  • TECHNICAL & SERVICE MANUALOUTDOOR UNIT : AE2MI40AH

    AE2MI56AHBAE3MI68AHAE4MI80AH

    AE2MI40AH

    AE4MI80AH

    AE2MI56AHBAE3MI68AH

    DC INVERTER MULTI-SYSTEM AIR CONDITIONEROutdoor Model No.

    AE2MI40AH

    AE2MI56AHB

    AE3MI68AH

    AE4MI80AH

    Capacity

    4.0kW

    5.6kW

    6.8kW

    8.0kW

    Product Code No.

    3 870 310 85 (1 852 349 45)

    3 870 310 86 (1 852 349 46)

    3 870 310 87 (1 852 349 47)

    3 870 310 88 (1 852 349 48)

    REFERENCE NO. SM700738

    < Applicable Indoor Units >

    Wall mounted type

    For details about the combination, refer to "Unit Combination Table" in the Appendix ofthis manual.

    AWMI22AHLAWMI27AHLAWMI35AHLAWI52AHLAWI68AHL

    NOTE

    Destination: Europe

    RoHS

    WARNING

    This product does not contain any hazardous substances prohibited by the RoHS Directive.

    You are requested to use RoHS compliant parts for maintenance or repair. You are requested to use lead-free solder.

    FILE NO.

    Do not vent R410A into atmosphere : R410A is a fluorinated greenhouse gas,covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 1975.

    F-GAS REGULATION (EC) No 842 / 2006

  • When Wiring

    ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.

    SPECIAL PRECAUTIONS

    This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.

    This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.

    CAUTION

    CAUTION

    WARNING

    WARNING

    Important! Please Read Before StartingThis air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.

    For safe installation and trouble-free operation, you must:

    Carefully read this instruction booklet before beginning.Follow each installation or repair step exactly as shown.Observe all local, state, and national electrical codes.Pay close attention to all warning and caution notices given in this manual.

    If Necessary, Get HelpThese instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.

    In Case of Improper InstallationThe manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.

    Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.Ground the unit following local electrical codes.Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.Install a protective leakage breaker depending on the installation location (especially a damp or humid location). If a leakage breaker is not installed, electric shock can occur.

    When Transporting

    Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.

    When Installing

    In a Ceiling or WallMake sure the ceiling/wall is strong enough to hold the units weight. It may be necessary to construct a strong wood or metal frame to provide added support.In a RoomProperly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water damage to walls and floors.In Moist or Uneven LocationsUse a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.In an Area with High WindsSecurely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle. In a Snowy Area (for Heat Pump-type Systems)Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.

    When Connecting Refrigerant Tubing

    Use the flare method for connecting tubing.Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.Check carefully for leaks before starting the test run.

    When Servicing

    Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.Keep your fingers and clothing away from any moving parts.Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.

    Others

    Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.

    2

  • Table of Contents

    APPLICABLE INDOOR UNITS

    1. OPERATING RANGE

    2. SPECIFICATIONS2-1. Unit Specifications 2-2. Major Component Specifications 2-3. Other Component Specifications

    3. DIMENSIONAL DATA

    4. REFRIGERANT FLOW DIAGRAM4-1. Refrigerant Flow Diagram

    5. PERFORMANCE DATA5-1. Temperature Charts

    6. ELECTRICAL DATA6-1. Electric Wiring Diagrams

    7. FUNCTIONS7-1. Explanation of Functions7-2. Protective Functions

    8. TROUBLESHOOTING8-1. Precautions before Performing Inspection or Repair8-2. Trouble Diagnosis by Error Monitor Lamps8-3. Checking the Outdoor System8-4. Trouble Diagnosis of Each Part8-5. Trouble Diagnosis of Fan Motor

    9. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT9-1. Characteristics of New Refrigerant R410A9-2. Checklist before Servicing9-3. Tools Specifically for R410A9-4. Tubing Installation Procedures9-5. In Case of Compressor Malfunction9-6. In Case Refrigerant is Leaking9-7. Charging Additional Refrigerant9-8. Retro-Fitting Existing Systems

    5

    6

    71115

    16

    20

    24

    41

    4549

    5253545558

    5959616162646565

    ....................................................................................................

    ...................................................................................................................

    ...........................................................................................................................................................................................................................................................................................

    ...................................................................................................................

    ...................................................................................................

    ............................................................................................................

    ....................................................................................................

    ...............................................................................................................................................................................................................

    ....................................................................................................................................

    ................................................................................................................................................................................................................................................................................

    ............................................................................................................................................................................

    ............................................................................................................................................................................................

    ..........................................................................................................................................................................................................................................................................

    ............................................................................................

    Page

    3

  • APPENDIX A INSTALLATION INSTRUCTIONS

    APPENDIX B UNIT COMBINATION TABLES

    A-1

    A-2

    .............................................................................

    .................................................................................

    Page

    4

  • APPLICABLE INDOOR UNITS

    AE2MI40AH

    Multi-Outdoor Unit

    Indoor Unit

    YES YES YES NO NO

    AE2MI56AHB YES YES YES YES NO

    AE3MI68AH YES YES YES YES YES

    AE4MI80AH

    2-Room

    2-Room

    4-Room

    4-Room YES YES YES YES YES

    AWMI22AHL AWMI27AHL AWMI35AHL AWI52AHL AWI68AHL

    NOTE 1. The table lists the wall-mounted type of indoor units as representative models.

    2. For details on the applicable indoor units other than the wall-mounted type, refer to the catalog.

    5

  • 1. OPERATING RANGE

    Maximum

    Minimum

    Maximum

    Minimum

    32 C D.B. / 23 C W.B.19 C D.B. / 14 C W.B.27 C D.B.16 C D.B.

    43 C D.B.19 C D.B.24 C D.B. / 18 C W.B._ D.B. / -15 C W.B.

    Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.

    Cooling

    Heating

    6

  • 2. SPECIFICATIONS2-1. Unit SpecificationsOutdoor Unit AE2MI40AHIndoor Unit AWMI27AHL 2

    DATA SUBJECT TO CHANGE WITHOUT NOTICE.

    CompressorRefrigerant / Amount charged at shipment kgRefrigerant Control

    4.1925

    4.013,600

    ( 2.0 to 5.0 )( 6,800 to 17,100 )

    Shipping Volume

    Cooling

    1,900

    Cooling

    NetShipping

    Package Dimensions

    Weight

    Height Width Depth

    Height Width Depthkgkg

    m3

    mm

    mm

    220 to 240V Single-Phase 50Hz

    198 to 264

    Dimensions & Weight (Outdoor Unit)

    Refrigerant Tubing Connections

    Unit Dimensions

    Electrical Rating

    Air Circulation (High)

    WPower Input

    VA

    Available Voltage RangeRunning Amperes

    Narrow tubeWide tube

    Refrigerant mm (in.)Tube Diameter mm (in.)

