XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace UPFLOW *UH-A9V-V UPFLOW/HORIZONTAL *DH-A9V-V DOWNFLOW DOWNFLOW/HORIZONTAL Direct Vent with Variable Speed Blower Variable Speed Inducer TDH2B060A9V3VB TDH2B080A9V3VB TDH2B080A9V4VB TDH2C100A9V4VB TDH2D120A9V5VB

Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

  • Upload
    lamngoc

  • View
    251

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

XV 95TUH2B060A9V3VBTUH2B080A9V3VBTUH2B080A9V4VBTUH2C100A9V4VB TUH2C100A9V5VBTUH2D120A9V5VB

PUB. NO. 22-1814-11

Upflow/ Horizontal Left,Downflow/ Horizontal Right Variable SpeedTwo Stage CondensingGas-Fired Furnace

UPFLOW

*UH-A9V-V

UPFLOW/HORIZONTAL

*DH-A9V-V

DOWNFLOW

DOWNFLOW/HORIZONTAL

Direct Vent withVariable Speed BlowerVariable Speed Inducer

TDH2B060A9V3VBTDH2B080A9V3VBTDH2B080A9V4VBTDH2C100A9V4VBTDH2D120A9V5VB

Page 2: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

2 Pub. No. 22-1814-11

GeneralFeatures

© 2013 Trane All Rights Reserved

NATURAL GAS MODELSCentral Heating furnace designs are certified by the American Gas Associa-tion for both natural and L.P. gas. Limit setting and rating data were established and approved under standard rating conditions using American National Standards Institute standards.

SAFE OPERATIONThe Integrated System Control has solid state devices, which continuously monitor for presence of flame, when the system is in the heating mode of operation. Dual solenoid combination gas valve and regulator provide addi-tional safety.

QUICK HEATINGDurable, cycle tested, heavy gauge aluminized steel heat exchanger quickly transfers heat to provide warm conditioned air to the structure. Low energy power vent blower, to in-crease efficiency and provide a positive discharge of gas fumes to the outside.

BURNERSMultiport Inshot burners will give years of quiet and efficient service. All models can be converted to L.P. gas without changing burners.

INTEGRATED SYSTEM CONTROLExclusively designed operational pro-gram provides total control of furnace limit sensors, blowers, gas valve, flame control and includes self diagnostics for ease of service. Also contains con-nection points for E.A.C./Humidifier.

ENERGY EFFICIENT OPERATIONFurnace is certified to leak 2% or less of nominal air conditioning CFM delivered when pressurized to .5” water column with all inlets, outlets, and drains sealed.

AIR DELIVERYThe variable speed blower motor has sufficient airflow for most heating and cooling requirements and will switch from heating to cooling speeds on demand from room thermostat. The blower door safety switch will prevent or terminate furnace operation when the blower door is removed.

SECONDARY HEAT EXCHANGERThe XV95 has a special type 29-4C™ stainless steel secondary heat exchanger to reclaim heat from flue gases which would normally be lost instead.

STYLINGHeavy gauge steel and “wrap-around” cabinet construction is used in the cabinet with baked-on enamel finish for strength and beauty. The heat exchanger section of the cabinet is completely lined with foil faced fiberglass insulation. This results in quiet and efficient operation due to the excellent acoustical and insulating qualities of fiberglass. Built-in bottom pan and alternate bottom, left or right side return air connection provision.

FEATURES AND GENERAL OPERATIONThe XV95 High Efficiency Gas Fur-naces utilize an Adaptive Heat Up Silicon Nitride Hot Surface Ignition system, which eliminates the waste of a constant burning pilot. The integrated system control lights the main burners upon a demand for heat from the room thermostat. Complete front service ac-cess.

a. Low energy power venter b. Vent proving pressure switch.

Page 3: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

3Pub. No. 22-1814-11

Contents

General Features 2 Features and Benefits 4 Standard Equipment 4 Optional Equipment 5 General Data 6-8 TUH2B060A9V3VBTUH2B080A9V3VBTUH2B080A9V4VBTUH2C100A9V4VBTUH2C100A9V5VBTUH2D120A9V5VBTDH2B060A9V3VBTDH2B080A9V3VBTDH2B080A9V4VBTDH2C100A9V4VBTDH2D120A9V5VB

Performance Data 9-19 Venting Table 20 Electrical Data 21-24 Field Wiring 25-26 Dimensions 27-28

Page 4: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

4 Pub. No. 22-1814-11

XV 95 STANDARD EQUIPMENT

Featuresand Benefits

• Lite Port™ extended system diag-nostics

• Stored fault code history in micro pro-cessor nonvocatile memory

• Cleanable high velocity filters (upflow only)

• Hinged blower door *

• Perfect fit door latches*

• Insulated blower door*

• Gasketed blower door*• Complete front service access• Left/right gas connection• Adjustable fan off times• Optional L.P conversion kit• Selectable cooling fan off delay

eliminates need for BAY24X045 time delay kit

• Variable Speed Blower Motor • Silicon Nitride Igniter with adaptive

heat up• Variable speed induced draft blower• Direct/Non-Direct vent option• Fused 24 volt control circuit• Manual reset burner safety switches• Power supply 115/1/60• Convertible to horizontal on left side• 2-stage gas valve• PVC venting-1 or 2 pipe option• Accessory hook-up capability• Integrated solid state control with self-

diagnostics• Attractive color accents • Heavy gauge aluminized steel heat

exchanger• Multi-port In-shot burners• Quiet induced draft blower

* (Upflow only)

