144
CONTROL AND MEASUREMENT DEVICES INGEPAC EF- CD User Manual

Ume Ingepac Ef CD Eng

Embed Size (px)

DESCRIPTION

ingeteam0

Citation preview

  • CONTROL AND MEASUREMENT DEVICES

    INGEPAC EF- CD

    User Manual

  • UME_INGEPAC_CD_eng Rev.: E (07/14)

    All rights reserved. No part of

    this publication may be

    reproduced, by whatever means,

    without the prior written

    permission of Ingeteam Power

    Technology.

    Ingeteam Power Technology reserves

    the right to make changes without

    prior notice.

  • INDEX

    Ingeteam Power Technology S.A.

    User Manual III

    1. GENERAL DESCRIPTION .................................................... 6

    1.1 FUNCTIONAL DESCRIPTION ..................................................... 6 1.2 MODEL ENCODING ............................................................. 7 1.3 USER INTERFACE ............................................................. 9 1.4 Parallel Redundancy Protocol (PRP) ......................................... 9 1.5 Link failover redundancY ................................................... 9 1.6 High-availability Seamless Redundancy (HSR) ............................... 10 1.7 INTERCONNECTIONS .......................................................... 11

    1.7.1 CPU ................................................................... 11 1.7.2 Power supply .......................................................... 11 1.7.3 Input/output cards .................................................... 11 1.7.4 Analogue inputs ....................................................... 14

    2. HARDWARE .............................................................. 25

    2.1 CONSTRUCTION FEATURES ..................................................... 25 2.1.1 Half chassis ( 19) .................................................. 25 2.1.2 19 chassis ........................................................... 25

    2.2 REAR TERMINALS ............................................................ 26 2.2.1 Configuration options ................................................. 26 2.2.2 Half chassis ( 19) .................................................. 26 2.2.3 19 chassis ........................................................... 27

    2.3 FRONT INTERFACE ........................................................... 28 2.3.1 Half chassis ( 19) .................................................. 28 2.3.2 19 chassis ........................................................... 29 2.3.1 Closed Terminals ...................................................... 30

    2.4 TECHNICAL CHARACTERISTICS ................................................. 30 2.4.1 Power supply voltage .................................................. 30 2.4.2 Digital outputs ....................................................... 31 2.4.3 Digital inputs ........................................................ 32 2.4.4 IRIG-B input and PPS .................................................. 32 2.4.5 Current and voltage circuits .......................................... 33 2.4.6 Front communication ................................................... 33 2.4.7 Rear communications ................................................... 34

    2.5 ENVIRONMENTAL CONDITIONS .................................................. 35 2.6 TESTS ..................................................................... 35

    2.6.1 Climatic test ......................................................... 35 2.6.2 Insulation and electrical safety tests ................................ 35 2.6.3 Electromagnetic tests ................................................. 36 2.6.4 Mechanical tests ...................................................... 36

    3. MEASUREMENT ........................................................... 37

    3.1 38BMeasurements depending on wiring procedures ............................. 41 3.1.1 Connection Type A ..................................................... 41 3.1.2 Connection Type B ..................................................... 41 3.1.3 Connection Type D ..................................................... 42 3.1.4 Connection Type E ..................................................... 42 3.1.5 Connection Type F ..................................................... 43 3.1.6 Connection Type G ..................................................... 43

    3.2 16BEnergy counterS ......................................................... 44

    4. AUTOMATISMS ........................................................... 45

    4.1 SYNCHRONISM ............................................................... 45 4.1.1 Undervoltage permission ............................................... 45 4.1.2 Synchronism permission ................................................ 46

    5. MONITORING ............................................................ 50

  • INDEX

    Ingeteam Power Technology S.A.

    User Manual IV

    5.1 EXTERNAL POWER SUPPLY MONITORING .......................................... 50 5.2 TEMPERATURE MONITORING .................................................... 51 5.3 DIS BLOCKING BY LACK OF VAUX .............................................. 52 5.4 INTERNAL BATTERY FAILURE MONITORING ....................................... 52 7.5 UNIT CHECKS ............................................................... 53

    6. CONFIGURATION ......................................................... 56

    6.1 CID ....................................................................... 56 6.1.1 Data Storage .......................................................... 56 6.1.2 Updating CID.ParamRev ................................................. 56

    6.2 GENERAL ................................................................... 56 6.3 FRECUENCY, MEASUREMENT AND TRANSFORMERS ................................... 57

    6.3.1 Current ............................................................... 57 6.3.2 Frequency and voltage ................................................. 58 6.3.3 Power and energy ...................................................... 58

    6.4 INPUTS/OUTPUTS ............................................................ 59 6.4.1 Inputs ................................................................ 59 6.4.2 Outputs ............................................................... 60 6.4.3 Treatment of digital input flicker .................................... 61

    6.5 LEDS ...................................................................... 61 6.5.1 Via GEN/IHMI node ..................................................... 61 6.5.2 Via CTRL/IHMI node .................................................... 62

    6.6 CONFIGURATION WITH INREF .................................................. 62 6.7 NAMES ..................................................................... 63 6.8 CONFIGURATION WITH INREF .................................................. 63

    7. SYNCHRONIZATION ....................................................... 64

    7.1 DATE AND TIME ............................................................. 64 7.2 SETTINGS .................................................................. 64

    8. DATA ACQUISITION FUNCTIONS ............................................ 66

    8.1 STATUS REPORT ............................................................. 66 8.2 PRIMARY MEASUREMENTS REPORT ............................................... 68 8.3 INCIDENT REPORT ........................................................... 69 8.4 HISTORICAL MEASUREMENT REPORT ............................................. 70 8.5 MAXIMETER/MINIMETER REPORT ................................................ 72 8.6 OSCILLOGRAPHY ............................................................. 72 8.7 DISPLAY ................................................................... 75

    9. USB ACCESS ............................................................ 79

    9.1 DOWNLOADING REPORTS ....................................................... 79 9.2 LOADING CID ............................................................... 80

    10. FTP ACCESS ........................................................... 81

    11. MAPPING THE UNITS SIGNALS, MEASUREMENTS AND METERS .................. 82

    11.1 SIGNALS .................................................................. 82 11.1.1 Type A signals ....................................................... 82 11.1.2 Type B signals ....................................................... 83 11.1.3 Type C signals ....................................................... 84 11.1.4 Type D signals ....................................................... 85

    11.2 MEASUREMENTS ............................................................. 86 11.3 COUNTERS ................................................................. 87

    12. LOGICS ............................................................... 89

    12.1 Control logicS ........................................................... 89 12.2 PROTECTION logicS ........................................................ 89 12.3 database sIGNALS ......................................................... 91

    13. IEC 61850 COMMANDS ................................................... 92

  • INDEX

    Ingeteam Power Technology S.A.

    User Manual V

    13.1 RUNNING IEC 61850 COMMANDS ............................................... 92 13.2 COMMAND BLOCKS ........................................................... 95

    13.2.1 Command blocks by command hierarchies ................................ 96 13.2.2 Blocks due to invalid/unknown/reached bay ............................ 98

    13.3 COMMAND SADDRESS ......................................................... 99

    14. RIO MODULES ......................................................... 101

    14.1 CONFIGURATION ........................................................... 101 14.2 OPERATION ............................................................... 101

    15. CHANGES REQUIRING THE REBOOTING OF THE SERVER ....................... 103

    15.1 MANUAL .................................................................. 103 15.2 AUTOMATIC ............................................................... 103

    16. RECEPTION GOOSES .................................................... 104

    16.1 LGOS MODEL .............................................................. 104 16.1.1 Configuration values ................................................ 104 16.1.2 Supervision values .................................................. 104

    16.2 GOOSERX MODEL ........................................................... 105

    17. TCP/IP NETWORK CONFIGURATION ........................................ 106

    17.1 DESCRIPTION ............................................................. 106 17.2 GENERAL CONSIDERATIONS ABOUT NETWORK CONFIGURATION ...................... 106 17.3 GOOSES .................................................................. 107

    18. KEYBOARD AND GRAPHIC DISPLAY ........................................ 108

    18.1 GENERAL OPERATION ....................................................... 108 18.1.1 Display structure ................................................... 108 18.1.2 Organization of the pages ........................................... 108 18.1.3 Treatment of the functional keys .................................... 109 18.1.4 Graphics pages ...................................................... 109 18.1.5 I/O pages ........................................................... 111 18.1.6 Event pages ......................................................... 113 18.1.7 Alarm pages ......................................................... 114 18.1.8 Device status pages ................................................. 114 18.1.9 Measurement pages ................................................... 116 18.1.10 Menu to other screens page ......................................... 118 18.1.11 Shortcut menu page ................................................. 119

    18.2 MENUS PAGES ............................................................. 120 18.2.1 Operation of the menus .............................................. 120 18.2.2 Password management ................................................. 131

    18.3 OTHER SCREENS ........................................................... 133 18.3.1 Contrast setting .................................................... 133 18.3.2 USB treatment ....................................................... 133

    19. MEASUREMENT LIST .................................................... 135

    APENDICE I PREVENTIVE MAINTENANCE ....................................... 140

    I.1. ERROR DETECTION ......................................................... 141 I.2. Error handling procedure ................................................ 142

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 6

    1. GENERAL DESCRIPTION

    1.1 FUNCTIONAL DESCRIPTION

    Table 1 shows the features and measurements available.