    42.045.00.22

    569 790 285

    645 920 385

    6.35 (1/4") 29.52 (3/8") 2

    mMax. allowable tubing length per unitFlare Type

    20

    R410A / 1.7Electric Expansion Valve

    DC Twin Rotary (Inverter)

    dB-A

    Fan Speeds Auto (Hi, Me, Lo)Control Microprocessor

    Features (Outdoor Unit)

    C.O.P.

    kW

    Performance

    %Power Factor 98

    W/W -

    Power Source

    BTU/hCapacity

    m3/h

    E.E.R. W/W 4.32

    230VVoltage Rating

    Type

    Number of Connectable Indoor Units

    6.15Max. Capacity of Operating Indoor Units kW

    Number of Operatable Indoor Units

    4.515,400

    ( 2.2 to 5.5 )( 7,500 to 18,800 )

    Heating

    1,900

    Compressor Locked Rotor Amperes A 14.5

    4.1925

    Heating

    98

    4.86-

    Operation Sound Hi 47 48

    Remarks:1. The Values shown in performance section and electrical rating section above are based on the following unit combination.

    For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : AWMI27AHL 2units Outdoor Unit : AE2MI40AH 1unit2. Rating conditions are: Cooling : Indoor air temp. 27C D.B. / 19C W.B. Heating : Indoor air temp. 20C D.B.

    Outdoor air temp. 35C D.B. / 24C W.B. Outdoor air temp. 7C D.B. / 6C W.B.

    2-Room Multi Outdoor Unit

    2

    2

    7

  • Outdoor Unit AE2MI56AHBIndoor Unit AWMI27AHL 1 + AWI52AHL 1

    DATA SUBJECT TO CHANGE WITHOUT NOTICE.

    CompressorRefrigerant / Amount charged at shipment kgRefrigerant Control

    7.521,695

    5.619,100

    ( 2.1 to 6.8 )( 7,200 to 23,200 )

    Shipping Volume

    Cooling

    2,900

    Cooling

    NetShipping

    Package Dimensions

    Weight

    Height Width Depth

    Height Width Depthkgkg

    m3

    mm

    mm

    220 to 240V Single-Phase 50Hz

    198 to 264

    Dimensions & Weight (Outdoor Unit)

    Refrigerant Tubing Connections

    Unit Dimensions

    Electrical Rating

    Air Circulation (High)

    WPower Input

    VA

    Available Voltage RangeRunning Amperes

    Narrow tubeWide tube

    Refrigerant mm (in.)Tube Diameter mm (in.)

    65.069.00.38

    740 900 320

    868 1,050 423

    6.35 (1/4") 29.52 (3/8") 2

    mMax. allowable tubing length per unitFlare Type

    25

    R410A / 2.8Electric Expansion Valve

    DC Twin Rotary (Inverter)

    dB-A

    Fan Speeds Auto (Hi, Me, Lo)Control Microprocessor

    Features (Outdoor Unit)

    C.O.P.

    kW

    Performance

    %Power Factor 98

    W/W -

    Power Source

    BTU/hCapacity

    m3/h

    E.E.R. W/W 3.30

    230VVoltage Rating

    2-Room Multi Outdoor UnitType

    2Number of Connectable Indoor Units

    8.65Max. Capacity of Operating Indoor Units kW

    2Number of Operatable Indoor Units

    7.324,900

    ( 2.4 to 8.4 )( 8,200 to 28,700 )

    Heating

    2,900

    Compressor Locked Rotor Amperes A 14.5

    7.701,735

    Heating

    98

    4.21-

    Operation Sound Hi 50 52

    Remarks:1. The Values shown in performance section and electrical rating section above are based on the following unit combination.

    For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : AWMI27AHL 1unit + AWI52AHL 1unit Outdoor Unit : AE2MI56AHB 1unit2. Rating conditions are: Cooling : Indoor air temp. 27C D.B. / 19C W.B. Heating : Indoor air temp. 20C D.B.

    Outdoor air temp. 35C D.B. / 24C W.B. Outdoor air temp. 7C D.B. / 6C W.B.

    8

  • Outdoor Unit AE3MI68AHIndoor Unit AWMI27AHL 3

    DATA SUBJECT TO CHANGE WITHOUT NOTICE.

    CompressorRefrigerant / Amount charged at shipment kgRefrigerant Control

    8.872,000

    6.823,200

    ( 2.9 to 8.1 )( 9,900 to 27,600 )

    Shipping Volume

    Cooling

    2,900

    Cooling

    NetShipping

    Package Dimensions

    Weight

    Height Width Depth

    Height Width Depthkgkg

    m3

    mm

    mm

    220 to 240V Single-Phase 50Hz

    198 to 264

    Dimensions & Weight (Outdoor Unit)

    Refrigerant Tubing Connections

    Unit Dimensions

    Electrical Rating

    Air Circulation (High)

    WPower Input

    VA

    Available Voltage RangeRunning Amperes

    Narrow tubeWide tube

    Refrigerant mm (in.)Tube Diameter mm (in.)

    65.069.00.38

    740 900 320

    868 1,050 423

    6.35 (1/4") 49.52 (3/8") 3 + 12.7 (1/2") 1

    mMax. allowable tubing length per unitFlare Type

    25

    R410A / 2.8Electric Expansion Valve

    DC Twin Rotary (Inverter)

    dB-A

    Fan Speeds Auto (Hi, Me, Lo)Control Microprocessor

    Features (Outdoor Unit)

    C.O.P.

    kW

    Performance

    %Power Factor 98

    W/W -

    Power Source

    BTU/hCapacity

    m3/h

    E.E.R. W/W 3.40

    230VVoltage Rating

    4-Room Multi Outdoor UnitType

    4Number of Connectable Indoor Units

    12.2Max. Capacity of Operating Indoor Units kW

    3Number of Operatable Indoor Units

    8.629,300

    ( 3.4 to 9.0 )( 11,600 to 30,700 )

    Heating

    2,900

    Compressor Locked Rotor Amperes A 14.5

    8.872,000

    Heating

    98

    4.30-

    Operation Sound Hi 50 52

    Remarks:1. The Values shown in performance section and electrical rating section above are based on the following unit combination.

    For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : AWMI27AHL 3units Outdoor Unit : AE3MI68AH 1unit2. Rating conditions are: Cooling : Indoor air temp. 27C D.B. / 19C W.B. Heating : Indoor air temp. 20C D.B.

    Outdoor air temp. 35C D.B. / 24C W.B. Outdoor air temp. 7C D.B. / 6C W.B.

    9

  • Outdoor Unit AE4MI80AHIndoor Unit AWMI27AHL 4

    DATA SUBJECT TO CHANGE WITHOUT NOTICE.

