Upload
gullipalli
View
395
Download
33
Tags:
Embed Size (px)
DESCRIPTION
wind load presentation asce 7-05
Citation preview
1S. K. Ghosh Associates Inc.
www.skghoshassociates.com
FREQUENTLY MISUNDERSTOOD IBC/ASCE 7 STRUCTURAL PROVISIONS
S. K. Ghosh and Susan DowtyS. K. Ghosh Associates Inc.
Palatine, IL and Aliso Viejo, CA
www.skghoshassociates.com
All sections referenced are from ASCE 7-05, unless otherwise noted.
PROVISION#1
Enclosure ClassificationFor Wind Design
Enclosure ClassificationSection 6.2 Definitions
Open Partially Enclosed (can experience
ballooning or suction effects caused by the build-up of internal pressure)
Enclosed
Internal Pressure
2S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Enclosure ClassificationSection 6.2 Definitions
OPENA building having each wall at least 80% open.
Ao 0.8 Agfor EACH side of the building
Enclosure ClassificationSection 6.2 Definitions
AO = A1 + A2 + A3 Ag = H W
Enclosure ClassificationSection 6.2 Definitions
Enclosure ClassificationSection 6.2 Definitions
Do stacks of hay obstruct flow of wind?
Enclosure ClassificationSection 6.2 Definitions
PARTIALLY ENCLOSED1.Ao 1.10Aoi2.Ao > 4 sq ft AND > 0.01Ag3. Aoi/Agi 0.20
Enclosure ClassificationSection 6.2 Definitions
Ao = total area of openings in a wall that receives positive external pressure
Aoi = sum of the areas of openings in the building envelope (walls and roof) not including AoAg = gross area of that wall in which Ao is identified
Agi = the sum of the gross surface areas of the building envelope not including Ag
3S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Enclosure ClassificationSection 6.2 Definitions
Note: Ao, Ag refer to wall that receives positive external pressure
Aoi , Agi refer to building envelope (walls and roof)
Enclosure ClassificationSection 6.2 Definitions
Openings : apertures or holes in the building envelope which allow air to flow through the building envelope and which are designed as open during design winds
Q: A: for Enclosure Classification
Q: Is a fixed glazed opening considered an opening?
A: NO.
Enclosure ClassificationSection 6.2 Definitions
ENCLOSEDA building that does not qualify as OPEN or PARTIALLY ENCLOSED.
Enclosure ClassificationSection 6.2 Definitions
Enclosure ClassificationFigure 6-5 Internal Pressure Coefficients,
GCpi
4S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Basic Wind Equation
For buildings with External and Internal Pressure:
p = qGCp qiGCpi
qi = Velocity pressure calculated for internal pressure.
ASCE 7-98 Positive Internal Pressure
ASCE 7-98 Negative Internal Pressure Q: A: for Enclosure Classification
Q: Why does a building need to be enclosed to use the Simplified Procedure?
A: See C6.4. GCpi = 0.18 is assumed in the tables. In a simple diaphragm building, internal pressures cancel out for the walls but not for the roof.
Q: A: for Enclosure Classification
Q: Should we treat roll-down doors and operable louvers as openings?
A: Yes and No.
PROVISION#2
Seismic and Wind Design of Parapets
5S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Common Earthquake Damage to Parapets
13.3.1 Nonstructural Component Seismic Design Force
Fp (min) = 0.3 SDS Ip Wp for SDS = 1.00,Fp = 0.30 IpWp
Fp (max) = 1.6 SDS Ip Wp for SDS = 1.00, Fp = 1.60 IpWp
Fp =0.4 ap SDS
(Rp / Ip)1 + 2zh Wp
13.1.3Nonstructural Component Importance Factor, Ip
Ip is based on 1. Whether component must function after
the design earthquake or2. Occupancy Category or3. Whether component contains hazardous
materials.Parapets: Ip is based on Occupancy
Category
Nonstructural Component ap and Rp
The values of ap range from 1.0 to 2.5 and can be taken as less than 2.5 based on dynamic analysis.
Rp values range from 1.0 to 12.0 (Tables 13.5-1 and 13.6-1).
Table 13.5-1 ap and Rp for Architectural Components
Architectural Component
ASCE 7-05
ap Rp
Cantilever Parapets 2.5 2.5
0.4SDS
1.2SDS
AA= 0.4SDS (1+2zA/h)
AB = 0.4SDS (1+2zB/h)
A
B
zA
zB
hFloor
Acceleration Distribution
Explanation of Fp Equation
Z = h for parapet design
6S. K. Ghosh Associates Inc.
www.skghoshassociates.com
The 7-in. concrete parapet shown forms part of a building assigned to SDC D with a component importance factor of 1.0. SDS= 1.0g at the site. Determine the strength-level seismic design moment in the parapet.
Example: Seismic Design of Parapets
Example: Seismic Design of Parapets
Weight of the parapet per linear foot isWp = 150 x 3 x 7/12 = 262.50 lb/ft
The seismic lateral force acting at the centroid of the parapet is given by ASCE Equation (13.3-1) as
Fp = (0.4apSDSIp / Rp)(1 + 2z/h )WpWhere Ip = component importance factor = 1.0
Example: Seismic Design of Parapets
SDS = 1.0g
Wp = weight of parapet = 262.5 lb/ft
ap = component amplification factor from ASCE Table 13.5-1 = 2.5
h = height of roof above the base = 20 ft
z = height of parapet at point of attachment = 20 ft
Example: Seismic Design of Parapets
Rp = component response modification factor from ASCE Table 13.5-1 = 2.5
Fp = (0.4 x 2.5 x 1.0 1.0 / 2.5) (1 + 2 x 20/20)Wp= 1.2Wp = 315 lb/ft
Neither ASCE Equation (13.3-2) nor (13.3-3) governs, and the bending moment at the base of the parapet is
Mp = 1.5 Fp = 472.5 lb-ft/ft
Example: Seismic Design of Parapets
Wind Forces on Parapets
ASCE 7-05 Figure C6-12
7S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Wind Forces on Parapets
ASCE 7-05 C6.5.11.5 For simplicity, the front and back pressures on the parapet have been combined into one coefficient for MWFRS design.
Wind Forces on Parapets
ASCE 7-05 Figure C6-12
Design Example
The main wind force-resisting system of a
5-story reinforced concrete office building
is designed following the requirements of
the 2009 IBC/ASCE 7-05 wind provisions.
Example Building
Example Building3 ft parapet
Design CriteriaLocation of building: Los Angeles, CaliforniaV = 85 mph (ASCE 7-05 Fig. 6-1)
Building is enclosed per definition under ASCE 7-05 Sec. 6.2
Assume Exposure B (ASCE 7-05 Sec. 6.5.6.3)Occupancy Category: II, I = 1.0 (ASCE 7-05
Table 6-1)
8S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Effects of Parapets on MWFRS loads
ASCE 7-05 Section 6.5.12.2.4:
pp = qpGCpn (ASCE 7-05 Eq. 6-20)qp = velocity pressure evaluated at the top of
the parapet= 0.00256 Kz Kzt Kd V2 I
GCpn = combined net pressure coefficient= +1.5 for windward parapet= -1.0 for leeward parapet
At top of parapet, h = 67.5 + 3 = 70.5 ft
Kz = 2.01(z/zg)2/ = 2.01(70.5/1200)2/7 = 0.894 (from ASCE 7-05 Table 6-3)
( = 7, zg = 1200 ft for Exposure B from ASCE 7-05 Table 6-2)
Velocity Pressure Exposure Coefficient, Kz
Topographic Effect Factor, KztWind Directionality Factor, Kd
Kzt = 1.0(Assuming the example building to be situated
on level ground, i.e., with H, as shown in ASCE 7-05 Fig. 6-4, equal to zero).
