WILO. CARACTERISTICI TEHNICE

Embed Size (px)

DESCRIPTION

wilo

Citation preview

  • Refrigeration, air-conditioning andcooling technology

    Planning Guide

    2007

    PLH_Titel_KKK.qxd 25.05.2007 10:21 Uhr Seite 2

  • C O N T E N T S

    Fundamentals of refrigeration, air-conditioning and cooling technology 5

    Pump curves 6

    Suction behaviour of the centrifugal pump 9

    Pump efficiency 11

    Power requirements of the pump 12

    Pressure behaviour 14

    Pumping of viscous media 15

    Noises Airborne sound Structure-borne sound 19

    Pumps as noise generators 19

    Airborne sound 20

    Structure-borne sound and waterborne sound 20

    Measures against noises 21

    Pump inlet 29

    Pump sump 29

    Suction lines and suction tanks 30

    Suctioning 31

    Pump performance control 33

    Control mode p-c 33Control mode p-v 34Differential pressure delivery-superimposed (p-q) 34Control mode p-T 35Operating mode DDC 35

    Generator circuits in the liquefier part 37

    Cooling tower / emergency cooler 37

    Heat recovery 38

    Geothermal power in the condenser circuit 39

    Generator circuits in the vaporiser part 41

    Constant volume flow in the vaporiser circuit 41

    Variable volume flow in the vaporiser circuit 42

    Cold-water loads 43

    Protection of pumps and refrigerating machines 47

    Minimum run-time of refrigeration generators and buffer mode 47

    Protection of the refrigerating machine in the vaporiser circuit 49

    Protection of the refrigerating machine in the condenser circuit 49

    Protection of circulating pumps 50

    Subject to change without prior notice 02/2007 WILO AG

    PLH_KKK_U2_31.QXP 25.05.2007 11:01 Uhr Seite 2

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007

    C O N T E N T S

    Examples for the pump selection in the condenser circuit 57

    Well system 57

    Open cooling tower system 59

    Closed cooling tower system 61

    Heat recovery via building heating and hot water production 63

    Ground collector system 65

    Ground spike system 67

    Examples for the pump selection in the cold water circuit 68

    Flow rate control with straight-through valves 68

    Flow rate control with distributor valve 70

    Admixing circuit for temperature control 72

    Examples for the pump selection in the vaporiser circuit 74

    Vaporiser circuit with constant volume flow 74

    Hydraulic decoupler in vaporiser circuit 75

    Vaporiser circuit with ice storage 76

    Vaporiser circuit with variable volume flow 78

    Economical consideration in the selection of fittings 83

    Appendix 86

    Seminars 98

    Information material 99

    Imprint 103

    PLH_KKK_U2_31.QXP 25.05.2007 11:01 Uhr Seite 3

  • PLH_KKK_U2_31.QXP 25.05.2007 11:01 Uhr Seite 4

  • Fundamentals of refrigeration, air-conditioning and cooling technologyThe transportation of refrigeration, air-conditioning and cooling fluid plays an impor-tant role inside of buildings. Cold water is pumped for cooling work machines in indus-try and to the vaporiser in building engineering. Air-conditioners require fluids forheat transport and utilise the active force of circulating pumps for faster exchangeand short regulation times. In cooling towers, fluids are pumped with and withoutfluid processing for accomplishing tasks.

    Fluid heat transfer media require pumps and systems for transport, which meet thevarious chemical, physical, mechanical and financial requirements.

    Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 5

    The contents of this brochure should give peo-ple who are being trained or getting additionaltraining basic knowledge of system design. Different designs and versions of systems withliquid heat transfer media can bring about directramifications due to irritating noise generationor component failure. The user should be givenan adequate practical basis with simple explana-tions, drawings and examples. The selection andappropriate use of pumps with their accessoriesin refrigeration, air-conditioning and coolingtechnology should become daily routine.

    It is to be considered that various standards (EN, DIN, VDE, ISO, IEC) and directives (VDI, DVGW, ATV, VDMA) are to be compliedwith and special aggregates and techniques selected. National building regulations and envi-ronmental protection directives, etc. pose addi-tional demands. The basic requirements are taken into consideration in this brochure. Sincerequirements are constantly changing, addition-al information channels with the newest state of the art must flow into system planning everyday. This cannot be achieved with the contentsof this brochure.

    Please observe the further option for increasingyour knowledge based on this planning guide forrefrigeration, air-conditioning and cooling sys-tems by using our documentation and informa-tion materials. We have compiled an up-to-dateoverview. Here you will find documents whichyou can read on your own and our seminar pro-gram with practical training.

    PLH_KKK_U2_31.QXP 25.05.2007 11:01 Uhr Seite 5

  • H1 21 2H2Q1

    Q2=

    Resistance changes quadradically with flow

    6 Subject to change without prior notice 02/2007 WILO AG

    System curve

    The static components consist of the geodeticpart which is independent of flow Hgeo and thepressure head difference

    between the entry and exit cross-section of thesystem.

    This last component is omitted in the case ofopen tanks. The dynamic components consist of the pump head loss HV, which increases qua-dratically with increasing flow, and the differ-ence in the velocity heads

    out of the entry and exit cross-section of thesystem.

    Abbreviation Description HA Required delivery head of the system

    HVL Pressure losses in the pipelines

    HVA Pressure losses in the fittings

    Hgeo Static head difference (static head difference to be overcome)

    HGes Total head losses

    Abbreviation Descriptionva Exit speed

    ve Entry speed

    pa Exit pressure

    pe Entry pressure

    Fluid density

    g Gravitational acceleration

    HV Pressure loss in the pipework

    System curve

    The system curve indicates the delivery head HArequired by the system. It consists of the com-ponents Hgeo, HVL and HVA. While Hgeo (static) re-mains constant independent of the volume flow,HVL and HVA (dynamic) increase quadratically dueto the widely varying losses in the pipelines andfittings, as well as due to increased friction, etc.due to temperature influences.

    Pump curves

    Flow Q [m/h]

    Hgeo

    HGes

    HVL + HVASystem curve

    HADel

    iver

    yhe

    adH

    [m]

    Q [m3/h]

    H1Q1

    H2

    Q2

    H[m

    ]0 3 41 2

    40

    50

    60

    70

    80

    30

    20

    10

    0

    pa - pe

    g

    va2 - ve2

    2 g

    Flow Q [m/h]

    System curve HA

    Del

    iver

    yhe

    adH

    Aof

    the

    syst

    em[m

    ]

    Static part = Hgeo + gpa - pe

    Dynamic part = HV + 2 gva2 - ve

    2

    F U N D A M E N TA L S

    System curve

    PLH_KKK_U2_31.QXP 25.05.2007 11:01 Uhr Seite 6

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 7

    Pump curve

    The flow rate of a centrifugal pump is specifiedby a pump curve in the Q vs. H diagram. In this,the flow Q is plotted, for example, in m3/h andthe pump delivery head H in m.

    The pump curve is curvilinear and drops in thediagram with increasing flow from left to right.The gradient of the pump curve is determined by the pump design and also specifically by theconstruction form of the impeller. Every changein the delivery head always results in a change inflow.

    The characteristic property of the pump curve isthe mutual dependence of the flow on the deliv-ery head.

    High flow -^- low delivery head, low flow -^- high delivery head.

    Although the installed pipeline system exclu-sively specifies which flow is pumped at the given pump capacity due to the internal resist-ances, the pump in question can always take ononly one duty point on its curve. This duty pointis the intersection of the pump curve with therespective system curve.

    Duty point

    The duty point is the intersection of the systemcurve and the pump curve. The duty point ad-justs itself independently in pumps with a fixedspeed.

    A change in the duty point occurs when, for ex-ample, in the case of a stationary pump station,the geodetic delivery head fluctuates betweenthe maximum and minimum values. Due to this,the delivered volume flow of the pump changessince this can only take on duty points on thepump curve.

    A reason for a fluctuating duty point could be avarying water level in the sump/tank, since herethe inlet pressure of the pump is changed by thedifferent level. On the discharge side, this changecan be due to incrustation of the pipeline or dueto the throttling of the valves or the load.

    Practically speaking, the system curve onlychanges by increasing or decreasing the resist-ances (e.g. closing or opening the throttling element, change in the pipeline diameter whenmodifications are carried out, incrustation, etc.)when there are solid-free fluids of normal vis-cosity in the system.

    Flow Q [m3/h]

    Pump curve

    System curve

    Intersection point =duty point

    Del

    iver

    yhe

    adH

    [m]

    The pump delivery head isalways as high as the flowresistance of the pipelinesystem.

    Pump curve

    F U N D A M E N TA L S

    Fluctuating water level in the tank

    Flow Q [m/h]

    HgeoMax-Level

    HgeoMin-Level

    B

    A

    Del

    iver

    yhe

    adH

    [m]

    System curve 2 Pump curve

    A, B = duty points

    System curve 1

    Speed and duty point

    Flow Q [m/h]

    Open gate valve

    Valve furtherthrottled

    B1

    B2

    B3

    Del

    iver

    yhe

    adH

    [m]

    System curves HA

    QH curve

    B = duty point

    PLH_KKK_U2_31.QXP 25.05.2007 11:01 Uhr Seite 7

  • F U N D A M E N TA L S

    8 Subject to change without prior notice 02/2007 WILO AG

    Flow Q [m3/h]

    H1

    H2

    Q1Q2

    n1

    n2Del

    iver

    yhe

    adH

    [m]

    Flow Q [m/h]

    H1

    H2

    Q1Q2

    D1

    D2Del

    iver

    yhe

    adH

    [m]

    Change in speed

    Change in the impeller diameter

    Q1

    Q2

    n1

    n2=

    H1 21 2H2n1

    n2=

    P1 21 2P2n1

    n2=

    Q1

    Q2

    D1

    D2D2 D1< 3 m/s

    Q Flow in m3/h

    g Gravitational acceleration 9.81 m/s2

    dE Inlet diameter of the suction pipe

    or the inlet nozzle in m

    If the minimum submergence can't be provided,floats or swirl-preventing conductor surfacesare to be provided to prevent turbulence causedby air suction.