    CompressorRefrigerant / Amount charged at shipment kgRefrigerant Control

    7.581,725

    8.027,300

    ( 2.9 to 9.2 )( 9,900 to 31,400 )

    Shipping Volume

    Cooling

    3,070

    Cooling

    NetShipping

    Package Dimensions

    Weight

    Height Width Depth

    Height Width Depthkgkg

    m3

    mm

    mm

    220 to 240V Single-Phase 50Hz

    198 to 264

    Dimensions & Weight (Outdoor Unit)

    Refrigerant Tubing Connections

    Unit Dimensions

    Electrical Rating

    Air Circulation (High)

    WPower Input

    VA

    Available Voltage RangeRunning Amperes

    Narrow tubeWide tube

    Refrigerant mm (in.)Tube Diameter mm (in.)

    82.086.00.45

    890 900 320

    1,019 1,050 423

    6.35 (1/4") 49.52 (3/8") 2 + 12.7 (1/2") 2

    mMax. allowable tubing length per unitFlare Type

    30

    R410A / 3.8Electric Expansion Valve

    DC Twin Rotary (Inverter)

    dB-A

    Fan Speeds Auto (Hi, Me, Lo)Control Microprocessor

    Features (Outdoor Unit)

    C.O.P.

    kW

    Performance

    %Power Factor 99

    W/W -

    Power Source

    BTU/hCapacity

    m3/h

    E.E.R. W/W 4.64

    230VVoltage Rating

    4-Room Multi Outdoor UnitType

    4Number of Connectable Indoor Units

    14.7Max. Capacity of Operating Indoor Units kW

    4Number of Operatable Indoor Units

    9.432,100

    ( 3.4 to 9.8 )( 11,600 to 33,400 )

    Heating

    3,070

    Compressor Locked Rotor Amperes A 17.0

    8.962,040

    Heating

    99

    4.61-

    Operation Sound Hi 50 52

    Remarks:1. The Values shown in performance section and electrical rating section above are based on the following unit combination.

    For other combination unit, please refer to the "Unit Combination Tables" in this manual. Indoor Unit : AWMI27AHL 4units Outdoor Unit : AE4MI80AH 1unit2. Rating conditions are: Cooling : Indoor air temp. 27C D.B. / 19C W.B. Heating : Indoor air temp. 20C D.B.

    Outdoor air temp. 35C D.B. / 24C W.B. Outdoor air temp. 7C D.B. / 6C W.B.

    10

  • Outdoor Unit AE2MI40AH

    2-2-1. Outdoor Unit

    Control PCB

    Control Circuit Fuse ControlsPart No.

    Microprocessor250V 25A

    CB-CMRV1424EH

    DATA SUBJECT TO CHANGE WITHOUT NOTICE.

    cc

    WHT - BLU :RED - WHT :

    BLU - RED :77.577.5

    77.5

    Micro FVAC

    External Finish Acrylic baked-on enamel finish

    FV50S ... 350

    --

    Internal ControllerYes

    Aluminum Plate Fin / Copper Tube2

    13 Face Area m2

    mm0.452

    CoilRowsFin Pitch

    Heat Exchanger Coil

    DAJ12-55J71-CR ... 1

    Compressor Oil ... Amount

    8

    50750 / 750

    Ohm

    DC Motor

    TypeCompressor Model / Nominal Output

    Compressor

    Coil Resistance (Ambient Temp. 20 C) Ohm

    DC Twin Rotary (Hermetic)C-6RVN93H0M / 1,000W

    R - S :S - T :T - R :

    0.4820.4820.482

    CT (Peak current cut-off control)Compressor Discharge Temp. ControlOperation cut-off control in abnormal ambient Temp.

    Safety Device

    Micro FVAC

    Run Capacitor

    Crankcase Heater

    YesYesYes

    Overload Relay CS-7L115ModelOperation Temp. Open : 115 C, Close : 95 C

    ---

    1 ... D420

    FanPropeller

    Q'ty ... Dia. mmType

    TypeOver-Current Protection

    Fan Motor

    Nominal OutputCoil Resistance

    Safety Device

    Run Capacitor

    TypeModel ... Q'tyNo. of Poles

    W

    2-2. Major Component Specifications

    (Ambient Temp. 20 C)

    Rough Measure RPM (Cool:Hi / Heat:Hi)

    11

  • Outdoor Unit AE2MI56AHB

    Control PCB

    Control Circuit Fuse ControlsPart No.

    Microprocessor250V 25A

    CB-CMRV1924EH

    cc

    FV50S ... 900

    Compressor Oil ... Amount

    TypeCompressor Model / Nominal Output

    Compressor

    Coil Resistance (Ambient Temp. 20 C) Ohm

    DC Twin Rotary (Hermetic)5KD240XAB21 / 1,700W

    U - V :V - W :W - U :

    0.7200.7080.726

    CT (Peak current cut-off control)Compressor Discharge Temp. ControlOperation cut-off control in abnormal ambient Temp.

    Safety Device

    Micro FVAC

    Run Capacitor

    Crankcase Heater

    YesYesYes

    Overload Relay CS-7LN115ModelOperation Temp. Open : 115 C, Close : 100 C

    --

    230V 25W

    1 ... D460

    FanPropeller

    Q'ty ... Dia. mmType

    DATA SUBJECT TO CHANGE WITHOUT NOTICE.

    -

    Micro FVAC

    External Finish Acrylic baked-on enamel finish

    --

    Internal ControllerYesYes

    Aluminum Plate Fin / Copper Tube2

    1.4 Face Area 0.595

    CoilRows

    Heat Exchanger Coil

    SIC-71FW-D490-1 ... 1

    8

    90750 / 750

    Ohm

    DC Motor

    TypeOver-Current ProtectionOver-Heat Protection

    (Ambient Temp. 20 C)

    Fan Motor

    Nominal OutputCoil Resistance

    Safety Device

    Rough Measure RPM (Cool:Hi / Heat:Hi)

    Run Capacitor

    TypeModel ... Q'tyNo. of Poles

    W

    m2mmFin Pitch

    12

  • Outdoor Unit AE3MI68AH

    Control PCB

    Control Circuit Fuse ControlsPart No.

    Microprocessor250V 25A

    CB-CMRV2444EH

    cc

    FV50S ... 900

    Compressor Oil ... Amount

    TypeCompressor Model / Nominal Output

    Compressor

    Coil Resistance (Ambient Temp. 20 C) Ohm

    DC Twin Rotary (Hermetic)5KD240XAB21 / 1,700W

    U - V :V - W :W - U :

    0.7200.7080.726

    CT (Peak current cut-off control)Compressor Discharge Temp. ControlOperation cut-off control in abnormal ambient Temp.

    Safety Device

    Micro FVAC

    Run Capacitor

    Crankcase Heater

    YesYesYes

    Overload Relay CS-7LN115ModelOperation Temp. Open : 115 C, Close : 100 C

    --

    230V 25W

    1 ... D460

    FanPropeller

    Q'ty ... Dia. mmType

    DATA SUBJECT TO CHANGE WITHOUT NOTICE.

