RBUPS Manual Rev1a
HYPERTEC UNINTERRUPTIBLE POWER SUPPLY
USER’S MANUAL
RBUPS1KVA RBUPS2KVA
RBUPS3KVA
2
Content
I General Safety Instructions .......................................................... 3
II. Conditions of Use ........................................................................ 3
III. Electrical Safety .......................................................................... 3
IV. Safe Operating Practices ........................................................... 4
V. Battery Information ..................................................................... 5
1.Summary. 1.1 Introduction .............................................................................. 6 1.2 Functions and characteristics .................................................. 6 1.3 Symbol Definitions ................................................................... 8
2.Product Introduction .................................................................... 9 2.1 Physical Attributes ................................................................... 9 2.2 The principle of the UPS ........................................................ 10 2.3 Model information .................................................................. 11
3.Installation .................................................................................. 11
3.1 Unpacking and inspection ...................................................... 11 3.2 Notes ..................................................................................... 11 3.3 UPS input connection ............................................................ 11 3.4 UPS output connection .......................................................... 12 3.5 Extended backup external battery connection option ............ 13 3.6 Installation .............................................................................. 14
4.Faceplate display and general operation ................................. 17 4.1 Faceplate Display and its control ........................................... 17 4.2 General Operation ................................................................. 20 4.3 Parameter setting .................................................................. 21 4.4 Parameters inquiry ................................................................. 25 4.5 Run mode .............................................................................. 27
5.Maintenance ................................................................................ 28
6.Troubleshooting and Specifications ......................................... 29 6.1 LED indication and warning table .......................................... 30 6.2 Troubleshooting ..................................................................... 32 6.3 EMC standard/Safety standard .............................................. 32 6.4 Product Performance ............................................................. 33 6.5 Communication interface ....................................................... 34
3
I. General safety instructions
This manual contains important safety instructions that should be followed
during the installation and maintenance of the UPS.
Please read this manual thoroughly before attempting to install or operate this
UPS.
DO NOT under any circumstances attempt to remove the UPS cover. It
contains hazardous voltages internally that may cause electric shock.
There are no user-serviceable parts inside. For service, please contact
your nominated service agent.
II. Conditions of Use
This equipment is designed for domestic use only. The manufacturer neither
recommends nor knowingly sells this product for use in critical life support
applications.
Intended for installation in a controlled environment. The controlled environment should be in accordance with the requirement s of the specification
Do not install or operate your UPS in or near water. Do not place UPS on an unstable cart, stand, table or other unsuitable
enclosure. Do not place UPS under direct sunlight or close to heat emitting sources. Do not place UPS power cord in any area where it may get damaged by
heavy objects. Placing magnetic storage media on top of the UPS may result in data
corruption. Your UPS provides conditioned power to connected equipment. Maximum
load must not exceed that shown on the UPS rating label. If uncertain, contact Legend.
III. Electrical Safety
DO NOT under any circumstances attempt to remove the UPS cover. It
may contain hazardous voltages internally that may cause electric shock.
There are no user-serviceable parts inside. For service, please contact
your nominated service agent.
The Hypertec UPS will provide a 220~240VAC 1φ(single-phase)power source. Please verify that this model matches your AC mains / load voltage requirements.
The Hypertec UPS must be earthed at all times during operation. This can
4
be achieved by only connecting the input power chord to a mains supply socket outlet with an integral earth terminal. A means of disconnecting the mains supply should be within 2 meters of the UPS.
Output sockets on the UPS are electrically live if the UPS is switched ON, even if the UPS is not plugged in to mains supply. The On/Off button on the UPS does not electrically isolate the internal parts. To isolate the UPS, firstly switch the UPS OFF, then unplug it from the socket outlet.
To reduce the risk of fire, use fuses with the correct rating when replacing fuses.
The UPS relies on your building wiring over-current protection, which must be rated at 16 amperes.
When using the communication features on the UPS, ensure the cabling connected to the USB communication port are kept separated by at least 25 mm from the power cords to and from the UPS input and outputs.
IV. Safe Operating Practices
This pluggable type A equipment has factory installed batteries, and hence may
be operated by anyone that has read and understood this manual.
During the installation of this equipment, it should be assured that the sum of
the leakage currents of the UPS and the connected loads does not exceed
3.5mA.
The mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily accessible.
When replacing batteries, replace with the same type and number of batteries.
Turn off and unplug your UPS before cleaning. Do not use liquid or aerosol cleaners. A dry cloth is recommended to remove dust from the surface of your UPS.
Do not handle any metallic connector before the UPS has been turned off and the power has been disconnected.
Turn off and unplug your UPS from the outlet and contact your nominated service agent if:
The power cord or plug is damaged. Liquid has been spilled on the UPS. The fuse blows frequently. The UPS does not operate even when user follows the operating
instructions.
5
V. Battery Information
CAUTION: Do not dispose of batteries in a fire, the battery may explode. CAUTION: Do not open or damage the battery or batteries, as released
electrolyte is harmful to the skin and eyes. A battery can present a risk of electric shock and high short circuit current.
The following precaution should be observed when working on batteries: Remove watches, rings or other metal objects. Use tools with insulated handles.
NOTE. The batteries used in your Hypertec UPS are maintenance free. This means that you DO NOT need to check the battery fluid levels. Trying to do so may cause injury to yourself, or may cause a fault with the battery / UPS.
The battery backup runtime is affected by the state of charge of the batteries, the age of the batteries and general condition of the batteries.
