36
RT-PRC022-E4 Voyager™ III Rooftop Units Cooling-only TKD/TKH 275-300-350-400-500-600 Heat-pump WKD/WKH 400-500-600 Gas-fired YKD/YKH 275-300-350-400-500-600 Heat pump with gas-fired heating DKD-DKH 400-500-600 R410A Refrigerant Voyager™ III Rooftop Units

Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Embed Size (px)

Citation preview

Page 1: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

RT-PRC022-E4

Voyager™ IIIRooftop Units

Cooling-only

TKD/TKH 275-300-350-400-500-600

Heat-pump

WKD/WKH 400-500-600

Gas-fired

YKD/YKH 275-300-350-400-500-600

Heat pump with gas-fired heating

DKD-DKH 400-500-600

R410A Refrigerant

Voyager™ III

Rooftop Units

Page 2: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

RT-PRC022-E4© 2013 Trane

Page 3: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Contents

3RT-PRC022-E4

Features and benefits 4

Options and accessories 9

Selection procedure 16

General data 17

Performance data 21

Gas burner performance 21Supply fan performances 22Sound levels 23

Electrical data 25

Dimensions and weights 26Dimensions, weights and clearances 25Weights of factory-installed accessories 26

Controls 28Equipment protection/operation 27Field-installed control options 28Room thermostats 29

Mechanical specifications 30Options and Accessories 32

Page 4: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Features and benefits

Standard Features• Factory installed and tested

microelectronic controls• Scroll compressors• Dedicated downflow or horizontal

configuration• FROSTAT™ coil frost protection on

all units• Supply airflow proving• Emergency stop input• Compressor lead-lag• Occupied-unoccupied switching• Timed override activation• FC supply fans• 50 mm standard efficiency filters

to start the system up• Finish exceeds salt spray

requirements of ASTM B117• Sloped condensate drain pan

Scroll Compressor

Simple Design with 70% Fewer

Parts

Fewer parts than an equal capacityreciprocating compressor meanssignificant reliability and efficiencybenefits. The single orbiting scrolleliminates the need for pistons,connecting rods, wrist pins andvalves. Fewer parts lead to increasedreliability. Fewer moving parts, lessrotating mass and less internalfriction means greater efficiency thanreciprocating compressors. The Scrollprovides important reliability andefficiency benefits. The Scroll allowsthe orbiting scrolls to be in contact inall three dimensions, forming acompletely enclosed compressionchamber which leads to increasedefficiency. In addition, the orbitingscrolls only come in contact with theminimum required force to create aseal so there is no wear between thescroll plates. The fixed and orbitingscrolls are made of high strength castiron which results in less thermaldistortion, less leakage, and higherefficiencies. The most outstandingfeature of the Scroll is that theslugging will not cause failure. Incontrast, the liquid or dirt found in areciprocating compressor may causeserious damage.

Low Torque Variation

The Scroll compressor has a verysmooth compression cycle withtorque variations that are only30 percent of that produced by areciprocating compressor. This meansthe scroll compressor imposes verylittle stress on the motor for greaterreliability. Low torque variationmeans reduced noise and vibration.

Figure 1

Suction Gas Cooled Motor

Compressor motor efficiency andreliability is further optimized withthis design. Cool suction gas keepsthe motor cooler for longer life andbetter efficiency.

4 RT-PRC022-E4

Page 5: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Features and benefits

Proven Design Through Testing and

Research

With over twenty years ofdevelopment and testing, Scrollcompressors have undergone morethan 400,000 hours of laboratorytesting and field operation. This workcombined with over 25 patentsmakes Trane the worldwide leader inair conditioning scroll compressortechnology.

Figure 2 - One of two matched scrollplates - the distinguishing feature of thescroll compressor.

Figure 3 - Low torque variation of 3-Dscroll compressors vs. reciprocatingcompressor

1 = Torque (%)2 = Crank angle3 = Scroll4 = 4 Cylinder reciprocating

Quality and Reliability

Reliatel controls

• Reliatel requires no special tools torun the Voyager unit through itspaces. Simply press the Test buttonlocated on the right side of thecontrol panel and the unit will walkthrough its operational stepsautomatically.

• As long as the unit has power andthe LED is lit, Reliatel is operational.The light indicates that Reliatel isfunctioning properly.

• Reliatel features expandeddiagnostic capabilities whenutilized with Trane's IntegratedComfortTM Systems.

• One Zone Sensor option has centralcontrol panel lights which indicatethe mode the unit is in and possiblediagnostic information (dirty filtersfor example).

0

20

40

60

80

20

40

60

80

100

90˚ 180˚ 270˚ 360˚

1

2

3

4

Figure 4 - RTRM (ReliaTel™ RefrigerationModule)

• Reliatel improves quality andreliability through the use of time-tested microprocessor controls andlogic. Reliatel:- prevents the unit from shortcycling, considerably improvingcompressor life.- ensures that the compressor willrun for a specific amount of timeallowing oil to return for betterlubrication, enhancing thereliability of the compressor.

• The Voyager with Reliatel reducesthe number of componentsrequired to operate the unit,thereby reducing possibilities forcomponent failure.

The unit is equipped in standard withphase reversing protectionpreventing reverse rotationoperation on compressors and otherunit motors.

RT-PRC022-E4 5

Page 6: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Features and benefits

Modulating Gas Burner

• EfficiencyThe modulating gas burner operatesas a condensing gas burner for themain part of its operating range. Thisresult in a drastically improvedefficiency (up to 105%) and optimumenergy usage.

• ComfortThe modulating burner adapts theheating capacity to the buildingneed. Modulation of heating capacityresults in continuous operation of theburner at part load. Reduced ON-OFFcycling improves the gasconsumption used during each startup of the burner as well as dischargeair temperature variation.

Temperature uniformity: Control ofthe supply air temperature reducesair stratification effect caused by hightemperature supply air. This result ina better mixing of the supply air withthe air in the room.• ReliabilityFull stainless steel weldedconstruction ensures reliable heatexchanger tightness.

Flame control: Ignition andcombustion controller use a provendirect spark ignition with pre-mixburner technology. This result in aconstant gas/air mix and optimizedcombustion quality over thecomplete operating map.

Drum and Tube Gas Heat Exchanger

• The drum and tube heat exchangeris designed for increased efficiencyand reliability and has utilizedimproved technology incorporatedin the large rooftop commercialunits for almost 20 years.

• The heat exchanger ismanufactured using aluminizedsteel with stainless steelcomponents for maximumdurability. The drum and tubedesign has been tested and passedover 150,000 cycles.

• The negative pressure gas valve willnot allow gas flow unless thecombustion blower is operating.This is one of our unique safetyfeatures.

• The forced combustion blowersupplies premixed fuel through asingle stainless steel burner screeninto a sealed drum where ignitiontakes place. It is more reliable tooperate and maintain than amultiple burner system.

• The ignitor is a gas ignition devicewhich doubles as a safety deviceutilizing a continuous test to provethe flame. The design is cycle testedat the factory for quality andreliability.

• The Trane Voyager Rooftop has, by

far, the best COP in its class. All

performances are Eurovent

certified which provides the

assurance of accurate

performance and common

comparison criteria.

Rigorous Testing

• All of Voyager's designs wererigorously rain tested at the factoryto ensure water integrity.

• Rigging tests include lifting a unitinto the air and letting it drop onefoot, assuring that the lifting lugsand rails hold up under stress.

• We perform a 100% coil leak test atthe factory. The evaporator andcondenser coils are leak tested at1.4 MPa and pressure tested to3.1 MPa.

• All parts are inspected at the pointof final assembly. Sub-standardparts are identified and rejectedimmediately.

• Every unit receives a 100% unit

run test before leaving the

production line to make sure it

lives up to rigorous Trane

requirements.

6 RT-PRC022-E4

Page 7: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Features and benefits

Figure 5 - Variable speed direct drivesupply fan

Variable Speed Direct Drive

Supply Fan

Efficient, flexible and lowmaintenance direct driven fan

High efficiency fan

Direct transmission, variable speeddrives delivers energy saving through3 aspects :• Higher fan nominal efficiency: The

pulley no longer penalizes theairflow stream at the an inlet,resulting in less turbulence andhigher fan static efficiency.

• Direct coupling drive efficiency:The direct coupling conceptavoids losses by belt friction.Classic belt drive is depletes partof the motor power caused byimproper belt tension, pulley mis-alignment. The direct driven fanimproves motor consumption byabout 15% to 20% compared tobelt driven fan.

• Reduction of power input with fanspeed modulation at part load orin ventilation mode. Substantialenergy savings can be achieved byreducing fan speed by only 20%,resulting in 20% less airflow and50% less absorbed power. On atypical application, the result is anannual energy saving of 30% ofthe total rooftop consumption.

• Power factor of the fan motor iscorrected and inrush current isvery low thanks to progressive fanramp up start (by default: 1minute ramp up time).

Reduced maintenance costs with :• Almost no maintenance direct

coupling compared to belt drive.• Easy commissioning with

adjustment of nominal airlfow andramp up time for progressivetextile duct inflation.

Ease of Installation

Voyager units provide many time andmoney saving features.

Conversionless Units

The dedicated design units (eitherdownflow or horizontal) require nopanel removal or alteration time toconvert in the field - a major costsaving during installation.

Improved Airflow

U-shaped airflow allows for improvedstatic capabilities. The need for highstatic motor conversion is minimizedand time is not spent changing tohigh static oversized motors.

Single Point Power

A single electrical connection powersthe unit.

Single side access

Service technicians can access allmajor components from one side,opening the easy access panels.

Standardized components

• Components are placed in thesame location for all Voyager units.

• One single Unit controller (ReliatelTM) can fit all Voyager models.This provides standardization ofparts.

RT-PRC022-E4 7

Page 8: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Features and benefits

Serviceability

Voyager was designed with inputfrom service contractors. Theirinformation helped us design a unitthat would get the service technicianoff the job quicker and save theowner money.

Voyager's Simpler Design

The Voyager design uses fewer partsthan previous units. Since it is simplerin design, it is easier to diagnose.

Micro

• The Micro requires no special toolsto run the Voyager unit through itspaces. Simply press the Test buttonlocated on the right side of thecontrol panel and the unit will walkthrough its operational stepsautomatically.

• As long as the unit has power andthe LED is lit, the Micro isoperational. The light indicates thatthe Micro is functioning properly.

• The Micro features expandeddiagnostic capabilities whenutilized with Trane's IntegratedComfortTM Systems.

• One Zone Sensor option has centralcontrol panel lights which indicatethe mode the unit is in and possiblediagnostic information (dirty filtersfor example).

Easy Access Low Voltage Terminal

Board

Voyager's Low Voltage TerminalBoard is external to the electricalcontrol cabinet. It is extremely easy tolocate and attach the thermostatwire. This is another cost and timesaving installation feature.

Indoor Air Quality• Filters. All rooftops are shipped

with throw-away filters as astandard to be used during the firstdays of operation (usually thejobsite is not completely clean, andhigh efficiency filters would getdirty in a couple of hours, thiswould be a waste of money). Wepropose optional EU4 permanentfilters for regular operation.

• Panels in the indoor air sectionhave a fire-resistant (M0) aluminumfoil-faced insulation. There is nomore insulation particles carriedover by the air. It can be cleanedwhich is particularly interesting forrestaurant applications.

• All our drain pains are sloped. Wethus avoid water stagnation thatgenerates corrosion and micro-organism life such as mold andfungi.

Reliatel Unit Controller Benefits

• Reliatel in the Voyager units hasbuilt-in anti-short-cycle timer, timedelay relay and minimum "on" timecontrols. These controls arefunctions of Reliatel and are factorytested to assure proper operation.

• Reliatel softens electrical "spikes"by staging on fans, compressorsand heaters.

• The Intelligent Fallback or AdaptiveControl is a benefit to the buildingoccupant. If a component goesastray, the unit will continue tooperate at predeterminedtemperature set point.

