December 21, 2017
Grant & Lyons John Lyons 149 Wurtemburg Road Rhinebeck, NY 12572 Re: Thompson Education Center - Proposed Building SBL: 65-1-11.59 Renner Road (TR-14) Town of Fallsburg, Sullivan County, NY
Building Permit/Building Plans Review Dear Mr. Lyons:
As you know, our client, the Basha Kill Area Association (“BKAA”), has significant concerns regarding the massive alleged single family structure proposed on Renner Road in the Town of Fallsburg. We have reviewed that structure’s Building Permit Application, which included an 81 sheet set of Building Plans (dated last revised September 20, 2017), for the 9,000 square foot single family home. Per our review of the permit and plans, the proposed structure in no way resembles a single family home. The following details the numerous inconsistencies and issues found throughout the building permit application. Building Construction
Building construction is consistent with a commercial or institutional structure. The
structure consists of a steel superstructure supporting concrete panel flooring. Floor to ceiling glass exterior is proposed in the southern portion of the building with prefabricated concrete panels for the remainder of the siding (See elevation view - Sheet A-201). A flat roof is proposed. Metal stud partitions will form interior walls and a drop gypsum board ceiling is proposed throughout. This type of building construction is exceptionally rare for single family residential structures, but very common in commercial construction.
2
Floor Plan and Site Layout In keeping with the proposed building construction discussed above, the floor plan and site
layout is typical for an office or institutional use, and very uncommon for a single family residence. Referring to Floor Plan drawings A-102 and A-103, the southern portion of the building floor plan is very similar on the first and second floor. There is a center corridor that is separated by “habitable space” on either side. Each habitable space has several rooms with a separate kitchen and bathroom. Four (4) kitchens, each with a dedicated refrigerator, sink, and dishwasher are proposed, one for each separate “habitable space”. A “janitor’s closet” is located along the central corridor on the first floor. The first floor contains a “data room” for “IT” equipment. Despite the claim that this is a very large 9 bedroom house, there is no master bedroom or master bathroom suite. All bedrooms are similar in size. The “house” has a fully compliant handicap ramp on the north entrance, which is not a requirement.
A single family home with this type of layout and construction is extremely rare and defies common logic. Alternatively, usage of the building as an office or institutional use would be commonplace and logical. Code Compliance & References
As an alleged “single family residence”, the building is required to meet the International
Residential Code (“IRC”). Commercial buildings (e.g. larger residential (e.g. multifamily), office, institutional, etc.) are mandated to meet the International Building Code, International Plumbing Code and International Mechanical Code. Although the significantly less restrictive IRC was required, the Building Plans almost exclusively comply with the commercial building codes (IBC, IPC, IMC). The following lists many instances where the Building Plans demonstrate a proposed commercial building:
Title Sheet T-100 1. Building Department Notes 3 and note on the bottom identified with two asterisks
indicate required conformance with the International Building Code, which a single family residence is not required to meet.
2. Under Project Information, the “Proposed Building Classification” is listed as “R-3 (Single-Family Residence)”. This is identified as one of the superficial references to a single family home. Per Building Code, R-3 is not a single family residence, rather either a Congregate Living Facility, Boarding House or an owner occupied Lodging House.
3. Building Department Note 6 indicates the “entire building to be fully sprinklered as per 2015 IBC 903.2.8.” Again, a single family residence isn’t required to meet the IBC. Section 903.2.8 refers directly to an R-3 classified building, which is not a single family residence. Single family residences are not required to be sprinklered unless they are three stories or more. Despite being two stories, the building is fully sprinklered as discussed below.
4. Fire Resistance Ratings Note 1 indicates that the contractor is “responsible for ensuring Table 601 of the 2015 International Building Code is enforced for construction”. Table
3
601 is only used for commercial construction and not required for a single family residence.
5. Under Energy Code Compliance, there is a rare reference to a residential code - the residential energy code (Table R401.1.2). However, the mechanical drawings show that building was designed in conformance with the commercial energy code (further discussed below).
6. Under 2008 Smoke/Carbon Monoxide Detector Notes, there are repeat references to the IBC instead of the IRC, including Notes 1, 2, and 4.
Sheet A-102
7. Both exterior stairways include railings that meet ANSI A117.1. A fully compliant handicap ramp is included at the north entrance. Both of these are necessary for commercial buildings, but not for single family residences.
Sheets A-102 & A-103 8. Exhaust fans for the kitchens are identified to meet Table 403.3.1.1 of the International
Mechanical Code. Residential requirements for exhaust fans are in the International Residential Code. Also, the legend includes combination smoke and carbon monoxide detectors to comply with the commercial code (IBC).
Sheet S-101 9. The Loading Schedule indicates a Live Load of 100 psf (pounds per square foot). This
would meet IBC Table 1607.1 #25, Public Rooms. Residential Live Load is 40 psf. The structure is significantly overdesigned for a residential use, which certainly results in larger structural components and additional construction cost.
Sheet SP-101 10. The Sprinkler Design Criteria oddly indicates that the Building is classified as “E”
occupancy group, which is Educational. The uses listed in the table include “office areas, toilet rooms, lobby areas” and “storage rooms, mechanical & electrical equipment spaces”. Note that bedrooms or other residential uses are not listed. A two story residential house, as this is claimed, is not obliged to be sprinklered. However, the building is fully sprinklered in accordance with the commercial building code.
Sheets EN-101 & EN102 11. Per the International Energy Conservation Code, a single family residence is compelled
to use the computer software “REScheck” to verify compliance. Instead, the commercial version of the program, “COMcheck” was used. Sheets EN-101 and EN102
BUILDING DEPARTMENT NOTES
BUILDING DEPARTMENT NOTES
1. THE SCOPE OF WORK IS THE CONSTRUCTION OF A NEW SINGLE FAMILY RESIDENCE.
2. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL DIMENSIONS AND CONDITIONS AND SHALL REPORT ALL DISCREPANCIES TO THE ARCHITECT IN WRITING PRIOR TO BIDDING FOR CLARIFICATION.
3. CONTRACTOR SHALL PERFORM ALL WORK IN ACCORDANCE WITH THE REGULATIONS OF THE TOWN OF FALLSBURG ZONING CODE, 2015 IBC, THE NATIONAL ELECTRICAL CODE NATIONAL BOARD OF FIRE UNDERWRITERS, THE FEDERAL OCCUPATIONAL SAFETY AND HEALTH ACT, AND WITH ALL AUTHORITIES HAVING JURISDICTION OVER THE PROJECT.
4. BEFORE COMMENCING WORK, THE GENERAL CONTRACTOR SHALL FILE ALL REQUIRED CERTIFICATES OF INSURANCE WITH THE DEPARTMENT OF BUILDINGS AND OBTAIN ALL REQUIREO PERMITS.
5. ALL MEANS OF INGRESS AND EGRESS SHALL REMAIN CLEAR AND UNOBSTRUCTED DURING THE CONSTRUCTION PROCESS
6. ENTIRE BUILDING TO BE FULLY SPRINKLERED AS PER 2015 IBC 903.2.8.
"ALL PROPOSED WORK CONFORMS TO 2015 INTERNATIONAL BUILDING CODE AND TOWN OF FALLSBURG ZONING CODE.
FIRE RESISTANCE RA TINGS
THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ENSURING TABLE 601 OF THE 2015 INTERNATIONAL BUILDING CODE IS ENFORCED FOR CONSTRUCTION TYPE II-A.
THE LISTOF FIRE RESISTANCE RATINGS BELOW IS NOT ALL INCLUSIVE OF ALL REQUIREMENTS IN THE CODE. REFER TO THE ABOVE MENTIONED TABLE FOR THE COMPLETE REQUIREMENTS.
INTERIOR BEARING WALLS AND BEARING PARTITIONS: 1 HR ENCLOSURE OF VERTICAL EXITS, EXIT PASSAGEWAYS, HOISTWAYS, AND SHAFTS: 2 HR. STRUCTURAL MEMBERS SUPPORTING A WALL: 1 HR FLOOR CONSTRUCTION INCLUDING BEAMS: 1 HR
ENERGY CODE COMPLIANCE
2015 INTERNATIONAL ENERGY CODE COMPLIANCE
R-VALUES PER TABLE R402.1.2, CLIMATE ZONE 6
OPAQUE ASSEMBLIES: CEILING: R-49 STEEL STUD FRAMED WALLS: R-15 CONTINUOUS+ R-12.3 CAVITY MASS WALL: R-15 CONTINUOUS +R-20 CAVITY FLOOR: R-30 BASEMENT WALL: R-15 CONTINUOUS +R-19 CAVITY SLAB & DEPTH: R-10, 4'-0' CRAWL SPACE WALL R-15 CONTINUOUS +R-19 CAVITY
GLAZING ASSEMBLIES: FENESTRATION LI-FACTOR: 0.32 SKYLIGHT LI-FACTOR: 0.55 GLAZING SHGC: NR
2008 SMOKE/CARBON MONOXIDE DETECTOR NOTES
1 SMOKE I CARBON MONOXIDE DEVICES SHALL BE INSTALLED IN ORDINANCE WITH THE 2015 IBC SECTION 907.2.11 AND NFPA 72.
2. SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS MAY BE COMBINED PROVIDED THESE DEVICES COMPLY WITH THE PROVISIONS OF 2015 IBC SECTION 915.4.3.
3. EACH SMOKE I CARBON MONOXIDE DETECTOR SHALL BE INSTALLED IN ACCORDANCE WITH THE REFERENCE STANDARD UL 2034, UL 2075. AND UL 217
4. EACH SMOKE I CARBON MONOXIDE DETECTOR SHALL BE INSTALLED OUTSIDE OF EACH SLEEPING ROOM IN THE IMMEDIATE VICINITY OR WITHIN 15'-0' OF THE ENTRANCE TO A SLEEPING ROOM: INSIDE EACH SLEEPING ROOM; AND ON EACH STORY WITHIN A DWELLING UNIT, INCLUDING BELOW GRADE STORIES AND PENTHOUSES PER 2015 IBC SECTION 907.2.11
5. EACH SMOKE I CARBON MONOXIDE DETECTOR SHALL BE OF A TYPE THAT ALLOWS FOR READILY TESTING OF SUCH DEVICE.
6. DUPLEX UNITS SHALL HAVE A DEVICE LOCATED ON EACH LEVEL IF ONLY ONE MEANS OF EGRESS IS PROVIDED FROM EACH LEVEL
7. CEILING MOUNTED DEVICES SHALL BE A MINIMUM DISTANCE OF 4' FROM ANY WALL.
8. WALL MOUNTED DEVICES SHALL BE A MINIMUM OF 4' TO A MAXIMUM OF 12' FROM THE CEILING.
9. EACH DWELLING UNIT SHALL BE EQUIPPED WITH AN APPROVED TYPE SMOKE I CARBON MONOXIDE DETECTOR DEVICE RECEIVING PRIMARY POWER FROM THE BUILDING WIRING WITH NO SWITCHES IN THE CIRCUIT OTHER THAN THE OVER CURRENT DEVICE PROTECTING THE BRANCH CIRCUIT AS PER 2015 IBC SECTION 915.4.1 AND 907.2.11.6
10. SUCH SMOKE I CARBON MONOXIDE DETECTOR MUST BE EITHER THE IONIZATION CHAMBER TYPE OR THE PHOTOELECTRIC DETECTOR TYPE ..
11. A "CERTIFICATE OF SATISFACTORY INSTALLATION FOR SMOKE /CARBON MONOXIDE DETECTORS' MUST BE FILED WITH THE DIVISION OF CODE ENFORCEMENT, 10 DAYS AFTER INSTALLATION.
12. WRITIEN INFORMATION OF TESTING AND MAINTENANCE OF THE DEVICES SHALL BE PROVIDED TO THE DWELLING UNIT OWNER.
. ~ . --'-- ~-- __ _J__~-"-&S·----------
PRIVATE RESIDENCE TOWN OF FALLSBURG
Sullivan County, New York
PROJECT INFORMATION
ADDRESS:
SECTION:
BLOCK:
LOT NUMBER:
ZONE:
LOT AREA:
PROPOSED BUILDING:
PROPOSED BUILDING CLASSIFICATION·
PROPOSED USE TYPE:
USE AND BULK REQUIREMENTS:
MAXIMUM HEIGHT: MAXIMUM LOT COVERAGE: MINIMUM FLOOR AREA MAXIMUM FLOOR COUNT:
AREA CALCULATIONS
SITE AREA= PROPOSED NEW FIRST FLOOR= PROPOSED NEW SECOND FLOOR=
Renner Rd TR 14
65
11.59
REC-1
4.9ACRES
9,328 SF
R-3 (SINGLE-FAMILY RESIDENCE)
P (PERMITIED USE)
REQUIRED (per zoning code Schedule 1) 35'-0" 10% 1,200 SF 2-112
4.9 ACRES (213,444 SQ.FT.) 6,186 SQ.FT. 3,141 SQ.FT.
LOT COVERAGE= (6,186) I (213,444) = 0.0289 = 2.9% FLOOR AREA= (6186) + (3141) = 9328 SQ.FT.
CONTROL INSPECTIONS
-STRUCTURAL STEEL· WELDING .STRUCTURAL STEEL· ERECTION & BOLTING -STRUCTURAL COLD-FORMED STEEL -MASONRY -SOILS · SITE PREPARATION .SPRAYED FIRE-RESISTANT MATERIALS -STRUCTURAL SAFETY· STRUCTURAL STABILITY -EXCAVATION· SHEETING, SHORING, AND BRACING -FIRESTOP, DRAFTSTOP, AND FIREBLOCK SYSTEMS -CONCRETE TEST CYLINDERS -CONCRETE DESIGN MIX -FOOTING AND FOUNDATION -FIRE-RESISTANCE RATED CONSTRUCTION -FINAL INSPECTION -INSULATION PLACEMENT AND R-VALUES -FENESTRATION THERMAL VALUES AND RATINGS -FENESTRATION RATINGS FOR AIR LEAKAGE -FENESTRATION AREAS -AIR SEALING AND INSULATION· VISUAL -LIGHTING IN DWELLING UNITS -INTERIOR LIGHTING POWER -LIGHTING CONTROLS -EXIT SIGNS -MAINTENANCE INFORMATION
ZONING / VICINITY MAP
PROVIDED 24'-6' 2.9% 9,328 SF 2
DRAWING LIST
T-100.00
C-100.00 C-101.00
A-001.00
A-101.00 A· 102.00 A-103.00 A-104.00
A-111.00 A-112.00 A-113.00
A-121.00 A-122.00 A-123.00
A-131.00 A-132.00
A-201.00 A-202.00 A-203.00 A-204.00 A-205.00 A-206.00
A-300.00
A-500.00
S-001.00 S-002.00 F-100.00 F-200.00 S-101.00 S-102.00 S-103.00 S-400.00 S-401.00
PROJECT INFORMATION, NOTES AND DRAWING LIST
SITE PLAN SITE DETAILS
BUILDING SITE PLAN
CONSTRUCTION PLAN • CELLAR FLOOR CONSTRUCTION PLAN· FIRST FLOOR CONSTRUCTION PLAN· SECOND FLOOR CONSTRUCTION PLAN • ROOF
REFLECTED CEILING PLAN· CELLAR FLOOR REFLECTED CEILING PLAN· FIRST FLOOR REFLECTED CEILING PLAN· SECOND FLOOR
ELECTRICAL PLAN · CELLAR FLOOR ELECTRICAL PLAN· FIRST FLOOR ELECTRICAL PLAN· SECOND FLOOR
FINISH PLAN· FIRST FLOOR FINISH PLAN· SECOND FLOOR
EXTERIOR ELEVATIONS EXTERIOR ELEVATIONS BUILDING SECTIONS BUILDING SECTIONS BUILDING SECTIONS BUILDING SECTIONS
CONSTRUCTION DETAILS
PLUMBING RISER DIAGRAMS
STRUCTURAL NOTES STRUCTURAL NOTES CELLAR FLOOR FRAMING PLAN & FOUNDATION FOUNDATION SECTIONS FIRST FLOOR FRAMING PLANS SECOND FLOOR FRAMING PLAN ROOF FRAMING PLAN TYPICAL SECTIONS TYPICAL SECTIONS
SITE PLAN
SP-101.00 SP-201.00 SP-202.00 SP-301.00 SP-302.00 SP-303.00 SP-401.00
M-101.00 M-201.00 M-202.00 M-203.00 M-204.00 M-301.00 M-302.00 M-303.00 M-304.00 M-305.00 M-306.00 M-401.00 M-402.00 M-501.00 M-502.00 M-601.00 EN-101.00 EN-102.00
E-101.00 E-201.00 E-202.00 E-203.00 E-301.00 E-302.00 E-303.00 E-304.00 E-305.00 E-306.00 E-307.00 E-401.00 E-501.00 E-601.00
P-101.00 P-201.00 P-202.00 P-203.00 P-301.00 P-302.00 P-303.00 P-304.00 P-401.00 P-501.00 P-601.00
CELLAR-ROOF: SPRINKLER SYMBOLS & NOTES CELLAR-ROOF: SPRINKLER SPECIFICATIONS I CELLAR-ROOF: SPRINKLER SPECIFICATIONS 11 CELLAR: SPRINKLER PLAN & NOTES 1ST FLOOR SPRINKLER PLAN & NOTES 2ND FLOOR: SPRINKLER PLAN & NOTES CELLAR-ROOF: SPRINKLER DETAILS
CELLAR-ROOF: MECHANICAL SYMBOLS & NOTES CELLAR-ROOF: MECHANICAL SPECIFICATIONS I CELLAR-ROOF: MECHANICAL SPECIFICATIONS 11 CELLAR-ROOF: MECHANICAL SPECIFICATIONS 111 CELLAR-ROOF: MECHANICAL SPECIFICATIONS IV CELLAR: MECHANICAL PIPING PLAN & NOTES 1ST FLOOR: MECHANICAL DUCTWORK PLAN & NOTES 1ST FLOOR: MECHANICAL PIPING PLAN & NOTES 2ND FLOOR: MECHANICAL DUCTWORK PLAN & NOTES 2ND FLOOR: MECHANICAL PIPING PLAN & NOTES ROOF: MECHANICAL DUCTWORK PLAN & NOTES CELLAR-ROOF: MECHANICAL DETAILS I CELLAR-ROOF: MECHANICAL DETAIL II CELLAR-ROOF: MECHANICAL CONTROLS & SEQUENCE CELLAR-ROOF: MECHANICAL REFRIGERANT RISER DIAGRAM CELLAR-ROOF: MECHANICAL SCHEDULE CELLAR-ROOF: MECHANICAL INTERNATIONAL CODE COMPLIANCE I CELLAR-ROOF: MECHANICAL INTERNATIONAL CODE COMPLIANCE 11
CELLAR-ROOF: ELECTRICAL SYMBOLS & NOTES CELLAR-ROOF: ELECTRICAL SPECIFICATIONS I CELLAR-ROOF: ELECTRICAL SPECIFICATIONS 11 CELLAR-ROOF: ELECTRICAL SPECIFICATIONS 111 CELLAR: ELECTRICAL- LIGHTING PLAN & NOTES CELLAR: ELECTRICAL- POWER PLAN & NOTES 1ST FLOOR: ELECTRICAL- LIGHTING PLAN & NOTES 1ST FLOOR: ELECTRICAL· POWER PLAN & NOTES 2ND FLOOR: ELECTRICAL- LIGHTING PLAN & NOTES 2ND FLOOR: ELECTRICAL- POWER PLAN & NOTES ROOF: ELECTRICAL POWER PLAN & NOTES CELLAR-ROOF: ELECTRICAL DETAILS CELLAR-ROOF: ELECTRICAL RISER DIAGRAM CELLAR-ROOF: ELECTRICAL PANEL SCHEDULES
CELLAR-ROOF: PLUMBING SYMBOLS & NOTES CELLAR-ROOF: PLUMBING SPECIFICATIONS I CELLAR-ROOF: PLUMBING SPECIFICATIONS 11 CELLAR-ROOF: PLUMBING SPECIFICATIONS Ill CELLAR: PLUMBING PLAN & NOTES 1ST FLOOR: PLUMBING PLAN & NOTES 2ND FLOOR: PLUMBING PLAN & NOTES ROOF: PLUMBING PLAN & NOTES CELLAR-ROOF: PLUMBING DETAILS CELLAR-ROOF: PLUMBING RISER DIAGRAM CELLAR-ROOF: PLUMBING SCHEDULE
,_ __ , (
'
253 Fifth Avenue New York, New York 10016 212.253.5577 www.diarch.net
PIETRZAK & PFAU ENC/NEER/NC &: SURVEYINC,PLLC
262 Greenwich Avenue Suite A Goshen, New York 10924 845.294.0606 www.pietrzakpfau.com
Wexler Associates
FALLSBURG SUBMISSION
Issue:
DOB STAMP:
PROJECT:
Structural Engineers
12 West 32nd Street 8th Floor New York, New York 10001 212.643.1500 www.nwexler.com
111 West 33rd Street 18th Floor New York, New York 10001 212.967 .8944 www.twigcon.com
09.20.17
Date:
----.-. ---------------------------------------1 PRIVATE RESIDENCE
I
PROJECT LOCATION SECTION: 65 BLOCK: 1
~: ~1 '
I ' '
' '
I '
PROPOSED ELJEt-. SDS DESIGN FOR 990 GPO MAX
5 LA.TS @ 56' EACH, 280 LF, TOTAL
$71"56'26"E
__ N04"51'32'E 1 243.74' 21·90' } CONDENSER UNITS '~r-~-:----:--.,ffiQf!llJl.l.JijE,---~--,---~--,----~----{,.g'il,21~---i:;m:i.m. E -smro --
INCOMING ELECTRICAL SERVICE 3,500 GALLON SEPTIC TANK
PU~P STATION
$04'51' 32""11'
EXISTING 12' 'MOE WELL ACCESS DRIVE
UTILIZE EXlSTING ACCESS ROAD
EXISTING 12' WIDE 'tiELL ACCESS DRIVE
GA TE_,,,
1,21o.9~ IRON PIN FOUND (TYP.)
