Transformer (Mumbai University)

  • Upload
    devn9

  • View
    218

  • Download
    0

Embed Size (px)

Citation preview

  • 8/13/2019 Transformer (Mumbai University)

    1/87

    8/14/2013 unit 4-Transformer

    Transformer

    The transformer is a static device, (the

    one which does not contain anyrotating or moving parts) which is usedto transfer electrical energy from oneac circuit to another ac circuit, with

    increase or decrease in voltage/currentbut without any change in frequency.

  • 8/13/2019 Transformer (Mumbai University)

    2/87

    8/14/2013 unit 4-Transformer

  • 8/13/2019 Transformer (Mumbai University)

    3/87

    8/14/2013 unit 4-Transformer

    Ac input Ac output

    I1, V1 I2, v2

    Transformer

  • 8/13/2019 Transformer (Mumbai University)

    4/87

    8/14/2013 unit 4-Transformer

    Application of a Transformer

  • 8/13/2019 Transformer (Mumbai University)

    5/87

    8/14/2013 unit 4-Transformer

    Transformer Symbol

    (Iron core)

    5

    Schematic symbol for transformer consists of twoinductor symbols, separated by lines indicating aferromagnetic core.

    The two inductor coils are easily distinguished in the symbol. Thepair of vertical lines represent an iron core common to bothinductors. While many transformers have ferromagnetic corematerials, there are some that do not, their constituent inductorsbeing magnetically linked together through the air.

  • 8/13/2019 Transformer (Mumbai University)

    6/87

    8/14/2013 unit 4-Transformer

    Laboratory transformer

    6

  • 8/13/2019 Transformer (Mumbai University)

    7/87

    8/14/2013 unit 4-Transformer

    Generator transformer

    7

  • 8/13/2019 Transformer (Mumbai University)

    8/87

    8/14/2013 unit 4-Transformer

    Substation transformer

    8

  • 8/13/2019 Transformer (Mumbai University)

    9/87

    8/14/2013 unit 4-Transformer

    3 Phase 3 wire transmission / 3 phase 4 wire utilization

  • 8/13/2019 Transformer (Mumbai University)

    10/87

    8/14/2013 unit 4-Transformer

    Transformer can be step up or stepdown transformer. The principle ofoperation is same.

    In step up the secondary coil consistsof large no of turns of insulated copper

    wires Low voltage high current ac

    high voltage low current

  • 8/13/2019 Transformer (Mumbai University)

    11/87

    8/14/2013 unit 4-Transformer

    AUTO-TRANSFORMER

    11

  • 8/13/2019 Transformer (Mumbai University)

    12/87

    8/14/2013 unit 4-Transformer

    ISOLATION TRANSFORMER

    12

    P i i ti

  • 8/13/2019 Transformer (Mumbai University)

    13/87

    8/14/2013 unit 4-Transformer

    Princip e o operation examEnergy is being transferred from the primary coil tothe secondary coil by means of a mutual magneticfields.

  • 8/13/2019 Transformer (Mumbai University)

    14/87

    8/14/2013 unit 4-Transformer

  • 8/13/2019 Transformer (Mumbai University)

    15/87

    8/14/2013 unit 4-Transformer

  • 8/13/2019 Transformer (Mumbai University)

    16/87

    8/14/2013 unit 4-Transformer

    Can D.C. Supply be used forTransformer?

    No The transformer works on the principle of mutual

    induction, for which current in one coil must changeuniformly. If d.c. supply is given, the current will notchange due to constant supply and transformer will

    not work. Practically winding resistance is very small. Ford.c., the inductive reactance XL is zero as d.c. has nofrequency. So total impedance of winding is very lowfor d.c. Thus winding will draw very high current ifd.c. supply is given to it. This may cause the burningof windings due to extra heat generated and may

    cause permanent damage to the transformer. There can be saturation of the core due to which

    transformer draws very large current from the supplywhen connected to d.c.

  • 8/13/2019 Transformer (Mumbai University)

    17/87

    8/14/2013 unit 4-Transformer

    Construction of transformer

  • 8/13/2019 Transformer (Mumbai University)

    18/87

    8/14/2013 unit 4-Transformer

    Construction contd.

