Technical Datasheet
Customer:Project:Project 1Office:User:mabo
BALTIMORE AIRCOILS2Q V3.4.3
BAC ref.:CCCT 12014-09-18
P 1/4quoteNr:
1 VXI 145-4
Main Accessories :
THERMAL DESIGN DATARequested capacity (overall/unitary)(@ 100% RPM)..................................... 993 / 993 kWMax. capacity (overall/unitary)(@ 100% RPM)............................................... 993 / 993 kWFluid type................................................................................................................ 35% EGFreezing point.............................................................................................................-20 CRequested fluid flow (overall/unitary)..............................................................37.5 / 37.5 l/sMax. fluid flow (overall/unitary)....................................................................... 37.5 / 37.5 l/sEntering wet bulb temp.............................................................................................22.0 CEntering dry bulb temp............................................................................................. 32.0 CProcess fluid inlet temperature.................................................................................35.0 CProcess fluid outlet temperature...............................................................................28.0 COperating mode............................................................................................................. WetPHYSICAL DATA (including accessories) - UNITARYOverall length........................................................................................................ 5965 mm Standard unit.................................................................................................... 5385 mm Pump 1............................................................................................................... 580 mmOverall width..........................................................................................................2397 mm Standard unit.................................................................................................... 2397 mmOverall height........................................................................................................ 4483 mm Standard unit.................................................................................................... 4483 mmShipping / operating weight........................................................................ 9260 / 14160 kg Standard unit......................................................................................... 9260 / 14160 kgHeaviest section...................................................................................................... 6690 kgMaterial option................................................................. BALTIBOND HYBRID COATINGOverflow diameter........................................................................................ (1x) ND 80 mmMake up diameter........................................................................................ (1x) ND 50 mmDrain diameter..............................................................................................(1x) ND 50 mmNumber of coils per unit......................................................................................................2Exact unit dimensions and weights may be influenced by accessories/optioncombinations.EVAPORATIVE COIL DATA - UNITARYEvaporative coil type..........................................................................................Bare / HDG
Evaporative coil arrangement..................................................................... Wet coil - 1passEvaporative coil inlet connections..................................................................... (2x) ND 100Evaporative coil outlet connections...................................................................(2x) ND 100Evaporative coil volume......................................................................................(2x) 995.0 lEvaporative coil surface.................................................................................. (2x) 185.0 mEvaporative coil dry weight............................................................................(2x) 2595.0 kgELECTRICAL DATA - UNITARYFan motor General Fan motor BHP (Net mechanical output power at motor shaft) ........... (1 x) 33.0 kW Fan motor oversized for Total ESP....................................................................................................... 0 Pa Accessories total external static pressure.................................................0 Pa Customer external static pressure............................................................ 0 Pa Dry operation allowed....................................................................................... No Fan motor voltage............................................................................................. 400 V Frequency......................................................................................................... 50 Hz Protection class...................................................................................................IP55 Mounting................................................................................................................ B3 Single speed Fan motor power................................................................................... (1 x) 37.0 kW Fan full load current (Nominal Voltage).................................... (1 x) 66.6 A ( 400 V ) Fan synchrone speed................................................................................1500 RPM Framesize.............................................................................................................225Spray pump motor power...................................................................................(1x) 4.0 kWSpray pump motor voltage..........................................................................................400 VFrequency................................................................................................................... 50 HzSpray pump full load current.......................................................................... (8.6 A ) 400 VSpray pump synchrone speed.............................................................................1500 RPMProtection classMountingFramesize.......................................................................................................................132* Note: For indicative cable sizing the "Fan Full Load Current" and the corresponding"Nominal Voltage" have to be used.AERODYNAMICAL DATA - UNITARYAir flow (100% RPM/100% RPM)................................................................36.6 / 36.6 m/s