    Table 1 Functions

    Functions and measurements

    Frequency

    Line phase voltages (phase and mean)

    Line to line voltages (combination of phase and

    mean)

    Current sequences

    Harmonic distortion (phase THD and mean THD)

    Neutral line-phase current

    Neutral harmonic distortion

    Active power (signed)

    Reactive power (signed)

    Apparent power

    Active energy counter (positive and negative)

    Active energy counter (positive and negative)

    Power factor (signed)

    Maximum and minimum counters

    Oscillography

    Historical reports

    Phase currents and voltages are measured with 0.2 class precision (by IEC688:1992).

    Reference conditions for this class are:

    V (measured) VN 2%

    F FN 0,1 %

    Waveform Sinusoidal, distortion factor 0,2

    Power factor 1,0.........0,8 inductive o

    capacitive

    Temperature 23C 2C

    V supply 1%

    Influence of environmental conditions:

    Magnitude Tolerance Variation in % referred to the class

    Temperature - 10C/55C 100%

    Frecuency FN 10% 100%

    Voltage VN 20% 50%

    Power factor +0,5...1...+0,5 50%

    Waveform distortion factor 0,2 200%

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 7

    1.2 MODEL ENCODING

    I/O

    1

    CO

    M1

    CO

    M2

    CO

    M3

    CO

    M4

    CO

    M5

    CO

    M6

    ET

    H1

    ET

    H2

    I/O

    2

    I/O

    3

    I/O

    4

    I/O

    5

    I/O

    6

    I/O

    7

    I/O

    8

    C D B

    0

    1

    2

    A

    B

    C

    D

    A

    Single PS 85-300 Vdc+ 6DI 220 Vdc + 4DO B

    Single PS 18-60 Vdc+ 6DI 24 Vdc + 4DO C

    Single PS 18-60 Vdc+ 6DI 48 Vdc + 4DO D

    Redundant PS 48 Vcc / 48Vcc F

    G

    A GFO

    B PFO

    C RS232C

    D RS485

    X No port

    E GFO

    F RJ45

    G GFO (ETH with PRP redundancy) Note 7

    H RJ45 (ETH with PRP redundancy) Note 7

    I GFO (Link failover redundancy) Note 9

    J RJ45 (Link failover redundancy) Note 9

    K LC (Link failover redundancy) Note 9

    L LC

    M GFO (ETH with HSR redundancy) Note 7

    N RJ45 (ETH with HSR redundancy) Note 7

    X No port

    A

    Note 1 B

    C

    A No board

    B 11 DI (24Vdc) + 9 DO

    C 11 DI (48Vdc) +9 DO

    D 11 DI (125 Vdc) + 9 DO

    E 11 DI (220 Vdc) + 9 DO

    F 32 DI (24Vdc)

    G 32 DI (48Vdc)

    H 32 DI (125 Vdc)

    I 32 DI (220 Vdc)

    J 16 DI (24Vdc)-8 independent DO

    K 16 DI (48Vdc)-8 independent DO

    L 16 DI (125 Vdc)-8 independent DO

    M 16 DI (220 Vdc)-8 independent DO

    N 16 DI (24 Vdc)- 16 DO

    O 16 DI (48Vdc)- 16 DO

    P 16 DI (125 Vdc)- 16 DO

    Q 16 DI (220 Vdc)- 16 DO

    R 16 DI (24Vdc)-8 AI Note 8

    S 16 DI (48Vdc)-8 AI Note 8

    T 16 DI (125 Vdc)-8 AI Note 8

    U 16 DI (220 Vdc)-8 AI Note 8

    V 16 DI (24 Vdc)- 8 AI (4 isolated) Note 8

    W 16 DI (48Vdc)- 8 AI (4 isolated) Note 8

    X 16 DI (125 Vdc)- 8 AI (4 isolated) Note 8

    Y 16 DI (220 Vcc)- 8 AI (4 isolated) Nota 8

    0 8DI (24Vcc) + 4DO (h.b.c.o.) + 4DO

    1 8DI (48Vcc) + 4DO (h.b.c.o.) + 4DO

    2 8DI (125Vcc) + 4DO (h.b.c.o.) + 4DO

    3 8DI (220Vcc) + 4DO (h.b.c.o.) + 4DO

    4 8DI (24Vcc) + 8DO

    5 8DI (48Vcc) + 8DO

    6 8DI (125Vcc) + 8DO

    7 8DI (220Vcc) + 8DO

    Note 1: The terminals for the power supply inputs are pyn type standard terminals.

    Note 2: To know the order of the boards in the rack, consult the number of the terminals on the rear views of each chassis.

    Note 3: In the 19" chassis, board 2 only available with pyn type standard terminals.

    Note 4: Available only for 1/2 19" chassis without measurement and 19" chassis.

    Note 5: Available only for 19" chassis.

    Note 6: Available only for 19" chassis without measurement.

    Note 7: PRP/HSR only available for ETH-1. With this option ETH-2 can only be of the same type as the ETH-1 (GFO or RJ45).

    Note 8: Standard analogue inputs configuration: +/-5mA, +/-5mA, +/-2.5mA, +/-2.5mA, +/-2.5mA, +/-2.5mA, +/-20mA, +/-20mA. Consult other configurations.

    Note 9:This option requires selecting both ETH1 as ETH2 and supports any combination of options I , J and K.

    Note 10: Not available for PRP ethernet communication

    ETH-1

    Board 3

    Closed terminals for analog inputs and pin type terminals for the rest

    COM-4 (Note 10)

    ETH-1

    COM-6 (Note 10)

    BOARD SELECTION

    ETH-2

    Board 5 (Note 5)

    Closed terminals

    MODEL

    Control

    1/2 chassis 19" 5U with configurable keyboard

    1/2 chassis 19" 5U with predefined keyboard

    Pin type standard terminals

    Control + Measurement + Synchronism

    INGEPAC EF CD MODEL

    REAR SERIAL COMMUNICATION PORT

    COM-1

    COM-2

    COM-3 (Note 10)

    Chassis 19" 4U with configurable keyboard

    Control + Measurement

    POWER SUPPLY MODULE

    HOUSING

    Chassis 19" 4U with predefined keyboard

    COM-5 (Note 10)

    REAR ETHERNET COMMUNICATION PORT

    Board 6 (Note 5)

    Board 2 (Note 3)

    Board 8 (Note 6)

    Board 7 (Note 5)

    ETH-2

    TERMINALS

    Single PS 85-300 Vdc+ 6DI 125 Vdc + 4DO

    Redundant PS 125 Vcc / 125Vcc

    Board 4 (Note 4)

    (Note 2)

    I/O BOARD CONFIGURATION

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 8

    The following figures show the oard position acording to model encoding. Figure 1 CD1 and CD2: 19 chassis

    Figure 2 CD1 and CD2: 19 chassis

    Figure 3 CD0 19 chassis

    Figure 4 CD0 19 chassis

    Figure 5 Redundant power supply 19

    chassis

    Figure 6 Redundant power supply 19 chassis

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 9

    1.3 USER INTERFACE

    Local. The front board is equipped with:

    10-digit numerical keyboard with decimal point, plus R key

    4 scroll keys: (Up), (Down), (Left), (Right)

    3 general keys (Enter), ESC (Escape), MENU

    Function keys depending on the model:

    5 function keys (I, O, DES, SEL, INF)

    7 function keys (I, O, F1...F5)

    12 function keys (I, O, DES, SEL, INF, F1F7)

    16 function keys (I, O, F1F14)

    19 fully assignable LEDs

    1 unit operation LED

    USB 2.0 front port for downloading reports and loading CID

    Front RJ45 port for communications

    1.4 PARALLEL REDUNDANCY PROTOCOL (PRP)

    The PRP (Parallel Redundancy Protocol) is a redundancy communication protocol defined in

    the IEC 62439-3 standard and it is one of the redundancy mechanism recommended in IEC 61850

    networks.

    In the PRP protocol the device use two redundant ethernet ports and the protocol is based

    on the simultaneous transmission and reception of data via both independent ports.

    In PRP solutions two independent ethernet networks are used. Each device is attached to

    both networks and sends and receives all the frames over both LANs simultaneously, consumes

    the first frame and discards the duplicate. With this mechanism PRP ensures zero-packet

    loss and zero recovery time upon single network failures.

    The two LANs have no connection between them and are assumed to be fail-independent, both

    are identical in protocol at the MAC-LLC level, but they can differ in performance and

    topology.

    With the PRP protocol additional information called RCT (Redundancy Control Trailer) is

    added to the Ethernet frame at the link layer in order to control redundancy. This

    information is transparent for devices that do not use PRP protocol and it is used by PRP

    devices to discard the duplicate frames.

    Devices without PRP can be connected to one of the redundant ethernet networks but in that

    case they only can communicate with the devices connected to the same network. In order to

    enable redundancy in non-PRP devices an external converter called RedBox (Redundancy Box)

    can be used.

    1.5 LINK FAILOVER REDUNDANCY

    With the link failover redundancy the device uses two ethernet ports for a redundant

    communication.

    In this redundancy mode the device communicates by one of the ethernet ports and if there

    is a link failure in that port, switches to the redundant port if the link status of that

    port is active.

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 10

    If the link status of the passive port returns to normal, the communication is maintained

    in the active port and the devices only change the active port in case of link failure.

    In this redundancy, unlike the case of PRP redundancy, it should not be used two

    independent ethernet networks. The two Ethernet ports of the equipment must be connected to

    different network switches, but must belong to the same network, so that the switches

    should be connected at some point in the network.

    This switching is almost instantaneous, allowing even gooses redundancy without loss or

    minimal loss (1 repetition). Regarding communications with IEC 61850 clients, depending on

    the ring reconfiguration time communications, we even could not lose the connection or the

    open session.

    1.6 HIGH-AVAILABILITY SEAMLESS REDUNDANCY (HSR)

    The HSR is a redundancy communication protocol defined in the IEC 62439-3 standard and it

    is one of the redundancy mechanism recommended in IEC 61850 networks.

