EHV Transmission Equipments

C. K. Thakur

Chief Design Engineer

(Project Engineering Electrical)

NTPC

Page 2: Switchyard lecture1

April 8, 2023 22

Over view

Switching Schemes. Type of Towers. Type of conductors. Switchyard types. Switchyard equipments. Switchyard Layouts.

Page 3: Switchyard lecture1

April 8, 2023 33

Switching schemes

Single bus. Main and Transfer (sectionalised). Double bus. One and half breaker scheme. Double main and Transfer (

Sectionalised). Double Breaker

Page 4: Switchyard lecture1

April 8, 2023 44

Factors Affecting Switching Scheme

System Security/Reliability.

- Feeder Fault.

- Bus Fault.

- Equipment Failure.

- Redundancy.

Page 5: Switchyard lecture1

April 8, 2023 55

Factors Affecting Switching Scheme (Contd.)

Operational Flexibility. Ease of Maintenance. Simplicity of Protection

Arrangements. Ease of Extension. Area available. Cost.

Page 6: Switchyard lecture1

April 8, 2023 66

Line Towers

Single Circuit. Double Circuit. Dead end type. Tension Towers. Suspension Towers.

Page 7: Switchyard lecture1

April 8, 2023 77

Tower Design

Wind Force.Wind Force. Conductor Tension.Conductor Tension. Span.Span. Type of conductor.Type of conductor.

Page 8: Switchyard lecture1

April 8, 2023 88

Tower Hardwares

Insulator Strings.Insulator Strings. Vibration Dampers.Vibration Dampers. Spacers.Spacers. Earthwire & OPGW.Earthwire & OPGW.

Page 9: Switchyard lecture1

April 8, 2023 99

Type of Conductor

ACSR Moose (800A). Zebra (700A). Rabbit (190A). Dog (290A).

Page 10: Switchyard lecture1

April 8, 2023 1100

Switchyard Type

Conventional Air Insulated Type. Gas Insulated type. Air Insulated (Enclosed type).

Page 11: Switchyard lecture1

April 8, 2023 1111

Switchyard Equipments.

Circuit Breaker. Disconnectors. Current Transformers. Capacitor Voltage Transformers. Lightning Arrestors. Post Insulators. Wave Traps

Page 12: Switchyard lecture1

April 8, 2023 1122

General Parameters

Dielectric Parameters .(IEC 694)

- Power Frequency Voltage.

- Lightning Impulse Voltage.

- Switching Impulse Voltage.

- Corona Extinction Voltage.

- RIV Level.

Page 13: Switchyard lecture1

April 8, 2023 1133

400kV Equipments

a. Rated voltage 420 kVb. Rated frequency 50 Hzc. Rated short time withstand

current capacity40 kA rms for one (1) second

d. Insulation levels for 420kV Circuitbreakers and DisconnectingSwitches

e. i) Rated one minute powerFrequency withstand voltage

a) 520 kV rms between liveterminals and earth.

b) 610 kV rms across isolatingdistance.

ii) Rated lightning impulsewithstand voltage

a) +/- 1425 kVp between live terminalsand earth.

b) +/- 1425 kVp impulse on oneterminal and 240 kVp powerfrequency of opposite polarity onother terminal (across isolatingdistance).

iii) Rated switching impulsewithstand voltage

a) +/- 1050 kVp between liveterminals and earth.

b) +/- 900 kVp impulse on oneterminal and 345 kVp powerfrequency of opposite polarity onother terminal (across isolatingdistance).

f. Max. Radio interference voltageat 266kVrms

1000 micro volts for frequencybetween 0.5 Mhz and 2.0 Mhz for allequipment. However, for insulatorstrings the measurement would beat 305 kV .

g. Corona extinction voltage Not less than 320 kV rms

Page 14: Switchyard lecture1

April 8, 2023 1144

220kV Equipments

a. Rated voltage 245 kVb. Rated frequency 50 Hzc. Rated short time withstand

current capacity40 kA rms for one (1) second

d. Insulation levels for 245kV Circuitbreakers and DisconnectingSwitches

e. i) Rated one minute powerFrequency withstand voltage

a) 460 kV rms between liveterminals and earth.

b) 460 kV rms across isolatingdistance.

ii) Rated lightning impulsewithstand voltage

a) +/- 1050 kVp between liveterminals and earth.

b) +/- 1050 kVp impulse on oneterminal and other terminalearthed (across isolatingdistance).

f. Max. Radio interference voltageat 156kVrms

1000 micro volts for frequencybetween 0.5 Mhz and 2.0 Mhz for allequipment.

