TI365F/24/ae/03.09 Technical Information Prosonic M FMU40/41/42/43/44 Ultrasonic Level Measurement Compact transmitters for non-contact level measurement of fluids, pastes and coarse bulk materials FMU44 FMU43 FMU42 FMU41 FMU40 Application Continuous, non-contact level measurement in fluids, pastes, sullages and coarse bulk materials Flow measurement in open channels and measuring weirs System integration via: – HART ® (standard), 4 to 20mA – PROFIBUS ® PA –FOUNDATION™ Fieldbus Maximum measuring range: FMU 40: 16 ft (5 m) in fluids / 6 ft (2 m) in bulk materials FMU 41: 26 ft (8 m) in fluids / 12 ft (3.5 m) in bulk materials FMU 42: 33 ft (10 m) in fluids / 16 ft (5 m) in bulk materials FMU 43: 50 ft (15 m) in fluids / 23 ft (7 m) in bulk materials – FMU44: 65 ft (20 m) in fluids / 33 ft (10 m) in bulk materials Features and benefits Quick and simple commissioning via menu-guided local operation with four-line plain text display Envelope curves on the local display for simple diagnosis Easy remote operation, diagnosis and measuring point documentation with the supplied FieldCare operating program. Suitable for explosion hazardous areas (Gas-Ex, Dust-Ex) Linearization function (up to 32 points) for conversion of the measured value into any unit of length, volume or flow rate Non-contact measurement method minimizes service requirements Optional remote display and operation (up to 65 ft / 20 m) from transmitter) Installation possible from thread G 1½“, 1½" NPT, 2" NPT or universal slip-on flange Integrated temperature sensor for automatic correction of the temperature dependent sound velocity

Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Embed Size (px)

Citation preview

Page 1: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

TI365F/24/ae/03.09

Technical Information

Prosonic M FMU40/41/42/43/44

Ultrasonic Level Measurement

Compact transmitters for non-contact level measurement of fluids,

pastes and coarse bulk materials

FMU44FMU43FMU42FMU41FMU40

Application

• Continuous, non-contact level measurement in fluids,

pastes, sullages and coarse bulk materials

• Flow measurement in open channels and measuring

weirs

• System integration via:

– HART® (standard), 4 to 20mA

– PROFIBUS® PA

– FOUNDATION™ Fieldbus

• Maximum measuring range:

– FMU 40:

16 ft (5 m) in fluids / 6 ft (2 m) in bulk materials

– FMU 41:

26 ft (8 m) in fluids / 12 ft (3.5 m) in bulk

materials

– FMU 42:

33 ft (10 m) in fluids / 16 ft (5 m) in bulk

materials

– FMU 43:

50 ft (15 m) in fluids / 23 ft (7 m) in bulk

materials

– FMU44:

65 ft (20 m) in fluids / 33 ft (10 m) in bulk

materials

Features and benefits

• Quick and simple commissioning via menu-guided

local operation with four-line plain text display

• Envelope curves on the local display for simple

diagnosis

• Easy remote operation, diagnosis and measuring point

documentation with the supplied FieldCare operating

program.

• Suitable for explosion hazardous areas

(Gas-Ex, Dust-Ex)

• Linearization function (up to 32 points) for conversion

of the measured value into any unit of length, volume

or flow rate

• Non-contact measurement method minimizes service

requirements

• Optional remote display and operation (up to 65 ft /

20 m) from transmitter)

• Installation possible from thread G 1½“, 1½" NPT, 2"

NPT or universal slip-on flange

• Integrated temperature sensor for automatic

correction of the temperature dependent sound

velocity

Page 2: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

2 Endress+Hauser

Table of Contents

Function and system design. . . . . . . . . . . . . . . . . . . . . 3

Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Equipment architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Operating frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Load HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Output damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Linearization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Auxiliary energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Terminal compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Fieldbus plug connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Current consumption (2-wire-instruments) . . . . . . . . . . . . . . . . . 13

HART ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Max. noise HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Performance characteristics. . . . . . . . . . . . . . . . . . . . 13

Reaction time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Measured value resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Pulse frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Measuring error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Influence of the vapor pressure . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . 14

Installation variants FMU 40, FMU 41 . . . . . . . . . . . . . . . . . . . . 14

Installation variants FMU42, FMU44 . . . . . . . . . . . . . . . . . . . . . 15

Installation variants FMU 43 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Installation conditions for level measurements . . . . . . . . . . . . . . 15

Installation in narrow shafts . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Installation conditions for flow measurements . . . . . . . . . . . . . . . 16

Blocking distance, nozzle installation . . . . . . . . . . . . . . . . . . . . . 18

Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Resistance to alternating temperature cycles . . . . . . . . . . . . . . . . 19

Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Ingress protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . 19

Process conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Process temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Process pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 20

Design; dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Housing design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Process connection, sealing material, sensor material . . . . . . . . . 23

Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Display and operating elements . . . . . . . . . . . . . . . . . . . . . . . . . 24

Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Certificates and Approvals . . . . . . . . . . . . . . . . . . . . . 26

CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Hazardous area approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

External standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . 26

Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 27

Product structure FMU 40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Product structure FMU 41 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Product structure FMU 42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Product structure FMU 43 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Product structure FMU 44 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Weather protection cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Installation bracket for FMU 40/41 . . . . . . . . . . . . . . . . . . . . . . 34

Adapter flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Cantilever . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Mounting Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Wall Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Commubox FXA191 HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Commubox FXA195 HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Service Interface FXA193 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Remote display FHX40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Supplementary documentation . . . . . . . . . . . . . . . . . 40

System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Operating manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Description of device functions . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Short instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Safety Instructions ATEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Safety Instructions NEPSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Control drawings Installation drawings . . . . . . . . . . . . . . . . . . . . 43

Page 3: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 3

Function and system design

Measuring principle

L00-FMU4x-15-00-00-de-001

E: Empty distance; F: Span (full distance); D: Distance from sensor membrane - product surface; L: Level; BD: Blocking distance

Time-of-flight method

The sensor of the Prosonic M transmits ultrasonic pulses in the direction of the product surface. The pulses are

reflected back and received by the sensor. The Prosonic M measures the time t between pulse transmission and

reception. The instrument uses the time t (and the velocity of sound c) to calculate the distance D between the

sensor membrane and the product surface:

D = c ⋅ t/2

As the device knows the empty distance E from a user entry, it can calculate the level as follows:

L = E - D

An integrated temperature sensor compensates for changes in the velocity of sound caused by temperature

changes.

Interference echo suppression

The interference echo suppression feature on the Prosonic M ensures that interference echos (e.g. from edges,

welded joints and installations) are not interpreted as a level echo.

Calibration

Enter the empty distance E and the span F to calibrate the device.

Blocking distance

Span F may not extend into the blocking distance BD. Level echos from the blocking distance cannot be

evaluated due to the transient characteristics of the sensor.

20 mA100%

4 mA0%

D

L

FE

BD

Sensor BD Max. range fluids Max. range bulk materials

FMU40 9.8" (0.25 m) 16 ft (5 m) 6.5 ft (2 m)

FMU41 13.8" (0.35 m) 26 ft (8 m) 11.5 ft (3.5 m)

FMU42 15.7" (0.4 m) 33 ft (10 m) 16 ft (5 m)

FMU43 23.6" (0.6 m) 50 ft (15 m) 23 ft (7 m)

FMU44 19.7" (0.5 m) 65 ft (20 m) 33 ft (10 m)

Page 4: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

4 Endress+Hauser

Equipment architecture 4 to 20 mA output with HART protocol

The complete measuring system consists of:

L00-FMxxxxxx-14-00-06-en-007

If the HART communication resistor is not built into the supply unit, it is necessary to insert a communication

resistor of 250 Ω into the 2-wire line.

Local operation

• with display and operating module VU 331

• with a Personal Computer, FXA 193 and the operating software FieldCare

Remote operation

• with HART handheld terminal DXR 375

• with a Personal Computer, Commubox FXA 191 and the operating software COMMUWIN II respectively

FieldCare.

ENDRESS + HAUSER

E+–

%

ENDRESS + HAUSERRMA 422

1# % &

Copy

G H I

P Q R S

, ( ) ‘

A B C

Paste

PageOn

PageUp

DeleteBksp

Insert

J K L

T U V

_ < >

D E F

Hot Key

+ Hot Key

M N O

W X Y Z

+ * /

4

7

.

2

5

8

0

375FIELD COMMUNICATOR

3

6

9

-

9 6

DELTABAR: * * * * * * * *

ONLINE

1 QUICK SETUP

2 OPERATING MENU

4 SV 0 °C

3 PV 352 mbar

HELP SAVE

dsdmdmdf das.asdas faasas la.

1# % &

Copy

G H I

P Q R S

, ( ) ‘

A B C

Paste

PageOn

PageUp

DeleteBksp

Insert

J K L

T U V

_ < >

D E F

Hot Key

+ Hot Key

M N O

W X Y Z

+ * /

4

7

.

2

5

8

0

375FIELD COMMUNICATOR

3

6

9

-

9 6

DELTABAR: * * * * * * * *

ONLINE

1 QUICK SETUP

2 OPERATING MENU

4 SV 0 °C

3 PV 352 mbar

HELP SAVE

dsdmdmdf das.asdas faasas la.

FieldCare FieldCare

HART handheldDXR375FXA191/195

Field Communicator375

transmitter powersupply unitRMA422or RN221N(communication resistorincluded)

PLC

CommuboxFXA191/195

operating anddisplay moduleVU331

service adapter- FXA291/ToF Adapter FXA291- FXA193

Power supply(for 4-wire)

Page 5: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 5

System integration using PROFIBUS PA

A maximum of 32 transmitters (8 if mounted in an explosion hazardous location EEx ia IIC according to

FISCO-model) can be connected to the bus.The segment coupler provides the operating voltage to the bus.

Both on-site as well as remote operation are possible.