    Suction tank and float

    Suction pipe

    Float

    The minimum distances of the suction line from walls and tank floor:

    DN 25 32 40 50 65 80 100 150 200B in mm 40 40 65 65 80 80 100 100 150

    The minimum submergence Smin for the recommended flow rates of 0.5 to 3 m/s are:

    DN 25 32 40 50 65 80 100 150 200 Smin m 0.25 0.35 0.65 0.65 0.70 0.75 0.80 0.90 1.25

    Suction tank with impact surface

    Suction and minimum distances

    Smin dE + 2.3 vS =dE

    g

    dE

    >_ 6 dE B

    S>_ dE

    >_ 5,5 dE

    B

    SvE

    >_ dE

    B

    S

    vE

    0,5 dE

    dE

    Suction tank

    Suction line

    Impactsurface

    Feed line incorrect

    PLH_KKK_U2_31.QXP 25.05.2007 11:02 Uhr Seite 30

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 08/2006 31

    P U M P I N TA K E

    Suctioning

    The standard circulation pumps are not self-priming. This means that the suction line andthe pump housing on the suction side have to bevented so that the pump can work. If the pumpimpeller is not under the fluid level, the pumpand suction line must be filled with fluid. Thistedious procedure can be avoided when the inletof the suction pipe is equipped with a foot valve(non-return valve). Venting is only required atthe initial commissioning or when a fitting isleaky.

    Suction operation

    Due to losses in the connection lines, pump andfittings, a maximum of 7 to 8 m suction head canbe achieved in practice. The head difference ismeasured from the surface of the water level tothe pump suction port.

    Foot valve

    Suction line installation

    correct incorrect

    Suction lines are to be installed which have atleast the nominal diameter of the pump port,but if possible, should be one nominal diameterlarger. Reductions are to be avoided. Especiallyfine filters must be kept away from the suctionside. The suction line is to be installed so that ithas a continuous incline to the pump and a footvalve (floating discharge) is to be installed whichprevents the line from running empty. The lineshould be kept as short as possible. In long suc-tion lines, increased friction resistances arisewhich strongly impair the suction head.

    Air pocket formation caused by leaks are to beavoided under all circumstances (pump damage,operating faults).

    When hose lines are installed, suction- andpressure-proof spiral hoses should be used.

    PLH_KKK_U2_31.QXP 25.05.2007 11:02 Uhr Seite 31

  • PLH_KKK_32_85.QXP 25.05.2007 10:10 Uhr Seite 32

  • The volume flow conveyed through a circulatingpump is dependent on the thermal output/cool-ing output requirement of the system beingsupplied. This requirement fluctuates dependingon the following factors: Climatic changes User behaviour Extraneous heat influence Influence of hydraulic control devices, etc.

    The circulating pump designed for maximumload status is adapted by means of a continuoussetpoint/actual-value comparison to the rele-vant system operating state. This automaticcontrol serves to adapt the pump performanceand thus also the power consumption continu-ously to the actual requirement/demand.

    Pump performance control

    Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 33

    Electronically controlled pumps from Wilo areable to control the mass flow automatically. This can help avoid throttling and makes an adjustment to the system duty point possible. In addition to the reduced power consumptionof the pump, throttling elements can also bedone without. This way, additional installationand material costs can be noticeably reduced.

    The same result can be achieved with Wilo con-trol devices which aren't directly mounted onthe pump.

    In the p-c control mode, the electronics cir-cuitry maintains the differential pressure gener-ated by the pump constant at the setpoint valueHS over the permitted volume flow range.

    Control mode p-c

    Flow Q [m/h]

    p-c

    nmax

    nregel

    HSetpoint

    HSetpoint-min

    Del

    iver

    yhe

    adH

    [m]

    p-c control

    Flow Q [m/h]

    Pump curve

    System curve for the measuring point

    Intersection point =duty point

    Del

    iver

    yhe

    adH

    [m]

    Control curve for remote signal transmitters I. e., any reduction of flow volume (Q) due tothrottling of the hydraulic regulating devices will in turn decrease the pump performance tomatch actual system demand by reducing thespeed of the pump. In parallel with speed alter-ation, the power consumption is reduced to be-low 50 % of the nominal power. The applicationof differential-pressure control requires a vari-able flow volume in the system. Peak-load oper-ation, e.g. in conjunction with a twin-headpump, will be effected automatically and load-sensitively. If the capacity of the controlledbase-load pump becomes insufficient to coverthe increasing load demand the second pumpwill automatically be started to operate in paral-lel to cover the risen demand. The variable speedpump will then be run down until reaching thepreset differential-pressure setpoint value.

    It is generally recommended to pick off the dif-ferential-pressure directly at the pump and tomaintain it there at a constant level. An alterna-tive would be to install the signal transmitter inthe system as a remote signal transmitter inthe so-called index circuit of the system (control-range extension). Operation with a remote signaltransmitter will partly allow much larger speed re-ductions and thus pump performance reductions.It is essential in this respect that the selectedmeasuring point is valid for the consumptionperformance of all the system sections. Wherethis calculated measuring point in the index cir-cuit may be subject to shifting to other parts ofthe pipe system, optimisation by means of theWilo DDG impulse selector is preferable. Mea-suring points ranging from 2 to 4 can be com-pared on a continuous basis. Only the lowestmeasured value forms the basis for the set-point/actual value comparison by the CR con-troller.

    PLH_KKK_32_85.QXP 25.05.2007 10:10 Uhr Seite 33

  • P U M P P E R F O R M A N C E C O N T R O L

    34 Subject to change without prior notice 02/2007 WILO AG

    p-v control mode

    Differential pressure delivery-superimposed (p-q)

    When refurbishing or upgrading existing sys-tems it is not always possible to evaluate thepoint in the circuit which shows the lowest dif-ferential pressure. Original installations havebeen completed years ago and now, after in-stalling individual room controls, noise problemshave developed. The index circuit of the systemis not known or it is not possible to integratenew sensor connections. A control-range exten-sion is nevertheless possible using the p-vcontrol mode (recommended for single-pumpsystems).

    In order to avoid the time and expenditure asso-ciated with index-circuit evaluation (extensiveand expensive cable routing, amplifiers, etc.), it is possible to superimpose the setpoint differ-ential-pressure value directly with a signal pro-portional to delivery. Using this method, it ispossible even with multi-pump systems toachieve a control-range extension in spite of central measured-value acquisition (differen-tial pressure sensor at the pump). This methodrequires, in addition to the differential pressuresensor which is to be fitted directly on the pumpsystem, the cooling-circuit output or the inputof the consumer rail, the onsite provision by the customer of a volume-flow transmitter(0/4 20 mA) to be installed in the system'smain feed pipe.

    Flow Q [m/h]

    p-c

    nmax

    nregel HSetpoint HSetpoint

    HSetpoint-min

    Del

    iver

    yhe

    adH

    [m]

    In the p-v control mode, the electronicschange the differential pressure setpoint to bekept by the pump linearly between HS and 1/2HS. The differential pressure setpoint H changeswith the flow Q.

    p-v control

    The use of p-q control is recommended forsuch systems whose index circuit or system per-formance is not known or in such cases wherelong signal distances cannot be bridged, partic-ularly for such systems where volume-flowtransmitters are already available.

    Differential pressure delivery-superimposed(p-q)

    Flow volume Q [%]

    Del

    iver

    yhe

    adH

    [%]

    p = constantp = delivery-super-

    imposed

    PLH_KKK_32_85.QXP 25.05.2007 10:10 Uhr Seite 34

  • P U M P P E R F O R M A N C E C O N T R O L

    DDC operating mode

    Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 35

    p-T control mode

    Flow Q [m/h]

    Hmax

    Hmin

    Tmax TmedTmin QmaxQmin

    Hvar.

    pos. operation

    neg. operation

    Del

    iver

    yhe

    adH

    [m]

    U [V]

    Off

    nmax

    nmin

    n[1

    /min

    ]

    1 1.5 3 10

    100%

    0%

    Setp

    oint

    10 V0/2 V

    Signal input

    20 mA 0/4 mA

    In the p-T control mode (programmable onlywith the IR-Monitor) the electronics circuitryvaries the setpoint differential pressure value tobe maintained by the pump as a function of themeasured fluid temperature. This temperature-prompted differential-pressure control modecan be used in constant-volume (e.g. one-pipesystems) and variable-flow systems with varyingfeed temperature. Conversely, the p-T controlmode supports heating pump technology, pro-vided the pump is installed in the return pipe ofthe system.

    p-T control

    In this mode the actual/setpoint level assess-ment required for control is referred to a remotecontroller. An analogue signal (0...10 V) is fed asa manipulated variable from the external con-troller to the Wilo pumps with built-in electroniccircuitry. The current speed is shown on the dis-play, and manual operation of the pump is deac-tivated.

    DDC pump operating mode with built-in electronic circuitry

    DDC operation always means that a signal fromthe higher-ordered controller must be registeredby the Wilo products. In addition, floating con-tacts for switching on-/off, etc. are required,depending on the used product. Also, floatingsignals or 0...10 V (0/4-20 mA) signals can beused by the Wilo products for monitoring andlogging. Details can be found in the product catalogues.

    DDC operating mode with Wilo switchgear

    When a Wilo control device is used, the setpointdepends on the used signal transmitter. Whenthe signal transmitter DDG 40 is used, this means,for example, that the setpoint at 0 % is equal tozero meters and at 100 % is equal to 40 meters.Analogously, this applies for all other measuringranges.

