TD01200001E For more information visit: www.eatonelectrical.com
LG Molded Case Circuit Breakers
250 – 630 Amperes Ordering Guide
Technical Data
New Information
Description Page
Catalog Numbering System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Product Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Complete Breaker Selection and Ordering Information . . . . . . . . . . . . . . .
4
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
Internal Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
Internal Accessories Selection Chart . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Earth Leakage (Ground Fault) Modules . . . . . . . . . . . . . . . . . . . . . . . . .
9
Plug-in Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
Flange Mounted Handle Mechanisms . . . . . . . . . . . . . . . . . . . . . . . . . .
10
Flex Shaft Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
Through-the-Door Handle Mechanisms . . . . . . . . . . . . . . . . . . . . . . . . .
10
Direct (Close-Coupled) Handle Mechanism . . . . . . . . . . . . . . . . . . . . . .
11
Special Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
Time-Current Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
Current Limiting Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
18
For more information visit: www.eatonelectrical.com TD01200001E
Technical Data
Page
2
Effective: March 2004
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Catalog Numbering System
Table 1. LG Catalog Numbering System
�
630 amperes is not a UL or CSA listed rating. 600 amperes is the maximum UL and CSA listed rating for the LG.
�
Contact factory if needed before September 2004.
Table 2. Trip Unit Catalog Numbering System
�
Contact factory if needed before September 2004.
L G S 3 25O FA G
Frame
L
Standard/Application
G = IEC/CE/UL�/CSA�
Performance (Icu)
600 480 415 240
E 18 35 35 65
S 25 50 45 85
H 35 65 70 100
C � 50 100 100 200
K Molded Case Switch
Poles
3 = Three4 = Four — Neutral 0% Protected7 = Four — Neutral 100% Protected8 = Four — Neutral 0 – 60% Protected9 = Four — Neutral 0 – 100% Protected
Amperes
250300350400500600
630 � Trip Unit
AA = Adjustable AdjustableFA = Fixed AdjustableKS = Molded Case Switch33 = 310+ Electronic LS �32 = 310+ Electronic LSI �35 = 310+ Electronic LSG �36 = 310+ Electronic LSIG �NN = Frame Only (No Trip)
Terminations/Hardware
Terminals Mounting Hardware
M = Metric End CapsG = Line/Load StandardW = Without Lugs
MetricMetricMetric
LT 4 250 FA
Trip
LT
Amperes
250300350400500600630
Poles
3 = Three4 = Four — Neutral 0% Protected7 = Four — Neutral 100% Protected8 = Four — Neutral 0 – 60% Protected9 = Four — Neutral 0 – 100% Protected
Trip Unit
AA = Adjustable Adjustable Thermal-MagneticFA = Fixed Adjustable Thermal-MagneticKS = Molded Case Switch33 = 310+ Electronic LS �32 = 310+ Electronic LSI �35 = 310+ Electronic LSG �36 = 310+ Electronic LSIG �
TD01200001E For more information visit: www.eatonelectrical.com
Technical Data
Effective: March 2004 Page
3
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Product Specifications
Table 3. LG Rating Chart
�
630 amperes is not a UL or CSA listed rating. 600 amperes is the maximum UL and CSA listed rating for the LG.
�
Contact factory if needed before September 2004.
�
2-poles in series. Ratings (dc) apply to substantially non-inductive circuits.
�
3-poles in series. Ratings (dc) apply to substantially non-inductive circuits.
�
Not suitable for dc application. 4-pole ground fault not available.
LG
Maximum Rated Current (Amperes) 400, 630
�
Breaker Type E S H C
�
Breaker Capacity (kA rms) ac 50 – 60 Hz
NEMA
�
UL 489 240 Vac 65 85 100 200
480 Vac 35 50 65 100
600 Vac 18 25 35 50
IEC 60947-2 220 – 240 Vac I
cu
65 85 100 200
I
cs
65 85 100 150
380 – 415 Vac I
cu
35 50 70 100
I
cs
35 50 70 75
660 – 690 Vac I
cu
12 20 25 35
I
cs
6 10 13 18
250 Vdc
�
I
cu
10 22 42 42
I
cs
10 22 42 42
600 Vdc
�
I
cu
10 22 35 35
I
cs
10 22 35 35
Number of Poles 3, 4
Ampere Range 100 – 630 A
�
Trip UnitsF = FixedA = AdjustableT = ThermalM = Magnetic
FT-AMAT-AMElectronic (Digitrip RMS 310)Molded Case SwitchMotor Circuit Protector
Interchangeable
■
Built-in
■
Thermal Magnetic Fixed Thermal
■
Adjustable Thermal
■
Magnetic Adjustable
Electronic rms
�
LS
■
�
LSI
■
�
LSG
■
�
LSIG
■
�
Dimensions in Inches (mm) H W D
3-Pole 10.13 (257.3) 5.48 (139.2) 4.06 (103.1)
4-Pole 10.13 (257.3) 7.22 (183.4) 4.06 (103.1)
Weight (approximate) lbs. (kgs.) 3-Pole 4-Pole
16 (7.3) 20 (9.1)
Utilization Category A
For more information visit: www.eatonelectrical.com TD01200001E
Technical Data
Page
4
Effective: March 2004
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Complete Breaker Selection and Ordering Information
Table 4. IC Rating at 415/480 V — Complete Breaker (Includes Frame, Trip Unit, Standard Terminals and Mounting Hardware)
�
�
Substitute suffix “W” for suffix “G” for breakers without lugs.