• Intelligent Anticipation is astandard feature of Reliatel. Itfunctions constantly as Reliatel andzone sensor work together inharmony to provide tightercomfort control than conventionalelectromechanical thermostats.

On dual fuel units (DKD/DKH), Reliatelautomatically selects the best sourceof heat. In low ambient operation,when mechanical heating is notdelivering enough perforamnce, thecompressor switches off and the gasburner delivers heat in optimizedconditions. This result in an optimizedenergy consumption and highercompressor life cyle.

8 RT-PRC022-E4

Page 9: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Options and accessories

In order to best suit customers requirements, Trane commercial Voyager can befitted with a lot of options and accessories. The following table demonstratesthese capabilities.

TKD TKH WKD WKH YKD YKH DKD DKH Application Description Incompatible with

FRESH AIR OPTIONS

0-25% manualfresh air hood

O O O O O O O OFresh air needed in thebuilding, up to 25% of thenominal airflow.

Manually sets a permanent amount of fresh air inthe unit, between 0-25% of the nominal airflow.

Economizer, CO2sensor, remotepotentiometer,barometric relief,power exhaust fans.

Economizercomparativeenthalpycontrol

O O O O O O O O

Fresh air needed in thebuilding, up to 50% ofnominal airflow, andintelligent energy saving.

The economizer is composed of 2 sets oftemperature and humidity sensors that measureambient and room enthalpy, and of a fresh airdamper connected to a return air damper. Thefree-cooling function modulates between thepermanent set value (between 0-50%) and 100%of the nominal airflow using the fresh airenthalpy to cool down the building. It also has apermanent fresh air function.

0-25% manual hood.

EnergyRecoveryModule

O O O O O O O O

When unit has to operatewith a fresh air rate higherthan 15% in extreme outdoortemperature (winter andsummer). It is important torecover heat from exhaust airand transfer it to the fresh air.Result is a reduction of theinstalled heating/coolingcapacity.

A energy recovery module is installed on thefresh air side of the unit.2 technologies for 2levels of efficiency (Plate heat exchangerefficiency 50-60%, Heat recovery wheelefficiency 60-85%)Free cooling function is integrated (100% freshair with by-passed exhanger).Heat recovery wheel has an hygroscopictreatment allowing partial transfer of moisture inparralel to sensible heat.

0-25% manual hood.

Remotepotentiometer

A A A A A A A ATo remotely set thepermanent fresh air intake.

Connected to the potentiometer of theeconomizer, can modify remotely the permanentfresh air amount brought into the unit between0-50% of the nominal airflow.

0-25% manual fresh airhood, notrecommended withCO2 sensor.

CO2 sensor O O O O O O O O Hygienic control of the air.

Works with the economizer and brings fresh air(modulating between the permanent fresh airsetpoint and 50% of the nominal airflow)whenever the CO2 concentration in the roommeets or exceeds the adjustable threshold. Thesensor itself has to be mounted in a relevantplace in the room or in the ductwork.

0-25% manual hood,not recommended withremote potentiometer.

Barometricrelief

O O O O O O O O

To minimize overpressure inthe building when fresh airintake is around 25% andpressure drop in the returnduct is very low.

Damper placed in the return section opens withthe overpressurization of the return air. 25% ofthis return air is blown outside.

0-25% manual hood,exhaust fans.

Exhaust fans O O O O O O O O

To minimize overpressure inthe building caused by theintroduction of fresh air,when the economizer freshair damper set at 40-50% OA(permanent value), and/orwhen the pressure drop inthe return duct is betweenthe building overpressureaccepted by the customer(12-25 Pa) and 200 Pa(maximum fan staticpressure).

When the exhaust fans are off, the gravitydampers open with increased building pressureto relieve the air pressure. When the exhaustfans are on, around 50% of airflow can beexhausted, depending on the pressure drop ofthe return.They turn on whenever the position ofthe economizer fresh air dampers meet orexceed the power exhaust setpoint (when thesupply fan is on).

0-25% manual fresh airhood, barometric reliefoption (because it isalready included in the « exhaust fans » option).

LegendA = Accessory (to be mounted on site)O = Option (factory mounted and tested)S = Standard feature mounted on all unitsOther options or configurations are available. Please contact your local sales office for more information.

RT-PRC022-E4 9

Page 10: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Options and accessories

LegendA = Accessory (to be mounted on site)O = Option (factory mounted and tested)S = Standard feature mounted on all unitsOther options or configurations are available. Please contact your local sales office for more information.

TKD TKH WKD WKH YKD YKH DKD DKH Application Description Incompatible with

HEATING DEVICES

Hot water coil O O O O - - - -

Need of heating oradditional heating oncooling only units or heatpump units. Hot waterloop available on site.

Avoids the powerconsumption of an electricheater by using the hot waterloop available to heat thebuilding.

Electric heaters, gas fired units.

Modulating Gas burner - - O O - - O O

Need more efficient gasburner (Condensing atpart load)Low mixed airtemperature (<5° C).Need dischargetemperature control.

Modulating heat outputadapted to the building needand discharge temperature.Condensation of flue gasesallow efficiency to rise up to105%.

Electric heaters, Hot water coil

Electric heaters O O O O - - - -

Need of heating oradditional heating oncooling only units or heatpump units. Very usefulwith a heat pump unit tokeep a good comfort levelduring the defrost cycle.

On a heat pump unit, inheating mode, turns on whenthe compressors job does notraise the temperature fastenough. On a heat pump, inheating mode, during theoutdoor coil defrost cycle, theelectric heater turns on toavoid blowing cold air in thebuilding.

Hot water coil, gas fired units.

VENTILATION

EU4 filters 50 mm & 100mm

O O O O O O O OTo filter the air (with lesspressure drop for 100mmfilters).

Washable media, treat thereturn and fresh air, 90%gravimetrical efficiency.

Clogged filter detector O O O O O O O OTo facilitate maintenanceof the filters.

When the pressure drop of thefilter exceeds the selectablevalue, this differentialpressostat report an alarm viaa dry contact to the micro-control.

80%-100% inverteron indoor fan (Beltdriven)

O O O O O O O OUsed to reduce fanspeed and provideenergy savings.

Speed inverter controls fanspeed automatically down to80% during part load, free-cooling and ventilation onlymode.

80%-100% inverteron indoor fan (Directdriven)

O O O O O O O O

Combine energy savingsof fan speed rediction andreduced transmission lossof the direct coupling.

Speed inverter controls fanspeed automatically down to80% during part load, free-cooling and ventilation onlymode. Additional saving ofdirect coupling that improvemotor absorned power by 10to 15% compared to beltdriven fan.

Soft starter O O O O O O O OTo achieve a progressivesupply fan start.

Soft starter option achieved bythe inverter. Starting time canbe adjusted from 0 to 3800seconds (factory-set at 60 s).

80%-100% inverteron indoor fan + soft starter

O O O O O O O O

Used to reduce fan speed,provide energy savings,and achieve a progressivesupply fan start.

Fan speed automatically dropsto 80% during part load, free-cooling mode and inventilation only. Soft starteroption achieved by theinverter.

10 RT-PRC022-E4

Page 11: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Options and accessories

TKD TKH WKD WKH YKD YKH DKD DKH Application DescriptionIncompa-tible

with

SAFETY

Firethermostat

A A A A A A A ATo stop the unit whentemperature of the airstream rises abnormally.

A kit of 2 manual reset thermostats aredelivered. The first one, to be placed in thereturn duct, stops the unit and put the unit ingeneral fault when the airstream rises above57° C, the second, to be placed in the supplyduct, reacts above 115° C. Temperaturethreshold cannot be changed.

Smokedetector

O O O O O O O OTo detect smoke in thebuilding.

Closes the return air damper if an economizer isinstalled, stops the indoor fan, switches off theelectric heater if installed and energized,and put the unit in general fault. This optionprovides a post ventilation period of 30 secondsin the case of high temperature cut out.

Hightemperaturesafetythermostat

- - - - O O O O

For the French ERPregulation only :additional securitythermostat for gas-firedunits.

This manual reset thermostat switches off theburner and the supply fan, and put the unit ingeneral fault if the supply temperature risesabove 120° C.

Fan failureswitch

O O O O O O O O

To improve security andreliability of the unit(when the indoor fan beltbreaks down forinstance).

Detects the lack of fan static pressure. If theindoor fan fails, then the unit operation is shutdown and the "Service" light LED on the ZoneSensor starts flashing. If no air flow goingthrough the unit is detected within 40 seconds(by differential pressure), the control will shutoff all mechanical operations, lock the system,send a diagnostic to the ICS, and the "Service"LED will flash. The system will remain lockeduntil a reset is initiated either manually orthrough the ICS. The option board is required.

Indoor fanbelt guard

O O O O O O O O

Used to improve safetywhen accessing the unit,during maintenance andto comply with somelocal regulations.

Two grids placed around the indoor fan beltdrive prevent people from letting their hands orfingers get in contact with the moving parts andtherefore reduce the risk of injury.

Three-PhaseMonitoringRelayPhaserevresal +Phase loss

S S S S S S S S

This device monitorsthree-phase power supplyin order to protect unitmotors. It prevent risk of startingunit in reverse roation andphase loss that couldcause motor burn out.

The relay disables the unit control when one ofthe following failures occurs on power supply:phase reversal, phase loss.No fault reporting is not delayed.

Three-PhaseMonitoringRelayPhaserevresal +Phase loss +Phaseimbalance

O O O O O O O O

This device monitorsthree-phase power supplyin order to protect unitmotors. This option isrecommended when thereare risks of power supplyimbalance or when powerfactor correctioncapacitors are used.

The relay disables the unit control when one ofthe following failures occurs on power supply:phase reversal, phase loss, phase imbalance(adjustable setting). The recommended settingis as follows: 5% imbalance on 3-phase voltage.Duration of imbalance should be set at 5seconds.

ROOFCURBS

Standardroofcurb

A - A - A - A -Connection between aflat roof and the rooftop.

Supports the rooftop and ensureswatertightness roof/roofcurb/rooftop, and easyconnection of the ductwork .

Adjustableroofcurb.

Adjustableroofcurb

A - A - A - A -Connection between asloped roof and therooftop.

Supports the rooftop and ensureswatertightness roof/roofcurb/rooftop, and easyconnection of the ductwork, correcting slope upto 5%.

Standardroofcurb.

LegendA = Accessory (to be mounted on site)O = Option (factory mounted and tested)S = Standard feature mounted on all unitsOther options or configurations are available. Please contact your local sales office for more information.

RT-PRC022-E4 11

Page 12: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Options and accessories

LegendA = Accessory (to be mounted on site)O = Option (factory mounted and tested)S = Standard feature mounted on all unitsOther options or configurations are available. Please contact your local sales office for more information.

TKD TKH WKD WKH YKD YKH DKD DKH Application DescriptionIncompatible

with

CONTROL

Reliatel™ OptionsModule (RTOM)

S S S S S S S S

Required for someoptional ReliaTel™ devices(frostat, clogged filterswitch, fan failure switch,discharge air sensor (DAS)used for supply airtempering and ICS inputdata, smoke detector,external on/off switch).

Communication interface between theReliatel™ Refrigeration Module (RTRM)and some options.

TCI-R O O O O O O O O

To communicate withTrane Integrated ComfortSystems, such as theTracer Summit™, theTracker™ or a Varitrac™system (CCP2).

Communication interface between aTrane ICS device and a Voyager™.

THS/P 01-03,remote sensorsfor THS/P 01,LCI-R

LCI-R O O O O O O O OTo communicate on aLonTalk®network at theunit level.

Communication interface between aLonTalk®device and a Voyager™.

THS/P 01-03,remote sensorsfor THS/P 01,TCI-R

THS03 A A A A A A A AControl of 1 cooling-only,heat pump or gas-firedrooftop.

Electronic thermostat, 2 stagescooling, 1 stage compressor heating, 2stages auxiliary heating. No CTI cardneeded, communicates in the samelanguage as the rooftop micro-controland uses 100% of its advanced controlfeatures.

TCI-R, LCI-R.