    1) Magnetic circuit consisting of limbs(core), yokes and clamping structures(providing the flux path)

    2) Electric circuit consisting of primaryand secondary windings

    3) Dielectric circuit consisting ofinsulation in different forms and used

    at different places in the transformeri.e core to primary winding, primarywinding to secondary winding, etc)

  • 8/13/2019 Transformer (Mumbai University)

    19/87

    8/14/2013 unit 4-Transformer

    Types of Transformers

    Depending on construction:

    Core type ,Shell type

    Depending on transformation ratio: Step-up ,Step-down,Isolation

    &Auto-Xmer

    Depending on supply:

    Single phase & three phase

    19

  • 8/13/2019 Transformer (Mumbai University)

    20/87

    8/14/2013 unit 4-Transformer

    Core type and shell typetransformer

    http://en.wikipedia.org/wiki/File:Transformer_winding_formats.jpg
  • 8/13/2019 Transformer (Mumbai University)

    21/87

    8/14/2013 unit 4-Transformer

    Core Type Transformer

    21

  • 8/13/2019 Transformer (Mumbai University)

    22/87

    8/14/2013 unit 4-Transformer

    Shell Type Transformer

    22

  • 8/13/2019 Transformer (Mumbai University)

    23/87

    8/14/2013 unit 4-Transformer

    Core type transformer

  • 8/13/2019 Transformer (Mumbai University)

    24/87

    8/14/2013 unit 4-Transformer

    Core type transformer

    A single phase core type transformer consists ofa magnetic frame with two cores, upper yokeand bottom yoke. The primary and secondarycoils are split into two half turns of the primaryand half the secondary turns are placed on each

    core (limb) A 3-phase core type transformer consists of

    minimum 3 cores, each provided with theprimary and secondary coils of one phase.

    Circular coils (windings) are used in the coretype transformer, which indicate theoretically

    that a circular core should be used. It is very complicated to manufacture circular

    core as a result, the stepped core is generallyused.

  • 8/13/2019 Transformer (Mumbai University)

    25/87

    8/14/2013 unit 4-Transformer

    Shell type Transformer

  • 8/13/2019 Transformer (Mumbai University)

    26/87

    8/14/2013 unit 4-Transformer

    Shell type transformer

    It consists of magnetic frame with a central core(limb) and two side cores, completing the pathof magnetic flux.

    Primary and secondary coils (windings) are

    placed on the central core in a particular fashionas shown in figure. Such an arrangement formsa shell of iron around copper.

    The central leg flux is divided at the yokesection, half i.e. /2 towards each side leg.

    As the flux in the section of yoke and side coresis only half, the cross section of the yokes andside cores is approximately half the section ofthe central limb

  • 8/13/2019 Transformer (Mumbai University)

    27/87

    8/14/2013 unit 4-Transformer

    Comparison

    Core Type

    1. The windingsenclose the wholecore.

    2. Average length ofthe core is more.

    3. Magnetic flux hasonly one continuouspath.

    4. More suitable forHV transformers.

    5. Easy to repair.

    Shell Type

    1. The core enclosesthe windings.

    2. Average length ofthe core is less.

    3. Magnetic flux isdistributed into twoparts.

    4. More suitable for LVtransformers.

    5. Difficult to repair.

    27

  • 8/13/2019 Transformer (Mumbai University)

    28/87

    8/14/2013 unit 4-Transformer

    Ideal Transformer (exam)

    An Ideal transformer is an imaginary transformerstudied to understand the concept easily.

    Characteristics

    1) An ideal transformers core is highly permeable

    so that it requires very small magneto motiveforce (mmf) to set up the flux in the core.

    2) Its leakage flux is zero, that is the entire flux isconfined to the core and links with both thewindings

    3) The resistance of the primary and secondarywinding is negligible (zero).

    Therefore E1=V1 and E2= V2

  • 8/13/2019 Transformer (Mumbai University)

    29/87

    8/14/2013 unit 4-Transformer

    Characteristics of idealtransformer

    4) There are no losses due toresistance, hysteresis and eddycurrents.

    5) Efficiency of an ideal transformeris 100% as no losses takes place.

    6) Voltage regulation is 0 %. Thatmeans secondary voltage willremain constant irrespective ofthe load current.

  • 8/13/2019 Transformer (Mumbai University)

    30/87

    8/14/2013 unit 4-Transformer

    Practical Transformer

    A practical transformer possesses the

    following characteristics:

    1. There are Cu & Iron losses.2. There is leakage flux.

    3. Its windings contain ohmic

    resistance.