ADDRESS:
TOWN OF FALLSBURG SULLIVAN COUNTY, NY
PROJECT INFORMATION, NOTES, AND DRAWING LIST Project No: 171042
Scale:
Date: 9.20.2017
Drawn By: RS/CS
Approved By: DI 001ot083
T-100.00 Printed oo 9.21.2017
© G;>
@
CD i
I [LANDSCAPI~
11 '-3"
@ '
'
TYPICAL AT EXTERIOR WALLS
36'-10"
STEEL' COLUMN I
TYP.:
®
105'-2''
. _: " ___ .:.1 _____ 1..c..i:.,'.~m=u-~------1U11....-.,nu•,a•w1w..,,_.,,,,.,.,uN"'''"'"'!""n""''"'"''
® (j) i
HABITABLE SPACE AREA= 810 SF
®
MIN. REQ. WINDOW AREA= 81 .0 SF PROVIDED= 723.2 SF, COMPLIANT ,
--- - --- +------HABITABLE SPACE
---- ARfA-m-60f-SF- ----Mltt:-REQ. V!:Nr!LA T10N-AAEA~41Hi-SF--·'· PROVIDED = 111. 7 SF, COMPLIANT
8 -tr--!HAB~A11,!f:l.!tf!~;E~3£;/lp'.t~~f!c.E
MIN. REQ. WINDOW AREA= 30.3 SF PROVIDED= 19.0 SF, COMPLIANT
IN. REQ. VENTILATION AREA= 15.2 PROVIDED= 19.0 SF, COMPLIANT
HABITABLE SPACE 1-21 AREA= 109 SF
, IN. REQ. WINDOW AREA= 10.9 SF ' PROVIDED= 19.0 SF, COMPLIANT IN. REQ. VENTILATION AREA= 5.5 SF
' PROVIDED= 19.0 SF, COMPLI T 9'-0"
®
REF
8
1-10
8
~ ,-,6"'' -""O""" -,
11 WARMING KITCHE · o_J COOKING APPLIAN ES I
~-j I I
Fl=="---t:=-,--1 I _J
1 i
1~ i~
[LANDSCAPl1 I
1 CONSTRUCTION PLAN - FIRST FLOOR SCALE: 3116" = 1'
r
MIN. REQ. WINDOW AREA= 60.7 SF PROVIDED= 120.8 SF, COMPLIANT
MIN. REQ. VENTILATION AREA= 30.4 SF PROVIDED= 120.8 SF, COMPLIANT
4'-6"
REF
-11--'=-.,"-"'t:::;1,.oocol.FM EXHAUSTT ROOF PER 2015 IMC TABLE 403.3.1.1
8
FULL-HEIGHT GLAZING PARTITION
~ HABITABLE SPACE -
AREA-140 SF MIN. REQ. WINDOW AREA= 14.0 F
= MIN. REQ. VENTILATION AREA= 7. S
,-.,...-, PROVIDED = 30.2 SF, COMPLIAN
3'-5'' -ffiJ-------'HJ'.-=' ,e2'---'·-----------------..J.......j, I'
UARD RAIL AND HAND RAIL
ONCRETE STEPS
I
I
I ,
!\._LINE OF ~ I SECOND FLOOR
ABOVE
---- - ----·-·----- - @ rn--
TYPICAL AT EXTERIOR W LS
I
~
'-----ALIGN-----'
FINISH FLOOR +1.46'
TOP OF CONG. +2.36'
' ~ ., '
~----ALIGN-----,
e FINISH FLOOR +2.46'
TOP OFCONC. +2.12'
I
~ ,.'_,._·,r,r .. -: .. · ... •,,.•,,.·,., ·¥·'. i·,:.\:-:->JT~1 ,.,., .• - -T- ,,·.
,. •'', I ."' ... · i.'.1 :\J.: ',!i,jij " I
BUILD-IN
1===::1::=-=-=··---j-- El .___._.,..-_-_---_--_-_--_,-..,,__-_ ...... _ ...... _ ...... _---_--_-~-_ _. ........ -8 BUILD-IN
ALIGN FINISH FLOOR +2.46'
TOPOFCONC. +2.36'
35'-9"
HABIT ABLE SPACE AREA = 1,394.54 SF
MIN. REQ. WINDOW AREA= 139.5 SF PROVIDED = 723.2 SF, COMPLIANT
MIN. REQ. VENTILATION AREA= 69.SSF PROVIDED= 111.7 SF, COMPLIANT
I I I I I
.. ···· I
I
~
CONSTRUCTION PLAN LEGEND
• @
0 XXX X
(1 ®
NEW PREFABRICATED EXTERIOR WALL
NEW FULL HEIGHT PARTITIONS AND STRUCTURE
ROOF DRAIN
WINDOW TYPE INDICATOR· REFER TO WINDOW TYPES
PARTITION TYPE INDICATOR· SEE SHEET A-300 FOR PARTITION TYPES
ROOM NAME & NUMBER
MILLWORK
DOOR AND DOOR NUMBERS • REFER TO DOOR SCHEDULE
FLUSH MOUNT HARDWIRED COMBINATION SMOKE AND CARBON MONOXIDE DETECTOR TO COMPLY WITH 2015 IBC
ELEVATION NUMBER
DRAWING NUMBER
DETAIL NUMBER
DRAWING NUMBER
® NOTES: 1. REPORT TO ARCHITECT FIELD DIMENSIONS IN CONFLICT WITH DRAWINGS. 2.ALL DIMENSIONS ON THIS PLAN ARE FINISHED DIMENSIONS U.O.N.
JANDSCAPI~
STEEL COLUMN
TYP.
i
-------- +-
[LANDSCAPI~
3.ALL WET AREAS TO RECEIVE INDUSTRY STANDARD 'GREEN BOARD' AND WATERPROOFING AS PER DETAILS. (TYP.)
LANDING - PRECAST CONG TILES ON CIP CONCRETE SLAB
4.SKIM COAT ALL WALLS THROUGHOUT.
FINISH FLOO ±0.00'
----------.\------"S::,LOe::P..sE-'1:"'12'---5;1.------------I-UP ;;: rF~IN-IS~H-F-L~O-OR,
UP
'-11"
N
RAMP - PRECAST CONG TILES ON CIP CONCRETE SLAB 4' CONG. CURB wl HANDRAIL
SIDEWALK - CIP CONCRETE SLAB
03 GREENING ROOM
4' CONG. CURB wl HANDRAIL
LANDING - PRECAST CONG TILES ON CIP CONCRETE SLAB
STAIR TREADS AND RISERS -PRE CAST CONG TILES ON CIP
CONCRETE SLAB 1-114"0 STEEL PIPE
HANDRAILS TYP.
12"
8 RISERS
-2.00'
5'--6"
PITCH TO DRAIN )
FINISH FLOOR +2.46'
TOP OFCONC. +2.12'
PITCH TO DRAIN )
1<-f-a-+-+-+-+---t-UP
15'-0" '-5'1 ; ,_, -+-----~~-------+-+--+--f---tt-t--_,_. !, ir ·-·--•• ,. ;
·!: ii
q: ,i! " lfl
Iii ;;,
" " 'i' !i! ,ii ·i! ;, ,,
101
i I REF AB EXTERIOR ii PANELS TYP .
. !i+
i:
t ;,: 11 !I
,1; Ii! i! ----"' r:
SIDEWALK· CIP CONCRETE SLAB
[LANDSCAPI~
FINISH FLOOR -2.00'
FINISH FLOOR -2.00'
I
I
L
253 Fifth Avenue New York, New York 10016 212.253.5577 www.diarch.net
1: PIETRZAK & PFAU T ENGINEER/NC & SURVEYINO,PLLD
262 Greenwich Avenue Suite A Goshen, New York 10924 845.294.0606 www.pietrzakpfau.com
Wexler Associates Structural Engineers
FALLSBURG SUBMISSION
Issue:
DOB STAMP:
PROJECT:
PRIVATE RESIDENCE
ADDRESS:
12 West 32nd Street 8th Floor New York, New York 10001 212.643.1500 www.nwexler.com
111 West 33rd Street 18th Floor New York, New York 10001 212.967.8944 www.twigcon.com
09.20.17
Date:
TOWN OF FALLSBURG SULLIVAN COUNTY, NY
CONSTRUCTION PLAN FIRST FLOOR
Project No: 171042
Scale: 3/16"=1'
Date: 9.20.2017
Drawn By: RS/CS
Approved By: DI 006 of083
A-102.00 Printed on 921 .2017
' . ' '
l
r /
------------------------------------------- -···-·····--···---- ---- ----------~----------------------
t
CD I
'
1·-,tl
3'-~"
12·-,t·
c;,... 5'-11" ~
®
I 6'-1~'1
BUILT-IN
® I
12·-,t·
EXTERIOR PfJ.tFAB PANEL,TYP\
;;;;\ 6'- ,J,. 5'-11" '{:5 "2
' ' F
eS'-1" 203 ,
I O M I
$ I
I
I
I
I
I
6' 1"i' ' ' e,·1·
® I
105'-4"
JQJ I
BEDROOM 1
3'4'
12'-9!'
9'-10"
®
1'-~"
12·-&1,,, 2
® ®
12·-~· 12'-~'
I i ,,, ..... ··.·fi!
11·~=-···=···4=··=·-="'-l+ -+-+ -li=--c==ic~-=i-1- +--+-- -i-:1-=-=ac=·L.'.::::;-,'+ I ....... -
J_ I '
: ; e-l-1 -.. l 1-=··=···-.. ·=· .. ~--··"--"'·· . I -1- -+ li ' -1- ·,
~ l! 1:tt£. ____ ...J.'14"'-§'.6"'...__~<!>J-I __ JI
l!'!l-t-lt 1 ,t- -----.L
1: r:r,-,,. / -· 1: / I,:
ii~ 1, : !I.
! ~ :: H')S\fil.B~~ltfE I 21'-11"
PROVIDED= 60.4 SF, COMPLIANT I
(3: TYPICAL AT ....!... ' / . 1:
~ / lj, EXTERIOR WALLS I , / I ,;
HABITABLESPACE I i ~ / I ll AREA=179SF ! e , 1 1 .,,, ! j:
MIi REQ.WIND0WAREA=17.9SF . , • i'--, /, _ _ _ _ _ _ _ _ _ _ I II t :Ji.jiil"'l\1' ¢:Titt:1_t.,. "'IN. REQ. VENTILATION AREA= 8.4 S
MIN. REQ. WINDOW AREA= 16~6 SF._
R O I PROVIDED= 60.4 SF, COMPLIANT , @
PR )VIDEO= 60.4 SF, COMPLIANT I - ' "---.._ / ' -MIN. EQ.VENTILATIONAREA=9.0SF , / , 11
i PRJV1DE0=60.4SF,COMPLIANT ,--+,"'I ~ / I A I :J
®···· I ' 1!~ I~ ...
Ii I 9'·7" I~ .. $" 'l cI. 1,j;:::::==.::--.::---· =··=··· ==t· .. © .... :;- ...
ft, 1i 1+ 11 : 1i~;.... H :
9'-7"
206 ROO
HABITABLE SPACE AREA= 199 SF i
M~~o~~&;f;N£~~t.Rc~Jp~ikf : MIN. REQ. VENTILATION AREA= 8.5 SF
PROVIDED= 30.2 SF, COMPLIANT ! Ii........ 14'-6" ! ,; I #------="-----+---+I p ! ,A l
I I
~WAR coo
' 11'-3" ,..../- I v I ii lil'----+--'-'-"'------A4 I / x ~ I I II
I V t ..... t T / ' ' T ii
ING Kile EN: i;roov1 ED = 60.4 SF, coMPLI llf;::;:;:~;:::;::::;;!:::::::;:::;;i-----.i:1 : I I
NG~'.'.fu NcEs 1 1 X· .. · n \ 8 , <t, Ii Q I L:J ~ I / r+ 11 201 I ' II ~ 1(3) 'v•.-,,,.'-+-H,-t+:ltl -~"BA"'T&.Hel!aoosaMrl ', , 1 ii
1: ! ----- -- -~ .!! IT V - . \" El3-=
/~:
I' V • b ' ' /p "
I l .!, 0 • ~ ~ 1 11 e ,A) 1ri:t1:"===<)):!:;=====::::!l·...:· ==---==----=--=-=""...:;;.='\_...:,L ___ INE...:O.:._Fjs:!:6F::::Fl::::T ===-=· ::::·:::::::·:!·J:· ·=··,~·~=. /=tit Ii -~···
20 RIOO
.. 1: '..L
I! i ;
'
,, /?rCON:TE STEPS i / r{,UARD RAIL\ i 'I ;-HAND RAIL \ I
' ' '
<t, FINISH FLOOR +13.45'
TOPOFCONC +13.35'
~ ~ <t> ~~~irp~~ttM~1JV / ' e+- "~ ~ ! / l i! ~ ~ TABLE4CJ3.3.1.1,.,, '- I 1 ----.___ / - -/-r-----~ -f-- - A·204
\_GUARD RAIL ~ ----.___ / I ~ i I • >--._ ~
I
1'HH-+<1-~>H-+++-H-+~i'II 42'AFFMIN. / i '~ ' , , I ~
/ ' "' //---------1,.- ~- A,~03 ~ i I / (1} ~~ "'
---+--~8··~1~f" _____ - rn <)) ...... m. _ _, ; d 8',11" : ! · ·~ ....
--' ' '
··~·-
/
,:, '" i'""' I- ti ------ -------------------- ----------------·--
~ 1-- ,q ' :ii : :!i CI 1 '1 e ' @
--+=2M-~e : : - 6'10" C IL ~ 1 V: ~ ; ,,> ! . ~ r _;. J-.A--+-ROOF DRAIN 1: , .
~ H':9J~1ffiE •.•• ?ftfE I i,, 8~09 )IOI ! ..... HABITABLE SPACE ' ;! II i i Ii :
i)! ! :·.:,i,
I '; : ,J!
A
/ V
/
• rm.~ vu"..,, I ! AREA-132 SF 11 - ; 1 DO ARE -->R,--lll---+--+----+-+' ---1---+--b--lJ'1~4 s=.l' MIN.IEQ.WINDOWAREA=30.3SI ,', -,.t--,1 ]MIN.REQ.WIN W A .-,-v,, GUE-,T""DROO'<•
PRO IDED = 19.0 SF, COMP~I~~ !,, 0 , ,, 1 I=::::.) PR VIDEO= 40.8 SF, COMPLIANT : ' = • {'V_j: lc/zs,1,c+t,-illi/!',l~\'J.•t-::.~I MIN.REQ.VENTILATIONAREA=6.6 , !
1 _:_ PRO IDED=ls.os;;.~;~PLIANT/ l"' ,_---+__,I ~2~PR v1~~~; .. 1sosF.coMPL1ANT i: ........... 1 ......
1 11
I,! . ® 6'·0" M ,-~,cc, - ® ~ ': I I I, 1'' '
t 1: : 7'.3•,, ~ 8 ' . ~ - ,_ @ I ~ 1-l ;j 1'1-- -!---·······················+-· ' . 1-+-- ...... . .... ------- -- +-~•:,,-11-· lH- -- -- ....
jj_,;_ ~@ ; ~::~~i HABlrAsLESPACE L!- ,I I n t--- · '' ®---- - ..