�
Neutral protection is indicated by the fourth character: 4 = 0%, 7 = 100%, 8 = adjustable 0 – 60% and 9 = 0 – 100%.
�
Typically used in IEC markets, adjustable thermal, adjustable magnetic trip units are not UL labeled.
�
630 amperes is not a UL or CSA listed rating. 600 amperes is the maximum UL and CSA listed rating for the LG.
�
Contact factory if needed before September 2004.
Table 5. IC Rating at 415/480 V — Complete LG Breaker with Electronic Trip Unit (Includes Frame, Trip Unit, Standard Terminals and Mounting Hardware)
�
Neutral CT for LSG and LSIG applied to 4-wire applications must be ordered as a separate item.
�
Required for 4-wire systems.
�
630 amperes is not a UL or CSA listed rating. 600 amperes is the maximum UL and CSA listed rating for the LG.
Neutral protection: 4= 0%, 6 = 60%, 7 = 100%. Electronic trip unit neutral protection is not adjustable.
AmpereRating
3-Pole 4-Pole (0%)
�
3-Pole 4-Pole (0%)
�
Fixed Thermal/Adjustable Magnetic
Adjustable Thermal/Adjustable Magnetic
�
Fixed Thermal/Adjustable Magnetic
Adjustable Thermal/Adjustable Magnetic
�
Fixed Thermal/Adjustable Magnetic
Adjustable Thermal/Adjustable Magnetic
�
Fixed Thermal/Adjustable Magnetic
Adjustable Thermal/Adjustable Magnetic
�
Catalog Number Catalog Number Catalog Number Catalog Number
IEC/CE/UL/CSA 35 (I
CS
= I
CU
)/35 IEC/CE/UL/CSA 50 (I
CS
= I
CU
) /50
250300320350
LGE3250FAGLGE3300FAG—LGE3350FAG
LGE3250AAG—LGE3320AAG—
LGE4250FAGLGE4300FAG—LGE4350FAG
LGE4250AAG—LGE4320AAG—
LGS3250FAGLGS3300FAG—LGS3350FAG
LGS3250AAG—LGS3320AAG—
LGS4250FAGLGS4350FAG—LGS4350FAG
LGS4250AAG—LGS4320AAG—
400500600630
�
LGE3400FAGLGE3500FAGLGE3600FAG—
LGE3400AAGLGE3500AAG—LGE3630AAG
LGE4400FAGLGE4500FAGLGE4600FAG—
LGE4400AAGLGE4500AAG—LGE4630AAG
LGS3400FAGLGS3500FAGLGS3600FAG—
LGS3400AAGLGS3500AAG—LGS3630AAG
LGS4400FAGLGS4500FAGLGS4600FAG—
LGS4400AAGLGS4500AAG—LGS4630AAG
IEC/CE/UL/CSA 70 (I
CU
= I
CS
)/65 IEC/CE/UL/CSA 100 (I
CS
= .75 I
CU
)/100
�
250300320350
LGH3250FAGLGH3300FAG—LGH3350FAG
LGH3250AAG—LGH3320AAG—
LGH4250FAGLGH4300FAG—LGH4350FAG
LGH4250AAG—LGH4320AAG—
LGC3250FAGLGC3300FAG—LGC3350FAG
LGC3250AAG—LGC3320AAG—
LGC4250FAGLGC4300FAG—LGC4350FAG
LGC4250AAG—LGC4320AAG—
400500600630
�
LGH3400FAGLGH3500FAGLGH3600FAG—
LGH3400AAGLGH3500AAG—LGH3630AAG
LGH4400FAGLGH4500FAGLGH4600FAG—
LGH4400AAGLGH4500AAG—LGH4630AAG
LGC3400FAGLGC3500FAGLGC3600FAG—
LGC3400AAGLGC3500AAG—LGC3630AAG
LGC4400FAGLGC4500FAGLGC4600FAG—
LGC4400AAGLGC4500AAG—LGC4630AAG
AmpereRating
LS LSI LSG
�
LSIG
�
Neutral CT
�
for LSG & LSIG
�
IEC/UL/CSA — 35/35 (3-Pole)
250400600630
�
LGE325033GLGE340033GLGE360033GLGE363033G
LGE325032GLGE340032GLGE360032GLGE363032G
LGE325035GLGE340035GLGE360035GLGE363035G
LGE325036GLGE340036GLGE360036GLGE363036G
LGFCT250LGFCT400LGFCT600LGFCT630
IEC/UL/CSA — 35/35 (4-Pole)
250400600630
�
LGE425033GLGE440033GLGE460033GLGE463033G
LGE425032GLGE440032GLGE460032GLGE463032G
LGE425035GLGE440035GLGE460035GLGE463035G
LGE425036GLGE440036GLGE460036GLGE463036G
LGFCT250LGFCT400LGFCT600LGFCT630
IEC/UL/CSA — 50/50 (3-Pole)
250400600630
�
LGS325033GLGS340033GLGS360033GLGS363033G
LGS325032GLGS340032GLGS360032GLGS363032G
LGS325035GLGS340035GLGS360035GLGS363035G
LGS325036GLGS340036GLGS360036GLGS363036G
LGFCT250LGFCT400LGFCT600LGFCT630
IEC/UL/CSA — 50/50 (4-Pole)
250400600630
�
LGS425033GLGS440033GLGS460033GLGS463033G
LGS425032GLGS440032GLGS460032GLGS463032G
LGS425035GLGS440035GLGS460035GLGS463035G
LGS425036GLGS440036GLGS460036GLGS463036G