Page 5: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

5Pub. No. 22-1814-11

Featuresand Benefits

XV 95 OPTIONAL EQUIPMENT

Thermostat, 2-Stage Heat / 1-Stage Cooling ........................................................................................................... TAYSTAT241 [ ]Thermostat, Media Programmable 2-Stage Heating ..............................................................................................TAYSTAT302C [ ]Thermostat, Mechanical Heating Only With Fan Switch .........................................................................................TAYSTAT303C [ ]Thermostat, Heating/Cooling Single Stage (Mounts Horizontally) ..............................................................................AY28X092 [ ]Thermostat, Heating/Cooling Single Stage (Mounts Vertically) ................................................................................BAYSTAT305 [ ]Thermostat, Media Programmable 1-Stage Heating/1-Stage Cooling ...................................................................TAYSTAT300C [ ]Propane Conversion Kit ........................................................................................................................................ BAYLPKT210A [ ]Media Air Filter, “Perfect Fit” High Efficiency (14-1/2" Wide Gas Furnace) ........................................................... TFM145A9FR0 [ ]Media Air Filter, “Perfect Fit” High Efficiency (17-1/2" Wide Gas Furnace) ........................................................... TFM175A9FR0 [ ]Media Air Filter, “Perfect Fit” High Efficiency (21" Wide Gas Furnace) ................................................................. TFM210A9FR0 [ ]Media Air Filter, “Perfect Fit” High Efficiency (24-1/2" Wide Gas Furnace) ........................................................... TFM245A9FR0 [ ] Media Air Filter, “Perfect Fit” Standard Efficiency (14-1/2" Wide Gas Furnace) ....................................................TFP145A9FR0 [ ]Media Air Filter, “Perfect Fit” Standard Efficiency (17-1/2" Wide Gas Furnace) ....................................................TFP175A9FR0 [ ]Media Air Filter, “Perfect Fit” Standard Efficiency (21" Wide Gas Furnace) ...........................................................TFP210A9FR0 [ ]Media Air Filter, “Perfect Fit” Standard Efficiency (24-1/2" Wide Gas Furnace) ....................................................TFP245A9FR0 [ ]Coil Enclosure (14-1/2" Wide Cabinets) ......................................................................................................... BAYCLE14A1422A [ ]Coil Enclosure (17-1/2" Wide Cabinets) ....................................................................................................... BAYCLE17A1722A [ ]Coil Enclosure (21" Wide Cabinets) .............................................................................................................. BAYCLE21A2130A [ ]Coil Enclosure (24-1/2" Wide Cabinets) ....................................................................................................... BAYCLE24A2430A [ ]Downflow Subbase ................................................................................................................................................. BAYBASE205 [ ]Side Filter Rack ....................................................................................................................................................... BAYFLTR200 [ ]Filter Kit/Horizontal Conversion TUH2-060,080 ....................................................................................................... BAYFLTR203 [ ]Filter Kit/Horizontal Conversion TUH2-100 .............................................................................................................. BAYFLTR204 [ ]Filter Kit/Horizontal Conversion TUH2-120 .............................................................................................................. BAYFLTR205 [ ]High Altitude Pressure Switch Kit TUH2-060 ............................................................................................ BAYSWT10AHALTA1 [ ]High Altitude Pressure Switch Kit TUH2-080,100,120 .............................................................................. BAYSWT08AHALTA1 [ ]Concentric Vent Kit TUH2 Furnaces ...............................................................................................................BAYAIR30AVENTA [ ]Sidewall Vent Termination Kit All 2 Pipe Direct Vent Furnaces ............................................................................BAYVENT200B [ ]Manufactured/Mobile Home Kit All 2 Pipe Direct Vent Furnaces ........................................................................BAYMFGH100A [ ]Cleanable Filter (14.5"/17.5" wide Upflow models) .................................................................................................. BAYFLTR317 [ ]Cleanable Filter (21" wide Upflow models) .............................................................................................................. BAYFLTR321 [ ]Cleanable Filter (24.5" wide Upflow models) ........................................................................................................... BAYFLTR324 [ ]CleanEffects™, Whole House Air Cleaner (Upflow 14-1/2" Wide Gas Furnace) ........................................... TFD145ALFR000B [ ]CleanEffects™, Whole House Air Cleaner (Upflow 17-1/2" Wide Gas Furnace) ...........................................TFD175ALFR000B [ ] CleanEffects™, Whole House Air Cleaner (Upflow 21" Wide Gas Furnace) ..................................................TFD210ALFR000B [ ] CleanEffects™, Whole House Air Cleaner (Upflow 24-1/2" Wide Gas Furnace) ...........................................TFD245ALFR000B [ ] CleanEffects™, Whole House Air Cleaner (Downflow 14-1/2" Wide Gas Furnace) ...................................... TFD14DALFR000B [ ] CleanEffects™, Whole House Air Cleaner (Downflow 17-1/2" Wide Gas Furnace) ...................................... TFD17DALFR000B [ ] CleanEffects™, Whole House Air Cleaner (Downflow 21" Wide Gas Furnace) ............................................ TFD21DALFR000B [ ] CleanEffects™, Whole House Air Cleaner (Downflow 24-1/2" Wide Gas Furnace) ...................................... TFD24DALFR000B [ ] CleanEffects™, Whole House Transformer Kit (120 to 24 Volt - all TFD Air Cleaners) ..................................... BAYTRANS12024 [ ]

1 Optional kit allows 200 ft. max. vent length from 5,000-12,000 feet above sea level. See installer's guide.

Page 6: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

6 Pub. No. 22-1814-11

GeneralData

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.32 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian

applicaitons, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Energy Star

TUH2 PRODUCT SPECIFICATIONS1

Product Specifications 1

MODELTYPERATINGS 21st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzFLACOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)HEAT EXCHANGERType -Fired -UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs)

TUH2B080A9V3VB 5Upflow / Horizontal

52,00050,44080,00077,600

9735 - 65

DIRECT10 x 8

1Variable

See Fan Performance Table1/2

Variable115/1/60

7.7Centrifugal

Direct - Variable1/50 - 5000

33 - 110/3/60 - 1801.0Yes

High Velocity1 - 17x25 - 1 in.