    -

    Micro FVAC

    External Finish Acrylic baked-on enamel finish

    --

    Internal ControllerYesYes

    Aluminum Plate Fin / Copper Tube2

    1.4 Face Area 0.595

    CoilRows

    Heat Exchanger Coil

    SIC-71FW-D490-1 ... 1

    8

    90750 / 750

    Ohm

    DC Motor

    TypeOver-Current ProtectionOver-Heat Protection

    (Ambient Temp. 20 C)

    Fan Motor

    Nominal OutputCoil Resistance

    Safety Device

    Rough Measure RPM (Cool:Hi / Heat:Hi)

    Run Capacitor

    TypeModel ... Q'tyNo. of Poles

    W

    m2mmFin Pitch

    13

  • Outdoor Unit AE4MI80AH

    Control PCB

    Control Circuit Fuse ControlsPart No.

    Microprocessor250V 25A

    CB-CMRV3144EH

    cc

    FV50S ... 1,200

    Compressor Oil ... Amount

    TypeCompressor Model / Nominal Output

    Compressor

    Coil Resistance (Ambient Temp. 20 C) Ohm

    DC Twin Rotary (Hermetic)5JD420XAB22 / 3,000W

    U - V :V - W :W - U :

    0.4350.4410.452

    CT (Peak current cut-off control)Compressor Discharge Temp. ControlOperation cut-off control in abnormal ambient Temp.

    Safety Device

    Micro FVAC

    Run Capacitor

    Crankcase Heater

    YesYesYes

    Overload Relay CS-7LN115ModelOperation Temp. Open : 115 C, Close : 100 C

    --

    230V 25W

    1 ... D460

    FanPropeller

    Q'ty ... Dia. mmType

    DATA SUBJECT TO CHANGE WITHOUT NOTICE.

    -

    Micro FVAC

    External Finish Acrylic baked-on enamel finish

    --

    Internal ControllerYesYes

    Aluminum Plate Fin / Copper Tube2

    1.4 Face Area 0.723

    CoilRows

    Heat Exchanger Coil

    SIC-71FW-D490-1 ... 1

    8

    90750 / 750

    Ohm

    DC Motor

    TypeOver-Current ProtectionOver-Heat Protection

    (Ambient Temp. 20 C)

    Fan Motor

    Nominal OutputCoil Resistance

    Safety Device

    Rough Measure RPM (Cool:Hi / Heat:Hi)

    Run Capacitor

    TypeModel ... Q'tyNo. of Poles

    W

    m2mmFin Pitch

    14

  • 2-3. Other Component Specifications

    00 10 20 30 40 50 60 70 80 90

    40

    60

    80

    100

    120

    140

    160

    180

    200

    20

    Res

    ista

    nce

    (k

    oh

    m)

    Temperature (C)

    40

    35

    30

    25

    20

    15

    10

    5

    0-20 -15 -10 -5 0 5 10 15 20

    Temperature (C)

    Res

    ista

    nce

    (k

    oh

    m)

    Outdoor air temp sensor

    Outdoor heat exchanger sensor

    AW / AN sensor

    BW / BN sensor

    CW / CN sensor

    DW / DN sensor

    TKS295B

    TKS292B

    TKS292B

    TKS292B

    TKS292B

    TKS292B

    Model No.of sensorSensor Name

    1

    1

    1/1

    1/1

    0

    0

    1

    1

    1/1

    1/1

    0

    0

    Quantity of Sensor

    1

    1

    1/1

    1/1

    1/1

    1/1

    1

    1

    1/1

    1/1

    1/1

    1/1

    AE2MI40AH AE2MI56AHB AE3MI68AH AE4MI80AH

    Sensor Name

    Compressor temp sensor TKS293B

    Model No.of sensor

    1 1

    Quantity of Sensor

    1 1

    AE2MI40AH AE2MI56AHB AE3MI68AH AE4MI80AH

    15

  • 295

    608 85

    790 70

    46

    336

    310

    285

    4-ID:23.6ID:18

    2-ID:12

    569

    15

    7012

    2158

    70

    14246

    Wide tube service valvedia.9.52 (3/8") 2

    Narrow tube service valvedia.6.35 (1/4") 2

    Unit: mm

    3. DIMENSIONAL DATAOutdoor Unit AE2MI40AH

    16

  • 293

    608 136

    12

    900 85

    35

    369

    345

    320

    ID:1

    8

    5-ID

    :23.

    6

    740

    18

    7511

    3150

    72

    11451

    Wide tube service valvedia.9.52 (3/8") 2

    Narrow tube service valvedia.6.35 (1/4") 2

    Outdoor Unit AE2MI56AHB

    Unit: mm

    17

  • 293

    608 136

    12

    35

    369

    345

    320

    ID:1

    8

    5-ID

    :23.

    6

    900 85

    740

    18

    7570

    11315

    072

    70

    11451

    70

    70

    Wide tube service valvedia.9.52 (3/8") 3

    Narrow tube service valvedia.6.35 (1/4") 4

    Wide tube service valvedia.12.70 (1/2") 1

    Outdoor Unit AE3MI68AH

    Unit: mm

    18

  • 293

    608 136

    12

    35

    369

    345

    320

    ID:1

    8

    5-ID

    :23.

    6

    900 85

    890

    18

    7570

    11315

    073

    70

    11451

    70

    70

    Wide tube service valvedia.9.52 (3/8") 2

    Narrow tube service valvedia.6.35 (1/4") 4

    Wide tube service valvedia.12.70 (1/2") 2

    Outdoor Unit AE4MI80AH

    Unit: mm

    19

  • 4. REFRIGERANT FLOW DIAGRAM4-1. Refrigerant Flow DiagramOutdoor Unit AE2MI40AH

    Insulation of Refrigerant Tubing

    Because capillary tubing is used in the outdoor unit, both thewide and narrow tubes of this air conditioner become cold. Toprevent heat loss and wet floors due to dripping ofcondensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulationshould be a min. 8 mm.

    After a tube has been insulated,never try to bend it into a narrowcurve because it can cause the tubeto break or crack.

    Wide tube

    Thickness:Min. 8 mm

    Insulation

    Narrow tube

    Thickness:Min. 8 mm

    IMPORTANT

    CAUTION

    Com

    pres

    sor

    4-wayvalve

    Mainaccumulator

    Subaccumulator

    Service valve onnarrow tube

    Service valve onwide tube

    Wide tube

    BN

    AN

    BW

    AW

    O.D.9.52mm

    O.D.9.52mm

    Narrow tubeO.D.6.35mm

    O.D.6.35mm

    Hea

    t exc

    hang

    er

    Capillary tube for split flow

    Cooling cycle

    Heating cycle

    Defrosting cycle

    Indoor unit Outdoor unit

    Defrost valvefor hot gas bypass

    Strainer

    S

    M

    M

    Electric expansion valve

    Muffler

    20

  • Narrow tubeO.D.6.35mm

    O.D.6.35mm

    Outdoor Unit AE2MI56AHB

    Insulation of Refrigerant Tubing

    Because capillary tubing is used in the outdoor unit, both thewide and narrow tubes of this air conditioner become cold. Toprevent heat loss and wet floors due to dripping ofcondensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulationshould be a min. 8 mm.