6
1. Summary
1.1 Introduction The Hypertec Uninterruptible Power Supply (UPS) provides uninterrupted,
high quality, efficient and reliable AC power to loads It also has functions for protection and monitoring of the UPS operation.
This series of 1KVA-3KVA products are designed as advanced ON-LINE
UPS that provide the multiple functions and good performance.
1.2 functions and characteristics
1.2.1 Digital Control Technology: Utilising high efficiency and high reliability controller algorithm design are used to optimize the output parameters of the UPS.
1.2.2 Self-Test diagnosis: A self test occurs before starting to find potential problems with the UPS to avoid any downtime.
1.2.3 Double conversion on-line topology: Makes the output of the UPS a Pure Sine Wave with consistent frequency and voltage. Other benefits are low noise and no interruption because of the main power fluctuation, hence providing more comprehensive protection for the attached equipment.
1.2.4 Intelligent function without surveillance: Output power is supplied automatically from the batteries when main power has failed. There is no transfer time when switching the output of the UPS when the main power fails or restores.
1.2.5 Bypass function: When the UPS meets a fault, it can transfer to bypass with no interruption to supply power to loads and provide alarm.
1.2.6 Advanced voltage compensation technology: This makes the input voltage range from 115v to 295v which reduces the battery usage and enhances the adaptive ability against inconsistent line power variation.
1.2.7 Advanced wide frequency input technology: The AC input frequency is 50Hz/60Hz making the input frequency range wider to allow load equipment of 60Hz specifications to be powered by the UPS. When the output frequency is 50Hz, the range of the AC input frequency is 45Hz-55Hz, When the output frequency is 60Hz, the range of the AC input frequency is 55Hz-65Hz.The UPS has good compatibility with a generator as the mains source and is suitable for different types of single-phase generators.
1.2.8 Advanced Power Factor Correction Technology (APFCT): With APFCT on the input of the UPS, the input power factor that can be achieved is greater than 0.98. It increases the power efficiency, removes the harmonic noise from UPS to utility and lowers the UPS operational cost. It really is an economical and environmentally friendly UPS.
1.2.9 ECO Function: This function can help you save electricity. When the input mains power is in a fixed range, the loads are supplied with power directly from the line source, while the inverter is on standby. If the input power becomes abnormal, the UPS will automatically transfer to backup to supply power to loads without
7
interruption.
1.2.10 Cold Start Capacity: When battery voltage is low, the UPS will protect itself and shut down automatically. When main power restores, the UPS will detect the main power and monitor it to determine whether the voltage and frequency are normal. If normal, UPS will turn on automatically to supply power to loads; if abnormal, UPS will start charger to charge the battery. The UPS will not turn on to supply power to loads until the voltage and frequency of the main power has been restored to normal conditions.
1.2.11 Emergency Start Function: When there is no main power, the UPS can be started by using a battery pack. It can meet the users’ emergency needs. The emergency start function is quite strong. In this scenario, the UPS can be started under a full load situation.
1.2.12 UPS Self - Protection Function: When the line power input/output voltage is too high or too low, overload, short-circuit, inverter temperature is too high, low voltage and overcharge of battery, network surge and so on, the UPS has inbuilt self protection mechanisms to prevent it being damaged.
1.2.13 Rack-Tower conversion LCD design. No matter what angle the display is to be viewed from, by simply pressing the key slightly can meet your perspective needs. The content displayed on the interface is rich. The capacity of the loads and the battery can be seen directly and the FLASH pictures and fan rotating icon can be displayed when charging. So it is easy to know it’s operation. When UPS fails, it can show the fault code, the machine can be maintained as soon as possible by inquiring fault code table.
1.2.14 The UPS can communicate with the computer using the included intelligent UPS monitoring software through either the USB or RS232 interface. All the parameters clearly displayed on the communication interface. The computer can control multiple functions of the UPS directly. With USB communication, the operation of the UPS can easily be monitored, even if the RS232 interface is occupied or connected at the same time. USB communications has priority.
1.2.15 Network monitoring: Via internal or an external SNMP adapter, UPS can go on the internet and provide the latest information and power messages. You can monitor and manage the UPS status through all kinds of network management systems.
1.2.16 In order to ensure the power of the important loads can last for a long time, you can plug the important loads into the second power down socket. When the battery voltage is below the predetermined value, only the first cut-off power socket is broken off, the second power down can keep on supplying power until the battery voltage reaches protect point and shut down.
1.2.17 Adopt international standard rack-mounted size. Whether you want to put it on the office desk or in the rack-mount as a system to manage, It can present your personal style with corresponding components.
8
1.3 Symbol Definitions
The safety symbols cited in this manual are shown in table 1-1, which are used
to inform readers of safety issues that should be obeyed when installation,
operation and maintenance.
Safety Symbol
Indication
Attention
Static discharge sensitive
Electric shock
There are three levers of safety grade: Dangerous, Warning and Attention. The
remark is on the right side of the safety symbol, the detailed comments is
behind, shown as following:
Dangerous
Indicate risk of serious injury or death or seriously damage the equipment
Warning:
Indicate risk of serious injury or damage the equipment.
Attention:
Indicate risk of injury or damage the equipment.