2 Round

Aluminized Steel - Type I

20

4 — 454 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

4115/1/60

10.8151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

168 / 156

TUH2B060A9V3VB 5Upflow / Horizontal

39,00037,83060,00058,200

9735 - 65

DIRECT10 x 8

1Variable

See Fan Performance Table1/2

Variable115/1/60

7.7Centrifugal

Direct - Variable1/50 - 5000

33 - 110/3/60 - 1801.0Yes

High Velocity1 - 17x25 - 1 in.

2 Round

Aluminized Steel - Type I

20

3 — 453 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

3115/1/60

10.8151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

158 / 146

TUH2C100A9V4VB 5Upflow / Horizontal

65,00062,855100,00096,70096.7

35 - 65DIRECT10 x 10

1Variable

See Fan Performance Table3/4

Variable115/1/60

9.6Centrifugal

Direct - Variable1/50 - 5000

33 - 110/3/60 - 1801.0Yes

High Velocity1 - 20x25 - 1 in.

3 Round

Aluminized Steel - Type I

20

5 — 455 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

5115/1/60

13.2151/2

H x W x D41-3/4 x 23 x 30-1/2

197 / 185

TUH2B080A9V4VB 5Upflow / Horizontal

52,00050,44080,00077,600

9735 - 65

DIRECT11 x 8

1Variable

See Fan Performance Table3/4

Variable115/1/60

9.6Centrifugal

Direct - Variable1/50 - 5000

33 - 110/3/60 - 1801.0Yes

High Velocity1 - 17x25 - 1 in.

2 Round

Aluminized Steel - Type I

20

4 — 454 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

4115/1/60

13.2151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

170 / 158

Page 7: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

7Pub. No. 22-1814-11

PRODUCT SPECIFICATIONS 1

MODELTYPERATINGS 21st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzFLACOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)HEAT EXCHANGERType -Fired -UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs)

GeneralData

TUH2/TDH2 PRODUCT SPECIFICATIONS1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.32 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian

applicaitons, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Energy Star

TUH2D120A9V5VB 5Upflow / Horizontal

78,00075,426120,000116,040

96.740 - 70

DIRECT10 x 10

1Variable

See Fan Performance Table1

Variable115/1/60

12.8Centrifugal

Direct - Variable1/50 - 5000

33 - 110/3/60 - 1801.0Yes

High Velocity1 - 24x25 - 1 in.

3 Round

Aluminized Steel - Type I

20

6 — 456 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

6115/1/60

17.2201/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

206 / 193

TDH2B080A9V3VB 5Downflow / Horizontal

52,00049,40080,00076,000

9635 - 65

DIRECT10 x 8

1Variable

See Fan Performance Table1/2

Variable115/1/60

7.7Centrifugal

Direct - Variable1/50 - 5000

33 - 110/3/60 - 1801.0Yes

High Velocity2 - 14x20 - 1 in.

2 Round

Aluminized Steel - Type I

20

4 — 454 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

4115/1/60

10.8151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

168 / 158

TDH2B060A9V3VB 5Downflow / Horizontal

39,00037,00060,00057,000

9635 - 65

DIRECT10 x 8

1Variable

See Fan Performance Table1/2

Variable115/1/60

7.7Centrifugal

Direct - Variable1/50 - 5000

33 - 110/3/60 - 1801.0Yes

High Velocity2 - 14x20 - 1 in.

2 Round

Aluminized Steel - Type I

20

3 — 453 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

3115/1/60

10.8151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

160/ 146

TUH2C100A9V5VB 5Upflow / Horizontal

65,00062,855100,00096,70096.7

35 - 65DIRECT11 x 10

1Variable

See Fan Performance Table1

Variable115/1/60

12.8Centrifugal

Direct - Variable1/50 - 5000

33 - 110/3/60 - 1801.0Yes

High Velocity1 - 20x25 - 1 in.

3 Round

Aluminized Steel - Type I

20

5 — 455 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

5115/1/60

17.2201/2

H x W x D41-3/4 x 23 x 30-1/2

199 / 187

Page 8: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

8 Pub. No. 22-1814-11

PRODUCT SPECIFICATIONS 1

MODELTYPERATINGS 21st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3AFUETemp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzFLACOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)HEAT EXCHANGERType -Fired -UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs)

TDH2D120A9V5VB5Downflow / Horizontal

78,00074,000120,000114,000

9640 - 70

DIRECT10 x 10

1Variable

See Fan Performance Table1

Variable115/1/60

12.8Centrifugal

Direct - Variable1/50 - 5000

33 - 110/3/60 - 1801.0Yes

High Velocity2 - 16x20 - 1 in.

3 Round

Aluminized Steel - Type I

20

6 — 456 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

6115/1/60

17.2201/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

206 / 196

TDH2C100A9V4VB 5Downflow / Horizontal

65,00061,750100,00095,000

9635 - 65

DIRECT10 x 10

1Variable

See Fan Performance Table3/4

Variable115/1/60

9.6Centrifugal

Direct - Variable1/50 - 5000

33 - 110/3/60 - 1801.0Yes

High Velocity2 - 16x20 - 1 in.