    30

  • 8/13/2019 Transformer (Mumbai University)

    31/87

    8/14/2013 unit 4-Transformer

    Comparison

    Practical Transformer

    1. There are Cu & ironlosses.

    2. There is leakage flux.

    3. Its windings containohmic resistance.

    4. Voltage regulation isnever 0%.

    5. Efficiency is 93-97 %.

    6. All constructedtransformers arepracticaltransformers.

    Ideal Transformer1. There is no loss.

    2. There is no leakageflux.

    3. Its windings consist of

    purely inductive coils,wound on a losslesscore.

    4. Voltage regulation is0%.

    5. Efficiency is 100%.6. It is impossible toconstruct an idealtransformer.

    31

  • 8/13/2019 Transformer (Mumbai University)

    32/87

    8/14/2013 unit 4-Transformer

    EMF equation of a transformer (e)

  • 8/13/2019 Transformer (Mumbai University)

    33/87

    8/14/2013 unit 4-Transformer

    EMF equation of a transformer

    The various quantities which affect themagnitude of the induced e.m.f. are :

    = Fluxm = Maximum value of flux

    N1 = Number of primary winding turnsN2 = Number of secondary winding turns

    f = Frequency of the supply voltageE1 = R.M.S. value of the primary induced

    e.m.f.E2 = R.M.S. value of the secondary induced

    e.m.f.

  • 8/13/2019 Transformer (Mumbai University)

    34/87

    8/14/2013 unit 4-Transformer

    refer notes

  • 8/13/2019 Transformer (Mumbai University)

    35/87

    8/14/2013 unit 4-Transformer

    Losses in transformer

    An ideal transformer has no loss.

    But in practical transformercopper losses (Pcu ) and ironlosses (Pi) takes place. Iron lossis further classified into two typesnamely hysteresis loss and eddy

    current loss.

  • 8/13/2019 Transformer (Mumbai University)

    36/87

    8/14/2013 unit 4-Transformer

    Copper Loss

    Copper losses occur in all those parts of atransformer that carry electric current.

    It is the total power loss taking place in the

    winding resistances of a transformer Copper Loss = Power loss in the primary

    resistance + Power loss in the secondaryresistance.

    Cu loss can be calculated by conducting

    SC test on the transformer.

    36

  • 8/13/2019 Transformer (Mumbai University)

    37/87

    8/14/2013 unit 4-Transformer

    Copper Loss

    Should be kept as low as possible toincrease efficiency.

    To reduce this reduce R1 & R2.

    Also called as variable loss-dependenton square of load current.

    37

  • 8/13/2019 Transformer (Mumbai University)

    38/87

    8/14/2013 unit 4-Transformer

    Iron Losses (or Core Losses)

    Hysteresis loss occurs in the magneticframe of the transformer.

    Due to time varying flux, there isinduced emf in the core which causeseddy currents to flow through the corebody.

    Iron loss can be calculated byconducting OC test on transformer.

    38

  • 8/13/2019 Transformer (Mumbai University)

    39/87

    8/14/2013 unit 4-Transformer

    Losses in a Transformer

    Hysteresis loss depends on area of hysteresis loopof magnetic material used for frame, volume ofcore, frequency of magnetic flux reversal. Thisloss can be minimized by selecting a material forthe core that has a low hysteresis coefficient(silicon steel)

    Eddy current loss depends on thickness of lamination of core, frequency of flux reversal,maximum value of flux density in core, volume ofcore, quality of magnetic material used for themagnetic frame. This loss can be minimized byusing laminated core.

    39

  • 8/13/2019 Transformer (Mumbai University)

    40/87

    8/14/2013 unit 4-Transformer

    Ideal Transformer(no load)

    40

  • 8/13/2019 Transformer (Mumbai University)

    41/87

    8/14/2013 unit 4-Transformer

    Conditions for an ideal or loss freetransformer

    The primary and secondary windingsdo not have any resistance i.e.winding resistance of primary and

    secondary should be zero.

    The losses taking place in the corei.e. hysteresis loss and eddy current

    loss should be zero. There should not be any leakage flux

  • 8/13/2019 Transformer (Mumbai University)

    42/87

    8/14/2013 unit 4-Transformer

    Phasor Diagram

    42

  • 8/13/2019 Transformer (Mumbai University)

    43/87

    8/14/2013 unit 4-Transformer

    Ideal transformer on load

    Refer notes

    Practical transformer on no load

    Refer notes

  • 8/13/2019 Transformer (Mumbai University)

    44/87

    8/14/2013 unit 4-Transformer

    Ideal transformer on load

    When some load is connected between thesecondary terminals of the transformer, thetransformer is said to be loaded or on load.