Kd = 0.85 (from ASCE 7-05 Table 6-4 for main wind force-
resisting system)
Effects of Parapets on MWFRS loadsqp = 0.00256 Kz Kzt Kd V2 I =
0.00256 0.894 1 0.85 852 1 = 14.06 psf
For windward parapet:pp = qpGCpn = 14.06 1.5 = 21.1 psf Force = 21.1 3 66 / 1000 = 4.18 kips
For leeward parapet:pp = qpGCpn = 14.06 (-1.0) = -14.06 psf Force = -14.06 3 66 / 1000 = -2.78 kips
Effects of Parapets on MWFRS loadsAt the roof level, 4.18 + 2.78 = 6.96 kips is to be added to the design wind force for MWFRS computed from the windward and leeward walls
Design of Parapets as ComponentASCE 7-05 Section 6.5.12.4.4:
p = qp(GCp GCpi) (ASCE 7-05 Eq. 6-24)qp = velocity pressure evaluated at the top of
the parapet= 0.00256 Kz Kzt Kd V2 I = 14.06 psf
GCp = External pressure coefficient from Figs. 6-11 through 6-17
GCpi = Internal pressure coefficient from Fig. 6-5
9S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Effective wind area of the parapet:Span = 3 ftWidth = 66 ft (> span/3)A = 3x66 = 198 ft2
External Pressure Coefficient, GCpLoad Case A (ASCE 7-05 Section 6.5.12.4.4)
Positive wall GCp = 0.68 (Figure 6-17 Zones 4 and 5)
Applied to front surface of the parapet
External Pressure Coefficient, GCp
Load Case A (ASCE 7-05 Section 6.5.12.4.4)Negative roof edge GCp = -1.76 (Figure 6-17
Zone 2*)Applied to back surface of the parapet
*Corner Zone 3 is treated as Zone 2 because the parapet is 3 ft high (Figure 6-17 Note 7)
External Pressure Coefficient, GCpLoad Case A (ASCE 7-05 Section 6.5.12.4.4)
GCp = 0.68 (-1.76) = 2.44GCpi = -0.18 for enclosed building (uniform
porosity)However, internal pressures on both surfaces of
the parapet cancel each other out.
p = 14.06 x 2.44 = 34.31 psf
External Pressure Coefficient, GCp
Load Case B (ASCE 7-05 Section 6.5.12.4.4)Effective wind area = 198 ft2
Positive wall GCp = 0.68 (Figure 6-17 Zones 4 and 5)
Applied to back surface of the parapet
External Pressure Coefficient, GCpLoad Case B (ASCE 7-05 Section 6.5.12.4.4)
Negative wall GCp = -0.76 (Figure 6-17 Zone 4)= -1.23 (Figure 6-17 Zone 5)
Applied to front surface of the parapet
External Pressure Coefficient, GCp
10
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Load Case B (ASCE 7-05 Section 6.5.12.4.4)
GCp = 0.68 (-0.76) = 1.44 (For Zone 4)= 0.68 (-1.23) = 1.91 (For Zone 5)
GCpi = -0.18 for enclosed building (uniform porosity)
However, internal pressures on both surfaces of the parapet cancel each other out.
p = 14.06 x 1.44 = 20.24 psf (Zone 4)= 14.06 x 1.91 = 26.85 psf (Zone 5)
External Pressure Coefficient, GCp
Clearly, Load Case A governs
Thus, design uniform wind pressure on the whole width of the parapet
p = 34.31 psf
Design of Parapets as Component
Q: A: for Wind Design of Parapet
Q: In Section 6.5.12.4.4 (parapets for C&C), the definition for the factor GCpi is based on the porosity of the parapet envelope. How is the porosity of the parapet determined?
Q: A: for Wind Design of ParapetA: In the case of parapets, it is expected
most cases to have uniform porosity, so the "enclosed" classification (+0.18, - 0.18) would be appropriate. However, if the two surfaces of the parapet are very different (one has openings, the other is fully sealed), the partially-enclosed case might be relevant.
Q: A: for Wind Design of Parapet
Q: What is the wind load on the parapet using Method 1, Simplified Procedure?
A: There is no clear answer. Some jurisdictions do not allow Method 1 to be used for buildings with parapets.
PROVISION#3
Torsion, Torsional Irregularity and Direction
of Seismic Loading
11
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
QE xe
V
ASCE 7-05 12.8.4 Horizontal Distribution of Forces
Rigid diaphragms Seismic story shear is to be distributed to elements
of seismic-force-resisting system based on stiffness of vertical-resisting elements
Flexible diaphragms Seismic story shear is to be distributed to elements
of seismic-force-resisting system based on tributary areas
Torsion Torsional moment due to difference in location of center of
mass and center of resistancemust be considered for rigid diaphragms
Accidental torsion For rigid diaphragms, must be included in addition to the
torsional moment Displacement of center of mass = 5% building
dimension perpendicular to direction of applied forces
ASCE 7-05 12.8.4 Horizontal Distribution of Forces Failure Torsion
1976 Philippines
12
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Amplification of Torsion For structures* assigned to SDC C, D, E, or F without flexible diaphragm and with horizontal irregularity Type 1a or 1b (Torsional Irregularity or Extreme Torsional Irregularity), the accidental torsion Mta at each floor level needs to be amplified by a factor:
Ax = max
1.2avg
2
3.0
*Not applicable to light-frame construction
Amplification of Torsion
A and B computed assuming Ax = 1.0
Adapted from ASCE 7-05 Figure 12.8-1
Torsional Irregularity Torsional Irregularity
Referenced in:Section 12.3.3.4 25% increase in seismic forces in connections in diaphragms and collectorsTable 12.6-1 Permitted analytical procedureSection 12.7.3 3-D structural model requiredSection 12.8.4.3 Amplification of accidental torsionSection 12.12.1 Design story drift based on largest difference in deflection Section 16.2.2 - 3-D structural model required in nonlinear response history procedure
Extreme Torsional Irregularity Extreme Torsional Irregularity Referenced in:Section 12.3.3.1 Prohibited in SDC E and FSection 12.3.3.4 25% increase in seismic forces in connections in diaphragms and collectorsSection 12.3.4.2 (Table 12.3-3) = 1.3Table 12.6-1 Permitted analytical procedureSection 12.7.3 3-D structural model requiredSection 12.8.4.3 Amplification of accidental torsionSection 12.12.1 Design story drift based on largest difference in deflection Section 16.2.2 - 3-D structural model required in nonlinear response history procedure
13
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Q: A: for Torsional Irregularity
Q: Do the torsional irregularity provisions apply to light-frame constructions?
