27
Transformer Life Management Conference [ TLM 2011] June 6 th ~ 7 th , 2011 Hannover, Germany

TLM2011 Presentation

Embed Size (px)

Citation preview

Page 1: TLM2011 Presentation

Transformer Life Management Conference

[ TLM 2011]

June 6th ~ 7th, 2011Hannover, Germany

Page 2: TLM2011 Presentation

General Knowledge

In the mid-1800’s, Thomas Edison changed everyone's life where he perfected his invention of the electric light bulb.

After 1879, George Westinghouse developed a device called a transformer to send the power over long distance.

The transformer is based on two principles.

- First, that an electric current can produce a magnetic field (electromagnetism),

- Second, that a changing magnetic field within a coil of wire induces a voltage across the ends of the coil (electromagnetic induction).

Page 3: TLM2011 Presentation

Summary of TLM 2011

1. Dissolved-Gas-Analysis (DGA): Tool for Power Transformer monitoring

2. New experience in the Transformer Diagnostics

3. Transformers of the Future4. 3-Days stay: Experience at Hannover

Page 4: TLM2011 Presentation

1.(DGA) : Tool for Power

Transformer monitoring

Page 5: TLM2011 Presentation

Introduction

DGA enables to track the condition & gives an early indication of transformer failures.

Standard guidelines:- IEC 60599: Guide to the interpretation

of dissolved and free gases analysis IEEE Std C57.104™-2008: IEEE Guide for

the Interpretation of Gases Generated in Oil-Immersed Transformers

CIGRE [http://www.cigre-a2.org/]

Page 6: TLM2011 Presentation

DGA – Diagnostic limits

• Combustible gasesa.Hydrogen ( H2): < 100 ppmb.Methane ( CH4): < 120 ppmc.Ethane (C2H6): < 65 ppmd.Ethylene ( C2H4): < 50 ppme.Acetylene (C2H2): < 1 ppmf. Carbon Monoxide (CO): < 350 ppm• Non-Combustible gasesg. Carbon Dioxide ( CO2): < 3500

ppm

Partial Discharge

(PD)

Overheated Oil

Arcing in Oil

Overheated Cellulose[ CO2/ CO

<3 or >10]

Page 7: TLM2011 Presentation

DGA – Diagnostic limits (2)

Total Dissolved Comb. Gases (TDCG): < 720ppm

CO2/CO <3: indicates excessive paper degradation

C2H2/H2 >2: in main tank indicates OLTC contamination

Roger’s ratio method Duval’s Triangle method

Page 8: TLM2011 Presentation
Page 9: TLM2011 Presentation

2. New experience in the

Transformer Diagnostics

Page 10: TLM2011 Presentation

Introduction

The fault must be located if increased proportions of hydrocarbon gases are found in the oil.

preventative maintenance must be performed in time to avoid an unexpected total failure

The most frequent sources of faults are the tap changers, bushings, the paper-oil insulation and the accessory equipment.

Page 11: TLM2011 Presentation

Sources of Transformer faults [ Source: CIGRE International Survey]

Page 12: TLM2011 Presentation

Diagnostic test methods

• Turns ratio test and excitation current (no-load) measurement

• Static winding resistance measurement• Dynamic winding resistance

measurement to test the On-Load Tap Changer (OLTC)

• Sweep Frequency Response Analysis (SFRA)

• Di-electric Response Analysis• Partial Discharge (PD) measurement

Page 13: TLM2011 Presentation

Turns ratio test and excitation current (no-load) measurement

WHAT? - Transformer Turns Ratio is the ratio of the number of turns in the high voltage winding to that in the low voltage winding.

WHY? - for assessing possible winding damage, such as turn-to-turn short circuits

REASON? - Transformer ratio can change due to several factors, including physical damage from faults, deteriorated insulation, contamination and shipping damage.

Page 14: TLM2011 Presentation

Turns ratio test and excitation current (no-load) measurement

WHAT? - The exciting current is the current that maintains the magnetic flux excitation in the core of a transformer.

WHY? - Unwanted circulating currents or unintentional grounds can affect the exciting current and indicate a problem.

REASON? - If the exciting current test shows phase angle deviations, then the cause may be a core failure or unsymmetrical residual flux.

Page 15: TLM2011 Presentation

Static winding resistance measurement

To check for loose connections, broken strands and high contact resistance in tap changers.

The deviations between switching upwards and switching downwards are almost same.

High deviations indicates high contact resistances caused by the contacts of the tap selector switches.

Page 16: TLM2011 Presentation

Static winding resistance measurement (2)

Page 17: TLM2011 Presentation

Dynamic winding resistance measurement on OLTC

dynamic behavior of the diverter switch can be analyzed.

measures the peak of the ripple (Imax–Imin) and the slope (di/dt) of the measuring current, as these are important criteria for correct switching.

If the switching process is interrupted, even for less than 500us, the ripple and the slope of the current change dramatically.

Page 18: TLM2011 Presentation

Dynamic winding resistance measurement on OLTC (2)

For tap changers in good condition the ripple and slope measurements for all three phases tapping UP should be similar as for tapping DOWN.

Page 19: TLM2011 Presentation

Dynamic winding resistance measurement on OLTC (3)

Page 20: TLM2011 Presentation

Sweep Frequency Response Analysis (SFRA) To evaluate the mechanical integrity of

core, windings and clamping structures within power transformers by measuring their electrical transfer functions over a wide frequency range.

5 Hz up to 10 kHz – defect in core & magnetic circuit

10 kHz up to 600 kHz – deformation in winding geometry

600 kHz up to 10MHz – abnormalities on the inter-connection and test system

Page 21: TLM2011 Presentation

Sweep Frequency Response Analysis (SFRA) (2)

Page 22: TLM2011 Presentation

3. Transformers of the

Future

Page 23: TLM2011 Presentation

To Be Consider – Good Transformer

Transportation [ Factory to Site] Design & configuration Installation process especially during

new oil filling into transformer Testing & commissioning Operating condition & condition

monitoring [DGA, Oil & winding temperature, current loading]

Page 24: TLM2011 Presentation

To Be Consider – Good Transformer (2)

Recommended testing at factory & site:- DGA testing ( for oil-filled transformer)- Additional Diagnostic testing ( such as

SFRA, static & dynamic resistance test on OLTC )

Page 25: TLM2011 Presentation

3-Days stay:Experience at Hannover

Page 26: TLM2011 Presentation

Thank you for listening

Page 27: TLM2011 Presentation

Discussion

Q & A