IL __ - ~""""_J AROC=223SF ··,,·---·"-.··'··········-··-·······+'··+······I I 1!--·------. ., .. ., .... ,..,_,, ______ ··-·-·-·:·---····-·.·
MIN. REQ. w1~Thw AREA= 22.3 SF LI LOO T · ~, '
@ : ~ HABITABLE SPACE ~=~:::..--= ~ Ml{:g~~{tN!r:i1!~~;~:1t¥SF ~ <+-··+·······-··"'···-·+··+··i<·-···>l ;•I:·:·; ... -.. · ,F,= __ ,_~R-~LE.-.... -.J::··.:··: ~ ! ::: AKl:A- lUl::I ::;.. LJ rWARMING KITCHEN; NO ::: rr '° ---t-+--,--+~"'2"'"~--<1 "
' MIN. EQ. WINDOW AREA a 10.9 SF COOKING APPLIANbES /,l\ ; ' TERRA E ' I ;;,
' 1i:~ {!1T1wi~!;~rN:1, I ~1.,3
.. 11'-3" I . \:t / L i r-;-:--i---1--ROOF DRAIN: : i! t 1,-_.,.n--,J<.-l ,'-+-~9c:,'·O;_" ___ -SI ! '-l:1'----,,l-,t~----1 REF : TYPkC~6~\I/, LS : ,._..,_. r-- !i -'· / T f-- : : :: T
®····· G~-ru__·····_·· ·, ~tr_~~-,-,-~,·:=§·····§····~-·-•,§c··,§+"''§':c:§:·:~§";§;"·'§;,;§);:~~H-t~::+,,§··'§':~.~--;§.:·~--· ··§);··---~. ···-~-·····§····~·~.~--'~----,~-~H~_++',~-·· -~1~ .. ;;······=='···~·-···=·-~······-··t, ~~I;,§·,,,,~:~;:~.~;:_--_····_·_·····_···_······_·· _···-·-:.--·········L······_j· ; .... : ':.: ! 29'-1' ' 5'-11' I 3·.,t· ! I I
21D 111 I DR OM BUILT-IN 1
CONSTRUCTION PLAN - SECOND FLOOR SCALE• 3/16" • 1'
I 212 1 PLAYROOM
I XTERIOR PREFAB ! I I I PANELS TYP. I I
I ~II I 2 I I I A-201 I I
<$) <$)$
/
/ /
/
/ .. - ... -/-
/ '
/ /
/
.. .. . ... i ... ·--
X /
€)1 I I I I I
··'\. ----
! '
: "' . "' I
A
V
' ,;, ' :1: i i( :;
·1: ! H
i! : ,, ' 1:
: 1:~ 'i 1, (0 -- --- ----------- •1, "·t'r ··· .L I;
, 11
I! 1:
~ !!~ ----'>----- -,-1:-- A-~03
"' ii ~ i: ' 1:
"' + Ii ·---- ----------- ---------- I ii -----~---- --- --- --------· ·-· ·· --- i'
CONSTRUCTION PLAN LEGEND J~: _______ -1
JOO(
X
®
NOTES:
NEW PREFABRICATED EXTERIOR WALL
NEW FULL HEIGHT PARTITIONS AND STRUCTURE
ROOF DRAIN
WINDOW TYPE INDICATOR· REFER TO WINDOW TYPES
PARTITION TYPE INDICATOR· SEE SHEET A-300 FOR PARTITION TYPES
ROOM NAME & NUMBER
MILLWORK
DOOR AND DOOR NUMBERS • REFER TO DOOR SCHEDULE
FLUSH MOUNT HARDWIRED COMBINATION SMOKE AND CARBON MONOXIDE DETECTOR TO COMPLY WITH 2015 IBC
ELEVATION NUMBER
DRAWING NUMBER
DETAIL NUMBER
DRAWING NUMBER
1.REPORT TO ARCHITECT FIELD DIMENSIONS IN CONFLICT WITH DRAWINGS. 2.ALL DIMENSIONS ON THIS PLAN ARE FINISHED DIMENSIONS U.O.N. 3.ALL WET AREAS TO RECEIVE INDUSTRY STANDARD 'GREEN BOARD' AND
WATERPROOFING AS PER DETAILS. (TYP.) 4.SKIM COAT ALL WALLS THROUGHOUT.
253 Fifth Avenue New York, New York 10016 212.253.5577
_www.diarch.net
,_,L PIETRZAK & PFAU T ENC/NEER/NC & SURVEYINC,PLW
262 Greenwich Avenue Suite A Goshen, New York 10924 845.294.0606 www.pietrzakpfau.com
-------------------------i
Wexler Associates Structural Engineers
12 West 32nd street 8th Floor New York, New York 10001 212.643.1500 www.nwexler.com
~------------·-------------;-----------------------;
111 West 33rd Street 18th Floor New York, New York 10001 212.967.8944 www.twigcon.com
--;-------------------------,
FALLSBURG SUBMISSION
Issue:
DOB STAMP:
PROJECT:
PRIVATE RESIDENCE
ADDRESS:
TOWN OF FALLSBURG SULLIVAN COUNTY, NY
CONSTRUCTION PLAN SECOND FLOOR
Project No: 171042
Scale: 3/16" = 1'
Date: 9.20.2017
Drawn By: RS/CS
Approved By: DI
09.20.17
Date:
007 of083
A-103.00 Printed on 9.21.2017
' '
. l
..
MODULAR CONSTRUCTION ON CONCRETE FOUNDATION CONNECTING CORRIDOR MODULAR CONSTRUCTION ON CONCRETE FOUNDATION
~----·----.---·------· . . '' ( . ·: . . . . . ! . '
,.._T~QF PARAPET V +29.00'
CD TOP OF ROOF
STRUCTURE---,
r-----111.ATERIAL B
,---MATERIALC
di, TOP OF RQOF STRUC U81c. V •24.34' b .• :::.J.J:,::;:.JC.J.::.:.c: .. :.cL: .. ;:: ... J: .• ,::.,L.J:.,+: ... J .•.•... ~.: ... L.::, . .J.J .. l...JC, .. cT._,.J.J,.L.:t,::.CJ.C .. ;,
/\ /\
,' \
' ';§"
" ! " /
"" 2ND F.FL. . +13.45'
' . : i
: ' ,,
i\ ! '
~ \
\ i \I !
"' 1§TF. FL. +2.46'
'J' N
NORTH BUILDING ELEVATION SCALE, 3116' = 1'
© ,---,AATERIAL C
®
- -----ry---·· ----- ·---'--'------·-
FIXED GLASS ,~->---,- PANELS-++->
® ,---!STONE CLADDING
. TYPEE
(j)
1!
"
,---fl!ATERIAL C
FIXED GLASS
® TOP OF ROOF
STRUCTURE~--,
'I
® STONE CLADDING
TYPEE---,
I
'<------i""'"°~'1t-------t-t------<;--,----tri----- PANELS--,-+------> 1:1 I
I 11
J =-:-._J :=····===~ :=====:· ,~I ··.···_· •-· .. ..:.:_:i·:====l··r-·1
·I
!
,. . I ! \
' !
\
MODULAR CONSTRUCTION ON CONCRETE FOUNDATION CONNECTING CORRIDOR MODULAR CONSTRUCTION ON CONCRETE FOUNDATION
.. _ -"'- TOP OF PARAPET V +29.00'
di, TOP OF ROOF STRUC URE 111117 +24,34'
di, 2ND F.FL. 1111P +13.45'
CIP CONCRETE RAMP WITH PRECAST CONCRETE TILES
r· --- --- ------- -----.----------------- ----------··-·-·-·-···---~----.---------- --- .•.. - ----------- ----- • ·-------------.--- ___ ,,., _________ . ---
'
® MATERIAL E
•. ·+·.J--·---------·-·-· ' -
- ...... ~---,
~-TOP OF ROOF STRUCTURE
®
'
II I
~-·1' ALUMINUM COPPING (TYP) (SEE DETAIL)
. !
(j) ,---MATERIAL C
(---iH. -.. - PANELS:-,c+---~ -·
® ® MATERIAL E MATERIAL C
·------- •·----·"'""- ... T-·- - .•
-·-·-·-·------.__l··~-- -
<---+IX GL~ NELS
FIXED GLASS 1·
, .... ,_., ~====: ~=:::;==~:I:=:.:====: ~====: :==:;;:=:.:=: :=:.:===:r1 ·-11:=:.:===: ~=;:::=~1 /. ! \ \ \
/ \.
\ ; d
\
\
~-TOP OF ROOF STRUCTURE
"' :~~: FL s,=~~~=~s~~~t~~~7'=·'"·-~.CC.-~. §~~rr=':iE',llt ··;t·:Jt-.s .. s ... s,s •. s. ~~j--~-S-I---S··S· s.s .. ~cS··S···~· ··t·S· :;s··]··'S-S··S··=--=·~·1S··~~=~~t~~]~I .. ~·~·-S .. S=:S::± ... S···=====-==·S:S:.i···t--·-''.-.. -... -... -... _-=-;--... -... ~ ... L.: ... ~ .. ===~t1
·"· ·,·· ..... , ... f-·· '···-
'i' GRADE ±0.00'
SOUTH BUILDING ELEVATION SCALE : 3116" • 1'
' ·------ j
©
. ' i· .J - -T
'
~-RAISED PANEL WI WINDOW (TYP)
___ 1_ ______ , ...• 4c. .. ·····"·"····~······ -· • I !
' le .
0
ONCRETE RAMP (BEYOND)
,----M,ATERIAL B
CD '
~-1' ALUMINUM COPPING (TYP) (SEE DETAIL)
CD
",ff,_,,_,,,,>,¢=)'•
: i
I iz !o ii= ' t.) ':, ' "' : ,-! ~ :o : t.)
:~ ':, le, -~
I . l . -----,.,
253 Fifth Avenue New York, New York 10016 212.253.5577 www.diarch.net
J., PIETRZAK & PFAU T ENOINEERINC & SURVEYINC,PLLO
262 Greenwich Avenue Suite A Goshen, New York 10924 845.294.0606 www.pietrzakpfau.com
Wexler Associates
FALLSBURG SUBMISSION
Issue:
DOB STAMP:
PROJECT:
Structural Engineer.s
12 West 32nd Street 8th Floor New York, New York 10001 212.643.1500 www.nwexler.com
111 West 33rd Street 18th Floor New York, New York 10001 212.967.8944 www.twigcon.com
09.20.17
Date:
PRIVATE RESIDENCE
ADDRESS:
TOWN OF FALLSBURG SULLIVAN COUNTY, NY c---------------~.~--~----1
EXTERIOR ELEVATIONS
Project No: 171042
Scale: 3/16"=1'
Date: 9.20.2017
Drawn By: RS/CS
Approved By: DI 01701083
A-201.00 Printed on 9.21.2017
. ,
; ,, ,i
ii . - ;
I i(
' .
I ,,
I ,, '
' ' ,
cp I
9 0 cp 112'-9}5" 12'-9}:;" 12'-9}:;" 12'-9}:;" 12'-9}:;" 12'-9}:;" 12'-9}:;" 12'-9}:;" I
I. I I I I I I I I t EL. =O O' /__/
0-------- r i '- ---=-~~-?=- - -=-L y--~=--c----=,~ T_=-c_-=-~ ~ -------- i-P~-. --~----__ -_ ~y---=--------==-----~y----_-_ -Ii_______.__,:---------® EL. =0 0~ ..__
11 u) u) u) 11 111 I ;" u) 11
Ii ~ ~ ~ "$/ : I I I ~ ~ ~ I I ~ m
I
N
I I : "' "' "' ioz;~ ! I I : "' "' : I
LJI /~ rl ll J ! ®--------LtJ CcpJ W1D x 22 CcpJ W10 x 22 C9-8 ' -------- 1fl CcpJ W10 x 22 CcpJ ~-t: ____ l _____ ®
' ~ en
I
<.O CD
11' I I ~ 1 I ~ ii i ~ i Ii 1i i i ii
! I I I ~ ~ I,: 11
Ii ,~G ~~ i,: I; I I ~ I, 'o·,-1<?·' I' I I I I I: (:' ', I I--~~~_-+ -- -=--=--=---I 1 W10 X 22 ,11 W10 X 22 ~ Lt-1 lrl~ W10 X 22 lrl G
©---------++tt W10 X 22 _J W10 X 22 I L _J L __s- -- -~- ---i__+++_J------L':-hl-t-'J------L':-h-1:-1 ------+-I : I :
~ ~ lj : 111 : ~ I ~ .-- ~ I : 0 I I S6 ::5 I ~ [L
~ - II i /'[~'t-io" ; ~~ I &,~
;; < : j_ UP I
I I W10 x 22 i W10 x 22 11 W10 x 22 I ~ --1------ -------
~-;;-f""-----i=i _J ----•1 '1\ }; .I L I _J , \ ,-,>'S" [ /1-' I ' '
I: I\ 1 'I I: : I 1! I \ !1 1! !1
lj r ·· I 11 EL.=2.46' 11 jl 1, DN \ 1 ,I 1,
1 n W16 x 45 p 1
t-tf+-1 -----1------------1--t--1+-----CdJI Jf------ Ccb j W10 x 22 Ccb j ~ I ~ I - - --- UP - I 111
I 'I CC) u)
l 1 : I I: lD LO : I ~ I : i ~ i I I ~ I I EL.=O.O' 1 I ~ ~ I 1
~' I. • 11 ,, , · -
~---
-20
---.-------@ ~
N
®- - -
I I I I I I I I
(
EL. =0.0' _../ 1
i i i i 1 1 1 -l __ EL =Q.0'
I I
53' I 11" I 10' -o}:;" I - 1 -- I I
I I I
1~!; -~
I I
d~ cb I ® 0
'
I I
0 FIRST FLOOR FRAMING PLAN
SCALE: 3/16" = 1'-0"
STRUCTURAL NOTES:
1. TOP OF CONC. PLANK EL.=2.46' 2. TOP OF STR. STEEL EL= (6"BELOW TOP OF SLAB U.O.N.)
T ' - r I ,l!il;llllllllllllW!IIRllllllililii.i.lllUB!
LOADING SCHEDULE
6" SOLID PLANK 75 PSF
STR. STEEL 8 PSF MECHANICAL 2 PSF LIVE LOADS 100 PSF
-
TOTAL 185 PSF
-< ,-'Ft -_ --
262 Greenwich Avenue Suite A Goshen, New York 10924 845.294.0606 www.pietrzakpfau.com
Wexler Associates Structural Engineers
12 West 32nd Street 8th Floor New York, New York 10001 212.643.1500 www.nwexler.com
Gonsuli,ng Eng1neer':t PC
FALLSBURG SUBMISSION
Issue:
DOB STAMP:
PROJECT:
PRIVATE RESIDENCE
ADDRESS:
7 Penn Plaza Suite 702 New York, New York 10001 212.967.8944 www.twigcon.com
09.20.17
Date:
TOWN OF FALLSBURG SULLIVAN COUNTY, NY
FIRST FLOOR FRAMING PLAN
Project No: 171042
Scale:
Date: 9.20.2017
Drawn By; RS/CS
Approved By: DI
S-101.00 P~nted on 9.20.2017
' ' ' !
,i ' _; ;
' )
\ ' I
' I
' !
'
[! I
' _! 1 ' l
I ' !
J . . ' ' . -· l
i ' ' '
ii • .i i
' l
1 ' '
' lj 1 • ! j
j ' . ' . ' '
.. . ' I l: ·' . -· \ ' ,
I j '
I ,, • i \ ' ,
I I
'
' ' ' '
·:•1 J . ' • I ' )
! ; '
DAN IONESCU I ARCHITECTS
SPRINKLER HEAD LOCATIONS SPRINKLER DEMOLITION NOTES TOWN OF FALLSBURG DOB SPRINKLER NOTES TOWN OF FALLSBURG DOB STANDPIPE NOTES SPRINKLER LEGEND 253 Fifth Avenue
1. GENERAL • NEW SIDEWALL SPRINKLER HEAD New York, New York 10016 AREAS WITH SUSPENDED CEILINGS • 1. THE INSTALLATION COMPONENT, SIZING, SPACING, CLEARANCES, 1. THE COMPLETE STANDPIPE SYSTEM COMPl YWITH THE FULL REQUIREMENTS OF N.Y.C.
RECESSED PENDENT - RELIABLE MODEL G4A 'QUICK RESPONSE A. PRIOR TO PROPOSAL SUBMISSION, THIS CONTRACTOR SHALL VISIT POSITION AND TYPE OF SYSTEMS SHALL CONFORM TO APPENDIX Q BUILDING CODE SEC. 905, APPENDIX Q AND NFPA 14-2007. 212.253.5577
CONCEALED AUTOMATIC SPRINKLER, 1/2" ORIFICE. 5.6 K FACTOR. THE SITE TO REVIEW THE EXISTING CONDITIONS ASSOCIATED WITH SECTION BC Q102 AND SECTION BC 903.
~ EXISTING SIDEWALL SPRINKLER HEAD
TOWN OF FALLSBURG MEA NUMBER 258-93-E THE SCOPE OF WORK AND ADJACENT AREAS TO ASCERTAIN THE 2. STANDPIPE SYSTEM COMPONENTS AND HARDWARE SHALL BE IN ACCORDANCE WITH CHAPTER www.diarch.net DIFFICULTIES WHICH WILL AFFECT THE EXECUTION OF THE WORK 2. ONLY APPROVED MATERIALS SHALL BE USED AS PER CHAPTER 6 OF 4 OF NFPA 14-2007 AND APPENDIX Q OF TOWN OF FALLSBURG BUILDING CODE. 0 NEW UPRIGHT HEAD
AREAS WITH NO SUSPENDED CEILINGS • OF THIS CONTRACT. APPENDIX Q SECTION BC 0102.
STANDARD UPRIGHT· RELIABLE MODEL GFR 'QUICK RESPONSE', B. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE 3. THE LOCATION OF FIRE DEPARTMENT HOSE CONNECTIONS SHALL BE APPROVED BY THE FIRE OH NEW UPRIGHT HEAD, RATED AT 212°F
3. DIRECT CONNECTION OF SPRINKLERS TO THE PUBLIC WATER SYSTEM AUTOMATIC SPRINKLER, 1/2" ORIFICE, 5.6 K FACTOR, TOWN OF THAT THE ABOVE SITE EXAMINATION HAS BEEN MADE AND LATER
COMMISSIONER PER SEC 905.1 OF TOWN OF FALLSBURG BUILDING CODE. SHALL CONFORM TO SECTION BCQ 102.1 SEE CHAP 23.1.1.