L00-FMxxXXXX-14-00-06-en-001

System integration using Foundation Fieldbus (FF)

A maximum of 32 transmitters (standard or EEx d) can be connected to the bus. For protection class EEx ia:

the maximum number of transmitters depends on the established rules and standards for intrinsically safe

circuits (EN 60070-14) and proof of instrinsic safety. Both local and remote operation are possible.

L00-FMxxXXXX-14-00-06-en-003

ENDRESS + HAUSER

service adapter- FXA291/ToF Adapter FXA291- FXA193

Micropilot MProsonic M

Levelflex M

ENDRESS + HAUSER

E+–

%

T

PROFIBUS DP

PROFIBUS PA

FieldCare

personal computer e.g. withFieldCare andProfibard resp. Proficard

segment coupler

PLC

operating anddisplay moduleVU331

MoreFunctions(valves etc)

T TFF link

service adapter- FXA291/ToF Adapter FXA291- FXA193

Levelflex M

ENDRESS + HAUSER

E+–

%

Prosonic MMicropilot M FieldCare

personal computere.g. withNI-FBUS configurator

operating anddisplay moduleVU331

power supply

power conditioner

power supply

power conditioner

Additionalfunctions(valves etc.)

Page 6: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

6 Endress+Hauser

System integration using Endress+Hauser Rackbus

You can interconnect a maximum of 64 2-wire devices with HART protocol to a Rackbus. Use an FXN 672

interface module for each device. You can integrate this bus into a higher-level bus by using a ZA gateway.

Gateways are available for MODBUS, FIP, PROFIBUS, INTERBUS etc. Both on-site and remote operation are

possible.

L00-FMxxXXXX-14-00-06-en-006

! Hinweis!

The FXN672 can be used with all 2-wire devices of the Prosonic M family.

FXN 671

mA1+

FXN 671

mA1+

FXN 671

mA1+

ZA 672 ZA 672

FXA193Micropilot M Prosonic M

Levelflex M

ENDRESS + HAUSER

E+–

%

FieldCare Package

personal computerwith Commuwin II

PLC

operating anddisplay moduleVU331

BusRS 232C

Gateway toMODBUS, FIP,PROFIBUS,INTERBUS etc.

FXN672

4…20 mA with HART

Page 7: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 7

System integration via Fieldgate

Vendor Managed Inventory

By using Fieldgate to interrogate tank or silo levels remotely, suppliers of raw materials can provide their regular

customers with information about the current supplies at any time and, for example, account for them in their

own production planning. For their part, the Fieldgate monitors the configured level limits and, if required,

automatically activates the next supply. The spectrum of options here ranges from a simple purchasing

requisition via e-mail through to fully automatic order administration by coupling XML data into the planning

systems on both sides.

Remote maintenance of measuring equipment

Fieldgates not only transfer the current measured values, they also alert the responsible standby personnel, if

required, via e-mail or SMS. In the event of an alarm or also when performing routine checks, service

technicians can diagnose and configure connected HART devices remotely. All that is required for this is the

corresponding HART operating software (e.g. FieldCare, ...) for the connected device. Fieldgate passes on the

information transparently, so that all options for the respective operating software are available remotely. Some

local service operations can be avoided by using remote diagnosis and remote configuration and all others can

at least be better planned and prepared.

L00-FXA520xx-14-00-06-en-009

! Note!

The number of instruments which can be connected in mutidrop mode can be calculated by the "FieldNetCalc"

program. A description of this program can be found in Technical Information TI 400F (Multidrop Conncector

FXN520). The program is available form your Endress+Hauser sales organization or in the internet at:

"www.endress.com � Download" (Text Search = "Fieldnetcalc").

-

FieldgateFXA520

ENDRESS+HAUSERRN 221N

ENDRESS+HAUSERRN 221N

.

FieldgateFXA520

20...45 VDC

FX

N5

20

FX

N5

20

Multidrop-ConnectorFXN520

HTTP scriptWeb browser…

AnalogEthernet

GSM

e.g. 2 x RN221N-B …

Channel 1 Channel 2

via HART Client:- FieldCare. . .

Remote monitoringRemote configuration/diagnostics

Page 8: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

8 Endress+Hauser

Input

Measured variable The distance D between the sensor membrane and the product surface is measured.

Using the linearisation function, the device uses D to calculate:

• level L in any units

• volume V in any units

• flow Q across measuring weirs or open channels in any units

Measuring range The measuring range is limited by the range of a sensor. The sensor range is, in turn, dependent on the

operating conditions. To estimate the actual range, proceed as follows (see also the calculation example in the

diagram):

1. Determine which of the influences shown in the following table are appropriate for your process.

2. Add the corresponding attenuation values.

3. From the total attenuation, use the diagram to calculate the range.

Fluid surface Attenuation

Calm 0 dB

Waves 5 to 10 dB

Strong turbulence (e.g. stirrers) 10 to 20 dB

Foaming Ask Endress+Hauser

Bulk material surface Attenuation

Hard, rough (e.g. rubble) 40 dB

Soft (e.g. peat, dust-covered clinker) 40 to 60 dB

Dust Attenuation

No dust formation 0 dB

Little dust formation 5 dB

Heavy dust formation 5 to 20 dB

Filling curtain in detection range Attenuation

None 0 dB

Small quantities 5 to 10 dB

Large quantities 10 to 40 dB

Temperature difference between

sensor and product surface

Attenuation

to 68°F (20°C) 0 dB

to 104°F (40°C) 5 to 10 dB

to 176°F (80°C) 10 to 20 dB

Page 9: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 9

L00-FMU4xxxx-05-00-00-en-002

Example (for FMU 43)

For typical solid applications, a certain amount of dust coverage is normally present. Therefore, the following

range results from the table and the diagram

These measuring conditions have been taken into account during the calculation of the maximum measuring

range in solid applications.

Operating frequency

• Dust-covered rubble approx. 50 dB

• no dust formation 0 dB

• No filling curtain in

detection range 0 dB

• Temperature diff. < 68°F (20°C) 0 dB

approx. 50 dB => range approx. 23 ft (7 m)

FMU 40

FMU 41

FMU 43

10 20 30 40 50 60 70 80

3 (1)

6 (2)

10 (3)

13 (4)

16 (5)

20 (6)

23 (7)

26 (8)

30 (9)

33 (10)

36 (11)

39 (12)

43 (13)

46 (14)

49 (15)

FMU 42

52 (16)

55 (17)

59 (18)

62 (19)

65 (20)FMU 44

Attenuation / dB

ran

ge

infe

et

(m)

Sensor Operating frequency

FMU40 approx. 70 kHz

FMU41 approx. 50 kHz

FMU42 approx. 42 kHz

FMU43 approx. 35 kHz

FMU44 approx. 30 kHz

Page 10: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

10 Endress+Hauser

Output

Output signal according to the instrument version ordered:

• 4 to 20 mA with HART protocol

• PROFIBUS PA

• Foundation Fieldbus (FF)

Signal on alarm Error information can be accessed via the following interfaces:

• Local display (error symbol, error code and plain text description)

• Current output (error current configurable)

• Digital interface

Load HART Minimum load for HART communication: 250 Ω

Output damping Freely selectable, 0 to 255 s

Linearization The linearization function of the Prosonic M allows conversion of the measured value into any unit of length

or volume. In open channels or measuring weirs, also a flow linearization is possible (calculation of the flow

from the measured level). The linearization table for calculating the volume in an horizontal cylindrical tank is

preprogrammed. You can also enter any number of other tables containing up to 32 value pairs either manually

or semi-automatically (by filling the vessel under controlled conditions).

The supplied FieldCare operating program can automatically calculate the table for any tank, weir or flume and

upload it into the device.

Flow curves for open channels can be calculated and entered into the instrument by FieldCare as well.

Auxiliary energy

Terminal compartment In the F12 housing, the terminals are located underneath the housing cover. In the T12 housing, they are under

the cover of the separate terminal compartment.

L00-FMR2xxxx-04-00-00-en-001

sealed terminalcompartment

F12 housing T12 housing

Page 11: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 11

Terminal assignment

• Connect the connecting line to the screw terminals (line cross-sections of 20 to 14 AWG / 0.5 to 2.5mm)

in the terminal compartment.

• Use 2-wire twisted pair cable with shield for the connection.

• Protective circuitry against reverse polarity, RFI and over-voltage peaks is built into the device (see also

Technical Information TI 241F/00/en "EMC Test Procedures")

The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the

auxiliary energy. Use 2-wire twisted pair cable with shield.

Refer to the following operating manuals for information on cable types, and how to set up and ground the

network:

• BA 198F/00/de „PROFIBIS -DP/-PA, Guidelines for planning and commissioning“

• BA 013S/04/en „Foundation Fieldbus, Installation and Commissioning Guidelines“

Fieldbus plug connectors For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected without opening

the housing.