    After a tube has been insulated,never try to bend it into a narrowcurve because it can cause the tubeto break or crack.

    Wide tube

    Thickness:Min. 8 mm

    Insulation

    Narrow tube

    Thickness:Min. 8 mm

    IMPORTANT

    CAUTION

    Com

    pres

    sor

    4-wayvalve

    Mainaccumulator

    Subaccumulator

    Service valve onnarrow tube

    Service valve onwide tube

    Wide tube

    BN

    AN

    BW

    AW

    O.D.9.52mm

    O.D.9.52mm

    Hea

    t exc

    hang

    er

    Cooling cycle

    Heating cycle

    Defrosting cycle

    Indoor unit Outdoor unit

    Defrost valvefor hot gas bypass

    Strainer

    S

    M

    M

    Electric expansion valve

    Header

    Header

    21

  • Outdoor Unit AE3MI68AH

    Insulation of Refrigerant Tubing

    Because capillary tubing is used in the outdoor unit, both thewide and narrow tubes of this air conditioner become cold. Toprevent heat loss and wet floors due to dripping ofcondensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulationshould be a min. 8 mm.

    After a tube has been insulated,never try to bend it into a narrowcurve because it can cause the tubeto break or crack.

    Wide tube

    Thickness:Min. 8 mm

    Insulation

    Narrow tube

    Thickness:Min. 8 mm

    IMPORTANT

    CAUTION

    Com

    pres

    sor

    4-wayvalve

    Mainaccumulator

    Subaccumulator

    Service valve onnarrow tube

    Service valve onwide tube

    Wide tube

    DN

    CN

    BN

    AN

    DW

    CW

    BW

    AW

    O.D.9.52mm

    O.D.9.52mm

    O.D.9.52mm

    O.D.12.7mm

    Narrow tubeO.D.6.35mm

    O.D.6.35mm

    O.D.6.35mm

    O.D.6.35mm

    Hea

    t exc

    hang

    er

    Cooling cycle

    Heating cycle

    Defrosting cycle

    Indoor unit Outdoor unit

    Defrost valvefor hot gas bypass

    Strainer

    S

    M

    M

    Electric expansion valve

    Header

    Header

    M

    M

    22

  • Outdoor Unit AE4MI80AH

    Insulation of Refrigerant Tubing

    Because capillary tubing is used in the outdoor unit, both thewide and narrow tubes of this air conditioner become cold. Toprevent heat loss and wet floors due to dripping ofcondensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulationshould be a min. 8 mm.

    After a tube has been insulated,never try to bend it into a narrowcurve because it can cause the tubeto break or crack.

    Wide tube

    Thickness:Min. 8 mm

    Insulation

    Narrow tube

    Thickness:Min. 8 mm

    IMPORTANT

    CAUTION

    Com

    pres

    sor

    4-wayvalve

    Mainaccumulator

    Subaccumulator

    Service valve onnarrow tube

    Service valve onwide tube

    Wide tube

    DN

    CN

    BN

    AN

    DW

    CW

    BW

    AW

    O.D.9.52mm

    O.D.9.52mm

    O.D.12.7mm

    O.D.12.7mm

    Narrow tubeO.D.6.35mm

    O.D.6.35mm

    O.D.6.35mm

    O.D.6.35mm

    Hea

    t exc

    hang

    er

    Cooling cycle

    Heating cycle

    Defrosting cycle

    Indoor unit Outdoor unit

    Defrost valvefor hot gas bypass

    Strainer

    S

    M

    M

    Electric expansion valve

    Header

    Header

    M

    M

    23

  • 5. PERFORMANCE DATA5-1. Temperature Charts

    5-1-1. Temperature Charts (AE2MI40AH)

    Outdoor Unit AE2MI40AH Indoor Unit AWMI22AHL 1Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    1.4(14.2)

    1.6(16.2)

    1.2(12.2)

    1.0(10.2)

    25 -5 0 5 10 15 20 25

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    2.0(20.4)

    1.5(15.3)

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    3

    4

    2

    125 -5 0 5 10 15 20 25

    4

    3

    2

    1

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    5-5 0 5 10 15 20 25

    55

    50

    45

    40

    35

    30

    25

    20

    20C

    17CIndo

    or air te

    mp.23

    Indoor a

    ir temp.

    23C

    Indoor a

    ir temp.

    23C

    20C

    17C

    30 35 40

    20

    25

    15

    10

    25

    2727C

    2424C

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    17C

    Indoor

    air tem

    p.23

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    27C24C

    Indoor air tem

    p.30

    Indoor air tem

    p.30C

    Indoor air tem

    p.30C

    27C24C

    27C

    2424C

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C17C

    Indoor air temp.23C

    Indoor air temp.23C

    20C17C

    Lo fan Hi fan

    Lo fan Hi fan

    Lo fan Hi fan

    24

  • Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    3

    4

    2

    125

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    6

    7

    5

    4

    3

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    5-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    25

    20C

    17C

    Indoor air t

    emp.23

    Indoor air t

    emp.23C

    Indoor air t

    emp.23C

    20C

    17C

    30 35 40

    20

    25

    15

    10

    25

    Lo fan Hi fan

    27C

    24C

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    17C

    Indoor a

    ir temp.23

    Indoor a

    ir temp.23

    C

    Indoor a

    ir temp.23

    C

    20C

    17C

    27C24C

    Indoor air tem

    p.30

    Indoor air tem

    p.30C

    Indoor air tem

    p.30C

    27C24C

    27C

    2424C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    2020C1717C

    Indoor air temp.23

    Indoor air temp.23C

    Indoor air temp.23C

    20C17C

    Outdoor Unit AE2MI40AH Indoor Unit AWMI27AHL 1

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.4(14.2)

    1.6(16.2)

    1.2(12.2)

    1.0(10.2)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    2.0(20.4)

    25

  • Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    5

    6

    4

    325

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    7

    8

    6

    5

    4

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    5-5 0 5 10 15 20 25

    65

    60

    55

    50

    45

    40

    35

    30

    20C

    17C

    Indoor air t

    emp.23

    Indoor air t

    emp.23C

    Indoor air t

    emp.23C

    20C

    17C

    30 35 40

    20

    25

    15

    10

    25

    27C

    24C

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    17C

    Indoor a

    ir temp.

    23

    Indoor a

    ir temp.

    23C

    Indoor a

    ir temp.

    23C

    20C

    17C

    27C

    24C

    Indoor air

    temp.30

    Indoor air

    temp.30C

    Indoor air

    temp.30C

    27C

    24C

    2727C

    2424C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    17C

    Indoor air t

    emp.23C

    Indoor air t

    emp.23C

    20C

    17C

    Outdoor Unit AE2MI40AH Indoor Unit AWMI35AHL 1

    Lo fan Hi fan

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.2(12.2)

    1.4(14.2)

    1.0(10.2)

    0.8(8.2)

    4.0(40.8)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    26

  • Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor Unit AE2MI56AHB Indoor Unit AWMI22AHL 15-1-2. Temperature Charts (AE2MI56AHB)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan HH fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    4

    5

    3

    225

    Lo fan Hi fan HH fan

    -5 0 5 10 15 20 25

    7

    8

    6

    5

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    8-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    25

    20C

    1717C

    Indoor ai

    r temp.23

    Indoor ai

    r temp.23

    C

    Indoor ai

    r temp.23

    C

    20C

    17C

    30 35 40

    20

    18

    16

    14

    12

    10

    25

    Lo fan Hi fan HH fan

    27C

    2424C

    Indoor a

    ir temp.