LGFCT250LGFCT400LGFCT600LGFCT630
IEC/UL/CSA — 70/65 (3-Pole)
250400600630
�
LGH325033GLGH340033GLGH360033GLGH363033G
LGH325032GLGH340032GLGH360032GLGH363032G
LGH325035GLGH340035GLGH360035GLGH363035G
LGH325036GLGH340036GLGH360036GLGH363036G
LGFCT250LGFCT400LGFCT600LGFCT630
IEC/UL/CSA — 70/65 (4-Pole)
250400600630
�
LGH425033GLGH440033GLGH460033GLGH463033G
LGH425032GLGH440032GLGH460032GLGH463032G
LGH425035GLGH440035GLGH460035GLGH463035G
LGH425036GLGH440036GLGH460036GLGH463036G
LGFCT250LGFCT400LGFCT600LGFCT630
TD01200001E For more information visit: www.eatonelectrical.com
Technical Data
Effective: March 2004 Page
5
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Table 6. Thermal Magnetic Trip Unit
� Neutral protection is indicated by the fourth character: 4 = 0%, 7 = 100%, 8 = adjustable 0 – 60% and 9 = 0 – 100%.
� Typically used in IEC markets, adjustable thermal, adjustable magnetic trip units are not UL labeled.� 630 amperes is not a UL or CSA listed rating. 600 amperes is the maximum UL and CSA listed
rating for the LG.
Table 7. Digitrip 310+ Electronic Trip Unit
� Required for 4-wire systems.� 630 amperes is not a UL or CSA listed rating. 600 amperes is the maximum UL and CSA listed
rating for the LG.� Neutral protection: 4= 0%, 6 = 60%, 7 = 100%. Electronic trip unit neutral protection is not
adjustable.Note: Long time pick up — No rating plug needed.
630 Ampere Settings — 630, 600, 500, 400, 350, 315, 300, 250 IEC only.600 Ampere Settings — 600, 500, 450, 400, 350, 315, 300, 250.400 Ampere Settings — 400, 350, 315, 300, 250, 225, 200, 160.250 Ampere Settings — 250, 225, 200, 175, 160, 150, 125, 100.
Note: Adjustable long time delay — 2 – 24 seconds at 6 x IrAdjustable short time delay — Inst., 120, 300 milliseconds
Note: Comes with clear plastic shroud to cover adjustment settings (suitable for sealing with wire or tie-wrap).
Note: LG electronic trip units with ground fault do not include a neutral CT. If the system is 4-wire requiring a neutral CT, it must be ordered as a separate item.
Digitrip 310+ Test Kit
Digitrip 310+ Test Kit Shown with JG MCCB
AmpereRating
3-Pole 4-Pole (0%) �
Fixed Thermal/Adjustable Magnetic
Adjustable Thermal/Adjustable Magnetic �
Fixed Thermal/Adjustable Magnetic
Adjustable Thermal/Adjustable Magnetic �
Catalog Number Catalog Number
250300320350
LT3250FALT3300FA—LT3350FA
LT3250AA—LT3320AA—
LT4250FALT4300FA—LT4350FA
LT4250AA—LT4320AA—
400500600630 �
LT3400FALT3500FALT3600FA—
LT3400AALT3500AA—LT3630AA
LT4400FALT4500FALT4600FA—
LT4400AALT4500AA—LT4630AA
AmpereRating
LS LSI LSG LSIG Neutral CTfor LSG & LSIG �
3-Pole250400600630 �
LT325033LT340033LT360033LT363033
LT325032LT340032LT360032LT363032
LT325035LT340035LT360035LT363035
LT325036LT340036LT360036LT363036
LGFCT250LGFCT400LGFCT600LGFCT630
4-Pole �
250400600630 �
LT425033LT440033LT460033LT463033
LT425032LT440032LT460032LT463032
LT425035LT440035LT460035LT463035
LT425036LT440036LT460036LT463036
LGFCT250LGFCT400LGFCT600LGFCT630
Table 8. Electronic Trip Unit Test Kit
Table 9. Components Frame — IC Rating at 415/480 V
� 630 amperes is not a UL or CSA listed rating. 600 amperes is the maximum UL and CSA listed rating for the LG.
� Contact factory if needed before September 2004.
Table 10. Motor Circuit Protectors — 600 Vac Maximum, 250 Vdc Maximum
Table 11. Molded Case Switches
630 amperes is not a UL or CSA listed rating. 600 amperes is the maximum UL and CSA listed rating for the LG.