A: Most likely, no. The torsional irregularity definition applies to diaphragms that are rigid or semirigid, which is typically not the case for light-frame construction.
Section 12.5.2 Direction of Loading
12.5.2 SDC B.The design seismic forces are permitted to be
applied independently in each of two orthogonal directions and orthogonal interaction effects are permitted to be neglected.
Section 12.5.2 Direction of Loading
12.5.3 SDC C.Structures that have horizontal structural
irregularity Type 5 of Table 12.3-1, shall use one of the following procedures.
ASCE 7-05 12.5.2 Direction of Loading
12.5.3 SDC C.a. Orthogonal Combination Procedure.
ELF, modal response spectrum, or linear response history analysis, with loading applied independently in any two orthogonal directions
100% + 30%
Section 12.5.2 Direction of Loading
12.5.3 SDC C.b. Simultaneous Application of Orthogonal
Ground Motion.
Linear or nonlinear response historyanalysis, with orthogonal pairs of groundmotion acceleration histories appliedsimultaneously.
14
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Section 12.5.2 Direction of Loading
12.5.4 SDC D, E or F.The orthogonal combination procedure shall
additionally be required for any column or wall that forms part of two or more intersecting seismic-force-resisting systems and is subjected to axial load due to seismic forces acting along either principal plan axis equaling or exceeding 20% of the axial load design strength of the column or wall.
PROVISION#4
REDUNDANCY
REDUNDANCY FACTOR, ASCE 7-05 Section 12.3.4
Note that = 1.0 when the SIMPLIFIED PROCEDURE of Section 12.14 is used.
SDC A NA
B & C 1.0
D, E & F 1.0 or 1.3
REDUNDANCY FACTOR, ASCE 7-05 Section 12.3.4
12.3.4 Redundancy12.3.4.1 Conditions Where
Value of is 1.012.3.4.2 Redundancy
Factor, , for SDC D through F
Section 12.3.4.1 for SDC D - F
= 1.0 for the following:
1. Structures assigned to SDC B and C.2. Drift calculation and P-delta effects.3. Design of nonstructural components.4. Design of nonbuilding structures, not
similar to buildings.
15
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Section 12.3.4.1 for SDC D - F
= 1.0 for the following:
5. Design of collector elements, splices and their connections for which load combinations with overstrength are used.
6. Design of members or connections where load combinations with overstrength are required for design.
7. Diaphragm loads determined using Eq. 12.10-1.8. Structures with damping systems designed in
accordance with ASCE 7-05 Chapter 18.
Section 12.3.4.2 for SDC D - F
= 1.0 or 1.3
= 1.3 unless ONE of two conditions is met.
If Condition # 1 is met, then = 1.0
If Condition #2 is met, then = 1.0
Both conditions do NOT need to be met
for = 1.0
Section 12.3.4.2 for SDC D - F
CONDITION #1 and CONDITION #2 only need to be checked at each story resisting more than 35% of the base shear.
Section 12.3.4.2 for SDC D - F
CONDITION #1:
Can an individual element be removed from the lateral-force-resisting-system without:
Causing the remaining structure to suffer a reduction of story strength > 33%, or
Creating an extreme torsional irregularity?
TABLE 12.3-3 REQUIREMENTS FOR EACH STORY RESISTING MORE
THAN 35% OF THE BASE SHEAR
CONDITION #2If a structure is regular in plan and there are at
least 2 bays of seismic force-resisting perimeterframing on each side of the structure in each orthogonal direction at each story resisting > 35% of the base shear.
Section 12.3.4.2 for SDC D - F
16
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Section 12.3.4.2 for SDC D - F
Seismic Force-Resisting Perimeter Framing
Two Bays
Q: A: for Redundancy
Q: How many bays are in a shear wall?A: Length of shear wall/ story heightor for
light-framed construction (defined in Section 11.2), 2 x length of shear wall/ story height
Q: A: for Redundancy
Q: Does the redundancy factor apply to the design of foundations?
A: Yes.
Q: I am using Condition #1 to determine for a wood-frame building. All of the shear walls are relatively long; in other words, the height of each shear wall (8) is less than its length (9, 10, 12). Can I assign = 1.0 because there are no shear walls with a h/l ratio > 1.0?
Q: A: for Redundancy
A: Yes. Q: A: for Redundancy
Q: We have a building that is 325 feet tall (31 stories) with shear walls. We are using Condition #1 to determine . When Table 12.3-3 uses the phrase height-to-length ratio, is that the height-to-length ratio within any story? Or is it referring to the overall height-to-length ratio which, for our building, would mean a height of 325 feet.
17
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Q: A: for Redundancy
A: The h/l ratio is intended to be story height-to-length ratio.
llll < 10 ft
h = 10 ft
Q: A: for Redundancy
Q: Can the value of be different at each level of the same building?
Q: A: for Redundancy
A: No, cannot be different at each level of the same building. However, depending on the structural system, can be different in the two orthogonal directions of the same building if Condition #1 is used.
Q: A: for Redundancy
Q: Why doesnt Table 12.3-3 address dual systems? If you have a dual system, can you assume = 1.0?
A: No.. Q: A: for RedundancyBraced frame, moment frame and shear wall
systems have to conform to redundancy requirements. Dual systems are also included, but in most cases are inherently redundant. Shear walls with a height-to-length aspect ratio greater than 1.0 have been included, even though the issue has been essentially solved by requiring collector elements and their connection to be designed for 0 times the design force.
18
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Q: A: for Redundancy
Q: Do you need to determine the redundancy factor for nonbuilding structures similar to buildings or can you assume the redundancy factor equals 1?
Q: A: for Redundancy
A: You need to determine the redundancy factor. If the code did not intend that the redundancy factor be determined for Nonbuilding structures similar to buildings, there would be an exception to Section 15.5.1 as is done in Section 15.6.
Q: A: for Redundancy
Q: Does the redundancy factor need to be determined if dynamic analysis is used?
A: Yes.
REDUNDANCY EXAMPLE
a
a
Wall AStiffness Ka
Wall BStiffness Kb
Wall CStiffness Kc
Wall DStiffness Kd
Wall EStiffness Ke
Wall FStiffness Kf
Wall GStiffness Kg
Wall HStiffness Kh
REDUNDANCY EXAMPLE
SDC D one story concrete shear wall building Ka = Kb = Kc = Kd = Ke = Kf = Kg = Kh = K All walls have the same nominal shear
strength, Vn. The story height is 18 feet. The length of each shear wall is 15 feet.
Let a denote the horizontal dimension of this building.
19
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
REDUNDANCY EXAMPLECONDITION #1 CONDITION #2
Step 1:Remove shear wall and see if story strength is reduced by more than 33%.
Step 2:See if there is an extreme torsional irregularity created.
Step 1:Check if structure is regular in plan.
Step 2:Are there at least 2 bays of.on each side in each orthogonal direction?
REDUNDANCY EXAMPLE
Check Condition #2 first (its easier)Q: How many bays are in a shear wall?A: Length of shear wall/ story heightor
for light-framed construction, 2 x length of shear wall/ story height.