4 to 20 mA with HART, 2-wire

L00-FMxxxxxx-04-00-00-en-015

4 to 20 mA active with HART, 4-wire

L00-FMxxxxxx-04-00-00-en-011

3 4I+ I-

1 2L- L+

4...20 mA

CommuboxFXA191/195DXR375

communicationresistor

(> 250 )�

alternatively

plantground

test sockets for testingof the signal current

power

5 6I+ I-

1 2L1/L+ N/L-

4...20mA

CommuboxFXA191/195DXR375

communicationresistor

(> 250 )�

alternatively

powerdisplay unit,recorder, PCS

AC / DCDC

plantground

PROFIBUS PA

L00-FMxxxxxx-04-00-00-en-012

FOUNDATION Fieldbus

L00-FMxxxxxx-04-00-00-en-013

3 41 2+–

T-BoxPROFIBUS PA

plantground

3 41 2+–

plantground

Page 12: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

12 Endress+Hauser

Pin assignment of the M12 plug connector (PROFIBUS PA plug)

Pin assignment of the 7/8" plug connector (FOUNDATION Fieldbus plug)

Supply voltage HART, 2-wire

The following values are the voltages across the terminals directly at the instrument:

HART, 4-wire, active

Terminals Cable cross-section: 0.5 to 2.5 mm (20 to 14 AWG)

L00-FMxxxxxx-04-00-00-yy-016

Pin Meaning

1 Ground

2 Signal +

3 Signal -

4 not connected

L00-FMxxxxxx-04-00-00-yy-017

Pin Meaning

1 Signal -

2 Signal +

3 not connected

4 ground

2

1 3

4+

nc

2

1 3

4+

– nc

VersionCurrent

consumption

Terminal voltage

minimum

Terminal voltage

maximum

2-wire HARTStandard

4 mA 14 V 36 V

20 mA 8 V 36 V

IS (EEx ia)4 mA 14 V 30 V

20 mA 8 V 30 V

XP (EEx d)4 mA 14 V 30 V

20 mA 11 V 30 V

Fixed current,

adjustable, e.g. for

solar power

operation

(measured value via

HART)

Standard 11 mA 10 V 36 V

IS (EEx ia) 11 mA 10 V 30 V

Fixed current for

HART multidrop

mode

Standard 4 mA1)

1) Start-up current 11 mA

14 V 36 V

IS (EEx ia) 4 mA1 14 V 30 V

Version Voltage max. load

DC 10.5 to 32 V 600 Ω

AC 50/60 Hz 90 to 253 V 600 Ω

Page 13: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 13

Cable entry • Cable gland: M20x1.5 (recommended cable diameter 6 to 10 mm)

• Cable entry G ½ or ½" NPT

• PROFIBUS-PA M12 plug

• Fieldbus Foundation 7/8" plug

Power consumption

Current consumption

(2-wire-instruments)

HART ripple 47 to 125 Hz: Vpp = 200 mV (measured at 500 Ω)

Max. noise HART 500 Hz tob 10 kHz: Vrms = 2.2 mV (measured at 500 Ω)

Galvanic isolation With 4-wire devices, the evaluation electronics and power voltage are galvanically isolated from each other.

Performance characteristics

Reaction time The reaction time depends on the parameter settings. The minimum values are:

• 2-wire devices (FMU40/41/42): min. 2 s

• 2-wire diveces (FMU43 - PROFIBUS PA or FOUNDATION Fieldbus): min. 2 s

• 2-wire devices (FMU44): min. 3 s

• 4-wire devices (FMU40/41/42/43/44): 0.5 s

Reference operating

conditions

• Temperature = +68°F (20°C)

• Pressure = 14.7 psia (1013 mbar abs.)

• Humidity = 50 %

• Ideal reflective surface (e.g. calm, smooth fluid surface)

• No interference reflections within signal beam

• Set application parameters:

– Tank shape = flat ceiling

– Medium property = liquid

– process conditions = calm surface

Measured value resolution

Version Power consumption

2-wire 51 mW to 800 mW

4-wire AC max. 4VA

4-wire DC; FMU 40/41 330 mW to 830 mW

4-wire DC; FMU 42/43 600 mW to 1 W

Communication Current consumption

HART 3.6 to 22 mA

PROFIBUS PA max. 13 mA

Foundation Fieldbus max. 15 mA

Sensor Measured value resolution

FMU40 0.04" (1 mm)

FMU41 0.04" (1 mm)

FMU42 0.08" (2 mm)

FMU43 0.08" (2 mm)

FMU44 0.08" (2 mm)

Page 14: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

14 Endress+Hauser

Pulse frequency • 2-wire devices (FMU40/41/42): max. 0.5Hz

• 2-wire devices (FMU43 - PROFIBUS PA or FOUNDATION Fieldbus): max. 0.5 Hz

• 2-wire devices (FMU44): max. 0.3 Hz

• 4-wire devices (FMU40/41/42/43/44): max. 2Hz

The exact values are dependent on the type of device and the parameter settings.

Measuring error Typical specifications for reference operating conditions (include linearity, repeatability, and hysteresis):

1whichever is greater

Influence of the vapor

pressure

The vapor pressure at 20°C (68°F) gives a hint on the accuracy of the ultrasonic level measurement. If the vapor

pressure at 20°C (68°F) is below 50 mbar (0.7 psi), ultrasonic level measurement is possible with very high

accuracy. This is valid for water, aqueous solutions, water-solid-solutions, dilute acids (hydrochloric acid,

sulfuric acid, ...), dilute bases (caustic soda, ...), oils, greases, slurries, pastes, ...

High vapor pressures or outgassing media (ethanol, acetone, ammonia, ...) can influence the accuracy. If

conditions like these are present, please contact the Endress+Hauser support.

Installation conditions

Installation variants FMU 40,

FMU 41

L00-FMU4xxxx-17-00-00-en-002

For installation bracket or adapter flange s. chapter "Accessories".

Sensor Measuring error

FMU40 ±0.08" (2mm) or 0.2% of set measuring distance (empty calibration)1

FMU41 ± 0.08" (2 mm) or 0.2% of set measuring distance (empty calibration)1

FMU42 ± 0.16" (4 mm) or 0.2% of set measuring distance (empty calibration)1

FMU43 ± 0.16" (4 mm) or 0.2% of set measuring distance (empty calibration)1

FMU44 ± 0.16" (4 mm) or 0.2% of set measuring distance (empty calibration)1

ENDRESS+HAUSERProsonic M

Installation with sleeveInstallation with counter nut

Installation with installation bracket

Counter nut (PC)suppliedfor G 1½” andG 2” instruments

Adapter flange

Sensor Nozzle

Sealing ring(EPDM)supplied

Installation with adapter flange

Sealing ring(EPDM)supplied

Page 15: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 15

Installation variants FMU42,

FMU44

L00-FMU42xxxx-17-00-00-en-001

Installation variants FMU 43

L00-FMU43xxxx-17-00-00-en-001

Installation conditions for

level measurements

L00-FMU4xxxx-17-00-00-de-005

• Do not install the sensor in the middle of the tank (3). We recommend leaving a distance between the sensor

and the tank wall (1) measuring 1/6 of the tank diameter.

• Use a protective cover, in order to protect the device from direct sun or rain (2).

• Avoid measurements through the filling curtain (4).

ENDRESS+HAUSER

Prosonic M

- .

Installation with universal flange Installation with mounting bracket

e.g. Zone 20 Zone 20

ENDRESS+HAUSER

Prosonic M

- .Zone 20

Installation withmounting bracket

Installation withuniversal slip-on flange (option)

slip-on flange

sensornozzle

e.g.Zone 20

1

2 3 4

5

6

1/6D

7

D

r

�L

Page 16: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

16 Endress+Hauser

• Make sure that equipment (5) such as limit switches, temperature sensors, etc. are not located within the

emitting angle α. In particular, symmetrical equipment (6) such as heating coils, baffles etc. can influence

measurement.

• Align the sensor so that it is vertical to the product surface (7).

• Never install two ultrasonic measuring devices in a tank, as the two signals may affect each other.

• To estimate the detection range, use the 3 dB emitting angle α.

Installation in narrow shafts

Installation conditions for flow

measurements

• Install the Prosonic M at the inflow side, as close above the maximum water level Hmax as possible (take into

account the blocking distance BD).

• Position the Prosonic M in the middle of the channel or weir.

• Align the sensor membrane parallel to the water surface.

• Keep to the installation distance of the channel or weir.

• You can enter the "Flow to Level" linearisation curve ("Q/h curve") using FieldCare or manually via the local

display.

Example: Khafagi-Venturi flume

L00-FMU4xxxx-17-00-00-en-003

Sensor α Lmax rmax

FMU40 11° 16 ft (5 m) 18.9" (0.48 m)

FMU41 11° 26 ft (8 m) 30.3 " (0.77 m)

FMU42 9° 33 ft (10 m) 31.1" (0.79 m)

FMU43 6° 50 ft (15 m) 31.1" (0.79 m)

FMU44 11 ° 65 ft (20 m) 76" (1.93 m)

In narrow shafts with strong interference echoes, we

recommend using an ultrasound guide pipe (e.g. PE

or PVC wastewater pipe) with a minimum diameter

of 4" (100 mm).

Make sure that the pipe is not soiled by accumulated

dirt. If necessary, clean the pipe at regular intervals.

L00-FMU4xxxx-17-00-00-en-010

ENDRESS+HAUSERProsonic MENDRESS+HAUSERProsonic M

ENDRESS+HAUSERProsonic MENDRESS+HAUSERProsonic M

ventinghole

1 x b0

b0

BD

Khafagi - Venturi - flumeDirection of flow

Inflow Outflow

Emptycalibr.

Hmax

Page 17: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 17

Example: Triangular weir

L00-FMU4xxxx-17-00-00-en-012

max

max

max

max

Empty calibr.

(= full calibr.)

min. 3 H

H

min. 2 H

min. 2 H

BD

Page 18: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

18 Endress+Hauser

Blocking distance,

nozzle installation

Install the Prosonic M at a height so that the blocking distance BD is not undershot, even at maximum fill level.

Use a pipe nozzle if you cannot maintain the blocking distance in any other way. The interior of the nozzle

must be smooth and may not contain any edges or welded joints. In particular, there should be no burr on the

inside of the tank side nozzle end. Note the specified limits for nozzle diameter and length. To minimize

disturbing factors, we recommend an angled nozzle edge (ideally 45°).

L00-FMU4xxxx-17-00-00-en-004

BD: blocking distance; SD: safety distance; E: empty calibration; F: full calibration (span); D: nozzle diameter; L: nozzle length

" Caution!

If the blocking distance is undershot, it may cause device malfunction.

! Note!

In order to notice if the level approaches the blocking distance, you can specify a safety distance (SD). If the

level is within this safety distance, the Prosonic M outputs a warning or alarm message.