9
2. Product Introduction 2.1 Physical Attributes
Fig 1 Front Panel View
Fig 2 1KVA Rear Panel View
Fig 3 2KVA/3KVA Rear Panel View
10
2.2 The Principle of the UPS
Fig 4 UPS Principle Diagram
Input filter: Complete filtering of the input AC utility power to provide clean
power into the UPS. AC/DC converter: Convert the filtered AC mains to DC and boost the DC for
DC/AC inverter. DC/DC booster: When the UPS works in battery mode, the circuit boosts
the DC for the DC/AC inverter. DC/AC inverter: Converts the boosted DC to a stable AC output. Bypass: When the UPS is overloaded or in fault mode, it automatically
transfers to bypass mode to supply power to the loads. Charger: Standard unit provides 1A; extended backup unit provides 7A/14A. Battery: Sealed Lead Acid Battery. Output filter: Complete filtering the output of the UPS to provide clean
power for loads.
11
2.3 Model
UPS Type MODEL NO Remark
Standard unit
RBUPS1KVA Internal 1A charger, 2 high-rate 9AH batteries
RBUPS2KVA Internal 1A charger, 4 high-rate
9AH batteries
RBUPS3KVA Internal 1A charger, 6 high-rate
9AH batteries
Extended backup unit
(OPTIONAL)
RBUPS1KVAH Internal 6A/12A charger, external 24V battery
RBUPS2KVAHInternal 6A/12A charger, external
48V battery
RBUPS3KVAHInternal 6A/12A charger, external
72V battery
Notice: extended backup unit can choose two chargers connected in parallel, the charger current is 14A.
3. Installation 3.1. Unpacking and inspection
3.1.1. Unpack the UPS and check its condition to ensure no damage has occurred during transportation. Also check the contents of the box against the contents list in this manual to ensure all contents are accounted for. If any damage has occurred or some parts missing, do not connect or use the UPS. Contact Legend for further advice.
3.1.2. Check if the equipment is what you ordered. You can confirm this through inspecting the ratings label on the back panel of the UPS.
3.2. Notes
3.2.1. Please place the UPS in a clean, stable environment, avoid the vibration, dust, too humidity, flammable gas and liquid, corrosive.
3.2.2. The ambient temperature around the UPS should be within in the range of 0℃~40℃. If the ambient temperature is above 40℃, it is a requirement that the rated value of the largest load be decreased by 12% with each 5°C temperature rise. The UPS is not to be operated in an environment where the highest temperature exceeds 50℃.
3.2.3. THE UPS should be placed in a sufficiently ventilated place.
3.3. UPS input connection
3.3.1. Only connect the UPS to the socket outlet using power cable that comes
with the UPS.
12
Fig 5 Input Connection
3.4. UPS Output Connection
3.4.1.
Fig 6 Output connections
13
3.5 Extended backup external battery connection (OPTIONAL)
Fig 7 Battery Connection
WARNING:
Before installing any additional battery units for longer backup time, ensure
that the UPS is turned off and the input power is also switched off (or the
input power plug is unplugged from the socket outlet)
Ensure that all plugs are correctly polarised and that the two terminals of
the battery are not short circuited in anyway.
Ensure any tools used are kept away from the two terminals as a precaution.
NOTICE:
When using the external battery, It is best to use external battery cable
which matches with the equipment.
When connecting load to THE UPS, first turn off load and then connect the
power cable and finally turn on load one-by-one.
Inductance loads such as motor, fluorescent lamp, copy cat are strictly
prohibited connecting to THE UPS to avoid damage.
Plug the UPS on the special socket with over-current protection, the power
socket that used should be connected with ground wire.
14
UPS is likely to have output voltage no matter whether the power input
cable is plugged in mains input socket. If you wish UPS have no output, first
break off the switch and then cancel the mains.
When connect laser printer, select the capacity of UPS according to the
UPS start power because the startup power is higher.
3.6 Installation
3.6.1. Plastic base installation
3.6.1.1. Remove the 2 plastic base brackets and the extender from their
packaging.
3.6.1.2. Inter-cross the fingers between one bracket and the extender and
flatten. See figure 8.
3.6.1.3. Now inter-cross the fingers of the other bracket with the extender
and flatten.
(A) (B)
(C) (D)
Fig 8 2KVA/3KVA(S/H) Plastic Base Bracket
3.6.2. Cabinet Installation Bracket Assembly
15
3.6.2.1. Fasten screws A & B, (2 x M4 screws) ( symmetrical on both sides,
a total of four)
Fig 9 Cabinet Installation Bracket Assembly
Fig 10 Cabinet Installation Bracket Assembly
3.6.3 Tower/Rack assembly
Fig 11 Standalone Tower Mount Assembly
16
Fig 12 Rack Mount Enclosure Assembly
17
4. Panel display and general operation The operation of the UPS is easy to understand and the instructions are clearly set out in the manual. No special training is required, however support is available upon request. Please contact Legend for further information.
4.1 Display and its Control
4.1.1. Key function
ON/OFF Key +
Press and hold these keys for more than half a second to turn on or turn off the UPS.
ROTATE Key +
Press and hold these keys for more than 2 seconds to rotate the LCD in any mode.
SELF-TEST/MUTE Key +
In Mains Mode or Economical Mode Press and hold the keys for more than 1 second for the UPS to run the self-test function.
In Battery Mode Press and hold the keys for more than 1 second to mute the UPS sound alarm.
INQUIRY Key or
o Non-Functional Setting Mode:
Press and hold the key for more than half a second (but less than 2 seconds) to indicate the menu items on the display in chronological order.
Press and hold for more than 2 seconds to sequentially scroll through the menu on the display every 2 seconds. If the key is again pressed and held for a short time, the display will show the output status.
o Functional setting mode:
Press and hold the key for more than half a second (but less than 2 seconds): Select the set option.