For example: (15/18)(2) = 1.67 < 2
REDUNDANCY EXAMPLE
CONDITION #1:Removal of a shear wall or wall pier with a
height-to-length ratio greater than 1.0 within any story, or collector connections thereto, would not result in more than a 33% reduction in story strength, nor does the resulting system have an extreme torsional irregularity (horizontal structural irregularity Type 1b).
REDUNDANCY EXAMPLECONDITION #1
Step 1: Remove shear wall and see if story strength is reduced by more than 33%.
Step 2: See if there is an extreme torsional irregularity created by doing so.
REDUNDANCY EXAMPLE
a
a
Wall AStiffness Ka
Wall BStiffness Kb
Wall DStiffness Kd
Wall EStiffness Ke
Wall FStiffness Kf
Wall GStiffness Kg
Wall HStiffness Kh
REDUNDANCY EXAMPLE
Definition of Extreme TorsionalIrregularity in ASCE 7-05 Table 12.3-1:
Extreme Torsional Irregularity exists where the maximum story drift, computed including accidental torsion, at one end of the structure transverse to an axis is more than 1.4 times the average of the story drifts at the two ends of the structure.
20
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
REDUNDANCY EXAMPLE
The torsional stiffness about the center of rigidity (CR) is determined as:
=
REDUNDANCY EXAMPLEThe determination of extreme torsional
irregularity requires the evaluation of the story drifts a and b, as shown below.
a/3 2a/3
a/6CR
CM
V
a b
REDUNDANCY EXAMPLE
According to ASCE 7-05 Table 12.3-1, extreme torsional irregularity does not exist when
This can be transformed to
REDUNDANCY EXAMPLE
Assume that the story drift caused only by the lateral force V is equal to , and that is the rotation caused by the torsion T, then
This ratio is less than 2.33 only if /(a) is larger than 1.08.
REDUNDANCY EXAMPLE
Therefore, no extreme torsional irregularity is created and = 1.0.
(Note that the term 0.05a is for accidental torsion)
Thus, the horizontal structural irregularity Type 1b does not exist and the configuration qualifies for a factor of 1.0.
PROVISION#5
SEISMIC ANALYSISPROCEDURE SELECTION
21
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Seismic Analysis Procedure Selection
STATIC ANALYSISPROCEDURES
ASCE 7-05SECTION
Simplified DesignProcedure
12.14
Equivalent Lateral Force Procedure
12.8
Seismic Analysis Procedure SelectionDYNAMIC ANALYSISPROCEDURES
ASCE 7-05SECTION
Modal Response Spectrum Analysis
12.9
Linear Response History Analysis
16.1
Nonlinear Response History Analysis
16.2
Simplified Design ProcedureException to Section 12.1
EXCEPTION: As an alternative, the simplified design procedure of Section 12.14 is permitted to be used in lieu of the requirements of Sections 12.1 through 12.12, subject to all of the limitations contained in Section 12.14.
Note: Section 12.13 is Foundation Design
Simplified Design ProcedureSection 12.14
1. Occupancy Category I or II2. Site Class A, B, C, or D3. Three stories or less in height4. Bearing wall system or building
frame system5. through 12
Q: A: for Simplified Design ProcedureQ: What are the benefits of using the
Simplified Design Procedure?
A: Here are the benefits: = 1, o = 2.5. No period (T) determination. No triangular distribution of seismic forces. Determination of Fa simplified; Ss need not
exceed 1.5g. Drift need not be calculated
Seismic Analysis Procedure SelectionTable 12.6-1
*
**
* 12.3-1** 12.3-2
22
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Seismic Analysis Procedure SelectionTable 12.6-1
If a building is assigned SDC D, E, or F and has a T 3.5 Ts, then dynamic analysis procedure must be used.
(Ts is the period at which the flat-top portion of the response spectrum transitions to the descending (period-dependent) branch.)
Seismic Analysis Procedure Selection
Seismic Analysis Procedure SelectionTable 12.6-1
Dynamic Analysis is required if a building meets all of the following conditions:
SDC D, E, or FNot of light-frame constructionContains one of the following
irregularities:Torsional or Extreme TorsionalStiffness-Soft Story, Stiffness Extreme Soft Story, Weight (Mass) or Vertical Geometric
Seismic Analysis Procedure Selection
Seismic Analysis Procedure Selection Table 12.6-1
All structures of light frame construction, irrespective of height
Dynamic analysis never required
Seismic Analysis Procedure Selection Table 12.6-1
Occupancy Category I or II buildings of other construction not exceeding two stories in height
Dynamic analysis not required
23
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Seismic Analysis Procedure SelectionQ: In Table 12.6-1, it states Regular
Structures with T < 3.5Ts and all structures of light frame construction are permitted to use an Equivalent Lateral Force Analysis. Does this mean that the building must meet both conditions (regular with T < 3.5Ts and light frame construction), or does only one of these two characteristics need to be satisfied?
Seismic Analysis Procedure Selection
A: It does not mean "and." It means "or." Regular Structures with T < 3.5Ts are permitted to use Equivalent Lateral Force Analysis. All structures of light frame construction, irrespective of height, are also permitted to use Equivalent Lateral Force Analysis.
PROVISION#6
DRIFT AND BUILDINGSEPARATION
QE xe
V
Drift DeterminationSection 12.8.6
Step 1: Determine xe at each floor level where xe is the lateral deflection at floor level x determined by elastic analysis under code-prescribed seismic forces.
Step 2: Multiply xe by Cd given in Table 12.12-1, the product representing the estimated design earthquake displacement.
Drift DeterminationSection 12.8.6
Step 3: Divide xeCd by I, Importance Factor: x = xeCd /I
Step 4: Determine design story drift:x = x (x 1)
24
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Drift DeterminationSection 12.8.6 Story Drift
x = x x-1 < ax = Cd xe / I
Cd = deflection amplification factor
Allowable Drift
StructureOccupancy Category
I or II III IV
Structures, other than masonry shear wall structures, 4 stories or less with interior walls, partitions, ceilings, and exterior wall systems that have been designed to accommodate the story drift.
0.025hsx 0.020hsx 0.015hsx
Masonry cantilever shear wall structures 0.010hsx 0.010hsx 0.010hsx
Other masonry shear wall structures 0.007hsx 0.007hsx 0.007hsx
All other structures 0.020hsx 0.015hsx 0.010hsx
ASCE 7-05 Table 12.12-1
For seismic forceresisting systems comprised solely of moment frames in structures assigned to Seismic Design Categories D, E, or F, the
design story drift shall not exceed a / for any story. shall be determined in accordance with Section 12.3.4.2.
Allowable Drift Additional Requirement
ASCE 7-05 Section 12.12.1.1
Q: A: for Drift Determination
Q: Why is drift divided by the Importance Factor?
A: Because the forces under which xeare computed are already amplified by I, and the drift limits set forth in Table 12.12-1 are more restrictive for higher occupancy category buildings.
Q: A: for Drift Determination
Q: Is drift determined differently for allowable stress design (ASD) than for strength design (SD)?
A: No. The same procedure is used regardless of whether ASD or SD is used.
