Transcript
Page 1: FRP Louver - Moffitt · FRP Louver fiberglass louver Page 72.1.5. of 8 PANTHER series (800) 474-3267 | MoffittHVAC.com Page 7 of 8 FRP Adjustable Blade Louver Guide Specification

(800) 474-3267 | 1351 13th Ave S. Suite 130 Jacksonville Beach, FL 32250 | MoffittHVAC.com

FRP Louver FRP Louver

PANTHER series FRP Natural Ventilation

Ventilation's Natural Solution since 1961

Page 2: FRP Louver - Moffitt · FRP Louver fiberglass louver Page 72.1.5. of 8 PANTHER series (800) 474-3267 | MoffittHVAC.com Page 7 of 8 FRP Adjustable Blade Louver Guide Specification

FRP Louver fiberglass louver

Page 1 of 8

PANTHER series Page 1 of 8 (800) 474-3267 | MoffittHVAC.com

FRP Louver Table of Contents

FRP Louvers Table of Contents ..................................................................................................................... 1

FRP Louver Product Details ........................................................................................................................... 2

FRP Adjustable Blade Louvers; 45° & 90° ..................................................................................................... 3

FRP Fixed Blade Louvers; 45° ........................................................................................................................ 4

FRP Fixed Blade Louvers; 45° cont. ............................................................................................................... 5

FRP Pictures .................................................................................................................................................. 6

FRP Adjustable Blade Louver Guide Specification ........................................................................................ 7

FRP Fixed Blade Louver Guide Specification ................................................................................................. 8

Page 3: FRP Louver - Moffitt · FRP Louver fiberglass louver Page 72.1.5. of 8 PANTHER series (800) 474-3267 | MoffittHVAC.com Page 7 of 8 FRP Adjustable Blade Louver Guide Specification

FRP Louver fiberglass louver

Page 2 of 8

PANTHER series Page 2 of 8 (800) 474-3267 | MoffittHVAC.com

FRP Louver Product Details

STANDARD FEATURES

Construction: Hetron 99P ® polyester resin

with UV inhibitor, synthetic veil, Class 1

flame spread of 25 or less.

Minimum size: 12” wide x 24” high.

Maximum Size: 60” wide x 120” high.

Frame: 6” deep channel, 1/4” thick.

Blades: 1/8” thick, Center or end pivot.

Pivots and Bearings: Fiberglass Reinforced

Polypropylene.

Linkage: Fiberglass reinforced

polypropylene & FRP control arm.

Operating Range: Opens to 45°.

Dampers: Parallel Blade, Gravity Back draft

type.

OPTIONAL FEATURES

Dampers: Opposed Blade configurations

available.

Color: available on large orders.

Hardware:

o 316 SS

o Monel

Screen: 1/2” mesh Polyethylene Bird

screen, polyethylene insect screen, or

stainless steel screen.

Mullion covers for multiple installations.

Operating Range: Opens full 90°

Wall Mounting: Sleeves or Flanges

Operators:

o Manual locking hand quadrant

o Chain

o Motor

Mounting Clips or Fasteners

Capping Strips

Stop Pins.

PRODUCT DESCRIPTION

Moffitt Corporation Fiberglass Wall Louvers are fabricated for the rigors of industry. Designed to provide

maximum air flow at a minimum pressure drop and water entrainment. Offered in both stationary and

adjustable configurations, these fiberglass louvers are serviceable in hostile environments with excellent

chemical resistance, drainable blade designs and several mounting options.

Page 4: FRP Louver - Moffitt · FRP Louver fiberglass louver Page 72.1.5. of 8 PANTHER series (800) 474-3267 | MoffittHVAC.com Page 7 of 8 FRP Adjustable Blade Louver Guide Specification

FRP Louver fiberglass louver

Page 3 of 8

PANTHER series Page 3 of 8 (800) 474-3267 | MoffittHVAC.com

FRP Adjustable Blade Louvers; 45° & 90°

STANDARD FEATURES:

1. Construction: Hetron 99P® polyester resin, class 1 flame spread of 25 or less,

UV inhibitor, synthetic veil

2. Frame: 6” deep channel, 1/4” thickness

3. Blades: “K” style, 1/8” thickness

4. Pivots: 5/8” dia. fiberglass reinforced

polypropylene

5. Operator: Manual locking quadrant

6. Bearings: Fiberglass reinforced

polypropylene

7. Linkage: Fiberglass reinforced

polypropylene brackets and FRP control

arm

8. Hardware: 304 stainless steel

9. Operating Range: 45°

10. Minimum Size: 12” wide x 24” high

11. Maximum Size: 60” wide x 120” high

12. Colors: Standard Gray

OPTIONAL FEATURES:

1. Color to Match: (Must meet quantity requirements)

2. Operating Range: Full 90°.

3. Off-center pivots prevent blade extension past front of

louver frame

4. Hardware: 316 stainless steel

5. Screen (Mounted on Rear of Louver): 1/2”

polyethylene mesh, 3/4” polyethylene mesh,

polyethylene insect screen, stainless steel

6. Mullion covers for multiple installations

7. Mounting clips and fasteners

8. Operator: Vinyl coated cable or electric motor

*NOTE: Opening size is normally 1/4”larger

than louver size. Structural support of louver

in opening by others. Screen adds

approximately 1/2” to depth

Frame Construction

Page 5: FRP Louver - Moffitt · FRP Louver fiberglass louver Page 72.1.5. of 8 PANTHER series (800) 474-3267 | MoffittHVAC.com Page 7 of 8 FRP Adjustable Blade Louver Guide Specification

FRP Louver fiberglass louver

Page 4 of 8

PANTHER series Page 4 of 8 (800) 474-3267 | MoffittHVAC.com

FRP Fixed Blade Louvers; 45°

STANDARD FEATURES:

1. Construction: HETRON 99P® polyester resin,

class 1 flame spread of 25 or less, UV

inhibitor, synthetic veil

2. Frame: 6” deep channel, 1/4” thickness

3. Blades: “K” style, 1/8” thickness

4. Screen: 1/2” mesh 19 ga. galvanized

5. Minimum Size: 12” wide x 24” high

6. Maximum Size: 60” wide x 120” high

7. Colors: Standard Gray

OPTIONAL FEATURES:

1. Color to Match: (Must meet quantity

requirements)

2. Hardware: 316 stainless steel, Monel

3. Screen: 1/2” polyethylene mesh, 3/4”

polyethylene mesh, polyethylene insect screen, stainless steel

4. Mullion covers for multiple installations

5. Mounting clips and fasteners

Dimensions are out-to-out of frame and

include flanges

Width

Hei

ght

12 24 36 48 60

24 .413 .996 1.580 2.163 2.746

36 .826 1.993 3.160 4.326 5.493

48 1.240 2.990 4.740 6.490 8.240

60 1.650 3.986 6.319 8.653 10.986

72 2.066 4.983 7.899 10.816 13.733

84 2.479 5.979 9.479 12.979 16.479

96 2.892 6.976 11.059 15.142 19.226

108 3.306 7.927 12.639 17.306 21.972

120 3.719 8.968 14.218 19.498 24.718

“K” BLADE - 45°

To determine minimum free area

required for the louver:

1. Divide the required CFM flow

by the maximum recommended

free area velocity.

2. Select the most desirable

louver size from the free area

table that meets the minimum

free area requirement.

NOTE: Ratings do not include the

effect of bird screen.

*NOTE: Opening size is normally 1/4” larger than

louver size. Structural support of louver in opening by

others. Screen adds approximately 1/2” to depth.

Page 6: FRP Louver - Moffitt · FRP Louver fiberglass louver Page 72.1.5. of 8 PANTHER series (800) 474-3267 | MoffittHVAC.com Page 7 of 8 FRP Adjustable Blade Louver Guide Specification

FRP Louver fiberglass louver

Page 5 of 8

PANTHER series Page 5 of 8 (800) 474-3267 | MoffittHVAC.com

FRP Fixed Blade Louvers; 45° cont.

Free Area Chart- Sq. Ft.

822 Beginning of Water Penetration

Free Area Velocity F.P.M. (Y)

Size

48"-48"

Wat

er

Pe

net

rati

on

oz.

per

Sq

. Ft.

(X

)

Fre

e A

rea

(15

min

. du

rati

on

)

Velocity thru Free Air (FPM)

Standard Air - .075 LB. per FT3

Pressure Drop

Page 7: FRP Louver - Moffitt · FRP Louver fiberglass louver Page 72.1.5. of 8 PANTHER series (800) 474-3267 | MoffittHVAC.com Page 7 of 8 FRP Adjustable Blade Louver Guide Specification

FRP Louver fiberglass louver

Page 6 of 8

PANTHER series Page 6 of 8 (800) 474-3267 | MoffittHVAC.com

FRP Pictures

Page 8: FRP Louver - Moffitt · FRP Louver fiberglass louver Page 72.1.5. of 8 PANTHER series (800) 474-3267 | MoffittHVAC.com Page 7 of 8 FRP Adjustable Blade Louver Guide Specification

FRP Louver fiberglass louver

Page 7 of 8

PANTHER series Page 7 of 8 (800) 474-3267 | MoffittHVAC.com

FRP Adjustable Blade Louver Guide Specification 1.1. DESCRIPTION

Furnish and Install Fiberglass 6” Adjustable Blade Louver and accessories as indicated on drawings.