THP03 A A A A A A A AControl of 1 cooling-only,heat pump or gas-firedrooftop.

Electronic programmable thermostat,2 stages cooling, 1 stage compressorheating, 2 stages auxiliary heating,LCD screen. Communicates in thesame language as the rooftop micro-control and uses 100% of its advancedcontrol features.

TCI-R, LCI-R.

Remote sensor boxfor THS/THP03

A A A A A A A ANeed of remote oradditional sensors withTHS/THP03

Senses the temperature and sends theinformation to the THS/P 03.

THS/P 01

Discharge airsensing ("Supply airtempering")

O O O O O O O O

Supply air temperingmaintains the supply airtemperature above alower limit duringminimum ventilationperiods in heating mode.Also used to monitor truedischarge air temperatureout of the unit.

A sensor is placed in the return airduct.

Hot water coil.

Remote fault relay O O O O O O O OTo send alarms signals to alocal BMS.

Report cool fail, Heat fail & system failinto one dry contact (Normally closedand normally open).

MISCELLANEOUS

Black epoxy coatingon condenser

O O O O O O O O Sea side application.The black epoxy coating slows downthe corrosion process on thealuminum fins.

Black epoxy coatingon condenser andevaporator

O O O O O O O OSea side application whena fresh air device is used.

The black epoxy coating slows downthe corrosion process on thealuminum fins.

12 RT-PRC022-E4

Page 13: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Options and accessories

Exhaust Air Options

When is it necessary to providebuilding exhaust?

Whenever an outdoor air economizeris used, a building generally requiresan exhaust system. The purpose ofthe exhaust system is to exhaust theproper amount of air to prevent overor under-pressurization of thebuilding.

A building may have all or part of itsexhaust system in the rooftop unit.Often, a building provides exhaustexternal to the air conditioningequipment. This external exhaustmust be considered when selectingthe rooftop exhaust system.

Voyager™ Commercial rooftop unitsoffer two types of exhaust systems:

1 Power exhaust fan

2 Barometric relief dampers

Application

recommendations

Power Exhaust Fan

The exhaust fan option is a dual, non-modulating exhaust fan withapproximately half the air-movingcapabilities of the supply fan system.

The experience of The TraneCompany is that a non-modulatingexhaust fan selected for 40 to50 percent of nominal supply airflowcan be applied successfully.

The power exhaust fan generallyshould not be selected for more than40 to 50 percent of design supplyairflow. Since it is an on/off non-modulating fan, it does not varyexhaust airflow with the amount ofoutside air entering the building.Therefore, if selected for more than40 to 50 percent of supply airflow, thebuilding may become under-pressurized when economizeroperation is allowing lesser amountsof outdoor air into the building. If,however, building pressure is not of acritical nature, the non-modulatingexhaust fan may be sized for morethan 50 percent of design supplyairflow.

Figure 6

TKD TKH WKD WKH YKD YKH DKD DKH Application DescriptionIncompatible

with

Phase out

THP01 A A - - A A A AControl of 1 cooling-only /gas-fired rooftop.

Electronic programmable thermostat,2 stages cooling, 2 stages auxiliaryheating, LCD screen.

TCI-R, LCI-R

THS01 A A - - A A A AControl of 1 cooling-only /gas-fired rooftop.

Electronic thermostat, 2 stagescooling, 2 stages auxiliary heating,LCD screen.

TCI-R, LCI-R

Remote sensor boxfor THS/THP01-02

- - A A - - - -Need for remote oradditional sensors withTHS/P 01-02.

Senses the temperature and sends theinformation to the THS/P 01-02.

THS/P 03, TCI-R, LCI-R

Ventilated roofcurbextension (FrenchERP regulations)

A A A A A A A A

Connection between aroofcurb and a rooftopunit installed on a roof.Used to comply to theFrench ERP (EtablissementRecevant du Public:Buildings open to thepublic) regulations.

Avoids contact between the rooftopand the roof. Openings on the sidesallow natural ventilation. Protection ofthe building in case of failure of therooftop causing overheating / fire.

LegendA = Accessory (to be mounted on site)Other options or configurations are available. Please contact your local sales office for more information.

RT-PRC022-E4 13

Page 14: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Options and accessories

Barometric Relief Dampers

Barometric relief dampers consist ofgravity dampers which open withincreased building pressure. As thebuilding pressure increases, thepressure in the unit return sectionalso increases, opening the dampersand relieving air. Barometric reliefmay be used to provide relief forsingle story buildings with no returnductwork and exhaust requirementsless than 25 percent.

Acoustical Considerations

Proper placement of rooftops iscritical to reduce transmitted soundlevels to the building. The ideal timeto make provisions to reduce soundtransmissions is during the designphase. And the most economicalmeans of avoiding an acousticalproblem is to place the rooftop(s)away from acoustically critical areas.If possible, rooftops should not belocated directly above areas such as:offices, conference rooms, executiveoffice areas and classrooms. Instead,ideal locations might be overcorridors, utility rooms, toilets orother areas where higher sound levelsdirectly below the unit(s) areacceptable.

Several basic guidelines for unitplacement should be followed tominimize sound transmission throughthe building structure:1) Never cantilever the compressor

end of the unit. A structural crossmember must support this end ofthe unit.

2) Locate the unit's center of gravityclose to or over column or mainsupport beam.

3) If the roof structure is very light,roof joists must be replaced by astructural shape in the criticalareas described above.

4) If several units are to be placed onone span, they should bestaggered to reduce deflectionover that span.

It is impossible to totally quantify theeffect of building structure on soundtransmission because this depends onthe response of the roof and buildingmembers to the sound and vibrationof the unit components. However, theguidelines listed above areexperience-proven guidelines whichwill help reduce sound transmissions.

Figure 7

14 RT-PRC022-E4

Page 15: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Options and accessories

Energy Recovery Module (ERM)

In order to recover heat from exhasutair, it is recomended to use theenergy recovery module. It is placedon the fresh air side of the unit.

In order to satisfy two levels ofefficiency, two technologies areavailable:

- Plate heat exchanger version withan efficiency of 50 to 60%,

- Heat recovery wheel with anefficiency of 60-85%.

The option is available in the twoairlfow configurations: horizontalflow and downflow

The free cooling function is still validwith this option.

The heat recovery wheel version hasan hygroscopic treatment allowingpartial transfer of moisture in parralelto sensible heat.

Clearance Requirements

The recommended clearancesidentified with unit dimensionsshould be maintained to assureadequate serviceability, maximumcapacity and peak operatingefficiency. Refer to the Minimumrecommended clearances Table inthis manual. A reduction in unitclearance could result in condensercoil starvation or warm condenser airrecirculation. If the clearances shownare not possible on a particular job,consider the following:• Do the clearances available allow

for major service work such aschanging compressors or coils?

• Do the clearances available allowfor proper outside air intake,exhaust air removal andcondenser airflow?

• If screening around the unit isbeing used, is there a possibility ofair recirculation from the exhaustto the outside air intake or fromcondenser exhaust to condenserintake?

Actual clearances which appearinadequate should be reviewed witha local Trane sales engineer.

When two or more units are to beplaced side by side, the distancebetween the units should beincreased to 150 percent of therecommended single unit clearance.The units should also be staggered asshown for two reasons:1) To reduce span deflection if more

than one unit is placed on a singlespan. Reducing deflectiondiscourages sound transmission.

2) To assure proper diffusion ofexhaust air before contact with theoutside air intake of adjacent unit.

Duct Design

It is important to note that the ratedcapacities of the rooftop can be metonly if the rooftop is properlyinstalled in the field. A well designedduct system is essential in meetingthese capacities.

The satisfactory distribution of airthroughout the system requires thatthere be an unrestricted and uniformairflow from the rooftop dischargeduct. This discharge section should bestraight for at least several ductdiameters to allow the conversion offan energy from velocity pressure tostatic pressure.

However, when job conditions dictateelbows be installed near the rooftopoutlet, the loss of capacity and staticpressure may be reduced through theuse of guide vanes and properdirection of the bend in the elbow.The high velocity side of the rooftopoutlet should be directed at theoutside radius of the elbow ratherthan the inside.

RT-PRC022-E4 15

Page 16: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Selection procedure

System type Cooling Only Heat pump

Airflow information

Configuration of return duct 1 - Horizontal flow 2 - Downflow Other ........................................

Configuration of supply duct 3 - Horizontal flow 4 - Downflow Other ........................................

Unit airflow ........................................ m3/h

Fresh air rate ........................................ m3/h ........................................ % of nominal airflow

External static pressure onreturn duct ........................................

Pa

External static pressure onsupply duct ........................................

Pa

Cooling mode design conditions

Unit cooling capacity ........................................ kW

Indoor air Dry Bulb ........................................ ° C

Indoor air wet Bulb / RelativeHumidity ........................................

° C........................................

%

Outdoor air Dry Bulb ........................................ ° C

Heating mode design conditions

Heating capacity ........................................ kW

Auxiliary heat type Electric Heat Gas Heat Hot Water coil

Gas type Natural gas G20 Natural gas G25 Propane gas G31

Auxiliary heating capacity ........................................ kW

Indoor air Dry Bulb ........................................ ° C

Outdoor air Dry Bulb ........................................ ° C

Outdoor air wet Bulb /Relative Humidity ........................................

° C........................................

% (only for Heat pump)

Options

Air filter class ........................................

Variable speed drive With Without

Economizer type Without Manual fresh airComparative enthalpy

economizer

Energy recovery on exhaust /fresh air Without Rotary heat wheel Plate heat exchanger

Fresh air control Constant Remote reference CO2 sensor controled

Unit control Local control withoutscheduling

Local control withscheduling

Multi-unit centralizedcontrol

Remote relay interfacecontrol

Remote control communicationinterface LON Modbus Bacnet Trane

Smoke detector With Without

Fire detector With Without

Disconnect switch With Without

Dirty filter switch With Without

Fan fail switch With Without

Outdoor coil corrosion protection Without Epoxy coating

Indoor coil corrosion protection Without Epoxy coating

Roofcurb None Flat Adjustable pitch

Mandatory informations to select a rooftop

To obtain product selection, please contact your local Trane sales office with the following information:

16 RT-PRC022-E4

Page 17: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

General Data

Table 1 - General data, Cooling only / Gas fired unit

TKD / TKH TKD / TKH TKD / TKH TKD / TKH TKD / TKH TKD / TKH

YKD / YKH YKD / YKH YKD / YKH YKD / YKH YKD / YKH YKD / YKH

275 300 350 400 500 600

Eurovent Performances (1) R410A R410A R410A R410A R410A R410ANet Cooling Capacity (kW) 82.9 88.4 93.3 123.1 135.1 157.5Total Power input in cooling (kW) 24.8 27.1 29.4 40 46.4 58.3EER 3.34 3.26 3.17 3.08 2.91 2.70Eurovent Efficiency class Cooling A A A A B CMain Power supply V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50Outdoor sound power level env. (dBA) 88 88 89 90 90 91Indoor sound power level in duct (dBA) 84 84 85 87 87 88Outdoor sound pressure level env. (6) (dBA) 56 56 57 57 57 58Unit amps

Unit rated amps (3) (A) 76 82 93 116 131 151Unit start up amps (3) (A) 209 248 260 325 393 413Unit power factor (1) 0.78 0.79 0.78 0.77 0.81 0.79Electric Heater

Heating Capacity (kW) 25 37.5 50 62.5 75 75Capacity steps (kW) 12.5 / 12.5 25 / 12.5 25 / 25 25 / 37.5 37.5 / 37.5 37.5 / 37.5Rated Amps (A) 36.1 54.1 72.2 90.2 108.3 108.3Gas burner (YKD / YKH)

Staged Low heat version

Heating Input (G20) (kW) 77 77 77 85 85 85Heating Output (G20) (kW) 69.3 69.3 69.3 77.4 77.4 77.4Steady State Efficiency (%) 90 90 90 91 91 91No. Burners # 1 1 1 1 1 1No. Stages # 2 2 2 2 2 2Gas Connection Pipe Size 3/4" NPT 3/4" NPT 3/4" NPT 3/4" NPT 3/4" NPT 3/4" NPTStaged High heat version