FALLSBURG MEA NUMBER 258-93-E CLAIMS WILL NOT BE RECOGNIZED FOR EXTRA LABOR, EQUIPMENT " EXISTING HEAD TO BE REMOVED AND CAPPED 4. STANDPIPE SYSTEMS IN BUILDINGS USE FOR HIGH-PILED COMBUSTIBLE STORAGE SHALL BE IN R
OR MATERIALS REQUIRED BECAUSE OF DIFFICULTIES 4. SPRINKLER SHALL BE PROTECTED AGAINST FREEZING AND INJURY AS ACCORDANCE WITH THE TOWN OF FALLSBURG FIRE CODE SPRINKLER DESIGN CRITERIA ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD SUCH PER APPENDIX Q BC 0102. SEC. 8.15.3 AND 6.2.8. •e NEW CONCEALED PENDENT SPRINKLER HEAD-PREACTION
AN EXAMINATION BEEN MADE. 5. INSTALLATION OF STANDPIPE SYSTEMS SHALL COMPLY WITH niE SPECIAL INSPECTION *PIETRZAK & PFAU BUILDING IS CLASSIFIED IN 'E' OCCUPANCY GROUP (LIGHT HAZARD) WITH INCIDENTAL STORAGE SPACES AND MECHANICAL 5. INSPECTIONS AND TESTS OF SPRINKLERS SHALL BE CONDUCTED AS REQUIREMENTS OF CHAPTER 17 OF TOWN OF FALLSBURG BUILDING CODE. • NEW CONCEALED PENDENT SPRINKLER HEAD
SPACES (CLASSIFIED AS ORDINARY HAZARD GROUP 1). THERE ARE NO AREAS CLASSIFIED AS 'EXTRA HAZARD' c. DEMOLITION WORK SHALL INCLUDE ALL MATERIALS, LABOR, PER SEC. 901.5AND APPENDIX Q SEC. BCQ102. CH. 16. ENGINEER/NC & SURVEYINC,Puc EXTENSIONS, CONNECTIONS, CUTTING, REPAIRING, ADAPTING AND 6. CONSTRUCTION DOCUMENTS FOR STANDPIPE SYSTEMS SHALL CONTAIN PLANS THAT INCLUDE EXISTING PENDENT SPRINKLER HEAD OniER FIRE PROTECTION WORK REQUIRED TO MAINTAIN SERVICE
@
6. THE OCCUPANCY OF THE AREAS TO BE SPRINKLERED IN ACCORDANCE THE INFORMATION ANO DATA LISTED IN SEC. 905.1.1 OF TOWN OF FALLSBURG BUILDING CODE. LIGHT HAZARD OCCUPANCY(OFFICE AREAS, TOILET ROOMS LOBBY AREAS)) PENDING THE COMPLETION OF THE PERMANENT WORK. Wini SECTIONS 5.2 AND A.5.2 OF APPENDIX Q SECTION BCQ102. 262 Greenwich Avenue AREA OF APPLICATION: 1500 SQ. FT. (REMOTE AREA) COORDINATE THE EXTENT OF DEMOLITION WORK WITH THE 7. ANY SPACE OR ROOM THAT CONTAINS EQUIPMENT OF SUCH NATURE THAT THE USE OF WATER @.) SMOKE DETECTOR
MAXIMUM COVERAGE PER SPRINKLER: 225 SQ. FT. ARCHITECT AND BUILDING MANAGEMENT. 7. WATER SUPPLY TEST PIPES AND GAUGES SHAU BE PROVIDED AS PER WOULD BE INEFFECTIVE IN FIGHTING A FIRE THEREIN OR WOULD BE OTHERWISE HAZARDOUS, Suite A DESIGN DENSITY: 0.10 GPM PER SQUARE FOOT
2. SCOPE OF WORK SECTION 8.16.1 AND 8.16.4 OF APPENDIX Q SECTION BC 0102. SHALL HAVE A CONSPICUOUS SIGN ON EACH DOOR OPENING ON SUCH SPACE OR ROOM ® HEAT DETECTOR Goshen, New York 10924 SPACING BETWEEN SPRINKLERS: 15'--0w MAXIMUM STATING THE NATURE OF THE USE AND THE WARNING: "IN CASE OF FIRE, USE NO WATER." DISTANCE BETWEEN SPRINKLERS & WALL~!2 OF ALLOWABLE DISTANCE BETWEEN SPRINKLERS A. ALL EXISTING WORK REQUIRED TO REMAIN BUT INTERFERING WITH B. PIPING, FITTING, SPECIFICATIONS, PIPE SCHEDULES, SYSTEM TEST
~ 845.294.0606 PIPES, PROTECTION AGAINST CORROSION, DAMAGE, VALVES, 8. STANDPIPE SYSTEMS SHALL BE INSTALLED WHERE REQUIRED BY SECTION 905.3.1 THROUGH
SPRINKLER PREACTION VALVE PROPOSED NEW FIRE PROTECTION (AS WELL AS ELECTRICAL, MECHANICAL AND GENERAL CONSTRUCTION WORK) SHALL BE HANGERS. SPRINKLER GUARDS AND SHIELDS SHALL BE AS PER 905.3.6AND IN THE LOCATIONS INDICATED IN SECTIONS 905.4, 905.5 AND 905.6. www.pietrzakpfau.com
ORDINARY HAZARD _iQROUP 11_ OCCUPANC'y(STORAGE ROOMS, MECHANICAL & ELECTRICAL EQUIPMENT SPACES) RELOCATED AND RECONNECTED USING MATERIALS CONFORMING APPENDIX Q SECTION BC Q102, CHAPTERS 6 AND 9. @ SPRINKLER DELUGE VALVE
AREA OF APPLICATION: 1500 SQ. FT. (REMOTE AREA) TO STANDARDS OF THIS CONTRACT. 9. STANDPIPE SYSTEMS ARE PERMITTED TO BE COMBINED WlTH AUTOMATIC SPRINKLER
* MAXIMUM COVERAGE PER SPRINKLER: 130 SQ. FT. 9. STOCK OF EXTRA SPRINKLERS SHALL BE FURNISHED AS PER SECTION SYSTEMS. sec. 905.3 OF TOWN OF FALLSBURG BUILDING CODE. SPRINKLER DRY PIPE VALVE
DESIGN DENSITY: 0.15 GPM PER SQUARE FOOT B. REMOVE ALL SPRINKLER HEADS, PIPING, VALVING AND HANGERS 6.2.9 APPENDIX Q SECTION BC Q102 (REQUIRED FOR EACH
SPACING BETWEEN SPRINKLERS: 15'-0w MAXIMUM ASSOCIATED WITH PIPING TO BE REMOVED BACK TO MAINS. TEMPERATURE RATING). 10. THE LOCATION OF CLASS I STANDPIPE HOSE CONNECTION SHALL COMPLY WITH SEC. 905.4 OF [0 MANUAL PULL STATION
DISTANCE BETWEEN SPRINKLERS & WALLSJ'2 OF ALLOWABLE DISTANCE BETWEEN SPRINKLERS IDENTIFY ALL PIPING BY SERVICE TYPE ANO CAP AT MAINS. TOWN Of FALLSBURG BUILDING CODE.
Wexler Associates 10. SPRINKLER ALARM WILL BE IN ACCORDANCE WITH SECTION 8.16.1 OF
c. REMOVE EXISTING SPRINKLER WORK AS INDICATED BELOW: APPENDIX Q SECTION BC 0102. 11. WHERE THE MOST REMOTE PORTION OF A FLOOR OR STORY IS MORE THAN 150 FEET FROM A 1h] MANUAL ABORT STATION
SPACING, LOCATION AND POSITION OF SPRINKLER WILL BE AS PER HOSE CONNECTION, ADDITIONAL HOSE CONNECTIONS SHALL BE PROVIDED IN APPROVED 0 F!RE HOSE CABINET Structural Engineers
REMOVE ALL EXISTING SPRINKLER WORK BACK TO RISER AND 11. LOCATIONS, SEC. 905.4. a. CAP. OR AS NOTED ON DRAWINGS.
SECTION 8 OF APPENDIX Q SECTION BCQ102.
b. CONTRACTOR TO CONTACT BUILDING MANAGEMENT AND 12. CLASS I MANUAL DRY STANDPIPES ARE ALLOWED IN OPEN PARKING GARAGE, SHALL BE <mm FIRE HOSE RACK 12 West 32nd Street 12. ALL BLIND SPACES EXCEEDING 6" IN WIDTH OR DEPTH WHICH CONTAIN PROVIDED THAT THE HOSE CONNECTIONS ARE LOCATED AS REQUIRED FOR CLASS II TENANT REGARDING REMOVAL SCOPE OF WORK TO MAINTAIN
CONTINUITY OF ALL SERVICES TO ALL TENANTS WHO ARE TO COMBUSTIBLE MATERIAL WILL BE SPRINKLERED. STANDPIPES IN ACCORDANCE WITH SEC. 905.5. 8th Floor
omm, FIRE HOSE RACK/SPRINKLER REMAIN OPERATIONAL AND NOT BE AFFECTED BY DEMOLITION New York, New York 10001 WORK.
13. ALL PIPING PASSING THROUGH WALLS WIU COMPLY WITH SECTION 13. STANDPIPE OUTLETS MAY BE OMITTED IN PORTIONS OF FIRST FLOORS OR BASEMENTS THAT -<:: ALL EXISTING BUILDING SPRINKLER VALVES SHALL REMAIN. BC712. ARE COMPLETELY SEPARATED FROM THE ENTRANCE HALL OR ENCLOSED STAIRWAYS LEADING
SIAMESE CONNECTION C, 212.643.1500 TO THE UPPER FLOORS, PROVIDED THAT POTABLE FIRE EXTINGUISHERS ARE INSTALLED,
D. PROVIDE ADDITIONAL SUPPORT FOR ALL EXISTING PIPING TO 14. THERE IS NO HIGH PILED STORAGE AS DEFINED IN SECTION 3-3.12 OF SUBJECT TO THE APPROVAL OF THE FIRE COMMISSIONER, SEC. 905.3.1. E-] SPRINKLER PLUG www.nwexler.com REMAIN WHICH ARE AFFECTED BY DEMOLITION OF EXISTING APPENDIX Q SECTION BC Q102.
CEILING AND PARTITIONS. 14. STAGES GREATER THAN 1,000 SQUARE FEET IN AREA SHALL BE EQUIPPED WITH A CLASS 111 WET = FLOOR CONTROL VALVE ASSEMBLY {FCVA) 15. DIST ANGE OF SPRINKLERS FROM HEAT SOURCE SHALL BE AS PER STANDPIPE SYSTEM WITH 1.5-INCH AND 2.5-INCH (38 mm AND 64 mm) HOSE CONNECTIONS ON
E. ALL MATERIALS AND EQUIPMENT SHALL BE DISPOSED OF IN TABLES 9.3.2.5 (a) AND 8.3.2.5 (b). EACH SIDE OF THE STAGE. ~ ACCORDANCE WITH APPLICABLE LAWS AND ENVIRONMENTAL VALVE TAMPER SWITCH
REGULATIONS. 16. AS PER SECTION BC903.12 PROVIDE DEPARTMENT OF WATER SUPPLY 15. UNDERGROUND BUILDINGS SHALL BE EQUIPPED niROUGHOUT WITH A CLASS I AUTOMATIC
T,~~I LETTER WITH FLOW TEST DATA IF THERE IS A DIRECT CONNECTION TO WET OR MANUAL WET. •,, FIRE EXTINGUISHER G F. COORDINATE WITH OWNER TO DETERMINE WHETHER EQUIPMENT THE STREET WATER SUPPLY.
IS TO BE TURNED OVER FOR FUTURE USE AND STORED IN THEIR 16. CLASS I STANDPIPE HOSE CONNECTIONS SHALL BE PROVIDED IN ALL LOCATIONS PER SEC. [J<J PREACTION TROUBLE HORN ASSOCIATED STORAGE LOCATIONS. 17. ALL PIPES PASSING THROUGH FOUNDATION WALLS SHALL BE 905.4 OF TOWN OF FALLSBURG BUILDING CODE. Const!l!;ng Engineers. PC
PROTECTED AS PROVIDED BY SECTION 305.5 OF THE PLUMBING CODE. [P PREACTION 6" BELL FOR SUPERVISION G. WHEN EXISTING SPRINKLER SYSTEM !S DEACTIVATED THIS 17. WHERE niE ROOF HAS A SLOPE OF LESS THAN 4 IN 12, EACH STANDPIPE SHALL BE PROVIDED
~-0 CONTRACTOR TO PROVIDE A TEMPORARY SPRINKLER LOOP 18. THIS APPLICATION IS NOT FILED AS A RESULT OF BY THE FIRE WITH A HOSE CONNECTION LOCATED EITHER ON THE ROOF OR AT THE HIGHEST LANDING OF 0) ~~ ~
111 WEST 33RD STREET AROUND THE CORE OR PROVIDE A 24 HOUR FIRE-WATCH UNTIL COMMISSIONER AS AUTHORIZED BY BS&A TO MODIFY THE CERTIFICATE
PREACTION 10w BELi/STROBE ALARM STAIRWAYS WITH STAIR ACCESS TO THE ROOF. AN ADDITIONAL. HOSE CONNECTION SHALL BE 18TH FLOOR
NEW SPRINKLER SYSTEM BECOMES ACTIVE. INCLUDE ALL IN BID OF OCCUPANCY NOR JS SUCH ACTION PENDING. PROVIDED AT THE TOP OF THE MOST HYDRAULICALLY REMOTE STANDPIPE FOR TESTING * -~'" 1r' PRICE. PURPOSE. SPRINKLER LINE REPRESENTATION New York, New York 10001 19. ALL VALVES SHALL BE IDENTIFIED AS REQUIRED BY SECTION 6-7.4 OF
~ APPENDIX Q SECTION BC 0102. 18. PROTECTION OF RISERS AND LATERALS OF CLASS I STANDPIPE SYSTEM SHALL COMPLY WITH 212.967.8944 SPRINKLER NOTES SEC. 905.4.1 OF TOWN OF FALLSBURG BUILDING CODE. NEW SPRINKLER PIPING
~ . ~· !· •' K'.~ .... < 20. DRAINAGE SHALL CONFORM TO SECTION 8.15.2 OF APPENDIX Q I,,, •: ·- ., .._ www.twigcon.com 1. THIS CONTRACTOR SHALL PROVIDE FIRE PROTECTION THROUGHOUT SECTION BC 0102. EXISTING SPRINKLER PIPING
,.t "'' ~-."'.:;·,;,>_,::,-,,.,,.. (::/
19. Cl.ASS II STANDPIPE HOSE CONNECTIONS SHALL BE ACCESSIBLE AND LOCATED SO THAT ALL u" - ~
THE ENTIRE SPACE WITHIN THE SCOPE OF WORK AS REQUIRED BY THE PORTIONS OF THE BUILDING ARE WITHIN 30 FEET (9144 mm) OF A NOZZLE ATIACHED TO 100 <'o 0975GS ((;
LOCAL CODES, LOCAL FIRE DEPARTMENT REGULATIONS, BUILDING 21. A ONE PIECE REDUCING FITTING OF GOOD DESIGN SHOULD BE USED EXISTING SPRINKLER PIPING TO BE REMOVE AND DISCARDED /0 i,.'v FEET (30480 mm) OF HOSE. f?o,'":'~-c:c..·OV-
MANAGEMENT REQUIREMENTS AND NFPA 13 FOR THE DURATION OF WHEREVER A CHANGE IS MADE IN THE SIZE OF PIPE, AS PER SECTION ' -~~\
THE PROJECT. ANY TEMPORARY FIRE PROTECTION SHALL BE 6.4.6 OF APPENDIX Q SECTION BCQ102. IN FUU Y SPRINKLERED BUILDINGS HAVING A COMBINED STANDPIPE SYSTEM THAT IS REMOVE EXISTING SPRINKLER HEAD AND
20. ASSOCIATED DROP NIPPLES BACK TO HORIZONTAL REMOVED UPON ACTIVATION OF PERMANENT FIRE PROTECTION HYDRAULICALLY CALCULATED. THE MINIMUM STANDPIPE SIZE IN BUILDINGS WITH FLOOR PIPING AND EXTEND NEW PIPING TO NEW HEAD SYSTEM. 22. ALL VALVES ON CONNECTIONS TO WATER SUPPLY TO SPRINKLER HEIGHTS LESS THAN 150 FT. ABOVE THE LOWEST LEVEL OF FIRE DEPAR™ENT VEHICLE
SHALL BE APPROVED OS&Y OR APPROVED INDICATOR TYPE. ACCESS SHALL BE 4 IN. SEC. 7.6.3 OF APPENDIX 0. LOCATION AS REQUIRED.
2. SPRINKLER HEADS SHALL BE ±i" FROM CENTER OF TILE, CONTRACTOR SPRINKLER DRAWING NOTATIONS SHALL ALLOW FOR ALL REQUIRED FITTINGS TO ACHIEVE THIS AND 23. DRAIN VALVES AND TEST VALVES SHALL BE APPROVED TYPE AS PER 21. CLASS Ill STANDPIPE SYSTEMS SHALL HAVE HOSE CONNECTIONS LOCATED AS REQUIRED FOR INCLUDE THIS IN THEIR CONTRACT PRICE. SECTION 6.7.3 OF APPENDIX Q SECTION BC Q102. CLASS I STANDPIPES IN SEC. 905.4 ANO SHALL HAVE CLASS II HOSE CONNECTIONS AS
HANGERS SHOULD BE SUPPORTED BY WROUGHT IRON U TYPE OR REQUIRED IN SEC. 905.5. ® DRAWING NOTE TAG
3. CONTRACTOR SHALL COORDINATE ALL NEW WORK WITH NEW WORK OF 24. OTHER TRADES AND EXISTING CONDITIONS. APPROVED ADJUSTABLE HANGERS. HANGERS SHALL BE OF THE TYPE 22. CABINETS CONTAINING FIRE·FIGHT!NG EQUIPMENT SUCH AS STANDPIPES, FIRE HOSES, FIRE
APPROVED FOR USE WITH THE PIPE OR TUBE INVOLVED, AS PER EXTINGUISHERS OR FIRE DEPARTMENT VALVES SHALL NOT BE BLOCKED FROM USE OR 4 4. MINIMUM PIPE SIZE TO ANY SPRINKLER HEAD SHALL BE 1 INCH. CHAPTER 9 OF APPENDIX Q SECTION BC 0102. OBSCURED FROM VIEW. SECTION DESIGNATION ON DRAWING WHERE SECTION IS CUT A-SECTION DESIGNATION
5. SPRINKLER PIPE SIZES SHOWN ARE FOR COST ESTIMATING ONLY, AND 25. PROVISIONS SHALL BE MADE TO FACILITATE FLUSHING SYSTEM PIPING 23. STANDPIPE SYSTEMS ARE REQUIRED DURING CONSTRUCTION, ALTERATION AND DEMOLITION B-DRAWING NO.
FOR FILING Wini THE BUILDING DEPARTMENT. THIS CONTRACTOR IS TO BY PROVIDING FLUSHING CONNECTION CONSISTING OF A CAPPED OPERATIONS SHALL BE PROVIDED IN ACCORDANCE WITH SEC. 3303.8 OF TOWN OF FALLSBURG BUILDI G CODE. PROVIDE THEIR OWN HYDRAULIC CALCULATIONS TO VERIFY PIPE NIPPLE4" LONG ON END OF A CROSS MAIN AS PER SECTION 9.14.160F ee SIZING AND INCLUDE ANY INCREASED/DECREASED PIPE SIZING WITHIN APPENDIX Q SECTION BCQ102. 24. CLASS II STANDPIPE SYSTEMS ARE PERMITTED FOR HIGH PILE AND RACK STORAGE
SPRINKLER RISER DESIGNATION
THEIR CONTRACT PRICE, OCCUPANCIES ONLY. SEC. 3.3.27.2 OF APPENDIX Q. 26. SPRINKLER SHALL BE AN APPROVED 1YPE AS PER SECTION 8.3 OF
fil TOWN OF FALLSBURG ADDITIONAL SPRINKLER APPENDIX Q SECTION BC 0102. 25. FITTINGS SHALL BE EXTRA-HEAVY PATTERN WHERE PRESSURES EXCEED 175 PSI (12.1 BAR). REVISION SYMBOL
SEC. 4.3.3 OF NFPA 14-2007. NOTES: MODIFICATION OF AN EXISTING SYSTEM 27. TEMPERATURE RATING SHAU COMPLY WITH SECTION 8.3 OF APPENDIX
Q SECTION BC Q102. 26. PROTECTION OF STANDPIPE SYSTEM WHERE A STANDPIPE OR LATERAL PIPE THAT IS ~ POINT OF NEW CONNECTION TO EXISTING WORK
REFERENCES: BUILDING CODE, 2014 EDITION AND NFPA.13-2007 AS NORMALLY FILLED WITH WATER PASSES THROUGH AN AREA SUBJECT TO FREEZING MODIFIED BY THE TOWN OF FALLSBURG BUILDING CODE 28. 18" MINIMUM CLEARANCE TO BELOW SPRINKLER DEFLECTOR AS PER TEMPERATURES ff SHALL BE PROTECTED TO MAINTAIN THE TEMPERATURE OF THE WATER IN FALLSBURG SUBMISSION 09.20.17 SEC 903 AND APPENDIX Q. SECTION 8.5.6 OF APPENDIX Q SECTION BC 0102. THE PIPING BETvVEEN 40 F AND 120 F (4.4 C AND 48.9 C). SEC. 6.1.2.3 OF NFPA 14-2007. SPRINKLER ABBREVIATIONS
1. SPRINKLER HEAD ORIFICE SIZES, TYPE. AND DEFLECTOR POSITIONS 29. SPACING AND LOCATION OF SPRINKLERS SHALL COMPLY WITH FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED NOT LESS THAN 18 lN. NOR MORE THAN FOR MODIFICATIONS OF AN EXISTING SYSTEM SHALL REMAIN THE 27. AFF ABOVE FINISHED FLOOR Issue: Date: CHAPTER 8 OF APPENDIX Q SECTION BCQ102. 36 IN. ABOVE THE LEVEL OF THE ADJOINING GROUND, SIDEWALK OR GRADE SURFACE. SEC. SAME. 6.3.6 OF NFPA 14-2007. FHR FIRE HOSE RACK
30. SPRINKLER SYSTEM COMPLIES WITH NFPA 13-2002 AS MODIFIED BY DOB STAMP: 2. SPRINKLER MODIFICATIONS SHALL NOT ALTER THE TYPE OF SPRINKLER APPENDIX Q SECTION BCQ102. SYSTEM. 28. THE MAXIMUM PRESSURE AT ANY POINT IN THE SYSTEM AT ANY TIME SHAU NOT EXCEED 350 FSC FIRE HOSE CABINET
31. SOURCES OF WATER SUPPLY FOR SPRINKLER SYSTEMS AS PER PSI (24.1 BAR). SEC. 7.2 OF NFPA 14-2007.
3. SPRINKLER PIPING RELOCATION SHALL NOT AFFECT THE OPERATION CHAPTER 23 OF APPENDIX Q SECTION BC 0102. FSP FIRE STANDPIPE
OF THE SPRINKLER SYSTEM. 29. BRANCH LINE SHALL BE SIZED BASED ON THE HYDRAULIC CRITERIA ESTABLISHED IN SEC. 7.8 & 7.10 BUT NOT LESS THAN 144" IN. (65 mm). SEC. 7.6.4 OF NFPA 14-2007. TS TAMPER SWITCH
THE HAZARD OCCUPANCY FOR THIS SPRINKLER SYSTEM UNDER THIS 32. PIPE SCHEDULE SYSTEMS SHALL BE IN ACCORDANCE WITH SECTION
4. 14.5 OF APPENDIX Q SECTION BC 0102. HYDRAULICALLY DESIGNED STANDPIPE SYSTEMS SHALL BE DESIGNED TO PROVIDE THE WATER APPLICATION SHALL REMAIN THE SAME.
