1-0 Product family Switch-disconnector-fuse (SASIL) NH fuse system The SASIL system includes LV HRC switch-disconnec- tor-fuses in accordance with IEC/EN 60947-3. Their strip-type, push-in and modular design ensures a rapid engineering and easy installation in low voltage assemblies (TTA/PTTA). An operator-independent snap-action mechanism und double-break feature (upstream and down- stream of the fuse) pro- vide increased personnel protection during the functional switching and exchange of the fuse The horizontal mounting method of SASIL strips with outgoing on right side allows a high packing density in switch gear cabinets. Naturally all SASIL strips can also be mounted vertically with cable termination on bot- tom side. SASIL combines fuse switch-disconnection, cur- rent measurement, posi- tion indication, electronic fuse monitoring, remote operation by motor- operated mechanism and bus connection in one compact device. • High personnel protection • Modular design • Easy installation • High operational safety • High protection against contact • High breaking capacity • High short-circuit strength • Push-in design • Cold-swapping of fuses • Integrated device accessories • High rated diversity factor • Remote operation possible • Communication capability

Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

  • Upload
    others

  • View
    14

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-0

Product family

Switch-disconnector-fuse (SASIL) NH fuse system

The SASIL system includesLV HRC switch-disconnec-tor-fuses in accordancewith IEC/EN 60947-3. Theirstrip-type, push-in andmodular design ensures arapid engineering and easyinstallation in low voltageassemblies (TTA/PTTA).

An operator-independentsnap-action mechanismund double-break feature(upstream and down-stream of the fuse) pro-vide increased personnelprotection during thefunctional switching andexchange of the fuse

The horizontal mountingmethod of SASIL stripswith outgoing on rightside allows a high packingdensity in switch gearcabinets. Naturally allSASIL strips can also bemounted vertically withcable termination on bot-tom side.

SASIL combines fuseswitch-disconnection, cur-rent measurement, posi-tion indication, electronicfuse monitoring, remoteoperation by motor-operated mechanismand bus connection in onecompact device.

• High personnelprotection

• Modular design• Easy installation• High operational safety• High protection against

contact• High breaking capacity• High short-circuit

strength• Push-in design• Cold-swapping of fuses• Integrated device

accessories• High rated diversity

factor• Remote operation

possible• Communication

capability

Page 2: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-1

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Product group Product type

3-pole, Strip, sizes 00-3, w. manually op. mech., w/o current msrmnt185 mm busbar system Strip, sizes 00-3, w. manually op. mech., w. 1 transformer

Strip, sizes 00-3, w. manually op. mech., w. 3 transformersStrip, sizes 00-3, w. manually op. mech., w. EE msrng moduleStrip, sizes 00-3, w. motor-op. mech.Coupling strip, size 3, w. manually op. mech.Double strip, sizes 00-3, w. manually op. mech.

2-pole, Strip, sizes 00-3, w. manually op. mech., w/o current msrmnt185 mm busbar system

SASIL accessories SASIL system accessoriesSASIL device mounting system, 185mm

Page01-0401-0601-1201-1601-1801-2001-22

01-26

01-2801-32

Type key 01-36

Wiring diagram 01-38

Drawings 01-41

Technical data 01-56

Page 3: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-2

Mounting dimensions of field distributor busbar system

225200 25

50

500525

10

90185 2

2

min. 30

344

550 1

23025

Busbar support SST-185/…

Switchingcabinet profilekit SSP

Fixing plate kitBP1/SST

Busbar coverSSA-185

Closing lock-outESS/SASIL…

Bus disconnectingelement kitSTE…/SST

Cable compartmentcoverKA/SSA-185

Cable separatorKSH/SASIL

Socket connector, 16-pole BL/SASIL00-3

Strip guideLF01/SASIL

Drawing toolAW/SASIL00-3

Separator sheet for plugging cable compartment cover(not supplied)

Fuse combination rail (SASIL)

Screw fixing of stripguide possible;Drill hole – Ø 5.3 (for M6)

Fastening railBS1/SST

SASIL mounting system

Page 4: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-3

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Type SASIL

Plug-incontact

1 or 3 transformers

Fuse monitor/Measuring module EE05

Auxiliary switches: 1 make and 1 break

PlungerClosing lock-out

Double-breakfeature

Manually op. mech., can be lockedwith up to 3 padlocks

Operator-independentsnap-action mechanism

LED, fuse failure

Customerconnection

Measuring deviceMoving iron / bimetallic

Transparent Terminal compartment cover

3mmtwo-way keybit lock

Fuse pick-up contacts

Layout of connector-strips

PIN SASIL without EE-Module 1 CT L1 (S2)2 CT L1 (S1)