Technical Datasheet
Customer:Project:Project 1Office:User:mabo
BALTIMORE AIRCOILS2Q V3.4.3
BAC ref.:CCCT 12014-09-18
P 2/4quoteNr:
Number of fans................................................................................................................... 3Fan type.............................................................................................................. CentrifugalApproximate Fan speed........................................................................................ 463 RPMHYDRAULICAL DATA - UNITARYTotal pressure drop(@37.5 / 37.5)............................................................... 71.0 / 71.0 kPa Standard unit...........................................................................................71.0 / 71.0 kPaSpray water flow................................................................................................ (1x) 38.5 l/sMaximum evaporation................................................................................ 0.451 / 0.451 l/sBleed (cycles of concentration 2.5).............................................................0.301 / 0.301 l/sMake-Up (cycles of concentration 2.5)....................................................... 0.751 / 0.751 l/sPan volume operating.................................................................................................1106 lPan volume overflow.................................................................................................. 2609 lPressure range mechanical make-up valve....................................................... 1 to 4,5 barAcoustical data (Standard unit no attenuation)100 % RPM (@ 15.0m).......................................................................................... 58 dB(A)Sound Power Level............................................................................................. 96.0 dB(A)All acoustical data as sound pressure levels at quietest side of unit at indicated distanceACCESSORIES - Motor accessories UNITARYPTC (only) (for fan motor)
ACCESSORIES - Winterisation package UNITARYPan heater package 2*4 kW (provides freeze protection to -18C ambient) 1 stage thermostat Protection class...................................................................................................IP54 Temperature range.................................................................................... -20..50 C Contacts...................................................................................................NO and NC Rating (@250VAC)............................................................................................. 10 A Pan heater 4 kW Rating (@400VAC).......................................................................................... 5.78 A Power................................................................................................................. 4 kW Low level cut out switch with integral stilling chamber Contacts......................................................................................................NO or NC Voltage......................................................................................................... 240 VAC Rating (@240VAC)............................................................................................... 1 A Index of protection..............................................................................................IP 65
note
Sound Rating
Customer:Project:Project 1Office:User:mabo
BALTIMORE AIRCOILS2Q V3.4.3
BAC ref.:CCCT 12014-09-18
P 3/4quoteNr:
Sound RatingHz Fan End(dB) Back(dB) End1(dB) End2(dB) Discharge(dB)63 66.0 60.0 65.0 65.0 62.0
125 66.0 62.0 62.0 62.0 65.0250 65.0 56.0 58.0 58.0 64.0500 63.0 56.0 60.0 60.0 63.0
1000 61.0 53.0 55.0 55.0 62.02000 58.0 49.0 50.0 50.0 59.04000 56.0 40.0 47.0 47.0 55.08000 49.0 40.0 40.0 40.0 52.0dB(A) 66.0 58.0 61.0 61.0 67.0
Input OptionsModel VXI 145-4Sound Attenuation no attenuationAdditional ESP (Pa) 0Fan Motor Size (kW) 1 x 37.0 kWApproximate Fan Speed 100.0 %Distance (m) 15.0
Total Sound Power LevelOctave Band (Hz) Total Sound Power Level
63 96.0125 96.0250 94.0500 93.0
1000 91.02000 87.04000 84.08000 79.0dB(A) 96.0
Octave band and A-weighted Sound Pressure Levels (SPL) in dB RE 0.0002 Microbar.Note: Sound data are free field data valid for unit installation without elevation, not taking into account any reflections. Octave band values are shown for indicative purposes only.
TSU-M
S 310 v14 EN
TSU-C/D
3 good reasons to opt for the new generation Baltibond hybrid coating
The effect of cycles of concentration on water and chemical consumption
Ice thermal storage products are used to build and store cooling in the form of ice during periods of reduced cooling demand. This way the mechanical refrigeration system needs not to be sized on peak load but on average conditions. Hence a smaller refrigeration system with much lower power requirements and a smaller refrigerant charge can be selected. Ice thermal storage products can either be of the internal or external melt type. For internal melt only glycol solutions can be used as secondary refrigerant. External melt ice storage products can use either direct refrigerant feed or glycol solutions.