30. WF WATERFLOW SWITCH
33. AUTOMATIC INTERLOCK CUTOFF SWITCH FOR VENTILATION WILL FLOW RATE AT A MINIMUM RESIDUAL PRESSURE OF 65 PSI (4.5 BAR) AT THE OUTLET OF niE
5. SPRINKLER MODIFICATIONS SHALL NOT AFFECT THE HYDRAULICALLY CONFORM TO CHAPTER 6 OF THE MECHANICAL CODE (APPLICABLE HYDRAULICALLY MOST REMOTE 144 IN. (65 mm} & 144 IN. (38 mm) HOSE CONNECTION. SEC. 7.8.1.1
DESIGNED AREA OF APPLICATION OF THE FLOOR. ONLY IF THERE IS AN AIR SYSTEM UTILIZING RECIRCULATED AIR AND OF OF NFPA 14-2007.
SPECIAL INSPECTIONS· TOWN OF FALLSBURG REQUIRING A THERMOSTATIC DEVICE). 31. HOSE CONNECTIONS ANO HOSE STATIONS SHALL BE UNOBSTRUCTED AND SHALL BE LOCATED NOT LESS THAN 3 FT. (0.9M) OR MORE THAN 5FT. (1.5 m) ABOVE THE FLOOR. SEC. 7.3.1 OF NFPA SPRINKLER DRAWING LIST
34. HYDRAULICALLY DESIGNED SPRINKLER SYSTEMS SHALL BE IN 14-2007. ACCORDANCE WITH CHAPTER 14 OF APPENDIX Q SECTION BCQ102.
SPRINKLER SYSTEM 32. AT THE TOP OF THE HIGHEST RISER THERE SHALL BE PROVIDED ABOVE THE MAIN ROOF LEVEL SHEET# DWG# DESCRIPTION
1. NEW AND ALTERED SPRINKLER SYSTEMS SHALL BE INSPECTED IN 35. MINIMUM BRANCH PIPE SIZE TO BE ONE INCH W). A THREE WAY MANIFOLD EQUIPPED WITH THREE 144 IN. HOSE VALVE WITH HOSE VALVE CAPS. ACCORDANCE WITH TOWN OF FALLSBURG BUILDING CODE SECTION SEC. 7.3.2.2 OF APPENDIX Q. 1 SP.101.GO CELLAR - ROOF: SPRINKt.ER SYMBOLS & NOTE$
903. THIS CONTRACTOR OR PERMIT HOLDER FOR THE SPRINKLER 36. THIS APPLICATION IS MADE ONLY FOR WORK INDICATED ON THE
WORK SHALL PERFORM ALL REQUIRED ACCEPTANCE TESTS, COMPLETE SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN ARE NOT TO BE 33. WHERE THE RESIDUAL PRESSURE AT A 144 IN. (40 mm) OUTLET ON A HOSE CONNECTION SP-2111.GO CELLAR - ROOf: SP1'8NKLER SPECIFICATIONS I RELIED UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OR 2
AND SIGN THE APPROPRIATE CONTRACTOR'S MATERIAL AND TEST EXCEED 100 PSI (6.9 BAR), AN APPROVED PRESSURE RESTRICTED DEVICE SHALL BE PROVIDED. CERTIFICATES. THE SPECIAL INSPECTOR SHALL WITNESS ALL IN ACCORDANCE WITH APPLICABLE CODES. SEC. 7.8.3.1 OF NFPA 14-2007. REQUIRED TESTS AND SHALL VERIFY THAT ALL INSTALLATIONS OF ALL 3 SP-2112.00 CELLAR• ROOF: SPRINKLER SPECIRCATION$ II
MATERIALS, FITTINGS, HANGERS, ASSEMBLIES AND SIGNAGE ARE IN 34. FOR CLASS I AND CLASS tu SYSTEMS THE MINIMUM FLOW RATE FOR THE HYDRAULICALLY PROJECT:
ACCORDANCE WITH THE APPROVED CONSTRUCTIONS DOCUMENTS MOST REMOTE STANDPIPE SHALL BE 500 GPM (1893 UMIN) SEC. 7.10.1.1.1 OF NFPA 14-2007. 4 SP-301.DO Cl:LI.AR : Sl'fi:INKLER Pl.AN & NOTES PRIVATE RESIDENCE AND THE CONTRACTOR HAS TRANSMITTED REQUIRED MAINTENANCE LITERATURE AND INSTRUCTIONS TO THE OWNER. THE SPECIAL 35. WHERE A HORIZONTAL STANDPIPE ON A CLASS I AND CLASS Ill SYSTEM SUPPLIES THREE OR
5 INSPECTOR SHALL VERIFY THE MATERIAL AND TEST CERTIFICATION MORE HOSE CONNECTIONS ON ANY FLOOR, THE MINIMUM FLOW RATE FOR THE
SP-302.DO 1ST FLOOR: SPRINKLER PLAN & NOTES
FORMS HAVE BEEN TRANSMITTED TO THE FIRE DEPARTMENT AND THE HYDRAULICALLY MOST DEMANDING HORIZONTAL STANDPIPE SHALL BE 750 GPM (2840 UMIN). ADDRESS: DEPARTMENT OF BUILDINGS. SEC. 7.10.1.1.2 OF NFPA 14-2007. 6 SP-303.00 2ND FLOOR: SPRINKLER PLAN II NOTES
2. THE SPECIAL INSPECTOR SHALL BE HIRED DIRECTLY BY THE OWNER OR 36. THE MINIMUM FLOW RATE FOR ADDITIONAL STANDPIPES SHALL BE 250 GPM PER STANDPIPE 7 SP..f01.00 CELLAR •ROOF: SPRINKLER DETAILS TOWN OF FALLSBURG THE GENERAL CONTRACTOR. COST FOR THE SPECIAL INSPECTOR WITH THE TOTAL NOT TO EXCEED 1250 GPM OR 1000 GPM FOR BUILDINGS SPRINKLERED
SULLIVAN COUNTY, NY SHALL BE INCLUDED AS PART OF THE SPRINKLER CONTRACTORS THROUGHOUT. SEC. 7.10.1.1.3 OF NFPA 14-2007. OVERALL BID AND BE BROKEN OUT SO THE OWNER AND OR GENERAL CONTRACTOR CAN HIRE THE SPECIAL INSPECTOR DIRECTLY WITH THE 37. CLASS I AND CLASS Ill STANDPIPES IN BUILDINGS WITH FLOOR HEIGHTS LESS THAN 150 FT.
FUNDS PROVIDED UNDER THE SPRINKLER CONTRACTORS BID. ABOVE GRADE PLANE SHALL BE AT LEAST 4 INCHES IN SIZE. STANDPIPES IN BUILDINGS WITH FLOOR HEIGHTS GREATER THAN 150 FT ABOVE GRADE PLANE SHALL BE NO LESS THAN 6 1ST FLOOR-ROOF STANDPIPE SYSTEM INCHES IN DIAMETER. SEC. 7 .6.1 OF APPENDIX Q.
1. NEW AND AL TE RED STANDPIPE SYSTEMS SHALL BE INSPECTED IN SPRINKLER ACCORDANCE WITH TOWN OF FALLSBURG BUILDING CODE SECTION 38. VALVES CONTROLLING WATER SUPPLIES SHALL BE SUPERVISED IN THE OPEN POSITION SO
905. TH1S CONTRACTOR OR PERMIT HOLDER FOR THE STANDPIPE THAT A CHANGE IN THE NORMAL POSITION OF THE VALVE WILL GENERATE A SUPERVISORY SYMBOLS & NOTES WORK SHALL PERFORM ALL REQUIRED ACCEPTANCE TESTS, COMPLETE SIGNAL AT THE SUPERVISING STATION REQUIRED BY SECTION 903.4. WHERE A FIRE ALARM
AND SIGN THE APPROPRIATE CONTRACTOR'S MATERIAL ANO TEST SYSTEM IS PROVIDED, A SIGNAL SHALL ALSO BE TRANSMITTED TO TI-IE CONTROL UNIT.
CERTIFICATES. THE SPECIAL INSPECTOR SHALL WITNESS ALL REQUIRED TESTS AND SHALL VERIFY THAT ALL INSTAUATIONS OF ALL 39. INSTALLATION OF STANDPIPE SYSTEMS SHALL COMPLY WITH THE
MATERIALS, FITIINGS, HANGERS, ASSEMBLIES AND SIGNAGE ARE 1N SPECIAL INSPECTION REQUIREMENTS OF CHAPTER 17 OF TOWN OF FALLSBURG BUILDING Project No: 171042 ACCORDANCE WITH THE APPROVED CONSTRUCTIONS DOCUMENTS CODE.
AND THE CONTRACTOR HAS TRANSMITTED REQUIRED MAINTENANCE Scale: N.T.S. LITERATURE AND INSTRUCTIONS TO THE OWNER. THE SPECIAL 40. STANDPIPE SYSTEM SPECIAL INSPECTIONS SHALL BE PERFORMED IN
INSPECTOR SHALL VERIFY THE MATERIAL AND TEST CERTIFICATION ACCORDANCE WITH SECTION [BC 1704.22] OF THE 2014 TOWN OF FALLSBURG BUILDING
FORMS HAVE BEEN TRANSMITIEO TO THE FIRE DEPARTMENT AND THE CODE.
DEPARTMENT OF BUILDINGS. Date: 9.20.2017
2. THE SPECIAL INSPECTOR SHALL BE HIRED DIRECTLY BY THE OWNER OR Drawn By: RS/CS THE GENERAL CONTRACTOR. COST FOR THE SPECIAL INSPECTOR SHALL BE INCLUDED AS PART OF THE STANDPIPE CONTRACTORS OVERALL BID AND BE BROKEN OUT SO THE OWNER AND OR GENERAL Approved By: DI 34 OF 83 CONTRACTOR CAN HIRE THE SPECIAL INSPECTOR DIRECTI. Y WITH THE FUNDS PROVIDED UNDER THE STANDPIPE CONTRACTORS BID.
SP-101.00 Pnnted on El.20.2017
····• -r 1~1111 "
~ COMcheck Software Version 4.0. 7 .O
V 1 Mechanical Compliance Certificate
Project Information
Energy Code·
Project Title:
loC1:1tion:
Climate Zone:
ProjectType
Constn;ction Srte: FALLSBURG, NY
Additional Efficiency Package
2015 IECC
Wurtsboro. New York
6a New Construction
Owner/Agent: DAN 10NESCU ARCHITECTS 253 FIFTH AVENUE NEW YORK, NY 10016 212.253.5577
Designer/Contractor TWIG Consulting Engineers PC 111 WEST 33RD ST Suite 17-101 New York, NY 10001 +1212.967.8944
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting al!owanet:l calculations.
Mechanical Systems List
Quantity System Type & Description
1 CU·1 (Single Zone): VRF. Air Cooled Heat Pump Heai1ng Mode· Capacity::: 81 kBlulh,
No minimum efficiency requirement applies Cooling Mode: Capacity" 72 kBtulh,
No minimum efficiency requirement applies Fan System. None
CU-2 (Single Zone) VRF. Air Cooled Heat Pump He.:lting Mode: Capacity= 108 k811.1/h,
No minimum efficiency requirement applies Cooling Mode: Capacity "' 96 kBlu.lh,
No mirnmum efficiency requirement applies Fan System: None
1 CU-3 (S;ngle Zone).
VRF, Air Cool ad Heat Pump Healing Mod-8: Capacity"' 81 kBtu/h,
No mlrilmum efficiency requirement applies Cooling Mode: Capacity = 72 kBtufu,
No m1rnmum efficiency requirement applies Fan Systf.lm: None
Mechanical Compliance Statement Compliance Statement: The proposed mechanical design represented in this document JS consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 2015 IECC requirements ln COMcheck Version 4.0.7 .0 and to comply with any applicable mandatory requirements fisted 1n the Inspection Checklist
Name -Title Martin M. Montague
Signature M. Montaque 09.15.17
Date
Project Title: Report date: 09/15/17
Data filename: P:\T,W.I.G\TWIG CONSULT!NG\Projects\Dl-Architects\Thomas Education Center\EN\EN.cck Page
!,Sectlon,1 · , f - T . - '": .. ,: - ,',: !-~~~-:~:_;~J ·,Plumbln~Rough~lntnsp«cttdn I Compl~S?' '} - .. --- __ t:om~Um~idns "
1C404.5., Heated water supply piping conforms DComphes Requirement will be met. !C404.5.l, to pipe length and volume Dooes Not [C404.5.2 requiremf'nts. Refer to section details.. i [PL6P ONot Observable f 0Not Applicable ! ____________ - - -·-'"'"''""_,_ -- --.... -,_,_,.,,,,_,,. --------- -----jC404.5. · Heated water supply piping conforms !C404.5.l, , to pipe length and volume iC404.~:2 requirements. Refer to section details. ![PL6P
[., .... -)C404.5, fC404.5.l, fC4o4:5.2 t[PL6}1 I
Heated water supply piping conforms to pipe length and volume requirements. Refer to section details.
Ocomplies. Dooes Not
ONot Observable ONot Applicable
Ocomplies Dooes Not
ONot Observable DNot Applicable
Requirement wm be met.
Requirement will be met.
L-------·--- - ........................... ,., - ------------- -----------IC404.6.3 Pumps that circulate water between a Ocomplies 1[PL7P heater and storage tank have controls Dooes Not : that limit operation from startup to ONot Observable
Requirement will be met.
i <= 5 mmutes after end ot heating ONot Applicable ~----.._.;_, cycle ··---·-------··--,---·- ___________ _ iC404.6.3,, Pumps that circulate water between a ·OComplies Requirement will be met. i[PL7P ' heater and storage tank h.ave controls Dooes Not j that 1'1mit operation from startup to , <= 5 minutes after end of heating [ cycle.
ONot Observable 0Not Applicable
[C404.6.3- Pumps that circulate water between a ------~
Dcomplies DDoes Not j[PL7P heater and storage tank have controls
, that limit operation from startup to r <= 5 minutes after end of heating ONot Observable
DNot Applicable
Requirement will be met.
, . cycle. !(404,i .. -Wat~r distnbutio-;, system that pumps oc~-;:.;.;·;;1;·~~-.. - ·-·-"·'"'E~~;pt1;;~: Requirement does not apply. i[PLBP water from a heated-water supply Dooes Not ! pipe back to the heated-water source ONot Observable i ttirough a cold-water supp!y pfpe is a , demand iecirculation water system 0Not Applicable i Pumps within this system have
controls that start the pump upon receiving a signal from the action of a user of a fixture or appliance and limits the temperature of the water entering the cold·water piping to 104"F
iC404.7 !{PLB]3 I •
Water distribution system that pumps water frorn a heated·water supply pipe back to the heated-water source ttlrough a cold-water supply pipe is a demand recirculation water system. Pumps within this system have controls that start the pump upon
1 receiving a signal from ttie action of a 1,. user of a fixture or appliance and
limits the temperature of the water
bcOmP1ie~ Dooes Not
ONot Observable 0Not Applicable
Exception: Requirement does not apply.
I entering the rold-wate-r piping to
'- _____ , __ !9_4_"_!-'_ ., -------"'- - - -···· . ·-··"-----------· ""'- """'"""'"_,_ ------ --- ·--·
-----··
1 of 11
----~
Project Title: Report date: 09/15/17
Data filename: P·\T W.I.G\TWIG CONSULT1NG\Projects\DI-Architects\Thomas. Education Center\EN\EN.cck Page 4 of 11
'"'"'" ••......•... ··--······· -···-·--· ..
'
I I
I
,I\/. COMcheck Software Version 4.0. 7 .0
V 1 Inspection Checklist Energy Code: 2015 IECC
Requirements: 100.0% were addressed directly in the COMcheck software Text !n the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table Is provided.
r·:sw1on, , , ·, • .,, t~ ., ,, '·f,·,,,,,.,,, ,.,, . : . ,:,, ., .. ,. ,. '.I' ~&..!<J .. :,bl:_~·~-·. Pifti>M~,~.&::<" _li: ,~!!:::(::;:J:;2.:;;~~~:~~~~-=--~ :_ ~-~c103.2 ·Plans, specifications, and/or Ocomplies Requirement wm be met. 'i!PR2J1 calculations provide all information :DDoes Not , with which compliance can be
determined for the mechanical 'ONot Observable systems and equ1pment and 0Not Applicable document where exceptions to the
I, standard are claimed. load
calculations per acceptable
1 engineering standards and handbooks. 1 .....•.• , .. ,.,-·------··
!C406 Plans, specifications, and/or Ocompl!es --~~-···-~·-····-·
Requirement will be met, ---------------·--------
! [PR9jl calculations provide an information DDoes Not i wrth which compliance can be J · determined for the additional energy ,ONot ObSlc!rvabfe L ___ .•cff,=",'•,,"~'Y~P~"c'~·~·~·~o~p~tio~,~·~'----•~o_N_o_t_•_P_P_"_"_b_l• _____________________ _ Additional Comments/Assumptions:
~TloW ;m·pact ,Tier31 =...J. -- --- ---- --- - -- ..
