Doble Testing Potential Transformers ( PT’s ) Bob Sarni Doble Engineering Company Doble Engineering Company 85 Walnut Street, Watertown, MA 02472

TRNG-6 Potential Transformer

Embed Size (px)

Citation preview

Page 1: TRNG-6 Potential Transformer

Doble Testing

Potential Transformers ( PT’s )

Bob Sarni

Doble Engineering Company

Doble Engineering Company 85 Walnut Street, Watertown, MA 02472

Page 2: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 2

Potential Transformers (PTs)

H1

H0

Isurface

Secondary Windings

Not Shown

Cascade Type

Page 3: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 3

Potential Transformers (PTs)

H1

CH

CHX

CHY

X1

X2

X3

Y1

Y2

Y3

H0 Line To Ground PT

Page 4: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 4

X1X2

X3

Y1

Y2Y3

CH1 CH2

CHY

CHX

Potential Transformers (PTs)

H1 H2

Line To Line PT

Page 5: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 5

Recommended Test Voltage

Liquid-Filled Line-to-Line PTs Rated Below 15 kV Insulation Class

PT Voltage Rating Test Voltage (kV)

7.2 to 8.7 5.0

4.2 to 5.0 2.5

2.4 2.0

*For Units Rated 15 kV and Above, Perform Tests at 10 kV

Page 6: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 6

Liquid-Filled Line-to-Ground PTs

a) Perform Test At the Rated Voltage of the Neutral Bushing

b) Cross-Check Tests are Performed at 10 kV or at Rated Line-to-

Ground Voltage, Whichever is Lower

Recommended Test Voltage

Page 7: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 7

Dry-Type Line-to-Line PTs Rated Below 15 kV Insulation ClassPT Voltage Rating Test Voltage (kV)

Overall a. 2 kV

b. Line-to-Ground Voltage*

c. 10% to 25% Above Line-to-Ground

operating Voltage

Cross-Check a. 2 kV

b. Line-to-Ground Operating Voltage

Exciting Current a. Line-to-Ground Operating Voltage

Recommended Test Voltage

*Note: Power Factor Tip Up Test

Page 8: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 8

Recommended Test Voltage

Dry-Type Line-to-Ground PTs Rated Below 15 kV Insulation Class

•Perform Test at a Voltage Not to Exceed the Neutral Bushing

Rating as Outlined in Previous Section

•Cross-Checks are Performed at 10 kV or Rated Line-to-Ground

Voltage, Whichever is Lower

•For Units Rated Above 15 kV, Perform Tests at 2 and 10 kV to

Determine Tip-Up Value

Page 9: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 9

Test Procedure - Single Phase - P T

Test

No.

Test

Mode Energize Ground Guard UST Test Description

1 GST H1, H2 X1,Y1 - - Overall

2 GST H1 X1Y1 H2 - H1 Cross Check

3 GST H2 X1Y1 H1 - H2 Cross-Check

4 UST H1 X1Y1 - H2 Excitation H1 to H2

5 UST H2 X1Y1 - H1 Excitation H2 to H1

6 Supplementary Hot-Collar tests on the primary line-terminalbushings

Page 10: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 10

Test Procedure - Single Phase - P T

X1X2X3

Y1Y2Y3

CH1 CH2

CHY

CHX

Test #1 : GST Ground - No LV Lead Required

Measure: CH1+CHX+CHY+CH2

H1 H0HV Lead

Page 11: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 11

Test Procedure - Single Phase - P T

Test #2: GST-Guard (Cross-Check Test #1)

•Measure: CH1+ 1/2CHX + 1/2CHY

X1X2X3

Y1Y2Y3

H1 H0

CH1 CHX CH2

CHY

HV Lead LV Lead

Page 12: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 12

Test Procedure - Single Phase - P T

Test #3: GST-Guard (Cross-Check Test #2)

•Measure: CH2+ 1/2CHX + 1/2CHY

X1X2X3

Y1Y2Y3

H1 H0

CH1 CHX CH2

CHY

HV LeadLV Lead

Page 13: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 13

Test Procedure - Single Phase - P T

X1X2X3

Y1Y2Y3

H1 H0

CH1 CHX CH2

CHY

HV Lead LV Lead

Test #4: Ungrounded Specimen Test (UST)

Measure: Excitation Current

Page 14: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 14

Test Procedure - Single Phase - P T

X1X2X3

Y1Y2Y3

H1 H0

CH1 CHX CH2

CHY

HV LeadLV Lead

Test #5: Ungrounded Specimen Test (UST)

Measure: Excitation Current

Page 15: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 15

Supplementary Tests - Single-Phase P T

Test No.