Function Setting Key
o Non-functional Setting Mode:
Press and hold the key for more than 2 seconds: Function setting interface.
o Functional Setting Mode:
Press and hold the key for more than half a second (but less than 2 seconds) to confirm the set option.
18
4.1.2. The description of LED display lamp functions
The LED’s on the display have specific functions. These are defined below.
Warning red LED is on: The UPS is in fault mode and has no output. For example: Overload beyond the allowed time, inverter fault, BUS fault, over temperature fault etc.
Bypass yellow LED is on: The UPS alarm is on. For example, Bypass Mode supply power and etc.
Battery yellow LED is on: The UPS alarm is on. For example, Battery mode supply power and etc.
Inverter green LED is on: The UPS is providing output power whether the source is mains, ECO mode or Battery Backup mode.
After starting the UPS, the four LED’s will turn on and then sequentially turn off. This sequence recurs several times until the UPS is functioning correctly.
For all LED indications for different modes, please refer to the LED/display panel and warning table in Appendix 2.
4.1.3. LCD display functions When the UPS is Tower Mounted, the LCD display should be orientated as
following Fig 13a. Press and hold the ROTATE keys for more than 1 second, the display will begin to rotate. Stop pressing the keys once the orientation is correct.
When Rack Mounted, the LCD displays as following Fig 13b.
19
Fig 13a. Tower Mounted Display Orientation Fig. 13b. Rack Mounted Display Orientation
The display comprises of a Numerical Value Section, a Capacity Graphics Section, a Fan Status Graphics Section and a Charger Status Graphics Section.
Numerical value section: Displays the corresponding numerical value of inquiring items(output, load, temperature, input, battery), for example, as the graphics shows above, the output voltage is 220v, the output frequency is 50Hz.
Capacity Graphics Section: Displays the capacity of the battery and load.
Every segment represents 20% capacity. As graphics shows above, the capacity of the battery is 80%-100% (5 segments). When, the load reaches 40%-60% (3 segments). When the UPS is overloaded, the icon will flash. When the battery capacity is too low or disconnected, the icon will also flash.
Fan Status Graphics Section: Displays if the fan is working correctly. When the fan works correctly, it will show the dynamic fan blades rotating; If the fan is not correctly working, the icon will keep on flashing and the alarm sound will occur.
Charger Status Graphics Section: Displays the status of the charger. When charger operates normally, the corresponding icon will vary dynamically and sequentially as shown in fig. 14a. When the charger works abnormally, the icon will flash as a whole as in Fig. 14b. When UPS is in battery mode, the number of the icons of the charger-state section will vary according to the changeable capacity of the battery (segments). For example, when there are five segments as in Fig. 14a, the corresponding number of icons is five rows as shown in Fig. 14c.
Fig 14a. Charger Status Graphics Section when correctly operating
20
Fig 14b. Charger Status Graphics
Section when in fault mode
Fig 14c. Battery Capacity indicator as on
the display when in Battery Mode
4.2 Operation
4.2.1 Start up operation
Turning on of the UPS in Line mode
o Once the mains power plug is plugged in, the UPS will start to charge the battery. The display shows that the output voltage is 0, which means UPS has no output. If it is expected to have output through Bypass mode, this can be done by setting the bps to “ON” through the settings menu.
o Press and hold the ON/OFF key for more than half a second to start the UPS, then it will start the inverter.
o Once started, the UPS will perform a Self Test and LED’s will turn on and then turn off in a sequential manner. When the self test finishes, it will change to line mode wand the corresponding LED’s will turn on. The UPS is now in line mode and is operational.
Turning on the UPS in Battery mode
o When mains power is disconnected, press and hold the ON/OFF key for more than half a second to start the UPS.
o The operation of UPS during start up is identical to that when mains power is available, with the exception that after the self test, the LED’s will indicate it is in battery mode and the mains is not available.
4.2.2 Turn off operation
Turning off of the UPS in line mode
o Press and hold the ON/OFF key for more than half a second to turn the UPS and inverter off.
o After the UPS has shut down, there will be no output and all LED’s will turn off. If output is needed, , this can be done by setting the bps to “ON” through the settings menu.
Turning off of the UPS in Battery mode
o Press and hold the ON/OFF key for more than half a second to turn the UPS off.
o When turning off the UPS, it will do self-testing firstly. The LED’s will turn on and the sequentially turn off until there is no display on the panel.
4.2.3 Generator operation The following process must be performed if the UPS is to be connected to a generator as the source of the AC input: First turn on generator and let it run according to its manufacturers
recommendations to obtain a stable output voltage.
21
Once the generator voltage has stabilised, connect to UPS input plug to the generator socket outlet.
Turn the UPS on. Once the UPS has turned on, connect loads one-by-one. It is recommended that the output capacity of the generator be twice the
UPS rated capacity It is not recommended that the UPS be put into ECO mode if the quality of
the input AC mains is not good.
4.2.4 UPS self-test / mute operation.
With the UPS is in line mode: o Press and hold the self-test/mute key for more than 1 second, The
LED’s will turn on and the sequentially turn off. The UPS will go into self-test mode and test its status. It will exit automatically after finishing the test and return to its operational status that it was in prior to the test.
When the UPS is in battery mode, press and hold the self-test/mute key for more than 1 second, the sound alarm will stop beeping. If you press and hold the self-test/mute key for one more second, it will restart to beeping.