FE

BD

SD

L

D

FMU 40/41

L

D

FMU 43

L

D

FMU 42/44

Maximum nozzle length

Nozzle diameter FMU40 FMU41 FMU42 FMU43 FMU44

DN50/2" 3.15" (80 mm)

DN80/3" 9.45" (240 mm) 9.45" (240 mm) 9.80" (250 mm)

DN100/4" 11.8" (300 mm) 11.8" (300 mm) 11.8" (300 mm) 11.8" (300 mm)

DN150/6" 15.7" (400 mm) 15.7" (400 mm) 15.7" (400 mm) 11.8" (300 mm) 15.7" (400 mm)

DN200/8" 15.7" (400 mm) 15.7" (400 mm) 15.7" (400 mm) 11.8" (300 mm) 15.7" (400 mm)

DN250/10" 15.7" (400 mm) 15.7" (400 mm) 15.7" (400 mm) 11.8" (300 mm) 15.7" (400 mm)

DN300/12" 15.7" (400 mm) 15.7" (400 mm) 15.7" (400 mm) 11.8" (300 mm) 15.7" (400 mm)

Emitting angle α 11° 11° 9° 6° 11°

Blocking distance 9.8" (0.25 m) 13.8" (0.35 m) 15.7" (0.4 m) 23.6" (0.6 m) 19.7" (0.5 m)

Max. range

in liquids

16 ft (5 m) 26 ft (8 m) 33 ft (10 m) 50 ft (15 m) 65 ft (20 m)

Max. range

in solids

6.5 ft (2 m) 11.5 ft (3.5 m) 16 ft (5 m) 23 ft (7 m) 33 ft (10 m)

Page 19: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 19

Ambient conditions

Ambient temperature -40 to +176°F (-40°C to +80°C)

The functionality of the LC display becomes restricted at Tu< -4°F (-20°C) and Tu> +140°F (+60°C).

If the device is operated outdoors in strong sunlight, you should use a protective cover.

Storage temperature -40 to +176°F (-40°C to +80°C)

Resistance to alternating

temperature cycles

to DIN EN 60068-2-14; Nb test : +80°C/-40°C, 1K/min, 100cycles

Climate class DIN EN 60068-2-38 (Test Z/AD) DIN/IEC 68 T2-30Db

Ingress protection • With closed housing, tested according to

– IP 68, NEMA 6P (24h at 1.83m under water surface)

– IP 66, NEMA 4x

• With open housing: IP 20, NEMA 1 (also ingress protection of the display)

" Caution!

Degree of protection IP 68 NEMA 6P applies for M12 PROFIBUS-PA plugs only when the PROFIBUS cable is

plugged in.

Vibration resistance DIN EN 60068-2-64 / IEC 68-2-64: 20 to 2000 Hz, 1 (m/s2)2/Hz; 3 x 100 min

Electromagnetic compatibility

(EMC)

• Interference emission to EN 61326, Equipment Class B

• Interference immunity to EN 61326, Appendix A (Industrial) and NAMUR Recommendation NE 21 (EMC).

• A standard installation cable is sufficient if only the analogue signal is used. Use a shielded cable when

working with a superimposed communication signal (HART).

Process conditions

Process temperature -40 to +176°F (-40°C to +80°C)

A temperature sensor is integrated in the sensor for correction of the temperature-dependent time-of-flight.

Process pressure • FMU 40/41: 10 to 44 psia (0.7 bar to 3bar abs.)

• FMU 42/43/44: 10 to 36 psia (0.7 bar to 2.5bar abs.)

Page 20: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

20 Endress+Hauser

Mechanical construction

Design; dimensions FMU40, FMU41

L00-FMU4xxxx-06-00-00-yy-006

Dimensions in inches (mm)

FMU42, FMU44 with slip-on flange

L00-FMU4xxxx-06-00-00-yy-007

Dimensions in inches (mm)

2.6”65( )

2.6”65( )

3.1”78( )

3.1”78( )

Ø( )

5.1”129

Ø( )

5.1”129

3.4”(~~86)

3.3”85( )

3.3”85( )

6.4”162( )

5.9”150( )

2.7”(68)

3.7”94( )

~( )5.8”148

~( )5.8”148

~( )3.3”83

FMU 40 FMU 41

Ø( )1.5”39 Ø 1.9”

( )50

~3.4”87~( )

0.9”22( )

0.9”22( )

ENDRESS+HAUSERProsonic M ENDRESS+HAUSER

Prosonic M

1.3”32( )

F12 T12

AF 60

2” NPTG2”

AF 60

1-½ NPT(G1½”)

~( )

4.3”110

Ø( )2.8”70

FMU 42 FMU 44

Ø( )3.9”98

~( )

4.2”107

~( )

5.7”145

2.6”65( )

2.6”65( )

3.1”78( )

3.1”78( )

Ø( )

5.1”129

Ø( )

5.1”129

3.4”(~~86)

3.3”85( )

3.3”85( )

3.3”85( )

6.4”162( )

5.9”150( )

2.7”(68)

3.7”94( )

ENDRESS+HAUSERProsonic M ENDRESS+HAUSER

Prosonic M

1.3”32( )

F12 T12

Page 21: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 21

FMU42, FMU44 with mounting bracket

L00-FMU4xxxx-06-00-00-yy-008

Dimensions in inches (mm)

FMU43

L00-FMU4xxxx-06-00-00-yy-009

Dimensions in inches (mm);A: with slip-on flange; B: with mounting bracket

Mounting bracket for FMU42, FMU43 and FMU44

L00-FMU4xxxx-06-00-00-yy-010

Dimensions in inches (mm)

ENDRESS+HAUSERProsonic M

F12/T12

3.0”75( )

3.0”75( )

4.7”119( ) 4.7”

119( )

M8

4.1”105( )

FMU 42

ENDRESS+HAUSERProsonic M

FMU 44

F12/T12

M8

4.9”125( )

1.2”30( )

1.2”30( )

3.3”85( )

2 x M8

3.1”78( )

2.6”65( )

Ø( )

5.1”129

~( )3.4”86

5.9”150( )

3.0”75( )

3.5”89( )6.2”158( )

~( )9.8”248

ENDRESS+HAUSERProsonic M

ENDRESS+HAUSER

Prosonic M

Ø( )

9.1”230

F12

A

ANSI 4” (DN 100)

B

4.68"(119)

4.72"(120)

0.98"(25)

4.84"(123)

0.08"(2) 0.98"

(25)

0.43"(11)

1.57"(40)

1.57"(40)

Page 22: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

22 Endress+Hauser

Flanges for FMU42 and FMU44

L00-FMU4xxxx-06-00-00-yy-011

Weight

suitable for A B C D E number of

boreholes

3" 150lbs / DN80 PN16 / 10K 80 150 mm

(5.91")

160 mm

(6.30")

200 mm

(7.87")

19 mm

(0.75")

45° 8

4" 150 lbs / DN100 PN16 / 10K 100 175 mm

(6.90")

190.5 mm

(7.50")

228.6 mm

(9.00")

19 mm

(0.75")

45° 8

6" 150 lbs / DN150 PN16 / 10 K 150 240 mm

(9.45")

241.3 mm

(9.50")

285 mm

(11.22")

23 mm

(0.91")

45° 8

8" 150 lbs 298.5 mm

(11.75")

298.5 mm

(11.75")

342.9 mm

(13.50")

22.5 mm

(0.89")

45° 8

DN200 PN16 / 10 K 200 290 mm

(11.42")

295 mm

(11.61")

340 mm

(13.39")

23 mm

(0.91")

30° 12

G2”ISO228

0.79”20( )

C

E

A

B

D

Sensor Weight

FMU40 approx. 5.5 lb (2.5 kg)

FMU41 approx. 6 lb (2.6 kg)

FMU42 approx. 6.6 lb (3 kg)

FMU43 approx. 8 lb (3.5 kg)

FMU44 approx. 9 lb (4 kg)

Page 23: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 23

Housing design Types of housings

• F12 housing with sealed terminal compartment for standard or EEx ia (intrinsically safe) applications

• T12 housing with separate terminal compartment and explosion proof encapsulation

Material

Aluminum, seawater resistant, powder-coated

Cover

• Aluminum, for version without local display

• Inspection glass for version with local display. This version cannot be supplied together with the ATEX II 1/

2 D certificate.

Process connection,

sealing material,

sensor material

Sensor Process connection Material in contact with process

FMU40 • Thread G 1½“

• Thread NPT 1½“ - 11.5

Sensor: PVDF

Seal: EPDM

FMU41 • Thread 2"

• Thread NPT 2" - 11.5

Sensor: PVDF

Seal: EPDM

FMU42 • Universal flange

DN 80 PN16 / ANSI 3" 150 lbs / JIS 10K 80

• Universal flange

DN 100 PN16 / ANSI 4" 150 lbs / JIS 10K 100

• Mounting bracket

Sensor: PVDF

Seal: VITON or EPDM

Flange: PP, PVDF or SS 316L (1.4435

or 1.4404)1)

1) Endress+Hauser supplies DIN/EN flanges made of stainless steel AISI 316L with the material number 1.4435 or

1.4404. With regard to their temperature stability properties, the materials 1.4435 and 1.4404 are grouped under

13E0 in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.

FMU43 • Universal flange

DN 100 / ANSI 4" / JIS16K100

• Mounting bracket

Sensor: UP and SS 316Ti

Seal: EPDM

Flange: PP or SS 316Ti

FMU44 • Universal flange

DN 100 PN16 / ANSI 4" 150 lbs / JIS 10K 100

• Universal flange

DN 150 PN16 / ANSI 6" 150 lbs / JIS 10K 150

• Universal flange

DN200 PN16 / JIS 10K 200

• Flange ANSI 8" 150 lbs

• Mounting bracket

Sensor PVDF

Seal: VITON or EPDM

Flange: PP, PVDF or SS 316L (1.4435

or 1.4404)1

Page 24: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

24 Endress+Hauser

Human interface

Display and operating

elements

The LCD module VU 331 for display and operation is located beneath the housing cover. The measured value

is legible through the glass in the cover. Open the cover to operate the device.