3 Round

Aluminized Steel - Type I

20

5 — 455 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

5115/1/60

13.2151/2

H x W x D41-3/4 x 23 x 30-1/2

185 / 175

TDH2B080A9V4VB 5Downflow / Horizontal

52,00049,40080,00076,000

9535 - 65

DIRECT11 x 8

1Variable

See Fan Performance Table3/4

Variable115/1/60

9.6Centrifugal

Direct - Variable1/50 - 5000

33 - 110/3/60 - 1801.0Yes

High Velocity2 - 14x20 - 1 in.

2 Round

Aluminized Steel - Type I

20

4 — 454 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

4115/1/60

13.2151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

172 / 160

GeneralData

TDH2 PRODUCT SPECIFICATIONS1

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.32 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian

applicaitons, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.5 Energy Star

Page 9: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

9Pub. No. 22-1814-11

*UH2B060A9V3V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

1.5

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS575 65

575 90

575 125

550155 -

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS640 70

640 110

640 140

630 175 -

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS700 85

700 125

700 160

700 200 -

2.0

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS700100

700130

700170

700210 -

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS800115

800155

800200

800250 -

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS900140

900195

900240

900290 -

2.5

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS875130

875180

875230

875270 -

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1000175

1000235

1000285

1000335

900310

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1125235

1125295

1125345

1100370

925318

3

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1050195

1050260

1050305

1050350

920315

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1200275

1200330

1200385

1100385

940330

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1325360

1325425

1300460

1175425

1000365

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

*UH2B060A9V3V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity = 2nd Stage Capacity =

37,83058,200

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

6005785

60057110

60057155

60057190

-

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

7004990

70049130

70049175

70049210

-

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

77544105

77544155

77544195

77544240

-

HIGH OFF OFFCFM

TEMP. RISEWATTS

87039135

87039185

87039235

87039290

-

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

86061140

92057200

92057245

92057300

67079245

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

100053190

100053255

100053305

100053340

70075255

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

112547250

112547315

112547370

102551355

77568285

HIGH OFF OFFCFM

TEMP. RISEWATTS

125042340

125042405

125042445

110048390

100053355

NOTES: * First letter may be "A" or "T" ** Factory setting

Page 10: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

10Pub. No. 22-1814-11

*UH2B080A9V3V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity = 2nd Stage Capacity =

50,440 77,600

AIRFLOW SETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

80056105

80056140

80056180

80056220

80056265

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

86052115

88051165

89050215

92048265

91049320

NORMAL ** ON OFF

CFMTEMP. RISE

WATTS

96046150

99045200

100044230

102044310

101044350

HIGH OFF OFFCFM

TEMP. RISEWATTS

108041195

111040255

112040315

112040365

108041390

HEATING2ND

STAGE

LOW ON ON CFMTEMP. RISE

WATTS

110062205

110062260

112061320

112061370

109063400

MEDIUM LOW OFF ON CFMTEMP. RISE

WATTS

121057265

124055340

126054410

126054470

113061430

NORMAL ** ON OFF CFMTEMP. RISE

WATTS

136050365

139049445

140049500

136050535

121057475

HIGH OFF OFFCFM

TEMP. RISEWATTS

136050355

139049450

140049520

135051535

118058465

NOTES: * First letter may be "A" or "T" ** Factory setting

*UH2B080A9V3V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2.0

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS75084

750122

750154

720185

710221

NORMAL (400 CFM/TON) ON ON OFF OFF CFM

WATTS840109

840146

840181

840226

820264

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS940136

940177

940215

940274

940318

2.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS850113

850150

870200

890250

890295

NORMAL (400 CFM/TON) OFF ON OFF OFF CFM

WATTS960150

990200

1000230

1020305

1010350

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1080195

1110255

1120315

1120365

1080390

3.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1020175

1020225

1040280

1050330

1050375

NORMAL (400 CFM/TON) ON OFF OFF OFF CFM

WATTS1170240

1180300

1200365

1200415

1130420

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1290310

1320410

1350470

1340520

1150440

3.5

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1170250

1190315

1210370

1210435

1100405

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1360365

1390445

1400500

1360535

1210475

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1360355

1390450

1400520

1350535

1180460

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Page 11: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

11Pub. No. 22-1814-11

*UH2B080A9V4V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity = 2nd Stage Capacity =

50,44077,600

AIRFLOW SETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

80056105

80056140

80056180

80056220

80056265

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

86052115

88051165

89050215

92048265

91049320

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

96046150

99045200

100044230

102044310

101044350

HIGH OFF OFFCFM

TEMP. RISEWATTS

108041195

111040255

112040315

112040365

108041390

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

110062205

110062260

112061320

112061370

109063400

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

121057265

124055340

126054410

126054470

113061430

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

136050365

139049445

140049500

136050535

121057475

HIGH OFF OFFCFM

TEMP. RISEWATTS

136050355

139049450

140049520

135051535

118058465

NOTES: * First letter may be "A" or "T" ** Factory setting

*UH2B080A9V4V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2.5

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS857107

849143

841179

833223

825266

NORMAL (400 CFM/TON) ON ON OFF OFF CFM

WATTS970158

971205

973251

966298

960345

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS1082209

1093266

1104323

1099374

1095424

3.0

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1004153

1019210

1035267

1038321

1041374

NORMAL (400 CFM/TON) OFF ON OFF OFF CFM

WATTS1163249

1173311

1184372

1179426

1174480

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1323345

1328411

1332477

1320532

1307586

3.5

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1176254

1188317

1200380

1195437

1190494

NORMAL (400 CFM/TON) ON OFF OFF OFF CFM

WATTS1356379

1362446

1368514

1353568

1339623

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1536503

1536575

1536647

1512699

1488751

4.0

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1376374

1367429

1359483

1354547

1348611

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1562530

1562604

1563677

1531720

1499765

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1768757

1759830

1749902

1654866

1559829

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Page 12: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

