of 35/35
DOCUMENT CONTROL NUMBER / © 2004 Tyco Safety Products PAGE 1 of 35 MX 17A-05-O 5 11/04 Registered Office: First Floor North Building Walden Court Parsonage Lane Bishop’s Stortford Herts CM23 5DB EQUIPMENT: PUBLICATION: ISSUE No. & DATE: ‘MX’ ADDRESSABLE FIRE CONTROLLERS OPERATING INSTRUCTIONS LIST OF CONTENTS 1. INTRODUCTION 5 1.1 KEY FUNCTIONS AND FEATURES 5 2. OPERATING INSTRUCTIONS 6 2.1 OPERATOR’S INDICATORS AND CONTROLS 6 2.1.1 GENERAL 6 2.1.2 OPERATOR DISPLAY MODULE 6 2.1.3 OPERATOR CONTROL MODULE 9 2.1.4 DCM800 DISPLAY CONTROL MODULE 9 2.2 LCD DISPLAY 11 2.2.1 FIRE WINDOW 11 2.2.2 STATUS WINDOW 11 2.2.3 MAIN WINDOW 11 2.2.4 SOFTKEY WINDOW 11 2.3 NORMAL OPERATION 12 2.3.1 EVENT MONITORING 12 2.3.2 EVENT DISPLAY 12 2.4 OPERATION IN ALARM 12 2.4.1 SYSTEM RESPONSE 12 2.4.2 SOUNDER SILENCING 13 2.4.3 RESETTING THE CONTROLLER 14 2.4.4 MULTIPLE EVENTS 14 2.4.5 PRE-ALARM WARNINGS 14 2.5 OPERATION IN FAULT CONDITION 14 2.5.1 SYSTEM RESPONSE 14 2.5.2 OPERATOR ACTION 14 2.6 FIRE CONTROL KEYS 15 2.6.1 EVACUATE or FIRE ALARM 15 2.6.2 DAY/NIGHT MODE 15 2.6.3 TEST 15 2.7 AUXILIARY DISPLAY DEVICES 15 2.7.1 GENERAL 15 2.7.2 REPEATERS 16 2.7.3 PRINTERS 16 3. CONTROLLER FUNCTIONS 16 3.1 ACCESS LEVELS 16 3.1.1 GENERAL 16 3.2 ENTERING PASSCODES 17 3.3 VALID VALUES 17 3.4 MAIN MENU 18 3.5 ACCEPT EVENTS 18 3.6 VIEW STATUS 18 3.7 ISOLATE/DE-ISOLATE 20 3.8 TIME/DATE 21 3.8.1 SET TIME/DATE 21 3.8.2 SUMMER/WINTER 21 3.9 EVENT LOG 21 3.9.1 VIEW EVENT LOG 22 3.9.2 PRINT EVENT LOG 22 3.9.3 FILTER 22 3.10 VIEW/PRINT STATUS 23 3.10.1VIEW/PRINT POINTS ISOLATED 23 3.10.2VIEW/PRINT POINTS UNTESTED/FAILED 23 3.10.3VIEW/PRINT POINT VALUES 23 3.10.4VIEW FAULTS 24 3.10.5VIEW LOOP POINT COUNTERS 24 3.11 SERVICE 25 3.11.1WALK TEST 26 3.11.2MAINTENANCE 28 3.11.3CONFIGURATION 29 4. ROUTINE CHECKS 34 4.1 GENERAL 34 4.2 DAILY CHECKS 34 4.3 WEEKLY CHECKS 34

t2000 User Fire Alarm System

  • View
    368

  • Download
    116

Embed Size (px)

Text of t2000 User Fire Alarm System

  • DOCUMENT CONTROL NUMBER /

    2004 Tyco Safety Products PAGE 1 of 35

    MX17A-05-O5 11/04

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    MX ADDRESSABLE FIRE CONTROLLERS

    OPERATING INSTRUCTIONS

    LIST OF CONTENTS

    1. INTRODUCTION 51.1 KEY FUNCTIONS AND FEATURES 5

    2. OPERATING INSTRUCTIONS 62.1 OPERATORS INDICATORS

    AND CONTROLS 62.1.1 GENERAL 62.1.2 OPERATOR DISPLAY

    MODULE 62.1.3 OPERATOR CONTROL

    MODULE 92.1.4 DCM800 DISPLAY CONTROL

    MODULE 92.2 LCD DISPLAY 11

    2.2.1 FIRE WINDOW 112.2.2 STATUS WINDOW 112.2.3 MAIN WINDOW 112.2.4 SOFTKEY WINDOW 11

    2.3 NORMAL OPERATION 122.3.1 EVENT MONITORING 122.3.2 EVENT DISPLAY 12

    2.4 OPERATION IN ALARM 122.4.1 SYSTEM RESPONSE 122.4.2 SOUNDER SILENCING 132.4.3 RESETTING THE CONTROLLER 142.4.4 MULTIPLE EVENTS 142.4.5 PRE-ALARM WARNINGS 14

    2.5 OPERATION IN FAULT CONDITION 142.5.1 SYSTEM RESPONSE 142.5.2 OPERATOR ACTION 14

    2.6 FIRE CONTROL KEYS 152.6.1 EVACUATE or FIRE ALARM 152.6.2 DAY/NIGHT MODE 152.6.3 TEST 15

    2.7 AUXILIARY DISPLAY DEVICES 152.7.1 GENERAL 152.7.2 REPEATERS 162.7.3 PRINTERS 16

    3. CONTROLLER FUNCTIONS 163.1 ACCESS LEVELS 16

    3.1.1 GENERAL 163.2 ENTERING PASSCODES 173.3 VALID VALUES 173.4 MAIN MENU 18

    3.5 ACCEPT EVENTS 183.6 VIEW STATUS 183.7 ISOLATE/DE-ISOLATE 203.8 TIME/DATE 21

    3.8.1 SET TIME/DATE 213.8.2 SUMMER/WINTER 21

    3.9 EVENT LOG 213.9.1 VIEW EVENT LOG 223.9.2 PRINT EVENT LOG 223.9.3 FILTER 22

    3.10 VIEW/PRINT STATUS 233.10.1VIEW/PRINT POINTS

    ISOLATED 233.10.2VIEW/PRINT POINTS

    UNTESTED/FAILED 233.10.3VIEW/PRINT POINT VALUES 233.10.4VIEW FAULTS 243.10.5VIEW LOOP POINT COUNTERS 24

    3.11 SERVICE 253.11.1WALK TEST 263.11.2MAINTENANCE 283.11.3CONFIGURATION 29

    4. ROUTINE CHECKS 344.1 GENERAL 344.2 DAILY CHECKS 344.3 WEEKLY CHECKS 34

  • MX17A-05-O5 11/04

    PAGE 2 of 35

    This page intentionally left blank

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 3 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    FIRE

    I

    0

    SILENCE

    BUZZER

    RESET

    EVACUATE

    SILENCE/

    RESOUND

    DISABLED

    FAULT

    ACTIVATED

    DAYMODE

    PREALARM

    DISABLED

    FAULT

    ACTIVATED

    SYSTEMFAULT

    MAINSFAULT

    POWERON

    FAULT

    DISABLED

    TEST

    GENERAL

    MISCELLANEOUS

    SOUNDERS

    CONTROLLER

    SIGNALLING

    DAY

    NIGHT

    INVESTIGATE

    DELAY

    POWERFAULT

    0

    12

    3

    45

    6

    78

    9

    ABC

    DEF

    GHI

    JKL

    MNO

    PQRS

    TUV

    WXYZ

    Last

    Fire

    002

    General

    Zone

    030

    B055

    4th

    Floor

    Washroom

    /Window

    F1

    F2

    F3

    F4

    F5

    LED

    Tst

    More

    Zone

    002

    B002

    1st

    Floor

    Corridoor

    Room

    117

    First

    Fire

    Information

    Fig. 1 MINERVA MX Fire Controller - Front Panel

    T2000 ONLY

  • MX17A-05-O5 11/04

    PAGE 4 of 35

    3

    DEF

    7

    PQRS

    F5F4F3F2F1

    1

    *

    2

    ABC

    6

    MNO

    9

    WXYZ

    0

    8

    TUV

    5

    JKL

    4

    GHI

    FIREFAULT

    DISABLED

    TEST

    PRE ALARM

    DAY MODE

    ACTIVATED

    FAULT

    DISABLED

    ACTIVATED

    FAULT

    DISABLEDSTATUS 1

    STATUS 2

    GENERAL SOUNDERS

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    27

    28

    29

    30

    31

    32

    33

    34

    35

    36

    37

    38

    39

    41

    42

    43

    44

    45

    46

    47

    48

    49

    50

    51

    52

    53

    54

    55

    56

    57

    58

    61

    62

    63

    64

    65

    66

    67

    68

    69

    70

    71

    72

    73

    74

    75

    76

    77

    78

    79

    80

    I

    0

    POWER ON

    MAINS FAULT

    SYSTEM FAULT

    40 60

    59

    SILENCE

    BUZZERRESET

    INVESTIGATE

    DELAYFUNCTION EVACUATE

    SILENCE

    RESOUND

    DAY

    NIGHT

    GENERAL SYSTEM SOUNDERS SIGNALLING CONTROLLER

    ZONE DISPLAY

    1 - Accept Events2 - Actual Status3 - (De-) Isolate4 - Time / Date5 - Event Log6 - View/Prn Status7 - Service

    9 - Test Buzzer,LED's Display

    Alarm Count: 0021

    SYSTEM

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back0000

    Main menu

    SounSIL

    Fig. 2 MX2 Fire Controller - Front Cover

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 5 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    1. INTRODUCTIONThe instructions given in this document are common to allthe MX range of fire controllers, any differences beingoutlined as appropriate This document is written forFirmware Version 5.0.The MINERVA MX range, form a comprehensive andcompatible range of modular and flexible EN54 approved(the MX2 and MX Black Box Panel are additional MXcompatible units which are fully EN54 : Part. 2 and Part. 4compliant) addressable fire controllers using Tyco MXTechnologyTM.