L00-FMxxxxxx-07-00-00-en-001

Function of the keys

Symbol in display

continuous flashing

Meaning Alarm Warning Communication Security Locking

Key(s) Meaning

O or V Navigate upwards in the selection list

Edit numeric value within a function

S or W Navigate downwards in the selection list

Edit numeric value within a function

X or Z Navigate to the left within a function group

F Navigate to the right within a function group, confirmation.

O and For

S and FContrast settings of the LCD

O and S and F

Hardware lock / unlock

After a hardware lock, an operation of the instrument via display or

communication is not possible!

The hardware can only be unlocked via the display. An unlock parameter must

be entered to do so.

ENDRESS + HAUSER

E+–

ENDRESS+HAUSER

MICROPILOT II

ENDRESS+HAUSER

MICROPILOT II

IP 65IP 65

Order Code:Ser.-No.:

Order Code:Ser.-No.:

Messbereich

Measuring range

Messbereich

Measuring rangeU 16...36 V DC

4...20 mA

U 16...36 V DC

4...20 mA

max. 20 m

max. 20 m

Ma

de

inG

erm

an

yM

au

lbu

rgM

ad

ein

Ge

rma

ny

Ma

ulb

urg

T>70°C :

A

t >85°C

T>70°C :

A

t >85°C

LCD

(liquid crystal display)

Symbols

3 keys

snap-fit

Page 25: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 25

Local operation Operation with VU 331

The LC-Display VU 331 allows configuration via 3 keys directly at the instrument. All device functions can be

set through a menu system. The menu consists of function groups and functions. Within a function, application

parameters can be read or adjusted. The user is guided through a complete configuration procedure.

L00-FMU4xxxx-07-00-00-en-004

Operation with the handheld terminal DXR 375

On devices with HART communication, you can also access the menu using the handheld terminal DXR 375.

L00-FMU4xxxx-07-00-00-de-005

XX

X

XS

S

OO FF

F

F

HOME

FG00 F000 F001 F002 F003 F004 ...

FG01

FG02

FG03

FG04

FG05

FG06

FG07

...

ENDRESS + HAUSER

E+–

Headline Position indicator

Main value UnitSymbol

Selection list

Function groups -> Functions

Help text

Envelopecurve

1# % &

Copy

G H I

P Q R S

, ( ) ‘

A B C

Paste

PageOn

PageUp

DeleteBksp

Insert

J K L

T U V

_ < >

D E F

Hot Key

+ Hot Key

M N O

W X Y Z

+ * /

4

7

.

2

5

8

0

375FIELD COMMUNICATOR

3

6

9

-

9 6

FMU42: LIC0001

ONLINE

1 GROUP SELECT

2 PV 8.7 m

HELP SAVE

dsdmdmdf das.asdas faasas la.

PageOn

PageUp

Bksp

Delete

Delete

FMU43: LIC0001

ONLINE

1 GROUP SELECTION

2 PV 8.7 m

HELP SAVE

dsdmdmdf das.asdas faasas la.

FMU43: LIC0001

GROUP SELECTION

HOMESAVE

dsdmdmdf das.asdas faasas la.H

FMRU43: LIC0001

HOMESAVE

dsdmdmdf das.asdas faasas la.H

Bksp

1 BASIC SETUP

2 SAFETY SETTINGS

BASIC SETUP

1 MEASURED VALUE

4 PROCESS COND.

5 EMPTY CALIBR.

3 MEDIUM PROPERTY

4 LINEARIZATION

5 EXTENDED CALIBR.

3 TEMPERATURE

2 TANK SHAPE

Page 26: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

26 Endress+Hauser

Remote operation Operation with FieldCare

FieldCare is Endress+Hauser's FDT based Plant Asset Management Tool. It can configure all intelligent field

devices in your plant and supports you in managing them. By using status information, it also provides a simple

but effective means of checking their health.

• Supports Ethernet, HART, PROFIBUS, FOUNDATION Fieldbus etc.

• Operates all Endress+Hauser devices

• Operates all third-party actuators, I/O systems and sensors supporting the FDT standard

• Ensures full functionality for all devices with DTMs

• Offers generic profile operation for any third-party fieldbus device that does not have a vendor DTM

Operation with Commuwin II (for communication variants HART or PROFIBUS-PA)

Commuwin II is an operating software with graphical support (MS Windows) for intelligent transmitters with

the communication protocols Rackbus, Rackbus RS-485, HART and PROFIBUS-PA.

Commuwin II supports the following functions:

• Online configuration of transmitters

• Loading and saving of instrument data (Upload/Download)

• Orderly visualisation of measured values and limit values

• Display and recording of measured values with a line recorder

It is not possible to display envelope curves with Commuwin II. To display them, please use the ToF Tool

program supplied.

Connections:

• HART with Commubox FXA 191 (available as accessory)

• PROFIBUS PA

Operation with NI-FBUS Configurator (only Foundation Fieldbus)

The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops, and a schedule

based on the fieldbus concepts.

You can use the NI-FBUS Configurator to configure a fieldbus network as follows:

• Set block and device tags

• Set device addresses

• Create and edit function block control strategies (function block applications)

• Configure vendor-defined function and transducer blocks

• Create and edit schedules

• Read and write to function block control strategies (function block applications)

• Invoke Device Description (DD) methods

• Display DD menus

• Download a configuration

• Verify a configuration and compare it to a saved configuration

• Monitor a downloaded configuration

• Replace devices

• Save and print a configuration

Certificates and Approvals

CE mark The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the

instrument passing the required tests by attaching the CE-mark.

Ex approval The available certificates are listed in the ordering information. Note the associated safety instructions (XA) and

control or installation drawings (ZD).

External standards and

guidelines

EN 60529

Protection class of housing (IP-code)

EN 61326

Electromagnetic compatibility (EMC requirements)

NAMUR

Standards committee for measurement and control in the chemical industry

Page 27: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 27

Ordering information

Product structure FMU 40 Certificates

A Variant for non-hazardous area

E NEPSI Ex nA II T6

G ATEX II 3G EEx nA II T6

I NEPSI Ex ia IIC T6

J NEPSI Ex d(ia) IIC T6

K TIIS Ex ia II C T6

N CSA General Purpose

Q NEPSI DIP

S FM IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2

T FM XP Cl. I,II,III Div. 1 Gr. A-G

U CSA IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2

V CSA XP Cl. I,II,III Div. 1 Gr. A-G

1 ATEX II 1/2 G or II 2 G; EEX ia IIC T6

2 ATEX II 1/2D, Alu blind cover

4 ATEX II 1/2 G or II 2 G; EEX d [ia] IIC T6

5 ATEX II 1/3D

Y Special certificate

Process connection

R G 1½“ threadISO 228

N NPT 1½“ - 11,5 thread

Y Special version

Power supply/communication

B 2 wire, 4...20mA-loop/HART

H 4 wire, 10,5...32VDC / 4-20mA HART

G 4 wire, 90...253VAC / 4-20mA HART

D 2 wire, PROFIBUS PA

F 2 wire, Foundation Fieldbus

Y Special version

Display / on-site operation

1 Without LC display

2 With LC display VU 331 incl. on-site operation

3 Prepared for remote display FHX 40

9 Special version

Housing

A Aluminum F12 housing coated to IP 68

C Aluminum T12 housing coated to IP 68; with separate terminal compartment

D Aluminum T12 housing coated to IP 68; with separate terminal compartment;

with overvoltage protection

9 Special version

Screw union/entry

2 M20x1.5 screw union

3 G 1/2“ entry

4 NPT 1/2“ entry

5 M12 PROFIBUS-PA plug-in connector

6 7/8" FF plug

9 Special version

FMU 40 - Product designation

Page 28: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

28 Endress+Hauser

Product structure FMU 41 Certificates

A Variant for non-hazardous area

E NEPSI Ex nA II T6

G ATEX II 3G EEx nA II T6

I NEPSI Ex ia IIC T6

J NEPSI Ex d(Ia) IIC T6

K TIIS Ex ia II C T6

N CSA General Purpose

Q NEPSI DIP

S FM IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2

T FM XP Cl. I,II,III Div. 1 Gr. A-G

U CSA IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2

V CSA XP Cl. I,II,III Div. 1 Gr. A-G

1 ATEX II 1/2 G or II 2 G; EEX ia IIC T6

2 ATEX II 1/2D, Alu blind cover

4 ATEX II 1/2 G or II 2 G; EEX d [ia] IIC T6

5 ATEX II 1/3D

Y Special certificate

Process connection

R G 2“ threadISO 228

N NPT 2“ - 11.5 thread

Y Special version

Power supply/communication

B 2 wire, 4...20mA-loop/HART

H 4 wire, 10.5...32VDC / 4-20mA HART

G 4 wire, 90...253VAC / 4-20mA HART

D 2 wire, PROFIBUS PA

F 2 wire, Foundation Fieldbus

Y Special version

Display / on-site operation

1 Without LC display

2 With LC display VU 331 incl. on-site operation

3 Prepared for remote display FHX 40

9 Special version

Housing

A Aluminum F12 housing coated to IP 68

C Aluminum T12 housing coated to IP 68 with separate terminal compartment

D Aluminum T12 housing coated to IP 68; with separate terminal compartment;

with overvoltage protection

9 Special version

Screw union/entry

2 M20x1.5 screw union

3 G 1/2“ entry

4 NPT 1/2“ entry

5 M12 PROFIBUS-PA plug-in connector

6 7/8" FF plug

9 Special version

FMU 41 - Product designation

Page 29: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 29

Product structure FMU 42 Certificates

A Variant for non-hazardous area

E NEPSI Ex nA II T6

G ATEX II 3G EEx nA II T6

I NEPSI Ex ia IIC T6

J NEPSI Ex d (Ia) IIC T6

K TIIS Ex ia II C T6 (in preparation)