    PLH_KKK_32_85.QXP 25.05.2007 10:10 Uhr Seite 35

  • PLH_KKK_32_85.QXP 25.05.2007 10:10 Uhr Seite 36

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 37

    Generator circuits in the liquefier part

    Cooling tower/emergency cooler

    Submersible pumps supply the condenser di-rectly with well water. The pumps could also beinstalled in a river or a reservoir. The submersiblepumps must be resistant to water corrosion.They are dimensioned from the delivery head forthe total pressure losses in the condenser circuitand the geodetic head difference between thewell floor and the highest point in the vaporisersystem.

    Submersible pumps supply the plate heat ex-changer directly with well water. The pumpscould also be installed in a river or a reservoir. By using stainless steel and/or plastic materialon the primary side of the exchanger, corrosiondamage can be avoided. The refrigerating ma-chine can be made out of the usual materials.They are dimensioned from the delivery head forthe total pressure losses in the condenser circuitand the geodetic head difference between thewell floor and the highest point in the heat ex-changer system.

    A cooling tower with collection tray, usually in-stalled on top of the building, takes over heatdissipation out of the condenser. Due to theconstant oxygen supply, pumps made of redbrass or plastic material should be selected. If there is continuous water conditioning, normal cast-iron designs can also be used. They are dimensioned from the delivery head for the total pressure losses in the condensercircuit and the geodetic head difference be-tween the well floor and the highest point in the nozzle fitting of the cooling tower.

    Since this is a closed circuit, standard materialcan be selected. The first filling is to be donewith water according to VDI 2035 etc. to protectagainst deposits and corrosion.

    On the generator side, one distinguishes between the cooling circuitin open and closed systems. Thus, using a suction well and sinkhole,ground or river water can be utilised for the primary circuit. Or the hot side of the generator is cooled with the air. By means of heat recovery,it is also possible to heat parts of buildings at the same time.

    Ground water for direct utilisation in the condenser

    Vaporiser Condenser

    Ground water for indirect utilisation in the condenser

    VaporiserCapacitors

    Open cooling tower system

    VaporiserCapacitors

    28C

    24C

    Closed cooling tower system in the condenser circuit

    VaporiserCondenser

    28C

    24C

    PLH_KKK_32_85.QXP 25.05.2007 10:10 Uhr Seite 37

  • G E N E R AT O R C I R C U I T S I N T H E L I Q U E F I E R PA R T

    38 Subject to change without prior notice 02/2007 WILO AG

    Heat recovery

    Indirect heating with cooling water The cooling water warmed up in the condenserof the refrigerating machine is used for heatingtasks via a heat exchanger. Due to galvanic insu-lation, the pump in the condenser circuit is onlyto be designed for these pressure losses. Thematerial selection is arbitrary due to the closedcircuit. If an emergency-cooler is added to thecondenser circuit, the pump is to be determinedbased on its requirements and there must be hy-draulic balancing between the heat exchangerand emergency cooler. To protect against corro-sion, the emergency cooling only makes senseas a closed cooling tower.

    The cooling water warmed up in the condenserof the refrigerating machine is used directly forheating tasks. Due to the direct connection, thepump in the condenser circuit is only to be de-signed for the pressure losses in the condenserand pipeline up to the distributor/collector. Thematerial selection is to be adapted to the heat-ing circuit. If an emergency-cooler is added tothe condenser circuit, the pump is to be deter-mined based on its requirements and there mustbe hydraulic balancing between the heat ex-changer and emergency cooler. It's better tosupply the emergency cooler with its own pumpcircuit. To protect against corrosion, the emer-gency cooling is only possible as a closed cool-ing tower.

    VaporiserCapacitors

    Gross calorific value - gas boiler

    M M

    Direct heating with cooling water

    VaporiserCapacitors

    Gross calorific value - gas boiler

    M M

    PLH_KKK_32_85.QXP 25.05.2007 10:10 Uhr Seite 38

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 39

    G E N E R AT O R C I R C U I T S I N T H E L I Q U E F I E R PA R T

    Geothermal power in the condenser circuit

    In the closed circuit between the condenser andheat exchanger line in the ground, the pump isonly to be designed based on these frictional re-sistances. For reasons of frost protection, it maymake sense to use a mixture of glycol and wateras the fluid. The material properties are to beadapted to these requirements.

    In the closed circuit between the condenser andground spike, the pump is only to be designedbased on these frictional resistances. For rea-sons of frost protection, it may make sense touse a mixture of glycol and water as the fluid.The material properties are to be adapted tothese requirements.

    Ground collector for cooling and for heatstorage

    Ground spikes for cooling and for heat storage

    Vaporiser Condenser

    VaporiserCondenser

    PLH_KKK_32_85.QXP 25.05.2007 10:10 Uhr Seite 39

  • PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 40

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 41

    Generator circuits in the vaporiser partIndependent of the basic hydraulic concept, in most cooling sys-tems, there is the requirement that the water mass flow throughthe vaporiser may only deviate from the nominal water mass flowby at most 10%. Otherwise, difficulties can be expected in the con-trol of refrigerating machines.

    There is also a danger of freezing when thethroughput is too low. The demand for a con-stant vaporiser water flow must be met, then,for all changes caused by the air-conditioningcontrol in the load part. Despite this strict re-quirement for a constant water volume flow inthe vaporiser, in the recent past, refrigeratingmachines were developed which allow a variablevolume flow. Thus, energy-saving speed-con-trolled pumps can also be used in the primarycircuit.

    To realise fault-free operation of cold-waternetworks with several generators and loads, onedivides the network into primary and secondarycircuits.

    Constant volume flow in the vaporiser circuit

    Vaporiser circuit with constant volume flow by means of a valve circuit

    Vaporiser circuit with constant volume flow by means of hydraulic decouplers

    An overflow from the feed to the return of thevalve circuit ensures that the volume flow re-mains constant and that a malfunction in thecontrol of the vaporiser performance is ruledout. The pump is to be dimensioned with respectto the pressure loss on the load which lies in thehydraulically most unfavourable position. On theloads lying in front of it, the water volume is tobe throttled to the nominal power. The volumeflow of the load is to be guaranteed. It might benecessary to select a higher flow to ensure theminimum volume flow in the vaporiser circuit.

    An overflow from the feed to the return of thedecoupler circuit ensures that the volume flowremains constant and that a malfunction in thecontrol of the vaporiser performance is ruledout. The pump is to be dimensioned based onthe pressure loss in the vaporiser and the resist-ances over the decoupler. The volume flow ofthe vaporiser is the required pump flow.

    VaporiserCapacitors

    M M M

    VaporiserCapacitors

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 41

  • Variable volume flow in the vaporiser circuit

    An overflow from the feed to the return of thedecoupler circuit ensures that the volume flowremains constant and that a malfunction in thecontrol of the vaporiser performance is ruledout. The pump is to be dimensioned based onthe pressure loss in the vaporiser and the resist-ances over the decoupler. The volume flow forthe vaporiser capacity is the required pump flow.To ensure the load capacity, the pipeline forconnection to the decoupler might have to bedesigned larger than what the vaporiser capacityrequires. In modern refrigerating machines, thepump capacity can be adapted to the require-ments of the load via temperature regulation.The minimum volume flow for the vaporiser isguaranteed by the speed limitation of the pumpdrive.

    In some modern refrigerating machines, thepump capacity can be adapted to the require-ments of the load via differential pressure regu-lation. The minimum volume flow for the vapor-iser and/or the pump can be ensured by theoverflow part. The overflow volume must be solarge that it is guaranteed that the supply line tothe load is kept cold. The complete volume flowfor the load and the overflow part for the pumpcapacity must be taken into account. Three-wayvalves in front of the loads are only requiredwhen a longer connection line is necessary.If the connection is near the distribution line,the time until cold fluid is there is usually ac-ceptable.

    Right now there are only a few possible applica-tions for regulating the pump capacity betweenzero and the nominal volume. On the one hand,cooling generators are not necessarily suitablefor this, and on the other hand, circulationpumps require a minimum volume flow for self-cooling and self-lubrication. More details can be found in the respective catalogues.

    G E N E R AT O R C I R C U I T S I N T H E VA P O R I S E R PA R T

    42 Subject to change without prior notice 02/2007 WILO AG

    Vaporiser circuit with variable volume flow via a hydraulic decoupler

    Vaporiser circuit with variable volume flow by means of a valve circuit

    Vaporiser circuit with variable volume flow over the load

    VaporiserCapacitors

    M

    M

    M

    M

    VaporiserCapacitors

    M M

    VaporiserCapacitors

    M

    M

    M

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 42

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 43

    G E N E R AT O R C I R C U I T S I N T H E VA P O R I S E R PA R T

    Cold-water load

    Volume flow control

    Because the room load is constantly changingand this is also the case for fresh air, the coolingcapacity is adjusted by means of changing flow.This circuit is only recommendable when thedistribution line is not far away from the load.Usually, all loads may not be connected this way.Not all refrigerating machines or circulatingpumps can work without flow. To avoid damagefrom freezing or dry running, the rerouting ordistribution circuit is to be selected, or at theend of the network there is a controlled over-flow. It's possible to control the overflow volumeby a fixed, throttled bypass or a bypass con-troller. A bypass controller is optimal when theposition of all control valves is monitored, andwhen a volume limit is fallen short of, an over-flow section compensates.

    The capacity is adjusted to the room load bychanging the flow in the load. In order that onlyso much flows through the bypass as is neededfor temperature maintenance or for maintainingthe required minimum volume for the refrigerat-ing machine and/or the pump, a balancing valveis installed in the bypass.