    30

    Indoor a

    ir temp.

    30C

    Indoor a

    ir temp.

    30C

    27C

    24C20C

    17C

    Indoor air tem

    p.23

    Indoor air tem

    p.23C

    Indoor air tem

    p.23C

    20C

    17C

    27C

    24C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    27C

    24C

    Indoor air temp.3

    0CIndoor a

    ir temp.30C

    27C

    24C

    20C

    1717C

    Indoor air temp.23

    Indoor air temp.23C

    Indoor air temp.23C

    20C

    17C

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.2(12.2)

    1.3(13.2)

    1.1(11.2)

    1.0(10.2)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    2.0(20.4)

    27

  • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor Unit AE2MI56AHB Indoor Unit AWMI27AHL 1Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    5

    6

    4

    325

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    7

    8

    6

    5

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    10-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    25

    20C

    17C

    Indoor air temp.

    23Indoor a

    ir temp.23C

    Indoor air temp.

    23C

    20C

    17C

    30 35 40

    20

    18

    16

    14

    12

    25

    Lo fan Hi fan

    27C

    24C

    Indoor air tem

    p.30

    Indoor air tem

    p.30C

    Indoor air tem

    p.30C

    27C

    24C20C

    17C

    Indoor ai

    r temp.23

    C

    Indoor ai

    r temp.23

    C

    20C

    17C

    27C

    24C

    Indoor a

    ir temp.

    30

    Indoor a

    ir temp.

    30C

    Indoor a

    ir temp.

    30C

    27C

    24C

    27C

    24C

    Indoor air tem

    p.30CIndoor

    air temp.30C

    27C

    24C

    2020C

    17C

    Indoor air tem

    p.23C

    Indoor air tem

    p.23C

    20C

    17C

    HH fan

    HH fan

    HH fan

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.2(12.2)

    1.3(13.2)

    1.1(11.2)

    1.0(10.2)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    2.0(20.4)

    28

  • Outdoor Unit AE2MI56AHB Indoor Unit AWMI35AHL 1Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    5

    6

    4

    325

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    7

    9

    3

    5

    8

    10

    4

    6

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    8-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    25

    20C

    17C

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    30 35 40

    18

    20

    16

    14

    12

    10

    25

    Lo fan Hi fan

    27C

    24C

    Indoor air tem

    p.30

    Indoor air tem

    p.30C

    Indoor air tem

    p.30C

    27C

    24C

    20C

    17C

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    27C

    24C

    Indoor air

    temp.30

    Indoor air

    temp.30C

    Indoor air

    temp.30C

    27C

    24C

    27C

    24C

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    2020C

    17C

    Indoor

    air tem

    p.23

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    HH fan

    HH fan

    HH fan

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.1(11.2)

    1.2(12.2)

    1.0(10.2)

    0.9(9.2)

    4.0(40.8)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    29

  • Outdoor Unit AE2MI56AHB Indoor Unit AWI52AHL 1Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    7

    8

    6

    5

    25

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    10

    12

    6

    8

    9

    11

    7

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    8-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    20C

    1717C

    Indoor ai

    r temp.23

    Indoor ai

    r temp.23

    C

    Indoor ai

    r temp.23

    C

    20C

    17C

    30 35 40

    18

    20

    16

    14

    12

    10

    25

    Lo fan Hi fan

    2727C

    2424C

    Indoor air t

    emp.30

    Indoor air t

    emp.30C

    Indoor air t

    emp.30C

    27C

    24C

    20C

    17C

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    27C

    24C

    Indoor ai

    r temp.30

    Indoor ai

    r temp.30

    C

    Indoor ai

    r temp.30

    C

    27C

    24C

    2727C

    2424C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    1717C

    Indoor a

    ir temp.

    23

    Indoor a

    ir temp.

    23C

    Indoor a

    ir temp.

    23C

    20C

    17C

    HH fan

    HH fan

    HH fan

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.1(11.2)

    1.2(12.2)

    1.0(10.2)

    0.9(9.2)

    4.0(40.8)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    30

  • Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan HH fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    4

    5

    3

    225

    Lo fan Hi fan HH fan

    -5 0 5 10 15 20 25

    7

    8

    6

    5

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    8-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    25

    20C

    1717C

    Indoor ai

    r temp.23

    Indoor ai

    r temp.23

    C

    Indoor ai

    r temp.23

    C

    20C

    17C

    30 35 40

    20

    18

    16

    14

    12

    10

    25

    Lo fan Hi fan HH fan

    27C

    2424C

    Indoor a

    ir temp.

    30

    Indoor a

    ir temp.

    30C

    Indoor a

    ir temp.

    30C

    27C

    24C20C

    17C

    Indoor air tem

    p.23

    Indoor air tem

    p.23C

    Indoor air tem

    p.23C

    20C

    17C

    27C

    24C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    27C

    24C

    Indoor air temp.3

    0CIndoor a

    ir temp.30C

    27C

    24C

    20C

    1717C

    Indoor air temp.23

    Indoor air temp.23C

    Indoor air temp.23C

    20C

    17C

    Outdoor Unit AE3MI68AH Indoor Unit AWMI22AHL 15-1-3. Temperature Charts (AE3MI68AH)

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.2(12.2)

    1.3(13.2)

    1.1(11.2)

    1.0(10.2)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    2.0(20.4)

    31

  • Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    5

    6

    4

    325

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    7

    8

    6

    5

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    10-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    25

    20C

    17C

    Indoor air temp.

    23Indoor a

    ir temp.23C

    Indoor air temp.

    23C

    20C

    17C

    30 35 40

    20

    18

    16

    14

    12

    25

    Lo fan Hi fan

    27C

    24C

    Indoor air tem

    p.30

    Indoor air tem

    p.30C

    Indoor air tem

    p.30C

    27C

    24C20C

    17C

    Indoor ai

    r temp.23

    C

    Indoor ai

    r temp.23

    C

    20C

    17C

    27C

    24C

    Indoor a

    ir temp.

    30

    Indoor a

    ir temp.

    30C

    Indoor a

    ir temp.