12Pub. No. 22-1814-11

*UH2C100A9V4V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2.5

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS80875

824125

840170

835210

830250

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS938100

963160

959205

964255

975310

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS1058150

1100200

1121265

1136330

1142395

3.0

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1004120

1010175

1027230

1044285

1050345

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1141170

1190245

1214310

1229380

1234450

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1336250

1375330

1387410

1388480

1384545

3.5

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1153180

1206250

1230320

1239395

1244460

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1390285

1418465

1439445

1441515

1373540

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1575400

1606495

1632590

1596645

1445590

4.0

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1388290

1423360

1444440

1444515

1390540

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1610415

1641515

1666635

1607650

1449595

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1847630

1863735

1816780

1687720

1532665

NOTES: *First letter may be "A" or "T" 1. At Continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

*UH2C100A9V4V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity = 2nd Stage Capacity =

62,855 96,700

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURESW 7 SW8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

87364100

89363145

90062195

89962240

90262290

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

97158115

99756

170

100656220

102255280

102954335

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

113649160

114649230

116548295

118047365

118447425

HIGH OFF OFFCFM

TEMP. RISEWATTS

125844225

129843300

131942390

132842450

128644490

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

126068213

130466305

132965380

133465460

131765510

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

146459315

147159

405

147858485

147858560

135064540

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

163153450

167851570

169051670

157955645

141961585

HIGH OFF OFFCFM

TEMP. RISEWATTS

184647640

186746760

179448770

164452700

149857650

NOTES: * First letter may be "A" or "T" ** Factory setting

Page 13: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

13Pub. No. 22-1814-11

*UH2C100A9V5V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER1st Stage Capacity =

2nd Stage Capacity =62,85596,700

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

87364100

89363145

90062195

89962240

90262290

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

97158115

99756170

100656220

102255280

102954335

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

113649160

114649230

116548295

118047365

118447425

HIGH OFF OFFCFM

TEMP. RISEWATTS

125844225

129843300

131942390

132842450

128644490

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

126068213

130466305

132965380

133465460

131765510

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

146459315

147159405

147858485

147858560

135064540

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

163153450

167851570

169051670

157955645

141961585

HIGH OFF OFFCFM

TEMP. RISEWATTS

184647640

186746760

179448770

164452700

149857650

NOTES: * First letter may be "A" or "T" ** Factory setting

*UH2C100A9V5V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

3.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1163222

1201304

1209375

1200433

1199495

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1339331

1365400

1366477

1377555

1382636

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1515440

1538535

1549620

1553708

1547796

4.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1339331

1365400

1366477

1377555

1382636

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1550471

1562550

1574645

1575733

1564813

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1744626

1758736

1770838

1772935

17601018

5.0

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1695578

1709728

1721820

1772930

17111007

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1919862

1919958

19051043

18311043

1709982

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTSNANA

NANA

NANA

NANA

NANA

NOTES: *First letter may be "A" or "T" 1. At Continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting. 3. NA = Not allowed.

Page 14: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

14Pub. No. 22-1814-11

*UH2D120A9V5V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

3.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1210220

1210270

1220325

1230400

1230445

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1400305

1440390

1450465

1450510

1410560

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1590425

1600520

1610600

1600645

1380575

4.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1390305

1400375

1430445

1440515

1420565

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1620420

1650530

1670595

1640660

1480600

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1840600

1830690

1820765

1670700

1490620

5

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1800570

1780630

1780705

1700695

1530615

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS2050845

2010875

1860805

1710735

1530655

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS2160995

2040935

1920875

1780805

1620730

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

*UH2D120A9V5V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity = 2nd Stage Capacity =

75,426 116,040

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

109062165

112060225

108063270

107063310

101067

380

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

121056220

120056280

120056330

118057395

116058

455

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

134050295

136050350

137049425

138049495

133051

535

HIGH OFF OFFCFM

TEMP. RISEWATTS

143047390

157043490

158043565

157043625

139049

565

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

166063485

169062590

168062640

164064675

146072

600

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

187056675

187056745

181058770

168062715

149070

625

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

206051880

199053890

185057810

171061750

153068

665

HIGH OFF OFFCFM

TEMP. RISEWATTS

220048

1030

209050965

194054895

179058830

164064

750

NOTES: * First letter may be "A" or "T" ** Factory setting

Page 15: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

15Pub. No. 22-1814-11

*DH2B060A9V3V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER1st STAGE CAPACITY =

2nd STAGE CAPACITY =37,44057,600

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

6005655

6005685

60056120

60056150

60056185

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

6755065

67550105

67550140

67550175

67550205

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

7504585

75045125

75045160

75045210

75045260

HIGH OFF OFFCFM

TEMP. RISEWATTS

85040115

85040155

85040205

85040260

85040320

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

90058125

90058165

90058220

90058270

90058315

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

100052170

105050230

105050295

105050335

105050370

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

110047215

115045285

115045340

115045395

110047440

HIGH OFF OFFCFM

TEMP. RISEWATTS

130040330

132539385

132539455

125042465

120043470

NOTES: * First letter may be "A" or "T" ** Factory setting

*DH2B060A9V3V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

1.5

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS52545

52570

525100

525135

525160

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS60055

60085

600120

600150

600185

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS67565

675105

625140

675175

675205

2.0

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS70070

700115

700145

700185

700220

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS800100

800135

800175

800225

800280

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS900125

900165

900220

900270

900330

2.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS875115

875160

875210

875260

875310

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1000150

1000207

1000265

1000320

1000380

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1125215

1125285

1125340

1125395

1125440

3

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1050175

1050240

1050305

1050345

1050380

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1200240

1200315

1200385

1200440

1100410

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1350330

1350410

1350500

1275485

1170450

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Page 16: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