Ice Thermal Storage Products
647 - 2676 kWh
AccessoriesFor increased Safety and Hygiene
Filtration System
External ladder and platform
Combined Inlet
Shields
Automatic Blow-down
Baltiguard Drive System
For easier Maintenance or lower Energy Consumption
Removable FillMotor
removaldavit
For reduced Sound Levels
VX Sound Attenuation
VL Sound Attenuation
S3000E and S1500E Sound Attenuation
Whisper Quiet fans
Save up to 33% water and chemicalsThe new generation Baltibond hybrid coating
1. Save money Increase the service life of your evaporative
cooling Reduce water consumption with higher cycles
of concentration Reduce chemical consumption with higher cycles
of concentration Experience an economical alternative to SST 304
Your BAC Representative :
325 - 5060 kWh
For more information :
Internal Ladder and Platform 2. Increase safetyThe smooth surface finish reduces the development of biofilm facilitates internal cleaning
3. Respect the environment Reduce chemical and water rejection Reduce water consumption with higher cycles of concentration
0,00
1,00
2,00
3,00
4,00
5,00
1 2 3 4 5
Galvanized Steel
New generationBaltibond hybrid coating
33%typicalsaving
Cycles ofconcentration
Rel
ativ
e w
ater
co
nsum
ptio
n
LOW ENVIRONMENTALIMPACT PRODUCTS
Critical spare parts kit
The performance of BAC open cooling towers is Eurovent certified.Open cooling towers are a proven and cost-effective method of cooling condenser water loops and industrial processes. In operation, the condenser water (or process water) flows directly over the heat transfer surface of the open cooling tower. As air is introduced into the tower, a fraction of this water is evaporated, cooling the remaining water. Open cooling towers provide evaporative cooling for many types of systems, and the specific application will largely determine which BAC cooling tower is best suited for a project. There are two main configurations of factory assembled open cooling towers: crossflow and counterflow. In crossflow cooling towers, the water flows vertically down the wet deck as the air flows horizontally across it. In counterflow cooling towers, the water flows vertically down the wet deck as the air flows vertically up it.
S3000E16 - 285 l/s
VT 0/17 - 455 l/s
Open Cooling Towers
Addition of product accessories can improve standard product features e.g. sound attenuation, plume abatement, maintenance, operational safety, corrosion protection. Contact your BAC representative for more information.
Closed Circuit Cooling Towers
Closed circuit cooling towers keep the process fluid clean and contaminant free in a closed loop. This creates two separate fluid circuits: an external circuit, in which spray water circulates over the coil and mixes with the outside air, and an internal circuit, in which the process fluid to be cooled circulates inside the coil. During operation, heat is transferred from the warm fluid in the coil to the spray water, and then to the atmosphere as a portion of the water evaporates.
BAC manufactures two types of closed circuit cooling towers: combined flow and counterflow.
Combined flow closed circuit cooling towers have both a heat exchange coil and wet deck surface for heat transfer; they utilize parallel flow of air and spray water over the coil, and crossflow of air and spray water flow through the wet deck surface.
VXI19 - 2615 kW
VFL70 - 575 kW
FXV-D1425 - 2290 kW
Evaporative CondensersIn an evaporative condenser, refrigerant vapour is condensed in a coil, which is continually wetted on the outside by a recirculating water system. Air is circulated over the coil, causing a small portion of the recirculating water to evaporate. The evaporation removes heat from the vapour in the coil, causing it to condense. Evaporative condensers provide lower condensing temperatures and compressor kilowatts savings up to 30% when compared with air cooled systems. BAC manufactures two types of evaporative condensers: combined flow and counterflow. Combined flow evaporative condensers have both a heat exchange coil and wet deck surface for heat transfer; they utilize parallel flow of air and spray water over the coil, and crossflow of air and spray water flow through the wet deck surface.
VCL180 - 1380 kW
VXC60 - 6920 kW
CXV-D2750 - 4025 kW
Water saving and hybrid products (HXI, HFL) are of the closed circuit type where the heat load to be rejected is transferred from the process fluid to be cooled to the ambient air through a heat exchange coil. The coil serves to isolate the process fluid from the outside air, keeping it clean and contamination free in a closed loop. The hybrid wet/dry products cool the liquid to be cooled by efficiently combining dry sensible air cooling with evaporative cooling. These products include two or more distinctive heat transfer surfaces or sections combined into one product optimising the use of the ambient dry and wet bulb temperature.