    In the HSR protocol the device use two redundant ethernet ports and the protocol is based

    on the simultaneous transmission and reception of data via both independent ports.

    In the HSR networks no external switches are used, instead each device has two ring ports,

    and all the devices are connected in a ring topology, with one port of the device connected

    to the previous device and the other connected to the following device.

    For each frame to send, the device sends it duplicated over both ports. So one frame

    travels in the ring in the clockwise direction and the other frame travels in counter-

    clockwise direction. Each direction is treated as a separate network. So if there is a

    failure in one point of the network, the frames reach the destination using the other

    direction in the ring. With this mechanism HSR ensures zero-packet loss and zero recovery

    time upon single network failure.

    An HSR tag is placed at the beginning of each frame to allow early identification of

    frames. With this tag each device can identify the HSR tagged traffic and reject the

    duplicated frames coming from the both ports of a device and the frames circulating in the

    ring. When a device receives a frame directed to it or that it sent, the frame is discarded

    and it is not forwarded again in the ring. The frame is also discarded if it is a frame

    that it already sent in the same direction (i.e. multicast frames).

    Devices within the ring are restricted to be HSR-capable IEDs. In order to enable

    redundancy in non-HSR devices an external converter called RedBox (Redundancy Box) can be

    used.

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 11

    1.7 INTERCONNECTIONS

    Interconnections depend on the modules selected. The connections associated to each of the

    modules are indicated, and thus the diagram will depend on the modules installed.

    1.7.1 CPU

    Figure 7 3-contact relay and IRIG-B

    1.7.2 Power supply

    The two options are a redundant power supply and a simple power supply with

    inputs/outputs.

    Figure 8 Simple power supply

    Figure 9 Double power supply

    1.7.3 Input/output cards

    The I/O modules available are:

    Module 1 (Figure 10): Equipped with 11 digital inputs and 9 digital outputs grouped as follows:

    Inputs: 4 independents + 3 with a common point + 4 with a common point.

    Outputs: 5 independents + 3 with a common point + 1 switched (3 contacts).

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 12

    Figure 10 Module 11 digital inputs and 9 digital outputs

    Module 2 (Figure 11): Equipped with 16 digital inputs and 16 digital outputs grouped as follows:

    Inputs: 16 with a common point.

    Outputs: 16 with a common point.

    Figure 11 Module 16 digital inputs and 16 digital outputs

    Module 3 (Figure 12): Equipped with 16 digital inputs and 8 digital outputs grouped as follows:

    Inputs: 16 with a common point.

    Outputs: 8 independent.

    Figure 12 Module 16 digital inputs and 8 digital outputs

    Module 4 (Figure 13): Equipped with 32 digital inputs grouped as follows:

    Inputs: 16 with a common point + 16 with a common point.

    Figure 13 Module 32 inputs

    Module 5 (Figure 14): Equipped with 16 digital inputs and 8 analogue inputs grouped as follows:

    Inputs: 16 with a common point.

    Analogue: 8 independent. The analogue inputs have standard configuration, that could be changed among the options: 1mA, 2.5mA, 5mA, 20mA, 5V,

    10V

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 13

    Standard configuration of analogue inputs

    Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8

    +/- 5mA +/- 5mA +/- 2.5mA +/- 2.5mA +/- 2.5mA +/- 2.5mA +/- 20mA +/- 20mA

    Figure 14 Module with 16 digital inputs and 8 analogue inputs

    Module 6 (Figure 15): Equipped with 16 digital inputs and 8 analogue inputs (4 isolated) grouped as follows:

    Inputs: 16 with a common point.

    Analogue: 8 independent, 4 of them are isolated and 4 have a common point. The analogue inputs have standard configuration, that could be changed

    among the options: 1mA, 2.5mA, 5mA, 20mA, 5V, 10V

    Standard configuration of analogue inputs

    Input 1 Input 2 Input 3 Input 4 Input 5 (isolated)

    Input 6 (isolated)

    Input 7 (isolated)

    Input 8 (isolated)

    +/- 5mA +/- 5mA +/- 2.5mA +/- 2.5mA +/- 2.5mA +/- 2.5mA +/- 20mA +/- 20mA

    Figure 15 Module with 16 digital inputs and 8 analogue inputs (4 isolated)

    Mdule 7 (Figure 16): Equipped with 8 digital inputs, 4 high speed digital outputs (hbco) and 4 digital outputs grouped as follows:

    Inputs: 8 independent.

    Outputs: 8 independent.

    Figure 16 Mdule 8 inputs, 4 outputs (hbco) y 4 digital outputs

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 14

    Mdule 8 (Figure 17): Equipped with 8 digital inputs, 8 digital outputs grouped as follows:

    Inputs: 8 independent.

    Outputs: 8 independent.

    Figure 17 Mdule 8 inputs, 8 outputs

    1.7.4 Analogue inputs

    The following diagram shows the configuration of the analogue inputs:

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 15

    1.7.4.1 Wiring diagrams

    The following figures show different interconnection options for the analogue inputs,

    in accordance with the available inputs.

    Figure 18 Connection A. 3 wires connection: 3TT and 3TC

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 16

    Figure 19 Connection A. 4 wires connection : 3TT and 3TC

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 17

    Figure 20 Connection A. 3 wires connection: 3TT, Vneutral and 3TC

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 18

    Figure 21 Connection B.Delta 3 wires: 2TT and 3TC

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 19

    Figure 22 Connection B.Delta 3 wires: 2TT and 2TC

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 20

    Figure 23 Connection D. Delta 3 wires: 2TT and 1TC (balanced load)

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 21

    Figure 24 Connection E.4 wires: 1TT and 1TC (balanced load)

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 22

    Figure 25 Connection F.3 delta wires: 1TT and 1TC (balanced load)

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 23

    Figure 26 Connection G.4 Y wires: 2TT and 3TC

  • GENERAL DESCRIPTION

    Ingeteam Power Technology S.A.

    User Manual 24

    Figure 27 Connection A with synchronism (model CD2)

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 25

    2. HARDWARE

    2.1 CONSTRUCTION FEATURES

    2.1.1 Half chassis ( 19)

    2.1.2 19 chassis

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 26

    2.2 REAR TERMINALS

    The rear section will vary in accordance with the options selected for the unit. The

    following figures show various possible configurations.

    2.2.1 Configuration options

    The rear section options may vary depending on the options selected:

    Power supply unit. There are two options available:

    Simple with inputs/outputs. Equipped with a 3-contact terminal with power supply with screw and a 17-contact terminal with screw (Figure 28).

    Redundant. Equipped with two 3-contact terminals for each of the power supplies.

    Inputs/outputs cards. All the input/output modules have two 17-contact terminals with screw.

    CPU. Equipped with a 6-contact terminal with screw for the digital output of 3 contacts and the IRIG-B inputs. Equipped with different Ethernet and standard

    communications module options (Figure 7).

    Analogue. Equipped with two 12-contact terminals with screw.

    Communications. To choose between:

    Ethernet: RJ45 and G.F.O.

    Standard: RS232, RS485, G.F.O. and P.F.O.

    Pin type or closed type terminals may be chosen for the analogue and input/output

    terminals.

    2.2.2 Half chassis ( 19)

    Different options which modify the view of the rear section may be selected (from top to

    bottom):

    Simple/redundant power supply

    1 or 2 I/O modules

    Communication ports in the CPU

    Choose between analogue card, I/O module or nothing

    Figure 28 shows rear section with the options:

    Simple power source with inputs/outputs

    2 input/output cards

    CPU with communication ports:

    Ethernet GFO + RJ45

    Standard RS232+RS485+GFO+PFO

    Analogue card with up to 12 transformers

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 27

    Figure 28 Rear section with analogue and simple source

    Figure 29 Rear section without analogue and simple source

    2.2.3 19 chassis

    Different options which modify the view of the rear section may be selected (from top to

    bottom and left to right):

    Simple/redundant power supply

    1 or no I/O modules

    Communication ports in the CPU

    Choose between analogue card, I/O module or nothing

    Number of I/O modules

    In Figure 30 the next options can be seen:

    Simple power source with inputs/outputs

    5 input/output cards

    CPU with communication ports:

    Ethernet GFO + RJ45

    Standard with 3 RS232 + 2 GFO + PFO

    Analogue card with up to 12 transformers

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 28

    Figure 30 Rear section with analogue and simple source

    Figure 1 Rear section without analogue and simple source

    2.3 FRONT INTERFACE

    2.3.1 Half chassis ( 19)

    There are two half-chassis front options ( 19 and 5U):

    Configurable functional keys (Figure 31)

    Fixed functional keys (Figure 32).

    The front interfaces are equipped with:

    Graphic display

    19 general use LEDs with interchangeable labels

    1 2-colour unit status LED

    Numeric keypad

    7 operational keys

    Ethernet communication

    Master USB communication

    Depending on the model, the following are available:

    5 functional keys for selecting with interchangeable labels + 2 operational keys

    3 fixed function keys + 2 operational keys.

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 29

    Figure 31 Configurable functional keys

    Figure 32 Fixed functional keys

    2.3.2 19 chassis

    There are two 19 and 4U chassis front options:

    Configurable functional keys (Figure 33)

    Fixed functional keys (Figure 34)

    The front interfaces are equipped with:

    Graphic display

    19 general use LEDs with interchangeable labels

    1 2-colour unit status LED

    Numeric keypad

    7 operational keys

    Ethernet communication

    Master USB communication

    Depending on the model, the following are available:

    14 functional keys for selecting with interchangeable labels + 2 operational keys

    3 fixed function keys + 2 operational keys + 7 functional keys with interchangeable labels for selecting.