    Standard MINERVA MX fire controllers include: MX1000 250 point, 40/80/120/160/200 or

    240 zone network capable fire controller 1loop controller in compact designer housing.

    MX4000 1000 point, 40/80/120/160/200or 240 zone network capable fire controller -2 to 4 loop controller in compact designerhousing.

    MX4000M 1000 point, 40/80/120/160/200or 240 zone network capable fire controller 2 to 4 loop controller in modular rack stylehousing.

    T2000 1000 point, 40/80/120/160/200 or240 zone network capable fire controller - 2to 4 loop controller in Marine approvedcompact housing.

    MXR Fully functional repeater in compactdesigner housing.

    T2000 Marine Full Function Repeater. MX2-100 - 250 point, 40/80/160/200 or 240

    zone network capable fire C.I.E. 1 loopC.I.E. in housing with integral backupbatteries.

    MX2-200 - 1000 point, 40/80/160/200 or240 zone network capable fire C.I.E. - 2 to 4loop C.I.E. in housing with integral backupbatteries.

    All variants fully comply with the requirements of EN54parts 2 and 4 and may be installed in a system whichcomplies with the requirements of BS 5839 : Part 1(2002). The Marine versions also comply with therequirements of S.O.L.A.S. and marine ClassificationSocieties.

    1.1 KEY FUNCTIONS AND FEATURESAll MINERVA MX controllers are built around commonhardware and software modules incorporating the followingcommon functions and features:

    An integral 110-250V ac battery backedpower supply providing 24V dc (nominal) atup to 5A (alarm load) for powering

    conventional detection zone interfaces(DIM800), conventional sounders andbeacons, door release mechanisms andinterface relays and remote full functionrepeaters.

    Power supply incorporates a 24V DCcharger capable of charging up to 38Ahbatteries to provide up to 72 hours backupand 30 minutes in alarm (BS 5839 : Part 1)or 90 hours backup and 15 minutes in alarm.

    Full EN54 compliant control switches andindicators with keyswitch enable andoptional programmable LED indicators andcontrol switches.

    Large backlit 16 line x 40 character LCDdisplay with detailed and preciseidentification of all sectors, zones andpoints, comprehensive 95 characteremergency procedure instructions and fullsystem status indication including countersof number of points in alarm, fault, disabledand test mode.

    Extensive menu driven and passwordcontrolled operator and engineer functionsincluding extensive isolate, override, test,service and diagnostic functions.

    System manager and engineer functionsincluding editing of point descriptions andviewing/printing of point values includingCO levels, temperatures and detectorobscuration levels.

    Optional self-test and verification ofdetectors from the controller.

    Peer-to-peer communication with up to 98other controllers providing a seamlessoperator interface to all other relevantdefined controllers on the network.

    Event log for logging of up to 3000 eventswhich can be viewed, selected and printed.

    Constant monitoring of all detectors andinput circuits and processing of detectorsensor information using standard, CCO andFastLogic fuzzy logic algorithms.

    Long term averaging and conditionmonitoring of smoke detectors with dirtydetector identification.

    Automatic or manual switching of detectormodes and sensitivities according to changesin occupancy patterns (day mode) andvariations in fire risk.

    Constant fault monitoring of all hardwarecomponents, power supplies, batteries,relays, sounder and speaker circuits,addressable loops, detectors and addressabledevices, monitored input circuits, remoteand local communication links.

  • MX17A-05-O5 11/04

    PAGE 6 of 35

    Communication with up to 250 addresses onup to 4 detection loops per controller and acombination of up to 1500 auxiliary I/O,controller plus 7 full function repeaters andmultiple remote printers.

    Signalling, supervision, status and faultindication of central station alarm signallingequipment such as BT Redcare STU.

    Option for one repeater to be provided from aremote PC computer using MX-Remoteservice and diagnostics software over thepublic switched telephone network (PSTN).

    Default cause and effect providing computercontrol of all outputs, sounders, beacons andspeakers in the event of alarm conditions.

    Powerful programmable cause and effectusing the flexible and easily configuredMINERVA group based event/actionprogramming language.

    Synchronisation and multiple output pulsepatterns for phased evacuation of up to 240zones using Bell Mapping.

    Arrangement of points in up to 240 detectionzones per controller.

    2. OPERATING INSTRUCTIONS2.1 OPERATORS INDICATORS

    AND CONTROLS2.1.1 GENERALALL operator controls and indicators are mounted on the frontpanel. For the MX/T2000, these are provided by the OperatorDisplay Module (ODM800 - top module) and the OperatorControl Module (OCM800 - bottom module). The ODMcontains the alphanumeric LCD display, keypad andSoftkeys. The OCM contains the ENABLE KEY,indicator LEDs and control keys.For MX2 systems all operator controls and indicators exceptthe ENABLE KEY are provided by the Display ControlModule (DCM800). The ENABLE KEY is providedseparately at the bottom of the front panel.

    2.1.2 OPERATOR DISPLAY MODULEThe Operator Display Module (Fig. 3) contains the followingindicators and controls:

    A 640 character backlit LCD alphanumericdisplay, arranged in 16 rows of 40 characters.This is used to display information about thesystem status and alarms. The backlight is onwhen the keyswitch is set to the enableposition, when a key is pressed or when anAlarm or Fault is present.

    Switches F1 to F5 - used to carry out thefunctions displayed on the bottom line ofthe LCD display.

    An alphanumeric keypad used for enteringaccess codes, text strings or generalinformation as follows:

    SCROLL UP and SCROLL DOWN keys -used to scroll through a display or log oneentry at a time. These keys will auto-repeatif held down, ie, will scroll continuously.

    When used in conjunction with theConfiguration menu, the UP key switchesto upper case and the DOWN key to lowercase.

    7PQRS

    8TUV

    9WXYZ

    6MNO

    5JKL

    4GHI

    3DEF

    2ABC

    0

    1

    Used to enter the number 0

    Used to enter the number 1 or specialsymbols

    Used to enter the number 2 or letters A,B or C

    Used to enter the number 3 or letters D,E or F

    Used to enter the number 4 or letters G,H or I

    Used to enter the number 5 or letters J,K or L

    Used to enter the number 6 or letters M,N or O

    Used to enter the number 7 or letters P,Q, R or S

    Used to enter the number 8 or letters T,U or V

    Used to enter the number 9 or letters W,X, Y or Z

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 7 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    0

    12

    3

    45

    6

    78

    9

    ABC

    DEF

    GHI

    JKL

    MNO

    PQRS

    TUV

    WXYZ

    First

    Fire

    Last

    Fire

    002

    General

    Zone

    002

    B002

    1st

    Floor

    Corridoor

    Room

    117

    Zone

    030

    B055

    4th

    Floor

    Washroom

    /Window

    F1

    F2

    F3

    F4

    F5

    LED

    Tst

    More

    Information

    Fig. 3 MX/T2000 - Operator Display Module

    SOFT

    KEY

    S

    SCRO

    LL U

    P

    SCRO

    LL D

    OW

    N

    ALP

    HA

    NUM

    ERIC

    KEY

    PAD

  • MX17A-05-O5 11/04

    PAGE 8 of 35

    3

    DEF

    7

    PQRS

    F5F4F3F2F1

    1

    *

    2

    ABC

    6

    MNO

    9

    WXYZ

    0

    8

    TUV

    5

    JKL

    4

    GHI

    FIREFAULT

    DISABLED

    TEST

    PRE ALARM

    DAY MODE

    ACTIVATED

    FAULT

    DISABLED

    ACTIVATED

    FAULT

    DISABLEDSTATUS 1

    STATUS 2

    GENERAL SOUNDERS

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    27

    28

    29

    30

    31

    32

    33

    34

    35

    36

    37

    38

    39

    41

    42

    43

    44

    45

    46

    47

    48

    49

    50

    51

    52

    53

    54

    55

    56

    57

    58

    61

    62

    63

    64

    65

    66

    67

    68

    69

    70

    71

    72

    73

    74

    75

    76

    77

    78

    79

    80

    I

    0

    POWER ON

    MAINS FAULT

    SYSTEM FAULT

    40 60

    59

    SILENCE

    BUZZERRESET

    INVESTIGATE

    DELAYFUNCTION EVACUATE

    SILENCE

    RESOUND

    DAY

    NIGHT

    GENERAL SYSTEM SOUNDERS SIGNALLING CONTROLLER

    ZONE DISPLAY

    ALPHANUMERICKEYPAD

    SCROLLUP

    SCROLLDOWN

    SOFTKEYS

    1 - Accept Events2 - Actual Status3 - (De-) Isolate4 - Time / Date5 - Event Log6 - View/Prn Status7 - Service