25
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Q: A: for Drift Determination
Q: Does minimum base shear need to be considered for drift determination?
A: Yes, Section 12.8.6.1 requires that all of the requirements of Section 12.8 be satisfied for the purpose of computing drift.
Q: A: for Drift Determination
Q: Does the upper-bound limitation on period T need to be considered for drift determination?
A: No. Section 12.8.6.2 does not require the period to be subject to the upper limit of CuTa for the purpose of drift determination.
Building SeparationSection 12.12.3
12.12.3 Building Separation. All portions of the structure shall be designed and constructed to act as an integral unit in resisting seismic forces unless separated structurally by a distance sufficient to avoid damaging contact under total deflection as determined in Section 12.8.6.
Building SeparationSection 12.12.3
This section applies to SDCs B through F.
Does not address adjacent buildings on the same property.
Does not address minimum setback distance from property line.
Building SeparationSection 12.12.3
Code Requirement 2006 IBC/ ASCE 7-052009 IBC/ ASCE 7-05
PORTIONS OF THE SAME STRUCTURE:
All portions of the structure shall be designed and constructed to act as an integral unit in resisting seismic forces unless separated structurally by a distance sufficient to avoid damaging contact under total deflection (x) as determined in Section 12.8.6.
ASCE 7-05 Section 12.12.3 (applies to all SDCs)
ASCE 7-05 Section 12.12.3 (applies to all SDCs)
Continued on next page
Building Separation2009 IBC Section 1613.6.7Code Requirement 2006 IBC/ ASCE 7-05
2009 IBC/ ASCE 7-05
BUILDING SEPARATIONS (paraphrased):All structures shall be separated from adjoining structures. Separations shall allow for the maximum inelastic displacement M (including torsion). Adjacent buildings on the same property shall be separated by at least MT where
When a structure adjoins a property line not common to a public way, that structure shall also be set back from the property line by at least the displacement, M, of that structure.
Exception: Smaller separations or property line setbacks shall be permitted when justified by rational analyses based on maximum expected ground motions.
No requirement
2009 IBC Section 1613.6.7
26
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Building Separation2009 IBC Section 1613.6.7
Note difference between x and MThe deflections of Level x at the center of
mass (12.8.6),x = Cd xe / I
M = Cd max / I (Equation 16-44)max = the maximum displacement at Level x
computed assuming Ax = 1 (12.8.4.3)
Building Separation2009 IBC Section 1613.6.7
Building Separation2009 IBC Section 1613.6.7
Separation of Two Adjacent Buildings
Building Separation2009 IBC Section 1613.6.7
10 separation
M1 at edge = 6
M2 at adjacent edge = 8
Q:A: for Building SeparationQ: ASCE 7-05 Section 12.12.3 contains the
language sufficient to avoid damaging contact. What is damaging contact?
A: To avoid any contact at all, the separation distance would have to be the arithmetic sum of M1 and M2. To avoid damaging contact, ASCE 7 allows the separation distance to be the statistical sum of M1 and M2, which is less than the arithmetic sum.
Q:A: for Building Separation
Q: I do not understand the logic of requiring less separation between two buildings on the same property than between two identical buildings on different sides of the property line.
27
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Q:A: for Building Separation
A: The first provision is concerned with damaging contact from pounding of buildings belonging to presumably the same owner. The property line setback requirement is based on consideration that one owner should not encroach onto another property.
PROVISION#7
R, Cd and 0 Values forHorizontal and Vertical
Combinations
R, Cd and o Values for Horizontal and Vertical Combinations
Horizontal Combinations can be either.
In different directions In same direction
Section 12.2.2 Combinations of Framing Systems in Different
Directions Different seismic force-resisting systems
may be used to resist seismic forces along each of two orthogonal plan axes.
The respective R, Cd, and o coefficients shall apply to each system, including the limitations on system use contained in Table 12.2-1.
Section 12.2.2 Combinations of Framing Systems in Different
Directions
R =5Cd = 5o = 2
R = 8, Cd = 5 , o = 3
Section 12.2.3 Combinations of Framing Systems in the Same
DirectionWhere different seismic force-resisting systems
are used in combination to resist seismic forces in the same direction of structural response, other than those combinations considered as dual systems, the more stringent system limitation contained in Table 12.2-1 shall apply and the design shall comply with the requirements of this section.
28
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
12.2.3.1 Vertical Combinations
R: Cannot increase as you go downCd and 0: Cannot decrease as you go down
R=8, Cd=5.5, 0=3
R=5, Cd=5, 0=2.5
8, 5.5, 3
8, 5.5, 3
8, 5.5, 3
5, 5.5, 3
5, 5.5, 3
5, 5.5, 3
R=5, Cd=5, 0=2.5
R=8, Cd=5.5, 0=3
5, 5, 2.5
5, 5, 2.5
5, 5, 2.5
5, 5.5, 3
5, 5.5, 3
5, 5.5, 3
R=5, Cd=5, 0=2.5
R=8, Cd=5.5, 0=3
5, 5.5, 3
5, 5.5, 3
5, 5.5, 3
5, 5.5, 3
R=8, Cd=5.5, 0=3 8, 5.5, 3
8, 5.5, 3
12.2.3.2 Horizontal Combinations
12.2.3.2 Where a combination of different structural systems is utilized to resist lateral forces in the same direction, value of R used for design in that direction shall not be greater than the least value of R for any of the systems utilized in that direction.
12.2.3.2 Horizontal Combinations12.2.3.2 Resisting elements are permitted to be
designed using the least value of R for the different structural systems found in each independent line of resistance if the following three conditions are met: 1) Occupancy Category I or II building, 2) two stories or less in height, and 3) use of light frame construction or flexible diaphragms.
The value of R used for design of diaphragms in such structures shall not be greater than the least value for any of the systems utilized in that same direction.
12.2.3.2 Horizontal Combinations
The deflection amplification factor, Cd, and the system overstrength factor, 0 , in the direction under consideration at any story shall not be less than the largest value of this factor for the R factor used in the same direction being considered.
12.2.3.2 Horizontal Combinations
The second paragraph of ASCE 7-05 Section 12.2.3.2 is far from clear.
One possible interpretation is that when different structural systems are combined in the same direction of a building or other structure, the largest Cd- and 0-values of all the individual structural systems shall be used.
12.2.3.2 Horizontal Combinations
The other possible interpretation is that the Cd-and 0-values shall correspond to the least R-value of all the individual structural systems. The second interpretation appears to be the more logical in view of the following example (discussion is continued in terms of Cd alone).
29
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
12.2.3.2 Horizontal Combinations
Consider a rather extreme example where a prestressed masonry shear wall (R = 1.5, Cd = 1.75) is combined with a special steel moment-resisting frame (R = 8, Cd = 5.5). There is no question that the R-value is 1.5. The question is whether the Cd-value is 1.75 or 5.5. 5.5 does not seem logical for two reasons.
12.2.3.2 Horizontal Combinations
First, the combined system is much more rigid than the special steel moment frame itself. Until the prestressed masonry shear wall hinges at its base, which is extremely unlikely in view of the large design forces that would result from an R = 1.5, large inelastic displacements do not seem to be possible.