16Pub. No. 22-1814-11

*DH2B080A9V3V - FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2.0

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS70095

700105

700115

680200

670235

NORMAL (400 CFM/TON) ON ON OFF OFF CFM

WATTS800130

800160

800205

790245

740265

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS900160

900215

900255

900300

750270

2.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS875145

875185

875240

875280

760270

NORMAL (400 CFM/TON) OFF ON OFF OFF CFM

WATTS1000205

1000265

1000310

1000340

800295

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1150295

1150340

1150385

1020350

800300

3.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1050235

1050295

1050340

1010350

800290

NORMAL (400 CFM/TON) ON OFF OFF OFF CFM

WATTS1200335

1200385

1200410

1040365

840310

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1350455

1350480

1210435

1070390

900345

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

*DH2B080A9V3V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st STAGE CAPACITY =2nd STAGE CAPACITY =

49,92076,800

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

80056130

80056170

80056210

79056245

-

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

90049162

90049210

90049260

90049295

-

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

100044205

100044265

100044310

100044345

80056295

HIGH OFF OFFCFM

TEMP. RISEWATTS

117038305

117038350

117038400

102044360

83054310

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

115060285

115060345

115060385

102067***360

83083***305

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

127554380

127554445

120057425

104066***380

90076***350

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

143048515

134051490

122056455

109063410

93074***380

HIGH OFF OFFCFM

TEMP. RISEWATTS

143048515

134051490

122056455

109063410

93074***380

NOTES: * - First letter may be "A" or "T" ** Factory setting *** Above MAX Temperature change value

Page 17: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

17Pub. No. 22-1814-11

*DH2B080A9V4V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER1st STAGE CAPACITY =

2nd STAGE CAPACITY =49,40076,000

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

80056130

80056170

80056210

79056245

-

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

90049162

90049210

90049260

90049295

-

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

100044205

100044265

100044310

100044345

80056295

HIGH OFF OFFCFM

TEMP. RISEWATTS

117038305

117038350

117038400

102044360

83054310

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

115060285

115060345

115060385

102067***360

83083***305

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

127554380

127554445

120057425

104066***380

90076***350

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

143048515

134051490

122056455

109063410

93074***380

HIGH OFF OFFCFM

TEMP. RISEWATTS

143048515

134051490

122056455

109063410

93074***380

NOTES: * - First letter may be "A" or "T" ** Factory setting *** Above MAX Temperature change value

*DH2B080A9V4V - FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2.5

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS849141

865191

881241

878294

876348

NORMAL (400 CFM/TON) ON ON OFF OFF CFM

WATTS953195

965250

977305

973358

970411

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS1057249

1065309

1073369

1069422

1064474

3.0

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS999188

1003241

1008394

1018354

1029414

NORMAL (400 CFM/TON) OFF ON OFF OFF CFM

WATTS1144300

1150362

1156423

1160486

1165548

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1288412

1297482

1305552

1303617

1300682

3.5

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1156307

1165374

1174440

1177502

1179563

NORMAL (400 CFM/TON) ON OFF OFF OFF CFM

WATTS1327446

1335518

1343589

1325641

1307693

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1506634

1502703

1498771

1418746

1338721

4.0

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1327446

1335518

1343589

1325641

1307693

NORMAL (400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1525656

1522727

1518797

1430761

1341725

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1706906

1635881

1563857

1471813

1379769

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Page 18: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

18Pub. No. 22-1814-11

*DH2C100A9V4V - FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER1st STAGE CAPACITY =

2nd STAGE CAPACITY =62,40096,000

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

92361

110

95559

165

96058210

95858265

94759310

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

102055

145

104753

190

105353250

104254295

102954350

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

115648

185

116648

240

117248300

117748350

117848420

HIGH OFF OFFCFM

TEMP. RISEWATTS

127544

225

130543

290

132842365

132842445

132842510

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

129866

235

132065

305

133565380

134364445

134364520

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

143960

310

145959

390

148258470

148358550

147059610

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

163953

430

165052

525

165052600

164452680

149658640

HIGH OFF OFFCFM

TEMP. RISEWATTS

179018

570

181847

670

181347770

170850750

153556675

NOTES: * - First letter may be "A" or "T" ** Factory setting *** Above MAX temperature change

*DH2C100A9V4V - FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2.5

LOW(350 CFM/TON)

ON ON OFF ONCFM

WATTS870100

885140

887185

881230

876270

NORMAL(400 CFM/TON)

ON ON OFF OFFCFM

WATTS989120

1018180

1016230

1012285

999325

HIGH(450 CFM/TON)

ON ON ON OFFCFM

WATTS1124175

1139225

1130275

1135335

1135390

3.0

LOW(350 CFM/TON)

OFF ON OFF ONCFM

WATTS1053145

1075200

1070245

1070295

1049350

NORMAL(400 CFM/TON)

OFF ON OFF OFFCFM

WATTS1186195

1205255

1220310

1220370

1216440

HIGH(450 CFM/TON)

OFF ON ON OFFCFM

WATTS1336255

1366340

1383405

1385470

1381545

3.5

LOW(350 CFM/TON)

ON OFF OFF ONCFM

WATTS1216190

1225255

1235320

1240385

1243445

NORMAL(400 CFM/TON)

ON OFF OFF OFFCFM

WATTS1394270

1422360

1436430

1437505

1430580

HIGH(450 CFM/TON)

ON OFF ON OFFCFM

WATTS1579395

1604475

1610555

1599645

1517640

4.0 LOW(350 CFM/TON)

OFF OFF OFF ONCFM

WATTS1377270

1412355

1426430

1433510

1428575

NORMAL(400 CFM/TON)

