Upload
lamminh
View
232
Download
1
Embed Size (px)
Citation preview
UC Davis Microgrid
Jared Balavender, DTU
Katarina Knezovic, DTU
Adrian Unkeles, UCSC
Yingying Zheng, UCD
Problem Statement
Client: UC Davis
Goal: Carbon Neutral by 2025
Main limitation
No net metering
Considerations:
Demand reductions and energy efficiency
Increased PV generation
Storage via Batteries
Demand response
Rescheduling the cooling system
Base scenario Consumption profile for 2012
Total demand: 229,443 MWh
Baseload: 165,564 MWh
72% of annual energy consumption goes to base load
0 1000 2000 3000 4000 5000 6000 7000 800015
20
25
30
35
40
45
Pow
er (M
W)
Time of year (h)
16.3 MW of PV 32,725 MWh
Equals 14.3% of current total demand
19.8% of baseload
Total UCD consumption in 2012
Assumptions
PV efficiency degradation of 0.25% per year
No possibility of net metering
2014 data equivalent to 2012 data
Campus cooling system electricity usage remains constant
Cooling system consists of 8 absorption chillers with total rated power of 12.6 MW at an average efficiency rate of 0.7 kW/ton
Electricity price is 0.07$/kWh and constant throughout project period
Baseload remains same percentage of demand
Refined Scope: Optimize use of doubling PV generation
Analyzed Cases
UC Davis doubles PV nominal capacity to 32.6 MW and
Two scenarios for the campus consumption profile:
1) no decrease – base scenario
Consumption the same throughout 10 years
2) 5% decrease in annual demand through project period
Total demand in 2025: 144,607 MWh
Baseload in 2025: 104,305 MWh
Excess PV generation
Estimated production for 32.6 MW photovoltaic array
Exceeds the demand for 1733 hours in the base scenario
0 1000 2000 3000 4000 5000 6000 7000 80000
5
10
15
20
25
30
Pow
er (M
W)
Time of year (h)
Estimated PV Power Generation
Excess PV generation
Scenario with no consumption decrease
0
200
400
600
800
1000
1200
1400
1 2 3 4 5 6 7 8 9 10
Excess PV generation (MWh/year)
Year Loss of PV generation
1 1.78%
2 1.74%
3 1.69%
4 1.65%
5 1.60%
6 1.56%
7 1.52%
8 1.48%
9 1.44%
10 1.40%
Excess PV generation
Scenario with 5% consumption decrease every year
0
2000
4000
6000
8000
10000
12000
14000
16000
1 2 3 4 5 6 7 8 9 10
Excess PV generation (MWh/year)
Year Loss of PV generation
1 1.78%
2 2.85%
3 4.21%
4 5.84%
5 7.72%
6 9.83%
7 12.12%
8 14.60%
9 17.21%
10 19.87%
Value of lost energy
Year Value of lost generation for Scenario 1 Year Value of lost generation
for Scenario 2
1 $91,362 1 $91,362 2 $88,808 2 $145,708 3 $86,306 3 $214,952 4 $83,834 4 $297,432 5 $81,409 5 $392,334 6 $79,055 6 $498,421 7 $76,763 7 $613,301 8 $74,517 8 $737,064 9 $72,324 9 $866,887 10 $70,173 10 $998,420
TOTAL $804,551 TOTAL $4,855,881
Assuming 0.07$/kWh -> even larger losses if the price increases
Potential technologies for utilizing excess energy
Two different battery technologies
simple cost-analysis conducted
case of no consumption decrease with all excess energy stored in the batteries -> not cost effective
Customer demand response
indirect strategies not cost-effective due to low electricity price
Temporary load shifting
changing the operation schedule of cooling chillers
the most feasible solution
Current cooling system
Rescheduling cooling chillers
Scenario 1
Load shifting is effective for the months of April through October.
Operation of chillers in most inefficient temperature range still leads to net cost benefits because the PV provides all the energy at that time.
Scenario 2
Load shifting is effective throughout the year, with duration and frequency peaking in the summer
12.67 MW peak excess PV in year 10
CO2 emissions
If all the excess energy was used to power the chillers during the day, significant CO2 savings would be made
No consumption change 5% decrease in consumption every year
Year Excess generation used by cooling system (MWh)
GHG Emission (Ton CO2e)
Year Excess generation used by cooling system (MWh)
GHG Emission (Ton CO2e)
1 1,305.17 404.60 1 1,305.17 404.60 2 1,268.69 393.29 2 2,081.55 645.28 3 1,232.95 382.21 3 3,070.74 951.93 4 1,197.63 371.27 4 4,249.02 1,317.20 5 1,162.99 360.53 5 5,604.77 1,737.48 6 1,129.35 350.10 6 7,120.30 2,207.29 7 1,096.62 339.95 7 8,761.45 2,716.05 8 1,064.53 330.00 8 10,529.49 3,264.14 9 1,033.19 320.29 9 12,384.10 3,839.07 10 1,002.47 310.77 10 14,263.14 4,421.57
TOTAL 3,563.01 TOTAL 21,504.61
Conclusion and recommendations Excess energy curtailment
No decrease in consumption: $804,551 lost
5% decrease in consumption: $4,855,881 lost
Batteries and customer demand response are not cost-effective for storing the excess energy
Changing the operation schedule for the chillers
Chillers rated power higher than maximum excess peak in both scenarios
Feasible to operate the chillers even with lower efficiency rates
ZNE goal unattainable unless net-metering restriction is lifted
Future works recommendations
Analyze chillers energy efficiency when shifting the operation from night to day
Reduce the base load through energy efficiency measures
Consider second-hand batteries