12.2.3.2 Horizontal CombinationsSecond, large values of xe would automatically
result from the low value of R used in design. These, multiplied by the Cd of 5.5 would yield unrealistically large total displacements. Cd of 1.75 appears to be much more logical.
This second interpretation was implicit in the 1997 Uniform Building Code, where 0.7R was used in place of Cd.
12.2.3.2 Horizontal Combinations
The proposed rewrite provides clarification of the second paragraph of ASCE 7-05 Section 12.2.3.2. The rewrite also offers clarification concerning another complication that may arise, which is that different structural systems having the same R-value sometimes have different Cd- and 0-values.
12.2.3.2 Horizontal CombinationsTable 12.2.3.2 R, Cd, and o Values for Combination of
Different Structural Systems Used in Same DirectionR value The least value of R for any of the systems used.
Exception: Resisting elements are permitted to be designed using the least value of R for the different structural systems found in each independent line of resistance if the following three conditions are met: 1) Occupancy Category I or II building, 2) two stories or less in height, and 3) use of light frame construction or flexible diaphragms.
Cd value The Cd value corresponding to the system with the least value of R for any of the systems used. In the case where two or more systems have the same least value of R, the largest of the corresponding values of Cd shall be used.
o value The o value corresponding to the system with the least value of R for any of the systems used. In the case where two or more systems have the same least value of R, the largest of the corresponding values of o shall be used.
Vertical combinations
R: Cannot increase as you go downCd and 0: Always correspond to R
ASCE 7-10 Section 12.2.3.1 Vertical Combinations
R = 8, Cd = 5.5, 0 = 3
R = 5, Cd = 5, 0 = 2.5
8, 5.5, 3
8, 5.5, 3
8, 5.5, 3
5, 5, 2.5
5, 5, 2.5
5, 5, 2.5
R = 5, Cd = 5, 0 = 2.5
R = 8, Cd = 5.5, 0 = 3
5, 5, 2.5
5, 5, 2.5
5, 5, 2.5
5, 5, 2.5
5, 5, 2.5
5, 5, 2.5
R = 5, Cd = 5, 0 = 2.5
R = 8, Cd = 5.5, 0 = 3
5, 5, 2.5
5, 5, 2.5
5, 5, 2.5
5, 5, 2.5
R = 8, Cd = 5.5, 0 = 3 8, 5.5, 3
8, 5.5, 3
30
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
12.2.4 Combination Framing Detailing Requirements
Structural components common to different framing systems used to resist seismic motions in any direction shall be designed using the detailing requirements of Chapter 12 required by the highest response modification coefficient, R, of the connected framing systems.
Q: A: for CombinationsQ: I am designing a building that has a combination of special
reinforced masonry shear walls and special steel braced frames in the same direction. R values are 5.5 and 6, respectively. I understand that I should design the building with the smaller R = 5.5 for both the masonry shear walls and steel braced frames in this direction for seismic design in accordance with ASCE 7-05 Section 12.2.3.2. But someone told me that the building should be designed by analyzing the entire building twice: use R = 5.5 for the entire building to analyze and design the masonry shear walls and use R = 6 for the entire building to design the steel frames. I don't think this is right. What is your thought on this?
Q: A: for Combinations
A: What you understand is correct. The latter interpretation is unfamiliar and incorrect.
PROVISION#8
MINIMUM SEISMICBASE SHEAR
CodeMaster2009 IBC Seismic Design
ASCE 7-05 12.8.1 Design Base Shear
31
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
ASCE 7-05 12.8 Equivalent Lateral Force Procedure Revisions to ASCE 7-05 Seismic
ProvisionsBuilding Code Minimum Base Shear Applicable in All SDCs
1997 UBC Vmin = 0.11 Ca I W
2000 & 2003 IBC Vmin = 0.044 SDS I W
2006 IBC & ASCE 7-05 w/ Supplement No. 1 Vmin = 0.01 W
2009 IBC & ASCE 7-05 w/ Supplement Nos. 1 and 2
Vmin = 0.044 SDS I W 0.01W
ASCE 7-05 w/ Supplement No. 2 Design Base Shear
Section 1613 Earthquake Loads
Section 1613.1 references ASCE 7 Chapter 35 entry for ASCE 7 reads as
follows:ASCE 7-05 Minimum Design Loads for Buildings and Other Structures including Supplements No. 1 and 2, excluding Chapter 14 and Appendix 11A
ASCE 7-05 Including Supplement No. 1
Including Supplement No. 1
ASCE 7-05 Supplement No. 2Supplement No. 2 modifies Eqs. 12.8-5,
15.4-1 and 15.4-3 as shown below:CS = 0.01 0.044SDSI 0.01 (Eq. 12.8-5) [applicable to buildings]CS = 0.03 0.044SDSI 0.03 (Eq. 15.4-1) [applicable to nonbuilding structures not similar to buildings]CS = 0.01 0.044SDSI 0.01 (Eq. 15.4-3) [applicable to an exception for nonbuilding structures not similar to buildings]
32
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Minimum Seismic Base Shearvs. Ground Motion
0.044SDSI 0.01 or SDSI 0.227or SS value given in table
Site Class I = 1 I = 1.25 I = 1.5
A 0.426 0.341 0.284B 0.341 0.273 0.227C 0.284 0.227 0.189D 0.213 0.170 0.142E 0.136 0.109 0.091
Minimum Seismic Base Shear
Minimum Seismic Base Shear
For special reinforced concrete moment frames,
0.016h0.9 9/8
h (70.31)1/0.9 = 113 ft
Minimum Seismic Base Shear -Example
Concrete SMRF building - R = 8, I = 1.0Height = 120 ft, SDS = 1.00, SD1 = 0.40Ta = 0.016(120)0.9 = 1.19 sec
GovernsDoes not govern
ASCE 7-05 Supplement No. 2
Q: Where does ASCE officially announce ASCE 7-05 Supplement No. 2?
A: http://content.seinstitute.org/files/pdf/SupplementNo2ofthe2005EditionofASCE7.pdf
Q: A: for ASCE 7-05 Supplement No. 2
Q: Does ASCE 7-05 Supplement No. 2 minimum base shear need to be considered for drift determination?
A: Yes, Section 12.8.6.1 requires that all of the requirements of Section 12.8 be satisfied for the purpose of computing drift.
33
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Q: A: for ASCE 7-05 Supplement No. 2
Q: Is ASCE 7-05 going to be published with errata and Supplement No. 2 incorporated?
A: Additional printings will, to the extent possible, include as extra pages the supplements and errata. However there's a conscious decision not to integrate them directly into the text so as to minimize confusion between one book and another.
PROVISION#9
FLEXIBLE VS. RIGIDDIAPHRAGMS
2006 and 2009 IBC Section 1602Definition for Diaphragms
DIAPHRAGMDiaphragm, blockedDiaphragm boundaryDiaphragm chordDiaphragm, flexibleDiaphragm, rigidDiaphragm, unblocked
FLEXIBLE DIAPHRAGMS
Prescriptive Approach&
Calculation Approach
2006 and 2009 IBC Section 1602 Definition for Flexible Diaphragm
Diaphragm, flexible.