Digitrip 310+ Electronic Trip Unit
Control Voltage Catalog Number
120 Vac230 Vac
MTST120VMTST230V
AmpereRating �
IC Ratingat 415/480 V
Catalog Number
3-Pole 4-Pole (0%)
630630630630
35/35 50/50 70/65100/100 �
LGE3630NNLGS3630NNLGH3630NNLGC3630NN
LGE4630NNLGS4630NNLGH4630NNLGC4630NN
ContinuousAmperes
Trip Range (Amperes)
Catalog Number
600 1125 – 22501500 – 30001750 – 35002000 – 4000
HMCPL600LHMCPL600NHMCPL600RHMCPL600X
2250 – 45002500 – 50003000 – 6000
HMCPL600YHMCPL600PHMCPL600M
AmpereRating
Numberof Poles
CatalogNumber
400 34
LGK3400KSGLGK4400KSG
630 34
LGK3630KSGLGK4630KSG
For more information visit: www.eatonelectrical.com TD01200001E
Technical DataPage 6 Effective: March 2004
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Table 12. Line and Load Terminals
� Includes LTS3K (3-pole) or LTS4K (4-pole) terminal covers.� Standard terminal included with complete breaker.
Table 13. Terminal Covers
� Included in TA63IL, T63IL, TA632L kits listed above.
Table 14. End Cap Kits
Table 15. Terminal Extensions
Table 16. Terminal Spreaders
Figure 1. Terminals and Terminal Cover for the LG Breaker — Includes LTS3K (3-Pole) or LTS4K (4-Pole) Terminal CoversNote: Extended terminal covers add 2.10 inches (53.3 mm) to breaker length.
Maximum BreakerAmperes
Terminal BodyMaterial
WireType
AWG Wire Range/Number of Conductors
Metric WireRange (mm2)
Number of Terminals Included
CatalogNumber
400400
AluminumAluminum
Cu/AlCu/Al
500 – 750 (1)500 – 750 (1)
240 – 380 (1)240 – 380 (1)
34
3TA631LK �
4TA631LK �
400400
CopperCopper
CuCu
500 – 750 (1)500 – 750 (1)
240 – 380 (1)240 – 380 (1)
34
3T631LK �
4T631LK �
630630
AluminumAluminum
Cu/AlCu/Al
2 – 500 (2) 2 – 500 (2)
35 – 240 (2) 35 – 240 (2)
34
3TA632LK ��
4TA632LK ��
630630
CopperCopper
CuCu
2 – 500 (2) 2 – 500 (2)
35 – 240 (2) 35 – 240 (2)
34
3T632LK �
4T632LK �
400400
AluminumCopper
Cu/AlCu
2 – 500 (1) 2 – 500 (1)
35 – 240 (1) 35 – 240 (1)
11
TA350LK �
T350LK �
Description CatalogNumber
3-Pole Terminal Cover �4-Pole Terminal Cover �
LTS3KLTS4K
Numberof Poles
CatalogNumber
34
L3RTWKL4RTWK
Numberof Poles
CatalogNumber
34
LGTEW3LGTEW4
Numberof Poles
CatalogNumber
34
LGTES3LGTES4
Warning Label
TA350L or T350L Terminal TA631L, T631L, T632L
or TA632L step-type terminal kitslisted above include LTS3K (3-pole)or LTS4K (4-pole) terminal cover and warning label (requiredfor proper application).
Terminal Cover
TD01200001E For more information visit: www.eatonelectrical.com
Technical DataEffective: March 2004 Page 7
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Product Description
Internal Accessories
Alarm LockoutThe alarm switches operate when the circuit breaker is tripped by a short cir-cuit or overcurrent, but also when it is tripped by a shunt trip or undervoltage release.
Auxiliary SwitchesAuxiliary switches are used for signaling and control purposes. The various functions of the auxiliary switches (changeover) are shown in Figure 2.
Shunt TripsThe shunt trip is used for remote tripping.
The coil of the shunt trip is rated only for short-time operation.
It is not permissible with the circuit breaker open to apply a continuous opening command to the shunt trip in order to prevent the breaker from closing. This means that interlocking circuits with continuous commands may not be set up with shunt trips.
Undervoltage ReleasesThe circuit breaker cannot be closed until the undervoltage release is ener-gized. If the release is not energized, the circuit breaker can only perform an idle switching operation.
Frequent idle switching actions should be avoided as they shorten the endur-ance of the circuit breaker.
Figure 2. Accessory Configurations
Figure 3. Contact Making by the Auxiliary and Alarm Switches as a Function of the Switching Position of the Circuit Breaker
For more information visit: www.eatonelectrical.com TD01200001E
Technical DataPage 8 Effective: March 2004
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Internal Accessories Selection Chart
Table 17. Internal Accessories Catalog Numbers and Ratings
� Suitable for use in ground fault applications (120 Vac only).