    9 - Test Buzzer,LED's Display

    Alarm Count: 0021

    SYSTEM

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Main menu

    Fig. 4 MX2 - Display Control Module

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 9 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    2.1.3 OPERATOR CONTROL MODULEThe Operator Control Module (Fig. 5) contains thefollowing indicators and controls:INDICATORS

    GENERAL 2 red General ALARM LEDs. A yellow General Fault LED. A yellow General Disablement LED. A yellow General Test LED.

    MISCELLANEOUS A red Pre-Alarm LED. A yellow LED to indicate Day Mode. A yellow LED to indicate customer defined

    functions eg, Delay.

    A yellow LED to indicate customer definedfunctions eg, Fire Doors.

    SIGNALLING A red Signalling Activated LED. A yellow Signalling Fault LED. A yellow Signalling Disabled LED.

    SOUNDER A red Sounders Activated LED. A yellow Sounder Fault LED. A yellow Sounders Disabled LED.

    CONTROLLER A green Power ON LED. A yellow Charger Fault LED. A yellow Processor Fault LED. A yellow Power Fault LED indicates loss of

    mains and back up power (T2000 only).

    CONTROLS ENABLE keyswitch - a two position

    keyswitch, with positions normal (0) andenable (1).

    Seven control switches: SILENCE BUZZER - used to silence

    the internal buzzer. SILENCE/RESOUND - used to silence/

    resound external sounders. EVACUATE (FIRE ALARM T2000) -

    used to activate external sounders. RESET - used to reset the system after

    an alarm or event has occurred. DAY MODE - used to set the system

    into the daytime operation mode. INVESTIGATE DELAY - is used to

    end signalling delay time and start theinvestigation time.

    SPARE - is configurable to customerrequirements.

    2.1.4 DCM800 DISPLAY CONTROLMODULE

    The DCM800 (Fig. 4) is used on the MX2 variants toprovide all the functions of the OCM800 and ODM800 asused in the MX and T2000 variants.Indicators and controls are defined as for the ODM800 andOCM800 modules in Section 2.1.2 and 2.1.3. TheDCM800 includes all indicators and controls listed in thesetwo sections except for the SPARE - FUNCTION KEYfrom the ODM800.

  • MX17A-05-O5 11/04

    PAGE 10 of 35

    FIRE

    I

    0

    SILENCE

    BUZZER

    RESET

    EVACUATE

    SILENCE/

    RESOUND

    DISABLED

    FAULT

    ACTIVATED

    DAY

    MODE

    PREALARM

    DISABLED

    FAULT

    ACTIVATED

    SYSTEMFAULT

    MAINSFAULT

    POWERON

    FAULT

    DISABLED

    TESTGENERAL

    MISCELLANEOUS

    SOUNDERS

    CONTROLLER

    SIGNALLING

    DAY

    NIGHT

    INVESTIGATE

    DELAY

    ENABLE

    KEYSWITCH

    CONTROL

    SWITCHES

    T2000

    ONLY

    (POWERFAULT)

    T2000

    ONLY

    (FIREALARM)

    Fig. 5 MX/T2000 - Operator Control Module

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 11 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    2.2 LCD DISPLAYThe LCD display is divided into four windows as shown in Fig. 6:

    Fire 19 characters x 8 lines Main 19 characters x 14 lines Status 19 characters x 5 lines Softkeys F1, F2, F4 and F5 - 7 characters, F3 - 8 characters

    1234567890123456789 1234567890123456789123 Main4 Window5678901234

    123 Fire4 Window5678

    12 Status3 Window45

    S'key 1 S'key 2 S'key 3 S'key 4 S'key 5

    Fig. 6

    2.2.1 FIRE WINDOWThe fire window in the quiescent mode will display theproduct name, date/time and company name.On detection of an Alarm condition, the fire window willdisplay First Fire and associated information. Formultiple alarms in the system the fire window will displaythe first and last alarms.The number of alarms is displayed at the right hand side ofline 5 in the fire window.

    First FireZone 002 B0011st Floor CorridoorRoom 117Last Fire 002Zone 030 B0554th FloorWashroom / Window

    2.2.2 STATUS WINDOWThe status window displays the number of faults, isolatesetc.

    2.2.3 MAIN WINDOWThe main window displays logs, information text, menusand device identification.

    2.2.4 SOFTKEY WINDOWThe softkey windows change dependant on the optionselected.

  • MX17A-05-O5 11/04

    PAGE 12 of 35

    2.3 NORMAL OPERATIONWhen the controller is initially powered up, with no faults oralarms in the system and the Enable key in the offposition, the following screen is displayed:

    2.3.1 EVENT MONITORINGThe term event is used to describe a change in systemstatus that must be acknowledged and/or generates anoutput.

    Examples of events include: Mains failure Detection of a fire condition Operation of EVACUATE/FIRE ALARM

    key

    All events trigger a response, the category of which dependson the event type and will be one of the following (inpriority order):

    Full Alarm or Alert Pre-Alarm

    Fault

    Isolation Test Mode Warning

    Information

    When an event occurs, it is stored in the event log. Thecontents of this log may be displayed in two formats:

    Unaccepted and locally accepted events All events in chronological order of

    occurrence

    The events are stored in chronological order withunaccepted events marked as outstanding. The event logmay hold up to 3000 events; in the unlikely occurrence ofthe log filling up, the oldest record will be overwritten.

    MX Panel

    Fri, 17-Mar-0011:57

    Company Name

    General

    LED Tst Light

    2.3.2 EVENT DISPLAYThe display automatically shows the last event of thecategory with the highest priority. With Scroll keys, it ispossible to get all events in this category in chronologicalorder. With Softkey F5 the user can change to anothercategory (if available).Important: Category Full Alarm/Alert shows only the firstpoint of a zone in alarm. If two points of one zone are inalarm, only the first one which was in alarm will bedisplayed. The second alarm can only be accessed via themenu option View Event Log.

    2.4 OPERATION IN ALARM2.4.1 SYSTEM RESPONSEWhen a fire condition is detected, the system responds asfollows:

    1) The internal buzzer will sound in acontinuous tone.

    2) Both red FIRE LEDs will light.3) The SOUNDERS and NOTIFICATION

    STATUS ACTIVATED red LEDs willlight.

    Note: If the alarm is initiated by a detector, there maybe a delay of from 1 to 10 minutes before theNOTIFICATION STATUS ACTIVATED ledlights. This is to allow time for the alarm to beinvestigated and any relevant action takenbefore signalling is initiated. A Callpoint set toevacuate will initiate signallingimmediately. Refer to Section 2.6.3.

    4) For the MX controllers, the sounders andany other configured outputs will beactivated.

    5) The LCD will display a message in theformat:

    First FireZone 002 B0021st Floor CorridoorRoom 117

    General

    Menu

    First Fire

    Passcode More

    001

    Information

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 13 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    6) For a T2000 controller, the sounders and anyo t h e r c o n f i g u r e d o u t p u t s w i l l b eactivated. If the alarm is not acceptedwithin the programmed delay period bypressing the INVESTIGATE DELAY key,all other sounder outputs will be activated.

    The message format is as follows:Under FIRE:

    The top line shows the Zone and Point number of thedevice in alarm.The second line shows the zone description (defined atconfiguration).The third line shows the point description (defined atconfiguration).The fourth line shows the type of alarm.If no information text is shown:

    The fifth line shows date and time.The sixth line shows the device type.

    The seventh line shows the actual CURRENTtemperature (if heat sensor).

    Note: The above is only displayed if Extended AlarmInformation has been selected atconfiguration.

    Under First Fire:The first three lines from FIRE arerepeated.The number of alarms is displayed on theblack bar underneath the first fireinformation.