    There are two main differences in air-condition-ing systems for room temperature adjustment.Firstly, the temperature of the air (convection),which is fed to the room, is adjusted; secondly,the room temperature is controlled via radiantheat exchangers, such as cooling ceilings or viacomponent tempering. For hydraulic structures,both systems can have a two-, three- or four-pipe connection. For cold-water transport, there are always onlytwo pipes. The third and fourth pipes are for theheating part so that the temperature in the roomcan be maintained for lower outdoor tempera-tures. In the three-pipe installation, heating andcooling have a common return. Four-pipe con-nection means that the cooling and heating partare installed separately up to the heat exchang-er. Transmission into the room can only occur viaa common conductor or by one each for heatingor cooling.

    In the following figures, only the cooling part isshown with a feed and return.

    Flow rate control with straight-through valve at constant feed temperature

    Flow rate control with distributor valve atconstant feed temperature

    M

    M

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 43

  • C O L D - WAT E R L O A D

    44 Subject to change without prior notice 02/2007 WILO AG

    Temperature control

    Flow rate control is not always favourable. The admix circuit can be used for controlled dehumidification and to prevent falling underthe dew point. The feed temperature can be adjusted to the room load and the limits can bekept by measuring the actual value at the criticalpoint of the system. The volume flow in the loadcircuit remains constant.

    Temperature control with admix valve

    The pump is to be designed according to the ca-pacity and frictional resistances in the load cir-cuit. There should be a differential pressure ofzero on the input side of the control loop. Thiscannot always be achieved in practice, even withcontrolled feeder pumps. For this reason, a dif-ferential pressure controller is to be put in theconnection line of the load circuit without auxil-iary power. In order to retain good load circuitcontrollability and to protect the pump fromdamaging thrust forces, a differential pressure of

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 45

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 45

  • PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 46

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 47

    When operating with constant water flow, safeoperation is possible when the switch-on/offcycles alternate as seldom as possible. Thismeans that the circulated volume must havesuch a high storage capacity that the minimumrunning time of the cooling generator is exceed-ed. From experience, one knows that 90 % ofsystems aren't suitable for this without takingadditional measures.

    Buffer

    The objective is to guarantee economic efficien-cy and operating safety, long switch-on/off cy-cles, and therefore to get long running/idle timesfor the cold-water generator and the hydraulicdecoupling from the cold-water generator andconsumer system. This is possible with a hy-draulic decoupler.

    This efficiency is enhanced by nozzle pipes andlayering sheets in the tank. The size of the hy-draulic decoupler as a buffer is to be determinedas follows: Hydraulic decoupler circuit as buffer

    VaporiserCapacitors

    When there's a change in the specific heat ca-pacity, the specific factor is also to be redeter-mined.

    Derivation of the specific factor 14.34

    kW Ftl 14.34 min

    twSi =

    The minimum system content (Si) depends on kW Nominal cooling capacity Ftl Partial load factor for multistage

    cooling generatorsmin Minimum running time tw Temperature difference Cpw Spec. heat capacity

    mw 857 = =h

    KJ kg K 3600 s kg860

    h

    kg

    s 4.2 KJ h K

    Factor 14.34 = = =min

    L kg=

    min

    L

    min

    860 kg h

    h 60 min

    3600

    Qw [kW]

    mw =

    SKJ

    s h

    K [tw] Cpw 4.2 KJ

    kg k

    Observation of constraints for pumps and refrigerating machinesThere are physical limits for all technical devices. The refrigeratingmachines require a volume throughput to prevent icing. If the watervolume which is required for the smallest control level of the vapor-iser doesn't flow, mechanical damage will result without a safetyshutdown.

    Minimum run-time of refrigeration generators and buffer mode

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 47

  • P R O T E C T I O N O F P U M P S A N D R E F R I G E R AT I N G M A C H I N E S

    48 Subject to change without prior notice 02/2007 WILO AG

    Ice storage

    Air-conditioning systems with maintenance-free ice storage systems have been built for thepast several years. The refrigerating machineand its connected load, including the recoolingcapacity, is only dimensioned for the basic load.Load peaks over approx. 50 % of the peak loadare covered by the stored ice. Brine serves as aheat carrier. Depending on the system structure,the connection to the house system might bemade via a hydraulic decoupler, or by a systeminsulator (heat exchanger).

    The switching states of the valves for the re-spective load statuses are shown in the tableabove.

    Various flow resistances result from the controlwith effects on the circulating pumps. When theice storage is discharged, the ice storage pumpmust overcome resistances of valves 3 and 4 aswell as that of the ice storage. In peak load op-eration, another resistance of the ice storagepump is only necessary with large volume flow,

    Hydraulic connection of ice storage

    Function table - ice storage operation

    Operating mode

    Discharge ice storage

    Refrigerating machine on network

    Discharge ice storageRefrigerating machineon network

    Charge ice storage

    Refrigerat- Vaporiser Ice stor- Valve 1 Valve 2 Valve 3 Valve 4 Valve 4 Valve 4 Valve 5ing machine pump age pump Gate 1 Gate 2 Gate 3

    Off Off On Closed Open Open Regulating Regulating Regulating Closed

    On On Off Closed Open Open / / / Closed

    On On On Open Closed Open Regulating Regulating Regulating Closed

    Off On Off Open Closed Closed Closed Open Open Open

    Vaporiser

    Vaporiser pump

    Capacitors

    Ice bank 1 Ice bank 2

    Ice bank pump

    Valve 1Valve 5

    Valve 3

    Valve 4

    Valve 2

    M M

    M

    M M

    since additional flow is forced by the vaporisercircuit, depending on the position of valve 1.

    Three different load statuses are given for thevaporiser pump. First the refrigerating machine is alone in the network. Only valve 2 is present asa resistance. If peak load operation is required,the resistances from valves 1, 3 and 4 as well asthat of the ice storage are there. If the ice stor-age is charged, the power losses for valves 1 and5, as well as for the ice storage, are to be over-come by the vaporiser pump. Based on these re-quirements, a control of the vaporiser pump overthe volume or temperature is recommended atthe vaporiser outlet.

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 48

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 49

    F U S E P R O T E C T I O N O F P U M P S A N D R E F R I G E R AT I N G M A C H I N E S

    The vaporiser circuit is influenced by its circu-lating pump. If the pump capacity is too low, the frost protection and/or /flow controllerswitch the refrigerating machine to the mal-function state, i.e. "Off". Before the compressoris switched on, the vaporiser pump must beswitched on and have a follow-up time. Circu-lating pumps require between 2 seconds and aminute to reach the nominal power, dependingon the ignition/start circuit.

    In the event of a shutdown, the standard circu-lating pump stops in less than 2 seconds. If aphase is missing in three-phase operation, or ifthere is undervoltage, the drive can be operatedwith slippage. The circulating pump runs underits nominal power without a motor protectionrelay releasing. Due to this, and because theflow volume can be throttled by the system orcompressor capacities can be incorrectly con-trolled, the vaporiser circuit must be equippedwith frost protection and flow controllers. Pad-dle, differential pressure or volume flow switch-es can be used for flow control. In addition, thevaporiser circuit is to be protected from faultystatic and dynamic pressures by a pressurisingsystem and a safety relief valve. In order for theflow volume to be guaranteed during the parallel

    Protection of the refrigerating machine in the vaporiser circuit

    Safety requirements for operating cooling generators

    Expansion valve

    Hot gas sensor

    Frost-protection sensor

    Flow controller

    HD pressure control

    ND pressure control

    Thermal protection

    Thermalprotection

    Phase sequence relay

    Vaporiser

    approx. 5 bar/4 C

    approx. 15 bar/45 C

    12 C 6 C

    Condenser

    Protection of the refrigerating machine in the condenser circuit

    The setback of the condenser temperature hasoperational limits. Minimum values are requiredfor the function of the refrigerating machine,especially of the expansion valves, and are to begotten from the documentation of the respec-tive manufacturer. The temperatures in the con-denser depend on the compressor capacity andthe inlet and outlet temperatures. The coolingwater outlet temperature depends on the circu-lated volume and the inlet temperature. In theusual case, to protect the refrigerating machine,temperature monitoring at the output of thecondenser is sufficient.

    Under certain circumstances, further safetymeasures are required for protecting the recool-ing system. Thus, to avoid damage, the inlettemperature in sinkholes or floor heating maynot exceed a maximum permissible value.Quick-acting valves which can close automati-cally without current might be necessary forthis.

    In addition, the condenser circuit is to be protec-ted from faulty static and dynamic pressures bya pressurising system and a safety relief valve. In order for the flow volume to be guaranteedduring the parallel operation of several vaporis-ers with their own circulating pumps, pipeworkin accordance with Tichelmann or with hydraulicdecouplers are recommendable.

    Condenser circuit with minimum protection

    VaporiserCapacitors

    operation of several vaporisers with their owncirculating pumps, pipework in accordance withTichelmann or with hydraulic decouplers are recommendable.

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 49

  • Protection of circulating pumps

    If the constraints are not observed, circulatingpumps can be damaged or destroyed by incor-rect pressures, fluids, forces, temperatures, cir-cuits, power supplies, vibrations, locations andcontrol-/operating modes.

    Fluid pressures

    The housing and impeller can be damaged or destroyed by cavitation due to excessively lowstatic pressure on the suction side of the circu-lating pump. The suction connection is also me-chanically destroyed if oscillations are alsoformed in the suction line due to gas formationor air suctioning. This won't happen directly, butbecomes apparent after a while, depending onthe conditions. In glandless pumps, the bearinglubrication stops and in the case of glandedpumps, the cooling film on the surface of themechanical seal is missing. This can be avoidedby monitoring the inlet pressure with pressuregauges-/or vacuum meters.

    An excessively high static pressure can cause thehousing to burst or seals to become ineffective.An excessively high contact pressure in mechan-ical seals can lead to elevated temperatures andpremature wear in the seal. The pump can beswitched off just to make sure with a maximumpressure controller, or a pressure reducer can beinstalled in front of the pump.

    Excessively high differential pressures betweenthe suction and pressure side of the pump leadto overheating in the pump compartment due tothe drive energy, which leads to premature wearin the bearings and seals. Efficient operation isnot reachable since the performance in such anoperating situation is low. This can be managedby differential pressure control, pump freewheeling valves or with overflow controllers.