Project Tltte: Report date: 09/15/17
Data filename: P:\T.W.f,G\TWIG CONSULT!NG\Projects\Dl·Architects\Thomas Education Center\EN\EN.cck Page 2 of 11
~-~~i~J p;~'.1:~~~~~~:ttt~r, t'.'.'.'.\'. ""'' = ~:. '."""· .,.·-···-.:.:,.:.: .. :;. __ " __ - ~-~-C404, 7 Water distribution system that pumps '0Complies Exception: Requirement does not apply.
l[PL8P water from a heated-water supply :00oes Not pipe back to the heated-water source through a cold-water supply pipe is a ONot Observable
, demand recirculation water system. ONot Applicable i Pumps within this system have I controls that start the pump upon 1 receiving a signal from the action of a ! user of a fixture or appliance and I limits the temperature of the water
· entering the cold·water p1p1ng to 104°F. L. __ _".e:'.'.,_~~---~~--------· --·---~~~-------------·,--~
Additional Comments/Assumptions:
!_~_[ Hi9h 1~pa':~ (Tie_r_ l!_ ~'J~f~~ium !mpa~!J!!~r 2) =-:::EfilLo~ lf!ipact (Tier 3) ________ .::.:=.:ccc.==.c:=== Project Title: Report date: 09/15/17
Data filename: P:\T.W.!.G\TWIG CONSULT!NG\Projects\Dl-Architects\Thomas Education Center\EN\EN.cck Page 5 of 11
' I ., .
·1
:
I
'
:1
' ' I
.
I I
j __ .....L...J.L.I._J...!..A_.:aJI.-----···----·~---, ... ,__. __ ,_-------··
:;£~"J __ ~~~-:~-~~-~-undation ~n~-pe~::_L __ ~~mp~1_ .. _, _LI____ _ __ c_omm_ ·-~-~~1.$::':~~~ .. C403.2.4. Snow/ice melting system sensors for Dcomp!ies Exception: Requirement does not apply. 5, future connection to controls. Freeze DDoes Not C403.2.4. protection systems heve automatic 6 controls installed. (F09)3
Additional Comments/Assumptions:
Project Title:
ONot Observable ONot Applicable
Data filename: P:\T.W.I.G\TWIG CONSULTING\Projects\D!-Architects\Thomas Education Center\EN\EN.cck
Reportdate: 09/15117
Page 3 of 11
.
.
•
.
' ··--·-·--·--· .. ----·-· '···---------·-----l
:;:;: l ... M.ech~~l.cai ~ough-ln fnspecti_o:l Complle~?-- .J. ---·---···- ·---~~-~-'":~~~~~.~ns ', , ' ,
, , ,'.' '
'. -.: ' : '. ,; : ~: (402.2.6 Thermally ineffective panel surfaces of.DCornplies ,Exception: Requirement does not apply, [ME41P sensible heating panels have :Dooes Not '
ins.u!ation >= R-3.5. :ONot Observable: '.DNot Applicable
IC403.2 12 HVAC fan syStems at d~lgn :ocomp!ies
1.1 cond1t1ons. do not exceed allowable iDDoes Not {ME£S P fan system motor nameplate hp or fan :.D Ob bl See the Mechanical SyrtEms list for values.
system bhp. · Not s.erva e. ,__ -- nNot Applicable C403.2.12 HVAC fan systems at design ---~;;~plies .1 conditions do not exceed allowable Dooes Not [ME65P fan sys.tern motor nameplate hp or fan :0 N Ob ble: See the Meehan/car Systems list tor values
system bhp. : at serva :DNot App!lcable
. ·--- - -
Exception: Requirement does not apply.
Exception: Requirement does not apply. ·-··---,-~--~--!
Ctl'o:i.2.12 HVAC fan SYstems at design------ --- Deoni'Piie5 . -·--e~~eption: ReQUirement d~~ not appiy.' .1 conditions do not exceed allowable -D0oes Not IME65)3 fan system motor nameplate hp or fan :0 b s~ t.tmMet:hanical Systems list for values.
system bhp. '. Not O servable :ONot Appllcab!e
C403.2.12' 'fam have efficiency grade (FE.Gi >= ;OComplies ----·· .. -.-.-..,-.·.·,·s·,n··.··1.·,··a~~-;ith motor nameplate tiorsepowerof = .3 , .67. The total efficiency of the fan at ;ODoes Not 5 hp. tMEl17F :the design point of operation<= 15%]
of maximum total efficiency of the ,DNot Observable fan. !ONot Applicable
~...1.-~" -"""' -
('.:403.2..12 Fans have efficiency grade (FEG} >= [:kOm?lieS .$ ' . _ 67, The total efficiency of the fan at ;D0oes Not IME117f the design potnt of operation<= 15%
of maximum total efficiency of the ONot Observable
----- - - - -Exception: Single fans with motor nameplate horsepowerof"" 5 hp.
fan. ;DNot Applicable ~------.-- CC..--.~------~--···- ---~--------' C403.2.12 Fans have efficiency grade (FEG) >= Oeompues 'Exception: Single fans with motor nameplate horsepowerof = ,3' 67. The total efficiency of the fan at DDoes Not 5 hp. ME1i7P the design point of operation<= 15% 'ONot Observable,
of maximum total efficiency of the fan. ,ONot Appllcable
&_Oi2.13 Unenclo5~ ;;ces that~~-heated {Mf71P use only radiant heat.
l-,-,-. .'--.. --C403.2.3 HVAC equipment efficiency verified. {ME5SP
"'.OCompii~ '.Oooes Not
:oNot Observable DNot Applicable
OComplies ;DDoes Not
'ONot Observable
;Exception: Requirement does not apply.
5~ the Mechanical Systems list for values
--·--··-·------------~O=Not Applicable ------·--·-------C403.2.6. Demand control ventilation provided 0Complies Exception: Requlreme~t does not apply. 1 for spaces >500 ft2 and >25 ,Dooes Not [ME59Jl people/1000 ft2 occupant-density and ·oNot Observable
served by systems with air side economizer, auto modulating outsfde '.ONot Applicable air damper control, or design airflow ,
______ _?_~_.~oo ctr:i::.. ________ ... _.----~-----------··---------·-· (403.2.6. Enclosed parking garage ventilation ;OComplies Exception: Requirement does. not apply. 2 has automatic contaminant detection :Dooes Not [MEllSP and capacity to stage or modulate
fans to 50% or less of design capacity. :DNot Observable :DNot Applicable -·-----------------,--~-~~=~----------------------.J
C403.2.7 Exhaust air energy recovery on ;Ocornp!ies [ME57P systems meeting Table C403.2.7(1) DDoes Not
and C403.2.7(2J. ;ONot Observable: '.DNot Applicable ,
Exception; ReQuirement does not apply.
l_:QHigh Im~~~ (r1er 1CITJ~~~!!-l:" Impact (Tier_2J I 3 !tow Impact (Tier 3} ...--, - ""''"'"'"""
Project Title: Reportdate: 09!15/17
Data filename: P:\T.W.I.G\TWIG CONSULTING\Prnjects\DI-Architects.\Thomas Education Center\EN\EN.cctc Page 6 of 11
: '
•
'
ENERGY CODE PROGRESS INSPECTIONS
y N PROGRESS INSPECTIONS
PROTECTION OF FOUNDATION INSULATION (IA1), (IIA1) INSULATION PLACEMENT AND R VALUES (IA2), (IIA2)
FENESTRATION THERMAL VALUES AND RATINGS (IA3), (IIA3)
FENESTRATION RATINGS FOR AIR LEAKAGE (IA4), (11A4)
• FENESTRATION AREAS (IA5), (IIA5)
AIR SEALING AND INSULATION· VISUAL (IA6), (IIA6)
AIR SEALING AND INSULATION - TESTING (IA7), (IIA7)
PROJECTION FACTORS
LOADING DECK WEATHER SEALS {IIA8)
VESTIBULES (IIA9)
FIREPLACES (IB1), (IIB1)
DAMPERS INTEGRAL TO BUILDING ENVELOPE (IB2), (IIB2) HVAC AND SERVICE WATER HEATING EQUIPMENT (IB3), (IIB3) HVAC AND SERVICE WATER HEATING SYSTEM CONTROLS (IB4), (IIB4) DUCT PLENUM AND PIPING INSULATION AND SEALING (185), (IIB5) DUCT LEAKAGE TESTING (IB6), (llB6)
ELECTRICAL METERING (IC1). (IIC1)
LIGHTING IN DWELLING UNITS (IIC2)
INTERIOR LIGHTING POWER (IC2), (IIC3)
EXTERIOR LIGHTING POWER (IIC4)
LIGHTING CONTROLS (IIC5)
EXIT SIGNS
TANDEM WIRING
ELECTRICAL MOTORS (IIC6)
MAINTENANCE INFORMATION (ID1), (1101)
PERMAMENT CERTIFICATE (102)
SPECIAL INSPECTION ITEMS REQUIRED YES NO SPECIAL INSPECTIONS
PHOTOLUMINESCENT EXIT PATH MARKINGS (BC 1024.B, BC 1704.30)
EMERGENCY POWER SYSTEMS GENERATORS (BC 1704.31)
SMOKE CONTROL SYSTEMS (BC 1704, 15)
MECHANICAL SYSTEMS (BC 1704.16)
FUEL-OIL STORAGE AND FUEL-OIL PIPING SYSTEMS (BC 1704.17)
HIGH PRESSURE STEAM PIPING (WELDING) (BC 1704.18)
FUEL-GAS PIPING (WELDING) (BC 1704.19)
SPRINKLER SYSTEMS (BC 1704.23)
. STANDPIPE SYSTEMS (BC 1704.24)
HEATING SYSTEMS (BC 1704.25)
. .
CHIMNEYS (BC 170426)
. FIRE-RESIST ANT PENETRATIONS & JOINTS (BC 1704.27)
ENERGY CODE COMPLIANCE INSPECTIONS (BC 110.3.5)
ENERGY ANALYSIS DRAWING LIST EN~101.00
EN-102.00
ENERGY ANALYSIS COMPLIANCE SHEET I
ENERGY ANALYSIS COMPLIANCE SHEET II
ENERGY ANALYSIS (DUCTWORK INSULATION)
ITEM DESCRIPTION
ALL SUPPLY DUClWORK ALL OUTDOOR DUCTWORK ALL OUTSIDE AIR OR MIXED AIR DUCTWORK AND LOUVER BLANK OFF PANEL
NOTES: ---
PROPOSED DESIGN VALUE
R-VALUE > 3.5 R-VALUE > 3.5
R-VALUE 2 3.5
CODE PRESCRIBED VALUE
R-VALUE > 3.5
R-VALUE 2 3.5 R-VALUE 2 3.5
R-VALUE 2 3.5
1. ALL SEALING TAPE SHALL CONFORM TO UL-181A OR UL-1818 WHEN USED AS A PRIMARY SEALANT.
ENERGY ANALYSIS (HVAC PIPING INSULATION)
DESCRIPTION PROPOSED DESIGN VALUE CODE PRESCRIBED VALUE
HEATING HOT WATER
NOMINAL PIPE NOMINAL PIPE NOMINAL PIPE NOMINAL PIPE DIAMETER < 1.5" DIAMETER > 1 S DIAMETER < 1.5" DIAMETER > 1.5"
2 2
REFRIGERANT 1 1-1/2 1-1/2
CITY COLD WATER
1-1/2" 1-1/2~ 1-1/2~ 1-1/2"
ENERGY ANALYSIS (PLBG PIPING INSULATION)
DESCRIPTION PROPOSED DESIGN VALUE CODE PRESCRIBED VALUE
HEATING HOT WATER
NOMINAL PIPE NOMINAL PIPE NOMINAL PIPE NOMINAL PIPE DIAMETER <1.0" DIAMETER 1-1.5" DIAMETER< 1.o~ DIAMETER 1 -1.5"
0,5' OS OS
ENERGY ANALYSIS (PLBG PIPING INSULATION) HEATING AND COOLING SYSTEM DESIGN LOADS FOR THE PURPOSE OF SIZING SYSTEMS AND EQUIPMENT HAVE BEEN DETERMINED IN ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING STANDARDS.
SERVICE WATER HEATING CALCULATION COMPLIANCE STATEMENT) HEATING AND COOLING SYSTEM DESIGN LOADS FOR THE PURPOSE OF SIZING SYSTEMS AND EQUIPMENT HAVE BEEN DETERMINED IN ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING STANDARDS.
DAN IONESCU I ARCHITECTS
253 Fifth Avenue New York, New York 10016 212.253.5577 www.diarch.net
le PIETRZAK & PFAU T ENGINEERING&: SURVEYINC,PLLC
262 Greenwich Avenue Suite A Goshen, New York 10924 845.294.0606 www.pietrzakpfau.com
Wexler Associates Structural Engineers
12 West 32nd Street 8th Floor New York, New York 10001 212.643.1500 www.nwexler.com
111 WEST 33RD STREET 18TH FLOOR New York, New York 10001 212.967.8944 www.twigcon.com
FALLSBURG SUBMISSION 09.20.17
Issue:
DOB STAMP:
PROJECT:
PRIVATE RESIDENCE
ADDRESS:
TOWN OF FALLSBURG SULLIVAN COUNTY, NY
Project No:
Scale: NTS,
Date:
Drawn By:
1ST FLOOR-ROOF MECHANICAL INTERNATIONAL CODE COMPLIANCE
171042
920.2017
RS/CS
Approved By: DI
Date:
rs? OF 83
EN-101.00 Pnnled on 9.20.2017
•.
;
} i l
' ;
' ij I
I I
! :;:~:r M~:~an:cat Rough-In ln~pectio:-1--~om~~:~1 I . ·- --~,, ComtuentS!A~lo~s~~-'. ~ -- _;,. ~ :>1 t-;-~--- -- ~ -- __J.:_ - -- ------ ---~--------'--"'--'--"-,_,, ___ ._._ iC403 2 8 Kitchen exhaust systems comply with Dcompt1es Exception: Requirement does not apply. l[MEU6P -replacement air and cond1t1oned Dooes Not . i • supply air lim1tat1ons, and satisfy hood ON t Ob bl i I rating requirements and maximum O O serva e
exhaust rate cntena Not Applicable
~03 2.9 HVAC ducts and plen~;;~~~ated--Ocomplles Exc;,;ilom Re(lu1re;ent d~;s~PP1-,---------E60]2 Where civets or p!enums are installed Dooes Not
in or under a slab, ver1f1cat1on may
I need to occur dunng Foundation DNot Observable Inspection DNot Applicable
!-C40!f.2;9~ucts o1nd plenums sealed based on Dcomplles Requirement will be m;t ___ ------------ ---1
rc:::·:.;·::~:~:::':~~:.::1
:::
0
~,,~;-- ~~~f sf i:~:'.~' .~~~.~~; Req,,;~ment does ,ot ,0,1, - - - --·
11.-3 column requires air leakage testing Dooes Not ] 1ME11]1 1 DNot Observable
C:403.2.a :ouctwork operating >3 1n. ~~ter ....... 1.3 column requires air leakage testing.
0Not Applicable
DcompHes Dooes Not
[MEllP i ONot Observable
exception: Requirement does not <1pply
1 DNot Applicable 1--~----------------~=--~~--------------------------IC403.2.'9. Ductwork operating >3 in. water Dcomplies [1.3. · column requires air leakage testing. Dooes Not
l[MEllP ONot Observable
Exception: Requirement does not apply.
I • 0Not Applicable
lc403.4.2. o'pen- or ~ioSed circUit coo!irlg to·wers Ocomptlf!s · ·Excepti.in; Requirement doe-,-n·o-,.--·,·,-1v···_ -- --- .-.. -·-----3.2.2' have a separate heat exchanger to Dooes Not
l[ME.1221-' isolate the cooling towedrom the ON t Ob bl ,1·
I heat pump loop, and heat loss is O serva e controlled by shutting down the 0Not AppHcable circulation pump on the cooling tower
\c4Q~.4:2 .. ~;:~- or c1~sect- circuit coolin-g towers Dcomp11es ----Excepl:IQ-;;·; Req·~irCme-nt ctOesnot app1y,-------- ----- j
.I I
I t
'
13.2.2 'have a separate heat exchanger to Dooes Not 1'
[MEi-2213 Isolate the cool mg t-ower from the · heat pump loop, and heat loss Is DNot Observable .
1 controlled by shutting down the DNot Applicable I 'circulation pump on the cooling tower I ·r--'-'----loop, - -· - ---- ---------- ----- -- ------------ -- --------------------C4Ql.4.i. o_ pen- or closed_ circuit cooling towers Dcompfies Exception: Requirement does not apply. 3.?·-7- have a separate heat exchanger to DDoes Not (ME122J1 isolate the cooling tower from the ON t Ob bl
heat pump loop, and heat loss is O ser;a e controlled by shutting down the DNot Applicable circulation pump on the cooling tower
~-,_._, __ loop.····------· -~--~----~---~-~-c--c---~--------------(403.4.4. Multiple zone VAV systems with DDC DComplies Exception: Requirement does not apply.
16 of individual zone boxes have static Dooes Not '{ME110J1 , pressure setpoint reset controls. O See the Meehan/cal Systems 11st for values.
Not Obsen1able
-·---·-··---------· ··----- ·-----~-·---·-- _ DNot Applicable C403.4.4. Multiple zone VAV systems with DOC DComplies Exception: Requirement does not apply. 6 of individual zone boxes have static Dooes Not
I [MEllOJl pressure setpomt reset controls. O · Se,e the Mechimicar Syswms fist tor valu&s. Not Observable
~--------------------gNot App_l_k_a_b1_, ____________________________ ~
r 1·:High Impact (TiE'r 1) ! 2:'. :Medium lmpaCt (Tier 2) '_3 :low Impact mer 3) ' -----··- -- ---- -----~- ,I. ---------- ---- -~-~. ·-------- ., .. _,_
Project Title: Report date; 09/15/17 Data filename· P:\T.W.I.G\TWIG CONSULTING\ProJects\OI-Architects\Thomas Education Centet\EN\EN.cck Page 7 of 11
Sectlou r ::r:::- " "" . -~.TJ::. &_J(}.~-- Fi~al lr1$pe~~n _ _ ! _ ~~mplle$: ]L_~~~- _ _ _ _ Com~:~~/~~-su~~~n~- ___ ~- _ --~--2--:
C408.2.l Commissioning plan developed by Dcomplies Requirement will be met. !Fl28]1 registered design professional or Dooes Not
approved agency DNot Observable DNot Applicable
:1· .--
:1
I I
C408.2.3. HVAC equipment has been tested to Dcoffiplies 1 ensure proper operation. Dooes Not
Requirement will be met.
(F131] 1 ONot Observable I I 0Not Applicable C408 2 3 - HvAC control systems ha~e been - oCOmpiieS ___ --R-eQlli~e-ment wil-1 be-~e-t:--- - - - - - -- -2 tested to ensure proper operation, Dooes Not
l{FllO]l calibration and adjustment of controls, ONot Obsen1able
0Not Applicable
-- __ J -
I i 1,(408.2.4 {Fl29] 1
I 1~408.2.5,
{Fl7)S
I
C408.2.5. 3 [F143]1
Preliminary commissioning report completed and certified by registered design professional or approved agency.