N CSA General Purpose

Q NEPSI DIP

S FM IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2

T FM XP Cl. I,II,III Div. 1 Gr. A-G

U CSA IS Cl. I,II,III Div. 1 Gr. A-G / NI Cl. I Div. 2

V CSA XP Cl. I,II,III Div. 1 Gr. A-G

1 ATEX II 1/2 G EEX ia IIC T6

2 ATEX II 1/2 D, Alu bond cover

4 ATEX II 1/2 G EEX d [ia] IIC T6

5 ATEX II 1/3D

Y Special certificate

Process connection

M Mounting bracket FAU20

P UNI flange 3"/DN80/80, PP, max. 2.5bar abs./ 36psia

suitable for 3" 150lbs / DN80 PN16 / 10K 80

Q UNI flange 3"/DN80/80, PVDF, max. 2.5bar abs./ 36psia

suitable for 3" 150lbs / DN80 PN16 / 10K 80

S UNI flange 3"/DN80/80, 316L, max. 2.5bar abs./ 36psia

suitable for 3" 150lbs / DN80 PN16 / 10K 80

T UNI flange 4"/DN100/100, PP, max. 2.5bar abs./ 36psia

suitable for 4" 150lbs / DN100 PN16 / 10K100

U UNI flange 4"/DN100/100, PVDF, max. 2.5bar abs./ 36psia

suitable for 4" 150lbs / DN100 PN16 / 10K100

V UNI flange 4"/DN100/100, 316L, max. 2.5bar abs./ 36psia

suitable for 4" 150lbs / DN100 PN16 / 10K100

Y Special version

Power supply/communication

B 2 wire, 4...20mA-loop/HART

H 4 wire, 10.5...32VDC / 4-20mA HART

G 4 wire, 90...253VAC / 4-20mA HART

D 2 wire, PROFIBUS PA

F 2 wire, Foundation Fieldbus

Y Special version

Display / on-site operation

1 Without LC display

2 With LC display VU 331 incl. on-site operation

3 Prepared for remote display FHX 40

9 Special version

Housing

A Aluminum F12 housing coated to IP 68

C Aluminum T12 housing coated to IP 68, with separate terminal compartment

D Aluminum T 12 housing coated to IP 68, with separate terminal compartment; with

overvoltage protection

Y Special version

Gland/Entry

2 M20x1.5 gland

3 G 1/2“ entry

4 NPT 1/2“ entry

5 M12 PROFIBUS-PA plug

6 7/8" FF plug

9 Special version

Sealing Sensor/Flange

2 VITON flat sealing

Page 30: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

30 Endress+Hauser

3 EPDM flat sealing

9 special version

Additional options

A Additional options not selected

FMU 42 - Product designation

Sealing Sensor/Flange

Page 31: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 31

Product structure FMU 43 Certificates

A Variant for non-hazardous area

M FM DIP Class II, III, Div. 1, Gr. E,F,G NI

N CSA General Purpose

P CSA DIP, Class II, III, Div. 1, Gr. E,F,G NI

Q NEPSI DIP

2 ATEX II 1/2 D or II 2 D, Aluminium Deckel

5 ATEX II 1/3 D or II 3 D, Sichtdeckel

Y Special version

Process connection/material

P Flange DN 100/ANSI 4"/JIS 16K100, PP (universal slip-on flange included)

S Flange DN 100/ANSI 4"/JIS 16K100, SS 316TI (universal slip-on flange included)

K Without slip-on flange/without mounting bracket (customer mounting equipment)

M With mounting bracket

Y Special version

Power supply/communication

H 4 wire, 10.5...32VDC / 4-20mA HART

G 4 wire, 90...253VAC / 4-20mA HART

D 2 wire, PROFIBUS PA

F 2 wire, Foundation Fieldbus

Y Special version

Display / on-site operation

1 Without LC display

2 With LC display VU 331 incl. on-site operation

3 Prepared for remote display FHX 40

9 Special version

Housing

A Aluminium F12 housing coated to IP 68

9 Special version

Screw union/entry

2 M20x1.5 screw union

3 G 1/2“ entry

4 NPT 1/2“ entry

5 M12 PROFIBUS-PA plug-in connector

6 7/8" FF plug

9 Special version

FMU 43 - Product designation

Page 32: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

32 Endress+Hauser

Product structure FMU 44 Approval

A Non-hazardous area

1 ATEX II 1/2G EEx ia IIC T6 (in preparation)

4 ATEX II 1/2G EEx d (ia) IIC T6 (in preparation)

G ATEX II 3 G EEx nA II T6 (in preparation)

2 ATEX II 1/2 D, Alu blind cover (in preparation)

5 ATEX II 1/3 D

S FM IS Cl.I,II,III Div.1 Gr.A-G, NI Cl.I Div.2 (in preparation)

T FM XP Cl.I,II,III Div.1 Gr.A-G (in preparation)

N CSA General Purpose

U CSA IS Cl.I,II,III Div.1 Gr.A-G, NI Cl.I Div.2

V CSA XP Cl.I,II,III Div.1 Gr.A-G

K TIIS EEx ia IIC T6 (in preparation)

I NEPSI Ex ia IIC T6 (in preparation)

J NEPSI Ex d(ia) IIC T6 (in preparation)

E NEPSI Ex nA II T6 (in preparation)

Q NEPSI DIP (in preparation)

Y Special version, to be specified

Process connection

A 8" 150lbs FF, 316L, max 2.5bar abs./36psia

E UNI flange 6"/DN150/150, PP, max 2.5bar abs./ 36psia,

suitable for 6" 150lbs / DN150 PN16 / 10K 150

F UNI flange 6"/DN150/150, PVDF, max 2.5bar abs./36psia,

suitable for 6" 150lbs /DN150 PN16 / 10K 150

G UNI flange 6"/DN150/150, 316L, max 2.5bar abs. 36psia,

suitable for 6" 150lbs / DN150 PN16 / 10K 150

H UNI flange DN200/200, PP, max 2.5bar abs./ 36 psia,

suitable for DN200 PN16 / 10K 200

J UNI flange DN200/200, PVDF, max 2.5bar abs./ 36psia,

suitable for DN200 PN16 / 10K 200

K UNI flange DN200/200, 316L, max 2.5bar abs./ 36psia,

suitable for DN200 PN16 / 10K 200

L 8" 150lbs FF, PP, max 2.5bar abs./ 36psia

M Mounting bracket FAU20

N 8" 150lbs FF, PVDF, max 2.5bar abs./ 36psia

T UNI flange 4"/DN100/100, PP, max 2.5bar abs./ 36psia,

suitable for 4" 150lbs / DN100 PN16 / 10K 100

U UNI flange 4"/DN100/100, PVDF, max. 2.5bar abs./ 36 psia,

suitable for 4" 150lbs / DN100 PN16 / 10K 100

V UNI flange 4"/DN100/100, 316L, max 2.5bar abs./ 36psia,

suitable for 4" 150lbs / DN100 PN16 / 10K 100

Y Special version, to be specified

Power supply; Output

B 2-wire; 4-20mA HART

D 2-wire; PROFIBUS PA

F 2-wire; FOUNDATION Fieldbus

G 4-wire 90-250VAC; 4-20mA HART

H 4-wire 10.5-32VDC; 4-20mA HART

Y Special version, to be specified

Operation

1 w/o display, via communication

2 4-line display VU331, Envelope curve display on site

3 Prepared for FHX40, Remote display (accessory)

9 Special version, to be specified

FMU 44 - product designation, part 1

Page 33: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 33

Scope of delivery • Instrument according to the version ordered

• FieldCare software

• Operating manual according to the communication version

• for certified instrument versions: Safety Instructions, Control- or Installation drawings

• for FMU 40 *R**** and FMU 41 *R****: counter nut (PC)

• for FMU 40/41: sealing ring (EPDM)

• for gland M20x1.5:

– 1 cable gland for 2-wire instruments

– 2 cable glands for 4-wire instruments

The cable glands are mounted on delivery.

Housing

A F12 Alu, coated IP68 NEMA6P

C T12 Alu, coated IP68 NEMA6P, Separate conn. compartment

D T12 Alu, coated IP68 NEMA6P + OVP, Sep. conn. compartment, OVP = overvoltage

protection

9 Special version, to be specified

CAble entry

2 Gland M20 (EEx d > thread M20)

3 Thread G1/2

4 Thread NPT 1/2

5 Plug M12

6 Plug 7/8“

9 Special version, to be specified

Process Sealing Sensor/ Flange

2 Viton

3 EPDM

9 Special version, to be specified

Additional option

A Basic version

Y Special version, to be specified

FMU 44 - complete product designation

Page 34: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

34 Endress+Hauser

Accessories

Weather protection cover A Weather protection cover made of stainless steel is recommended for outdoor mounting (order code:

543199-0001). The shipment includes the protective cover and tension clamp.

L00-FMR2xxxx-00-00-06-en-001

Installation bracket for

FMU 40/41

L00-FMU4x-00-00-00-de-001

• for FMU 40, G1½: Order No. 942669-0000

• for FMU 41, G2: Order No. 942669-0001

suited for NPT 1½" and 2" as well

ENDRESS+HAUSER

MICROPILOT II

ENDRESS+HAUSER

MICROPILOT II

IP 65

Order Code:Ser.-No.:

Order Code:Ser.-No.:

Messbereich

Measuring range

Messbereich

Measuring rangeU 16...36 V DC

4...20 mA

U 16...36 V DC

4...20 mA

max. 20 m

max. 20 m

Made

inG

erm

any

Maulb

urg

Made

inG

erm

any

Maulb

urg

T>70°C :

A

t >85°C

T>70°C :

A

t >85°C

F12 / F23 / T12 housing

15.7"(400)

9.84"(250)

1.18"(30)

0.12"(3)

4.72"(120)

4.72"(120)

� 0.63"(16)

Page 35: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 35

Adapter flange

L00-FMUX3XXX-00-00-00-en-001

Version with metrical thread (FAU 70 E)

Version with conical thread(FAU 70 A)

Process Connection

12 DN 50 PN 16 A, flange EN1092-1 (DIN2527 B)

14 DN 80 PN 16 A, flange EN1092-1 (DIN2527 B)

15 DN 100 PN 16, A, flange EN1092-1 (DIN2527 B)

Sensor Connection

3 Thread ISO228 G1-1/2

4 Thread ISO228 G2

Flange Material

2 316L

7 Polypropylene

FAU 70 E Product designation

Process Connection

22 2" 150lbs FF, flange ANSI B16.5

24 3" 150lbs FF, flange ANSI B16.5

25 4" 150lbs FF, flange ANSI B16.5

Sensor Connection

5 Thread NPT1-1/2

6 Thread NPT2

Flange Material

2 316L

7 Polypropylene

FAU 70 A Product designation

adapter flangesealing ringEPDM(supplied)

sensor nozzle

Page 36: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

36 Endress+Hauser

Cantilever

L00-FMU4xxxx-06-00-00-yy-005

• The 1.97" (50 mm) or 2.44" (62 mm) orifices serve for the mounting of the FMU 40 or FMU 41 sensor,

respecitvely.