    The differential pressure between the suctionand pressure side of the pump, which lies to theright outside of the documented manufacturercharacteristic curve, leads to an overload of thedrive and to impermissible forces on the bearing.The lubrication films on the rotating parts whichcome in contact with the fluid are destroyed.This state can be avoided by means of differen-tial pressure control or volume limiters at thepump.

    F U S E P R O T E C T I O N O F P U M P S A N D R E F R I G E R AT I N G M A C H I N E S

    50 Subject to change without prior notice 02/2007 WILO AG

    If, for example, a pump is installed after a hy-draulic decoupler as a feeder for a load connect-ed after it, it must be made sure that in the caseof a partial load, the residual differential pres-sure of this pump isn't too high. The load pumpsare then started up and too many run. If such anoperational situation is to be expected, a differ-ential pressure controller in front of the second-ary pump is the solution.

    Fluid

    If the planning of the system was done with wa-ter as the heat carrier and if, for whatever rea-son, brine is filled, the delivery data of the pumpno longer applies. All manufacturers specify theflow rate for water in their catalogues. Overall, a density and viscosity of 1 is assumed. Any de-viation from this means another flow rate.

    Abrasive substances in the fluid lead to prema-ture pump failure. For this reason, water treatedin accordance with VDI 2035 or VDTV approvedfluids should be filled. For details, see the cata-logues or offers for the respective types.

    If, for example, a system was pressurised withwater, emptied and after six weeks was filled up with a commercially available brine, the in-hibitors of the brine will dissolve the rust in thelines and will cause premature wear in the rotat-ing parts of the pump. In open systems, the fluidis to be subjected to continuously monitoredtreatment and suitable materials are to be se-lected.

    If water mixtures are used, the system is to befilled from a premixing tank with the correctmixing ratio. Adding admixtures later will notlead to a sufficient concentration everywhereand energy transport will not be consistent. Also, there is usually an increased danger of corrosion.

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 50

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 51

    F U S E P R O T E C T I O N O F P U M P S A N D R E F R I G E R AT I N G M A C H I N E S

    Forces

    Pumps are installed in pipeline systems whichproduce forces due to temperature expansionsor vibrations, which act directly on the connec-tion by the flowing fluid. For safety reasons,pumps are to be integrated in the pipeline sys-tem without tension in and loads on the con-nection. The fixed points for the pipes are to beprovided according to the known technical rules.

    Fluids in their flowing state exert dynamic forcesdue to the direction changes caused by bendsand fittings. For this reason, pumps should beinstalled in stabilising sections, diffusers or rec-tifiers on the suction and pressure side, espe-cially in the case of high flow rates.

    Temperatures

    Failing control units make the fluid deviate fromthe design. As a result, cavitation or excessivevolume flows result from excessive fluid tem-peratures. If the operating temperature of thefluid is lower than planned, the volume flowdrops. In both cases, the drive can be overloa-ded and the motor protection switches thepump off for safety reasons. Since systems to-day are operated without maintenance person-nel constantly there due to cost reasons, it isrecommended to monitor the temperatures withalarm equipment.

    Ambient pump temperatures act directly on thedrive and the housing. The housings can usuallyaccommodate over- and undertemperatures,but only when they don't occur suddenly. Theelectrodrive can't be operated under 0C or over40C without having a special design. Machineinstallation rooms are therefore to be well-ven-tilated or cooled. Direct radiated heat on elec-tromotors is to be prevented.

    Circuits

    Motors for star-/delta start-up may not run per-manently in the star configuration. 230-voltdrives can't handle 400 volts. Voltages which aretoo low can also lead to electromotor damage.The mains is to be connected appropriately forthe drive (see catalogues).

    All pumps supply the fluid with energy. This ki-netic energy is converted to heat due to theconservation of energy law (nothing is lost). As long as there is a flow, the heat from thepump is transported. When straight-throughvalves or admixing valves of the loads are closed,the conduction of heat is prevented. Thermal in-sulation and insulation in accordance with ener-gy-saving regulations act like a thermos flaskand the pump compartment heats up.

    In practice, especially in the cooling sector, thepressurising system is not designed for tempera-tures above 110C, but these can be exceeded inpumps operating at zero flow. Overflow equip-ment which allows the fluid to cool can help. It makes more sense to switch off the pump bymonitoring the closing positions of all controlvalves. It is possible to shut down by means of aflow signal transmitter. Here, the pump can beintermittently started again with a forced start-up, in order to register the opening of the con-trol valves.

    Parallel pump operation in a hydraulic systemonly works with the same pump capacities un-less a differential pressure controller checks theworking point and only enables the smallerpump when its pressure capacity has beenreached.

    Series pump operation in a hydraulic system onlyworks with the same pump capacities unless avolume controller checks the working point andonly enables the smaller pump when its volumecapacity has been reached.

    In a closed system, a pump can convert its com-plete delivery head into suction. For this reason,the pressurising system must always be on thesuction side of the pump, or there must be acontrol unit in the pump circuit which limits theflow, and therefore reduces the inlet pressure. If this isn't possible due to installation reasons,the configured pressure of the pressurising sys-tem must be increased by the maximum deliveryhead of the pump at zero volume.

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 51

  • F U S E P R O T E C T I O N O F P U M P S A N D R E F R I G E R AT I N G M A C H I N E S

    52 Subject to change without prior notice 02/2007 WILO AG

    Power supply

    Power supplies from the public mains powersupply are subject to certain constraints whichare taken into account in the design of drivesand control units. Voltage drops can occur dueto lines being too long or too thin, which canlead to output deficits and overheating. Controllines and power lines are to be laid separatelydue to induction processes. Systems are to beprotected against overvoltage (e.g. lightning)and to be switched off in the event of under-voltage. Surge arresters and mains monitoringrelays with all-pole insulation of the power sup-ply provide solutions.

    If self-powered systems, mains replacement op-eration or converter operation are planned, thefollowing conditions must be met: All Wilo pumps are designed to run on Euro-

    pean standard voltage 230/400 V (10 %) inaccordance with DIN IEC 60038. They havebeen marked with the CE marking in accor-dance with the EU machine directive since January 1, 1995. When pumps are utilised in in-stallations with pumping media temperaturesabove 90C, a corresponding heat-resistantconnection line must be used.

    When operating Wilo pumps with control unitsor module accessories, it is essential to adhereto the electrical operating conditions as set outin VDE 0160. When operating glandless andglanded pumps in conjunction with frequency-converter models not supplied by Wilo, it is nec-essary to use output filters to reduce motor noiseand prevent harmful voltage peaks and to ad-here to the following limit values: Glandless pumps with P2 and glanded

    pumps with P2 1.1 kW rate of voltagerise du/dt < 500 V/s, voltage peaks < 850 V.

    Installations with large cable lengths (l > 10 m)between converter and motor may cause increa-ses of the du/dt and levels (resonance). Thesame may happen for operation with more than4 motor units at one voltage source. The outputfilters must be selected as recommended by theconverter manufacturer or filter supplier, respec-tively. The pumps must be operated at a maxi-mum of 95 % of their rated motor speed if thefrequency converter causes motor losses. If gland-less pumps are operated on a frequency conver-ter, the following limits may not be fallen shortof at the connection terminals of the pumps: Umin = 150 V, fmin = 30 Hz

    The service life and operational reliability of acirculating pump depend to a great extent onthe choice of the correct motor protection de-vice. Motor protection switches are unsuitablefor utilisation in conjunction with multi-speedpumps due to their different nominal currentratings at different speed settings which requirecorrespondingly different fuse protection. All glandless circulating pumps are either blocking-current proof provided with internal protection against

    unacceptably high winding temperatures provided with full motor protection through

    thermal winding contact and separate relay provided with full motor protection and built-

    in trip mechanism (for series, see catalogue data).

    No further motor protection by the customer is required except where this is stipulated forblocking current-proof motors and motorswith internal protection against unacceptablyhigh winding temperatures by the energy sup-ply company.

    Standard glanded pumps are to be protected byonsite motor protection switches with a nominalcurrent setting. Full motor protection is onlyachieved, however, when a thermal winding con-tact or a PTC thermistor detector is additionallymonitored.

    If the glanded pump is equipped with a controlmounted to the motor housing, it is equippedwith full motor protection from the manufacturer.

    The protective measure of protective groundingis to be used for frequency converter controllerswith three-phase current connections. Residualcurrent protective equipment in accordance with DIN VDE 0664 is not permitted. Exception:Selective universal-current-sensitive residualcurrent circuit breaker (recommended nominalresidual current = 300 mA).

    Maximum back-up fuses are to be provided according to the onsite installation and the installed devices in accordance with DIN/VDE.The maximum permissible cable/wire cross-sec-tion is to be taken from the catalogues. The am-bient operating conditions are to be taken intoconsideration in selecting the cables. Specialconditions, such as water-pressure tightness orshields, etc. might be required.

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 52

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 53

    F U S E P R O T E C T I O N O F P U M P S A N D R E F R I G E R AT I N G M A C H I N E S

    Vibrations

    Every circulating machine and every flowing fluid generates vibrations. All Wilo pumps arelow-vibration versions. As a result of the system,resonance can occur, and vibrations are amplified.For this reason, please observe the following.

    Pipelines and pumps should be installed in astress-free condition. The pipelines must befixed in such a way that the pump is not sup-porting the weight of the pipeline. In-linepumps are designed for direct horizontal andvertical installation in a pipeline. From a motorpower of 18.5 kW it is not permissible to installthe pump with the pump shaft in a horizontalattitude. On a vertically mounted pump thepipeline must be stress-free and the pump mustbe supported on the pump feet. To suppress vibration amplification, installation on a base isrecommended. Monobloc or standard pumps are to be mounted on concrete foundations ormounting brackets.