OFF OFF OFF OFFCFM

WATTS1599425

1624510

1636585

1618670

1512635

HIGH(450 CFM/TON)

OFF OFF ON OFFCFM

WATTS1801580

1818690

1815775

1694735

1525660

NOTES: * - First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Page 19: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

19Pub. No. 22-1814-11

*DH2D120A9V5V - FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st STAGE CAPACITY =2nd STAGE CAPACITY =

74,880115,200

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURESW 8 SW 7 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

102565150

102565200

100067240

100067290

100067340

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

120056230

120056270

120056330

120056390

120056450

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

135049280

135049340

135049490

135049470

135049530

HIGH OFF OFFCFM

TEMP. RISEWATTS

155043400

155043

490

155043560

155043620

145046600

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

155066380

155066470

155066540

155066610

145071***690

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

185056660

185056750

185056780

170060720

150069640

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

205050860

200051880

185056810

170060750

155066670

HIGH OFF OFFCFM

TEMP. RISEWATTS

210549

1000

205050940

190054880

177558820

162563750

NOTES: * First letter may be "A" or "T" ** Factory setting

*DH2D120A9V5V - FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

3.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1225240

1225280

1225340

1225400

1225450

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1400310

1400390

1400470

1400520

1400570

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1600450

1600520

1600590

1600640

1450600

4.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1400300

1400380

1400450

1400520

1400570

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1600460

1600530

1600610

1600670

1450600

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1800610

1800700

1800760

1650690

1500630

5

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1750580

1750640

1750720

1650680

1450610

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS2000830

2000860

1850800

1700740

1550660

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS2100970

2000910

1900850

1650780

1600710

NOTES: * - First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Page 20: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

20 Pub. No. 22-1814-11

Maximum Vent Length Table

VENT LENGTH TABLE

ALTITUDE MAXIMUM TOTAL EQUIVALENT LENGTH IN FEETFOR VENT AND INLET AIR (SEE NOTES)

0-7,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE

*UH/DH2B060A9V3VB 200 200 200

*UH/DH2B080A9V3VB *UH/DH2B080A9V4VB

50 120 200

*UH/DH2C100A9V4VB *UH2C100A9V5VB

Not Allowed 60 200

*UH/DH2D120A9V5VB Not Allowed Not Allowed 200

7,000-9,500 Feet 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE

*UH/DH2B060A9V3VB 100 100 100

*UH/DH2B080A9V3VB *UH/DH2B080A9V4VB

25 60 100

*UH/DH2C100A9V4VB *UH2C100A9V5VB

Not Allowed 30 100

*UH/DH2D120A9V5VB Not Allowed Not Allowed 100

9,500-12,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 or 4 INCH PIPE

*UH/DH2B060A9V3VB 50 50 50

*UH/DH2B080A9V3VB *UH/DH2B080A9V4VB

Not Allowed 30 50

*UH/DH2C100A9V4VB *UH2C100A9V5VB

Not Allowed Not Allowed 50

*UH/DH2D120A9V5VB Not Allowed Not Allowed 50

NOTES: * - First letter may be "A" or "T"1. Minimum vent length for all models: 3' horizontal or 3' vertical.2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapt-ers at the top of the furnace). If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).4. One SHORT radius 90° elbow is equivalent to 10' of 3" or 4" pipe and one LONG radius elbow is equivalent to 6' of 3" or 4" pipe. One 90° elbow is equivalent to 7½' of 2½" pipe or 5' of 2" pipe. Two 45° elbows equal one 90°elbow.5. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5 feet. BAYVENT200B equivalent length is 0 feet. 6. Pipe adapters are field supplied (except for the *UH/DH2D120 models).7. For Canadian applications ONLY, IPEX 196006 may be used for horizontal and vertical terminations. IPEX 081216, IPEX 081218, and IPEX 081219 may only be used for horizontal vent terminations. Equivalent lengths are IPEX 196009 = 5 feet, IPEX 081216 = 11 feet, IPEX 081218 = 16 feet, and IPEX 081219 = 21 feet

Page 21: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

21Pub. No. 22-1814-11

ElectricalData

*UH2 WIRING DIAGRAM

From drawing D344303

Page 22: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

22 Pub. No. 22-1814-11

ElectricalData

*UH2 SCHEMATIC DIAGRAM

From drawing D344303

Page 23: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

23Pub. No. 22-1814-11

*DH2 WIRING DIAGRAM

ElectricalData

From drawing D344304

Page 24: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

24 Pub. No. 22-1814-11

*DH2 SCHEMATIC DIAGRAM

ElectricalData

From drawing D344304

Page 25: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

25Pub. No. 22-1814-11

Field Wiring

1. Be sure power agrees with equipment nameplates. 2. Low voltage (24 volt wiring) to be No. 18 A.W.G. min. 3. Grounding of equipment must comply with local codes. 4. Set thermostat heat anticipator per unit wiring diagram. 5. These leads provide 115V. power for connection of electronic

air cleaner and humidifier MAX. load 1.0 amps each. 6. When a single stage heating thermostat without fan switch

is used, no wiring on "G" terminal is used. 7. W1 and W2 must be jumpered together for proper operation.

Second stage heat will begin based on IFC switch setting. 8. Set dip switches with power off per installation instructions

to set airflow and indoor fan off delays. 9. Continuous fan airflow can be increased by adding this jumper. 10. This wire is only for thermostats requiring connection to

transformer common terminal. 11. Optional humidistat is to be connected between R and BK. Factory installed jumper R

to BK on the circuit board must be cut if optional humidistat is used. The jumper must also be cut when applying an airflow command signal to the BK input such as with the variable speed single-zone and multi-zone system controllers. On single speed cooling only/non-heat pump systems, jumper Y to O for proper operation of the delay profiles and the humidistat. For two compressor or two speed systems, jumper YLo to O.