Water Saving ProductsHFL
170 - 1870 kW
HXI130 - 1275 kW
DFCH120 - 800 kW
Water Saving Condensers
The HXC hybrid condenser offers significant water savings versus traditional water-cooled and evaporative condensers. Thanks to the standard design features the HXC satisfies additional environmental concerns by minimising also energy consumption, refrigerant charge and plume. The TrilliumSeries condensers are dry condensers equipped with an adiabatic pre-cooler section. Before the air is drawn through the high density finned coil however, it is pre-cooled adiabatically as it passes through an evaporative pad where water is evaporated in the air.
HXC545 - 1895 kW
PFE235 - 1365 kW
PCE540 - 2710 kW
340 - 1560 kW
SP
220 - 1620 kW
DFCV-ADDry fluid coolers (DFC) cool the liquid in a closed circuit by means of sensible heat transfer from the high-density finned coil block to the air at ambient dry bulb temperature. The SpartiumCooler and TrilliumSeries coolers are dry coolers equipped with an adiabatic pre-cooler section. Before the air is drawn through the high density finned coil however, it is pre-cooled adiabatically as it passes through an evaporative pad where water is evaporated in the air.
DRY COOLERS
CLOSED CIRCUIT COOLING TOWERS
340 - 1030 kW
DCV-AD
FXVE155 - 1790 kW
CXVE440 - 2765 kW
DFCV220 - 1500 kW
Heat Transfer Products
Crossflow Counter flow
Combined flow
Indoor installation
Axialfan
Centrifugalfan
Low sound
Energy efficiency
Easy maintenance
Operational safety
Water saving
Open
cool
ing
tow
ers
S1500E S3000E PTE VTL-E VT 0/1
Clos
ed ci
rcui
t coo
ling
tow
ers
FXVE FXV-D PFE VFL VXI HXI HFL DFC Spartium Series Trillium Series
Refr
iger
ant C
onde
nser
s CXVE CXV-D PCE VCL VXC HXC Trillium Series
S1500E8 - 215 l/s
VTL-E3 - 130 l/s
BAC participates in the ECC programme for cooling towers. Check ongoing validity of certificate: www.eurovent-certification.com or www.certiflash.com
C A A A
C A A A
F A D D
A F D E
A F D E
C A A A E
C A A A E
F A D D D
A F D E D
A F D E D
C A B B C
A B B CA
A A AD D
A AD BC
A AD BC
C A A A E
C A A A E
F A D D D
A F D E D
A F D E D
C A CB B
AC B
BestG A
D A
PTE12 - 170 l/s
TSU-M
S 310 v14 EN
TSU-C/D
3 good reasons to opt for the new generation Baltibond hybrid coating
The effect of cycles of concentration on water and chemical consumption
Ice thermal storage products are used to build and store cooling in the form of ice during periods of reduced cooling demand. This way the mechanical refrigeration system needs not to be sized on peak load but on average conditions. Hence a smaller refrigeration system with much lower power requirements and a smaller refrigerant charge can be selected. Ice thermal storage products can either be of the internal or external melt type. For internal melt only glycol solutions can be used as secondary refrigerant. External melt ice storage products can use either direct refrigerant feed or glycol solutions.