    Correct selection of the pump base version isone of the factors of decisive importance forlow-noise operation of the pumps. A direct andrigid connection between the pump unit and thebase block is recommended for the purpose ofincreasing the mass capable of absorbing vibra-tion and for compensating of uncompensatedgravitational forces. Vibration-isolated installa-tion does however require at the same time anelastic intermediate layer for separating thefundament block itself from the solidium.

    The type and the material of the intermediatelayer to be selected depends on a variety of different factors (and areas or responsibility), including among others rotational speed, aggre-gate mass and centre of gravity, constructionaldesign (architect) and the development of otherinfluences caused by pipe lines, etc. (planners/installation company).

    It is recommended - taking into account allstructurally and acoustically relevant criteria -that a qualified building acoustics specialist be given the task of configuration and designwhere necessary.

    The external dimensions of the base block shouldbe about 15 to 20 cm longer in the length andwidth than the external dimensions of the pumpunit. Care should be taken to ensure that thedesign of the base pedestal that no acousticbridges are formed by plaster, tile or auxiliaryconstructions that would nullify or sharply re-duce the sound insulation effect.

    Planners/and installation companies must takecare to ensure that the pipe connections to thepump are completely stress-free in their designand unable to exercise any gravitational or vi-brational influences on the pump housing what-soever.

    Fixed points with no connection to the base arerecommended for the pipe connections on thesuction and pressure sides of the pump.

    Please also observe thechapter "Pump as a noisegenerator".

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 53

  • F U S E P R O T E C T I O N O F P U M P S A N D R E F R I G E R AT I N G M A C H I N E S

    54 Subject to change without prior notice 02/2007 WILO AG

    Sites

    The standard pumps must be protected from theweather and installed in a dry frost -/dust-free,well-ventilated and non-explosive atmosphere.In the case of outdoor installations, special mo-tors and special corrosion protection are re-quired.

    The installation of standard pumps with the mo-tor and terminal box facing downwards is notpermissible. Free space (at least about 1.2 mwithout space requirement for material on twosides) is to be provided for dismounting the mo-tor, lantern and impeller. For a nominal motorpower greater than 4 kW, a suitable tackle sup-port for installation and maintenance work isrecommended. If the pumps are installed higherthan 1.8 m off the ground, there should be onsiteworking platforms which are permanently in-stalled or which can be set-up any time in mo-bile form.

    Borehole and submersible pumps are to have apermanent minimum and maximum water cov-erage, according to their specifications. Thereshould always be sufficient room for loweringand pulling up the pumps and their pipework. In the case of sump installations, intermediateplatforms for installation and maintenance workmust always be available according to the validaccident prevention regulations.

    To test the pump capacity, an inlet and outletsection is to be provided in front of and behindthe pump during pipe installation.

    The minimum dimension for the measuring point Ad and As is 2 times the pipe diameter, for Us 5+Nq/53 and for Ud 2.5. It is recommendedto install pressure gauges with a test cock.

    All rated power data and operating values applyat a rated frequency of 50 Hz, a rated voltage of 230 /400 V to 3 kW or 400/ 690 V starting at4 kW, a maximum coolant temperature (KT - airtemperature) of max. 40C and an installationaltitude of up to 1000 m above mean sea level.For cases outside of these parameters a powerrating reduction must be applied or a larger mo-tor or a higher insulation class must be selected.

    Minimum distances of the measuring points for checking the pump pressure

    Us

    As

    Ud

    Ad

    D

    D

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 54

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 55

    F U S E P R O T E C T I O N O F P U M P S A N D R E F R I G E R AT I N G M A C H I N E S

    Type of control

    Pumps which serve as admission pressure pumpsare only to be switched on/off when the volumedecrease through the secondary pump circuitlies at the required minimum/ maximum flowvolume. When several admission pressure pumpsare operating in parallel, an automatic switch-on/off of the individual pumps within their per-mitted working ranges is required.

    Circulating pumps in secondary circuits are onlyto be switched on when the primary circuit isdelivering the required minimum volume. Theyare to be switched off when the admission pres-sure pump provides so much pressure that thevolume flow is too high.

    If there is an on-site, stepless speed control, the minimum and maximum speed are to be lim-ited so that there is no overloading and the mo-tor self-cooling function is guaranteed. Throttleand bypass controllers in the pump circuit are to be configured so that the maximum and mini-mum permitted volume flows are always guar-anteed. It makes sense to monitor the fluid tem-perature with an automatic limit shut-downfunction on the pump.

    The parallel operation of pumps and the simul-taneous stepless control of one, several or allpumps is only possible with a load-sensitive, automatic switch-on/off or cut-in functionwithin the permissible limits of the flow and delivery head of the individual aggregates.

    In order to avoid malfunctions and damage, theadmission pressure/pressurising system is to bemonitored. Because of the constantly changingpressures in controlled pump circuits, a differentfeed flow is always possible.

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 55

  • PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 56

  • Formula for the pressure / the delivery head H

    HGes = Hgeo + HA HA = HVL + HVA

    Calculation

    HGes = Hgeo + HVL + HVA

    HVL = R I

    HVL = 100 75

    HVL = 7 500 Pa

    Result

    HGes = Hgeo + HVL + HVA

    HGes = 120 000 Pa + 7 500 Pa + 57 127 Pa

    HGes = 184 627 Pa

    Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 57

    Examples for the pump selection in the condenser circuitWell system

    To conduct heat away from the condenser, a wellsystem has been selected. The brine for the suc-tion well lies 10 m under the floor of the installa-tion room for the refrigerating machine. Due tothe geodetic head difference, a submersiblepump system was selected. A pipeline length of30 m results between the submersible pump andthe connection to the refrigerating machine. The suction side of the condenser lies 2 m underthe highest point of the pipeline to the sinkholeand has a total pipe length of 45 m. The heat ca-pacity is 200 kW and should be conducted awayinto the well system with a temperature differ-ence of 6 K. The circulated volume is determinedas follows:

    Formula for volume flow VPU

    Calculation

    Abbreviation Description1.16 Spec. heat capacity [Wh/kgK]

    q Dimensioned temperature difference

    [K] 10-20 K for standard systems

    QN Heat demand [kW]

    HA Pressure loss of the system in Pa

    Hgeo Geodetic pressure head difference in Pa (1 m WS 10 000 Pa)HGes Total pressure loss in Pa

    HVL Pipeline pressure loss in Pa

    HVA Fitting pressure loss in Pa

    R Pipe friction resistance in Pa/m

    L Pipe length

    Resistance values in Pa Density of fluid in kg/m3

    w2 Flow rate in m/s2

    Z Pressure loss in fittings in Pa

    Total losses

    VPU =QN

    1.16 m3/h

    VPU =200

    1.16 6m3/h

    VPU = 28.74 m3/h

    The desired pump head results from the pipelinerequirements. The total altitude difference is 12 m. The pipeline material is PVC in a nominaldiameter of 100. The R value is 100 Pa/m at aflow rate of about 1 m/s. Based on the installedfittings, bends and the condenser resistance, theaddition of 8 bends, a suction valve and 2 shut-off valves results in a value of 114.13.

    HVA = Z

    w2

    Z = Pa2

    999.6 12

    Z = 114.13 Pa2

    Z = 57 127 Pa

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 57

  • E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O N D E N S E R C I R C U I T

    58 Subject to change without prior notice 02/2007 WILO AG

    Flow Q [m/h]

    Del

    iver

    yhe

    adH

    [m] 40

    35

    30

    25

    20

    15

    10

    5

    0 5

    13

    10 15 20 25 30 35 40

    Operating data specifications Flow 28.74 m3/h

    Delivery head 18.5 m

    Pumped fluid Water

    Fluid temperature 10 C

    Density 0.9996 kg/dm3

    Kinematic viscosity 1.31 mm2/s

    Vapor pressure 0.1 bar

    Hydraulic data (duty point) Flow 31.3 m3/h

    Delivery head 20.3 m

    A submersible pump with a flow rate of Q = 28.74 m3/h and H = 18.5 m is to be selected.

    The selected pump is the Wilo-Sub TWU 6-2403with cooling jacket.

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 58

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 59

    E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O N D E N S E R C I R C U I T

    The condenser circuit is cooled via an opencooling tower. At the same capacity of 200 kWand a temperature difference of 5 K, the follow-ing volume flow results:

    Formula for volume flow VPU

    VPU =QN

    1.16 m3/h

    VPU =200

    1.16 5m3/h

    VPU = 34.48 m3/h

    For the pressure loss calculation, a pipe length of88 m is given with 14 bends, 4 stop valves and analtitude difference of 2.2 m between the minimumwater level and nozzle fitting. PVC pipework isselected with a nominal diameter of 80. This re-sults in a resistance coefficient of = 59.7. The result is:

    A monobloc pump with a flow rate of Q = 34.48m3/h and H = 16.5 m is to be selected.

    Formula for the pressure / the delivery head H

    HGes = Hgeo + HA HA = HVL + HVA

    Calculation

    HGes = Hgeo + HVL + HVA

    HVL = R I

    HVL = 400 88

    HVL = 35 200 Pa

    Result

    HGes = Hgeo + HVL + HVA

    HGes = 22 000 Pa + 35 200 Pa + 107 230 Pa

    HGes = 164 430 Pa

    Abbreviation Description1.16 Spec. heat capacity [Wh/kgK]

    q Dimensioned temperature difference

    [K] 10-20 K for standard systems

    QN Heat demand [kW]

    HA Pressure loss of the system in Pa

    Hgeo Geodetic pressure head difference in Pa (1 m WS 10 000 Pa)HGes Total pressure loss in Pa

    HVL Pipeline pressure loss in Pa

    HVA Fitting pressure loss in Pa

    R Pipe friction resistance in Pa/m

    L Pipe length

    Resistance values in Pa Density of fluid in kg/m3

    w2 Flow rate in m/s2

    Z Pressure loss in fittings in Pa

    Total losses

    HVA = Z

    w2

    Z = Pa2

    999.6 1.92

    Z = 59.7 Pa2

    Z = 107 230 Pa

    Open cooling tower system

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 59

  • E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O N D E N S E R C I R C U I T

    60 Subject to change without prior notice 02/2007 WILO AG

    The selected pump is the Wilo-CronoBloc-BL 40/130-3/2 with red brass impeller.