    Due to load on the secondary , a finitesecondary current starts flowing.

    If the load is R+L type the I2 will lagbehind V2 by an angle 2.

    As per the lenzs law, the secondary currentI2 will oppose the cause producing it.Hence it opposes the magnetic flux. This iscalled demagnetizing effect of I2

  • 8/13/2019 Transformer (Mumbai University)

    45/87

    8/14/2013 unit 4-Transformer

    Ideal transformer on load

    I2 = I2 * N2/N1 =kI2 I2 = kI2 is 180 degree out of phase

    with I2.

    The net primary current is 1 =2 + mag Thus due to load on secondary side,

    the primary current of thetransformer increases to supply theadditional power to the load

  • 8/13/2019 Transformer (Mumbai University)

    46/87

    8/14/2013 unit 4-Transformer

    Practical transformer on NO load

    When the practical transformer is onNo load, the secondary current will bezero. Hence the copper loss in the

    secondary winding is zero. However a small primary current does

    flow under the no load condition. Dueto small primary resistance, a small

    primary copper loss takes place evenat no load

  • 8/13/2019 Transformer (Mumbai University)

    47/87

    8/14/2013 unit 4-Transformer

    Practical transformer on NO load

    The primary current under no loadcondition has to supply the ironlosses and a small primary copper

    loss. The primary current under the no

    load condition is denoted by o. o =m +c m is the magnetizing component c is the active component

  • 8/13/2019 Transformer (Mumbai University)

    48/87

    8/14/2013 unit 4-Transformer

    Practical transformer no No load

    Im is the purely reactive component.

    It magnetizes the core and producesflux in the core.

    This component is at 90 degree w.r.tto E1.

    Im is also called as wattlesscomponent.

  • 8/13/2019 Transformer (Mumbai University)

    49/87

    8/14/2013 unit 4-Transformer

    Practical transformer no No load

    Ic is the active component of no loadcurrent Io.

    Its job is to supply the total loss

    under no load conditions. It is therefore called as the power

    component or core less component ofIo.

    It is at 90 degree w.r.t themagnetizing current Im.

  • 8/13/2019 Transformer (Mumbai University)

    50/87

    8/14/2013 unit 4-Transformer

    Practical Transformer(no load)

    50

  • 8/13/2019 Transformer (Mumbai University)

    51/87

    8/14/2013 unit 4-Transformer

    o =m +c Im and Ic are 90degree phase shifted

    w.r.t each other and Io is the resultantof the two.

    No laod power factor = coso

    Im = Io sino

    Ic= Io coso

    Io=Im2 + Ic2 o = tan-1(Im/Ic)

  • 8/13/2019 Transformer (Mumbai University)

    52/87

    8/14/2013 unit 4-Transformer

    Total input power on No load

    Wo = V1 Io coso

    Io coso =Ic

    Wo= V1 Ic primary current Io is very small therefore

    primary copper loss is very very small. Icis called as core loss or iron losscomponent.

    Wo represents the core loss or iron loss ascopper is small.

    Wo- iron loss= V1 Ic

  • 8/13/2019 Transformer (Mumbai University)

    53/87

    8/14/2013 unit 4-Transformer

    Practical Transformer(on load)-w/o resistance and leakage

    53

  • 8/13/2019 Transformer (Mumbai University)

    54/87

    8/14/2013 unit 4-Transformer

    Practical transformer on load

    When some load is connected between thesecondary terminals of the transformer, itis said to be on load.

    Due to the load on secondary, a finitesecondary current starts flowing.Depending on the type of load (resistive,inductive , capacitive) the secondary

    current I2 will be in phase, or lag or leadthe load voltage V2.

  • 8/13/2019 Transformer (Mumbai University)

    55/87

    8/14/2013 unit 4-Transformer

    Due to loading of the transformer, the primary currentincreases above its no load value due to the followingfactors:

    1) when the transformer is loaded, the load current I2 willstart flowing. Due to increase in load current I2 thesecondary ampere turns N2I2 will also increase.

    2)This increased secondary (mmf) N2I2 will increase theflux 2 set up by the secondary current.

    3) This flux opposes the main flux 1 set up in the core bythe current flowing through the primary winding. Hence thesecondary mmf N2 I2 is called as the demagnetizingampere turns.