4.3 Parameter setting
The UPS has settings function. It can be run when the UPS is in any mode. After setting, it will become effective at once when meets some standards. The set information can be saved only when the battery connected and normally turning off the UPS.
The operation that can be set are as follows:
4.3.1 ECO mode setting(1)
① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, the letters “ECO” will flash ② Enter the ECO setting interface. Press and hold the function setting keyfor more than half a second(less than 2 seconds), then come to setting interface of ECO, at this time, the letters “ECO” will light for a long time. The “ON”(or OFF) below the ECO will flash. Press and hold the inquiring key for more than half a second (less than 2 seconds) to determine whether the ECO function is used or not. If used, the corresponding word is “ON”, if not, the word is “OFF”. It can be determined by yourself.
③ Confirm the ECO selecting interface. After selecting ON or OFF, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the ECO setting function is completed and the “ON” or “OFF” below the “ECO” will light without flash. ④Set the ECO tolerance range. Short press the scroll key or for more than half a second (shorter than 2 seconds)to select the voltage range in percentage. +5%,+10%,+15%,+25%(default is +25%) , then short press
22
function setting key for more than half a second (shorter than 2 seconds)to confirm the selection, then to set the minus range ⑤To set the minus range in the same way. ⑥ Exit from the setting interface. Press and hold function setting key for more than 2 seconds, exit from the setting interface and turn to main interface.
4.3.2 Bypass mode setting(2)
① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the function setting key for more than half a second(less than 2 seconds), select the function setting, choose the bypass output interface, at the moment, the letters “bPS” will flash
② Enter the Bypass output selecting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of bPS, at this time, the letters “bPS” will light for a long time. The “ON” below the bPS will flash. Press and hold the inquiring key for more than half a second (less than 2 seconds) to determine whether the bPS function is used or not. If used, the corresponding word is “ON”, if not, the word is “OFF”. It can be determined by yourself. ③ Confirm the Bypass output selecting interface. After selecting ON or OFF, press and hold the function setting key for more than half a second (less than 2 seconds), Now, the bPS setting function is completed and the “ON” or “OFF” below the “bPS” will light without flash. ④ Set the BPS tolerance range. Short press the scroll key or for more than half a second (shorter than 2 seconds)to select the voltage range in percentage. +5%,+10%,+15%,+25%(default is +25%) , then short press function setting key for more than half a second (shorter than 2 seconds)to confirm the selection, then to set the minus range
⑤ To set the minus range in the same way. ④ Exit from the setting interface. Press and hold function setting key for more than 2 seconds, exit from the setting interface and return to main interface. ⑤ After setting bPS as ON, when mains power plugged in without turning on the UPS or no mains power plugged in, there is bypass output but no power down backup function.
4.3.3 Output voltage setting(3)
① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the inquiring key for more than half a second(less than 2 seconds), select the function setting, choose output voltage setting interface, at the moment, the letters “OPU” will flash
23
② Enter the output voltage selecting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of output voltage OPU, at this time, the letters “OPU” will light for a long time. The numerical value below the OPU will flash. Press and hold the inquiring key for more than half a second (less than 2 seconds), select the numerical value in accordance with “OPU” function. The provided voltages are 208V,220V, 230V, 240V you can choose anyone by yourself (The default is 220v). ③ Confirm the output voltage selecting interface. After selecting numerical value, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the OPU setting function is completed and the numerical value below the “OPU” will light without flash. ④ Exit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface. NOTE:When setting the output voltage, you’d better cut off the load of the UPS first.
4.3.4 Battery Pack (EBP) number and type setting(4)
① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the scroll key for more than half a second(less than 2 seconds), select the function setting, choose battery setting interface, at the moment, the letters “bAt” will flash.
② Enter the battery setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of battery, the letters “bAt” will stop flashing. The numerical value below the “bAt” will flash. Press and hold the scroll key for more than half a second (less than 2 seconds), select the numerical value in accordance with the real connected battery packs. ③ Confirm the battery packs setting interface。 After selecting numerical value, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the battery packs setting is confirmed and the battery type value below will flash。
24
④ set the battery type in the same way. ⑤ Exit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
4.3.5 Load segment setting(5)
① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the scroll key for more than half a second(less than 2 seconds), select the function setting, choose battery setting interface, at the moment, the letters “Seg 1” will flash.
Enter the load segment setting interface. Press and hold the function setting ②
key for more than half a second(less than 2 seconds), then come to setting interface of load segment, the letters “Seg 1” will stop flashing. The numerical value below the “Seg 1” will flash. Press and hold the scroll key for more than half a second (less than 2 seconds), select the battery voltage, 10.5v,11.0v,11.5v(default is 10.5v)。
Confirm the power sheddi③ ng shielding battery voltage setting. After selecting numerical value, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the load shielding battery voltage setting is confirmed.
Exit from the setting interfac④ e. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
4.3.6 Automatic Battery Test mode setting(6)
① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the inquiring key for more than half a second(less than 2 seconds), select the function setting, choose Automatic Battery Test setting interface, at the moment, the letters “Abt” will flash ② Enter the “Abt” setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of “Abt”, at this time, the letters “Abt” will light for a long time. The “ON”(or OFF) below the “Abt” will flash. Press and hold the inquiring key for more than half a second (less than 2 seconds) to determine whether the “Abt” function is used or not. If used, the corresponding word is “ON”, if not, the word is “OFF”. It can be determined by yourself.