    Cavitation can be ruled out since the water levelin the cooling tower is about 12 m above thepump inlet. The fluid must constantly be saltedand treated due to the corrosion and legionellaproblem.

    Flow Q [m/h]

    Del

    iver

    yhe

    adH

    [m] 26

    24

    20

    22

    16

    18

    12

    14

    10

    4

    8

    2

    0 8 124

    1

    126

    126

    16 20 24 28 32 36 40 44 48 52 56 60 64 68

    Flow Q [m/h]

    NPS

    H[m

    ] 10

    4

    8

    2

    0 8 124 16 20 24 28 32 36 40 44 48 52 56 60 64 68

    126

    Flow Q [m/h]

    Effi

    cien

    cy[%

    ] 80

    40

    60

    20

    0 8 124 16 20 24 28 32 36 40 44 48 52 56 60 64 68

    126

    Flow Q [m/h] Shaf

    tpow

    erP2

    [kW

    ] 4

    2

    3

    1

    0 8 124 16 20 24 28 32 36 40 44 48 52 56 60 64 68

    Operating data specificationsFlow 34.48 m3/h

    Delivery head 16.5 m

    Pumped fluid Water

    Fluid temperature 32 C

    Density 0.9951 kg/dm3

    Kinematic viscosity 0.7605 mm2/s

    Vapor pressure 0.1 bar

    Hydraulic data (duty point)Flow 37.3 m3/h

    Delivery head 19 m

    Shaft power P2 2.51 kW

    Speed 2000 rpm

    NPSH 3.43 m

    Impeller diameter 125 mm

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 60

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 61

    E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O N D E N S E R C I R C U I T

    Closed cooling tower system

    Based on its being winter-proof, the capacity of 200 kW is recooled via a closed cooling tower.Antifrogen L having a concentration of 40 % to 60 % water is filled for frost protection.

    Formula for volume flow VPU

    Calculation

    VPU =200

    1.04 5m3/h

    VPU = 38.46 m3/h

    A pipe length of 88 m is given for calculating thepressure loss, with 14 bends and 4 stop valves.PVC pipework is selected with a nominal diame-ter of 80. This results in a resistance coefficientof = 59.7. The result is:

    A monobloc pump with a flow rate of Q = 38.46 m3/h and H = 19.9 m is selected.

    VPU =QN

    1.04 m3/h

    Formula for the pressure / the delivery head H

    HGes = (Hgeo + HA) fp HA = HVL + HVA

    Calculation

    HGes = (Hgeo + HVL + HVA) fp

    HVL = R I

    HVL = 400 88

    HVL = 35 200 Pa

    Result

    HGes = (Hgeo + HVL + HVA) fp

    HGes = (0 + 35 200 Pa + 111 422 Pa) 1.36

    HGes = 199 406 Pa

    HVA = Z

    w2

    Z = Pa2

    1 034 1.92

    Z = 59.7 Pa2

    Z = 111 422 Pa

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 61

  • E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O N D E N S E R C I R C U I T

    62 Subject to change without prior notice 02/2006 WILO AG

    The selected pump is the Wilo-CronoBloc-BL 40/140-4/2.

    Cavitation can be ruled out since this is a closedcircuit. The diaphragm extension vessel is to bedetermined for a volume expansion of 2 to 5 %.

    Flow Q [m/h]

    Del

    iver

    yhe

    adH

    [m] 30

    242628

    2022

    1618

    1214

    10

    468

    20 8 124

    1

    138

    138

    138

    138

    16 20 24 28 32 36 40 44 48 52 56 60 64 68

    NPS

    H[m

    ]Ef

    fici

    ency

    [%]

    Shaf

    tpow

    erP2

    [kW

    ]

    Flow Q [m/h]

    10

    468

    20 8 124 16 20 24 28 32 36 40 44 48 52 56 60 64 68

    Flow Q [m/h]

    100

    406080

    200 8 124 16 20 24 28 32 36 40 44 48 52 56 60 64 68

    Flow Q [m/h]

    5

    234

    10 8 124 16 20 24 28 32 36 40 44 48 52 56 60 64 68

    Operating data specificationsFlow 38.46 m3/h

    Delivery head 19.9 m

    Pumped fluid Antifrogen L (40 %)

    Fluid temperature 27 C

    Density 1.039 kg/dm3

    Kinematic viscosity 5.963 mm2/s

    Vapor pressure 0.1 bar

    Hydraulic data (duty point)Flow 41.3 m3/h

    Delivery head 23.1 m

    Shaft power P2 2.57 kW

    Speed 2000 rpm

    NPSH 3.67 m

    Impeller diameter 138 mm

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 62

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 63

    E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O N D E N S E R C I R C U I T

    In the case of heat recovery, the flow rate can bedetermined with a larger temperature difference.A difference of 20 K is reasonable. At the samecapacity of 200 kW and a temperature differenceof 20 K, the following volume flow results:

    Formula for volume flow VPU

    Calculation

    VPU =200

    1.16 20m3/h

    VPU = 8.62 m3/h

    VPU =QN

    1.16 m3/h

    Steel pipework is selected with a pipe length of36 m with a nominal diameter of 50, with 8 bendsand 4 flat slide valves. This results in a resistancecoefficient of = 74.9. The result is:

    To minimise maintenance costs, a glandlesspump with a flow rate of Q = 8.62 m3/h and H = 4.09 m is selected.

    Heat recovery via building heating and hot water production

    Formula for the pressure / the delivery head H

    HGes = Hgeo + HA HA = HVL + HVA

    Calculation

    HGes = Hgeo + HVL + HVA

    HVL = R I

    HVL = 160 36

    HVL = 5 760 Pa

    Result

    HGes = Hgeo + HVL + HVA

    HGes = 0 + 5 760 Pa + 35 165 Pa

    HGes = 40 925 Pa

    Abbreviation Description1.16 Spec. heat capacity [Wh/kgK]

    q Dimensioned temperature difference

    [K] 10-20 K for standard systems

    QN Heat demand [kW]

    HA Pressure loss of the system in Pa

    Hgeo Geodetic pressure head difference in Pa (1 m WS 10 000 Pa)HGes Total pressure loss in Pa

    HVL Pipeline pressure loss in Pa

    HVA Fitting pressure loss in Pa

    R Pipe friction resistance in Pa/m

    L Pipe length

    Resistance values in Pa Density of fluid in kg/m3

    w2 Flow rate in m/s2

    Z Pressure loss in fittings in Pa

    Total losses

    HVA = Z

    w2

    Z = Pa2

    977.7 0.982

    Z = 74.9 Pa2

    Z = 35 165 Pa

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 63

  • E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O N D E N S E R C I R C U I T

    64 Subject to change without prior notice 02/2007 WILO AG

    Flow Q [m/h]

    Del

    iver

    yhe

    adH

    [m] 5,0

    4,5

    4,0

    3,5

    3,0

    2,5

    2,0

    1,5

    1,0

    0,5

    0 5

    12

    max

    min

    10 15 20 25 30

    Operating data specificationsFlow 8.62 m3/h

    Delivery head 4.09 m

    Pumped fluid Water

    Fluid temperature 70 C

    Density 0.9777 kg/dm3

    Kinematic viscosity 0.4084 mm2/s

    Vapor pressure 0.3121 bar

    Hydraulic data (duty point)Flow 8.88 m3/h

    Delivery head 4.3 m

    Power consumption P1 0.295 kW

    Speed 2600 rpm Note!The pump must constantly circulate the requiredwater volume when the refrigerating machine isin operation. This is to be ensured by a hydraulicswitch, heat exchanger, differential pressurevalves or bypasses.

    The necessary cooling towers are to be designedwith their own pump, as described before. Whenantifreeze is added, system separation with heatexchangers is recommended.

    The selected pump is the Wilo-TOP-S 50/4 3-PN 6/10.

    Cavitation can be ruled out since this is a closedcircuit. For protection, the condenser circuitshould have its own safety valve and beequipped with its own diaphragm extension vessel for a volume expansion of 2 to 5 %.

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 64

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 65

    E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O N D E N S E R C I R C U I T

    Ground collector system

    To protect against freezing, the system is filledwith a glycol mixture (40% Antifrogen N + 60%water). The circulated volume is determined asfollows:

    Formula for volume flow VPU

    Calculation

    VPU =200

    0.97 6m3/h

    VPU = 34.29 m3/h

    VPU =QN

    0.97 m3/h

    The desired pump head results from the pipelinerequirements. PVC pipeline material is selectedwith a nominal diameter of 125. The R value is 50 Pa/m at a flow rate of about 0.8 m/s. Based on the installed fittings, bends and the conden-ser resistance, the addition of 8 bends and 2 shut-off valves results in a value of 109.63.Another 20 kPa are to be included in the calcula-tion for the collector and the pipe length to beconsidered is 75 m.

    A pump with a flow rate of Q = 34.29 m3/h and H = 9.0 m is to be selected.