    Due to reduction in the main flux 1, the induced emf in theprimary winding E1 will also reduce. Hence the differencebetween Vi and E1 will increase and the primary current willincrease.

  • 8/13/2019 Transformer (Mumbai University)

    56/87

    8/14/2013 unit 4-Transformer

    Effect of additional primary current

    The additional current drawn by the primary windingdue to the loading is called as the load component I2

    I2 is 180 degree out of phase with load current I2.The current I2 develop its own magnetic flux 2.

    2 is in opposite direction to that of 2. Hence it helps the main flux 1.

    1 and 2 are in the same direction Thus the reduction in the main flux due to 2 is

    compensated by 2 and the core flux 1 will almost

    remain constant. Therefore for any load between no load to full load,

    the core flux will always remain constant.

  • 8/13/2019 Transformer (Mumbai University)

    57/87

    8/14/2013 unit 4-Transformer

    Phasor Diagram

    57

  • 8/13/2019 Transformer (Mumbai University)

    58/87

    8/14/2013 unit 4-Transformer

    Effect of leakage reactance

    http://en.wikipedia.org/wiki/File:Transformer_flux.gif
  • 8/13/2019 Transformer (Mumbai University)

    59/87

    8/14/2013 unit 4-Transformer

    notes

    P ti l T f ( l d)

  • 8/13/2019 Transformer (Mumbai University)

    60/87

    8/14/2013 unit 4-Transformer

    Practical Transformer(on load)-with resistance and leakage

    60

    Ph di f it

  • 8/13/2019 Transformer (Mumbai University)

    61/87

    8/14/2013 unit 4-Transformer

    Phasor diagram for unitypower factor load

    61

    Ph di f l i

  • 8/13/2019 Transformer (Mumbai University)

    62/87

    8/14/2013 unit 4-Transformer

    Phasor diagram for laggingpower factor

    62

    Ph di f l di

  • 8/13/2019 Transformer (Mumbai University)

    63/87

    8/14/2013 unit 4-Transformer

    Phasor diagram for leadingpower factor

    63

    T f P t

  • 8/13/2019 Transformer (Mumbai University)

    64/87

    8/14/2013 unit 4-Transformer

    Transformer Parameters1. Effect OF Winding Resistances

    High voltage side Low current side High resistancesideLow voltage side High current side Low resistanceside

    Sejal Chopra,DBIT,Kurla 64

  • 8/13/2019 Transformer (Mumbai University)

    65/87

    8/14/2013 unit 4-Transformer

    Equivalent Impedance

    65

    i l d

  • 8/13/2019 Transformer (Mumbai University)

    66/87

    8/14/2013 unit 4-Transformer

    Equivalent Impedance

    66

  • 8/13/2019 Transformer (Mumbai University)

    67/87

    8/14/2013 unit 4-Transformer

    Rules for Transferring Parameters and Quantities

    Sejal Chopra,DBIT,Kurla 67

  • 8/13/2019 Transformer (Mumbai University)

    68/87

    8/14/2013 unit 4-Transformer

    Rules for Transferring Parameters andQuantities

    Sejal Chopra,DBIT,Kurla 68

  • 8/13/2019 Transformer (Mumbai University)

    69/87

    8/14/2013 unit 4-Transformer

    Rules for Transferring Parameters andQuantities

    69

    Equivalent circuit of

  • 8/13/2019 Transformer (Mumbai University)

    70/87

    8/14/2013 unit 4-Transformer

    qTransformer

    70

    No load equivalent circuit

    Equivalent circuit of

  • 8/13/2019 Transformer (Mumbai University)

    71/87

    8/14/2013 unit 4-Transformer

    qTransformer

    71

    Exact equivalent circuit

  • 8/13/2019 Transformer (Mumbai University)

    72/87

    8/14/2013 unit 4-Transformer

    Exact equivalent circuitreferred to primary

    72

    R2'= R2/K2 , X2' = X2/K

    2' , Z2' = Z2/K2

    While E2' = E2/K' I2' = K I2Where K = N2 /N1

    Exact equivalent circuit

  • 8/13/2019 Transformer (Mumbai University)

    73/87

    8/14/2013 unit 4-Transformer

    Exact equivalent circuitreferred to secondary

    73

    R1' = K2 R1 , X1' = K

    2 X1, Z1' = K2 Z1

    E1'= K E1, Io' = I1 /K' Io' = Io /K

  • 8/13/2019 Transformer (Mumbai University)