    2.4.2 SOUNDER SILENCINGWhen a FIRE ALARM is received, investigate the cause ofthe alarm.

    WARNING:

    WHEN SEARCHING AN AREA FOR THE SOURCE OF A FIRE ALARM SIGNAL, WHERE A FIRE ALARM HAS BEEN

    INITIATED BY A CARBON MONOXIDE FIRE DETECTOR, IT MUST BE

    REMEMBERED THAT A CARBON MONOXIDE FIRE DETECTOR MAY

    GENERATE AN ALARM BEFORE OTHER FIRE INDICATORS (SUCH AS SMOKE) ARE

    PRESENT.

    THIS OCCURS MOST NOTABLY IN DEEP SEATED FIRES IN DENSELY PACKED

    MATERIALS, AREAS WHERE FIRES MAY OCCUR IN CUPBOARDS AND

    STOREROOMS REMOTE FROM DETECTORS AND WHERE SMOKE

    IMPERVIOUS BARRIERS EXIST BETWEEN THE SEAT OF THE FIRE AND THE

    DETECTOR (SUCH AS WITHIN WALL CAVITIES). THESE FACTORS SHOULD BE

    CONSIDERED CAREFULLY BEFORE DECLARING SAFE ANY AREA WHERE A CARBON MONOXIDE FIRE DETECTOR

    HAS RAISED AN ALARM.

    Once the cause of the alarm has been determined and allappropriate action has been taken, silence the sounders asfollows:

    a) Insert the key into the front panel keyswitchand turn it clockwise to the enableposition.

    b) Press SILENCE/RESOUND.

    The system will respond as follows:i) The sounders will be silenced.ii) The SOUNDER ACTIVATED LED will

    extinguish.iii) All other outputs will remain activated.iv) The LCD display will remain showing the

    t y p e o f a l a rm a n d th e f u l l z o n eidentification. The GENERAL displaywindow will show Sounder SIL.

    If it is required to manually resound the sounders, pressingthe SILENCE/RESOUND key will reactivate thesounders.

  • MX17A-05-O5 11/04

    PAGE 14 of 35

    2.4.3 RESETTING THE CONTROLLERNote:

    1) When the system is in a Fire Alarm state,Silence must be operated before Reset ispossible. This interlock is always presentunder Fire Alarm condition, even if all soundersare isolated.

    2) The controller should also NOT be reset untilthe source of the alarm has been determinedby the Fire Brigade or the cause otherwisefound (and the condition removed).

    Once the notes above have been observed, press theRESET key. The display will show the following message:

    Reset

    in

    Progress...

    *

    When the count reaches 0 after 17 to 20 seconds, the LCDwill return to the normal display (Section 2.3) if no faults orother events are present.

    2.4.4 MULTIPLE EVENTSIf, when in alarm condition, a second alarm (of anotherzone) is received, the system response is dependent on thenature and source of the second alarm as follows:

    a) If the sounders have NOT been silenced, thefollowing will occur:

    i) The internal buzzer will continue to soundwithout interruption.

    ii) The LCD will continue to display thealarm message for the FIRST fire alarmand also the last fire alarm.

    iii) The alarm count will be incremented.

    2.4.5 PRE-ALARM WARNINGSIf the LCD shows a message including a warningindication, a pre-alarm condition has been detected by thecontroller. This may be indicated for example, if a detectoridentifies a build-up of smoke or heat that might result froma fire, but the alarm threshold has not yet been reached. Theinternal buzzer will sound but the sounders and visual fireindicators will remain inactive at this stage. Proceed asfollows:

    a) Accept the event, (if the option is available),noting the location of the event.

    b) Initiate action to deal with the conditionindicated, taking care to determine if thewarning was initiated by a fire condition orby a system fault.

    If the detector subsequently shows an alarm condition, analarm will be generated, regardless of whether the pre-alarm warning was accepted.

    2.5 OPERATION IN FAULT CONDITION2.5.1 SYSTEM RESPONSEWhen a Fault condition is detected, the system will respondas follows:

    a) The internal buzzer will pulse.b) The yellow GENERAL FAULT LED will

    light.c) The LCD backlight will come on and will

    display the following type of screen:

    The message format is as follows:The top line shows the Zone and pointnumber in fault condition.The second line shows the zone description(defined in configuration).The third line shows the point description(defined in configuration).The fourth line shows the type of fault.

    If no information text is shown:

    The fifth line shows the date and time.the sixth line shows the device type.

    The message will continue to be displayed until theintervention of an operator or the fault is cleared.

    2.5.2 OPERATOR ACTIONWhen a Fault condition occurs, proceed as follows:

    a) Press the SILENCE BUZZER key.The internal buzzer will silence, but theLED and display will continue to operate asdescribed.

    Zone 000 R10System ZoneBattery Fault IP

    BATTERY FAULT

    17-Mar-00 15:00:00Digital Input

    MX Panel

    Fri, 17-Mar-0015:00

    Company Name

    Flt P 002

    General

    LED Tst

    FAULT

    Info More

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 15 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    b) Investigate the source of the fault and wherepossible remove.

    Note: If the fault cannot be cured, contact your localsupplier and arrange for a service visit.

    The fault information will be displayed until the fault iscleared.

    2.6 FIRE CONTROL KEYSThere are six fire control keys on the Operator Control Module(or Display Control Module for MX2), namely:

    SILENCE BUZZER SILENCE/RESOUND RESET DAY MODE INVESTIGATE DELAY EVACUATE (FIRE ALARM for Marine)

    Only the SILENCE BUZZER key is active without theEnable key being inserted and turned to the Enabledposition.The functions of SILENCE BUZZER, SILENCE/RESOUND and RESET have already been described. Thefunctions of EVACUATE or FIRE ALARM,INVESTIGATE DELAY and DAY MODE are described inthe following paragraphs.

    2.6.1 EVACUATE or FIRE ALARMOnce enabled by the keyswitch, pressing EVACUATE orFIRE ALARM will cause the following:

    a) The internal buzzer will sound continuously.b) The red FIRE LEDs will light.c) The sounders and any other configured outputs

    are activated.d) The LCD will display the following type of

    screen:

    First FireZone 000 RB002R12System ZoneEvacuate Button

    General

    Menu

    F I R EFirst Fire

    Information

    Not Available

    Info Passcode Level >

    001

    2.6.2 DAY/NIGHT MODEIn night mode the system activates immediately when analarm is received, the internal buzzer, all sounders andalarm signalling outputs operate.

    In day mode, on receipt of an alarm, only the internalbuzzer and sounders are activated immediately. A delaytime is started (default 60 seconds) in which the alarmmessage must be acknowledged (Investigate delayswitch) to start the investigation time. If there is noacknowledgement within this time, the alarm signallingoutputs will be activated.The investigation time (default 10 minutes) is the timeremaining for staff to carry out investigation of the alarmsource, before the alarm signalling outputs will beactivated.An evacuate callpoint will initiate an immediate alarm.Signalling is always immediate if sounder faults exist inthe system.

    2.6.3 INVESTIGATE DELAYThe INVESTIGATE DELAY switch is only active whenthe controller is in the DAY MODE of operation. If aFire Alert is received at the controller, the signalling outputis delayed for 1 minute, if the Investigate Delay switch ispressed during this period a further delay (configurablebetween 1 and 10 minutes) is initiated. This delay allowsfor the alarm to be investigated, if it is a false alarm, thecause of the alarm can be removed and the controller to besilenced and reset. If the alarm is real, then pressing theEVACUATE/FIRE ALARM, switch will cause thesignalling output to activate.

    2.6.4 TESTPressing LED TEST causes all the LEDs and internalbuzzer to operate for a few seconds. If the system includesa repeater panel, only the panel that is operated is activated.

    2.7 AUXILIARY DISPLAY DEVICES2.7.1 GENERALDepending on the configuration of the system, there maybe one or more auxiliary display devices fitted. Thesedevices may be of the following types:

    Repeaters

    Printers

    The functions of and operating instructions for thesedevices are given in the following paragraphs.

  • MX17A-05-O5 11/04

    PAGE 16 of 35

    2.7.2 REPEATERSA repeater allows the controller to be operated from aremote location and provides remote indications of thestate of the controller. The front panel of the repeater isidentical to that of the controller (see Fig. 1) and allcontroller operations may be performed at the repeaterpanel.

    2.7.3 PRINTERSRefer to the manual supplied with the printer for operatinginstructions.

    2.7.3.1 LCD REPEATERSLCD Repeaters can:

    Display the alarm and fault messages asdisplayed on the Controller on a backlit 4 x20-character alphanumeric display.

    Provide an internal log for up to 150 events. Provide an internal audible warning of an

    event.

    Allow the event log to be displayed usingthe scroll keys.

    Silence the internal buzzer and externalsounder (if fitted) with the key.