25
③ Confirm the “Abt” selecting interface. After selecting ON or OFF, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the “Abt” setting function is completed and the “ON” or “OFF” below the “Abt” will light without flash.
Exit from the setting interface. Press and hold function setting key④ for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
If used, the corresponding word is “ON”,One month periodically check the battery connections.
4.3.7 Warning Code Display mode setting(7)
① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the inquiring key for more than half a second(less than 2 seconds), select the function setting, choose Warning Code Display setting interface, at the moment, the letters “wc” will flash
② Enter the “wc” setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of “wc”, at this time, the letters “Abt” will light for a long time. The “ON”(or OFF) below the Abt will flash. Press and hold the inquiring key for more than half a second (less than 2 seconds) to determine whether the “wc” function is used or not. If used, the corresponding word is “ON”, if not, the word is “OFF”. It can be determined by yourself.
③ Confirm the “wc” selecting interface. After selecting ON or OFF, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the “wc” setting function is completed and the “ON” or “OFF” below the “wc” will light without flash.
④ Exit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
26
If used, the corresponding word is “ON”,2~5 seconds cycle Warning Code, please refer to Warning Code information Table in Appendix1.
4.3.8 EPO Input Polarity setting(8)
① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the scroll key for more than half a second(less than 2 seconds), select the function setting, choose EPO Input polarity setting interface, the letters “EPO” will flash.
② Enter the EPO Input Polarity setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds) , the letters “EPO” will stop flashing. The letters below the “EPO” will flash. Press and hold the scroll key for more than half a second (less than 2 seconds), select the EPO input polarity, “+P”(open circuit execute EPO function) or “–P”(short circuit execute EPO function)
③Confirm the setting. After selecting EPO input polarity, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the setting is confirmed.
④Exit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
4.3.9 (Battery) End of discharge setting(9)
① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface ,short press the scroll key for more than half a second (less than 2 seconds) to select Eod setting, the letters “Eod” will flash.
②Enter the Eod setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds) at this time, the letters “Eod” will stop flashing.
27
③Set the Eod tolerance range. Short press the scroll key or for more than half a second (shorter than 2 seconds)to select the voltage range in percentage. 10.0V, 10.5V, 11.0V (default is 10.0V),then short press function setting key for more than half a second (shorter than 2 seconds)to confirm the selection, then to set the minus range
④After the minus range is confirmed. Long press function setting key for more than 2 seconds to exit setting menu..
4.3.9 Frequency Converter mode setting(10)
① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the scroll key for more than half a second(less than 2 seconds), select the function setting, choose output frequency setting interface, the letters “OPF” will flash.
② Enter the output frequency of converter mode setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds) , the letters “OPF” will stop flashing. The letters below the “OPF” will flash. Press and hold the scroll key for more than half a second (less than 2 seconds), select the output frequency, “50Hz”(output fixed to 50Hz and active converter mode) or “60Hz”(output fixed to 60Hz and active converter mode) or “IPF”(inactive converter mode and active normal mode)
③ Confirm the setting. After selecting converter mode output frequency, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the setting is confirmed.
④ Exit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
IPF:UPS output frequency with the same frequency as the mains input.
50.0Hz:UPS output frequency is fixed at 50.0Hz, independent of the mains input frequency .
60.0Hz:UPS output frequency is fixed at 60.0Hz, independent of the mains input frequency.
4.4 Parameter inquiry
Press and hold the inquiring key or for more than half a second (but less than 2 seconds) to inquire about specific parameters. The inquired items include input, battery, output, load, temperature. The items displayed on the display are shown as follows: Output:Displays the output voltage and output frequency of the UPS. As
demonstrated in the following figure, the output voltage is 220v, the output frequency is 50Hz.
28
Load: Displays the numerical value of the active power (WATT) and apparent power (VA) of the load. As demonstrated in the following figure, the WATT of the load is 100w, VA is 100VA (when the load is disconnect, it is a normal phenomenon to show a small numerical value of WATT and VA).
Temperature: Displays the temperature of the inverter in the UPS. As demonstrated in the following figure. The temperature of the inverter is 37℃.
Input: Displays the voltage and frequency of the input. As demonstrated in the following figure, the input voltage is 210v, input frequency is 49.8Hz.
29
Battery: Display the voltage and capacity of the battery (determined by
type). As the following graphics shows: the battery voltage is 28v, the capacity of battery is 100 % (the capacity of battery is approximately reckoned according to the battery voltage).
By pressing and holding the inquiring key for more than 2 seconds, a sequential display of the inquiry items will occur, changing every 2 seconds Press and hold the key for some time again for it to return to output status.
4.5 Run mode
4.5.1 Bypass mode
LED indications on the front panel when in bypass mode are as follows:
The BYPASS yellow LED is on and the buzzer beeps once every 2 minutes. The warning red LED is also on when beeping. The exact load and battery capacity are displayed.
Changing to bypass mode occurs under the following two conditions:
Turn off the UPS in line mode while start the bypass output. Overload in line mode.
NOTE: When the UPS is in bypass mode, there is no backup in the case of a mains fault.
30
4.5.2 Line mode
LED indicators on front panel in line mode are as follows:
The inverter green LED is on.
When the input AC mains meets the conditions for normal operation, the UPS will work in line mode.
4.5.3 Battery mode
LED indicators on the front panel in battery mode are as follows:
Both the inverter green LED and battery yellow LED are on, the buzzer beeps once every 4 seconds. The warning red LED is also on when beeping.