A diaphragm is flexible for the purpose of distribution of story shear and torsional moment where so indicated in Section 12.3.1 of ASCE 7, as modified in Section 1613.6.1.
12.3.1.1 Flexible Diaphragm Condition. Diaphragms constructed of untopped steel decking or wood structural panels are permitted to be idealized as flexible in structures in which the vertical elements are steel or composite steel and concrete braced frames, or concrete, masonry, steel, or composite shear walls. Diaphragms of wood structural panels or untopped steel decks in one- and two-family residential buildings of light-frame construction shall also be permitted to be idealized as flexible.
ASCE 7-05 Section 12.3.1.1Definition for Flexible Diaphragm
(Prescriptive)
34
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
12.3.1.3 Calculated Flexible Diaphragm Condition. Diaphragms are permitted to be idealized as flexible where the computed maximum in-plane deflection of the diaphragm under lateral load is more than two times the average story drift of adjoining vertical elements of the seismic force resisting system of the associated story under equivalent tributary lateral load as shown in Fig. 12.3-1.
ASCE 7-05 Section 12.3.1.3Definition for Flexible Diaphragms
by Calculation
ASCE 7-05 Figure 12.3-1 Definition for Flexible Diaphragm
by Calculation
MAXIMUM DIAPHRAGMDEFLECTION (MDD)AVERAGE DRIFT OFVERTICAL ELEMENT
(ADVE)
Note: Diaphragm is flexible If MDD > 2 (ADVE).
S
De
SEISMIC LOADING
2006 and 2009 IBC Section 1613.6.1Definition for Flexible Diaphragm
(Prescriptive)1613.6.1 Assumption of flexible
diaphragm. Add the following text at the end of Section 12.3.1.1 of ASCE 7:
Diaphragms constructed of wood structural panels or untopped steel decking shall also be permitted to be idealized as flexible, provided four given conditions are met
2006 and 2009 IBC Section 1613.6.1Definition for Flexible Diaphragm
Condition #1:Toppings of concrete or similar materials
are not placed over wood structural panel diaphragms except for nonstructural toppings no greater than 1 inches thick.
2006 and 2009 IBC Section 1613.6.1Definition for Flexible Diaphragm
Condition #2:Each line of vertical elements of the
lateral force-resisting system complies with the allowable story drift of Table 12.12-1.
2006 and 2009 IBC Section 1613.6.1Definition for Flexible Diaphragm
Condition #3:Vertical elements of the lateral-force-
resisting system are light-framed walls sheathed with wood structural panels rated for shear resistance or steel sheets.
35
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
2006 and 2009 IBC Section 1613.6.1Definition for Flexible Diaphragm
Condition #4:Portions of wood structural panel diaphragms that
cantilever beyond the vertical elements of the lateral-force-resisting system are designed in accordance with [2006 IBC: Section 2305.2.5] [2009 IBC: Section 4.2.5.2 of AF&PA SDPWS].
ASCE 7-05 Section 12.3.1.2Definition for Rigid Diaphragm
(Prescriptive)12.3.1.2 Rigid Diaphragm
Condition. Diaphragms of concrete slabs or concrete filled metal deck with span-to-depth ratios of 3 or less in structures that have no horizontal irregularities are permitted to be idealized as rigid.
2006 and 2009 IBC Section 1602.1Definition for Rigid Diaphragm
(Calculation)Diaphragm, rigid
A diaphragm is rigid for the purpose of distribution of story shear and torsional moment when the lateral deformation of the diaphragm is less than or equal to two times the average story drift.
ASCE 7-05 Figure 12.3-1 Definition for Diaphragm
MAXIMUM DIAPHRAGMDEFLECTION (MDD)AVERAGE DRIFT OFVERTICAL ELEMENT
(ADVE)
Note: Diaphragm is flexible If MDD > 2 (ADVE).
S
De
SEISMIC LOADING
Note: Per 2009 IBC Section 1602.1, diaphragm is rigid if MDD 2(ADVE)
ASCE 7-05 Section 12.3.1Definition for Diaphragms
12.3.1 Diaphragm Flexibility.Unless a diaphragm can be idealized as either flexible or rigid in accordance with Sections 12.3.1.1, 12.3.1.2, or 12.3.1.3, the structural analysis shall explicitly include consideration of the stiffness of the diaphragm (i.e. semirigid modeling assumption).
Is diaphragm wood structural panels or untopped steel decking?
Is any of the following true?1- & 2-family dwelling of light-frame construction
Vertical elements one of the following:Steel braced framesComposite steel and concrete braced framesConcrete, masonry, steel or composite shear walls
Four conditions in 2009 IBC Section 1613.6.1 are met
Is diaphragm Concrete slab? Concrete filled metal deck?
Is span-to-depth ratio 3 and no horizontal irregularities?
Assume Rigid
Assume Flexible
See Next Slide
Y
NN
Y
Y
Y
N
N
STAR
T
36
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
MAXIMUM DIAPHRAGMDEFLECTION (MDD)AVERAGE DRIFT OFVERTICAL ELEMENT
(ADVE)
Is MDD > 2 (ADVE)?
S
De
SEISMIC LOADING
Assume Flexible
YAssume Rigid
N
PROVISION#10
Special Seismic Load Combinations
2006 IBC 1605.4 Special Seismic Load Combinations
Section 1605.4 is deleted in its entirety in the 2009 IBC.
SPECIAL SEISMIC LOAD COMBINATIONSis replaced with
LOAD COMBINATIONS WITH OVERSTRENGTH FACTORSof ASCE 7-05
Why Was 2006 IBC Section 1605.4 Deleted?
To eliminate a disconnect between IBC and ASCE 7-05: 2006 IBC Section 1605.4 had one set of
special seismic load combinations applicable to both ASD and strength design.
ASCE 7-05 has two sets of load combinations with overstrength factorsone for ASD and one for strength design.
Why Was 2006 IBC Section 1605.4 Deleted?
To eliminate a disconnect between IBC and ASCE 7-05 (cont.): 2006 IBC had separate, unique load
combinations that were to be applied where specifically required.
ASCE 7-05 prescribes an equation for Em that is to be used in ASCE 7-05 Ch. 2 load combinations.
37
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
1605.4 Special Seismic Load Combinations (2006 IBC)
1.2D + f1L + Em (Equation 16-22) 0.9D + Em (Equation 16-23)
Em = 0 QE + 0.2 SDSD, whileE = QE + 0.2 SDSD
12.4.3.2 Load Combinations with Overstrength Factor (ASCE 7-05)
Basic Combinations for Strength Design with Overstrength Factor
(1.2 + 0.2SDS)D + 0QE + L + 0.2S(0.9 0.2SDS)D + 0QE + 1.6H
12.4.3.2 Load Combinations with Overstrength Factor (ASCE 7-05)
Basic Combinations for Allowable Stress Design with Overstrength Factor(1.0 + 0.14SDS)D + H + F + 0.70QE(1.0 + 0.105SDS)D + H + F + 0.5250QE + 0.75L
+ 0.75(Lr or S or R)(0.6 0.14SDS)D + 0.70QE + H
12.4.3.3 Load Combinations with Overstrength Factor (ASCE 7-05)
Where allowable stress design methodologies are used, allowable stresses are permitted to be determined using an allowable stress increase of 1.2.