    Figure 33 Configurable functional keys

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 30

    Figure 34 Fixed functional keys

    2.3.1 Closed Terminals

    The next figures show the closed terminals used in the digital I/O boards (Figure 35)

    and the transformer inputs (V/I) (Figure 36).

    Figure 35 Closed Terminals I/O boards

    Figure 36 Closed Terminals transformer inputs (V/I)

    2.4 TECHNICAL CHARACTERISTICS

    2.4.1 Power supply voltage

    125 Vdc models: 110Vdc-20% up to 250Vac + 10%:

    Operating range:

    Direct: 85Vdc up to 300Vdc

    Alternating: 85Vac up to 265Vac

    24/48 Vdc models: 24Vdc-20% up to 48Vdc + 20%:

    Operating range:

    Direct: 18Vdc up to 60Vdc

    Burden. Depends on the cards connected.

    20W + 0,5W for each relay activated

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 31

    2.4.2 Digital outputs

    Independent standard and trip outputs:

    The characteristics of the independent contact outputs are as follows:

    Permanent current: 8 A at 25C

    Make: 30 A 1sec

    Connection capacity 2500W at 250Vdc

    Open or break capacity:

    200Vdc 125Vdc 48Vdc

    With resistive load 1.0A 1.5A 2.0A

    With inductive load

    L/R=40ms

    0.7A 1.0A 1.5A

    Operating time: 5ms activation and 8ms deactivation

    Signal outputs:

    The characteristics of the 3-contact switched, common point signal outputs are:

    Permanent current: 5 A at 25C

    Make:

    30 A sec.

    20 A 1 sec.

    Open or break capacity:

    200Vdc 125Vdc 48Vdc

    With resistive load 0.2A 0.4A 1.0A

    With inductive load

    L/R=40ms

    0.1A 0.2A 0.5A

    Operating time: 8ms activation and deactivation

    The compliance of the common point outputs is the same as that of the independent

    outputs. However, due to sharing a common point, only 2 relays can be activated

    simultaneously.

    High break contact outputs (h.b.c.o outputs):

    The characteristics of the independent contact outputs are as follows:

    Permanent current: 8 A at 25C

    Make: 30 A 1sec

    Connection capacity 2500W at 250Vdc

    Open or break capacity:

    200Vdc 125Vdc 48Vdc

    With resistive load 10A 10A 10A

    With inductive load 10A L/R=20ms 10A L/R=40ms 10A L/R=40ms

    Cyclic capacity: 4 cycles in 1 second, 2 minutes waiting for thermal dissipation

    Operating time:

    5ms activation and 5ms deactivation with resistive load

    6ms activation and 14ms deactivation with L/R = 40ms

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 32

    2.4.3 Digital inputs

    The input burden is lower than 3mA at nominal voltage.

    The inputs do not have polarity.

    They have a fixed range with 4 nominal voltage options:

    Rated V Characteristics

    24Vdc

    Not activated below 9 Vdc.

    Activated above 12 Vdc.

    Maximum voltage 72 Vdc

    48Vdc

    Not activated below 32 Vdc.

    Activated above 37 Vdc.

    Maximum voltage 72 Vdc

    125Vdc

    Not activated below 82 Vdc.

    They are activated above 87 Vdc.

    Maximum voltage 300 Vdc

    250Vdc

    Not activated below 165 Vdc.

    Activated above 172 Vdc.

    Maximum voltage 300 Vdc

    2.4.4 IRIG-B input and PPS

    Equipped with an input for synchronization by GPS, using IRIG-B time codes (Figure 37)

    Demodulated input (TTL levels).

    Cable type: 2-wire, shielded

    Insulation: 2000 V

    The input circuit is a 390 ohm serial resistance with an opto-isolator; for a 5 V signal,

    the approximate burden is 10 mA.

    The number of units that can be connected in parallel to a generator depends on the

    output current supply capacity; a typical value is 70 mA, which would enable the

    connection of 6 units (although the length and the type of cable can also influence). The

    cable must be shielded and twisted.

    There is a pulse per second (PPS) input for synchronization:

    Demodulated input (TTL levels).

    Cable type: 2-wire, shielded

    Insulation: 2000 V

    Figure 37 Connection example

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 33

    2.4.5 Current and voltage circuits

    Phases, neutral. Single rated current 1/5 A.

    Measurement range: 0,001A to 7,5A.

    Thermal capacity:

    Permanent 20 A

    Short duration 50 A (10 sec.)

    500 A (1 sec.)

    Burden at In= 5 A

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 34

    USB

    USB 2.0 compatible version

    Master operating mode

    Speed: 480Mbps (high-speed), 12Mbps (full-speed) or 1.5Mbps (low-speed)

    Insulation 500V

    2.4.7 Rear communications

    2.4.7.1 Ethernet communication

    Ethernet via RJ45 cable

    RJ45 connector (female)

    Cable type: Shielded

    Cable length: 100 m maximum

    Baud rate: 10/100 Mb.

    Insulation 500V

    Ethernet via glass optical fiber

    ST connector

    Wavelength: 1300nm

    Permitted attenuation 8 db with glass fiber

    Multimode glass optical fiber: 62.5 /125 m

    Baud rate: 100 Mb.

    Maximum distance: 1.5km

    Ethernet via LC conector

    Connector: LC duplex

    Wavelength: 1310 nm

    Permitted attenuation 8 db with glass fiber

    Multimode: 62.5/125 u m and 50/125um

    Baud rate: 100 Mb.

    Maximum distance: 1.5km

    2.4.7.2 Standard communications

    Glass optical fiber

    ST connector

    Wavelength: 820nm

    Permitted attenuation: 8 db with 62.5 /125 m glass fiber

    Multimode glass optical fiber: 62.5 /125 m

    Maximum distance: 1.5km

    Plastic optical fiber

    HP standard connector

    Wavelength: 660nm

    Permitted attenuation: 24.7db with 1mm plastic cable and 22db with 200 m silica cable

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 35

    Maximum distance: 115m with 1mm plastic cable and 1.9km with 200 m silica cable

    RS232

    DTE 9 pin female D type

    Cable type: Shielded

    Cable length: 15 m maximum

    Insulation 500V

    RS485

    DTE 9 pin female D type

    Cable type: Shielded crossed pair

    Cable length: 1.000 m maximum.

    Insulation 500V

    2.5 ENVIRONMENTAL CONDITIONS

    Operating temperature: -40 to +60C

    Storage temperature: -40 to 85 C

    Relative humidity: Up to 95% without condensation

    2.6 TESTS

    2.6.1 Climatic test

    TEST STANDARD

    Cold IEC -60068-2-1

    -40C, 16 hours

    Dry Heat IEC -60068-2-2

    +85C, 16 hours

    Damp heat steady state IEC -60068-2-78

    +40C/93%RH, 96 hours

    Damp heat cyclic

    IEC -60068-2-30

    55C/95% HR 6 cyclesof 12+12

    hours

    rapid change of temperature IEC -60068-2-14

    -20C/+70C 2 cycles of 4+4

    hours

    External protection level IEC60529

    IP30

    2.6.2 Insulation and electrical safety tests

    TEST STANDARD

    Dielectric test

    IEC 60255-5

    2.5 kVac

    Insulation resistance test IEC 60255-5

    > 100 M at 500Vdc.

    Impulse voltage test

    IEC 60255-5

    5kV MC

    5kV MD

    Protective earthing continuity test IEC 61131-2

    30 A 0.1

    Measurements of high Leakage current IEC 60255-27

  • HARDWARE

    Ingeteam Power Technology S.A.

    User Manual 36

    2.6.3 Electromagnetic tests

    TEST STANDARD

    1MHz burst immunity test IEC 60255-22-1

    2.5kV MC

    2.5kV MD

    Damped oscillatory waves immunity test IEC 61000-4-18

    2.5kV MC

    2.5kV MD

    Electrostatic discharges immunity test

    IEC 61000-4-2

    8kV/15kV

    Electrical Fast transient immunity test

    IEC 61000-4-4:

    4kV,5kHz

    Surge immunity test

    IEC 61000-4-5

    4kV MC

    2kV MD

    DC power supply interruptions, dips and variations immunity

    test

    IEC 61000-4-29

    100% 300 ms

    60% 300 ms

    30% 5s

    AC power supply interruptions and dips immunity test

    IEC 61000-4-11

    100% 10 ms, 20 ms, 5 s

    60% 200 ms

    30% 500 ms

    20% 5 s

    Ripple immunity test IEC 61000-4-17

    15% (50 and 100 Hz)

    Measurements of Harmonics current emissions IEC 61000-4-7 / IEC 61000-

    3-2

    Power frequency immunity test IEC 60255-22-7

    Class B

    Measurements of Radioelectric emissions IEC 61000-6-4

    Class A

    Radiated radiofrequency fields immunity test

    IEC 61000-4-3

    10V/m

    Conducted disturbances induced by radiofrequency fields

    immunity test

    IEC 61000-4-6

    10Vrms

    50 Hz magnetic fields immunity test IEC 61000-4-8

    100 A/m 1000 A/m (2 s)

    Pulse magnetic fields immunity test IEC 61000-4-9

    1000 A/m

    Damped oscillatory magnetic field immunity test IEC 61000-4-10

    100 A/m

    2.6.4 Mechanical tests

    TEST STANDARD

    Vibration (sinusoidal)

    IEC 60255-21-1:

    Class I

    Shocks and bumps:

    IEC 60255-21-2

    Class I

    Seismic IEC 60255-21-3

    Class I

  • MEASUREMENT

    Ingeteam Power Technology S.A.