AccessoryType
Electrical Rating ContactArrangement
Catalog NumberVolts Frequency Hz Amperes
Shunt Trip 12 – 60110 – 240380 – 600
50/60 dc50/60 dc50/60
Refer to I.L.29C152 — SNT060CPKSNT120CPK �
SNT480APK
Auxiliary Switch 600125250
50/60dcdc
60.500.25
1A – 1B2A – 2B
AUX1A1BPKAUX2A2BPK
Bell Alarm 600125250
50/60dcdc
60.500.25
1M – 1B2M – 2B
ALM1M1BJPKALM2M2BJPK
Combination Alarm/Auxiliary Switch
600125250
50/60dcdc
60.500.25
1A – 1B and1M – 1B
AUXALRMJPK
Undervoltage Release 12 24 48 – 60 48 – 60110 – 127110 – 125208 – 240220 – 250380 – 500525 – 600
50/60 dc50/60 dc50/60 dc50/60dc50/60dc50/6050/60
— — UVR012CPKUVR024CPKUVR048APKUVR048DPKUVR120APKUVR125DPKUVR240APKUVR250DPKUVR480APKUVR600DPK
ST
a
a
b
Make
Break
a
b
UV
Auxiliary Switch Instruction Leaflet . . . . . 29C153 DWG Number . . . . . . . . . . . . . . . . . . . . . . 66C1575Shunt Trip Instruction Leaflet . . . . . . . . . . . 29C152 DWG Number . . . . . . . . . . . . . . . . . . . . . . 66C1576Undervoltage Release Instruction Leaflet. . . . . . . . . . . . . . . . . . . . . 29C155 DWG Number . . . . . . . . . . . . . . . . . . . . . . 66C1577
TD01200001E For more information visit: www.eatonelectrical.com
Technical DataEffective: March 2004 Page 9
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Earth Leakage(Ground Fault) Modules
LG Breaker with Earth Leakage Module(4-Pole Breaker Shown)
For low-level, coordinated ground fault protection, IEC and UL-rated earth leakage modules are available for LG breakers. The module does not restrict the use of other breaker accessories. The LG module is bottom mounted for
circuits up to 400 and 630 amperes.The module is completely self-contained since the current sensor, relay and power supply are located inside the product. Current pick-up settings are selectable from 0.03 – 30 amperes for the UL rated modules, and 0.03 – 10.0 amperes for the IEC modules. Time delays are also selectable from instantaneous – 1.0 sec-onds for 0.10 ampere settings and above. A current pick-up setting of 0.03 amperes defaults to an instantaneous time setting regardless of the time dial’s position. Two alarm contacts come as standard: a 50% pretrip and a 100% after trip, both based only on earth leakage current levels.
Table 18. LG Frame Earth Leakage Modules
Figure 4. UL-Rated LG Frame Earth Leakage Module Faceplate
Figure 5. IEC-Rated LG Frame Earth Leakage Module Faceplate
Amperes Numberof Poles
CatalogNumber
UL-Rated, Bottom Mounted, 120 – 480 Vac, 50/60 Hz400400
34
ELLBN3400WELLBN4400W
600600
34
ELLBN3600WELLBN4600W
IEC-Rated, Bottom Mounted, 230 – 415 Vac, 50/60 Hz400400
34
ELLBE3400WELLBE4400W
630630
34
ELLBE3630WELLBE4630W
Plug-in Blocks
LG Breaker with Plug-in Block
Plug-in adapters expedite installation and front removal of circuit breakers. Plug-ins are available for rear connec-tion applications on 3- and 4-pole circuit breakers. Trip-on drawout interlock kits are included. Use terminal shields for IP30 protection.
Table 19. Plug-in Blocks and Accessories
� Included with plug-in block. Trips the breaker when breaker is removed from the plug-in block.
Table 20. Rear Connecting Studs
BreakerFrame
Numberof Poles
CatalogNumber
LG-Frame Plug-in BlocksLG630LG630
34
PAD3LPAD4L
Trip-on Drawout Interlock Kit �
LG 3, 4 PIILLG
Terminal Shields IP30LGLG
34
LTS3KLTS4K
Numberof Poles
CatalogNumber
34
LRCS3WKLRCS4WK
For more information visit: www.eatonelectrical.com TD01200001E
Technical DataPage 10 Effective: March 2004
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Flange Mounted Handle Mechanism
The Flex Shaft™
Flange Mounted handle mechanisms mount on the flange of an enclosure door. The Flex Shaft is an extra heavy-duty mechanism that includes a flexible shaft in various lengths, 3 feet (0.9 m) through 10 feet (3 m) for use with various size enclosures.
The Flex Shaft handle will accept up to three padlock shackles, each with a maximum diameter of 3/8 inch (9.5 mm). Can be used with NEMA 12/3R fabricated enclosures. An optional handle is available for Flex Shaft that is suitable for use with NEMA 4/4X environments.
The Flex Shaft comes preset from the factory, requiring only minor field adjustments on installation, which takes about 10 minutes — a significant time savings compared to installation of other types of flange handle mecha-nisms. The Flex Shaft mechanism also takes up less interior enclosure space than competitive designs and the han-dle fits standard flange cutouts. Flex Shaft handle can be remotely mounted from breaker, where an operator can use it by “funneling” the cable through conduit.