Heating Input (G20) (kW) 130 130 130 170 170 170Heating Output (G20) (kW) 117.5 117.5 117.5 154.8 154.8 154.8Steady State Efficiency (%) 90 90 90 91 91 91No. Burners # 2 2 2 2 2 2No. Stages # 2 2 2 2 2 2Gas Connection Pipe Size 1" NPT 1" NPT 1" NPT 1" NPT 1" NPT 1" NPTModulating gas heat version

Heating Input Min Max (G20) (kW) 44 / 155 44 / 155 44 / 155 44 / 155 44 / 155 44 / 155Heating Output Min/Max (G20) (kW) 46.3 / 145 46.3 / 145 46.3 / 145 46.3 / 145 46.3 / 145 46.3 / 145Steady State Efficiency (%) 105% - 93.5% 105% - 93.5% 105% - 93.5% 105% - 93.5% 105% - 93.5% 105% - 93.5%No. Burners # 1 1 1 1 1 1Modulation % 32%-100% 32%-100% 32%-100% 32%-100% 32%-100% 32%-100%Gas Connection Pipe Size 1" ISO R7 1" ISO R7 1" ISO R7 1" ISO R7 1" ISO R7 1" ISO R7Condensate outlet Pipe Size mm 18 18 18 18 18 18Compressor

Number # 2 2 2 2 2 2Type Scroll Scroll Scroll Scroll Scroll ScrollModel 13T / 13T 13T / 15T 15T / 15T 15T / 25T 15T / 30T 25T / 30TRated Amps (2) (A) 25.1 / 25.1 25.1 / 30.5 30.5 / 30.5 30.5 / 51.2 30.5 / 58 51.2 / 58Locked rotor Amps (2) (A) 158 / 158 158 / 197 197 / 197 197 / 260 197 / 320 260 / 320Outdoor Coil

Type Wavy Wavy Wavy Wavy Wavy WavyTube Size OD (mm) 9.52 9.52 9.52 9.52 9.52 9.52Face Area (m²) 4.8 4.8 4.8 6.1 6.1 6.1Rows / Fin series # / FPF 2 / 192 2 / 192 2 / 192 2 / 192 2 / 192 3 / 192Indoor Coil

Type Wavy Wavy Wavy Wavy Wavy WavyTube Size OD (mm) 9.52 9.52 9.52 9.52 9.52 9.52Face Area (m²) 2.9 2.9 2.9 3.4 3.4 3.4Rows / Fin series # / FPF 3 / 180 3 / 180 3 / 180 4 / 180 4 / 180 4 / 180Refrigerant Control TXV TXV TXV TXV TXV TXVDrain Connection No./Size (mm) 1 / 32mm 1 / 32mm 1 / 32mm 1 / 32mm 1 / 32mm 1 / 32mmOutdoor Fan

Nominal Airflow (m3/h) 41100 41100 41100 48700 48700 43600Type Axial Axial Axial Axial Axial AxialDiameter (mm) 710 710 710 710 710 710Drive type Direct Direct Direct Direct Direct DirectNumber / Voltage # / V 3 / 400V 3 / 400V 3 / 400V 4 / 400V 4 / 400V 4 / 400VMotor HP (kW) 1.1 1.1 1.1 1.1 1.1 1.1Motor Rated Amps (2) (A) 2.5 2.5 2.5 2.5 2.5 2.5Motor RPM (rpm) 915 915 915 915 915 915

RT-PRC022-E4 17

Page 18: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

General data

Table 1 - General data, Cooling only / Gas fired unit (cont.)

TKD / TKH TKD / TKH TKD / TKH TKD / TKH TKD / TKH TKD / TKH

YKD / YKH YKD / YKH YKD / YKH YKD / YKH YKD / YKH YKD / YKH

275 300 350 400 500 600

Indoor Fan

Minimum Airflow (m3/h) 10880 12240 13600 16320 19680 23600Nominal Airflow (m3/h) 13600 15300 17000 20400 24600 29500Maximum Airflow (m3/h) 16320 18360 20400 24480 29520 35400Maximum static pressure available (4) (Pa) 525 520 465 590 600 600Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC CentrifugalDiameter / Width (in / in) 22.4" / 22" 22.4" / 22" 22.4" / 22" 25" / 25" 25" / 25" 25" / 25"Drive type Belt Belt Belt Belt Belt BeltNumber # 1 1 1 1 1 1Motor HP (Standard/Oversized) (kW) 5.5 / 7.5 5.5 / 7.5 5.5 / 11 5.5 / 11 5.5 / 15 5.5 / 15Motor Rated Amps (Standard/Oversized) (A) 11.1 / 15.2 11.1 / 15.2 11.9 / 21.1 11.9 / 21.1 11.1 / 28.8 11.1 / 28.8Motor Locked rotor Amps (Standard/Oversized) (A) 70 / 106 70 / 106 70 / 162 70 / 162 70 / 216 70 / 216Motor RPM (Standard/Oversized) (rpm) 1450 / 1450 1450 / 1450 1450 / 1450 1450 / 1450 1450 / 1450 1450 / 1450Energy Recovery Module (5)

Plate Heat exchanger version

Heat recovery efficiency at 10% / 50% fresh air (%) 62% / 59% 61% / 58% 61% / 58% 61% / 58% 61% / 58% 61% / 57%Air pressure drop at 10% / 50% fresh air (Pa) 3Pa / 56Pa 4Pa / 69Pa 5Pa / 83Pa 2Pa / 38Pa 3Pa / 54Pa 4Pa / 75PaExhaust fan kW at 10% / 50% fresh air (kW) 0.3kW / 0.4kW 0.3kW / 0.6kW 0.3kW / 0.6kW 0.5kW / 0.7kW 0.5kW / 1kW 0.5kW / 1.4kWLength (Downflow / Horizontal flow) (mm) 2288 / 2440 2288 / 2440 2288 / 2440 3050 / 3335 3050 / 3335 3050 / 3335Width (Downflow / Horizontal flow) (mm) 2295 / 2143 2295 / 2143 2295 / 2143 2295 / 2295 2295 / 2295 2295 / 2295Height (Downflow / Horizontal flow) (mm) 1858 / 1808 1858 / 1808 1858 / 1808 2010 / 1960 2010 / 1960 2010 / 1960Weight (Downflow / Horizontal flow) (kg) 799 / 807 799 / 807 799 / 807 1155 / 1240 1155 / 1240 1155 / 1240Rotary Wheel Heat exchanger version

Heat recovery efficiency at 10% / 50% fresh air (%) 84% / 69% 83% / 66% 83% / 64% 85% / 71% 84% / 68% 83% / 64%Air pressure drop at 10% / 50% fresh air (Pa) 10Pa / 72Pa 12Pa / 83Pa 13Pa / 95Pa 13Pa / 91Pa 16Pa / 114Pa 20Pa / 143PaExhaust fan kW at 10% / 50% fresh air (kW) 0.4kW / 0.5kW 0.4kW / 0.7kW 0.4kW / 0.7kW 0.5kW / 0.8kW 0.5kW / 1kW 0.5kW / 1.4kWLength (Downflow / Horizontal flow) (mm) 2440 / 2440 2440 / 2440 2440 / 2440 2745 / 2745 2745 / 2745 2745 / 2745Width (Downflow / Horizontal flow) (mm) 1990 / 2143 1990 / 2143 1990 / 2143 2295 / 2295 2295 / 2295 2295 / 2295Height (Downflow / Horizontal flow) (mm) 2010 / 1960 2010 / 1960 2010 / 1960 2335 / 2265 2335 / 2265 2335 / 2265Weight (Downflow / Horizontal flow) (kg) 877 / 981 877 / 981 877 / 981 1288 / 1363 1288 / 1363 1288 / 1363Power Exhaust Fan (Option)

Type Axial Axial Axial Axial Axial AxialDiameter (mm) 630 630 630 630 630 630Drive type Direct Direct Direct Direct Direct DirectNumber / Voltage # 2 / 400V 2 / 400V 2 / 400V 2 / 400V 2 / 400V 2 / 400VMotor HP (kW) 0.6 0.6 0.6 0.6 0.6 0.6Motor Rated Amps (2) (A) 1.2 1.2 1.2 1.2 1.2 1.2Filters

Type Furnished 2" Throwaway 2" Throwaway 2" Throwaway 2" Throwaway 2" Throwaway 2" Throwaway(No.) Size Recommended 16x(395x495x45) 16x(395x495x45) 16x(395x495x45) 17x(395x495x45) 17x(395x495x45) 17x(395x495x45)Operating limits

Minimum operating outdoor air temp. (Cooling). °C -18 -18 -18 -18 -18 -18Maximum operating outdoor air temp. (Cooling). °C 52 52 52 49 49 52Minimum intake air temp. on the indoor coil (Cooling) °C 16 16 16 16 16 16Minimum intake air temp. on the indoor coil (Heating) °C 5 5 5 5 5 5Dimensions (3)

Length TKD/TKH (mm) 4580 4580 4580 5200 5200 5200YKD/YKH (Low heat) (mm) 4580 4580 4580 5900 5900 5900YKD/YKH (High heat) (mm) 5285 5285 5285 5900 5900 5900Width (mm) 2302 2302 2302 2302 2302 2302Height (mm) 2093 2093 2093 2268 2268 2268Operating weight TKD/TKH (kg) 1625 1629 1655.5 2055 2114 2241YKD/YKH (Low heat) (kg) 1668 1684 1714.5 2169 2227 2494YKD/YKH (High heat) (kg) 1861 1871 1900.5 2225 2284 2551Shipping weight TKD/TKH (kg) 1725 1729 1755.5 2195 2254 2381YKD/YKH (Low heat) (kg) 1768 1784 1914.5 2309 2367 2634YKD/YKH (High heat) (kg) 1981 1991 2020.5 2365 2424 2691Unit construction

Sheet metal / Thickness Type / mm GalvaSteel / 1.2 GalvaSteel / 1.2 GalvaSteel / 1.2 GalvaSteel / 1.2 GalvaSteel / 1.2 GalvaSteel / 1.2Paint Type / RAL Polyester / 9002 Polyester / 9002 Polyester / 9002 Polyester / 9002 Polyester / 9002 Polyester / 9002 Insulation / Thickness Type / mm M0 / 25 M0 / 25 M0 / 25 M0 / 25 M0 / 25 M0 / 25System Data

Refrigerant circuit # 1 1 1 2 2 2Capacity steps % 0 / 50 / 100 0 / 46 / 100 0 / 50 / 100 0 / 37 / 63 / 100 0 / 33 / 66 / 100 0 / 45 / 55 / 100Refrigerant Charge

Circuit A (kg) 20.7 20.7 21.0 7.0 7.0 18.5Circuit B (kg) - - - 21.6 21.6 18.5

(1) At Eurovent rating conditions : Indoor return Air (27° C DB / 19° C WB) - Outdoor Ambient 35° C(2) per motor @ 400V(3) Max load amp for standard unit. with exhaust fan options(4) At the nominal airflow with oversized drive(5) Performance of Energy recovery module given for Indoor 19° C/50% / Outdoor Ambient -5° C(6) At 10m from the unit in a free fieldElectrical & refrigerant charge Data are subject to change without notice. Please refer to unit nameplate data.