    3. CONTROLLER FUNCTIONSAs stated, the MX controller has built-in functions. Thesefunctions allow the operator to perform such actions asviewing the event log, setting the date and time, etc. Thefunctions are arranged according to sophistication andaccess to certain of them necessarily needs to be restrictedto trained staff.The control of access has been achieved by assigningfunctions to Access Levels, each Access Level having anassociated numeric passcode. The passcode for aparticular Access Level is defined at system configuration.

    MUTE

    3.1 ACCESS LEVELS3.1.1 GENERALThe access levels available are as follows:

    Customer Operator 1 to 7 - 4 digits Customer Manager 1 - 5 digits Customer Manager 2 - 6 digits

    These access levels are described in the followingparagraphs. A maximum of 99 Passcodes are availablewhich may be split between Access Levels as required.

    Note: The Customer Operator 1 Access Level isachieved by turning the ENABLE key to theenable position (ie, a Passcode is notrequired).

    Table 1 contains Access Levels and Menu Optionsavailable at each level.

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 17 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    EnableKey

    PageNo.Customer Operator

    CustomerManager

    1 2 3 4 5 6 7 1 2Lamp/Buzzer/LCD Test OFFUnrestored Events OFFInformation Text OFFView Events (Scrolling) OFF

    MAIN MENU ON 18Accept Events ON 18View Status ON 18Isolate/De-Isolate ON 20Time/Date ON 21

    Set time/Date ON 21Summer/Winter ON 21

    Event log ON 21View Event Log ON 22Print Event Log ON 22Filter ON 22

    View/print status ON 23Points Isolated ON 23Points Untested/Failed ON 23Point Values ON 23View Faults ON 24Loop Point Counter ON 24

    Service ON 25Walk Test ON 26Maintenance engineer ON 28

    Fire Alarm Cycle Count ON 28Maintenance Request ON 28Battery Test ON 28Software Initialisation Count ON 29Project Numbers ON 29Software Versions ON 29Menu Points ON 29

    Configuration ON 29Change Text ON 30

    Table. 1 Menu Options and Access Levels

    3.2 ENTERING PASSCODESIn order to avoid repetition, however, the general procedurefor entering a PASSCODE is described as follows:

    i) Turn the ENABLE key to the ONposition, press F3 (Passcode), enter yourID (press F5 Enter if the ID has only onedigit).

    3.3 VALID VALUESThe following are values which may be entered for eachoption:

    * depending on the configuration 40/80/120/160/200 or240 zones.

    Panel Number 1 - 99Zone Number 1 -

    240*Sector Number 1 - 240RBus Number 0 - 15

    Real PointPseudo PointXBus Point

    1 - 241 - 81 - 96

    Local I/OReal PointPseudo PointIOBus pointTimer PointUser Point

    1 - 181 - 421 - 241 - 101 - 10

  • MX17A-05-O5 11/04

    PAGE 18 of 35

    3.4 MAIN MENUWhen the system is in quiescent mode (ie, displaying thedate and time), entering a passcode affords the user accessto the main menu. The structure of this menu is shownbelow.

    The menu shown is for Customer Manager 2 level. Only theoptions appropriate to the access level entered will bedisplayed.Each of the options available leads to further menus orfunctions, which are described in the following paragraphs.

    3.5 ACCEPT EVENTSAllows displayed events to be accepted. Press 1 from themaine menu, the following type of screen will be displayed:

    Use the F4 Key keys to move betweenevents. Usr F3 Accept to accept an event.

    3.6 VIEW STATUSAllows the status of all points and zones on the system to beviewed. Press 2 from the Main menu, the following type ofscreen will be displayed:

    1 - Accept Events2 - View Status3 - Isolate/De-Isol4 - Time / Date5 - Event Log6 - View/Print Data7 - Service8 - Configuration9 - Test Buzzer,

    LEDs & Display

    Alarm Count: 0021

    MX Panel

    Wed, 01-Aug-0000:01

    Company Name

    General

    Back

    Main menu

    Zone 000 R10System ZoneBattery Fault IP

    BATTERY FAULT

    01-Mar-00 14:15:02Digital Input

    SYSTEM

    Wed, 01-Mar-0014:15

    Company Name

    Fault 02

    General

    Back

    Accept Events

    1000Accept >>

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 19 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    Loop Point (Addressable Loop)Use the +, - and >> keys to select therequired Loop and Point, then press Enterkey.

    RBus Point (Remote Bus)Use the +, - and >> keys to select therequired RBus, Category and Point, thenpress Enter key.

    Local I/O Point (Field Interface Module)Use the +, - and >> keys to select therequired Category and Point, then press Enterkey.

    The following type of screen will be displayed:

    Point Input and Point Output are displayed in the sameformat.

    The top line shows the selected option.The second line shows the Zone and Point number of thedevice.The third line shows the Sector description (defined atconfiguration).The fourth line shows the Zone description (defined atconfiguration).The fifth line shows the Point description (defined atconfiguration).The sixth line shows the device type.

    Point

    Panel02Loop

    A 001

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    View Status

    >> - + Enter

    PointZone 006 A007

    Zone 06Call alarm in roomCP 820

    Input Output

    Normal

    MX Panel

    Wed, 01-Mar-0214:15

    Company Name

    General

    Back

    View Status

    Actual Status IP can be in one of the following states: Normal Fault

    Active

    PreAlarm

    Actual Status OP can be in one of the following conditions: On Off Pulse 1 Pulse 2

    Selecting Zone will display the following type of screen:

    Function Keys F3/F4 will decrement/increment the zonenumber.

    Description

    Alarm Yes One or more devices of a zone in Alarm Mode

    Fault Yes One or more devices of the zone in Fault Mode

    Isolate Yes All alarm input devices of the zone are Isolated

    Walk Test Yes All alarm input devices of a zone in Walk Test

    Zone 002South Building1st Floor Corridoor

    Alarm : NOFault : NOIsolate : NOWalk Test : NO

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    View Status

    _ +

  • MX17A-05-O5 11/04

    PAGE 20 of 35

    3.7 ISOLATE/DE-ISOLATEThe Isolate/De-isolate option allows the following to beisolated/de-isolated:

    Point Complete 1 Point Input 2 Point Output 3 Zone Detectors 4

    Zone Callpoints(also interrupt devices) 5

    Zone Alarm I/Ps 6 Zone Sounders 7 Zone Controls 8 Zone Extinguish 9 Extinguish Controls F2 Fault Signalling F3 Alarm Signalling F4 All Sounders F5

    Press 3 from the Main menu. The following screen will bedisplayed:

    Select the required number from the Isolate/De-Isolate menu,then select the type of point (as described in Section 3.5):

    Loop Point (Addressable Loop)Use the +, - and >> keys to select therequired Loop and Point, then press Enterkey.

    RBus Point (Remote Bus)Use the +, - and >> keys to select therequired RBus, Category and Point, thenpress Enter key.

    Local I/O Point (Field Interface Module)Use the +, - and >> keys to select therequired Category and Point, then press Enterkey.

    1 - Point2 - Point I/P only3 - Point O/P only4 - Zone Detectors5 - Zone Callpoints6 - Zone Alarm I/Ps7 - Zone Sounders8 - Zone Controls9 - Zone Extinguish

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Isolate/De-Isolate

    Alm Sig All SNDFlt SigExt.Ctl

    CAUTION:

    Isolating I/O points may break compliance with EN54. Caution should be exercised when

    dealing with mandatory switches and indicators. Such operations are reserved for

    authorised trained personnel only.

    The following screen shows an example of Point isolation:

    In the Customer Operator access levels, only points on theaddressable loop can be isolated or de-isolated.Isolations are counted and displayed (eg, Isol 001). If onlythe input or output of a point is isolated, this is counted as acomplete isolation of the point.The following screen shows an example of Zone isolation:

    Successes: Number of points that wereDe-Isolated

    Matches: Number of points in Zone (detectors)

    Point CompleteZone 002 B002South Building1st Floor CorridoorRoom 117801 H

    Status IP: NormalISOLATED INPUT

    1 - Isolate2 - De-Isolate

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    Isola 001

    General

    Back

    Isolate/De-Isolate

    Isolation Status

    Zone DetectorsZone 001

    Zone 01

    IsolateAll

    Successes : 003Matches : 003

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    Isola 003

    General

    Back

    Isolate/De-Isolate

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 21 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    The following screen shows an example of All Soundersisolation:

    Successes: Number of sounders (De-)IsolatedMatches: Number of sounders in Zone

    3.8 TIME/DATEPress 4 from the Main menu. The following type of screenwill be displayed:

    3.8.1 SET TIME/DATEPress 1 from the Time/Date menu. The following type ofscreen will be displayed:

    All Sounders

    Successes : 006Matches : 006

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    Isola 006

    General

    Back

    Isolate/De-Isolate

    1 - Set Time/Date2 - Summer/Winter

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Time / Date

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Time / Date

    >> - +

    Date : 01-Mar-00Time : 14:15:17

    Save

    Use the >> key to move the cursor between options, enterdate and time values via the keypad or Softkey F3 (-) andF4 (+).