Flex Shaft is UL listed under File E64893 and meets CSA requirements.
Table 21. Flex Shaft Ordering Information
Note: NEMA 4/4X handle mechanisms are available. Add Suffix X to complete Catalog Number.
Add Suffix L to complete Catalog Number for 6-inch (152.4 mm) handle.
Original narrow handle design (No C Suffix) is available. Remove C from Catalog Number.
Note: When selecting the length of shaft, ensure minimum bending radius of 4 inches (101.6 mm) is maintained to operate properly.
The standard method of shipment includes the mechanism preset at the factory; however, minor field adjust-ments may be required.
Flex Shaft Accessories
Table 22. Standard Door Hardware (Required Adapter Kit)
Table 23. Door Hardware Adapter Kit(Required on Standard Door Hardware)
Table 24. Door Hardware for Hoffman A – 25 Enclosure
Table 25. NEMA — IP Crossover
Through-the-DoorHandle Mechanisms
Rotary Handle
The Cutler-Hammer Rotary is suitable for use with NEMA 12 enclosure types. Optional NEMA 4/4X handles are also available. All rotary handle mecha-nisms include a handle “Lock Off,” to prevent turning the breaker ON while in the OFF position. All Rotary handles indicate ON/OFF/Tripped/Reset positions, however, Universal Rotary has the added feature of inter-national markings for ON (I) and OFF (O). Cutler-Hammer Universal Rotary is made of molded material and is available in black or yellow/red.
Table 26. LG-Frame Universal Rotary Ordering Information
� Complete catalog number includes handle, mechanism, shaft and mounting hardware.
� Add Suffix “X” for NEMA 4/4X.
BreakerFrame
Flexible Shaft LengthFeet (m)
4 (1.2) 7 (2.1) 10 (3.1)
Catalog Number
LG LHMFS04 LHMFS07 LHMFS10
Latch Panel HeightInches (mm)
CatalogNumber
2 Point2 Point3 Point
Up to 30.00 (762.0)Up to 40.00 (1016.0)Over 40.00 (1016.0)
DH1RDH2RDH3R
Catalog Number
AMTDHA
Latch Panel HeightInches (mm)
CatalogNumber
2 Point3 Point
Up to 40.00 (1016.0)Over 40.00 (1016.0)
HDH-2RHDH-3R
Crossover Type
NEMA IP
13R124/4X
IP20IP55IP54IP66
Shaft Lengthin Inches (mm)
HandleColor
CatalogNumber ��
6.00 (152.4)12.00 (304.8)24.00 (609.6)
BlackBlackBlack
KLHMVD06BKLHMVD12BKLHMVD24B
6.00 (152.4)12.00 (304.8)24.00 (609.6)
RedRedRed
KLHMVD06RKLHMVD12RKLHMVD24R
TD01200001E For more information visit: www.eatonelectrical.com
Technical DataEffective: March 2004 Page 11
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Direct (Close-Coupled)Handle Mechanism
Direct Handle Mechanism
Direct (Close-Coupled) Handle Mecha-nisms mount directly to the circuit breaker. They are used in shallow enclosures where the standard vari-able depth through-the-door type mechanism is not practical or cannot be used. They are typically for applica-tions where high volume, standardized enclosures are being fabricated.
The Universal Direct handle mechanism comes with a door interlock to prevent opening the enclosure while the circuit breaker is in the ON position. It is also available without a door interlock.
The Universal Direct handle mechanism is UL 489 listed, IEC 60947-1/2 and meets CSA requirements.
Table 27. Universal Direct
Table 28. Locks and Interlocks
Special CalibrationSpecial non-UL listed calibrations are available for certain ambient tempera-tures other than 40ºC and for frequen-cies other than 50/60 Hz or dc. Reduced interrupting ratings will apply for 400 Hz applications.
50ºC CalibrationAdd suffix “V” to Catalog Number for complete breaker when ordering listed ampere ratings for breakers to be used in 50ºC ambients. Contact Eaton Electrical for availability.
Moisture-Fungus TreatmentAll Cutler-Hammer circuit breaker cases are molded from glass-polyester which does not support the growth of fungus. Any parts which are susceptible to the growth of fungus will require special treatment. Order by description.
Frame Handle Color
White Red
With Interlock
Without Interlock
Without Interlock
Catalog Number
LG LHMCCBI LHMCCB LHMCCR
Description CatalogNumber
Padlockable Handle Lock Hasp LPHL
Padlockable Handle Lock Hasp — OFF Only
LPHLOFF
Padlockable Handle Block LBHPOFF
Key Interlock Kit (Provision Only) KYKL
Sliding Bar Interlock — 3-Pole Field Fitted, Requires 2 Breakers
SBKL3
Sliding Bar Interlock — 4-Pole Field Fitted, Requires 2 Breakers
SBKL4
Walking Beam Interlock —3-Pole Factory Fitted, Requires2 Breakers
WBLL3630
Walking Beam Interlock — 4-Pole Factory Fitted, Requires 2 Breakers
WBLL4630
For more information visit: www.eatonelectrical.com TD01200001E
Technical DataPage 12 Effective: March 2004
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Technical Data
Table 29. Electrical Characteristics
� 630 amperes is not a UL or CSA listed rating. 600 amperes is the maximum UL and CSA listed rating for the LG.