• The 0.87" (22 mm) orifice may be used for an additional sensor.

A B C D for Sensor Material Order Code

23"

585 mm

9.83"

250 mm

0.08"

2 mm

7.87"

200 mm

FMU 40 316Ti/1.4571 52014132

galv. steel 52014131

FMU 41 316Ti/1.4571 52014136

galv. steel 52014135

42.7"

1085 mm

29.5"

750 mm

0.12"

3 mm

11.8"

300 mm

FMU 40 316Ti/1.4571 52014134

galv. steel 52014133

FMU 41 316Ti/1.4571 52014138

galv. steel 52014137

A

D M8

1.38”(35)

1.38”(35)

1.97”(50)0.79”

(20)

0.79”(20)

1.97” / 2.44”(50 / 62)

0.87”(22)

C

C

0.26”(6.5)

0.59”(15)

3.94”(100)

0.98”(25)

3.94”(100)

2.95”(75)

2.95”(75)

4.13”(105)

B

Page 37: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 37

Mounting Frame

L00-FMU4x-00-00-00-yy-005

Wall Bracket

L00-FMU4x-00-00-00-yy-006

Commubox FXA191 HART For intrinsically safe communication with FieldCare via the RS232C interface. For details refer to TI237F/00/

en.

Commubox FXA195 HART For intrinsically safe communication with FieldCare via the USB interface. For details refer to TI404F/00/en.

Height Material Order Code

28" (700 mm) galv. steel 919791-0000

28" (700 mm) 1.4301 (AISI 304) 919791-0001

55" (1400 mm) galv. steel 919791-0002

55" (1400 mm) 1.4301 (AISI 304) 919791-0003

0.13”(3.2)

0.79”(20)

2.17”(55)

3.94”(100)

0.98”(25)

28” / 55”(700 / 1400)

1.77”(45) 2.99”

(76)

7.97”(200)

0.26”(6.5)

0.51”(13)

Ø 1.33”(33.7)

5.12”(130) 5.91”

(150)

3.94”(100)

3.94”(100)

2.36”(60)

0.16”(4)

Material Order Code

galv. steel 919792-0000

316Ti/1.4571 919792-0001

0.98”(25)

~ 3.46”(88)

0.20”(5)

0.26”(6.5)

5.91”(150)

5.91”(150)

ø 1.33”(33.7)

0.13”(3.2)

4.33”(110)

4.33”(110)

0.51”(13)

7.09”(180) ~ 8.39”

(213)

Page 38: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

38 Endress+Hauser

Service Interface FXA193 The Service-Interface connects the Service plug of Proline and ToF instruments with the 9 pin RS 232C

interface of a PC. (USB connectors must be equipped with a usual commercial USB/Serial adapter.)

Product structure

Associated documentation

• Technical Information: TI063D

• Safety Instructions for ATEX II (1) GD: XA077D

• Supplementary information for the cable adapters: SD092D

Commubox FXA291

The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface (= Endress+Hauser

Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to

TI405C/07/en.

! Note!

For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional accessory:

• Cerabar S PMC71, PMP7x

• Deltabar S PMD7x, FMD7x

• Deltapilot S FMB70

• Gammapilot M FMG60

• Levelflex M FMP4x

• Micropilot FMR130/FMR131

• Micropilot M FMR2xx

• Micropilot S FMR53x, FMR540

• Prosonic FMU860/861/862

• Prosonic M FMU4x

• Tank Side Monitor NRF590 (with additional adapter cable)

• Prosonic S FMU9x

ToF Adapter FXA291

The ToF Adapter FXA291 connects the Commubox FXA291 via the USB interface of a personal computer or

a notebook to the following Endress+Hauser instruments:

• Cerabar S PMC71, PMP7x

• Deltabar S PMD7x, FMD7x

• Deltapilot S FMB70

• Gammapilot M FMG60

• Levelflex M FMP4x

• Micropilot FMR130/FMR131

• Micropilot M FMR2xx

• Micropilot S FMR53x, FMR540

• Prosonic FMU860/861/862

• Prosonic M FMU4x

• Tank Side Monitor NRF590 (with additional adapter cable)

• Prosonic S FMU9x

For details refer to KA271F/00/a2.

Approvals

A For use in non-hazardous areas

B ATEX II (1) GD

C CSA/FM Class I Div. 1

D ATEX, CSA, FM

9 other

Connection cable

B Connection cable for ToF devices

E Connection cable for Proline and ToF devices

H Connection cable for Proline and ToF devices and Connection cable for Ex two-wire devices

X without connection cable

9 others

FXA193- Complete product designation

Page 39: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 39

Remote display FHX40

L00-FMxxxxxx-00-00-06-en-003

Technical data (cable and housing) and product structure:

For connection of the remote display FHX40 use the cable which fits the communication version of the

respective instrument.

ENDRESS+HAUSER

ENDRESS+HAUSER

IP 65

Order Code:Ser.-No.:

Order Code:Ser.-No.:

Messbereich

Measuring range

Messbereich

Measuring rangeU 16...36 V DC

4...20 mA

U 16...36 V DC

4...20 mA

max. 20 m

max. 20 m

Ma

de

inG

erm

an

yM

au

lbu

rgM

ad

ein

Ge

rma

ny

Ma

ulb

urg

T>70°C :

A

t >85°C

T>70°C :

A

t >85°C

max. 3.15”(80)

min. 1.18”(30)

3.78”(96)

3.46”(88)

6.30”(160)

0.33”(8.5)

4.65”(118)

7.09”(180)

Separate housingFHX 40, NEMA 4(IP 65)

Prosonic MMicropilot MLevelflex M

Cable

3.15”(80)

4.80”(122)

4.80”(122)

4.17”(106)

0.25”(6.3)

4.72”(120)

4.72”(120)

3.23”(82)

Wall-mounting(without mounting bracket)

Pipe-mounting(mounting bracket and plate

supplied optionally,see product structure)

pipe

Max. cable length 20 m (65 ft)

Temperature range -30 to +70°C (-22 to 158°F)

Degree of protection IP65/67 (housing); IP68 (cable) acc. to IEC 60529

Materials Housing: AlSi12; cable glands: nickle plated brass

Dimensions 122x150x80 mm (HxWxD) / 4.8" x 5.9" x 3.2"

Approval:

A Nn-hazardous area

1 ATEX II 2 G EEx ia IIC T6, ATEX II 3D

S FM IS Cl.I Div.1 Gr.A-D

U CSA IS Cl.I Div.1 Gr.A-D

N CSA General Purpose

K TIIS ia IIC T6 (in preparation)

Cable:

1 20m/65ft; for HART

5 20m/65ft; for PROFIBUS PA/FOUNDATION Fieldbus

Additional option:

A Basic version

B Mounting bracket, pipe 1"/ 2"

FHX40 - Complete product designation

Page 40: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

40 Endress+Hauser

Supplementary documentation

System Information SI 005F

Ultrasonic level measurement

Operating manual Depending on the communication variant ordered, the following operating manuals are supplied with the

device:

These instructions describe the installation and first commissioning of the Prosonic M. From the operating

menu, all functions are included, which are required for standard measurement tasks. Additional functions are

not contained in the manual.

Description of device

functions

BA 240F

This contains a detailed description of all the functions of the Prosonic M and is valid for all communication

variants.

A pdf file of this document can be found

• in the supplied "ToF Tool - FieldTool Package" at "Help/ToF Tool Help/ Online Manual/ Operating

Manual/Ultrasonic/Prosonic M FMU4x Functions"1).

• in the internet at "www.endress.com". Click "Download" and enter the product code "FMU4*" into the

search form.

Short instructions KA 183F

Can be found under the device housing cover.

The most important menu functions are summarised on this sheet. It is intended primarily as a memory jogger

for users who are familiar with the operating concept of Endress+Hauser time-of-flight instruments.

Safety Instructions ATEX The following safety instructions are supplied with ATEX-certified device versions. If the devices are used in

explosive areas, comply with all the specifications in these safety instructions.

Communication Operating manual

4 to 20mA, HART BA 237F

Profibus PA BA 238F

Foundation Fieldbus BA 239F

1) If the Operating Instructions have not been installed together with the "ToF Tool - FieldTool Package", they can be added to the installation subsequently.