    74/87

    8/14/2013 unit 4-Transformer

    Calculation of Regulation

    74

  • 8/13/2019 Transformer (Mumbai University)

    75/87

    8/14/2013 unit 4-Transformer

    Efficiency of a Transformer Power output = Power input Total

    losses

    Power input = Power output + Totallosses

    Power input = Power output + Pi + Pcu = Power output/power input

    = Power output/(power output + Pi +Pcu )

    Now power output = V2 I2 cos

    where cos = Load power factor75

  • 8/13/2019 Transformer (Mumbai University)

    76/87

    8/14/2013 unit 4-Transformer

    Efficiency of a Transformer

    Sejal Chopra,DBIT,Kurla 76

    This is full load percentage efficiency with,

    I2 = Full load secondary current

  • 8/13/2019 Transformer (Mumbai University)

    77/87

    8/14/2013 unit 4-Transformer

    Efficiency of a Transformer

    Let n =Fraction by which load is lessthan full load = Actual load/Full load

    when load changes, the load current

    changes by same proportion. new I2= n (I2) F.L.Similarly the output V2 I2 cos2 also

    reduces by the same fraction. new Pcu = n

    2 (Pcu ) F.L.

    77

  • 8/13/2019 Transformer (Mumbai University)

    78/87

    8/14/2013 unit 4-Transformer

    Efficiency of a Transformer

    78

    Condition for Maximum

  • 8/13/2019 Transformer (Mumbai University)

    79/87

    8/14/2013 unit 4-Transformer

    Condition for MaximumEfficiency

    79

    Condition for Maximum

  • 8/13/2019 Transformer (Mumbai University)

    80/87

    8/14/2013 unit 4-Transformer

    Condition for MaximumEfficiency

    for maximum efficiency,

    d /d I2 = 0

    Now = (V2I2cos

    2)/(V

    2I2cos

    2+ Pi + I22 R2e)

    80

    Condition for Maximum

  • 8/13/2019 Transformer (Mumbai University)

    81/87

    8/14/2013 unit 4-Transformer

    Condition for MaximumEfficiency

    81

    Condition for Maximum

  • 8/13/2019 Transformer (Mumbai University)

    82/87

    8/14/2013 unit 4-Transformer

    Condition for MaximumEfficiency

    (V2 I2 cos 2 + Pi + I22 R2e)(V2 cos 2)- (V2 I2 cos 2)(V2 cos 2 + 2I2 R2e) =0

    Cancelling (V2 cos 2) from both theterms we get,

    V2 I2 cos 2 + Pi +I22 R2e - V2 I2 2 - 2I22

    R2e = 0... Pi - I2

    2 R2e= 0

    ... Pi = I22 R2e = Pcu

    82

    Load Current I2m at Maximum Efficiency

  • 8/13/2019 Transformer (Mumbai University)

    83/87

    8/14/2013 unit 4-Transformer

    For max, I22 R2e = Pi but I2 = I2mI2m

    2 R2e = PiI2m = (Pi/ R2e)

    This is the load current at max,

    Let (I2)F.L. = Full load current

    ... I2m/(I2) F.L.= (1/(I2) F.L.)(Pi/ R2e)

    ... I2m/(I2) F.L.= (Pi )/({(I2) F.L.}2

    R2e)

    = (Pi )/((Pcu) F.L.)

    ... I2m = (I2 )F.L.(Pi )/((Pcu) F.L.)

    \ This is the load current at max intermsof full load current.

    83

  • 8/13/2019 Transformer (Mumbai University)

    84/87

    8/14/2013 unit 4-Transformer

    KVA supplied at maximum Efficiency

    For constant V2 the KVA supplied isthe function of.

    KVA at max = I2m V2= V2 (I2) F.L. x

    (Pi)/((Pcu)F.L.)KVA at max = (KVA rating) x (Pi)

    /((Pcu)F.L.)

    84

    KVA supplied at maximum

  • 8/13/2019 Transformer (Mumbai University)

    85/87

    8/14/2013 unit 4-Transformer

    KVA supplied at maximumEfficiency

    85

  • 8/13/2019 Transformer (Mumbai University)

    86/87

    8/14/2013 unit 4-Transformer

    Open Circuit Test (O.C. Test)

    86

  • 8/13/2019 Transformer (Mumbai University)

    87/87

    Short Circuit Test (S.C. Test)