    User Manual 37

    3. MEASUREMENT

    The measurements corresponding to 4 current trafos and 4 voltage trafos are calculated over

    these models, based on those calculated by the powers and energies.

    T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12

    I phase A I phase B I phase C I neutral -- -- -- -- V neutral V phase A V phase B V phase C

    There are rms and fundamental frequency measurements.

    The measurements measured and/or calculated by the unit are:

    Voltage measurements. There are rms and fundamental frequency measurements. See Table 1.

    Phase A simple voltage Vab compound voltages

    Angle V phase A Vbc compoundvoltajes

    Phase B simple voltage Vca compoundvoltages

    Angle V phase B Average compound voltages

    Phase B simple voltage Voltage unbalance

    Angle V phase B Harmonic distortion in Va, Vb, Vc and average (%)

    Average simple voltage Frequency

    Neutral voltage

    Angle V neutral

    Measurements of currents. There are rms and fundamental frequency measurements. VerTable 2.

    Phase A current (Amperes) Neutral current

    Angle I phase A Angle i neutral

    Phase B current (Amperes) Harmonic distortion in Ia, Ib, Ic and average (%)

    Angle I phase B Current unbalance

    Phase C current (Amperes)

    Angle I phase C

    Phase average current

    Measurements of power and energy. There are rms and fundamental frequency measurements. VerTable 3.

    Active power(kW) Active energy counter (positive)

    Reactive power(kVAR) Active energy counter (negative)

    Aparent power (kVA) Reactive energy counter (positive)

    Power factor phase A, B, C and average Reactive energy counter (negative)

  • MEASUREMENT

    Ingeteam Power Technology S.A.

    User Manual 38

    Table 1 Voltage measurements

    Measurement Description Node Data Atribute

    V phase A rms (module and angle) VA MMXU PhV phsA

    V phase B rms (module and angle) VB MMXU PhV phsB

    V phase C rms (module and angle) VC MMXU PhV phsC

    Phase Average voltage rms (module) AVERAGE V MMXU PhV net

    V neutral rms (module and angle) VN MMXU PhV neut

    V phase A fundamental (modulo y

    argumento) VA (fundamental) FUNMMXU

    FunPhV phsA

    V phase B fundamental (module and angle) VB (fundamental) FUNMMXU FunPhV phsB

    V phase C fundamental (module and angle) VC (fundamental) FUNMMXU FunPhV phsC

    V neutral fundamental (module and angle) VN (fundamental) FUNMMXU FunPhV neut

    V compound AB VAB MMXU PPV phsAB

    V compound BC VBC MMXU PPV phsBC

    V compound CA VCA MMXU PPV phsCA

    V compound average AVERAGE U MMXU PPV net

    THD voltage phase A THD phase A Voltage MHAI ThdPhV phsA

    THD voltage phaseB THD phase B Voltage MHAI ThdPhV phsB

    THD voltage phaseC THD phase C Voltage MHAI ThdPhV phsC

    THD voltage average THD Average Voltage MHAI ThdPhV net

    THD neutral voltage THD Neutral Voltage MHAI ThdPhV neut

    Sequence V0 (module and angle) V0 MSQI SeqV c1

    Sequence V1 (module and angle) V1 MSQI SeqV c2

    Sequence V2 (module and angle) V2 MSQI SeqV c3

    Frequency Frequency MMXU Hz net

    Table 2 Current measurements

    Measurement Description Node Data Atribute

    I phase A rms (module and angle) IA MMXU A phsA

    I phase B rms (module and angle) IB MMXU A phsB

    I phase C rms (module and angle) IC MMXU A phsC

    Phase Average currentrms (module) AVERAGE I MMXU A net

    I neutral rms (module and angle) IN MMXU A neut

    I phase A fundamental (module and angle) IA (fundamental) FUNMMXU FunA phsA

    I phase B fundamental (module and angle) IB (fundamental) FUNMMXU FunA phsB

    I phase C fundamental (module and angle) IC (fundamental) FUNMMXU FunA phsC

    I neutral fundamental (module and angle) IN (fundamental) FUNMMXU FunA neut

    THD current phase A THD phase A current MHAI ThdA phsA

    THD current phase B THD phase B current MHAI ThdA phsB

    THD current phase C THD phase C current MHAI ThdA phsC

    THD current average THD Average current MHAI ThdA net

    THD neutral current THD Neutral current MHAI ThdA neut

    Sequence I0 (module and angle) I0 MSQI SeqA c1

    Sequence I1 (module and angle) I1 MSQI SeqA c2

    Sequence I2 (module and angle) I2 MSQI SeqA c3

  • MEASUREMENT

    Ingeteam Power Technology S.A.

    User Manual 39

    Table 3 Power measurements

    Measurement Description Node Data Atribute

    Total active power ACTIVE POWER P MMXU TotW net

    Total reactive power REACTIVE POWER Q MMXU TotVAr net

    Average apparent power POWER S MMXU TotVA net

    Phase A active power Phase A Active Power MMXU W phsA

    Phase A reactive power Phase A Reactive Power MMXU VAr phsA

    Phase A apparent power Phase A S Power MMXU VA phsA

    Phase B active power Phase B Active Power MMXU W phsB

    Phase B reactive power Phase B Reactive Power MMXU VAr phsB

    Phase B apparent power Phase B S Power MMXU VA phsB

    Phase C active power Phase C Active Power MMXU W phsC

    Phase C reactive power Phase C Reactive Power MMXU VAr phsC

    Phase C apparent power Phase C S Power MMXU VA phsC

    Phase A power factor Cosine phi rms phase A MMXU PF phsA

    Phase B power factor Cosine phi rms phase B MMXU PF phsB

    Phase C power factor Cosine phi rms phase C MMXU PF phsC

    Average power factor Cosine phi rmsaverage MMXU PF net

    Total active power (fundamental) Active power P (fund) FUNMMXU FunTotW net

    Total reactive power (fundamental) Reactive power Q (fund) FUNMMXU FunTotVAr net

    Average apparent power (fundamental) Power S (fund) FUNMMXU FunTotVA net

    Phase A active power (fundamental) Phase A Active Power (fund) FUNMMXU FunW phsA

    Phase A reactive power (fundamental) Phase A Reactive Power (fund) FUNMMXU FunVAr phsA

    Phase A apparent power (fundamental) Phase A S Power (fund) FUNMMXU FunVA phsA

    Phase B active power (fundamental) Phase B Active Power (fund) FUNMMXU FunW phsB

    Phase B reactive power (fundamental) Phase B Reactive Power (fund) FUNMMXU FunVAr phsB

    Phase B apparent power (fundamental) Phase B S Power (fund) FUNMMXU FunVA phsB

    Phase C active power (fundamental) Phase C Active Power (fund) FUNMMXU FunW phsC

    Phase C reactive power (fundamental) Phase C Reactive Power (fund) FUNMMXU FunVAr phsC

    Phase C apparent power (fundamental) Phase C S Power (fund) FUNMMXU FunVA phsC

    Phase A power factor (fundamental) Cosine phi rms phase A (fund) FUNMMXU FunPF phsA

    Phase B power factor (fundamental) Cosine phi rms phase B (fund) FUNMMXU FunPF phsB

    Phase C power factor (fundamental) Cosine phi rms phase C (fund) FUNMMXU FunPF phsC

    Average power factor (fundamental) Cosine phi rms average (fund) FUNMMXU FunPF net

    The available measurements depend on the connection type:

    A Connection. The simple currents (Ia, Ib, Ic) and neutral and voltages (Va, Vb, Vc) and neutral are directly measured, and the rest of the measurements are

    calculated on the basis of these

    B Connection. The simple currents (Ia, Ib, Ic) and neutral and compound voltages (Vab, Vbc, Vca) are directly measured, and the rest of the measurements are

    calculated on the basis of these. Simple voltages are not available.

    D Connection. The simple current Ia and compound voltages (Vab, Vbc, Vca) are directly measured. The rest of the measurements are calculated on the basis of

    these. Simple voltages are not available. The currents Ib and Ic are calculated

    from Ia because the load is balanced

    E Connection. The simple current of phase A (Ia)and simple voltage of phase A (Va)are directly measured, and the rest of the measurements are calculated on the

    basis of theseThe voltage Vb and Vc are calculated from Va and the currents Ib and

    Ic are calculated from Ia because the load is balanced.

    F Connection. The simple current of phase C (Ic)and compound voltage of phases AB (Vab)are directly measured.The voltage Vbc and Vca are calculated from Vab and the

    currents Ia and Ib are calculated from Ia because the load is balanced. Simple

    voltages are not available.

    G Connection. The simple currents (Ia, Ib, Ic) and neutral and voltages (Va, Vc) are directly measured. The rest of the measurements are calculated on the basis of

    these. The simple voltage Vb is calculated from the other voltages (balanced load).

    The power measurements are calculated with the meausured voltajes and currents. Depending

    on the connection type, phase and/or total power are available.

    Depending on the connection type, phase and/or average power factor are available.

  • MEASUREMENT

    Ingeteam Power Technology S.A.

    User Manual 40

    There are four Energy counters: positive active, negative active, positive reactive,

    negative reactive.