Instrument version Certificate Communication Housing Safety Instructions

• FMU40 - 1*B*A*

• FMU41 - 1*B*A*

• FMU42 - 1*B*A***

ATEX II 1/2 G or II 2 G

EEx ia II C T6HART (2-wire) F12 XA 174F

• FMU40 - 1*B*D*

• FMU41 - 1*B*D*

• FMU42 - 1*B*D***

ATEX II 1/2 G or II 2 G

EEx ia II C T6HART (2-wire) T12 with overvoltage protection XA 224F

• FMU40 - 1*D*A*

- 1*F*A*

• FMU41 - 1*D*A*

- 1*F*A*

• FMU42 - 1*D*A***

- 1*F*A***

ATEX II 1/2 G or II 2 G

EEx ia II C T6

• Profibus-PA

• Foundation FieldbusF12 XA 175F

• FMU40 - 1*D*D*

- 1*F*D*

• FMU41 - 1*D*D*

- 1*F*D*

• FMU42 - 1*D*D***

- 1*F*D***

ATEX II 1/2 G or II 2 G

EEx ia II C T6

• Profibus-PA

• Foundation FieldbusT12 with overvoltage protection XA 225F

Page 41: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 41

• FMU40 - 4*B*C*

- 4*D*C*

- 4*F*C*

• FMU41 - 4*B*C*

- 4*D*C*

- 4*F*C*

• FMU42 - 4*B*C***

- 4*D*C***

- 4*F*C***

ATEX II 1/2 G or II 2 G

EEx d [ia] II C T6

• HART (2-wire)

• Profibus-PA

• Foundation Fieldbus

T12 XA 176F

• FMU40 - G*****

• FMU41 - G*****

• FMU42 - G*******

ATEX II 3G EEx nA II T6

• HART (2-wire)

• HART (4-wire, DC)

• HART (4-wire, AC)

• Profibus-PA

• Foundation Fieldbus

• F12

• T12

• T12 with overvoltage protection

XA 179F

• FMU40 - 2*B*A*

- 2*D*A*

- 2*F*A*

- 5*B*A*

- 5*D*A*

- 5*F*A*

• FMU41 - 2*B*A*

- 2*D*A*

- 2*F*A*

- 5*B*A*

- 5*D*A*

- 5*F*A*

• FMU42 - 2*B*A***

- 2*D*A***

- 2*F*A***

- 5*B*A***

- 5*D*A***

- 5*F*A***

• ATEX II 1/2D

• ATEX II 1/3D

• HART (2-wire)

• Profibus-PA

• Foundation Fieldbus

F12 XA 180F

• FMU40 - 2*G*A*

- 2*H*A*

- 5*G*A*

- 5*H*A*

• FMU41 - 2*G*A*

- 2*H*A*

- 5*G*A*

- 5*H*A*

• FMU42 - 2*G*A***

- 2*H*A***

- 5*G*A***

- 5*H*A***

• ATEX II 1/2D

• ATEX II 1/3 D

• HART (4-wire, DC)

• HART (4-wire, AC)F12 XA 259

• FMU43 - 2*G*A*

- 2*H*A*

- 5*G*A*

- 5*H*A*

• ATEX II 1/2 D or II 2 D

• ATEX II 1/3 D or II 3 D

• HART (4-wire, DC)

• HART (4-wire, AC)F12 XA 177F

• FMU43 - 2*D*A*

- 2*F*A*

- 5*D*A*

- 5*F*A*

• ATEX II 1/2 D or II 2 D

• ATEX II 1/3 D or II 3 D

• Profibus-PA

• Foundation FieldbusF12 XA 178F

Instrument version Certificate Communication Housing Safety Instructions

Page 42: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

42 Endress+Hauser

Safety Instructions NEPSI The following safety instructions are supplied with NEPSI-certified device versions. If the devices are used in

explosive areas, comply with all the specifications in these safety instructions.

Instrument version Certificate Communication Housing Safety Instructions

• FMU40 - I*B*A*

• FMU41 - I*B*A*

• FMU42 - I*B*A***

Ex ia II C T1 ... T6

NEPSI GYJ071468HART (2-wire) F12 XA 436F

• FMU40 - I*B*D*

• FMU41 - I*B*D*

• FMU42 - I*B*D***

Ex ia II C T1 ... T6

NEPSI GYJ071468HART (2-wire) T12 with overvoltage protection XA 442F

• FMU40 - I*D*A*

- I*F*A*

• FMU41 - I*D*A*

- I*F*A*

• FMU42 - I*D*A***

- I*F*A***

Ex ia II C T1 ... T6

NEPSI GYK071468

• Profibus-PA

• Foundation FieldbusF12 XA 437F

• FMU40 - I*D*D*

- I*F*D*

• FMU41 - I*D*D*

- I*F*D*

• FMU42 - I*D*D***

- I*F*D***

Ex ia II C T1 ... T6

NEPSI GYJ071468

• Profibus-PA

• Foundation FieldbusT12 with overvoltage protection XA 443F

• FMU40 - J*B*C*

- J*D*C*

- J*F*C*

• FMU41 - J*B*C*

- J*D*C*

- J*F*C*

• FMU42 - J*B*C***

- J*D*C***

- J*F*C***

Ex d [ia] II C T1 ... T6

NEPSI GYJ071468

• HART (2-wire)

• Profibus-PA

• Foundation Fieldbus

T12 XA 438F

• FMU40 - Q*B*A*

- Q*D*A*

- Q*F*A*

• FMU41 - Q*B*A*

- Q*D*A*

- Q*F*A*

• FMU42 - Q*B*A***

- Q*D*A***

- Q*F*A***

DIP A21/A22 TA, T*

NEPSI GYJ071468

• HART (2-wire)

• Profibus-PA

• Foundation Fieldbus

F12 XA 441F

• FMU40 - Q*G*A*

- Q*H*A*

• FMU41 - Q*G*A*

- Q*H*A*

• FMU42 - Q*G*A***

- Q*H*A***

DIP A21/A22 TA, T*

NEPSI GYJ071468

• HART (4-wire, DC)

• HART (4-wire, AC)F12 XA 444F

• FMU43 - Q*G*A*

- Q*H*A*DIP A21/A22 TA, T*

• HART (4-wire, DC)

• HART (4-wire, AC)F12 XA 439F

• FMU43 - Q*D*A*

- Q*F*A*DIP A21/A22 TA, T*

• Profibus-PA

• Foundation FieldbusF12 XA 440F

• FMU40 - E*****

• FMU41 - E*****

• FMU42 - E*******

NEPSI Ex nA IIC T6

• HART

• Profibus PA

• Foundation Fieldbus

• F12

• T12XA 403F

Page 43: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

Endress+Hauser 43

Control drawings Installation

drawings

The following control or installation drawings are supplied with the FM, CSA and TIIS-certified device

versions:

Instrument version Certificate Communication Housing Control or Installation

Drawing

• FMU40 - S*B*A*

• FMU41 - S*B*A*

• FMU42 - S*B*A***

FM IS HART (2-wire) F12 ZD 096F

• FMU40 - S*D*A*

- S*F*A*

• FMU41 - S*D*A*

- S*F*A*

• FMU42 - S*D*A***

- S*F*A***

FM IS• Profibus-PA

• Foundation FieldbusF12 ZD 097F

• FMU40 - S*B*D*

• FMU41 - S*B*D*

• FMU42 - S*B*D***

FM IS HART (2-wire) T12 with overvoltage protection ZD 139F

• FMU40 - S*D* D*

- S*F*D*

• FMU41 - S*D* D*

- S*F*D*

• FMU42 - S*D* D***

- S*F*D***

FM IS• Profibus-PA

• Foundation FieldbusT12 with overvoltage protection ZD 140F

• FMU40 - T*B*C*

- T*D*C*

- T*F*C*

• FMU41 - T*B*C*

- T*D*C*

- T*F*C*

• FMU42 - T*B*C***

- T*D*C***

- T*F*C***

FM XP

• HART (2-wire)

• Profibus PA

• Foundation Fieldbus

T12 ZD 098F

• FMU40 - U*B*A*

• FMU41 - U*B*A*

• FMU42 - U*B*A***

• FMU44 - U*B*A***

CSA IS HART (2-wire) F12 ZD 088F

• FMU40 - U*D*A*

- U*F*A*

• FMU41 - U*D*A*

- U*F*A*

• FMU42 - U*D*A***

- U*F*A***

• FMU44 - U*D*A***

- U*F*A***

CSA IS• Profibus-PA

• Foundation FieldbusF12 ZD 099F

• FMU40 - U*B* D*

• FMU41 - U*B* D*

• FMU42 - U*B* D***

• FMU44 - U*B* D***

CSA IS HART (2-wire) T12 with overvoltage protection ZD 101F

• FMU40 - U*D*D*

- U*F*D*

• FMU41 - U*D*D*

- U*F*D*

• FMU42 - U*D*D***

- U*F*D***

• FMU44 - U*D*D***

- U*F*D***

CSA IS• Profibus-PA

• Foundation FieldbusT12 with overvoltage protection ZD 102F

Page 44: Technical Information Prosonic M FMU40/41/42/43/44 · PDF fileTechnical Information Prosonic M FMU40/41/42/43/44 ... asas la. #%& ABC DEF 7 8 6 9 ... PLC operating and display module

Prosonic M

44 Endress+Hauser

• FMU40 - V*B*C*

- V*D*C*

- V*F*C*

• FMU41 - V*B*C*

- V*D*C*

- V*F*C*

• FMU42 - V*B*C***

- V*D*C***

- V*F*C***

• FMU44 - V*B*C***

- V*D*C***

- V*F*C***

CSA XP

• HART (2-wire)

• Profibus PA

• Foundation Fieldbus

T12 ZD 100F

• FMU 40 - K*****

• FMU 41 - K*****

TIIS

Ex ia IIC T6HART F12 ZD 138F

Instrument version Certificate Communication Housing Control or Installation

Drawing

United States

Endress+Hauser, Inc.

2350 Endress Place

Greenwood, IN 46143

Tel. 317-535-7138

Sales 888-ENDRESS

Service 800-642-8737

fax 317-535-8498

[email protected]

www.us.endress.com

TI365/24/ae/03.09

© 2009 Endress+Hauser, Inc.

Canada

Endress+Hauser Canada

1075 Sutton Drive

Burlington, ON L7L 5Z8

Tel. 905-681-9292

800-668-3199

Fax 905-681-9444

[email protected]

www.ca.endress.com

Mexico

Endress+Hauser, México, S.A. de C.V.

Fernando Montes de Oca 21 Edificio A Piso 3

Fracc. Industrial San Nicolás

54030. Tlalnepantla de Baz

Estado de México

México

Tel: +52 55 5321 2080

Fax +52 55 5321 2099

[email protected]

www.mx.endress.com