3 CT L2 (S2)

4 CT L2 (S1)

5 CT L3 (S2)

6 CT L3 (S1)

7 ESOO-norm. open contact8 ESOO-norm. open contact9 ESOO-norm. closed contact

10 ESOO-norm. closed contact11 Switch position indicator

normally closed contact12 Switch position indicator

normally closed contact13 Switch position indicator

normally open contact14 Switch position indicator

normally open contact15 free16 free

SASIL with EE-Module GND-BUS connectionSwitch position indicator normally open contactBUS-Connection-Data A

BUS-Connection-Data B

BUS-Connection shieding

Switch position indicator normally open contactEE-Module/Relay - norm. closed contactEE-Module/Relay - norm. open contactEE-Module/Relay - common contactPE-arrangementN-arrangement

free

Switch position indicator normally closed contactSwitch position indicator normally closed contactDC 24V (+)DC 24V (-)

SASIL-MOT without EE-Module CT L1 (S2)CT L1 (S1)

Switch position indicator normally closed contactSwitch position indicator normally closed contactSwitch position indicator normally open contactSwitch position indicator normally open contactES05 - normally closed contact ES05 - normally open contactES05 - commonPE-arrangementN-arrangement

Motor drive - ON (DC 24V)

Motor drive - GND

Motor drive - OFF (DC 24V)

DC 24V (+)DC 24V (-)

SASIL-MOT with EE-Module GND-BUS connectionSwitch position indicator normally open contactBUS-Connection-Data A

BUS-Connection-Data B

BUS-Connection shieding

Switch position indicator normally open contactEE-Module/Relay - norm. closed cont.EE-Module/Relay - norm. open cont.EE-Module/Relay - common contactPE-arrangementN-arrangement

Motor drive - ON (DC 24V)

Motor drive - GND

Motor drive - OFF (DC 24V)

DC 24V (+)DC 24V (-)

16-pole push-on terminal strip

Page 5: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Current distributioncomponents

Switch-disconnector-fuses (SASIL), LV HRCsystem

3-pole, 185mm busbarsystem

Strip, sizes 00 to 3, w.manually-op. mech.,w/o current msrmnt

1-4

Product definition

SASIL strips are 3-polepluggable strip-typeswitch-disconnector-fuses.The strips are equippedwith an operator-independ-ent snap-action mechanismand manually-operatedmechanism for clear posi-tion indication andaccomodate 3 LV HRCfuse-links in accordancewith DIN 43620, sizes00/160A to 3/630A.

All SASIL strips have plug-incontacts and can be se-curely plugged in an uprightfield distributor busbar sys-tem of 10mm thickness and185mm distance betweenbusbar centres using thecorresponding strip guides.A screw terminal for cablelug connection is availableat the output side. A screwterminal for cable lug con-nection is available at theoutput side. The interlock-ing mechanism in the han-dle prevents the strip cover

from opening in the con-nected state. A dou-ble-break feature (upstreamand downstream of thefuse) allows a safe ex-change of the fuse.

Applications

SASIL strips are mainlyused for system, cable andmotor protection inthree-phase systems up to690V in main andsubdistribution boards oflow voltage assemblies inaccordance with IEC/EN60439-1 (TTA/PTTA), for in-dustrial, power station andbuilding services applica-tions. Their horizontal fit-ting and compact dimen-sions allow a large numberof cable outlets to be fittedin a limited space. A uni-form width, depth and griddimension of 25mm of thestrip height (50mm, 75mm,150mm) enable a rapid en-gineering and mounting ofthe strips with differentcomponent sizes used in

the switchgear cabinet. Thecontrol line and auxiliarycircuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.

Product construction

The device accessories arefactory-fitted in the SASILstrip.

POSITION INDICATOR1 make contact and 1 breakcontact, wired up on apush-on terminal strip, forexternal indication.

PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.

ELECTRONIC FUSE MONI-TORIndicates fuse failure by afrontal LED and relays thefault signal to the push-onterminal strip viamake/break contacts.

Page 6: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Position indicator,1M+1B

Fuse monitor ES00,AC400V-690V

Utilization category,AC500V/690V

Std.P Type Article No.

SASIL...