1.2. QUALITY ASSURANCE MOFFITT (Jacksonville, FL, 1 800-474-3267) FRP Products establish the standard of quality required. Manufacturer and erector shall demonstrate a minimum of five (5) years of related industry experience.

1.3. SUBSTITUTIONS No substitutions will be considered unless written request for approval has been submitted by the bidder and has been received by the designer at least ten (10) days prior to bid date. Any proposed substitutions should meet the standards set by the specification.

1.4. SUBMITTALS Furnish approval drawings prior to fabrication and erection drawings prior to shipment showing all erection procedures and accessories required for the specified product.

2.1. CONSTRUCTION 2.1.1. Unit shall be constructed of isophalic polyester fire retardant resin equivalent to Hetron 99P® polyester resin with

a Class 1 flamespread of 25 or less. Ultraviolet inhibitors shall be incorporated into the resin. Louver sections shall include fiberglass unidirectional filaments and synthetic veil. Louver shall have a minimum of 40% glass by weight. Coloring shall be achieved by use of pigments impregnated through the entire profile.

2.1.2. Louver frames shall be 6" deep channel type and a minimum 1/4" thickness 2.1.3. Louver blades shall be "K" style design and a minimum 1/8" thickness, opening at 45°. 2.1.4. Louver bearings, pivots, linkages and brackets shall be fiberglass reinforced polypropylene. Control arms shall be

of fiberglass construction. 2.1.5. Louver blades shall operate by (fiberglass thumbscrew locking quadrant, pull cable operation, electric motor

operation). 2.1.6. Hardware shall be (304SS, 306SS, Monel).

2.2. OPTIONS/ACCESSORIES

Available accessories include: 1/2" mesh polypropylene bird screen mounted in removable PVC frame, SS screen, fiberglass mullion covers.

Page 9: FRP Louver - Moffitt · FRP Louver fiberglass louver Page 72.1.5. of 8 PANTHER series (800) 474-3267 | MoffittHVAC.com Page 7 of 8 FRP Adjustable Blade Louver Guide Specification

FRP Louver fiberglass louver

Page 8 of 8

PANTHER series Page 8 of 8 (800) 474-3267 | MoffittHVAC.com

FRP Fixed Blade Louver Guide Specification 1.1. DESCRIPTION

Furnish and Install Fiberglass 6” Stationary Blade Louver and accessories as indicated on drawings.

1.2. QUALITY ASSURANCE MOFFITT (Jacksonville, FL, 1 800-474-3267) FRP Products establish the standard of quality required. Manufacturer and erector shall demonstrate a minimum of five (5) years of related industry experience.

1.3. SUBSTITUTIONS No substitutions will be considered unless written request for approval has been submitted by the bidder and has been received by the designer at least ten (10) days prior to bid date. Any proposed substitutions should meet the standards set by the specification.

1.4. SUBMITTALS Furnish approval drawings prior to fabrication and erection drawings prior to shipment showing all erection procedures and accessories required for the specified product.

2.1. CONSTRUCTION 2.1.1. Unit shall be constructed of isophalic polyester fire retardant resin equivalent to Hetron 99P® polyester resin with

a Class 1 flamespread of 25 or less. Ultraviolet inhibitors shall be incorporated into the resin. Louver sections shall include fiberglass unidirectional filaments and synthetic veil. Louver shall have a minimum of 40% glass by weight. Coloring shall be achieved by use of pigments impregnated through the entire profile.

2.1.2. Louver frames shall be 6" deep channel type and a minimum 1/4" thickness 2.1.3. Louver blades shall be "K" style design and a minimum 1/8" thickness, opening at 45°. 2.1.4. Hardware shall be (304SS, 306SS, Monel).

2.2. OPTIONS/ACCESSORIES

Available accessories include: 1/2" mesh polypropylene bird screen mounted in removable PVC frame, SS screen, fiberglass mullion covers.


Recommended