    Formula for the pressure / the delivery head H

    HGes = (Hgeo + HA) fp HA = HVL + HVA

    Calculation

    HGes = (Hgeo + HVL + HVA) fp

    HVL = R I

    HVL = 50 75

    HVL = 3 750 Pa

    Result

    HGes = (Hgeo + HVL + HVA) fp

    HGes = (0 + 3 750 Pa + 57 537 Pa) 1.47

    HGes = 90 092 Pa

    Abbreviation Description1.16 Spec. heat capacity [Wh/kgK]

    q Dimensioned temperature difference

    [K] 10-20 K for standard systems

    QN Heat demand [kW]

    HA Pressure loss of the system in Pa

    Hgeo Geodetic pressure head difference in Pa (1 m WS 10 000 Pa)HGes Total pressure loss in Pa

    HVL Pipeline pressure loss in Pa

    HVA Fitting pressure loss in Pa

    R Pipe friction resistance in Pa/m

    L Pipe length

    Resistance values in Pa Density of fluid in kg/m3

    w2 Flow rate in m/s2

    Z Pressure loss in fittings in Pa

    Total losses

    HVA = Z + collector resistance

    w2

    Z = Pa2

    1 070 0.82

    Z = 109.63 Pa2

    Z = 37 537 Pa

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 65

  • E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O N D E N S E R C I R C U I T

    66 Subject to change without prior notice 02/2007 WILO AG

    Flow Q [m/h]

    Del

    iver

    yhe

    adH

    [m] 12

    9

    10

    11

    8

    7

    6

    5

    4

    3

    2

    1

    0 5

    1

    173

    10 15 20 25 30 35 40 45 50 55 60 65

    Operating data specificationsFlow 34.29 m3/h

    Delivery head 9 m

    Pumped fluid Antifrogen N (40%)

    Fluid temperature 10 C

    Density 1.073 kg/dm3

    Kinematic viscosity 4.507 mm2/s

    Vapor pressure 0.1 bar

    Hydraulic data (duty point)Flow 34.7 m3/h

    Delivery head 9.22 m

    Shaft power P2 1.31 kW

    Speed 1450 rpm

    NPSH 2.39 m

    Impeller diameter 173 mm

    The selected pump is the Wilo-CronoLine-IL 65/170-1.5/4.

    Cavitation can be ruled out since this is a closedcircuit. For protection, the condenser circuitshould have its own safety valve and be equip-ped with its own diaphragm extension vessel for a volume expansion of 5 to 7 %.

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 66

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 67

    E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O N D E N S E R C I R C U I T

    The selected pump is the Wilo-CronoBloc- BL 80/150-1.5/4.

    Cavitation can be ruled out since this is a closedcircuit. For protection, the condenser circuitshould have its own safety valve and be equip-ped with its own diaphragm extension vessel for a volume expansion of 5 to 7 %.

    The closed circuit of a ground spike system isspecified with a pressure loss of 3.1 m. The pres-sure for the condenser (2 m) is to be added. The pump must achieve a delivery head of atleast 5.1 m.

    To protect against freezing, the system is filledwith a glycol mixture (40 % Tyfocor L and 60 %water). The circulated volume is determined asfollows:

    Formula for volume flow VPU

    Abbreviation Description0.97 Spec. heat capacity [Wh/kgK]

    q Dimensioned temperature difference

    [K] 2-6 K for standard systems

    QN Heat demand [kW]

    VPU =200

    1.01 4m3/h

    VPU = 49.32 m3/h

    VPU =QN

    1.01 m3/h

    A pump with a flow rate of Q = 49.32 m3/h and H = 5.1 m is to be selected.

    Flow Q [m/h]

    Del

    iver

    yhe

    adH

    [m] 7

    5,5 6

    6,5

    54,5

    43,5

    32,5

    2

    11,5

    0,50 10

    1

    144

    20 30 40 50 60 70 80 90 100 110 120 130

    Operating data specificationsFlow 49.32 m3/h

    Delivery head 5.1 m

    Pumped fluid Tyfocor L (40%)

    Fluid temperature 10 C

    Density 1.045 kg/dm3

    Kinematic viscosity 6.604 mm2/s

    Vapor pressure 0.1 bar

    Hydraulic data (duty point)Flow 52.6 m3/h

    Delivery head 5.78 m

    Shaft power P2 1.41 kW

    Speed 1450 rpm

    NPSH 2.54 m

    Impeller diameter 144 mm

    Ground spike system

    Calculation

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 67

  • 68 Subject to change without prior notice 02/2007 WILO AG

    Examples for the pump selectionin the cold water circuit

    The flow is determined as follows:

    Formula for volume flow VPU

    Abbreviation Description1.16 Spec. heat capacity [Wh/kgK]

    q Dimensioned temperature difference

    [K] 10-20 K for standard systems

    QN Heat demand [kW]

    VPU =QN

    1.16 m3/h

    VPU =227

    1.16 6m3/h

    VPU = 32.61 m3/h

    The pressure loss of the system (4.65 m) is takenas the maximum pump head from a pipeworkcalculation. Due to the main pressure loss of 3 min the individual load circuit, a pump which hasconstant pressure regulation is to be selected.

    Flow rate control with straight-through valves

    Flow rate control with straight-through valves and pump performance adjustment

    M

    M

    M

    M

    65 kW

    37 kW

    6 C

    12 C

    125 kW

    Operating data specificationsFlow 32.61 m3/h

    Delivery head 4.65 m

    Pumped fluid Water

    Fluid temperature 6 C

    Density 0.9999 kg/dm3

    Kinematic viscosity 1.474 mm2/s

    Vapor pressure 0.1 bar

    Hydraulic data (duty point)Flow 32.6 m3/h

    Delivery head 4.65 m

    Power consumption P1 0.699 kW

    Flow Q [m/h]

    Del

    iver

    yhe

    adH

    [m] 14

    987

    13

    101112

    6543210 5

    max

    min

    10 m

    8 m

    6 m

    4 m

    2 m

    10 15 20 25 30 35 40 45

    0 5 10 15 20 25 30 35 40 45

    Flow Q [m/h]

    Pow

    erco

    nsum

    ptio

    nP1

    [kW

    ] 0,9

    0,6

    0,5

    0,8

    0,7

    0,4

    0,3

    0,2

    0,1

    max

    min

    10 m

    8 m

    6 m

    4 m

    2 m

    Calculation

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 68

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 69

    Wilo-Stratos 65/1-12 PN 6/10 is the choice. This pump is low-maintenance and works withlittle energy. To protect against corrosion bycondensation water, the pump is equipped witha Wilo-ClimaForm.

    By monitoring the open position of the controlvalves, the pump is to be switched off when thevalves are closed to protect against running dry.If this isn't possible, for example because thedistances of the distributor line are too long, anoverflow of 10% is to be permanently ensured at the ends of the distributor line (see short sec-tion in the schematic diagram). Note: It may benecessary to dimension the pump larger!

    Cavitation can be ruled out since this is a closedcircuit. For protection, the vaporiser circuit shouldhave its own safety valve and be equipped withits own diaphragm extension vessel for a volumeexpansion of 5 to 7 %.

    E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O L D WAT E R C I R C U I T

    n

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 69

  • E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O L D WAT E R C I R C U I T

    70 Subject to change without prior notice 02/2007 WILO AG

    Flow rate control with distributor valve

    For maintaining the temperature in the con-trolled system of the load, a flow rate controlwith distributor valves is selected. The pump requires a flow of 10% at the duty point for the smallest load, which is ensured via throttlevalves or volume limiters in the admix line.

    The flow is determined as follows:

    Formula for volume flow VPU

    Abbreviation Description1.16 Spec. heat capacity [Wh/kgK]

    q Dimensioned temperature difference

    [K] 10-20 K for standard systems

    QN Heat demand [kW]

    VPU =QN

    1.16 m3/h

    VPU =227

    1.16 5m3/h

    VPU = 38.79 m3/h

    Since a long pipe section is to be overcome up to the loads, a p-v controlled pump can be se-lected. In the load circuit, only 4 m is requiredfrom the 8.2 m delivery head of the pump.

    Flow rate control with distributor valves andpump performance adjustment

    M

    55 kW

    45 kW

    18 C

    23 C

    125 kW

    M

    M

    M

    Operating data specificationsFlow 38.79 m3/h

    Delivery head 8.2 m

    Pumped fluid Water

    Fluid temperature 18 C

    Density 0.9966 kg/dm3

    Kinematic viscosity 1.053 mm2/s

    Vapor pressure 0.1 bar

    Hydraulic data (duty point)Flow 38.8 m3/h

    Delivery head 8.2 m

    Power consumption P1 1.34 kW

    Flow Q [m/h]

    Del

    iver

    yhe

    adH

    [m] 14

    987

    13

    1011 12

    6543210 5

    12 m

    max

    min

    10 m

    8 m

    6 m

    4 m

    10 15 20 25 30 35 40 45 50 55 60 65 70

    Flow Q [m/h]

    Pow

    erco

    nsum

    ptio

    nP1

    [kW

    ] 1,8

    1,2

    1

    1,6

    1,4

    0,8

    0,6

    0,4

    0,2

    0 5

    12 m

    max

    min

    10 m

    8 m6 m

    4 m

    10 15 20 25 30 35 40 45 50 55 60 65 70

    Calculation

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 70

  • Wilo Planning Guide - Refrigeration, air-conditioning and cooling technology 02/2007 71

    E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O L D WAT E R C I R C U I T

    Only the Wilo-Stratos 80/1-12 is a good choiceconsidering the low maintenance and operatingcosts. The setpoint curve to be adjusted in thecontrolled state runs between 8.6 m (max. speed)and 4.3 m (min. control speed). This guaranteesthat only a maximum of 10% of the dimensionedvolume flows for maintaining the temperature inthe distributor circuit when the bypass section iscorrectly configured.

    Cavitation can be ruled out since this is a closedcircuit. For protection, the vaporiser circuit shouldhave its own safety valve and be equipped withits own diaphragm extension vessel for a volumeexpansion of 5 to 7 %.

    PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 71

  • E X A M P L E S F O R T H E P U M P S E L E C T I O N I N T H E C O L D WAT E R C I R C U I T

    72 Subject to change without prior notice 02/2007 WILO AG

    Admixin