Furnished HVAC as-built drawings submitted w;thin 90 days of system acceptance
An air and/or hydronic system balancing report is provided for HVAC systems.
Dco~Piie~ Dooes Not
ONot Observable 0Not Applicable
- -Requirement will be met.
·ocompiies Requirement will be met. Dooes Not
0Not Observable 0Not Applicable
DcomP!ies Dooes Not
ONot Observable DNot Applicable
-Requirement will be met.
- -I
1~408 2 5~ t~1r~i~~~r;;~s;~o;1~~;~f~:~~~:~·-·- 8~~~:~~!-·- --R-;;ire;;;;t-wi11-b·;~-et --- -- ---·-··-·----·-·---
! [F130]1 receipt of certificate of occupancy. _J ONot Observable I DNot Applicable ~---~-----Additional Comments/Assumptions:
1 ;High Impact [Tier 1) r 2· [ Medium lmPact (Tier 2) . 3 jLow Impact \Tier 3)___j -···---- ..... ,-----·---------~ .. ------------·--- _____ ,, _______ ,.,,_, __ Project Title: Data filename P:\T.W.I.G\TWIG CONSUL TING\Projects\DI-Architects\Thomas Education Center\EN\EN.cck
Report date: 09/15/17 Page 10 of 11
I I
I
L---·-· ----~ -- ------- ----------··----------·---- ---·----· ·---·-------"--
Se-l:twn • _]_:P'""" '"' . , .. , ,< ,,,"', ~
A~:9:!i _M~e-b.~:~~~~~gh~tt~P«uo~i;;_~~fflpil~?.:::f: ~·/, :·/ e~~~/~:1"~~- 0
------· _ _:~~
C403 4 4 Mu_lt1ple zone VAV systems with DOC Ocomphes Exception: Requirement does not apply I 16 of md1vidua1 zone boxes have static ,Dooes Not [MEl 10P pressure setpoint reset controls. 'ON Ob bl See the Mochanlcal S~tems 1/st fur values.
/ ot serva e,
!·-·- .. --,- _ ----· ____ , ___ --~-N?_t_A~pl!~.'.3~e __ :" ... ---- ___ ___ -·-----·--------! I C4. 08.2.2. Air outlets and zone terminal devices 'OCompl!es ! Exception: Requirement does not apply, l have means for air balancing. '.Dooes Not
I [ME'53"J' ONot Observable
L.---------------~O=N~ot~A~p~p~i;~ca~b~l•'--'----------------------1 Additional Comments/Assumptions:
[}:THig_h lmpac_t (Tier 1)---~edium Impact {Tier 2) -~-:i_ jLow lmpac_t (Tier 3) ___ J Project Tftle: Report date: 09/15/17 Data filename· P:\T.W I.G\TWIG CONSULTING\Projects\01-Arch!tects\Thomas Education center\EN\EN.cck Page s of 11
Project Title; Data filename P:\T WJ.G\TWIG CONSULTING\Projects\OI-Architects\Thomas Education Center\EN\EN.cck
Report date: 09/15/17 Page 11 of 11
-
•
:
-
.
_ _'._L ____ J. __ !JlillllHIII HM tffl!t)fflffill
·-·:r· --------------- I I . '".
J - : & R!.~ID ___ -· -· --~-i::l ln~~ed~~n i Complies? Comments/~~.:-~~=--~-·:'._-. _;;_;; C303.3, Furnished O&M manuals for HV_A_C_~_Ocomplies RequirerT\ent :_;;illbe!TI;t:---C408.2_5 systems within 90 de1ys of system Dooes Not 3 acceptance. [F18P ONot Observable
0Not Applicable
··-···--------- ·-·-----C403.2.2 {F127P
HVAC systems and equipment capacity does not exceed calculated loads.
Ocomplies Dooes Not
ONot Observable
~·-· . .. _ __ __ _ __ _ ___ ------· _____ DNot Applicable
controlled by a thermostat control. Dooes Not Minimum one hum1d1ty control device per installed DNot Observable humid1fication/dehumidification 0Not Applicable
Requirement will be met.
IC4032 4 He __ "_Ing and cooling t-0 each zone i-S TJc~;:;,·p1ies- - - -Require~~t Wil1 be ~-et~
.~Y~~!:!:I.:. ---------------- --~-"~------------ ----------j C403.2.4. Heating and cooling to each zone 1s DComplies Requirement will be met. 1 controlled by a thermostat control. Dooes Not [F/47P Minimum one humidity control device
per installed DNot Observable humidification/dehumidification 0Not Applicable system. ----- -~~------------------·------------~
C403.2.4. Heating and cooling to each zone is Dcomplies 1 controlled by a thermostat control. Dooes Not
Requirement will be met.
per installed humidification/dehumidification DNot Applicable l!Fl47P . Mini_rnum one humidity control device ONot Observable
___ , ___ system. ______ _________ -· C403.2.4. Heat pump controls prevent Ocomplies Requirement will be met.
.1 supplemental electric resistance heat Dooes Not [Fl42}3 from coming on when not needed
i ONot Observable l DNot Applicable jC403.2A, Heat pump controls prevent - Dc~mplieS ___ Re_q_o __ " __ e_m_e_n_t_w_U_I b-,-m-,-,_--- -------- --- --- -------1.1 supplemental electric resistance heat DDoes Not [Fl42]3 from coming on when not needed.
- ··-·--··---· ··-------C403.2.4. Heat pump controls prevent 1.1 supplemental electric resist;:mce heat [Fl42]~ from coming on when not needed.
-···-· C403.2.4. 1.2 [Fl38]l
Thermostatic controls have a 5 °F deadband
DNot Observable 0Not Applicable "----~~--~----------------Dcomplies Requirement will be met. Dooes Not
DNot Observable DNot Applicable
Dcomplies Dooes Not
0Not Observable DNot Applicable
- ---Requirement will be met.
C403.2.4. 1.3 [Ft20JJ
Temperature controls have seti,"oint Ocomp1ies -------------------------
Requirement will be met. overlap restnctions. Dooes Not
---------------C403.2.4. Each zone equipped with setback 2 controls using automatic time clock or [F13gp programmable control system.
C403.2.4. 2.1. C403.2.4. 2.2 [F140)3
Automatic Controls: Setback to 55°F (heat) and 85~F (cool); 7-day clock, 2-hour occupant override, 10-hour backup
DNot Observable DNot Applicable
Dcomp!ies DDoes Not
0Not Observable DNot Applicable
Dcomphes DDoes Not
DNot Observable DNot Applicable
Requirement wl!I be met.
Requirement will be met
Project Title· Report date: 09/15/17 Data filename: P:\T,W-'-G\TWIG CONSULTING\Projects,01-Architects\Thomas Education Center\EN\EN.cck Page 9 of 11
-- .. ,·----
-
-
-
:
ENERGY CODE PROGRESS INSPECTIONS y N
/
PROGRESS INSPECTIONS
PROTECTION OF FOUNDATION INSULATION (IA1), (IIA1) INSULATION PLACEMENT AND R VALUES {IA2), {IIA2)
FENESTRATION THERMAL VALUES AND RATINGS (IA3), (IIA3)
FENESTRATION RATINGS FOR AIR LEAKAGE {IA4), (IIA4)
FENESTRATION AREAS (IA5). (IIAS)
AIR SEALING AND INSULATION - VISUAL (IA6), (IIA6)
AIR SEALING AND INSULATION - TESTING (IA7), (IIA7)
PROJECTION FACTORS
LOADING DECK WEATHER SEALS (IIA8)
VESTIBULES (HA9)
, FIREPLACES (181). (1181)
DAMPERS INTEGRAL TO BUILDING ENVELOPE (182). (1182) HVAC AND SERVICE WATER HEATING EQUIPMENT (IB3), (1183) HVAC AND SERVICE WATER HEATING SYSTEM CONTROLS (184). (1184) DUCT PLENUM AND PIPING INSULATION AND SEALING (IB5), (1185) DUCT LEAKAGE TESTING {IB6), (1186)
ELECTRICAL METERING (IC1), (IIC1)
LIGHTING IN DWELLING UNITS (IIC2)
INTERIOR LIGHTING POWER (IC2), (IIC3)
EXTERIOR LIGHTING POWER (IIC4)
LIGHTING CONTROLS (IICS)
EXIT SIGNS
TANDEM WIRING
ELECTRICAL MOTORS (IIC6)
MAINTENANCE INFORMATION {ID1), (1101)
PERMAMENT CERTIFICATE (ID2)
SPECIAL INSPECTION ITEMS REQUIRED YES NO SPECIAL INSPECTIONS
- PHOTOLUMINESCENT EXIT PATH MARKINGS (BC 1024.8, BC 1704.30)
- EMERGENCY POWER SYSTEMS GENERATORS (BC 1704.31)
SMOKE CONTROL SYSTEMS (BC 1704.15)
-MECHANICAL SYSTEMS (BC 1704.16)
._- FUEL-OIL STORAGE AND FUEL-OIL PIPING SYSTEMS (BC 1704.17)
HIGH PRESSURE STEAM PIPING (WELDING) (BC 1704.18)
FUEL-GAS PIPING (WELDING) (BC 1704.19)
.. , SPRINKLER SYSTEMS (BC 1704.23)
·: STANDPIPE SYSTEMS (BC 1704.24)
HEATING SYSTEMS (BC 1704.25)
'-._ CHIMNEYS (BC 1704.26)
FIRE-RESISTANT PENETRATIONS & JOINTS (BC 1704.27)
ENERGY CODE COMPLIANCE INSPECTIONS (BC 110.3.5)
ENERGY ANALYSIS DRAWING LIST EN-101.00
EN-102.00
ENERGY ANALYSIS COMPLIANCE SHEET I
ENERGY ANALYSIS COMPLIANCE SHEET II
ENERGY ANALYSIS (DUCTWORK INSULATION) ITEM DESCRIPTION
ALL SUPPLY DUCTWORK ALL OUTDOOR DUCTWORK
ALL OUTSIDE AIR OR MIXED AIR DUCTWORK AND LOUVER BLANK OFF PANEL
NOTES:
PROPOSED DESIGN VALUE
R-VALUE <!: 3.5 R-V ALLIE e!: 3.5 R-VALUE <!: 3.5
R-VALUE 2: 3.5
CODE PRESCRIBED VALUE
R-VALUE > 3.5 R-VALUE o!: 3.5 R-VALUE o!: 3.5
R-VALUE.:: 3.5
1. ALL SEALING TAPE SHALL CONFORM TO UL-181AOR UL-181B WHEN USED AS A PRIMARY SEALANT.
ENERGY ANALYSIS (HVAC PIPING INSULATION) DESCRIPTION PROPOSED DESIGN VALUE CODE PRESCRIBED VALUE
HEATING HOT WATER
NOMINAL PIPE NOMINAL PIPE NOMINAL PIPE NOMINAL PIPE DIAMETER s 1.5" DIAMETER> 1.5" DIAMETER s; 1.5" DIAMETER> 1.5"
2 2
REFRIGERANT 1 1-1/2 1-1/2
CITY COLO WATER
1-1/2" 1-1/2" 1-1/2"
ENERGY ANALYSIS {PLBG PIPING INSULATION)
DESCRIPTION PROPOSED DESIGN VALUE CODE PRESCRIBED VALUE
NOMINAL PIPE NOMINAL PIPE NOMINAL PIPE NOMINAL PIPE DIAMETER <1.0" DIAMETER 1 -1S DIAMETER< 1.0" DIAMETER 1 - 1.5"
HEATING HOT WATER 0.5" 0.5"
ENERGY ANALYSIS (PLBG PIPING INSULATION)
0.5"
HEATING AND COOLING SYSTEM DESIGN LOADS FOR THE PURPOSE OF SIZING SYSTEMS AND EQUIPMENT HAVE BEEN DETERMINED IN ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING STANDARDS.
SERVICE WATER HEATING CALCULATION COMPLIANCE STATEMENT) HEATING AND COOLING SYSTEM DESIGN LOADS FOR THE PURPOSE OF SIZING SYSTEMS AND EQUIPMENT HAVE BEEN DETERMINED IN ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING STANDARDS.
DAN IONESCU I ARCHITECTS
253 Fifth Avenue New York, New York 10016 212.253.5577 www.diarch.net
,.,L PIETRZAK & PFAU T ENCJNEERJNC &: SURVEYINC,PLLC
262 Greenwich Avenue Suite A Goshen, New York 10924 845.294.0606 www.pietrzakpfau.com
Wexler Associates
FALLSBURG SUBMISSION
Issue:
DOB STAMP:
PROJECT:
PRIVATE RESIDENCE
ADDRESS:
Structural Engineers
12 West 32nd Street 8th Floor New York, New York 10001 212.643.1500 www.nwexler.com
111 WEST 33RD STREET 18TH FLOOR New York, New York 10001 212.967 .8944 www.twigcon.com
09.20.17
Date:
TOWN OF FALLSBURG SULLIVAN COUNTY, NY
1ST FLOOR-ROOF MECHANICAL INTERNATIONAL CODE COMPLIANCE
Project No: 171042
Scale: N.T.S.
Date: 9.20.2017
Drawn By: RS/CS
Approved By: DI iss OF 83
EN-102.00 Pnnted on 9.20.2017
i :1 i
' ' )
-' J
,,•
i
1.
STROBE ALARM
--------THERMOSTAT
80"
LIGHT SWITCHES
i NOTE ---
'121.. THERMOSTATS AND STROBE ALARMS SHALL ALIGN ABOVE LIGHT SWITCHES.
ELEVATION PER ARCHITECTURAL DOCUMENTS
WALL DEVICE LOCATION ELEVATION SCALE: N.T.S.
TABLE 3: TYPICAL MOUNTING HEIGHTS
WALL SWITCHES 48" (120 CM)
RECEPTACLE OUTLETS (GENERAL) 18" (45 CM)
RECEPTACLE OUlLETS 42" (105 CM), OR (KITCHEN, UlllllY ROOM, WORKBENCHES, ETC.) 6" (15 CM) ABOVE COUNTERTOP
SPECIAL PURPOSE OUTLET WITHIN 72" (180 CM) OF INTENDED USE
TELEPHONE OUllETS 18" (45 CM)
WALL INTERCOM STATIONS 48" (120 CM)
NIGHT LIGHTS 18" (45 CM)
WALL LIGHTING OUllETS 84" (210 CM)
THERMOSTATS 48•' (120 CM)
PUSHBUTIONS 48" (120 CM)
ELEVATOR AND HOISTWAY CONTROL BUTTONS 42" (105 CM)
BED LIGHTS 72•· (180 CM)
PATIENT BEDSIDE STATIONS 48" (120 CM)
96" (240 CM) WHEN POSSIBLE. OR 6" (15
CLOCK OUllET CM) BELOW CEILING. ABOVE DOORS,
CENTER THE CLOCK OUTLET BETWEEN DOOR TRIM AND CEILING
BELLS, BUZZERS, CHIMES 96" 9240CM) WHEN POSSIBLE, OR
6" (15 CM) BELOW CEILING
FIRE ALARM PULL STATIONS 48" (120 CM)
FIRE ALARMS (GONGS, BELLS, HORNS, LIGHTS) 80-' (200 CM) ABOVE FINISH LINE. OR
6" (15CM) BELOW CEILING
TABLE 3 DESCRIBES TYPICAL MOUNTING HEIGHTS FOR VARIOUS OUTLETS AND CONTROL DEVICES. ALL HEIGHTS ARE MEASURED FROM FINISHED FLOOR TO CENTERLINE OF DEVICE. THESE HEIGHTS COMPLY WITH THE REQUIREMENTS OF THE ADAG (AMERICAN WITH DISABILITY ACT GUIDELINES).
5. NECA-1 RECOMMENDED OUTLET MOUNTING HEIGHTS SCALE: N.T.S.
Nominal Serivce Utilization Nameplate NEMA
Standard -5°/o ,+5°/o -13o/o, +6°/o Motor -10%, +10%
120 114 - 126 104.4-127.2 115 103.5 - 126.5
208 197.6 -218.4 181 -220.5 200 180 -220
240 228-252 208.9 - 254.4 230 207 -253
277 263.2 - 290.9 241 -293.6
480 456-504 417.6-508.8 460 414 - 506
bandwidth bandwidth bandwidth 10°/o 19% 20%
6. NATIONAL STEADY STATE VOLTAGE REGULATION STANDARDS SCALE: N.T.S.
L l ~-_L • " __ c. ~J"hlill'IIIUNllrcm1nu1m11•um'IIJKiUIII
NOTES:
1. INCREASED GUTIERS MAY BE REQUIRED TO SUIT FEEDER CABLES.
N UTRAL SHALL PASS HROU SAME HOLE IN BARRIER AS PHASE 2. E T GH INCOMING FEEDER CABLES
CONDUIT (TOP OR
I BOTIOM ENTRAN_:_.r
SEE NOTE #1 -··1-DOUBLE SIZE NEUTRAL CONDUCTOR
_/
MAIN CIRCUIT BREAK (IF REQUIRED)
ER_./
-/
__..
1
1 Ii ~L
/ SECTION I
N I
I
CONDUCTORS.
--
PANEL SECTION II
--111 111 I N I
I
EUTRAL DOUBLE BU_
2. FEED THRU METHOD FOR MUL Tl-SECTION PANELBOARD SCALE: N.T.S.
TO 120 OR 277 VOLT
SOURCE. REFER TO
PLANS FOR CIRUIT No.
- L '
>--11--
-LIGITTING CONTROL -DEVICE -
-
I LAMP 1
n , , ~
LAMP2
FLOURESCENT
BALLAST
FLOURESCENT
EMERGENCY
POWER PACK
TS ' (
II
n I
TEST SWITCH POWER "ON" INDICATOR LED
NOTES:
1. THIS DIAGRAM INDICATES GENERAL ARRANGEMENT ONLY. EXACT WIRING QUANTITY AND CONNECTIONS SHALL BE IN
ACCORDANCE WITH MANUFACTURERS WIRING DIAGRAMS.
2. FOR 2'X2' & 2'X4' FIXTURES TEST SWITCH & LED SHALL BE MOUNTED ON AN ACCESSIBLE PORTION OF THE FIXTURE
HOUSING. FOR PL DOWNLIGHTS OR WALLWASHERS THE TEST SWITCH & LED SHALL BE MOUNTED ON AN ACCESSIBLE
PORTION OF THE FIXTURE HOUSING, IF THIS IS NOT POSSIBLE THEY SHALL BE MOUNTED ON AN ADJACENT CEILING
TILE UTILIZING A WHITE SINGLE GANG PLATE
3. EMERGENCY POWER PACK SHALL BE LIGHT ALARMS SERIES AM OR APPROVED EQUAL WITH A MINIMUM ILLUMINATION
TIME REQUIREMENT OF 90 MINUTES AND SHALL PROVIDE EMERGENCY ILLUMINATION OUTPUT TO ONE LAMP WITHIN A
FIXTURE AS FOLLOWS:
-SERIES AM12 (1100 LUMENS), FOR 2'X2' & 2'X4' FIXTURE.
-SERIES AM11 (650 LUMENS), FOR COMPACT FLUORESCENT FIXTURE WITH 7, 9 OR 13 WATT LAMPS AT95% OF
THE LAMPS RATED LUMEN OUTPUT.
