminals
Wire clamp
Connectors
Field wiring
Protective earth
Symbols show as follows:BLK: BlackRED: RedBLU: BlueWHT: WhiteYLW: YellowORN: OrangeGRN Green
,
WIRING DIAGRAM VAM1500, 2000FVAM150~2000FTotal Heat ExchangerHRV (Heat Reclaim Ventilation)4PW13545-1C
Installation manual
19
Power supplySingle phase220-240/220 V50/60 Hz
External output terminalsAdapter for wiring(optional accessories) (KRP50-2)
Terminals for the input front outside
Remote controller(Optional accessories)
Terminals for the centralized control
Switchbox
L-RED N-BLUA1P Printed circuit board (Control)A2P Printed circuit board (Interface)
C1R-C4R Capacitor (M1FM4F)F1U-F2U Fuse (250 V, 10 A)K1R-K3R Magnetic relay(M1F)K4R-K6R Magnetic relay(M2F)
K7R Magnetic relay(M1D)K8R Magnetic relay(M2D)
M1D-M2D Motor (Damper motor)M1F-M3F Motor (Air supply Fan motor)M2F-M4F Motor (Exhaust Fan motor)Q1L-Q4L Thermo switch (MF1-M4F Built-in)RY1-RY3 Magnetic relay (M3F)RY4-RY6 Magnetic relay (M4F)
R1T Thermistor (Indoor air)R2T Thermistor (Outdoor air)
S1W-S2W Limit switchT1R Transformer (Supply 220-240 V/22 V)X1M Terminal (Power supply)X2M Terminal (Control)
Optional AccessoriesAdapter for wiring (KRP50-2)
Ry1 Magnetic relay (On/Off)Ry2 Magnetic relay (Humifider operation)
Remote controllerSS1 Selector switch (Main/Sub)
Optional ConnectorX9A Connector (for KRP50-2)
X10 A Connector (for KRP50-2)X11A Connector
NOTE Terminals
Wire clamp
Connectors
Field wiring
Protective earth
Symbols show as follows:BLK: BlackRED: RedBLU: BlueWHT: WhiteYLW: YellowORN: OrangeGRN Green
,
NOTES NOTES
33
1 8718 2 3
11
9
1
184200
18
10
19
10
17
4200
16 2
119
14
15
6
1
18
1312
415
280
500
415
280
280
415
912
VAM800F902
150-
250
600-
140
4
4
415
415
415
280
415
280
280
280
415
415
1186
280
500
VAM2000F
912
200-
300
650-
280
140
287 31
11
94
2004
350
61
1
17
4350
16
11
14
16215
9
124 250
13
18 18
18
18
1
18 18
118
1
1910
10
4PW13545-1C
Copy
right
D
aikin
Installation manualSafety considerationsMeaning of warning and caution symbols
DimensionsInstallationInstallation positionThe method of installationDuct connection
SystemIndependent systemCentralized control system (VRV system).
Electric wiringConnection of wiringPrecautionsOperating procedureList of SettingsIndependant systemWiring and connections in combination with VRV-SYSTEMCentralized control systemRemote control
Test runNotesWiring diagramWiring diagram