W14

SEE NOTE 10

SEE NOTE 9

Y1/Ylo

W14 JUMPERSEE NOTE 11

FIELD ADDED JUMPER W1 TO W2.

SEE FURNACE WIRING DIAGRAM FOR 2ND STAGE TIMING.

From Dwg. B342027 Rev. 1

SEE NOTE 6

B/C B/C

TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES

HUM SEENOTE 5

EAC SEENOTE 5

FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE1 STAGE HEATING

USING A 1 STAGE HEATING THERMOSTATNO COOLING

Figure 60

Page 26: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

26 Pub. No. 22-1814-11

Field Wiring

1. Be sure power agrees with equipment nameplates.2. Low voltage (24 volt wiring) to be No. 18 A.W.G. min.3. Grounding of equipment must comply with local codes.4. Set thermostat heat anticipator per unit wiring diagram.5. These leads provide 115V. power for connection of electronic

air cleaner and humidifier MAX. load 1.0 amps each.6. This wire is only for thermostats requiring connection to

transformer common terminal.7. Continuous fan airflow can be increased by adding this jumper.8. Set dip switches with power off per installation instructions

to set airflow and indoor fan off delays.9. Optional humidistat is to be connected between R and BK. Factory

installed jumper R to BK on the circuit board must be cut if optionalhumidistat is used. The jumper must also be cut when applying an airflowcommand signal to the BK input such as with the variable speed single-zoneand multi-zone system controllers. On single speed cooling only/non-heat pumpsystems, jumper Y to O for proper operation of the delay profiles and the humidistat.For two compressor or two speed systems, jumper YLo to O.

W14

SEE NOTE 6

From Dwg. B342025 Rev. 0

Y1/Ylo

W14 JUMPERSEE NOTE 9

SEE NOTE 7

B/C B/C

TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES

HUM SEENOTE 5

EAC SEENOTE 5

FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE2 STAGE HEATING

USING A 2 STAGE HEATING THERMOSTATNO COOLING

Figure 61

Page 27: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

27Pub. No. 22-1814-11

Field Wiring

W14

OUTDOOR UNIT (NO TRANSFORMER)

SEE NOTE 6

SEE NOTE 7

From Dwg. B342022 Rev. 1

Y1/Ylo

W14 JUMPERSEE NOTE 9

B/CB/C

TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES

HUM SEENOTE 5

EAC SEENOTE 5

FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE1 STAGE HEATING, 1 STAGE COOLING

USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT(OUTDOOR SECTION WITHOUT TRANSFORMER)

FIELD ADDED JUMPER W1 TO W2.

SEE FURNACE WIRING DIAGRAM FOR 2ND STAGE TIMING.

Figure 62

Page 28: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

28 Pub. No. 22-1814-11

Field Wiring

W14

OUTDOOR UNIT (NO TRANSFORMER)

SEE NOTE 6

SEE NOTE 7

Y1/Ylo

SEE NOTE 9

W14 JUMPERSEE NOTE 9

From Dwg. B342020 Rev. 0

B/CB/C

TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES

HUM SEENOTE 5

EAC SEENOTE 5

FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE2 STAGE HEATING, 1 STAGE COOLING

USING A 2 STAGE HEATING, 1 STAGE COOLING THERMOSTAT(OUTDOOR SECTION WITHOUT TRANSFORMER)

Figure 63

Page 29: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

29Pub. No. 22-1814-11

Field Wiring

BLK/TWIN W2 W1 R G B Y YLO O

BLK/TWIN

BK JUMPERW14

W2 W1 R G B Y YLO O

OFF

1

21

2

ON

HUMIDISTAT HOOKUPIf an optional Humidistat is to be connected between “R” and “BK”, the factory installed jumper between “R” and “BK” on the circuit board must be cut. If an optional Humidistat is used, the jumper must also be cut when applying an airflow com-mand signal to the “BK” input such as with the variable speed single-zone and multi-zone system controller. On single speed cooling only/ non-heat pump systems, jumper “Y” to “O” for proper operation of the delay profiles and the Humidistat. For two compressor or two speed systems, jumper “YLO” to “O”.

Figure 64

The factory installed jumper be-tween “R” and “BK” on the circuit board must be cut if an optional Humidistat is installed.

Figure 65

OUTDOOR UNIT(NO TRANSFORMER)

SEE NOTE 6

SEE NOTE 7

W14R-BK

JUMPERSEE NOTE 9

B/CB

FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE2 STAGE HEATING, 2 STEP STAGED COOLING

(OUTDOOR SECTION WITHOUT TRANSFORMER)

TO 115 V 1 PH.,60 HZ., POWERSUPPLY PERLOCAL CODES

HUM SEENOTE 5

EAC SEENOTE 5

Page 30: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

30 Pub. No. 22-1814-11

Dimensions

*UH

2 U

PF

LO

W / H

OR

IZO

NTA

L O

UT

LIN

E D

RA

WIN

G(A

LL

DIM

EN

SIO

NS

AR

E IN

INC

HE

S)

Page 31: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

31Pub. No. 22-1814-11

*DH

2 D

OW

NF

LO

W / H

OR

IZO

NTA

L O

UT

LIN

E D

RA

WIN

G(A

LL

DIM

EN

SIO

NS

AR

E IN

INC

HE

S)

Dimensions

Page 32: Trane Product Data - Upflow/Horizontal Left, Downflow ... · XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB PUB. NO. 22-1814-11 Upflow

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

Trane6200 Troup HighwayTyler, TX 75707www.trane.com