    Table 4 Available measurements with connection type

    Measurement A B D E F G

    Voltage phase A (module)

    Voltage phase B (module)

    Voltage phase C (module)

    AverageV simple (module)

    V neutral (module)

    Voltage phase A (angle)

    Voltage phase B (angle)

    Voltage phase C (angle)

    Voltage neutral (angle)

    Voltage phases AB (module)

    Voltage phases BC (module)

    Voltage phases CA (module)

    Average V compound (module)

    Current phase A (module)

    Current phase B (module)

    Current phase C (module)

    Average current (module)

    I neutral (module)

    Current phase A (angle)

    Current phase B (angle)

    Current phase C (angle)

    Current neutral (angle)

    THD Voltage phaseA

    THD Voltage phaseB

    THD Voltage phaseC

    THD voltaje average

    THD V neutral

    THD Voltage phasesAB

    THD Voltage phasesBC

    THD Voltage phasesCA

    THD voltaje compoundaverage

    THD Current phaseA

    THD Current phaseB 99

    THD Current phaseC

    THD Current average

    THD I neutral

    Sequence V0

    Sequence I0

    Sequence V1

    Sequence I1

    Sequence V2

    Sequence I2

    Active Power

    Reactive Power

    Apparent Power

    Active Power phase A

    Reactive Power phase A

    Apparent Power phase A

    Active Power phase B

    Reactive Power phase B

    Apparent Power phase B

    Active Power phase C

    Reactive Power phase C

    Apparent Power phase C

    Power Factor phase A

    Power Factor phase B

    Power Factor phase C

    Power Factor average

  • MEASUREMENT

    Ingeteam Power Technology S.A.

    User Manual 41

    3.1 38BMEASUREMENTS DEPENDING ON WIRING PROCEDURES

    The available measurements on each connection type are showed in Table 4.

    3.1.1 Connection Type A

    The simple currents and voltages are directly measured, and the rest of the measurements

    are calculated on the basis of these.

    Each phase power is calculated with Equation1.

    Equation1. Phase Power

    iii

    iii

    iii

    IVS

    IVQ

    IVP

    )Im{

    )Re{

    (beingieach phase A, B and C).

    Total power is calculated with Equation 2:

    Equation 2. Total Power

    P P P P

    Q Q Q Q

    S S S S

    T A B C

    T A B C

    T A B C

    The power factor uses Equation 3 for each phase andEquation 4 for total power.

    Equation 3.Power factor for each phase

    i

    i

    iS

    Pcos

    Equation 4. Total Power Factor

    T

    T

    TS

    Pcos

    Direct, inverse and zero sequences of currents and voltages are available (Equation 5).

    Equation 5. Currents and voltages Sequences

    )(3

    10 cVbVaVV

    )(3

    1 21 cVabVaaVV

    )(3

    1 22 cVabVaaVV

    )(3

    10 cIbIaII

    )(3

    1 21 cIabIaaII

    )(3

    1 22 cIabIaaII

    where a=1|120

    3.1.2 Connection Type B

    The simple currents and compound voltages are directly measured.

    There are not measurements of simple voltages, power for each phase (P, Q, S and power

    factor) and zero sequence. All of them are marked as invalid.

  • MEASUREMENT

    Ingeteam Power Technology S.A.

    User Manual 42

    Total active power (P), reactive power (Q) and apparent power (S) are calculated using

    Equation 6 and average power factor using Equation 4.

    Equation 6. Total Power

    caabcbT VIVIP

    In the connections, where compound voltages are measured, the voltage zero sequence is

    not available and the direct and inverse sequences are calculated with the compound

    voltaje as:

    Equation 7. Sequences calculation

    3)(

    3

    1 180330

    2

    1

    j

    eacVacbVabaVV

    3)(

    3

    1 180330

    2

    2

    j

    eacVacbVabaVV

    where a=1|120

    This wiring type may be connected with only two current trafos, while the measurement of

    the third current is carried out as the sum of the other two (see Equation 7).

    3.1.3 Connection Type D

    In this case, the compound voltages and phase A current are directly measured.

    The other two currents, as they are for balanced load, are the same in module as the

    measured current, but dephased 120 and 120 respectively.

    From this point on, the compound voltages and phase currents are available, and the rest

    of the measurements are calculated on the basis of these.

    There are not measurements of simple voltages, power for each phase (P, Q, S and power

    factor) and zero sequence. All of them are marked as invalid.

    Total active power (P), reactive power (Q) and apparent power (S) are calculated using

    Equation 8 and average power factor using Equation 4.

    The voltage zero sequence is not available. The direct and inverse sequences are

    calculated with the compound voltaje using Equation 7.

    Equation 8. Total Power calculation

    )(3 bcaT VIP

    3.1.4 Connection Type E

    In this case, only one measurement voltage and one measurement current are available.

    The other two voltages are the same in module as the measured current, but dephased 120

    and 120 respectively, because the load is balanced.

    The other two currents are the same in module as the measured current, but dephased 120

    and 120 respectively, because the load is balanced.

    As the load is balanced, all the sequences are zero.

    The power of each phase is the same and it is enough to calculate one of them (Equation

    9) and the total power as three times the calculated phase (Equation 10).

  • MEASUREMENT

    Ingeteam Power Technology S.A.

    User Manual 43

    Equation 9.Power for phase A

    AAA

    AAA

    AAA

    IVS

    IVQ

    IVP

    Im

    Re

    Equation 10. Total Power

    AT

    AT

    AT

    SS

    QQ

    PP

    3

    3

    3

    The total and phase power factors are also the same and it is enough with calculating

    phase A.

    Equation 11. Power factor

    cos AA

    A

    P

    S

    3.1.5 Connection Type F

    In this case, only a measured compound voltage (Vab) and measured current (Ic) are

    available.

    The other two voltages are the same in module as the measured current, but dephased 120

    and 120 respectively, because the load is balanced.

    The other two currents are the same in module as the measured current, but dephased 120

    and 120 respectively, because the load is balanced.

    As the load is balanced, all the sequences are zero.

    There are not measurements of simple voltages, power for each phase (P, Q, S and power

    factor) and zero sequence. All of them are marked as invalid.

    The total power is calculated starting from measured compound voltage and simple current

    (Equation 12).

    Equation 12. Total Power factor

    CpotT

    CpotT

    CpotT

    ABpot

    IVS

    IVQ

    IVP

    jVV

    3

    Im3

    Re3

    Only the average power factor is available (Equation 13).

    Equation 13. Power factor

    T

    TT

    S

    Pcos

    3.1.6 Connection Type G

    In this case, the three phase currents and simple voltages of phase A and C are directly

    measured.

  • MEASUREMENT

    Ingeteam Power Technology S.A.

    User Manual 44

    As the load is balanced, phase B voltage is calculated with Equation 14.

    From this point on, the simple voltages and phase currents are available, and the rest of

    the measurements are calculated on the basis of these.

    The equations are the same as A connection.

    Equation 14. Vb Voltage calculation

    CAB VVV

    3.2 16BENERGY COUNTERS

    They correspond to the primary of the measurement transformers, so there are parameters

    that indicate transformatio ratio of the voltage and current trafos.

    The measurement is given as the number of pulses. There is a programmable parameter that

    indicates the number of kWh/pulse for the active energy counters, and another kVARh / pulse

    for the reactive energy counters.

    So, the settings related to the energy counters are:

    Voltage trafo ratio

    Current trafo ratio

    Active Energy counter (kWh)

    Reactive Energy counter (kVARh)

    Application example:

    A 1500kWh burden measurement will read 1500 pulses for an active energy constant of 1 kWh

    primary / pulse. The Reading will be 300 pulses for an active energy constant of 5 kWh

    primary / pulse.

    Table 5 Energy counters

    Name Node Data Atribute

    Positive active Energy counter Active Energy Out MMTR SupWh actVal

    Negative active Energy counter Active Energy In MMTR DmdWh actVal

    Positive reactive Energy counter Reactive Energy Out MMTR SupVArh actVal

    Negative reactive Energy counter Reactive Energy In MMTR DmdVArh actVal

  • AUTOMATISMS

    Ingeteam Power Technology S.A.

    User Manual 45

    4. AUTOMATISMS

    Only in models CD2.

    4.1 SYNCHRONISM

    The synchronism function or synchrocheck waits for the appropriate conditions established

    in the settings, to determine breaker closure, both manual and automatic.

    Two voltage signals from the two sides of the breaker, which we will call side A and side

    B, are compared.

    Side A corresponds to the voltage input selected with the setting Side A Phase Select.

    This setting selects the analogue input used. The selection between ground to phase and

    phase to phase voltages is made with the connection type. With this setting a compensation

    factor is applied to equalize the module and the angle of the two voltages compared (side A

    and side B).

    Side B corresponds to the analogue voltage input connected to the synchronism voltage

    terminals.

    Table 2 shows the settings of this function:

    Enabled. Indicates whether the function is enabled or not. When enabled, the function tests the synchronism conditions. When disabled, manual closure permission is granted,

    but automatic permission is refused.

    Side A phase Select: selectable between A/AB, B/BC or C/CA, corresponding to the measurement of the selected voltage transformer. A/AB for transformer 10, B/BC for

    transformer 11 and C/CA for transformer 12.

    Compensation factor (Vs1): the factor by which the module is multiplied in order to equalize the voltages.

    Compensation angle (Vs1): the factor to be added to the angle in order to equalize the voltages.

    The synchronism function can be disabled by means of a setting (NO) or a breaker closure

    permission block digital input.

    When disabled, manual closure permission is granted but not automatic closure permission.

    In order to give closure permission when enabled, the function contemplates the conditions

    that grant undervoltage permission or synchronism permission. If any of then grants

    permission, closure permission is granted. Manual and automatic closure permissions are

    analysed independently.

    Undervoltage:

    When disabled undervoltage permission is refused.

    When enabled, undervoltage conditions are analised. If undervoltage permission is granted, closure permission is granted, independently of synchronism conditions.

    Synchronism: when undervoltage permission is not granted, synchronism conditions are analised

    When disabled synchronism permission is refused.

    When enabled, synchronism conditions are analised. .