This increase shall not be combined with increases in allowable stresses or load combination reductions except that combination with the duration of load increases permitted in AF&PA NDS is permitted.
1617.1.2 Maximum Seismic Load Effect, Em (2000, 2003 IBC)
Where allowable stress design methodologies are used with the special load combinations of Section 1605.4, design strengths are permitted to be determined using an allowable stress increase of 1.7 .
What Takes the Place of Deleted 2006 IBC Section 1605.4?
New language in 2009 IBC Section 1605.1.
38
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
What Takes the Place of Deleted 2006 IBC Section 1605.4?
1605.1 General. Buildings and other structures and portions thereof shall be designed to resist:1. The load combinations specified in Section 1605.2,
1605.3.1 or 1605.3.2,2. The load combinations specified in Chapters 18 through
23, and3. The load combinations with overstrength factor
specified in Section 12.4.3.2 of ASCE 7 where required by Section 12.2.5.2, 12.3.3.3 or 12.10.2.1 of ASCE 7. With the simplified procedure of ASCE 7 Section 12.14, the load combinations with overstrength factor of Section 12. 14.3.2 of ASCE 7 shall be used.
Q: A: for Load Combinations with Overstrength Factor
Q: Section 1605.1 of the 2009 IBC requires buildings and other structures and portions thereof to be designed to resist the load combinations with overstrength factor specified in Section 12.4.3.2 of ASCE 7-05 where required by Section 12.2.5.2, 12.3.3.3, or 12.10.2.1. Can you elaborate?
Q: A: for Load Combinations with Overstrength Factor
Cantilever Column Systems 12.2.5.2SDC B - F
A:
Foundation and other elements used to provide overturning resistance at the base of cantilever column elements shall have the strength to resist the load combinations with over strength factor of Section 12.4.3.2.
Q: A: for Load Combinations with Overstrength Factor
A: Elements Supporting Discontinuous Walls or Frames
12.3.3.3SDC B - F
Q: A: for Load Combinations with Overstrength Factor
Q: A: for Load Combinations with Overstrength Factor
39
S. K. Ghosh Associates Inc.
www.skghoshassociates.com
Q: A: for Load Combinations with Overstrength Factor
A: Collector Elements 12.10.2.1 (SDC C - F)
Q: A: for Load Combinations with Overstrength Factor
Load Combinations with Overstrength Factor
Chapter 18 References:1810.3.6.1 Splices of deep foundation elements, SDC C through F
1810.3.9.4 Seismic reinforcement, SDC C and above, Exception 3
1810.3.11.2 Deep foundation element resistance to uplift forces, SDC D through F
1810.3.12 Grade beams, SDC D through F
Thank You!!
For more informationwww.skghoshassociates.com
Main Office334 East Colfax Street, Unit EPalatine, IL 60067Phone: (847) 991-2700Fax: (847) 991-2702Email: [email protected]
West Coast Office43 Vantis DriveAliso Viejo, CA 92656 Phone: (949) 215-6560Email: [email protected]
2005EditionofASCE7MinimumDesignLoadsforBuildingandOtherStructures
SupplementNo.2
Supplement No. 2 of ASCE 705 revises the minimum base shear equations for bothbuildings and nonbuilding structures. The need for this change was indicated by theresults from the75%DraftofATC63,QuantificationofBuildingSystemPerformanceandResponseParameters,whichindicatethattallbuildingsmayfailatanunacceptablylowseismiclevelandthereforetheminimumbaseshearequationforbuildingsisbeingrestoredtothatwhichappearedinthe2002editionofASCE7.
Becausenonbuildingstructuresnotsimilar tobuildingshave lowRvaluescomparedtothespecialreinforcedconcretemomentframesstudiedinATC63,theASCE7standardscommitteechosenottorestorethehighminimumbaseshearsfornonbuildingstructuresnotsimilar tobuildings found inASCE702. Inmanycases, thesepreviousminimumbaseshearsgavemanynonbuildingstructuresnotsimilartobuildingseffectiveRvaluesless than 1.0. Therefore, the Seismic Subcommittee believes that the minimum baseshear equation of 0.044SDSI used for buildings should also be applied to nonbuildingstructuresnotsimilartobuildings.
SupplementNo.2modifiesthreeequationsofthestandard(Eq.12.85,15.41and15.43)asshownbelow:
SupplementNo.2toASCE705:
Revise Equation 12.85 of Section 12.8.1.1 of ASCE 705 as shownbelow:
12.8.1.1CalculationofSeismicResponseCoefficient. Theseismicresponsecoefficient,Cs,shall bedeterminedinaccordancewithEq.12.82.
=
IR
SC DSs (Eq.12.82)
where:
SDS= thedesignspectralresponseaccelerationparameterintheshortperiodrangeasdeterminedfromSection11.4.4
R = theresponsemodificationfactorinTable12.21,and
I = theoccupancyimportancefactordeterminedinaccordancewithSection11.5.1
Thevalueof CscomputedinaccordancewithEq.12.82neednotexceedthefollowing:
L1D
s TTfor
IR
T
SC
= (Eq.12.83)
L2
L1Ds TTfor
IR
T
TSC >
= (Eq.12.84)
Csshallnotbelessthan
Cs=0.01 0.044SDSI0.01 (Eq.12.85)
Inaddition,forstructureslocatedwhereS1 isequaltoorgreaterthan0.6g,Csshallnotbelessthan
=
I
RS.
Cs150 (Eq.12.86)
whereIandRareasdefinedin Section12.8.1.1and
SD1= thedesignspectralresponseaccelerationparameterataperiodof1.0sec,asdeterminedfromSection11.4.4
T = thefundamentalperiodofthestructure(sec)determinedinSection12.8.2
TL = longperiodtransitionperiod(sec)determinedinSection11.4.5S1 = themappedmaximumconsideredearthquakespectral
responseaccelerationparameterdeterminedinaccordancewithSection11.4.1
ReviseEquations 15.41 and15.42 ofSection15.4.1, item2,as shownbelow:
2. Fornonbuildingsystemsthathavean RvalueprovidedinTable15.42,theseismicresponsecoefficient(Cs)shallnotbetakenlessthan
Cs=0.030.044SDSI 0.03 (15.41)
andfornonbuildingstructureslocatedwhereS10.6g,Csshallnotbetakenlessthan
=
IRS
Cs18.0 (15.42)
EXCEPTION:TanksandvesselsthataredesignedtoAWWAD100,AWWAD103,API650AppendixE,andAPI620AppendixLasmodifiedbythisstandard,shallbesubjecttothelargeroftheminimumbaseshearvaluesdefinedbythereferencedocumentorthefollowingequations:
Cs=0.010.044SDSI 0.01 (15.43)
andfornonbuildingstructureslocatedwhereS10.6g,Csshallnotbetakenlessthan
=
IRS
Cs15.0 (15.44)
Minimumbaseshearrequirementsneednotapplytotheconvective(sloshing)componentofliquidintanks.