Test Mode

Energize

Ground

Guard

UST

Test Description

6 UST H1, H2 Yn - Xn CHX

7 UST H1, H2 Xn - Yn CHY

8 GST H1 - H2, Xn, Yn

- Bushing H1

9 GST H2 - H1, Xn, Yn

- Bushing H2

Note: n designates any winding connection, 1, 2 or 3

Page 16: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 16

X1X2X3

Y1Y2Y3

CH1 CH2

CHY

CHX

Test #6 : UST

Measure: CHXH1 H0

HV Lead

LV Lead

Supplementary Tests - Single-Phase P T

Page 17: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 17

X1X2X3

Y1Y2

Y3

CH1 CH2

CHY

CHX

Test #7 : UST

Measure: CHYH1 H0

HV Lead

LV Lead

Supplementary Tests - Single-Phase P T

Page 18: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 18

Test Procedure - Single Phase - P T

X1X2X3

Y1Y2Y3

H1 H0

CH1 CHX CH2

CHY

HV Lead

LV Lead

Test #8: GST-Guard Red & Blue

Measure: CH1

LV Lead

Page 19: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 19

Test Procedure - Single Phase - P T

X1X2X3

Y1Y2Y3

H1 H0

CH1 CHX CH2

CHY

HV Lead

LV Lead

Test #9: GST-Guard Red & Blue

Measure: CH2

LV Lead

Page 20: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 20

Single Phase Internally Grounded PT

H1

CH

CHX

CHY

Neutral Shown Internally Grounded H0

X1

X2X3

Y1Y2Y3

Page 21: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 21

Test No. Mode Energize Ground Guard UST

1 UST H1 HO ---- X1,Y1

2 GST H1 HO X1,Y1 ----

Test No. 1: Measures Line-End Interwinding Insulation

Test No. 2: Measure Excitation Current

Single Phase Internally Grounded PT

Test Procedure

Page 22: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 22

Cascade Potential Transformers

H0

H1

Ground Lead

Page 23: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 23

Cascade Potential Transformers

•Test Preparation - Single Phase Line-to-Ground PT

•One Side Of Each Secondary Winding Grounded

•Remove Ground Link From Neutral

•Short Circuit H1(Line) to H0 (Neutral)

•Test No. 1 Only

NOTE: Test Voltage for Tests 1, 3, 4, 5 Limited by

Rating of Neutral Bushing (5 kV)

Page 24: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 24

Cascade Potential Transformers

Test #1: GST-Ground

H0

H1

Ground Lead

HV Cable

Test Voltage for Tests 1, 3, 4, 5 Limited by Rating of Neutral Bushing (5 kV)

Secondary Windings

Not Shown

Page 25: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 25

H1

Cascade Potential Transformers

H0

HV Cable

Ground Lead

Test #2: GST-Guard

Measure: Cross-Check #1

LV Lead

Secondary Windings

Not Shown

Page 26: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 26

Cascade Potential Transformers

Test #3: GST-Guard

Measure: Cross-Check #2

H0

HV CableGround Lead

H1

LV Lead

Test Voltage for Tests 1, 3, 4, 5 Limited by Rating of Neutral Bushing (5 kV)

Secondary Windings

Not Shown

Page 27: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 27

Cascade Potential Transformers

H0

HV Cable

Ground Lead

Test #4: UST

Measure: Excitation Current

Secondary Windings

Not Shown

Page 28: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 28

Cascade Potential Transformers

H0

HV CableGround Lead

H1

LV Lead

Test #5: UST

Measure: Excitation Current

Test Voltage for Tests 1, 3, 4, 5 Limited by Rating of Neutral Bushing (5 kV)

Secondary Windings

Not Shown

Page 29: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 29

Cascade Potential Transformers

Test No. Test Mode Energize Ground Floating Test

Description

1A GST H0 X1, X2, X3 H1 Overall

Y1, Y2, Y3

Tests 2 Through 5 - Same as

Conventional PT

Alternative Method for Performing the Overall Test*

*Note: No Short Circuit Used Between H1 & H0

Page 30: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 30

Cascade Potential Transformers

H0

HV CableGround Lead

H1

Test #1A: GST-Ground

Test Voltage for Tests 1, 3, 4, 5 Limited by Rating of Neutral Bushing (5 kV)

No Short Circuit on Primary Winding

Secondary Windings

Not Shown

Page 31: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 31

Use of Guard Collar on Cascade PT

H1

H0

Connect to Guard

Isurface

Secondary Windings

Not Shown

Page 32: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 32

Test Procedure-Single-Phase PT - DTA

Page 33: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 33

Analysis of Results: PTs

•Compare Overall Power Factor Test Values to

Previous Test Results

•Compare Overall Power Factor Values to Similar Units

(Doble Test-Data-Reference-Book)

•Compare Cross-Check Power Factors

•Most PTs Test Results are Similar

Page 34: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 34

Analysis of Results: PTs

PT #1

Test No. mA Watts %PF

1 (Overall) 2.540 0.104 0.41

2 (H1 Cross-check) 1.256 0.056 0.45

3 (H2 Cross-check) 1.248 0.046 0.37

Examples:

PT #2

Test No. mA Watts %PF

1 (Overall) 2.650 0.354 1.32

2 (H1 Cross-check) 1.356 0.313 2.31

3 (H2 Cross-check) 1.248 0.055 0.44

Page 35: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 35

What is Wrong With PT #2?

Analysis of Results: PTs

•Consider Performing Supplemental Tests to Locate

Cause of Problem

•Refer to Doble Test Equipment Instruction Manual

Page 36: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 36

Test No. mA Watts % Power Factor

1 (Overall) 3.040 0.152 0.50

2 (H1 Cross-Check) 0.278 0.0312 1.12

3 (H0 Cross-Check) 2.810 0.128 0.46

Typical Good Unit

Analysis of Results: PTs

Page 37: TRNG-6 Potential Transformer

Doble Testing Potential Transformers 37

Analysis of Results: PTs

Test No. mA Watts % Power Factor

1 (Overall) 3.080 0.181 0.58

2 (H1 Cross-Check) 0.311 0.0682 2.19

3 (H0 Cross-Check) 2.810 0.128 0.46

Questionable Unit