When the input mains fails or fluctuates out of the range allowed by the UPS, the UPS will automatically change to battery mode. The UPS will alarm when battery voltage is low and the UPS will shutdown once it has reached its minimum threshold to protect the batteries. The time before shutdown when in battery mode is dependant upon the state of charge of the batteries and the load attached to the UPS.
4.5.4 ECO mode
LED indicators on the front panel when in ECO mode are as follows: Both the inverter green LED and bypass yellow LED are on.
When the input mains meets the input range of the ECO the UPS will begin ECO mode operation. If input mains exceeds the range of ECO several times in a row in a minute but stays in inverting input range, UPS will change back to inverting mode automatically.
4.5.5 Fault mode
LED indicators on the front panel when in fault mode are as follows:
31
Fault mode(Display interface on which the fault code displays)
The UPS goes into fault mode if an overload fault, inverting fault and/or over-temperature fault occurs. The UPS cuts off the output and fault codes will be displayed. At that moment, you can press the mute key to make the buzzer stop beeping temporarily to wait for maintenance. You can also press the ON/OFF key to shut down the UPS until confirmation that there is no serious fault. NOTE: For information regarding fault codes, please refer to Fault Code Information Table in section 7.2.
5. Maintenance Only minimum maintenance is required for this series of UPS. The battery is a sealed lead acid battery and is maintenance free. It only needs to be kept charged to obtain the expected lifetime. The battery charger operates regardless of whether or not the UPS has been turned on, so long as the input power cord is plugged into a working socket outlet. This automatically maintains the state of charge of the batteries and provide protection for over-charging and deep discharging.
5.1 Battery maintenance
o It is recommended that the batteries are manually discharged and then
charged at least once every three to four months if UPS has not been
used for a long time or the mains input source has not had an
interruption. The battery will need to be fully discharge to low-voltage
protection shutdown. This then needs to be fully charged.
o In high ambient temperature areas, batteries should be manually
charged and discharged once every two months. The process is the
same as that described above.
o Under normal operation, the battery working life is about three years. If
you find that the battery does not operate correctly and is shortening
32
the backup time or the battery voltage fluctuates, then the UPS
batteries should be checked, and possibly replaced, as soon as
possible. This must only be performed by qualified personnel.
o When replacing the batteries, it is recommended to change all the
batteries rather than changing the batteries individually on separate
occasions. Failing to do this, may result in permanent damage to your
charging circuit due to the variances in battery performance.
NOTICE:
Before replacing batteries, ensure to turn off the UPS and turn off or
disconnect the mains supply. Remove any metallic jewellery on your hands
such as rings, watch, bracelets and so on as a safety precaution.
When replace batteries, please use the screwdriver with insulating handle.
Do not lay the tools or metallic goods on the battery.
Never revert or short circuit between the battery anode and cathode.
6. Troubleshooting and performance of
product
The following messages are the information that users would find on the UPS
display when a possible fault occurs. Users can judge if the fault is caused by
external factors and determine how to deal with it by making full use of the
information.
Fault indicator on, indicates that the UPS has detected some fault.
Buzzer beeps, indicates that UPS need to be paid attention to, if beeps for a
long time, it means that there is something wrong with the machine.
If support is required, contact Legend. The following information should be
provided to help with fault analysis:
o The UPS MODEL NO. and SERIAL NO.
o The Date the fault happened.
o A Detailed description of the problem (include indicator statements on
display and LED panel)
33
6.1 LED indication and warning table
Table 6a:Warning and Fault Codes
Table 6b:The corresponding working status of indications
NO Working status Indication
Warning Remarks Nor Bat Bps Fau
1 Line mode
Normal voltage ● None
High/low voltage protection, turn to battery mode
● ● ★ Once every four seconds
2 Battery mode
Normal voltage ● ● ★ Once every
four seconds
Battery Voltage abnormal warning ● ★
★ Once per
second
3 Bypass mode
Main AC Normal voltage in bypass
mode ● ★ Once every
two minutes Eliminate after starting
the UPS
Main AC high voltage warning in
bypass mode ★ Once every
four seconds
Main AC low voltage warning in
bypass mode ★ Once every
four seconds
4 Battery disconnect warning
Bypass mode ● ★ Once every four seconds
Affirm if the battery switch is closed
Inverting mode ● ★ Once every four seconds
Affirm if the battery switch is closed
Power up or start Six times Affirm if the battery is connected well
5 Output overload protection
Overload warning in line mode, ● ★ Twice per
secondsRemove the less important loads
Overload in line mode, protection ● ● Long beeps
Remove the less important loads
Overload warning in battery mode ● ● ★ Twice per
secondRemove the less important loads
34
Overload in battery mode,
protection ● ● ● Long beeps Remove the less
important loads
6 Overload warning in bypass mode ● ★ Once every 2
secondsRemove the less important loads
7 Fan fault (fan icon flash) ▲ ▲ ▲ ★ Once every 2
secondsCheck if the fan is blocked by object.
8 Fault mode ● Long beeps
If display fault code and icon lights, contact for maintenance when you can’t deal with it by yourself.
● _indicator lights for a long time
★ _indicator flashes
▲ _the status of indicator depends on other conditions
NOTE: When UPS has fault, it is convenient for you to know the working status of UPS and the
exact information about the fault promptly by referring to the two tables listed above.
6.2 Troubleshooting
When a fault occurs, refer to the table below to attempt to troubleshoot the fault. If the fault still exists, please contact Legend.