18 RT-PRC022-E4

Page 19: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

General data

Table 2 - Reversible / Dual fuel unit

WKD / WKH WKD / WKH WKD / WKH

DKD / DKH DKD / DKH DKD / DKH

400 500 600

Eurovent Performances (1) R410A R410A R410ANet Cooling Capacity (kW) 115.8 134.6 154.7Total Power input in cooling (kW) 39.9 50.8 63.1EER 2.90 2.65 2.45Eurovent Efficiency class Cooling B C DMain Power supply V/Ph/Hz 400/3/50 400/3/50 400/3/50Net Heating Capacity (kW) 106.8 145.6 172.1Total Power input in Heating (kW) 32.5 44.5 52.5COP 3.29 3.27 3.28Eurovent Efficiency class Heating B B BOutdoor sound power level env. (dBA) 90 90 91Indoor sound power level in duct (dBA) 87 87 88Outdoor sound pressure level env. (6) (dBA) 57 57 58Unit amps

Unit rated amps (3) (A) 117 148 162Unit start-up amps (3) (A) 293 357 424Unit power factor (1) 0.78 0.72 0.76Electric Heater (WKD / WKH)

Heating Capacity (kW) 62.5 75 75Capacity steps (kW) 25 / 37.5 37.5 / 37.5 37.5 / 37.5Rated Amps (A) 90.2 108.3 108.3Gas burner (DKD / DKH)

Staged Low heat version

Heating Input (G20) (kW) 85 85 85Heating Output (G20) (kW) 77.4 77.4 77.4Steady State Efficiency (%) 91 91 91No. Burners # 1 1 1No. Stages # 2 2 2Gas Connection Pipe Size 3/4" NPT 3/4" NPT 3/4" NPTStaged High heat versionHeating Input (G20) (kW) 170 170 170Heating Output (G20) (kW) 154.8 154.8 154.8Steady State Efficiency (%) 91 91 91No. Burners # 2 2 2No. Stages # 2 2 2Gas Connection Pipe Size 1" NPT 1" NPT 1" NPTCompressor

Number # 2 2 2Type Scroll Scroll ScrollModel 20T / 20T 25T / 25T 30T / 30TRated Amps (1) (A) 39.7 / 39.7 51.2 / 51.2 58 / 58Locked rotor Amps (2) (A) 215 / 215 260 / 260 320 / 320Outdoor Coil

Type Wavy Wavy WavyTube Size OD (mm) 9.52 9.52 9.52Face Area (m²) 6.3 6.3 6.3Rows / Fin series # / FPF 3 / 168 3 / 168 3 / 168Refrigerant Control TXV TXV TXVIndoor Coil

Type Wavy Wavy WavyTube Size OD (mm) 9.52 9.52 9.52Face Area (m²) 3.4 3.4 3.4Rows / Fin series # / FPF 4 / 180 4 / 180 4 / 180Refrigerant Control TXV TXV TXVDrain Connection No./Size (mm) 1 / 32mm 1 / 32mm 1 / 32mmOutdoor Fan

Nominal Airflow (m3/h) 50600 48100 48100Type Axial Axial AxialDiameter (mm) 710 710 710Drive type Direct Direct DirectNumber / Voltage # / V 4 / 400V 4 / 400V 4 / 400VMotor HP (kW) 1.1 1.1 1.1Motor Rated Amps (1) (A) 2.5 2.5 2.5Motor RPM (rpm) 915 915 915

RT-PRC022-E4 19

Page 20: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

General data

Table 2 - Reversible / Dual fuel unit (cont.)

WKD / WKH WKD / WKH WKD / WKH

DKD / DKH DKD / DKH DKD / DKH

400 500 600

Indoor Fan

Minimum Airflow (m3/h) 16320 19680 23600Nominal Airflow (m3/h) 20400 24600 29500Maximum Airflow (m3/h) 24480 29520 35400Static pressure available (4) (Pa) 590 600 600Type FC Centrifugal FC Centrifugal FC CentrifugalDiameter / Width (in / in) 25" / 25" 25" / 25" 25" / 25"Drive type Belt Belt BeltNumber / Voltage # / V 1 / 400V 1 / 400V 1 / 400VMotor HP (Standard/Oversized) (kW) 5.5 / 11 5.5 / 15 5.5 / 15Motor Rated Amps (Standard/Oversized) (A) 11.1 / 21 11.1 / 28.8 11.1 / 28.8Motor Locked rotor Amps (Standard/Oversized) (A) 70 / 162 70 / 216 70 / 216Motor RPM (Standard/Oversized) (rpm) 1450 / 1450 1450 / 1450 1450 / 1450Energy Recovery Module (5)

Plate Heat exchanger version

Thermal efficiency at 10% / 50% fresh air (%) 61% / 58% 61% / 58% 61% / 57%Air pressure drop at 10% / 50% fresh air (Pa) 2Pa / 38Pa 3Pa / 54Pa 4Pa / 75PaExhaust fan kW at 10% / 50% fresh air (kW) 0.5kW / 0.7kW 0.5kW / 1kW 0.5kW / 1.4kWLength (Downflow / Horizontal flow) (mm) 3050 / 3335 3050 / 3335 3050 / 3335Width (Downflow / Horizontal flow) (mm) 2295 / 2295 2295 / 2295 2295 / 2295Height (Downflow / Horizontal flow) (mm) 2010 / 1960 2010 / 1960 2010 / 1960Weight (Downflow / Horizontal flow) (kg) 1155 / 1240 1155 / 1240 1155 / 1240Rotary Wheel Heat exchanger version

Thermal efficiency at 10% / 50% fresh air (%) 85% / 71% 84% / 68% 83% / 64%Air pressure drop at 10% / 50% fresh air (Pa) 13Pa / 91Pa 16Pa / 114Pa 20Pa / 143PaExhaust fan kW at 10% / 50% fresh air (kW) 0.5kW / 0.8kW 0.5kW / 1kW 0.5kW / 1.4kWLength (Downflow / Horizontal flow) (mm) 2745 / 2745 2745 / 2745 2745 / 2745Width (Downflow / Horizontal flow) (mm) 2295 / 2295 2295 / 2295 2295 / 2295Height (Downflow / Horizontal flow) (mm) 2335 / 2265 2335 / 2265 2335 / 2265Weight (Downflow / Horizontal flow) (kg) 1288 / 1363 1288 / 1363 1288 / 1363Power Exhaust Fan (Option)

Type Axial Axial AxialDiameter (mm) 660 660 660Drive type Direct Direct DirectNumber / Voltage # / V 2 / 400V 2 / 400V 2 / 400VMotor HP (kW) 0.75 0.75 0.75Motor Rated Amps (2) (A) 2.9 2.9 2.9Filters

Type Furnished 2" Throwaway 2" Throwaway 2" Throwaway(No.) Size Recommended 17x(395x495x45) 17x(395x495x45) 17x(395x495x45)Operating limits

Minimum operating outdoor air temp. (Cooling) °C -18 -18 -18Minimum operating outdoor air temp. (Heating) °C -15 -15 -15Maximum operating outdoor air temp. (Cooling) °C 52 52 52Maximum operating outdoor air temp. (Heating) °C 18 18 18Minimum intake air temp. on the indoor coil (Cooling) °C 16 16 16Minimum intake air temp. on the indoor coil (Heating) °C 10 10 10Dimensions (3)

Length WKD / WKH (mm) 5200 5200 5200DKD / DKH (mm) 5900 5900 5900Width (mm) 2302 2302 2302Height (mm) 2268 2268 2268Operating Weight WKD / WKH (kg) 2081 2282 2297

DKD / DKH (Low heat ) (kg) 2195 2395 2550DKD / DKH (High heat) (kg) 2251 2452 2607

Shipping Weight WKD / WKH (kg) 2221 2422 2437DKD / DKH (Low heat ) (kg) 2335 2535 2690DKD / DKH (High heat) (kg) 2391 2592 2747

Unit construction

Sheet metal / Thickness Type / mm GalvaSteel / 1.2 GalvaSteel / 1.2 GalvaSteel / 1.2Paint Type / RAL Polyester / 9002 Polyester / 9002 Polyester / 9002 Insulation / Thickness Type / mm M0 / 25 M0 / 25 M0 / 25System Data

Refrigerant circuit # 2 2 2Capacity steps (Cooling) % 0 / 50 / 100 0 / 50 / 100 0 / 50 / 100Capacity steps (Heating) % 0 / 50 / 100 0 / 50 / 100 0 / 50 / 100Refrigerant Charge (3)

Circuit A (WKD / WKH) (kg) 15.0 19.0 19.0Circuit B (WKD / WKH) (kg) 15.0 19.0 19.0

(1) At Eurovent rating conditions : Indoor return Air (27° C DB / 19° C WB) - Ambiant 35° C(2) per motor(3) Max load amp for standard unit. with exhaust fan options. without electric heat(4) At the nominal airflow with oversized drive(5) Performance of Energy recovery module given for Indoor 19° C/50% / Outdoor Ambient -5° C(6) At 10m from the unit in a free fieldElectrical & refrigerant charge Data are subject to change without notice. Please refer to unit nameplate data.

20 RT-PRC022-E4

Page 21: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Performance Data

Gas Burner Performance

Table 3 - Gas burner performance

G250 G350 G400 PCH150

YK* 275-300-350 Low Heat 1YK* 275-300-350 High Heat 1 1DK-YK* 400-500-600 Low Heat 1DK-YK* 400-500-600 High Heat 2YK* 275-300-350 Modulating 1YK* 400-500-600 Modulating 1

Burner G250 G350 G400 PCH150

Natural Gas G20 (20 mbar) 34.02 MJ/m3 (15°C-1013)

Gas Flow (15 C-1013 mbar) (m3/h)Nominal rate 5.6 8.1 9 16.4

Reduced rate 5.08 8.13 8.47 4.66

Heating Capacity (kW)Nominal rate 48.2 69.3 77.4 145

Reduced rate 43.7 69.1 72.8 46.3

Heating Rate (kW)Nominal rate 53 77 85 155

Reduced rate 48 76.8 80 44

Efficiency %Nominal rate 90.9 90.0 91.1 93.5

Reduced rate 91 90 91 105.2

CO % < 0.001% < 0.001% < 0.001% < 0.001%

Smoke analysis G20 - 20mbar NOx ppm 19 ppm 9 ppm 46 ppm 34 ppm

@ 400V-3-50Hz Nox mg/kWh 33 16 81 60

CO2 % 8.5% 9.7% 9.6% 8.7%

Burner G250 G350 G400 PCH150

Natural Gas G25 (20 ou 25 mbar) 29.30 MJ/m3 (15°C-1013)

Gas Flow (15 C-1013 mbar) (m3/h)Nominal rate 5.3 8.2 8.8 19.07

Reduced rate 5.15 8.02 8.21 5.41

Heating Capacity (kW)Nominal rate 38.3 60.3 62.9 145

Reduced rate 37.5 58.5 59.5 46.3

Heating Rate (kW)Nominal rate 43 67 71.5 155

Reduced rate 41.9 65.3 66.8 44

Efficiency %Nominal rate 89 90 88 93.5

Reduced rate 89 90 89 105.2

CO % < 0.050% < 0.001% < 0.001% < 0.001%

Smoke analysis G25 - 25mbar NOx ppm - - - 34 ppm

@ 400V-3-50Hz Nox mg/kWh - - - 61

CO2 % 7.1% 7.0% 7.4% 8.7%

Burner G250 G350 G400 PCH150

Natural Gas G31 (30, 37 ou 50 mbar) 88.00 MJ/m3 (15°C-1013)

Gas Flow (15 C-1013 mbar) (m3/h)Nominal rate 2.2 2.7 3.5 6.32

Reduced rate 2.17 2.56 3.19 1.79

Gas Flow (15 C-1013 mbar) (kg/h)Nominal rate 4.2 5.1 6.6 9.83

Reduced rate 7.1 4.9 6.1 2.79

Heating Capacity (kW)Nominal rate 48.6 57.5 78.2 145

Reduced rate 47.7 55.3 71.8 46.3

Heating Rate (kW)Nominal rate 54 65.3 85 155

Reduced rate 53 62.6 78 44

Efficiency %Nominal rate 90 88 92 93.5

Reduced rate 90 88.3 92 105.2

Combustion Air Flow (Avec E=25%) (m3/h)Nominal rate 72 98 113 206

Reduced rate 71 93 103 59

CO % < 0.001% < 0.001% 0.002% < 0.001%

Smoke analysis G20 - 20mbar NOx ppm - - - 34 ppm

@ 400V-3-50Hz Nox mg/kWh - - - 59

CO2 % 9.3% 8.9% 12.0% 9.4%

RT-PRC022-E4 21

Page 22: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

Performance Data

Supply fan performances

Table 4 - Supply fan drive selections

5.5 kW 7.5 kW 11 kW 15 kW

drive type RPM drive type RPM drive type RPM drive type RPM

A = 460C = 520D = 580

E = 650G = 725

A = 460C = 520D = 580

E = 650G = 725 G = 725

H = 415K = 465L = 515

M = 610N = 685

H = 415K = 465L = 515

M = 610N = 685 N = 685

K = 465L = 515

M = 610 M= 610N = 685 N = 685

P = 737

275-300

350

400

500

600

22 RT-PRC022-E4

Page 23: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

23RT-PRC022-E4

Performance Data

Sound levelsData given at 300Pa and 35° C ambientSound Power Reference = 10E--12 Watt

Table 5 - Overall Outdoor Sound Power Level (Env.)