    4.1.1 Undervoltage permission

    Permission is granted if there is voltage on one or on both sides of the breaker. In

    order to verify whether there is no voltage present on one side of the breaker, the

    voltage measured is checked to see whether it is lower than the programmed value (see

    Table 2).

  • AUTOMATISMS

    Ingeteam Power Technology S.A.

    User Manual 46

    A-Side Voltage presence (V): the voltage measured in side A must exceed this value in order to consider that there is voltage on that side of the breaker.

    A-Side Lack of Voltage (V): the voltage measured in side A must be lower than this value in order to consider that there is an absence of voltage on that side of the

    breaker. It must be at least 5% less than Voltage presence.

    B-Side Voltage presence (V): the voltage measured in side B must exceed this value in order to consider that there is voltage on that side of the breaker.

    B-Side Lack of Voltage (V): the voltage measured in side B must be lower than this value in order to consider that there is an absence of voltage on that side of the

    breaker. It must be at least 5% less than Voltage presence.

    Autoreclose condition. Indicates the conditions for granting reclosing permission with undervoltage:

    Without permission: under no circumstances will the function grant undervoltage permission

    Not A and Yes B: there must be an absence of voltage on side A in order for the function to grant undervoltage permission.

    Yes A and Not B: there must be an absence of voltage on side B in order for the function to grant undervoltage permission.

    Not A and Not B: there must be an absence of voltage on both sides of the breaker in order for the function to grant undervoltage permission.

    Not A or Not B: there must be an absence of voltage on one of the sides of the breaker in order for the function to grant undervoltage permission.

    A xor B: there must be voltage presence on one side of the breaker and an absence on the other in order for the function to grant undervoltage permission.

    Manual closing condition. Indicates the conditions for granting undervoltage manual closing permission:

    Without permission: under no circumstances will the function grant undervoltage permission

    Not A and Yes B: there must be an absence of voltage on side A in order for the function to grant undervoltage permission.

    Yes A and Not B: there must be an absence of voltage on side B in order for the function to grant undervoltage permission.

    Not A and Not B: there must be an absence of voltage on both sides of the breaker in order for the function to grant undervoltage permission.

    Not A or Not B: there must be an absence of voltage on one of the sides of the breaker in order for the function to grant undervoltage permission.

    A xor B: there must be voltage presence on one side of the breaker and an absence on the other in order for the function to grant undervoltage permission.

    The detection of the presence or the absence of voltage is always done in all the phases.

    However, the analysis of the conditions for granting or refusing breaker close permission

    is only carried out if the function is enabled.

    4.1.2 Synchronism permission

    Synchronism permission is given when following conditions indicated by the corresponding

    setting are simultaneously fulfilled during a programmable time. These conditions are

    based on the comparison of voltage modules, phases and frequency on both sides of the

    breaker. The analysis is performed whenever there is voltage on both sides of the

    breaker.

    Table 2 shows the settings of this function:

    Enabling of synchrocheck with reclosure:

    None: under no circumstances will the function grant synchronism permission.

  • AUTOMATISMS

    Ingeteam Power Technology S.A.

    User Manual 47

    No compensation: comparisons between angles, modules and frequencies are taken into account to grant permission if the set conditions are met during the

    programmed time

    Enabling of synchrocheck with manual closure:

    None: under no circumstances will the function grant synchronism permission.

    No compensation: comparisons between angles, modules and frequencies are taken into account to grant permission if the set conditions are met during the

    programmed time

    Breaker close time (s): taken into account when calculating the angle difference and providing that the enabling "with compensation" has been programmed. In this

    case, the frequency slip is taken into account to compensate for this time.

    Voltage difference (V): the difference between the voltage modules on side A and side B must be less than this value in order for permission to be granted.

    Frequency difference (Hz): the difference between the frequencies on side A and side B must be less than this value in order for permission to be granted.

    Angle difference (): the difference between the voltage angles on side A and side B must be less than this value in order for permission to be granted.

    Manual closure condition compliance time (s): the time during which the conditions for the granting of permission for closure must be met.

    Reclosure condition compliance time (s): the time during which the conditions for the granting of permission for reclosure must be met.

    Synchronism function measurements available in the unit status:

    Module, argument, frequency of the voltage on side A

    Module, argument, frequency of the voltage on side B

    The difference between the module, argument, frequency of the voltage on side A and side B. They are only available when the voltage presence conditions are met

    on both sides.

    The function has independent settings, commands and outputs:

    Node: PROT/RSYN1

    Settings and logical inputs: There are 6 settings tables. See Table 2.

    Blocking input :: logic input which, when active, blocks the function.

    Close blocking: logic input which, when active, blocks the breaker close permission.

    Commands:

    DOrdSyBlk1: Function block and unblocking. Only acts when the function is enabled.

    DOrdPeBlk1: Close permission block and unblock. Only acts when the function is enabled.

    Outputs: Table 3 shows the functions output data.

  • AUTOMATISMS

    Ingeteam Power Technology S.A.

    User Manual 48

    Table 2 Synchronism settings

    Data Setting Minimum Maximum Step Remarks Type

    SynEna Enabled 0 1 1 enum

    SiASel Side A Phase Select AA/AB, B/BC, C/CA enum

    CoModVs1 Compensation factor (Vs1) 0.1 3 0.01 float

    CoArgVs1 Compensation angle (Vs1) 0 330 30 float

    PrVSiA A-Side Voltage presence(V) 10 200 0.1 float

    AbVSiA A-Side Lack of Voltage (V) 10 200 0.1 float

    BrClTmms1 Closing time (ms) 0 100000 10 float

    SyWReEna1 Sync. Enabled (AR) No,

    Without compensation enum

    SyWMaClEna1 Sync. Enabled (Close) No,

    Without compensation enum

    SyDifV1 Voltage difference (V) 0 90 0.1 float

    SyDifF1 Frequency difference(Hz) 0.01 5 0.01 float

    SyDifA1 Angle difference () 0 360 1 float

    ReTmms1 Sync. Time (Autoreclose) 0 100000 10 float

    MaClTmms1 Sync.Time (Man.closing) 0 100000 10 float

    PrVSiB1 B-Side Voltage presence(V) 10 200 0.1 float

    AbVSiB1 B-Side Lack of Voltage (V) 10 200 0.1 float

    ClCond1 Manual closing condition enum

    ReCond1 Autoreclose condition enum

    LogInBlSy1 Blocking input Int32

    LogInBlCl1 Close blocking Int32

    MaskEna Enable Events Record NO (0) / YES (1) Boolea

    n

    Synchrocheck function signals (see Table 3). It is necessary that voltage presence is

    detected on both sides of the breaker in all of them:

    Positive slip Breaker 1: active if the frequency on the B side is also greater than that on side A by more than 10mHz.

    Negative slip Breaker 1: active if the frequency on the A side is also greater than that on side B by more than 10mHz.

    Underfrequency side B B1: active if the frequency difference of both sides exceeds the setting value and the frequency on side A is greater than that on side B.

    Overfrequency side B B1: active if the frequency difference of both sides exceeds the setting value and the frequency on side B is greater than that on side A.

    Delay without comp. side B 1: with the difference between the arguments exceeds the setting value and is greater on side A than on side B.

    Advance without comp. side B 1: with the difference between the arguments exceeds the setting value and is greater on side B than on side A.

    Over Module side B B1: the voltage difference is greater than the programmed setting and the voltage in B is greater than in A.

    Under Module side B B1: the voltage difference is greater than the programmed setting and the voltage in A is greater than in B.

    Perm. without comp.. B1: indicates that differences in voltage, argument and frequencies are lower than the corresponding settings.

    Perm. Manual Close V B1: Manual closure permission for voltage checks. Its active when the undervoltage conditions are met.

    Permission Recloser V B1: Reclosure permission for voltage checks. Its active when the undervoltage conditions are met.

    Perm. Manual Close B1: closure permission for undervoltage or for synchronism. Its actived, due to compliance with the undervoltage conditions or the

    synchronism conditions. If the function is disabled, manual closure permission

    will also be signalled.

  • AUTOMATISMS

    Ingeteam Power Technology S.A.

    User Manual 49

    Perm. Reclose Br 1: reclosure permission for undervoltage or synchronism, so that the recloser decides on the automatic closure of the breaker. Its actived, due to

    compliance with the undervoltage conditions or the synchronism conditions.

    Table 3 Synchronism function outputs for breaker 1

    Signal Data Atribute

    Positive Slip Breaker 1 PosSlipBr1 stVal

    Negative Slip Breaker 1 NegSlipBr1 stVal

    Underfrequency side B B1 UFSideBBr1 stVal

    Overfrequency side B B1 OFSideBBr1 stVal

    Delay without comp. side B 1 DBNSlipBr1 stVal

    Adv. without comp.side B B1 ABNSlipBr1 stVal

    Over Module side B B1 OAbsBBr1 stVal

    Under Module side B B1 UAbsBBr1 stVal

    Perm. without comp.. B1 PNoSlipBr1 stVal

    Perm. Manual Close B1 PMCBr1 stVal

    Perm. Close Recloser Br 1 PRecBr1 stVal

    Perm. Manual Close V B1 PMClVChBr1 stVal

    Permission Recloser V B1 PRecVChBr1 stVal

    Enable Synchro Breaker 1 EnaBr1 stVal

    Voltage presence Va/Vab side A SAVPres phsA

    Voltage presence Vb/Vbc side A SAVPres phsB

    Voltage presence Vc/Vca side A SAVPres phsC

    Voltage presence ABC side A SAVPres general

    No Voltage Va/Vab side A SAVAbs phsA

    No Voltage Vb/Vbc side A SAVAbs phsB

    No Voltage Vc/Vca side A SAVAbs phsC

    No Voltage ABC side A SAVAbs general

    Voltage presence side A SAPres stVal

    No Voltage side A SAAbs stVal

    Voltage presence side B B1 SBVPresBr1 stVal

    No Voltage side B B1 SBVAbsBr1 stVal

    Active Sync V Vs1 Vs1 stVal

  • MONITORING

    Ingeteam Power Technology S.A.