� See footnotes for exceptions.� Thermal overload release set to the lower value.� Thermal overload release set to the upper value, resp. fixed-setting
thermal overload releases.
Description LG
Maximum Rated Current In Depending on the Version 400, 630 A �
Rated Insulation Voltage U, According to IEC 60947-2 Main Conducting Paths Auxiliary Circuits
750 Vac690 Vac
Rated Impulse Withstand Voltage Uimp Main Conducting Paths Auxiliary Circuits
8 kV4 kV
Rated Operational Voltage Ue IEC NEMA
690 Vac600 Vac
UL 489 and CSA C22.2 No. 5.1 Yes �
Permissible Ambient Temperature -20 to +70°C
Permissible Load for Various Ambient Temperatures Close to the Circuit Breaker, Related to the Rated Current of the Circuit Breaker■ Circuit Breakers for Plant Protection
– At 40°C– At 50°C– At 55°C– At 60°C– At 70°C
�
100% 96% 93% 90% 84%
�
100% 91% 86% 82% 70%
■ Circuit Breakers for Motor Protection– At 40°C– At 50°C– At 55°C– At 60°C– At 70°C
100%100%100%100% 90%
■ Circuit Breakers for Starter Combinations and Isolating Circuit Breakers– At 40°C – At 50°C– At 55°C– At 60°C– At 70°C
100%100% 95% 90% 84%
Rated Short Circuit Breaking Capacity (dc) Not for Circuit Breakers for Motor Protection(Time Constant � = 10 rms)
2 Conducting Paths in SeriesFor up to: 250 VdcNEMA (Time Constant � = 8 rms)
2 Conducting Paths in Series250 Vdc
42 kA Maximum
42 kA
Description LG
Main Switch Characteristics According to IEC 60947-2 in Combination with Lockable Rotary Drives
Yes
Utilization Category A
Endurance (Operating Cycles) 8,000
Maximum Switching Frequency 240 1/h
Conductor Cross Sections and Terminal Types for Main Conductors■ Solid or Stranded■ Finely Stranded with End Sleeve■ Bus BarTightening Torque for Box TerminalsTightening Torque for Bus Bar Connection Pieces
BoxTerminals
95 to 240 mm2
70 to 150 mm2
—42 Nm
30 Nm
Flat BarTerminals
——
600 A31 Nm
6 Nm
Conductor Cross Sections for Auxiliary Circuits with Terminal Connection or Terminal Strip■ Solid ■ Finely Stranded with End Sleeve■ With Brought-out Cable Ends■ Tightening Torque for Fitting Screws
0.75 to 2.5 mm2
0.75 to 2.5 mm2
0.82 (AWG 18) mm2
0.80 to 1.4 Nm
Power Loss per Circuit Breaker at Maximum Rated Current ln (The Power Losses of the Undervoltage Releases (“r” Releases) Must Be Observed if Necessary) at Three-Phase Symmetrical Load■ For Plant Protection ■ As Isolating Circuit Breaker■ For Starter Combinations■ For Motor Protection
255 W160 W160 W120 W
Permissible Mounting Position
Approximate Weight Pounds lbs. (kgs.) 3-Pole16 (7.3)
4-Pole20 (9.1)
90° 90°
90° 90°
TD01200001E For more information visit: www.eatonelectrical.com
Technical DataEffective: March 2004 Page 13
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Technical Data (Continued)
Table 29. Electrical Characteristics (Continued)
Dimensions in Inches (mm)
Figure 6. LG-FrameNote: TA631L, T631L, TA632L, T632L terminals add 1.19 inches (30.2 mm) to line or load side of LG MCCB.
Note: LTS3K or LTS4K terminal covers add 2.13 inches (54.1 mm) to line or load side of LG MCCB.