    Note:1) When a value has been changed, F5 shows

    Save, use this key when all editing has beencompleted.

    2) Months January to September can also beentered with the keypad:

    1 = January ...................

    9 = September

    3.8.2 SUMMER/WINTERPress 2 from the Time/Date menu. The following type ofscreen will be displayed:

    These screens cannot be changed, the information isconfigured in MX CONSYS, use F5 to toggle betweenWinter and Summer.Dates are not shown on a T2000.

    3.9 EVENT LOGPress 5 from the Main menu. The following type of screenwill be displayed:

    SummertimeMX Panel

    Wed, 01-Jan-0014:15

    Company Name

    General

    Back

    Summer/Winter

    Winter

    1 - View Event Log2 - Print Event Log3 - Filter

    MX Panel

    Wed, 09-Aug-0000:01

    Company Name

    General

    Back

    Event Log

  • MX17A-05-O5 11/04

    PAGE 22 of 35

    3.9.1 VIEW EVENT LOGThis option allows all events in the event log to be viewedor printed.Select option 1 from the Event Log menu, the following typeof screen will be displayed:

    The latest event is displayed, use the keys toscroll through the log and the || key to move to the front of the log.

    EventID - Displays the absolute number ofan event (1 to 65,535). After 65,535 it startswith 1 again.

    0001/0010 - The first number is the actualposition in the event log (1 means it displaysthe newest event log entry. The secondnumber displays the number of entries in theevent log (max. 3,000).

    The newest/last event will be displayed when the Event Logis entered.

    3.9.2 PRINT EVENT LOGSelect option 2 from the Event Log menu, the following typeof screen will be displayed:

    This menu option is only available if at least one printer isconfigured.

    Event ID 00010Zone 000System Zone

    TEST FINISHED

    04-Feb-02 19:30:00- Empty -Information only

    0001/0010

    MX Panel

    Wed, 01-Jan-0014:15

    Company Name

    General

    Back

    Event Log

    >>>> - + Print

    Destination :Default Printer

    How far back:to start: 0010

    How many entriesrequired: 0010

    Lowest priorityof interest : 00

    Print initiated

    The destination printer can be selected if more than oneprinter is configured.The priorities available are shown in the following table:

    It is always printed from the selected priority (eg, Non LifeRisk) to the Highest Priority (eg, Non Life Risk, Level 12,Life Risk Alarm and General Alarm).

    3.9.3 FILTERSelect option 3 from the Event Log menu, the followingtype of screen will be displayed:

    It is possible to view and to print the events of singlecategories. The category is selected by pressing theappropriate option number. It is also possible to selectseveral categories, the selected categories are denoted by a+ sign.

    Press F4 to view the selected categorie(s) as described inSection 3.8.1 or F5 to print the selected category(s) asdescribed in Section 3.8.2.

    Lowest Priority Information Only. Level 2. Expected Events. Isolates. Warnings. Visible Isolate. Other Faults. Critical Faults. Gas Alert. Alarm Threshold. Non-Life Risk . Level 12. Life Risk Alarms

    Highest Priority General Alarm

    1 - Fire -2 - Gas Alert -3 - Pre Alarm -4 - Supervisory -5 - Fault -6 - Isolate -7 - Test Mode -8 - Warning -9 - Information -

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Event Log

    PrintView

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 23 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    3.10 VIEW/PRINT STATUSAllows the following options to be viewed/printed. Onnetworked systems, the status of any panel on the networkmay be viewed/printed:

    Points Isolated Points Untested/Failed (during Walk Test) Point Values View Faults (no print option) Loop Point Counters (no print option)

    Select option 6 from the Main menu, the following type ofscreen will be displayed:

    3.10.1 VIEW/PRINT POINTS ISOLATEDSelect option 1 from the View/Print Status menu, thefollowing type of screen will be displayed:

    Note: If the panel is part of a networked system,another screen is displayed before the abovescreen where the panel number may beselected.

    Press F5 Print to print a list of all isolated points.The F2 Key selects either isolated inputs or isolated outputs.Points which are completely isolated (input and output) willbe shown in both lists.

    1 - Points Isolated2 - Pts Unt./Failed3 - Point Values4 - View Faults

    MX Panel

    Wed, 01-Jan-0014:15

    Company Name

    General

    Back

    View/Print Data

    InputTotal : 004

    Zone 001 -001 BPoint Text--------------------001 -002 BPoint Text

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Points Isolated

    PrintOutput

    3.10.2 VIEW/PRINT POINTS UNTESTED/FAILED

    Note: This option only works whilst still in Walktest.

    Select option 2 from the View/Print Status menu, thefollowing type of screen will be displayed:

    Note: If the panel is part of a networked system,another screen is displayed before the abovescreen where the panel number may beselected.

    Press F5 to print the Untested/Failed points.Points which are not tested or points which return the wrongcondition are then listed.

    3.10.3 VIEW/PRINT POINT VALUESSelect option 3 from the View/Print Status menu, thefollowing type of screen will be displayed:

    Select the panel number (if the panel is part of a networkedsystem), loop and point number required.>> - next field_ - the number is decremented+ - the number is incremented

    Total : 004

    Zone 001 -001 BPoint Text--------------------Zone 001 -002 BPoint Text

    MX Panel

    Wed, 01-Jan-0014:15

    Company Name

    General

    Back

    Pts Untested/Failed

    Print

    Panel 02

    Loop PointA 002

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Point Values

    Enter>> - +

  • MX17A-05-O5 11/04

    PAGE 24 of 35

    Pressing F5 displays the following screen:

    Press F5 to print the Point Values of the selected loop (notonly the displayed point).

    3.10.4 VIEW FAULTSSelect option 4 from the View/Print Status menu, thefollowing type of screen will be displayed:

    This option is view only.

    3.10.5 VIEW LOOP POINT COUNTERSThis option is view only. Select option 5 from the View/Print Status menu, the following screen will be displayed:

    Zone 002 B002South Building1st Floor CorridoorRoom 117801H

    Real: 801 H (020)Mode: 1 Sens.: 0

    20 C (032)

    MX Panel

    Wed, 01-Jan-0014:15

    Company Name

    General

    Back

    Point Values

    Print

    o

    Total : 002

    Zone 000 R10Zone 000 R12

    MX Panel

    Wed, 01-Jan-0014:15

    Company Name

    Flt P 002

    General

    Back

    View Faults

    Panel02

    LoopA

    MX Panel

    Wed, 01-Jan-0014:15

    Company Name

    General

    Back

    Loop Point Counters

    >> - + Enter

    Note: Only the Loop will be shown if the panel is notnetworked.

    Select the required panel (only if the panel is networked)and loop, then press the Enter key. The following messageis displayed:

    Please Wait...

    for approximately 2 minutes until the count is complete, ifno faults are found, the following type of screen will bedisplayed:

    Configured - the number of pointsconfigured in CONSYS.

    There are no multiple reserved pointaddresses.

    Conditions for PASSED The number of configured points is equal

    the detected count of points on the loop. There are no unconfigured points. Detected points from left, right and both

    sides are equal.If all conditions are not satisfied, the ATTENTION screenwill be displayed showing the relevant counters.

    Configured - the number of pointsconfigured in CONSYS.

    CounterLoop : APASSED

    Configured : 010

    MX Panel

    Wed, 01-Jan-0014:15

    Company Name

    General

    Back

    Loop Point Counters

    Details Scan

    CounterLoop : AA T T E N T I O N

    Configured : 010

    Conf. & Ident: 009

    MX Panel

    Wed, 01-Jan-0014:15

    Company Name

    General

    Back

    Loop Point Counters

    Details Scan

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 25 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    Conf & Ident - shows how many points areconnected, identified and configured on theloop.

    Not Conf. - shows how many points wereidentified on the loop but not configured inCONSYS.

    Both Sides/Left Side/Right Side - Showshow many points on the loop are recognisedby the panel. Left Side and Right Side isthe count from both sides. Both Sidesmeans the detection of a closed loop.

    Note: If the value of Conf & Ident is different to thenumber of installed devices, multiple reservedaddress may be the cause.

    3.10.5.1 DETAILSPress the Details key (F2), the following type of screenwill be displayed:

    All 250 addresses may be displayed using the >> key.The connection detail of each point is shown by thefollowing symbols:

    Function key F2 scrolls through the loop.

    o OK: point connected, configured and identified (eg, point 33 and points 60 to 64)Point was configured (in MX CONSYS) but not connected or identified (eg, point 21)Point was not configured but connected (eg, point 6)

    MX Panel

    Wed, 01-Jan-0014:15

    Company Name

    General

    Back

    Loop Point Counters

    >>

    DetailsLoop : APoint 01234567890 : ......u...10 : ..........20 : .c........30 : ...o......40 : ..........50 : ..........60 : ooooo.....70 : ..........80 : ..........

    c

    u

    3.10.5.2 SCANPress the Scan key (F3), the following type of screen willbe displayed:

    The points are shown which were detected from both sides(Left/Right).They are displayed as follows:

    Function key F2 scrolls through the loop.