    User Manual 50

    5. MONITORING

    5.1 EXTERNAL POWER SUPPLY MONITORING

    This function checks if the external supply voltage is within the set range. It generates

    two signals:

    Auxiliary power supply greater than maximum threshold. If the supply voltage exceeds the set maximum threshold.

    Auxiliary power supply lower than minimum threshold. If the supply voltage is below the set minimum threshold.

    The settings for configuring the external power supply monitoring (Table 4):

    Enabled: Enables the external power supply monitoring function.

    Minimum threshold. Indicates the minimum power supply voltage threshold, below which an alarm is issued.

    Maximum threshold. Indicates the maximum power supply voltage threshold, above which an alarm is issued.

    Table 4 External power supply monitoring settings

    Name IEC 61850 Setting Minimum Maximum Step Remarks Type

    SupSpvEna Enabled

    NO (0) / YES

    (1) enum

    LoSuppV Minimum threshold 10 280 1 float

    HiSuppV Maximum threshold 10 280 1 float

    It has independent settings, commands and outputs:

    PROT/CESS1 node

    Settings. There are 6 settings tables. For details see Table 4.

    There are no logical inputs or commands

    Outputs: Table 5 shows the functions output data.

    Enabled. It is active when enabled and not blocked.

    Power supply greater than maximum threshold. Indicates that the power supply has exceeded the maximum threshold.

    Power supply lower than minimum threshold. Indicates that the power supply is below the minimum threshold.

    Measurement. The external power supply value is available (see Table 6)

    Table 5 Power supply monitoring outputs

    Signal Data Attribute

    Enabled StEna stVal

    Power supply greater than maximum OverVcc general

    Power supply lower than minimum UnderVcc general

    Table 6 Power supply monitoring measurement

    Measurement Data Attribute

    External power supply Supply net

  • MONITORING

    Ingeteam Power Technology S.A.

    User Manual 51

    5.2 TEMPERATURE MONITORING

    This function checks if the temperature is within the set range. It generates two signals:

    Temperature greater than maximum threshold. If the temperature exceeds the set maximum threshold.

    Temperature lower than minimum threshold. If the temperature is below the set minimum threshold.

    The settings for configuring the external power supply monitoring (Table 4):

    Enabled: Enables the temperature monitoring function.

    Minimum temperature (C). Indicates the minimum temperature threshold, below which an alarm is issued.

    Maximum temperature (C). Indicates the maximum temperature threshold, above which an alarm is issued.

    Table 7 Temperature monitoring settings

    Name IEC 61850 Setting Minimum Maximum Step Remarks Type

    TmpSpvEna Enabled

    NO (0) / YES

    (1) enum

    LoTmpVal Minimum temperature (C) -40 0 1 float

    HiTmpVal Maximum temperature (C) 50 100 1 float

    It has independent settings, commands and outputs:

    PROT/CTSU1 node

    Settings. There are 6 settings tables. For details see Table 7.

    There are no logical inputs or commands

    Outputs: Table 8 shows the functions output data.

    Enabled. It is active when enabled and not blocked.

    Temperature greater than maximum threshold. Indicates that the temperature has exceeded the maximum threshold.

    Temperature lower than minimum threshold. Indicates that the temperature is below the minimum threshold.

    Measurement. The temperature value is available (see Table 9Table 6)

    Table 8 Temperature monitoring outputs

    Signal Data Attribute

    Enabled StEna stVal

    Power supply greater than maximum OverTemp general

    Power supply lower than minimum UnderTemp general

    Table 9 Temperature measurement

    Measurement Data Attribute

    Temperature Temp net

  • MONITORING

    Ingeteam Power Technology S.A.

    User Manual 52

    5.3 DIS BLOCKING BY LACK OF VAUX

    If enabled, it checks that the external power supply exceeds the battery failure threshold,

    generating an alarm signal when it is below the threshold.

    The settings for configuring the battery failure monitoring (Table 10)

    Enabled: Enables the battery failure monitoring function.

    Table 10 Battery failure monitoring settings

    Name IEC 61850 Setting Minimum Maximum Step Remarks Type

    SupSpvEna Enabled NO / YES enum

    There are independent settings and outputs:

    PROT/CSUS1 node

    Settings. There are 6 settings tables. See Table 10.

    There are no logical inputs or commands

    Outputs: Table 11 shows the functions output data.

    Enabled. It is active when enabled and not blocked.

    Low power supply (DFFA). Indicates that the external power supply is below the minimum threshold.

    Table 11 Battery failure monitoring outputs

    Signal Data Attribute

    Enabled StEna stVal

    Low power supply (DFFA) DFFA general

    5.4 INTERNAL BATTERY FAILURE MONITORING

    The internal battery used for data maintenance is checked to ensure that it does not fall

    below a security level.

    There are independent outputs:

    GEN/LPHD1 node

    It does not use settings.

    There are no logical inputs or commands.

    Outputs: Table 12 shows the functions output data.

    Internal battery failure. Indicates that the internal battery level is below the minimum threshold.

    Measurement. The temperature value is available (see Table 13Table 6)

    Table 12 Internal battery failure outputs

    Signal Data Attribute

    Battery failure BatAlm general

    Table 13 Internal battery measurement

    Measurement Data Attribute

    internal battery IntBat net

  • MONITORING

    Ingeteam Power Technology S.A.

    User Manual 53

    7.5 UNIT CHECKS

    The unit continually checks the various incorporated elements and cards. If an error is

    detected in any of the elements or cards, an alarm is generated. If the error affects the

    units operation, a critical error is generated, which in addition to the signal acts on :

    Colour front LED. Non-configurable status LED, which indicates the units general status. If the LED is green, it indicates that everything is correct, while if it

    is red it indicates a critical error in the unit.

    CPU Relay. Non-configurable 3-contact relay, which indicates the units general status. If the LED is active (common terminal NO), it indicates that everything

    is correct, while if it is deactivated (common terminal NC) it indicates a

    critical error in the unit. If the unit is switched off, the relay is deactivated.

    The unit's alarm signals are to be found in the LPHD node. The available signals indicate faults in the card check, in the communications between the cards, in the

    units configuration, etc.:

    Critical hardware error. Indicates that a critical error has been produced. In addition to this signal, the cause that produced the signal will be indicated.

    CPU error. Indicates that the check has detected an error in the CPU. It generates critical error signal.

    Analogue error. Indicates an error in transformers card. It generates critical error signal.

    I/O micro error. Indicates an error in the I/O cards micro.

    Analogue connection error. Indicates that a fault has been produced in the communications between the CPU and the transformers card. It generates critical

    error signal.

    I/O connection error. Indicates that a fault has been produced in the communication between the CPU and an I/O card. It generates critical error signal. Additionally,

    it will indicate the card which has suffered the failure:

    Error card address x. Indicates that there is a communication error with the card with the address x.

    Front connection error. Indicates that a fault has been produced in the communications between the CPU and the units front card. It generates critical

    error signal.

    Shared analogue memory error. Indicates that a fault has been produced in the Data exchange memory between the CPU and the transformers card. It generates critical

    error signal.

    Error shared I/O memory. Indicates that a fault has been produced in the Data exchange memory between the CPU and the I/O cards. It generates critical error

    signal.

    RTC clock error. Indicates that the check has detected an error in the real time clock.

    Continuous component monitoring alarm. Indicates that an error in the continuous measurement monitoring has been detected in the transformers card.

    Alarm settings. Indicates that errors have been detected in the storage of the units settings. It generates critical error signal.

    Memory check alarm. Indicates that errors have been detected in the checking of the units memory. It generates critical error signal.

    Converter check alarm. Indicates that errors have been detected in the transformers card AD converter. It generates critical error signal.

    Converter voltage level alarm. Indicates that errors have been detected in the transformers card reference voltages. It generates critical error signal.

    Relay activation alarm. Indicates that an error has been detected in the activation of at least one of the I/O cards relays. It generates critical error signal.

  • MONITORING

    Ingeteam Power Technology S.A.

    User Manual 54

    I/O configuration error. Indicates that the configuration of the I/O cards does not coincide with the units correct configuration. It generates critical error signal.

    General Vdc error. Indicates a failure in the internal power supply levels. It generates critical error signal.

    Frequency configuration error. This is not a unit failure, but rather a configuration failure. Indicates that the frequency measurement of the signals

    being injected into the unit do not match the set measurement, that is, the unit is

    configured as 50Hz and the signals which are being injected are greater than 55Hz;

    or that the unit is configured as 60 Hz and the signals being injected are less

    than 55 Hz.

    Internal battery failure. Indicates that the data storage battery is below the security levels and that the data may be lost at shutdown.

    Version compatibility error. Indicates that the versions of the unit's firmware are not correct.

    Time setting configuration alarm. Indicates that there is an error in the configuration of the units time setting.

    ICD error. Indicates the last ICD received by the device was wrong and it was refused by the device. Once activated, this signal is deactivated when a correct

    ICD is received.

    For each I/O card there is are 5 signals, indicating:

    Status OK. Indicates that the card is configured correctly and without errors.

    Configured & No_detected. Indicates that the card is configured by the user, but not detected in the unit. This may be because it is not assembled or because it

    has an error. Equivalent to the current