    30C

    27C

    24C

    27C

    24C

    Indoor air tem

    p.30CIndoor

    air temp.30C

    27C

    24C

    2020C

    17C

    Indoor air tem

    p.23C

    Indoor air tem

    p.23C

    20C

    17C

    Outdoor Unit AE3MI68AH Indoor Unit AWMI27AHL 1

    HH fan

    HH fan

    HH fan

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.2(12.2)

    1.3(13.2)

    1.1(11.2)

    1.0(10.2)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    2.0(20.4)

    32

  • Outdoor Unit AE3MI68AH Indoor Unit AWMI35AHL 1Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    5

    6

    4

    325

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    7

    9

    3

    5

    8

    10

    4

    6

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    8-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    25

    20C

    17C

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    30 35 40

    18

    20

    16

    14

    12

    10

    25

    Lo fan Hi fan

    27C

    24C

    Indoor air tem

    p.30

    Indoor air tem

    p.30C

    Indoor air tem

    p.30C

    27C

    24C

    20C

    17C

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    27C

    24C

    Indoor air

    temp.30

    Indoor air

    temp.30C

    Indoor air

    temp.30C

    27C

    24C

    27C

    24C

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    2020C

    17C

    Indoor

    air tem

    p.23

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    HH fan

    HH fan

    HH fan

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.1(11.2)

    1.2(12.2)

    1.0(10.2)

    0.9(9.2)

    4.0(40.8)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    33

  • Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    7

    8

    6

    5

    25

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    10

    12

    6

    8

    9

    11

    7

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    8-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    20C

    17C

    Indoor ai

    r temp.23

    Indoor ai

    r temp.23

    C

    Indoor ai

    r temp.23

    C

    20C

    17C

    30 35 40

    18

    20

    16

    14

    12

    10

    25

    Lo fan Hi fan

    2727C

    2424C

    Indoor air t

    emp.30

    Indoor air t

    emp.30C

    Indoor air t

    emp.30C

    27C

    24C

    20C

    17C

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    27C

    24C

    Indoor ai

    r temp.30

    Indoor ai

    r temp.30

    C

    Indoor ai

    r temp.30

    C

    27C

    24C

    2727C

    2424C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    1717C

    Indoor a

    ir temp.

    23

    Indoor a

    ir temp.

    23C

    Indoor a

    ir temp.

    23C

    20C

    17C

    Outdoor Unit AE3MI68AH Indoor Unit AWI52AHL 1

    HH fan

    HH fan

    HH fan

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.1(11.2)

    1.2(12.2)

    1.0(10.2)

    0.9(9.2)

    4.0(40.8)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    34

  • Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    8

    9

    7

    6

    25

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    12

    14

    8

    10

    11

    13

    9

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    8-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    2020C

    1717C

    Indoor a

    ir temp.

    23

    Indoor a

    ir temp.

    23C

    Indoor a

    ir temp.

    23C

    20C

    17C

    30 35 40

    18

    20

    16

    14

    12

    10

    25

    Lo fan Hi fan

    2727C

    24C

    Indoor air temp.

    30CIndoor a

    ir temp.30C

    27C

    24C20

    C

    17C

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    27C

    24CInd

    oor air

    temp.3

    0C

    Indoor

    air tem

    p.30C

    27C

    24C

    27C

    24C

    Indoor air te

    mp.30

    Indoor air te

    mp.30C

    Indoor air te

    mp.30C

    27C

    24C

    20C

    17C

    Indoor a

    ir temp.

    23

    Indoor a

    ir temp.

    23C

    Indoor a

    ir temp.

    23C

    20C

    17C

    Outdoor Unit AE3MI68AH Indoor Unit AWI68AHL 1

    HH fan

    HH fan

    HH fan

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.1(11.2)

    1.2(12.2)

    1.0(10.2)

    0.9(9.2)

    4.0(40.8)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    35

  • Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan Hi fan HH fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    4

    5

    325 -5 0 5 10 15 20 25

    8

    9

    7

    6

    5

    4

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    5-5 0 5 10 15 20 25

    55

    50

    45

    40

    35

    30

    25

    20

    20C

    17C

    Indoor

    air tem

    p.23

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    30 35 40

    25

    20

    15

    10

    25

    2727C

    24C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    17C

    20C

    17C

    24C24C

    27C

    2424C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    1717C

    Indoo

    r air t

    emp.2

    3

    Indoo

    r air t

    emp.2

    3C

    Indoo

    r air t

    emp.2

    3C

    20C

    17C

    Outdoor Unit AE4MI80AH Indoor Unit AWMI22AHL 15-1-4. Temperature Charts (AE4MI80AH)

    Lo fan Hi fan Hi fan HH fan

    Lo fan Hi fan Hi fan HH fan

    27C

    27C

    Indoor

    air tem

    p.30

    Indoor

    air tem

    p.30C

    Indoor

    air tem

    p.30C

    Indoo

    r air t

    emp.2

    3

    Indoo

    r air t

    emp.2

    3C

    Indoo

    r air t

    emp.2

    3C

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.0(10.2)

    1.2(12.2)

    0.8(8.2)

    0.6(6.2)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    2.0(20.4)

    1.5(15.3)

    36

  • Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan Hi fan HH fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    4

    5

    325 -5 0 5 10 15 20 25

    7

    8

    6

    5

    4

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    5-5 0 5 10 15 20 25

    55

    50

    45

    40

    35

    30

    25

    20

    20C

    17C

    Indoor

    air tem

    p.23

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    30 35 40

    25

    20

    15

    10

    25

    2727C

    24C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    17CIn

    door

    air te

    mp.23

    Indoo

    r air t

    emp.2

    3C

    Indoo

    r air t

    emp.2

    3C

    20C

    17C

    24C

    24C

    27C

    2424C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    1717CInd

    oor a

    ir tem

    p.23C

    Indoo

    r air t

    emp.2

    3C

    20C

    17C

    Outdoor Unit AE4MI80AH Indoor Unit AWMI27AHL 1

    Lo fan Hi fan Hi fan HH fan

    Lo fan Hi fan Hi fan HH fan

    Indoor

    air tem

    p.30

    Indoor

    air tem

    p.30C

    Indoor

    air tem

    p.30C

    27C

    27C

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.0(10.2)

    1.2(12.2)

    0.8(8.2)

    0.6(6.2)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    2.0(20.4)

    1.5(15.3)

    37

  • Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 4025

    Lo fan Hi fan Hi fan HH fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    4

    5

    6

    325 -5 0 5 10 15 20 25

    12

    13

    10

    11

    9

    8

    7

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    5-5 0 5 10 15 20 25

    55

    50

    45

    40

    35

    30

    25

    20

    20C

    1717C

    Indoor

    air tem

    p.23

    Indoor

    air tem

    p.23C

    Indoor

    air tem

    p.23C

    20C

    17C

    30 35 40

    25

    20

    15

    10

    25

    2727C

    24C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    17C

    Indoo

    r air t

    emp.2

    3

    Indoo

    r air t

    emp.2

    3C

    Indoo

    r air t

    emp.2

    3C

    20C

    17C

    24C24C

    2727C

    2424C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    1717CIn

    door

    air t

    emp.2

    3

    Indoo

    r air t

    emp.2

    3C

    Indoo

    r air t

    emp.2

    3C

    20C

    17C

    Outdoor Unit AE4MI80AH Indoor Unit AWMI35AHL 1

    Lo fan Hi fan Hi fan HH fan

    Lo fan Hi fan Hi fan HH fan

    Indoor a

    ir temp.