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz GlobalTKD/H - YKD/H 275 74.9 dBA 74.1 dBA 78.7 dBA 82.4 dBA 83.3 dBA 79.5 dBA 72.1 dBA 56.9 dBA 88 dBATKD/H - YKD/H 300 74.9 dBA 74.1 dBA 78.7 dBA 83.0 dBA 83.6 dBA 80.5 dBA 73.7 dBA 56.9 dBA 88 dBATKD/H - YKD/H 350 74.9 dBA 74.1 dBA 78.8 dBA 83.5 dBA 83.8 dBA 81.3 dBA 74.9 dBA 56.9 dBA 89 dBATKD/H - YKD/H 400 76.0 dBA 75.3 dBA 80.0 dBA 84.8 dBA 85.1 dBA 82.4 dBA 75.7 dBA 57.9 dBA 90 dBATKD/H - YKD/H 500 75.9 dBA 75.3 dBA 80.0 dBA 84.5 dBA 85.1 dBA 81.5 dBA 74.4 dBA 57.9 dBA 90 dBATKD/H - YKD/H 600 76.0 dBA 75.3 dBA 80.0 dBA 85.6 dBA 86.1 dBA 82.6 dBA 75.5 dBA 57.9 dBA 91 dBAWKD/H - DKD/H 400 76.0 dBA 75.3 dBA 80.0 dBA 83.9 dBA 84.5 dBA 83.4 dBA 75.8 dBA 57.9 dBA 90 dBAWKD/H - DKD/H 500 76.0 dBA 75.3 dBA 80.0 dBA 85.1 dBA 85.4 dBA 82.8 dBA 75.8 dBA 57.9 dBA 90 dBAWKD/H - DKD/H 600 75.9 dBA 75.3 dBA 80.0 dBA 86.0 dBA 86.8 dBA 82.4 dBA 75.2 dBA 57.9 dBA 91 dBA

Table 6 - Supply Indoor Sound Power Level (In duct)

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz GlobalTKD/H - YKD/H 275 56.5 dBA 63.9 dBA 67.9 dBA 78.6 dBA 71.9 dBA 70.1 dBA 65.9 dBA 59.8 dBA 80 dBATKD/H - YKD/H 300 57.0 dBA 64.4 dBA 68.4 dBA 79.1 dBA 72.4 dBA 70.6 dBA 66.4 dBA 60.3 dBA 81 dBATKD/H - YKD/H 350 58.0 dBA 65.4 dBA 69.4 dBA 80.1 dBA 73.4 dBA 71.6 dBA 67.4 dBA 61.3 dBA 82 dBATKD/H - YKD/H 400 58.9 dBA 68.3 dBA 72.4 dBA 82.1 dBA 75.4 dBA 73.6 dBA 67.4 dBA 60.2 dBA 84 dBATKD/H - YKD/H 500 58.5 dBA 68.9 dBA 72.9 dBA 81.6 dBA 75.9 dBA 74.1 dBA 69.9 dBA 62.8 dBA 84 dBATKD/H - YKD/H 600 58.1 dBA 69.5 dBA 73.4 dBA 81.1 dBA 76.4 dBA 74.6 dBA 72.4 dBA 65.4 dBA 84 dBAWKD/H - DKD/H 400 58.9 dBA 68.3 dBA 72.4 dBA 82.1 dBA 75.4 dBA 73.6 dBA 67.4 dBA 60.2 dBA 84 dBAWKD/H - DKD/H 500 58.5 dBA 68.9 dBA 72.9 dBA 81.6 dBA 75.9 dBA 74.1 dBA 69.9 dBA 62.8 dBA 84 dBAWKD/H - DKD/H 600 58.1 dBA 69.5 dBA 73.4 dBA 81.1 dBA 76.4 dBA 74.6 dBA 72.4 dBA 65.4 dBA 84 dBA

Table 7 - Return Indoor Sound Power Level (In duct)

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz GlobalTKD/H - YKD/H 275 56.5 dBA 63.9 dBA 67.9 dBA 78.6 dBA 71.9 dBA 70.1 dBA 65.9 dBA 59.8 dBA 80 dBATKD/H - YKD/H 300 57.0 dBA 64.4 dBA 68.4 dBA 79.1 dBA 72.4 dBA 70.6 dBA 66.4 dBA 60.3 dBA 81 dBATKD/H - YKD/H 350 58.0 dBA 65.4 dBA 69.4 dBA 80.1 dBA 73.4 dBA 71.6 dBA 67.4 dBA 61.3 dBA 82 dBATKD/H - YKD/H 400 58.9 dBA 68.3 dBA 72.4 dBA 82.1 dBA 75.4 dBA 73.6 dBA 67.4 dBA 60.2 dBA 84 dBATKD/H - YKD/H 500 58.5 dBA 68.9 dBA 72.9 dBA 81.6 dBA 75.9 dBA 74.1 dBA 69.9 dBA 62.8 dBA 84 dBATKD/H - YKD/H 600 58.1 dBA 69.5 dBA 73.4 dBA 81.1 dBA 76.4 dBA 74.6 dBA 72.4 dBA 65.4 dBA 84 dBAWKD/H - DKD/H 400 58.9 dBA 68.3 dBA 72.4 dBA 82.1 dBA 75.4 dBA 73.6 dBA 67.4 dBA 60.2 dBA 84 dBAWKD/H - DKD/H 500 58.5 dBA 68.9 dBA 72.9 dBA 81.6 dBA 75.9 dBA 74.1 dBA 69.9 dBA 62.8 dBA 84 dBAWKD/H - DKD/H 600 58.1 dBA 69.5 dBA 73.4 dBA 81.1 dBA 76.4 dBA 74.6 dBA 72.4 dBA 65.4 dBA 84 dBA

Table 8 - Indoor Sound Level Correction with Airflow

TKD/H - YKD/H 275 10880 m3/h - 3 dB 13600 m3/h 0 dB 16320 m3/h + 3 dBTKD/H - YKD/H 300 12240 m3/h - 3 dB 15300 m3/h 0 dB 18360 m3/h + 3 dBTKD/H - YKD/H 350 13600 m3/h - 3 dB 17000 m3/h 0 dB 20400 m3/h + 3 dBTKD/H - YKD/H - WKD/H - DKD/H 400 16320 m3/h - 3 dB 20400 m3/h 0 dB 24480 m3/h + 3 dBTKD/H - YKD/H - WKD/H - DKD/H 500 19680 m3/h - 3 dB 24600 m3/h 0 dB 29520 m3/h + 3 dBTKD/H - YKD/H - WKD/H - DKD/H 600 23600 m3/h - 3 dB 29500 m3/h 0 dB 35400 m3/h + 3 dB

Page 24: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

RT-PRC022-E424

Table 9 - Maximum length

Zone sensor wire size

Wiresize

(mm²)

Maximumwire lengh

(m)

0.33 450.5 76

0.75 115

1.3 185

2 300

0.33 100.5 15

0.75 23

1.3 37

2 60

WireSize

(mm²)

Maximumwire lengh

(m)

0.25 500.5 100

1 200

THS/THP 03

Conventional thermostat

CO2 sensor wire size

Electrical data

Page 25: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

25RT-PRC022-E4

Dimensions and weights

Dimensions, Weights and Clearances

Overall unit dimensions, shipping weights and operating weights are given inthe General Data tables.

Table 10 - Dimensions, Weights and Clearances

Unit size

Dimensions (mm)Shipping

weight

(kg)

Operating

weight (kg)

Minimum clearances (mm) Point loading weight

X Y Z A B C D E

A B C D E F

(kg) (kg) (kg) (kg) (kg) (kg)

YKD/YKH 275 L 4580 2302 2093 1768 1668 1900 2440 1220 1220 1830 384 384 217 234 217 232

YKD/YKH 300 L 4580 2302 2093 1784 1684 1900 2440 1220 1220 1830 387 387 219 236 219 236

YKD/YKH 350 L 4580 2302 2093 1915 1715 1900 2440 1220 1220 1830 394 394 223 240 223 241

YKD/YKH 400 L 5900 2302 2268 2309 2169 1900 2440 1220 1220 1830 499 499 282 304 282 303

YKD/YKH 500 L 5900 2302 2268 2367 2227 1900 2440 1220 1220 1830 512 512 290 312 290 311

YKD/YKH 600 L 5900 2302 2268 2634 2494 1900 2440 1220 1220 1830 574 574 324 349 324 349

YKD/YKH 275 H 5285 2302 2093 1981 1861 1900 2440 1220 1220 1830 428 428 242 261 242 260

YKD/YKH 300 H 5285 2302 2093 1991 1871 1900 2440 1220 1220 1830 430 430 243 262 243 263

YKD/YKH 350 H 5285 2302 2093 2021 1901 1900 2440 1220 1220 1830 437 437 247 266 247 267

YKD/YKH 400 H 5900 2302 2268 2365 2225 1900 2440 1220 1220 1830 512 512 289 312 289 311

YKD/YKH 500 H 5900 2302 2268 2424 2284 1900 2440 1220 1220 1830 525 525 297 320 297 320

YKD/YKH 600 H 5900 2302 2268 2691 2551 1900 2440 1220 1220 1830 587 587 332 357 332 356

TKD/TKH 275 4580 2302 2093 1725 1625 1900 2440 1220 1220 1830 374 374 211 228 211 227

TKD/TKH 300 4580 2302 2093 1729 1629 1900 2440 1220 1220 1830 375 375 212 228 212 227

TKD/TKH 350 4580 2302 2093 1756 1656 1900 2440 1220 1220 1830 381 381 215 232 215 231.5

TKD/TKH 400 5200 2302 2268 2195 2055 1900 2440 1220 1220 1830 473 473 267 288 267 287

TKD/TKH 500 5200 2302 2268 2254 2114 1900 2440 1220 1220 1830 486 486 275 296 275 296

TKD/TKH 600 5200 2302 2268 2381 2241 1900 2440 1220 1220 1830 515 515 291 314 291 315

WKD/WKH 400 5200 2302 2268 2221 2081 1900 2440 1220 1220 1830 479 354 250 229 333 436

WKD/WKH 500 5200 2302 2268 2422 2282 1900 2440 1220 1220 1830 525 388 274 251 365 479

WKD/WKH 600 5200 2302 2268 2437 2297 1900 2440 1220 1220 1830 528 390 276 253 368 482

DKD/DKH 400 L 5900 2302 2268 2335 2195 1900 2440 1220 1220 1830 505 373 263 241 351 462

DKD/DKH 500 L 5900 2302 2268 2535 2395 1900 2440 1220 1220 1830 551 407 287 263 383 504

DKD/DKH 600 L 5900 2302 2268 2690 2550 1900 2440 1220 1220 1830 587 434 306 281 408 534

DKD/DKH 400 H 5900 2302 2268 2391 2251 1900 2440 1220 1220 1830 518 383 270 248 360 472

DKD/DKH 500 H 5900 2302 2268 2592 2452 1900 2440 1220 1220 1830 564 417 294 270 392 515

DKD/DKH 600 H 5900 2302 2268 2747 2607 1900 2440 1220 1220 1830 600 443 313 287 417 547

Page 26: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

RT-PRC022-E426

Dimensions and weights

Weights of factory-installed accessories

Net weights should be added to unit weight when ordering factory-installedaccessories. To estimate shipping weight, add 2.3 kg to net weight.