Page 15: Switchyard lecture1

April 8, 2023 1155

132kV Equipments

a. Rated voltage 145 kVb. Rated frequency 50 Hzc. Rated short time withstand

current capacity31.5 kA rms for one (1) second

d. Insulation levels for 145kV Circuitbreakers and DisconnectingSwitches

e. i) Rated one minute powerFrequency withstand voltage

a) 275 kV rms between liveterminals and earth.

b) 275 kV rms across isolatingdistance.

ii) Rated lightning impulsewithstand voltage

a) +/- 460 kVp between liveterminals and earth.

b) +/- 460 kVp impulse on oneterminal and other terminalearthed (across isolatingdistance).

f. Max. Radio interference voltageat 92kVrms

1000 micro volts for frequencybetween 0.5 Mhz and 2.0 Mhz for allequipment.

Page 16: Switchyard lecture1

April 8, 2023 1166

General Parameters (Contd.)

Rated Current. Short Time Current. Creepage Distance.

Page 17: Switchyard lecture1

April 8, 2023 1177

Circuit Breakers Type

MOCB. ABCB. SF6

Page 18: Switchyard lecture1

April 8, 2023 1188

Circuit Breaker

Fault clearing. Load Make Break. Break Time. Single/Multi Break. Voltage Distribution across breaks. Closing resistors. Operating mechanism

(Spring/Pneumatic/Hydraulic)

Page 19: Switchyard lecture1

April 8, 2023 1199

Disconnectors

HCB Type. Double Break Type. Pantograph type. Vertical Break type. Provision of Earth Switches. Motor / Pneumatic operated. Gang operated/Single pole type.

Page 20: Switchyard lecture1

April 8, 2023 2200

Current Transformer

Bar Primary type. Dead tank/Live tank type. Ring Type. No. of Cores. Ratio. Accuracy.

Page 21: Switchyard lecture1

April 8, 2023 2211

Capacitor Voltage Transformer

Capacitance. Voltage Ratio. No. Of Cores. Accuracy.

Page 22: Switchyard lecture1

April 8, 2023 2222

Lightning Arrestor

Gap Type / Gapless Type. Voltage Rating. Energy Capability. Monitoring. Location.

Page 23: Switchyard lecture1

April 8, 2023 2233

Post Insulators

Voltage Rating. Cantilever Strength. Fixing Details.

Page 24: Switchyard lecture1

April 8, 2023 2244

Wave Trap

Rated Inductance(0.5/1.0 mH). Rated current. Band Width. Coupling (Phase to Phase).

Page 25: Switchyard lecture1

April 8, 2023 2255

Switchyard Layout Guidelines

Place All Equpt. At ground level for ease of maintenance.

Busbars placed at right angles to feeders. Accessibility of feeders from either side of

switchyard. Conductor crossings at right angles be

separated to achieve adequate clearances.

Page 26: Switchyard lecture1

April 8, 2023 2266

Switchyard Layout Guidelines(Contd.)

For 400kV - Phase to Phase 4000 mm - Phase to earth 3500mm

For 220kV - Phase to Phase 2100 mm

- Phase to earth 2100mm

Page 27: Switchyard lecture1

April 8, 2023 2277

Switchyard Layout Guidelines(Contd.)

Lower level connections can be of Rigid pipe or flexible conductor.

Upper level connections can be of strung type only.

For aesthetic looks and similarity all same equipments be in one line as far as possible.

Road near circuit breaker be kept for maintenance purpose.

Page 28: Switchyard lecture1

April 8, 2023 2288

Switchyard Layout Guidelines(Contd.)

Provide Double insulator strings for upper level for safety reasons and to avoid busfaults due to conductor snapping.

Cable trenches to be routed for ease in maintenance and movement.

Lightning protection to be provided using Lightning masts and/or shield wires.

Lighting to be provided by fixtures on LM platform.