    3.11 SERVICEPress 7 from the Main menu, the following screen will bedisplayed:

    Note: The Maintenance and Diagnostics options areonly available at Customer Manager level andwill not be displayed for lower levels.

    Empty (not used)OK: detected from both sides (eg, points 33 and 82)Only detected from left side (eg, points 4 and 21)

    Only detected from right side (eg, 60 to 64)

    MX Panel

    Wed, 01-Jan-0014:15

    Company Name

    General

    Back

    Loop Point Counters

    >>

    Left / Right ScanLoop : APoint 01234567890 : ....l.....10 : ..........20 : .l........30 : ...*......40 : ..........50 : ..........60 : rrrrr.....70 : ..........80 : ..*.......

    .

    *

    l

    r

    1 - Walk Test2 - Maintenance3 - Diagnostics

    MX Panel

    Wed, 09-Aug-0000:01

    Company Name

    General

    Back

    Service

  • MX17A-05-O5 11/04

    PAGE 26 of 35

    3.11.1 WALK TESTWhen selected, this option allows single or multiple pointsto be tested without an alarm being raised.Press 1 from the Service menu.Only one Walk Test session can be active at one time.

    Use the >>, - and + keys to select the requiredoptions. The Panel number is only displayed when it is partof a networked system.Depending on the selected settings, the display willchange. The following screen is an example of Areaselected as Point.

    To start the Walk Test press F5.

    Possible SettingsPanel

    Panel selection is only available for panels that are in anetworked system.

    Area

    All Walk Test of all elements of a specific type.(Selection in the field Type eg, callpoints).

    Zone Walk Test of all elements of a specific type in a special zone.

    Point Walk Test of the input of a single point.

    Panel : 01Area : AllType : InputLoop : All

    Automatic : NO

    Multisensor : Part

    MX Panel

    Wed, 09-Mar-0200:01

    Company Name

    General

    Back

    Walk test

    >> + - Start

    Panel : 01Area : PointType : InputLocation : LoopZone : 01Point : 01

    Automatic : NO

    Multisensor : Part

    MX Panel

    Wed, 09-Mar-0200:01

    Company Name

    General

    Back

    Walk test

    >> + - Start

    Type

    Loop

    Only with Area as All or Zone.Walk Test of all loops or of a specific loop (A, B, C or D).

    LocationOnly with Area selected as Point.

    Zone

    Only with Area selected as Point.

    PointOnly with Area selected as Point.Selection of a specific zone is possible.

    AutomaticOnly if type selected is detectors.

    Lasertest

    Lasertest is not used.

    Multisensor

    It is only possible to select either Automatic, Lasertestor Multisensor. The panel itself prevents selection of morethan one option.

    Input Walk Test of all inputs.

    Detectors Walk Test of detectors.

    Alarm I/Ps Walk Test of default inputs covered by supergroup Fire Alarm Inputs SG.

    Call Points Walk Test of call points.

    Sounders Walk Test of sounders by loop or all loops plus FIM sounders.

    Loop A point on the loop.

    Loop Selection of a specific zone is possible.

    YES Self test will be carried out by detectors. The following detectors support the self test function:801PH801CH801I

    NO No self test will be done by the detectors.

    Full Part

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 27 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    Note: If Full Walk Test is selected, both modes ofthe detector must be activated (eg, both heatand optical mode for 801PH).If Part Walk Test is selected, the detector hasto be activated in the mode in which it isoperating (eg, for 801PH optical and heat, bothmodes active, then activation of either theoptical or heat will activate the processing. Ifonly the heat mode is active, then onlyactivation of the heat mode will create analarm.

    3.11.1.1 ALL INPUTSSelect the following settings:

    Area: All

    Type: Input

    Loop: All

    Press F5 to start the Walk Test.The following screen shows an example for the Walk TestAll Inputs option:

    Press F3 to display selected settings.Press F5 to end Walk Test.

    Selected: Number of points selected by the test.Excluded: Number of Points not in Walk Test (ie,

    points isolated).Been Active: Number of points which have been

    activated during Walk Test.Been Clear: Number of points which were not

    active when starting Walk Test.Successful: Number of tested points.Curr.Active: Points which are currently active.TestZ001: Number of zones which are in Walk

    Test. The pointer is only counted if all points in a zone are in Walk Test.

    All Inputs

    Selected : 007Excluded : 000Been Active : 005Been Clear : 007Successful : 005Curr.Active : 000

    MX Panel

    Wed, 09-Mar-0200:01

    Company Name

    General

    Back

    Walk test

    Settings End

    TestZ 001

    CAUTION:

    THE FINISHING OF A WALK TEST IS ONLY POSSIBLE IF ALL POINTS IN THE WALK

    TEST ARE INACTIVE.

    3.11.1.2 SOUNDERSSelect Sounders in the Type field.No results will be shown on the display. The selectedsounders will be activated in a pulsing mode.

    3.11.1.3 POINTSelect the following settings:

    Press F5 to start the Walk Test.The following screen shows an example for the Walk Testof Point Input:

    Area: Point.

    Type: Input (appears automatically). Location: Loop (appears automatically). Zone: Required number.

    Point: Required number.

    Selected: 1, if point is in Walk test. Excluded: 1, if point is not in Walk Test (ie, if point

    is isolated). Activations: 1, if point was activated during Walk

    Test. Curr.Active: Yes, if point is currently active.

    Point I/P onlyZone 006 A007

    Zone 06Call alarm in roomCP820

    Selected : 1Excluded : 0Activations : 0Curr.Active : NO

    MX Panel

    Wed, 09-Mar-0200:01

    Company Name

    General

    Back

    Walk test

    Settings End

    TestZ 001

  • MX17A-05-O5 11/04

    PAGE 28 of 35

    Press F3 for a display of selected settings.Press F5 to end Walk Test.

    CAUTION:THE FINISHING OF A WALK TEST IS ONLY

    POSSIBLE IF ALL POINTS IN THE WALK TEST ARE INACTIVE.

    3.11.2 MAINTENANCEPress 2 from the Service menu. The following type ofscreen will be displayed:

    3.11.2.1 VIEW FIRE ALARM CYCLE COUNTWhen selected, the number of Alarm sequences may beviewed.Press 1 from the Maintenance menu. The following type ofscreen will be displayed:

    TestZ 001 Number of zones which are in Walk Test. (The pointer is only counted if all points of a zone are in Walk Test. If one detector on the zone is switched off, the pointer is not decreased. In the case of Walk Test for one point, the pointer is only decreased if that point is the only point on the zone).

    Total: 000MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Maintenance

    Print

    Count :

    0025

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Fire AL.Cycle Count

    3.11.2.2 VIEW/PRINT MAINTENANCEREQUEST

    When selected, this option displays a list of detectors whichare near the limit of their threshold compensation limit.Press 3 from the Maintenance menu. The following type ofscreen will be displayed:

    Press F5 to print the Maintenance Request.

    3.11.2.3 BATTERY TESTWhen selected, this option allows the state of the battery andthe charger current to be displayed.Press 4 from the Maintenance menu. The following type ofscreen will be displayed:

    Total : 003

    Zone 002 B002Zone 004 A126Zone 008 B006

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Maintenance Request

    Print

    Battery State :Battery Low

    Battery Voltage :20.764 V

    Charger Current :00.500 A

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Battery Test

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 29 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    3.11.2.4 SOFTWARE INITIALISATION COUNTWhen selected, this option allows the number of times theCPU has been re-initialised information to be displayed.

    F5 allows the count to be reset to zero.

    3.11.2.5 PROJECT NUMBERSWhen selected, this option allows the project and MXCONSYS information to be displayed.Press 6 from the Maintenance menu. The following type ofscreen will be displayed:

    3.11.2.6 SOFTWARE VERSIONSWhen selected, the software versions of the following aredisplayed:

    Firmware

    Local I/O Each Loop Each MPM

    Network card (if fitted)Press 7 from the Maintenance menu. The following type ofscreen will be displayed:

    -Firmware 25MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Softw. Init. Count

    Reset

    Project:Queen El. Hospital

    Consys: V1.0

    Created:21-Jul-00 10:18Downloaded:27-Jul-00 08:20Last User Update:26-Jul-00 09:10

    MX Panel

    Wed, 01-Mar-0000:01

    Company Name

    General

    Back

    Project Numbers

    Press F5(+) for additional details of the software versions.