Table 11 - Factory -installed accessories net weights (kg)

Notes : Net weight should be added to unit weight when ordering factory installed accessories.

Table 12 - Filter arrangement

UNIT SizeStandardRoofcurb

PitchedRoofcurb

BarometricRelief

PowerExhaust

OversizedSupply

FanMotor

0-25%Man

DamperEconomizer

Elec.Heat

HotWaterCoil

Direct

driven fan

(standard

motor)

TKD/TKH 275 225 315 50/65 78/94 54 23 117/128 100 89 43

TKD/TKH 300 225 315 50/65 78/94 54 23 117/128 100 89 43

TKD/TKH 350 225 315 50/65 78/94 54 23 117/128 100 89 43

TKD/TKH/WKD/WKH 400 260 360 50/65 78/94 56 23 131/135 140 100 55

TKD/TKH/WKD/WKH 500 260 360 50/65 78/94 56 23 131/135 140 100 55

TKD/TKH/WKD/WKH 600 260 360 50/65 78/94 56 23 131/135 140 100 55

YKD/YKH 275L 225 315 50/65 78/94 54 23 117/128 - - 43

YKD/YKH 275H 250 345 50/66 78/94 54 23 117/128 - - 43

YKD/YKH 300L 225 315 50/65 78/94 54 23 117/128 - - 43

YKD/YKH 300H 250 345 50/66 78/94 54 23 117/128 - - 43

YKD/YKH 350L 225 315 50/65 78/94 54 23 117/128 - - 43

YKD/YKH 350H 250 345 50/66 78/94 54 23 117/128 - - 43

YKD/YKH/DKD/DKH 400 270 380 50/65 78/94 56 23 131/135 - - 55

YKD/YKH/DKD/DKH 500 270 380 50/65 78/94 56 23 131/135 - - 55

YKD/YKH/DKD/DKH 600 270 380 50/65 78/94 56 23 131/135 - - 55

Standard 2" EU4 - AR500 4" EU4 - AR500

UNIT Quantity Size Quantity Size Quantity Size

275 16 (395x497x45) 16 (395x495x45) 16 (395x495x90)

300 16 (395x497x45) 16 (395x495x45) 16 (395x495x90)

350 16 (395x497x45) 16 (395x495x45) 16 (395x495x90)

400 17 (395x497x45) 17 (395x495x45) 17 (395x495x90)

500 17 (395x497x45) 17 (395x495x45) 17 (395x495x90)

600 17 (395x497x45) 17 (395x495x45) 17 (395x495x90)

Page 27: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

27RT-PRC022-E4

Equipment

protection/operation

Timings and Features

Increased reliability

Fewer components (movingelectromechanical parts); lesslikelihood of equipment down time orfailure. Standard

Proportional Integral (PI) Control

Proportional - sets corrective actionproportional to deviation fromsetpoint. Integral - fine-tunes the rateof corrective action proportional tothe error (results in superiortemperature control). Standard

Built In "TEST" Mode

Aids in quick verification of systemand control operation; exercises bothhardware and software (no specialtools required). Standard

On Board Diagnostics

Assists with equipmenttroubleshooting if a problem shouldoccur. Standard

Low Ambient Start Timer (LAST)

Function

Bypasses low pressure control when acompressor starts, eliminatingnuisance compressor lockouts.Standard

Anti Short Cycle Timer (ASCT)

Function

Provides a three minute minimum"ON" time and a three minuteminimum "OFF" time for compressors;enhances compressor reliability byensuring proper oil return. Standard

Time Delay Relay (TDR) Function

Provides an incremental stagingdelay between compressors;minimizes equipment current inrushand consumption by keepingcompressors from startingsimultaneously. Standard

Built In Fan Delay Relay (FDR)

Function

Provides custom indoor fan timingsequences for the different types ofequipment, enhancing efficiency andreliability. Standard

Built in Evaporator Defrost Control

Function

Provides low ambient cooling downto -18° C. Standard

Intelligent Fallback

Built-in Default Control providesadaptive operation, which allows theequipment to continue to operate,and provide comfort in the event ofcertain input failures. Also, allowstemporary operation without athermostat. Standard

Emergency Stop Terminals on Low

Voltage Terminal Board

Provides a convenient point todisable the equipment completelyand immediately. Standard

Lower Installation Cost

When using a Trane THS03 or THP03,control voltage wiring may be run upto five times further than anyelectromechanical system with noincrease in wire section. Example:Electromechanical System - 22 musing 0.5 mm2 wire. MicrocontrolSystem (THS/P 03) 110 m 0.5 mm2

wire. Standard

Alternating Lead/Lag

During periods of part load operation,each compressor cycles alternately ascircuit number one, equalizingcompressor wear and run time.Enable by cutting the wire at RTRMjunction number J3-8.

Demand defrost - Heat pump

Defrost only if needed; not based ontime like most other systems. Adaptsto changing weather conditions andlowers operating costs. Standard

Controls

Page 28: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

RT-PRC022-E428

Controls

Heat pump Soft Start

Provides a smooth transition intoheating after defrost, minimizingnoise and compressor stressassociated with switch over. Standard

Heat pump Smart Recovery and

Smart Staging

Inhibits auxiliary heat operation if thespace is recovering adequately(0.1° C/minute) with the heat pumpalone, providing considerable savingsin operating costs. Standard

Economizer Preferred Cooling

Provides fully integrated operation.Will not turn on a compressor withthe economizer, if the space isrecovering adequately with theeconomizer alone (0.1° C./minute).Allows the equipment to be utilizedin more varied applications. Standardwith economizer

Features lost when using a

conventional thermostat

• When a Conventional Thermostatis applied, equipment operationdiffers significantly. The basicequipment protection featuresremain intact, and the followingfeatures end benefits are lost :

• Proportional Integral (PI) control islost, equipment is controlled by athermostat or generic buildingautomation system device.

• Intelligent Fall Back is lost, if afailure occures in the devicecontrolling the equipment,operation will cease.

• Heat Pump Smart Recovery andSmart Staging is not available.Heat Pump operation becomesmore costly unless the genericcontrol applied can accomplishthis.

Three-Phase Monitoring Relay

This device monitors three-phasepower supply in order to protect unitmotors.

This option is recommended whenthere are risks of power supplyimbalance, phase reversal or whenpower factor correction capacitors areused.

The relay disables the unit controlwhen one of the following failuresoccurs on power supply: phasereversal, phase loss, phase imbalance(adjustable setting). Therecommended setting is as follows:5% imbalance on 3-phase voltage.Duration of imbalance should be setat 5 seconds.

Field-installed Control

Options

Zone sensors

Zone sensors are the buildingoccupants' comfort control devices.They replace the conventionalelectromechanical thermostats. Zonessensors are to be used with theVoyager™ II units with the Microcontrol. These sensors are available inthe following options:• THP03: Sensor, programmable

setpoint and operation modeaccording to a schedule

• TZS01: Sensor only, used whenconnected with CCP2 or Tracker™

• TZS02: Sensor and setpointadjustable thumbwheel

• THS03: Sensor, setpoint andoperation mode, unit Ledindication (mode and alarms)

From left to right TZS01, TZS02, THS03THP03

Page 29: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

29RT-PRC022-E4

Room thermostats

Trane Communication Interface (TCI)

This microprocessor interface allowsthe unit to communicate to Trane'sIntegrated Comfort™ system(CCP2, Tracker™).

THS03 room thermostat

Controls

THP03 room thermostat

Conv. Thermostat THS03 THP03

Programmable • - •Control type design • - •Electronic Electro-mechanical Reliatel

For cooling-only units (TS*/TK*) • • •For heat pump units (WS*/WK*) • • •For gas-fired units (YS*/YK*) • • •Number of cooling stages 2 3 3

Auxiliary heating stages (electric heater,hot water coil) 2 2 / 1 Modulating

Liquid crystal display • - •

Table 13 - Characteristics of programmable and conventional thermostats

LonMark®Communication

Interface LCI-R

This microprocessor interface allowsthe unit to communicate to Trane'sIntegrated Comfort™ system (TracerSC, Tracker™) or other open buildingautomation systems

Tracker™ multi rooftops centralized

control

• Intuitive, menu-driven user interface• 2 wires cable communication with

units (LonMark®)• 365-day scheduling and

10 schedules• Capability of including all equipment

and devices in one schedule

• Temporary schedule override• Easy-to-administer security system

with two levels of access• Automatic daylight savings time

changeover• Error and alarm messaging• Setpoint viewing and editing• Trend data collection• Report generation• Optimal start

Features exclusive to the PC software(optional)

- RJ45 - Ethernet connection- Backup and restore capability- Standard graphics and HTML

graphical interface

- Binary output programmingcapability

- Operator-defined custom alarmscapability

- Printer support

Connection to controllers over sharedEthernet/IP connection• E-mail forwarding of alarms and

messages• Standard timed override

(after hours) usage report• Standard daily, monthly,

and yearly energy reports

Note: The Tracker PC software is notneeded to set up and operatea typical building.

Page 30: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

RT-PRC022-E430

Mechanical Specifications

Casing

Unit casing shall be constructed ofzinc coated, heavy-gauge, galvanizedsteel. All exterior components shall bemounted in a weather resistant steelcabinet and painted with a polyesterwhite RAL 9002 powder paint. Wheretop cover seams exist, they shall bedouble hemmed and gasket sealed toprevent water leakage. Cabinetconstruction shall allow access for allmaintenance on two sides of the unit.Service panels shall have handles andshall be removable while providing awater and air tight seal.. The indoorair section shall be completelyinsulated with fire resistant,permanent, odorless glass fibermaterial, aluminum foil faced. Thebase of the unit shall have provisionsfor crane lifting.

Hinged Service Access + ¼ locks:

Standard

Filter access panel and supply fanaccess panel shall be hinged for easeof unit service + ¼ turn locks shall bestandard.

Electrical Control box upper accessdoor shall deliver a protection againstrain or snow during commissioningand maintenance operations.

Filters

Unit shall be provided on standardwith 50 mm, throwaway EU3 filters.50 mm EU4, 100 mm EU4 filters shallbe optional.

Compressors

All units shall have Trane CSHD/CSHNscroll type compressors. Compressorshall be direct-drive, hermetic withself-lubrication. Motor shall besuction gas-cooled and shall have avoltage utilization range of plus orminus 10 percent of unit nameplatevoltage. Internal temperature andcurrent sensitive motor overloadsshall be included for maximumprotection. Each compressor shall beprotected by external dischargetemperature thermostat, windingtemperature thermostat and reverserotation/phase loss protection. Eachcompressor shall have crankcaseheaters installed, properly sized tominimize the amount of liquidrefrigerant present in the oil sumpduring off cycles. All scrollcompressors shall be provided withphase monitoring protection.

Refrigerant Circuits

The unit shall be operating withR410A HFC-based refrigerant.Each refrigerant circuit shall haveindependent thermostatic expansiondevices, service pressure ports andrefrigerant line filter driers factory-installed as standard. An area shall beprovided for replacement suction linedriers. Refrigeration circuit shall beprotected against refrigerant leak bya low pressure switch. Service valvesshall be provided as standard andlocated on low pressure and highpressure side of the refrigerationpiping.

General

Units shall be dedicated downflow orhorizontal airflow. Operating rangeshall be between 50° C and -18° Ccooling as standard for all units. Allunits shall be factory assembled,internally wired, fully charged withrefrigerant, and 100 percent run-tested before leaving the factory.Wiring internal to the unit shall becolored and numbered for simplifiedidentification.

Unit shall be available with a mainrefrigeration circuit in cooling onlyand reversible version. Auxiliary heattype shall be selectable: Hot waterheat, Gas heater and electrical heaterin both refrigeration circuit versions.