Fault Cause Solution
The “INPUT” letters on LCD display section flashes
Anti-connection of mains live and neutral or mains is out of range
Re-connect the input power cable and make a correct connection
Battery capacity indicator flashes
Battery low voltage or battery disconnected
Check UPS battery, connect battery well, if battery damaged, replace it
Mains normal, but UPS has no input
UPS input breaker open circuit
Press the breaker for reset
Short back up time
Battery not fully charged
Keep UPS connecting with mains power for more than 8 hours, recharge battery
UPS overload Check the usage of loads, remove some redundant devices
Battery aged When replace battery, contact franchiser to get battery and relative assembly
UPS doesn’t startup after pressing the ON key
Didn’t press the combination keys of “on”
Press the two keys at the same time
UPS has no battery connected or battery voltage low and too many loads connected
Connect UPS battery well, if battery voltage low, please turn off UPS and remove some loads, then start UPS
Fault occurs inside UPS
Contact supplier for servicing
35
The icon of charger status on LCD display flashes and buzzer beeps once per second
Charger doesn’t work normally or battery aged
Contact supplier for servicing
6.3 EMC standard/Safety standard
Our products conform to the following EMC and safety standards.
6.4 Product Performance
6.4.1 Electric performance
Model 1KVAS/H 2KVAS/H 3KVAS/H Rated capacity 900W/1KVA 1800W/2KVA 2700W/3KVA
input
input Single phase and earthing
Voltage range
160-290VAC @ full load 140-290VAC @70%< load≤80% 120-290VAC @60%< load≤70%
110-290VAC @load≤60%
Frequency range 46Hz-54Hz±0.5Hz@50HZ or 56Hz-64Hz±0.5Hz@60HZ
Power factor ≥0.98 Current harmonic < 7% (100% linear load )
output
Output style Single phase and earthing Rated voltage 200/208/220/230/240VAC Power factor 0.9
Voltage precision ±2%
Output Fre-quency
Line mode
1、When input frequency is in the range,the output frequency Sychronized with the utility on AC mode. 2、When input frequency is out of the range,the output frequency is (50/60 ± 0.2) Hz when turn to battery mode
Battery (50/60 ± 0.2) Hz Crest ratio 3:1
Transfer time Mains ←→ battery = 0ms Mains ←→ bypass < 4ms
Overload capacity >110%, 30s turn to bypass mode;
EMC standard number Safety standard number IEC62040-2 IEC 62040-1
IEC61000-4-2 AS 62040-1
IEC61000-4-3 GB 4943-2005
IEC61000-4-4
IEC61000-4-5
36
>150%, 300ms turn to bypass mode
efficiency
Line mode
Full load ≥ 90%
Battery mode
Full load ≥ 85%
ECO mod
Full load ≥ 94%
Output voltage distortion
≤3% (100% linear load ) ≤5% (100% nonlinear load )
Battery
Input battery voltage 24VDC 48VDC 72VDC Internal battery
capacity 2 4 6
Internal battery type 12V/9AH sealed lead acid maintenance free battery ( only refers
to standard UPS )
Backup time Full load ≥ 4min(only refers to standard UPS),As for long backup UPS, the backup time is determined by the capacity of battery.
Charge current(A)
1.2/6/12 1.2/6/12 1.2/6/12
NOTE: The rated output voltage has been already provided. The function of setting the rated output voltage by LCD menu is an optional. Operational Environmental Specification
Model 1KVA-3KVA series
Ambient Temperature 0℃~40℃
Relative humidity 0~95% non-condensing
Altitude <1500m. when >1500m, lower the rated power for use
Store temperature t -25℃~55℃
Mechanical Specification
Model Dimension
W*D*H (mm)
Net
weight/Gross
weight(kg)
1KVAS 440*380*86.5
12/14.5
1KVAH 7/9.5
2KVAS
440*520*131
21.5/24.3
2KVAH 11.5/14.3
3KVAS 26/28.8
3KVAH 11.7/14.5
37
6.5 Communication interface
6.5.1 RS232 communication interface
This UPS provides a standard DB9 communication interface on its rear panel. The wiring specifics of the pins are as follows:
6.5.2 RS232 cable specifications
When connecting the UPS to a PC using a RS232 cable, a standard RS232 cable with the following pin configurations is to be used.
PIN 1(hole)to PIN 2
2 2
3 3
5 5
6.5.3 Optional communication interface
USB communication interface
USB communication interface: Install the intelligent monitoring software UPSilon2000 that comes with the UPS. Monitoring of the UPS can now be implemented by direct connection of the UPS to the PC. When both RS232 and USB are connected, Priority is given to the USB interface.
Intelligent slot The following intelligent cards can be installed into the intelligent slot of the UPS: intelligent USB card, intelligent SNMP card and intelligent dry contact card. The expansion cards support plug and play installation. Any type of these expansion cards should be used according to their instruction manuals.
o Intelligent USB card: Use the monitoring function of the USB interface system to monitor and manage the power source of the UPS.
o Intelligent SNMP card: When connecting to the internet by SNMP card, it communicates with the monitoring computer to monitor power source of the UPS remotely.
38
o Intelligent dry contact card: Use the monitoring function of the dry contact interface system to monitor and manage the power source of the UPS.
NOTE:
o Remove the cover before installing the optional accessories. o The operating instruction of the UPSilon monitoring software can be
found on the installation CD. o The operating instructions of the intelligent USB card, SNMP card and
dry contact card should come with the expansion cards themselves. Others contact their manufacturers.