    3.11.2.7 MENU POINTSWhen selected, this option allows any configured pointdisplayed to be operated by pressing the appropriate numberbutton, this will toggle from OFF to ON and ON to OFF.Press 9 from the Maintenance menu. The following type ofscreen will be displayed:

    3.11.3 CONFIGURATIONPress 8 from the Main menu. The following screen will bedisplayed:

    -Firmware V 2.0-Bootrom V 1.1-Local I/O V 1.0-Loop A V 1.0-MPM 00 V 1.1-Net V 1.5

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Software Versions

    +

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Menu Points

    >>

    Menu Point 1: OFFIsolate Zone

    Menu Point 2: ONSensit.Change

    Menu Point 3:-Unconfigured-

    Menu Point 4:-Unconfigured-

    ON

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Configuration

    1 - Change Text

  • MX17A-05-O5 11/04

    PAGE 30 of 35

    Menu option 9- Restart will only be displayed if text hasbeen changed and the changes saved.

    RESTRICTIONS ON THE USE OF THEFOLLOWING OPTIONWhen using Configuration menu option 1, ALWAYScommit configuration changes by using Menu option 9 -Restart before leaving the panel.Avoid inactivity timeouts.NEVER use the Back option from the configuration menuif Menu option 9 - Restart is showing.If you do not want to commit changes, by using Menuoption 9 - Restart, option, turn the keyswitch to OFFposition to avoid a timeout situation, do NOT USE theBack option.

    Configuration changes across a network are possible, butchanges to more than one panel at a time MUST NOT beattempted within one session. When a panels configurationhas been changed, it must be restarted using menu option 9Restart.

    Failure to comply with these restrictions may lead tounpredictable effects or system instability.

    3.11.3.1 CHANGE TEXTPress 1 from the Configuration menu. The following screenwill be displayed:

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Change Text

    1 - Point Text2 - Zone Text3 - Sector Text4 - Panel Text5 - Info Text

    3.11.3.2 POINT TEXT MODIFYPress 1 from the Change Text menu. The following screenwill be displayed:

    Select the required loop and point then press Enter. Thefollowing type of screen will be displayed:

    >> - copies the old text to the New text position.- moves the cursor back one position.+ moves the cursor forward one position.Modify the old text or insert new text using thealphanumeric keypad, when finished press Enter.Pressing the scroll up key allows text to be entered inupper case.

    Pressing the scroll down key changes to lower casetext.

    The message Save Data? appears and the functionschange F4 to Yes and F5 to No. Selecting F5 allows thetext modifications to be changed.Selecting F4 Yes displays the message:

    Please wait.....

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Point Text Modify

    Loop : APoint : 001

    >> - + Enter

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Point Text Modify

    Zone 255 -007 A

    Old textCallp. alarm room

    New text

    >> - + Enter

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 31 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    then the following screen is displayed:

    It is now possible to change the text for another Point.Selecting F1 Back will display the following screen:

    Only Change Text and Restart are available allowingmore points to be changed or using Restart to allow thechanges to take effect.

    3.11.3.3 ZONE TEXT MODIFYPress 2 from the Configuration menu. The following screenwill be displayed:

    Select the required and press Enter. The following type ofscreen will be displayed:

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Change Text

    1 - Point Text

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Configuration

    1 - Change Text

    9 - Restart

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Zone Text Modify

    Zone : 001

    - + Enter

    >> - copies the old text to the New text position.- moves the cursor back one position.+ moves the cursor forward one position.

    Modify the old text or insert new text using thealphanumeric keypad, when finished press Enter.The message Save Data? appears and the function changeF4 to Yes and F5 to No. Selecting F5 allows the textmodifications to be changed.Selecting F4 Yes displays the message:

    Please wait.....

    then the following screen is displayed:

    It is now possible to change the text for another Zone.Selecting F1 Back will display the following screen:

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Zone Text Modify

    Zone : 001

    Old textZone 01

    New text

    >> - + Enter

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Change Text

    2 - Zone Text

  • MX17A-05-O5 11/04

    PAGE 32 of 35

    Only Change Text and Restart are available allowingmore points to be changed or using Restart to allow thechanges to take effect.

    3.11.3.4 SECTOR TEXT MODIFYPress 3 from the Configuration menu. The following screenwill be displayed:

    Select the required sector, then press Enter. The followingtype of screen will be displayed:

    >> - copies the old text to the New text position.- moves the cursor back one position.+ moves the cursor forward one position.

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Configuration

    1 - Change Text

    9 - Restart

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Sector Text Modify

    Sector : 001

    - + Enter

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Sector Text Modify

    Sector 001

    Old textSector 01

    New text

    >> - + Enter

    Modify the old text or insert new text using thealphanumeric keypad, when finished press Enter.The message Save Data? appears and the function changeF4 to Yes and F5 to No. Selecting F5 allows the textmodifications to be changed.Selecting F4 Yes displays the message:

    Please wait.....

    then the following screen is displayed:

    It is now possible to change the text for another Sector.Selecting F1 Back will display the following screen:

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Change Text

    3 - Sector Text

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Configuration

    1 - Change Text

    9 - Restart

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 33 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    3.11.3.5 PANEL TEXT MODIFYPress 4 from the Configuration menu. The following screenwill be displayed:

    Select the required Panel.>> - copies the old text to the New text position.- moves the cursor back one position.+ moves the cursor forward one position.Modify the old text or insert new text using thealphanumeric keypad, when finished press Enter.The message Save Data? appears and the function changeF4 to Yes and F5 to No. Selecting F5 allows the textmodifications to be changed.Selecting F4 Yes displays the message:

    Please wait.....

    then the following screen is displayed:

    It is now possible to change the text for another Panel.

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Panel Text Modify

    Panel 00

    Old TextADT

    New Text

    Enter>> - +

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Change Text

    4 - Panel Text

    Selecting F1 Back will display the following screen:

    3.11.3.6 INFO TEXT MODIFYThis option allows Info Text created in Consys to bemodified. Press 5 from the Change Text menu. Thefollowing screen will be displayed:

    Using the + and - keys select the Info Text message tomodify, then press Enter.The following type of screen will appear:

    The >> key deletes all text.The + key advances the cursor one space, the - key goesone space back.

    MX Panel

    Wed, 01-Mar-0014:15

    Company Name

    General

    Back

    Configuration

    1 - Change Text

    9 - Restart

    MX Panel

    Wed, 01-Mar-0314:15

    Company Name

    General

    Back

    Info text modify

    - + Enter

    Infotext No. : 001

    MX Panel

    Wed, 01-Mar-0314:15

    Company Name

    General

    Back

    Info text modifyInfotext No. : 001

    + Enter

    This zone is in aHazardous AreaSpecialprecautionsare required

    ->>

  • MX17A-05-O5 11/04

    PAGE 34 of 35

    Use the alphanumeric keys to modify the text, whenfinished, press Enter.The following screen will be displayed:

    MX Panel

    Wed, 01-Mar-0314:15

    Company Name

    General

    Back

    Info text modifyInfotext No. : 001

    Save data?

    Yes No

    This zone is in aHazardous AreaSpecialprecautionsare required

    4. ROUTINE CHECKS4.1 GENERALIn order to comply with the requirements of BritishStandard BS 5839 Part 1 (1988), the installation must bechecked on a regular basis by a responsible member of staffto confirm that the controller and all ancillary devices areoperating correctly. The required routine checks aredescribed in the following paragraphs.For Marine Systems, carry out routine checks in accordancewith the customers own procedures.

    4.2 DAILY CHECKSProceed as follows:

    a) Ensure the front panel of the controller isindicating a normal condition (ie, no alarmor fault LEDs are lit and the LCD isdisplaying the date and time).

    Note: If the panel is not indicating a normal conditionrecord the condition in the log book and takeany necessary action.

    b) Check that any fault recorded on theprevious day has received attention.

    4.3 WEEKLY CHECKSThese checks would normally be carried out by aresponsible member of the customers staff.

    WARNING:

    WARN ALL PERSONNEL THAT THE SOUNDERS ARE ABOUT TO BE TESTED.

    Proceed as follows:a) If necessary, clean the front panel of the

    controller with a suitable cleansing agent.b) Set one device (either a callpoint or

    detector) from one zone into alarm andcheck that the system responds as follows: The controllers internal buzzer sounds in

    a continuous tone. The two red FIRE LEDs on the

    controller front panel light. The appropriate red FIRE ZONAL LED

    flashes (if configured). The general and zonal sounders operate.

  • MX17A-05-O5 11/04

    2004 Tyco Safety Products PAGE 35 of 35

    Registered Office: First Floor North Building Walden Court Parsonage Lane Bishops Stortford Herts CM23 5DB

    EQUIPMENT:PUBLICATION:ISSUE No. & DATE:

    The alphanumeric display gives thelocation of the alarm.

    c) Record the device used to initiate the test inthe site log book and reset the controller.

    d) Check the condition of the printout on anyprinters attached to the system and replacethe ribbon if it is becoming feint.

    e) Ensure that each printer has an adequatesupply of paper.

    Any defect should be recorded in the log book andappropriate action taken.

    JM/jm28th November 2004