Ice Thermal Storage Products
647 - 2676 kWh
AccessoriesFor increased Safety and Hygiene
Filtration System
External ladder and platform
Combined Inlet
Shields
Automatic Blow-down
Baltiguard Drive System
For easier Maintenance or lower Energy Consumption
Removable FillMotor
removaldavit
For reduced Sound Levels
VX Sound Attenuation
VL Sound Attenuation
S3000E and S1500E Sound Attenuation
Whisper Quiet fans
Save up to 33% water and chemicalsThe new generation Baltibond hybrid coating
1. Save money Increase the service life of your evaporative
cooling Reduce water consumption with higher cycles
of concentration Reduce chemical consumption with higher cycles
of concentration Experience an economical alternative to SST 304
Your BAC Representative :
325 - 5060 kWh
For more information :
Internal Ladder and Platform 2. Increase safetyThe smooth surface finish reduces the development of biofilm facilitates internal cleaning
3. Respect the environment Reduce chemical and water rejection Reduce water consumption with higher cycles of concentration
0,00
1,00
2,00
3,00
4,00
5,00
1 2 3 4 5
Galvanized Steel
New generationBaltibond hybrid coating
33%typicalsaving
Cycles ofconcentration
Rel
ativ
e w
ater
co
nsum
ptio
n
LOW ENVIRONMENTALIMPACT PRODUCTS
Critical spare parts kit
TSU-M
S 310 v14 EN
TSU-C/D
3 good reasons to opt for the new generation Baltibond hybrid coating
The effect of cycles of concentration on water and chemical consumption
Ice thermal storage products are used to build and store cooling in the form of ice during periods of reduced cooling demand. This way the mechanical refrigeration system needs not to be sized on peak load but on average conditions. Hence a smaller refrigeration system with much lower power requirements and a smaller refrigerant charge can be selected. Ice thermal storage products can either be of the internal or external melt type. For internal melt only glycol solutions can be used as secondary refrigerant. External melt ice storage products can use either direct refrigerant feed or glycol solutions.
Ice Thermal Storage Products
647 - 2676 kWh
AccessoriesFor increased Safety and Hygiene
Filtration System
External ladder and platform
Combined Inlet
Shields
Automatic Blow-down
Baltiguard Drive System
For easier Maintenance or lower Energy Consumption
Removable FillMotor
removaldavit
For reduced Sound Levels
VX Sound Attenuation
VL Sound Attenuation
S3000E and S1500E Sound Attenuation
Whisper Quiet fans
Save up to 33% water and chemicalsThe new generation Baltibond hybrid coating
1. Save money Increase the service life of your evaporative
cooling Reduce water consumption with higher cycles
of concentration Reduce chemical consumption with higher cycles
of concentration Experience an economical alternative to SST 304
Your BAC Representative :
325 - 5060 kWh
For more information :
Internal Ladder and Platform 2. Increase safetyThe smooth surface finish reduces the development of biofilm facilitates internal cleaning
3. Respect the environment Reduce chemical and water rejection Reduce water consumption with higher cycles of concentration
0,00
1,00
2,00
3,00
4,00
5,00
1 2 3 4 5
Galvanized Steel
New generationBaltibond hybrid coating
33%typicalsaving
Cycles ofconcentration
Rel
ativ
e w
ater
co
nsum
ptio
n
LOW ENVIRONMENTALIMPACT PRODUCTS
Critical spare parts kit
VXI
Closed circuit cooling towers
Construction details
1. Material options
Heavy-gauge hot-dip galvanized steel is used for external unit steel
panels and structural elements featuring Baltiplus Corrosion
Protection.
The unique Baltibond hybrid coating is an optional extra. A hybridpolymer coating for longer service life, applied pre-assembly to all hot-
dip galvanized steel components of the unit.
Optional stainless steel panels and structural elements of type 304or 316 for extreme applications.
Or the economical alternative: a water-contact stainless steel coldwater basin. Its key components and the basin itself are stainlesssteel. The rest is protected with the Baltibond hybrid coating.
2. Heat transfer mediaOur heat transfer media is a cooling coil. In comprehensive lab thermal performance tests, it showed proved thermal coolerperformance and offers you unrivalled system efficiency.
The coil is constructed of continuous length of prime surface steel, hot-
dip galvanized after fabrication. Designed for maximum 10 bar
operating pressure according to PED.
Try our optional extended surface coils with selected rows, finnedat 3 to 5 fins per inch and hot-dip galvanized after fabrication, for dry
operation during winter time.
Optional stainless steel coils are in type 304L or 316L.
This file has been generated from the BAC website on: 22-08-2014
For more up to date information, visit: https://www.baltimoreaircoil.eu/products/VXI-construction-details
3. Air movement systemWith motor-driven centrifugal fan and a V-belt drive. You can easilyremove the entire motor base for proper belt tensioning to ensure
constantly correct belt alignment. Together with the heavy duty fanshaft bearings this guarantees optimal operational efficiency. Single-and multi speed motors available.Centrifugal fan(s) are forward-curved and nearly noiseless.Overcome external static pressure! Use sound attenuators and duct
work etc. for air intake/discharge with no loss of thermal performance!