-SERIES AM18 (850 LUMENS), FOR COMPACT FLUORESCENT FIXTURE WITH 10,13,16,18 OR26 WATT LAMPS AT
95% OF THE LAMPS RATED LUMEN OUTPUT.
4. UGHTING CONTROL DEVICE IS SWITCH, DIMMER, OCCUPANCY SENSOR, ETC .. AS DESCRIBED ON PLAN FOR EACH
APPLICATION.
TYPICAL DETAIL OF EMERGENCY LIGHTING FIXTURE 7. SCALE: N.T.S.
3.
8.
N
1.
2.
PIAND1YPE (TYPICAL)
HINGE
re ~
PANEL "RP-45E"
120/208V,3PH UNIT PANEL
I PHkBLA~1 PH B:BLUE PH C:RED )
B
S0URCE:DP-7E 1
I'\ - -
PANEL NAME
PANEL VOLTAGE & PHASE
PANEL SYSTEM
CONDUCTOR COLOR CODE IDENTIFICATION. MOUNT ON INSIDE COVER ABOVE SCHEDULE
PANEL SOURCE
PANELBOARD IDENTIFICATION DETAIL SCALE: N.T.S.
TORK ELECTRONIC TIMECLOCK MODEL# DGU100 TORK TIME SWITCH
OUTPUT TERMINALS
NO C NC ~
I
~ L
208 277 H N N 120 240 VAC c__ MOMENTARY CONTACT SWITCH
FOR TIMECLOCK OVERRIDE. C ON OFF TIME SWITCH 1NPUT POWER
DO NOT APPLY INPUT
VOLTAGE MAIN LOAD OUTPUT
TERMINALS
NC NO C
i TORK
MODEL# LOS-A
OTES:
CONTRACTOR SHALL SET TIMECLOCK PER OWNER'S REQUIREMENTS.
TIMECLOCK SHALL BE MANUFACTURED BY TORK (ASTRONOMIC TIMECLOCK).
TIMECLOCK LIGHTING CONTROL WIRING DIAGRAM SCALE: N.T.S.
I
DOOR TO COVER CIRCUIT BREAKER ONLY.
LOCK
s
., - cJ
•
•
•
•
- CONTINUOUS PIANO HINGE
4. DOOR IN DOOR COVER DETAIL SCALE: N.T.S.
H 120V
15A
N
J
1 LIGHTING LOAD VIA LOCAL SWITCHES
SPARE
I ' J_ J_ I~---== ---~
T T
LIGHTING LOAD VIA LOCAL SWITCHES
~ SPARE
I ' J_ J_ ~ ~--! ---- - -.-
T T
-
~
MECHANICALLY HELD ELECTRICALLY OPERATED REMOTE CONTROL RELAY SUITABLE FOR LINE TO
LINE VOLTAGE UP TO 600 VOLTS.
ASCO 917, 4 N.O. CONTACTS, 120V CONTROL VOLTAGE
IN NEMA 1 ENCLOSURE. INSTALL NEXT TO PANEL HLP-5
MECHAN1CALL Y HELO ELECTRICALLY OPERATED REMOTE CONTROL RELAY SUITABLE FOR LINE TO
LINE VOLTAGE UP TO 600 VOLTS.
ASCO 917, 4 N.O. CONTACTS, 120V CONTROL VOLTAGE
IN NEMA 1 ENCLOSURE. INSTALL NEXT TO PANEL HPP-7
DAN IONESCU I ARCHITECTS
253 Fifth Avenue New York, New York 10016 212.253.5577 www.diarch.net
J.c PIETRZAK & PFAU T ENGINEERING &- SURVEYTNG,PLLC
262 Greenwich Avenue Suite A Goshen, New York 10924 845.294.0606 www.pietrzakpfau.com
Wexler Associates Structural Engineers
12 West 32nd Street 8th Floor New York, New York 10001 212.643.1500 www.nwexler.com
111 WEST 33RD STREET 18TH FLOOR New York, New York 10001 212.967.8944 www.twigcon.com
FALLSBURG SUBMISSION 09.20.17
Issue:
DOB STAMP:
PROJECT:
PRIVATE RESIDENCE
ADDRESS:
TOWN OF FALLSBURG SULLIVAN COUNTY, NY
Project No:
Scale: NTS.
Date:
Drawn By:
Approved By:
CELLAR - ROOF ELECTRICAL DETAILS
171042
9.20.2017
RS/CS
DI
Date:
OOF 83
E-401.00 Printed on 9.20.2017
I
'.l \ l
' !
i IJ I
' .
J '
' )
!
1/
' I ' ,
PLUMBING NOTES
1. ALL NEW HOT AND COLD WATER LINES TO BE COPPER TUBING AND SHALL ORIGINATE ON THE SAME FLOOR FROM THE NEAREST WET COLUMN WITH PROPER ACCESS FOR MAINTENANCE. IF ATIACHED OR DISSIMILAR METAL, A CORROSION INHIBITOR IS TO BE PROVIDED.
2. INSULATE ALL WATER SUPPLY LINES.
3. WASTE LINES SHALL BE PROPERLY PITCHED TO PREVENT "TRAPPED" WATER. INSTALL WASTE LINE CONNECTIONS WITH LONG TERM OR 45" "Y" FITIINGS.
4. RETAIN EXISTING CLEAN OUT CONNECTIONS AND PROVIDE CLEAN OUT CONNECTIONS AT NEW FITIINGS.
5. WHEN CONNECTING NEW HOT AND COLD WATER LINES TO EXISTING RISERS, CONTRACTORS SHALL LEAVE A PLUGGED VALVED OUTLET FOR EACH, FOR FUTURE USE.
6. ALL NEW HOT AND COLD WATER LINES ATTENDANT FITTINGS MUST BE PROPERLY INSULATED AND COVERED.
7. INDIVIDUAL SHUT-OFF VALVES MUST BE SUPPLIED AND INSTALLED FOR EACH NEW FIXTURE, INCLUDING WATER COOLERS.
8. ALL NEW PIPES ARE TO BE SUPPORTED FROM SLAB OR STEEL BEAMS, NOT FROM EXISTING PIPES OR DUCT WORK.
9. ALL WATER SHUTDOWNS TO BE COORDINATED THROUGH THE BUILDING MANAGER. ALL WATER SHUTDOWNS ARE TO BE PERFORMED OR SUPERVISED BY BUILDING PERSONNEL, AT THE DISCRETION OF THE BUILDING MANAGER.
10. PLUMBER SHALL BE RESPONSIBLE THAT ENTIRE INSTALLATION IS IN ACCORDANCE WITH LOCAL AND STATE CODES.
11. PRIVATE BATHROOMS MUST BE INSTALLED ON MINIMUM 4" WASTE LINE.
12. ALL VALVES ARE TO BE PROPERLY TAGGED.
13. ANY WET COLUMNS USED SHOULD BE PROVIDED WITH A 24" x 24" STEEL SURFACE MOUNTED ACCESS DOOR.
14. HOT WATER HEATERS SERVING PRIVATE BATHROOMS, KITCHENS. ETC. ARE TO BE SUPPLIED FROM THE WET COLUMN THAT SUPPLIES THE COLD WATER TO THESE AREAS.
PLUMBING DEMOLITION NOTES
1. GENERAL
A. PRIOR TO PROPOSAL SUBMISSION, THIS CONTRACTOR SHALL VISIT THE SITE TO REVIEW THE EXISTING CONDITIONS ASSOCIATED WITH THE SCOPE OF WORK AND ADJACENT AREAS TO ASCERTAIN THE DIFFICULTIES WHICH WILL AFFECT THE EXECUTION OF THE WORK OF THIS CONTRACT.
B. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT THE ABOVE SITE EXAMINATION HAS BEEN MADE AND LATER CLAIMS WILL NOT BE RECOGNIZED FOR EXTRA LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD SUCH AN EXAMINATION BEEN MADE.
C. DEMOLITION WORK SHALL INCLUDE ALL MATERIALS, LABOR, EXTENSIONS, CONNECTIONS, CUTTING, REPAIRING, ADAPTING AND OTHER PLUMBING WORK REQUIRED TO MAINTAIN SERVICE PENDING THE COMPLETION OF THE PERMANENT WORK. COORDINATE THE EXTENT OF DEMOLITION WORK WITH THE ARCHITECT AND BUILDING MANAGEMENT.
2. SCOPE OF WORK
A. ALL EXISTING WORK REQUIRED TO REMAIN BUT INTERFERING WITH PROPOSED NEW PLUMBING (AS WELL AS ELECTRICAL, MECHANICAL AND GENERAL CONSTRUCTION WORK) SHALL BE RELOCATED AND RECONNECTED USING MATERIALS CONFORMING TO STANDARDS OF THIS CONTRACT.
B. REMOVE ALL FIXTURES AS NOTED ON THE ARCHITECTURAL PLANS. PROVIDE TEMPORARY COVERS FOR HOT, COLD AND SANITARY CONNECTIONS DURING NEW CONSTRUCTION.
C. REMOVE BASE BUILDING PIPING AS INDICATED BELOW:
a. REMOVE ALL ABANDONED BASE BUILDING PIPING BACK TO THE EXISTING WET COLUMNS OR SHAFTS, OR AS NOTED ON DRAWINGS.
b. CONTRACTOR TO CONTACT BUILDING MANAGEMENT AND TENANT REGARDING REMOVAL SCOPE OF WORK TO MAINTAIN CONTINUITY OF ALL SERVICES TO ALL TENANTS WHO ARE TO REMAIN OPERATIONAL AND NOT BE AFFECTED BY DEMOLITION WORK.
c. ALL EXISTING BUILDING VALVES FOR DOMESTIC WATER MAINS AT SHAFTS ARE TO REMAIN.
D. PROVIDE ADDITIONAL SUPPORT FOR ALL EXISTING PIPING TO REMAIN WHICH ARE AFFECTED BY DEMOLITION OF EXISTING CEILING AND PARTITIONS.
E. ALL MATERIALS AND EQUIPMENT SHALL BE DISPOSED OF IN ACCORDANCE WITH APPLICABLE LAWS AND ENVIRONMENTAL REGULATIONS.
F. COORDINATE WITH OWNER TO DETERMINE WHETHER EQUIPMENT IS TO BE TURNED OVER FOR FUTURE USE AND STORED IN THEIR ASSOCIATED STORAGE LOCATIONS.
PLUMBING LEGEND
T
'
r -
>-----4-------
, . '
' I~
- -y
g
@
* ~
-
BUTTERFLY VALVE
GATE VALVE
EXISTING GATE VALVE
PRESSURE REDUCING VALVE
CHECK VALVE
EXISTING CHECK VALVE
BALL VALVE
PLUG VALVE
O,S&YVALVE
EXISTING O,S & Y VALVE
MIXING VALVE
SOLENOID VALVE
VALVE WITH HOSE BIBB
STRAINER WITH BLOW OFF VALVE
STRAINER
FLOOR DRAIN
CLEAN OUT DECK PLATE
FUNNEL FLOOR DRAIN
STRAINER
LADDER
a--------, PIPE UP
C--->
[--->
' ' ' 5'
' cp
' ' ill ' ,-..., T f---->
>----CD---<
PIPE DROP
BOTIOM CONNECTION
TOP CONNECTION
CAP
PLUG OUTLET
CLEANOUT
FRESH AIR INLET
HOUSE TRAP
SHOCK ABSORBER
PIPE SENSOR WELL
VACUUM BREAKER
VACUUM BREAKER
PIPE GUIDE
UNION
PIPE SLEEVE
FLOW SWITCH
PRESSURE GAGE
THERMOMETER
THERMOWELL
DOMESTIC WATER METER
., ELECTRONIC WATER COOLER
Ira TWO-COMPARTMENT SINK
m THREE COMPARTMENT SINK
co WATER CLOSET
IZI MOP RECEPTOR
0 LAVATORY
[ZJ MOP RECEPTOR
El KITCHEN SINK
(:) SLOP SINK
[8] SHOWER
DI BATHTUB
m::,, BIDET
[D WATER CLOSET (FLUSH VALVE-WALL HUNG)
[JD WATER CLOSET (FLUSH TANK)
~ URINAL
[I LAVATORY
= TWO-COMPARTMENT SINK (ELEVATION)
fa E, EDA WATER COOLER ELEVATION
w WATER CLOSET (ELEVATION)
= MOP RECEPTOR (ELEVATION)
a BATHTUB (ELEVATION)
CJ KITCHEN SINK (ELEVATION)
""' LAVATORY (ELEVATION)
= THREE COMPARTMENT SINK (ELEVATION)
b BIDET (ELEVATION)
g ROOF DRAIN (ELEVATION)
d SLOP SINK (ELEVATION)
m WATER CLOSET (ELEVATION)
~ URINAL (ELEVATION)
[Y WALL HUNG WATER CLOSET (ELEVATION)
(NOT ALL SYMBOLS ARE NECESSARILY USED ON THIS PROJECT)
PLUMBING DRAWING LIST
1 P-101.00 CELLAR - ROOF: PLUMBING SYMBOLS & NOTES
2 P-201.00 CELLAR - ROOF: PLUMBING SPECIFICATIONS I
3 P-202.00 CELLAR - ROOF: PLUMBING SPECIFICATIONS II
4 P-203.00 CELLAR - ROOF: PLUMBING SPECIFICATIONS Ill
5 P-301.00 CELLAR: PLUMBING PLAN & NOTES
6 P-302.00 1 ST FLOOR: PLUMBING PLAN & NOTES
7 P-303.00 2ND FLOOR: PLUMBING PLAN & NOTES
8 P-304.00 ROOF: PLUMBING PLAN & NOTES
9 P-401.00 CELLAR - ROOF: PLUMBING DETAILS
10 P-501.00 CELLAR - ROOF: PLUMBING RISER DIAGRAM
11 P-601.00 CELLAR - ROOF: PLUMBING SCHEDULE
PLUMBING LINE REPRESENTATION
----------------
, , , , .
----·----
-"V\1-' ---
----·----
--------
---------
l( M )(
NEW COLD WATER PIPING
NEW HOT WATER PIPING
NEW HOT WATER PIPING WITH TEMPERATURE MAINTENANCE CABLE
NEW HOT WATER RECIRCULATION
NEW VENT PIPING
NEW SANITARY OR STORM WATER PIPING ABOVE
NEW SANITARY OR STORM WATER PIPING BELOW
NEW GAS LINE
NEW ACID WASTE PIPING
EXISTING COLD WATER PIPING TO REMAIN
EXISTING HOT WATER PIPING TO REMAIN
EXISTING HOT WATER RECIRCULATION PIPING TO REMAIN
EXISTING VENT PIPING TO REMAIN
EXISTING SANITARY OR STORM WATER PIPING ABOVE 4TH TO REMAIN
EXISTING SANITARY OR STORM WATER PIPING BELOW 4TH TO REMAIN
EXISTING PIPE TO BE REMOVED
PLUMBING DRAWING NOTATIONS
©
© ~ (>
ffi EB E9 EB --
DRAWING NOTE TAG
SECTION DESIGNATION ON DRAWING WHERE SECTION IS CUT A-SECTION DESIGNATION B-DRAWING NO.
POINT OF NEW CONNECTION TO EXISTING WORK
REMOVE AND PATCH EXISTING WORK
REVISION SYMBOL
FIRE STANDPIPE RISER DESIGNATION
PLUMBING RISER DESIGNATION
LEADER DESIGNATION
PIPING FLOW DIRECTION
TOWN OF FALLSBURG BUILDING DEPARTMENT PLUMBING NOTES
1. ALL PLUMBING WORK SHALL COMPLY WITH THE TOWN OF FALLSBURG BUILDING CODE, AND CHAPTERS 1 THROUGH 13 OF THE TOWN OF FALLSBURG PLUMBING CODE.
2. PROTECTION OF PIPING AS OULINED IN SECTION PC305 SHALL BE PROVIDED AS REQUIRED.
3. IN GENERAL, PIPING MATERIALS SHALL BE AS PER SECTION PC303.
4. CONSTRUCTION AND SPACING OF HANGERS AND SUPPORTS SHALL BE AS DIRECTED IN SECTION PC308.
5. WATER SUPPLY SYSTEM SHALL BE AS DIRECTED IN SECTIONS PC601 THROUGH PC613. VALVES SHALL BE PROVIDED AT RISERS AND ELSEWHERE AS PER SECTION PC606.
6. SANITARY MATERIALS, DRAINAGE, SIZING, GRADING, AND OFFSETS SHALL BE AS OULINED IN SECTIONS PC701 THROUGH PC715.
7. CLEAN-OUTS SHALL BE AS PER SECTION PC?OB.
8. TRAPS SHALL SHALL BE AS PER SECTION PC1002.
9.
10.
VENT MATERIALS, SIZING, GRADING, CONNECTIONS, LOCATIONS AND OFFSETS SHALL BE AS DIRECTED IN SECTIONS PC901 THROUGH PC919.
SPECIAL AND MISCELLANEOUS PIPING SHALL BE AS DIRECTED IN SECTION PC1201 THROUGH 1203.
AFF
BFP
CM
COOP
cw DIA
DN
EWC
FAI
FD
FFD
FL
FS
HB
HW
HWR
IM
LAV
LDR
MIN
MR
NO
RD
RPZ
RTU
s SH
ss UR
V
VB
VTR
w WH
WC
PLUMBING ABBREVIATIONS
ABOVE FINISHED FLOOR
BACKFLOW PREVENTER
COFFEE MAKER
CLEAN OUT DECK PLATE
COLDWATER
DIAMETER
DOWN
ELECTRIC WATER COOLER
FRESH AIR INLET
FLOOR DRAIN
FUNNEL FLOOR DRAIN
FLOOR
FLOOR SINK
HOSE BIBB
HOT WATER
HOT WATER RECIRCULATION
ICE MAKER
LAVATORY
LADDER
MINIMUM
MOP RECEPTOR
NUMBER
ROOF DRAIN
REDUCED PRESSURE BACKFLOW PREVENTER
ROOF TOP UNIT
SANITARY
SHOWER
SERVICE SINK
URINAL
VENT
VACUUM BREAKER
VENT THRU ROOF
WASTE
WALL HYDRANT
WATER CLOSET
(NOT ALL ABBREVIATIONS ARE NECESSARILY USED ON THIS PROJECT)
DAN IONESCU I ARCHITECT$
253 Fifth Avenue New York, New York 10016 212.253.5577 www.diarch.net
j,, PIETRZAK & PFAU T ENC/NEER/NC & SURVEYINC,PLLC
262 Greenwich Avenue Suite A Goshen, New York 10924 845.294.0606 www.pietrzakpfau.com
Wexler l\ssociate5 Structural Engineers
12 West 32nd Street 8th Floor New York, New York 10001 212.643.1500 www.nwexler.com
111 WEST 33RD STREET 18TH FLOOR New York, New York 10001 212.967.8944 www.twigcon.com
FALLSBURG SUBMISSION 09.20.17
Issue:
DOB STAMP:
PROJECT:
PRIVATE RESIDENCE
ADDRESS:
TOWN OF FALLSBURG SULLIVAN COUNTY, NY
Project No:
Scale: NTS.
Date:
Drawn By:
Approved By:
CELLAR-ROOF PLUMBING SYMBOLS & NOTES
171042
9.20.2017
RS/CS
DI
Date:
~3 OF 83
P-101.00 Pn~tedon 9.20.2017
ii i
' '
' 1,
•
' 11 •
i