Performance

The unit with a capacity above 100kWshall be certified and registered onthe Eurovent certification under RTprogram (http:/ /www.eurovent-certification.com).

Page 31: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

31RT-PRC022-E4

Evaporator and Condenser Coils

Condenser coils shall have 3/8"(10 mm) copper tubes mechanicallybonded to lanced aluminum platefins. Evaporator coils shall be 3/8" (13mm) internally finned copper tubesmechanically bonded to highperformance aluminum plate fins. Allcoils shall be leak tested at the factoryto ensure pressure integrity. All coilsshall be leak tested to 2.1 MPa andpressure tested to 4.5 MPa. Allevaporator coils shall be ofintermingled configuration. Slopedcondensate drain pans are standard.Indoor coil shall be protected asstandard on all units by an ant frostthermostat.

Outdoor Fans

The outdoor fans shall be direct drive,statically and dynamically balanced,draw-through in the verticaldischarge position. The fan motorsshall be permanently lubricated andshall have built-in thermal overloadprotection.

Indoor Fan

Units shall have belt driven, forwardcurved centrifugal fans with fixedmotor sheaves. All motors shall becircuit breaker protected.

Controls

Unit shall be completely factory wiredwith necessary controls and terminalblock for power wiring. Units shallprovide an external location formounting fused disconnect device.Unit controller shall be provided forall 24 volt control functions. Theresident control algorithms shallmake all heating, cooling and/orventilating decisions in response toelectronic signals from sensorsmeasuring indoor and outdoortemperature. The control algorithmmaintains accurate temperaturecontrol, minimizes drift from set pointand provides better building comfort.Unit controller shall provide anti-short cycle timing and time delaybetween compressors to provide ahigher level of machine protection.Heat pump unit shall manage defrostcycles based on demand defrost logicon the 2 independent circuits.

Electrical components and wiringshall be compliant with EN 60204-1electrical directive. Unit shall bepowered by 400V/3/50Hz supply(without neutral) on a single point ofpower connection.

Ventilation Override shall allow abinary input from the fire/life safetypanel to cause the unit to overridestandard operation and assume oneof two factory preset ventilationsequences, exhaust or pressurization.The two sequences shall be selectablebased open a binary select input.

Phase monitoring relay: Standard

Unit shall detect phase loss, phasereversal from main power supply.In case of fault, the unit shall stop.

Through-The-Base Electrical

Provision: Standard

An electrical service entrance shall bestandard which allows access to routeall high and low voltage electricalwiring inside the curb, through thebottom (vertically) and through theside (Horizontally) of the outdoorsection of the unit and into thecontrol box area.

Disconnect Switch: Standard

A factory installed disconnect switchwith external handle shall bestandard. The disconnect switch shallbe mounted inside the unit controlbox. It should avoid power side accesswhen switch is set in ON position

Mechanical Specifications

Page 32: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

RT-PRC022-E432

Variable Frequency Drives (VFDs)

VFDs shall be factory installed andtested to provide supply fan motorspeed modulation. The VFD shallreceive speed reference from the unitcontroller based upon supply zoneheating/cooling demand and shallcause the drive to accelerate ordecelerate as required to maintainthe zone temperature setpoint. Thefan coupling shall be direct type withthe motor shaft. Units shall have asoft rubber direct coupling betweencentrifugal fans and motor. Motor,fan and VFD shall be individuallyreplaced in case of maintenanceoperation.

Fan Fail Switch

This option allows checks for supplyfan pressure. The fan failure switchwill stop all unit functions and reportService alarm on the zone sensormodule or Building managementsystem.

Clogged Filter Switch

This option allows for individual dirtyfilter indication. The switch will lightthe Service LED on the zone sensorand will allow continued unitoperation.

Smoke Detector

This option shall trip off in case ofpresence of smoke in the supply sideof the unit and shall close the returnair damper, if any, and stop the unit.

Phase monitoring relay

The phase monitoring relay shalldetect phase loss, phase reversal andphase imbalance from main powersupply. In case of fault, the unit muststop.

Black Epoxy Fin Coating

An optional coil corrosion resistantcoating shall protect indoor andoutdoor aluminum fins.

Fire thermostats

Field installed manually resettablehigh temperature thermostats shallprovide input to the unit controls toshut down the system if thetemperature sensed at the return is57° C or at the discharge 115° C.

Roof Curb – Downflow

The roof curb shall be designed tomate with the downflow unit andprovide support and watertightinstallation when installed properly.

The roof curb design shall allow fieldfabricated rectangular supply/returnductwork to be connected directly tothe curb.

Curb shall be shipped knocked downfor field assembly.

Adjustable Roof Curb

This factory assembled accessory isadjustable on site and allowscorrection of the slope of the roof upto 5%.

Hot Water Coil

This option shall be factory mountedand placed in the discharge section. Itshall be shipped with one 3-wayvalve, 0 to 100% modulating built-incontrol and freezestat protection. Ifneeded, on reversible unit, hot watercoil shall be selected as first source ofheat before mechanical heating.

Mechanical Specifications

Options and Accessories

Manual Fresh Air damper

A manually controllable outside airdamper shall be adjustable for up to25 percent outside air. Manualdamper is set at desired position atunit start up.

Economizer

Economizer shall be factory installed.The assembly includes: fullymodulating 0-100 percent motor anddampers, minimum position setting,preset linkage, wiring harness, anddifferential enthalpy control.

Barometric Relief

The barometric relief damper shall beoptional with the economizer. It shallbe available as a factory installedoption on all units. Option shallprovide a pressure operated damperfor the purpose of space pressureequalization and be gravity closing toprohibit entrance of outside airduring the equipment "off" cycle.

Power Exhaust Fan

Power exhaust shall be optional withthe economizer. It shall be availableas a factory installed option on allunits. It shall assist the barometricrelief damper in maintaining buildingpressurization.

Remote Potentiometer

A remote potentiometer shall beavailable to remotely adjust the uniteconomizer minimum position.

CO2 Sensor

This accessory shall be compatiblewith economizer options. It shallmeasure CO2 concentration in orderto increase or decrease the fresh airamount in the building.

Page 33: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

33RT-PRC022-E4

Energy Recovery Module - Plate

heat exchanger version

Energy recovery module should havea total efficiency of 58% or higher at -5° C outdoor, 19° C indoor and 30%fresh air rate Module shall beequipped with freeze monitoringpressure switch that initiate defrostcycle when exchanger in clogged byfrost in winter application

Energy Recovery Module - Heat

wheel version

Energy recovery should have a totalefficiency of 70% or higher at -5° Coutdoor, 19° C indoor and 30% freshair rate. Fresh air and exhaust air flowshall be filtered before entering in theheat exchanger in order to preventexchanger clogging.

Thermostats and Zone Sensors

The thermostats and zone sensorsshall be provided to interface withthe ReliaTel®unit controls and shall beavailable in either manual, automaticprogrammable with night setback,with system malfunction lights orremote sensor options.

Communication Interface (TCI-R)

ReliaTel®Trane CommunicationInterface (TCI) shall be provided tointerface with the Trane IntegratedComfort™ System and shall beavailable as a field or factory-installed. The TCI shall allow controland monitoring of the rooftop unitvia a two wires communication link.The following alarm and diagnosticinformation shall be available:

Electric Heaters

Electric heat shall be available forfactory installation within basic unit.Electric heater elements shall beconstructed of heavy-duty nickelchromium elements we connected for380 and 415 volt. Staging shall beachieved through the unit controller.Each heater package shall haveautomatically reset high limit controloperating through heating elementcontactors. All heaters shall beindividually fused from factory, whererequired.

Staged Gas Heater

The heating section shall have a drumand tube heat exchanger(s) designusing corrosion resistant steelcomponents. A forced combustionblower shall supply premixed fuel toa single burner ignited by a pilotlesshot surface ignition system. In orderto provide reliable operation, anegative pressure gas valve shall beused that requires blower operationto initiate gas flow. On an initial callfor heat, the combustion blower shallpurge the heat exchanger(s)45 seconds before ignition. Afterthree unsuccessful ignition attempts,the entire heating system shall belocked out until manually reset at thethermostat. Units shall be suitable foruse with natural gas or propane (fieldinstalled kit). All units shall have twostage heating.

Burner of 48kW and 70kW shall have ano emissions of CO (< 0.001%) andNOx emission below 30ppm (class 5according to the requirements ofStandard EN483)

Burner of 77kW shall have a noemissions of CO (< 0.001%) and NOxemission below 50ppm (class 4according to the requirements ofStandard EN483)

Modulating Gas heater

The gas burner should be modulatingfrom 30% to 100%. Control of theburner should be delivered accordingto the heating demand and supply airtemperature. Burner should becondensing below 60% heatingoutput. Efficiency of the burnershould be below 94% at full load and105% at reduced load. Gas heatexchanger should be drum and tubetype, build in stainless steel. A forcedcombustion blower shall supplypremixed fuel to a single burnerignited by pilot burner integratedwith spark ignition system. Premixburner shall have a no emissions ofCO (0%) and NOx emission below35ppm (class 5 according to therequirements of Standard EN483)

Energy Recovery Module – General

Heat recovery should include directdriven exhaust fan. Fan speed shouldbe adjusted by a separate frequencydrive according to fresh air flow inorder to maintain buildingpressurization.

Fresh air flow shall be filtered beforeentering in the heat exchanger inorder to prevent clogging on thefresh air side.

When free cooling is needed, energyrecovery should be by-passed toavoid heat exchange on the freshflow entering into the building.

Mechanical Specifications

Page 34: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

RT-PRC022-E434

Trane Modbus Communication

Interface (PIC)

Modbus Communication Interface(PIC) shall be provided to interfacewith the Trane Integrated Comfort™System and shall be available field orfactory-installed. The PIC shall allowcontrol and monitoring of the rooftopunit via a two wire communicationlink and Modbus protocol. Thefollowing alarm and diagnosticinformation shall be available:

LonTalk® Communication Interface

(LCI-R)

The field or factory-installed ReliaTel®

LonTalk Communication Interface(LCI-R) will be provided to interfacewith the Trane Integrated Comfort™System or LonTalk®capable thirdparty building managementnetworks. The LCI-R will allow controland monitoring of the rooftop unitvia a two wires communication link.

Reliatel® Unit controller Originated

Data

• Unit operating mode• Unit failure status

- Cooling failure- Heating failure- Emergency service stop

indication- Supply fan proving- Timed override activation- High temperature thermostat

status• Zone temperature• Supply air temperature• Cooling status (all stages)• Stage activated or not• Stage locked out by Reliatel• HPC status for that stage• Compressor disable inputs• Heating status• Number of stages activated• High temperature limit status• Economizer status• Requested minimum position• Damper position• Dry bulb/enthalpy input status• Outside air temperature• Outside relative humidity• Sensor Failure

- Humidity sensor- Outdoor Air Temperature sensor- Supply Air Temperature sensor- Return Air Temperature sensor- Zone temperature sensor- Mode input- Cooling/heating setpoint from

sensors- Unit mounted potentiometer

• Unit Configuration data- Gas or electric heat- Economizer present

• Local setpoint• Local mode setting• Clogged filter service indicator• CO2 setpoint• CO2 value

Mechanical Specifications

Building Management System

communication Originated Data

• Command operating mode• Host controllable functions:

- Supply fan- Economizer- Cooling stages enabled- Heating stages enabled- Emergency shutdown

• Minimum damper position• Heating setpoint• Cooling setpoint• Supply air tempering

enable/disable• Slave mode (CV only)• Tracer/Local operation• Daytime warm-up enable/disable• Power exhaust setpoint

Page 35: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

35RT-PRC022-E4

Page 36: Voyager™ III Rooftop Units - Trane-Commercial · makes Trane the worldwide leader in air conditioning scroll compressor technology. Figure 2 - One of two matched scroll plates -

© 2013 Trane All rights reservedRT-PRC022-E4_0513Supersedes RT-PRC022-E4_0912

We are committed to using environmentallyconscious print practices that reduce waste.

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader increating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advancedcontrols and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.