Description LG
Auxiliary SwitchesRated Thermal Current lthRated Making Capacity
6 A20 A
ac (ac-15)– Rated Operational Voltage– Rated Operational Current
dc (dc-13)– Rated Operational Voltage– Rated Operational CurrentBack-up FuseMiniature Circuit Breaker
230/400/600 V6/3/0.25 A
125/250 V0.5/0.15 A
6/4/4 A6/4 A
ReleasesUndervoltage Releases (“r” Releases)Response Voltage:– Drop (Breaker Tripped) Us– Pickup (Breaker May Be Switched on) Us
Power Consumption in Continuous Operation at:– 50/60 Hz 12 Vac– 50/60 Hz 24 Vac– 50/60 Hz 48 – 60 Vac– 50/60 Hz 110 – 127 Vac– 50/60 Hz 208 – 240 Vac– 50/60 Hz 380 – 500 Vac– 50/60 Hz 525 – 600 Vac– 12 Vdc– 24 Vdc– 48 – 60 Vdc– 110 – 125 Vdc– 220 – 250 VdcMaximum Opening Time
35 – 70%85 – 110%
1.9 VA3.9 VA
2.5 – 3.8 VA1.8 – 2.4 VA2.7 – 3.8 VA3.4 – 5.8 VA3.4 – 4.3 VA
1.6 W3.1 W
2.0 – 3.1 W1.6 – 2.2 W3.1 – 4 W
50 ms
Description LG
Shunt TripsShunt Trips (“f” Releases)Response Voltage:– Pickup (Breaker Tripped) Us
Power Consumption in (Short Time) at:– 50/60 Hz 24 Vac– 50/60 Hz 48 – 60 Vac– 50/60 Hz 48 – 127 Vac– 50/60 Hz 110 – 240 Vac– 50/60 Hz 380 – 440 Vac– 50/60 Hz 380 – 600 Vac– 50/60 Hz 480 – 600 Vac– 12 – 24 Vdc– 48 – 60 Vdc– 110 – 125 Vdc– 220 – 250 Vdc
70 – 110%
87 – 405 VA710 – 1105 VA
– 66 – 432 VA127 – 188 VA
–34 – 60 VA
164 – 631 W830 – 1580 W112 – 150 W40 – 58 W
Maximum Load Duration InterruptsAutomatically
Maximum Opening Time 50 ms
Molded Case Switch (with High Magnetic Trip)Unfused IC at 415 V (kA)Self-Protected, Will Trip Above:
704000/6300
5.58(141.7)
10.13(257.3)
4.06(103.1)
5.48(139.2)
1.92(48.8)
2.43(61.7)
3.16(80.3)
R .25(6.4)
2.00(50.8)
2.69(68.3)
5.38(136.7)
BREAKER
For more information visit: www.eatonelectrical.com TD01200001E
Technical DataPage 14 Effective: March 2004
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Time-Current Curves
Tripping CharacteristicsThe operating values specified for the inverse time overcurrent releases (thermal overload releases, “a” releases) are mean values of the scatter bands of all setting ranges from the cold state and with uniform current loading of the conducting paths.
The tripping characteristics of the instantaneous (electromagnetic) short circuit releases (“n” releases) are based on the rated phase current In which, in the case of circuit breakers with adjust-able thermal overload releases, is also the upper value of the setting range. With a lower setting current, a corre-spondingly higher multiple is obtained for the operating current of the “n” release.
Figure 7. Tripping Time Characteristics (Thermal Memory)
Cold Cold
Warm
Warm
0 1 5 min 10
2/3
1
1/3
Cooling Down
Heating Up
Figure 8. Type LG Time Current Curve for Standard Thermal Magnetic Trip Units
TD01200001E For more information visit: www.eatonelectrical.com
Technical DataEffective: March 2004 Page 15
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Figure 9. LG Electronic Trip Unit Long Delay Response and Short Delay with I2T Response Curve
For more information visit: www.eatonelectrical.com TD01200001E
Technical DataPage 16 Effective: March 2004
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Figure 10. LG Electronic Trip Unit Long Delay Response and Short Delay with Flat Response Curve
TD01200001E For more information visit: www.eatonelectrical.com
Technical DataEffective: March 2004 Page 17
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Figure 11. LG Electronic Trip Unit Ground Fault Delay Response Curve
For more information visit: www.eatonelectrical.com TD01200001E
Technical DataPage 18 Effective: March 2004
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
Current Limiting Curves
Current Limiting Characteristics and Maximum I2t Values
Figure 12. Type LG Current Limiting Characteristics for 50/60 Hz 380/415/480 Vac
Figure 13. Type LG Maximum I2t Values for 50/60 Hz 380/415/480 Vac
Figure 14. Type LG Current Limiting Characteristics for 50/60 Hz600/660/695 Vac
Figure 15. Type LG Maximum I2t Values for 50/60 Hz 600/660/695 Vac
CSA is a registered trademark of the Canadian Standards Association. NEMA is the registered trademark and service mark of the National Electrical Manufacturers Association. UL is a federally registered trademark of Underwriters Laboratories Inc.
0.3
5 7 10 20 30 50 kA 100
200
kA
100
80
60
40
20
10
8
6
4
2
CU
T-O
FF
CU
RR
EN
T I
P
SHORT CIRCUIT CURRENT ISrms
0.2
cos =0.25
5 7 10 20 30 50 kA 100
100
80
60
40
20
10
6
4
2
1
I2 t
VA
LUE
X10
5
SHORT CIRCUIT CURRENT ISrms
8
5 7 10 20 30 50 kA 100
200
kA
100
80
60
40
20
10
8
6
4
2
CU
T-O
FF
CU
RR
EN
T I
P
SHORT CIRCUIT CURRENT ISrms
0.3
0.2
cos =0.25
5 7 10 20 30 50 kA 100
100
80
60
40
20
10
6
4
2
1
I2 t
VA
LUE
X10
5
SHORT CIRCUIT CURRENT ISrms
8
A2s
TD01200001E For more information visit: www.eatonelectrical.com
Technical DataEffective: March 2004 Page 19
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
This page intentionally left blank.
Technical DataPage 20 Effective: March 2004
LG Molded Case Circuit Breakers 250 – 630 Amperes Ordering Guide
© 2004 Eaton CorporationAll Rights ReservedPrinted in USAPublication No. TD01200001E/Z-2324March 2004