Our drift eliminators come in UV-resistant plastic, which will not rot,decay or decompose and their performance is tested and certified byEurovent. They are assembled in easily handled and removablesections, for optimal internal access.Steel eliminators, protected with the unique Baltibond hybrid coating,
for optimal corrosion protection, are also available for specific
applications.
4. Water distribution systemThese consist of:
A header and spray branches with wide non-clog plastic nozzles, secured by rubber grommets. You can easily remove, cleanand flush both nozzles and spray branches.
A cold water basin with:
- strainers which are easy to lift out and the anti-vortexing device alsohelps stop trapped air
- mechanical make up- circular access doorClose coupled, bronze fitted centrifugal spray pump with totallyenclosed fan cooled (TEFC) motor. Bleed line with metering valveinstalled from pump discharge to overflow.
Like to know more about the VXI construction details? Contact your local BAC representative.
Powered by TCPDF (www.tcpdf.org)
This file has been generated from the BAC website on: 22-08-2014
For more up to date information, visit: https://www.baltimoreaircoil.eu/products/VXI-construction-details
VXI
Closed circuit cooling towers
Key benefits
Reliable
Quiet
Compact
VXI characteristicsCounter flow, centrifugal fan, forced draft
Capacity rangeup to 2615 kW
Maximum entering fluid temperature82C
Typical applicationsSmall to medium HVAC and industrial applications
Tight enclosures and installations requiring a single air inlet
Indoor installations
Sound critical installations
High temperature industrial application
Dry operation in winter time
This file has been generated from the BAC website on: 07-07-2014
For more up to date information, visit: http://www.baltimoreaircoil.eu/products/VXI
Reliable operation guaranteedSince 1978, thousands globally installed, proving the VXI coolers reliabilityFans, motor and drive system (V-belt) are located in the dry air , preventing moisture and condensation. No external moving parts, helping it withstand the toughest weather.
Various corrosion-resistant materials, including the unique Baltibond hybrid coating for guaranteed longservice life.
Optional extended surface coil with steel fins for dry operation
Ideal for a quiet operationVXI closed circuit cooling towers include quiet internal centrifugal fans for minimal surrounding noise.Single-side air inlet, and a quieter tower rear for more noise-sensitive areas.Cut operation noise still further with factory-designed and tested sound attenuators.
More compactCompact design for confined spaces,Single-side air inlet lets you install next to solid walls,Units housable indoors thanks to centrifugal fans allowing intake or discharge ductwork.
Reduced shipping, rigging and installation costsVXI units are factory-assembled. We ship larger models in 2 sections to reduce the size and weight of the
heaviest section for easy on-site assembly with smaller cranesSingle fan side requiring fewer motor starters to install and wire.VXI offers high capacity and minimal operating weight. Save on steel supports, both underneath theequipment and in the building itself for rooftop installations.
VXI-C models can be container-shipped (in 10 containers). Fan enclosures shippable loose in thetower bottom section for easy on-site assembly.
Interested in the VXI cooling tower for cooling your process fluid? Contact your local BACrepresentative.
DownloadsM - VX (ES)
R - VX (EN)
Powered by TCPDF (www.tcpdf.org)
This file has been generated from the BAC website on: 07-07-2014
For more up to date information, visit: http://www.baltimoreaircoil.eu/products/VXI
VXI
Closed circuit cooling towers
Principle of operation
Warm process fluid (1) enters through a heat exchange coil (2) andgets water sprayed on by the spray system (3) at the top of the coolingtower. At the same time the centrifugal fan (4), located at the bottom ofthe unit, blows ambient air upwards (5) through the tower. Duringoperation, heat is transferred from the internal circuit coil to the water,
and then to the atmosphere as a portion of the water that evaporates.
The cooled down fluid then exits the unit (6). The tower sump (7) orbasin collects the remaining water. The spray water pump(8) recirculates the water up to the water spray system. The warmsaturated air (9) leaves the tower through the drift eliminators (10) ,which remove water droplets from the air.
You want to use the VXI cooling tower to cool your process fluid?Contact your local BAC representative for more information.