    30

    Indoor a

    ir temp.

    30C

    Indoor a

    ir temp.

    30C

    27C27C

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.0(10.2)

    1.2(12.2)

    0.8(8.2)

    0.6(6.2)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    2.0(20.4)

    1.5(15.3)

    38

  • 30 35 4025

    Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    6

    5

    7

    8

    9

    425 -5 0 5 10 15 20 25

    14

    12

    13

    11

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    5-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    25

    2020C

    1717C

    Indoor a

    ir temp.

    23

    Indoor a

    ir temp.

    23C

    Indoor a

    ir temp.

    23C

    20C

    17C

    30 35 40

    25

    20

    15

    10

    25

    2727C

    24C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    17CIndo

    or air te

    mp.23

    Indoor a

    ir temp.

    23C

    Indoor a

    ir temp.

    23C

    20C

    17C

    24C24C

    2727C

    2424C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    17C

    Indo

    or a

    ir te

    mp.

    23C

    Indo

    or a

    ir te

    mp.

    23C

    20C

    17C

    Outdoor Unit AE4MI80AH Indoor Unit AWI52AHL 1

    Lo fan Hi fan

    Indoor a

    ir temp.

    30

    Indoor a

    ir temp.

    30C

    Indoor a

    ir temp.

    30CLo fan Hi fan

    27C27C

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.0(10.2)

    1.2(12.2)

    0.8(8.2)

    0.6(6.2)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    2.0(20.4)

    1.5(15.3)

    39

  • 30 35 4025

    Cooling Characteristics(RH : 46%, Indoor fan speed : High fan)(230V, 50Hz)

    Heating Characteristics(RH : 85%, Indoor fan speed : High fan)(230V, 50Hz)

    (1) Low pressure performance chart (1) High pressure performance chart

    (2) Operating current performance chart (2) Operating current performance chart

    (3) Indoor discharge air performance chart (3) Indoor discharge air performance chart

    This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

    Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)

    The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.

    NOTE

    Outdoor air temperature (C) Outdoor air temperature (C)

    Lo fan Hi fan

    -5 0 5 10 15 20 25

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Ope

    ratin

    g cu

    rren

    t (A

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    30 35 40

    9

    8

    10

    11

    12

    25 -5 0 5 10 15 20 25

    14

    12

    13

    11

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Indo

    or d

    isch

    arge

    air

    tem

    pera

    ture

    (C

    )

    Outdoor air temperature (C) Outdoor air temperature (C)

    5-5 0 5 10 15 20 25

    60

    55

    50

    45

    40

    35

    30

    25

    20C

    1717C

    Indoor a

    ir temp.

    23

    Indoor a

    ir temp.

    23C

    Indoor a

    ir temp.

    23C

    20C

    17C

    30 35 40

    25

    20

    15

    10

    25

    2727C

    24C

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    17C

    Indoor a

    ir temp.

    23

    Indoor a

    ir temp.

    23C

    Indoor a

    ir temp.

    23C

    20C

    17C

    2727C

    2424C

    Indoor air temp.30

    Indoor air temp.30C

    Indoor air temp.30C

    27C

    24C

    20C

    17C

    Indo

    or a

    ir te

    mp.

    23C

    Indo

    or a

    ir te

    mp.

    23C

    20C

    17C

    Outdoor Unit AE4MI80AH Indoor Unit AWI68AHL 1

    Lo fan Hi fan

    Indoor

    air tem

    p.30

    Indoor

    air tem

    p.30C

    Indoor

    air tem

    p.30C

    Lo fan Hi fan

    24C

    24C

    27C

    27C

    Low

    pre

    ssur

    e at

    wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    Hig

    h pr

    essu

    re a

    t wid

    e tu

    be s

    ervi

    ce v

    alve

    MP

    aG (

    kgf/c

    m2 G

    )

    1.0(10.2)

    1.2(12.2)

    0.8(8.2)

    0.6(6.2)

    3.5(35.7)

    3.0(30.6)

    2.5(25.5)

    2.0(20.4)

    1.5(15.3)

    40

  • WARNINGTo avoid electrical shock hazard, be sure todisconnect power before checking, servicingand/or cleaning any electrical parts.

    6. ELECTRICAL DATA6-1. Electric Wiring DiagramsOutdoor Unit AE2MI40AH

    8FA2-5257-56900-2

    YELBLUREDBLK

    WHT

    REA

    CTA

    NC

    E

    CO

    NT

    RO

    LLE

    R

    BLKBLK

    BLK

    BLK

    WH

    T

    COIL

    /OUT

    DOOR

    COILTHERMISTOR

    COMPRESSORTHERMISTOR

    WH

    T

    RED

    (2P)

    CO

    NN

    ECTO

    R

    (2P)

    CO

    NN

    ECTO

    R

    (4P) CONNECTORWHT

    OUTDOORTHERMISTOR

    COM

    P

    MAG

    NETI

    C CO

    IL(5P) CONNECTOR

    RED

    MV

    0

    TER

    MIN

    ALPL

    ATE

    1 2 3 4 5 6 7 8

    GN

    DA INDDORUNIT

    B INDDORUNIT

    TO INDDOR UNIT

    POWERSUPPLY

    NL

    WH

    T

    12

    34

    1 21

    12

    2

    YELYELBLKBLK

    YELYELBLKBLK

    1 12 2

    3 34 4

    A-TH

    AW THERMISTOR

    AN THERMISTOR

    (4P) CONNECTORRED

    12

    34

    YELYELYELYEL

    YELYELYELYEL

    1 12 2

    3 34 4

    B-TH

    BW THERMISTOR

    BN THERMISTOR

    (4P) CONNECTORBLU

    12

    34

    WW

    YELYELYELYEL

    YELYELYELYEL

    1 12 2

    3 34 4

    55

    GRYGRY

    5 55

    44

    BLKBLK

    4 44

    33

    YELYEL

    3 33

    22

    REDRED

    2 22

    11

    ORGORG

    1 11

    DEF1

    DEF0

    (2P) CONNECTORBLK

    BLKBLK

    BLUBLU

    DE

    F

    CO

    ILD

    EFR

    OST

    VAL

    VE

    2211

    WW

    RV1

    RV0

    (2P) CONNECTORWHT

    BLKBLK

    BLUBLU

    RV

    CO

    IL4W

    AY V

    ALVE

    2211

    WW

    L2L1

    E-2

    MV0

    MAG

    NETI

    C CO

    IL

    (5P) CONNECTOR

    BLUM

    V1

    FAN

    MO

    TOR

    5

    12

    34

    56

    7

    5

    GRYGRY

    5 55

    44

    BLKBLK

    4 44

    33

    YELYEL

    3 33

    22

    REDRED

    2 22

    11

    ORGORG

    1 11