Size 00 Without Without AC23 1 00-50 A6200000

Size 00 Without With AC23 1 00-50/SKL/ES00 A6205036

Size 00 With Without AC23 1 00-50/SKL/SÖ A6204002

Size 00 With With AC23 1 00-50/SKL/SÖ/ES00 A6224011

Size 1 Without Without AC23 1 1 A1200001

Size 1 Without With AC23 1 1/SKL/ES00 A1205008

Size 1 With Without AC23 1 1/SKL/SÖ A1204042

Size 1 With With AC23 1 1/SKL/SÖ/ES00 A1224014

Size 2 Without Without AC23 1 2 A2200006

Size 2 Without Without AC22 1 2N A2200502

Size 2 Without With AC23 1 2/SKL/ES00 A2205009

Size 2 Without With AC22 1 2N/SKL/ES00 A2205500

Size 2 With Without AC23 1 2/SKL/SÖ A2204040

Size 2 With Without AC22 1 2N/SKL/SÖ A2204500

Size 2 With With AC23 1 2/SKL/SÖ/ES00 A2224055

Size 2 With With AC22 1 2N/SKL/SÖ/ES00 A2224500

Size 3 Without Without AC23 1 3 A3200003

Size 3 Without Without AC22 1 3N A3200502

Size 3 Without With AC23 1 3/SKL/ES00 A3205006

Size 3 Without With AC22 1 3N/SKL/ES00 A3205500

Size 3 With Without AC23 1 3/SKL/SÖ A3204058

Size 3 With Without AC22 1 3N/SKL/SÖ A3204500

Size 3 With With AC23 1 3/SKL/SÖ/ES00 A3224010

Size 3 With With AC22 1 3N/SKL/SÖ/ES00 A3224500

1-5

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 7: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Current distributioncomponents

Switch-disconnector-fuses (SASIL), LV HRCsystem

3-pole, 185mm busbarsystem

Strip, sizes 00 to 3, w.manually-op. mech.,w. 1 transformer

1-6

Product definition

SASIL strips are 3-polepluggable strip-typeswitch-disconnector-fuses.The strips are equippedwith an operator-independ-ent snap-action mechanismand manually-operatedmechanism for clear posi-tion indication andaccomodate 3 LV HRCfuse-links in accordancewith DIN 43620, sizes00/160A to 3/630A, and 1current transformer.

All SASIL strips have plug-incontacts and can be se-curely plugged in an uprightfield distributor busbar sys-tem of 10mm thickness and185mm distance betweenbusbar centres using thecorresponding strip guides.A screw terminal for cablelug connection is availableat the output side.The interlocking mecha-nism in the handle pre-vents the strip cover fromopening in the connectedstate. A double-break fea-ture (upstream and down-stream of the fuse) allows asafe exchange of the fuse.

Applications

SASIL strips are mainlyused for system, cable andmotor protection inthree-phase systems up to690V in main andsubdistribution boards oflow voltage assemblies inaccordance with IEC/EN

60439-1 (TTA/PTTA), for in-dustrial, power station andbuilding services applica-tions. Their horizontal fit-ting and compact dimen-sions allow a large numberof cable outlets to be fittedin a limited space.A uniform width, depth andgrid dimension of 25mm ofthe strip height (50mm,75mm, 150mm) enable arapid engineering andmounting of the strips withdifferent component sizesused in the switchgear cab-inet.

The control line and auxil-iary circuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.

Product construction

The device accessories arefactory-fitted in the SASILstrip.

CURRENT MEASUREMENT1-phase current measure-ment by N/1A or N/5Atransformers, class 1, in ac-cordance with VDE 0414, fit-ted in phase L1. The follow-ing transformer ratios areavailable:50A/75A/100A/150A/200A/250A/400A/600A. Thetransformers can be wiredup either internally on ameasuring device or exter-nally on a push-on terminalstrip.

All transformers can be op-erated open for an unlim-ited period of time.In the case of a cable infeed(Z version), the transform-ers are installed „back tofront“ (turned through180°).

MEASURING DEVICESIt is possible to use 48mm x48mm measuring devicesas class 1.5 moving iron cur-rent meters or bimetalliccurrent meters (from atransformer ratio of 150A)with an average value dis-play of T=8min. or T=15min.Bimetallic current metersprovide a maximum valuedisplay by resettable slavepointers.Moving iron current metershave a dial with 2-fold over-load area, while bimetalliccurrent meters have a dial

with 1.2-fold overload area.

POSITION INDICATOR1 make contact and 1 breakcontact, wired up on apush-on terminal strip, forexternal indication.

PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.

ELECTRONIC FUSE MONI-TORIndicates fuse failure by afrontal LED and relays thefault signal to the push-onterminal strip viamake/break contacts.

To order strips with othertransformer ratios or measu-ring devices, use type key onpage 1-36

Page 8: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transfor-mer ratio,class 1

Transfor-mer wiring(M: mea-suringdeviceS: terminalstrip)

Measuringdevice(B: bime-tallicI: movingiron)

Positionindicator,1M+1B

FusemonitorES00,AC400V-690V

Utilizationcategory,AC500V/690V

Std.P Type Article No.

SASIL...

00 150A-1A M B/T15min Without Without AC23 1 00-50/1W150-1M/MB15 A6217004

00 150A-1A M B/T15min Without With AC23 1 00-50/1W150-1M/SKL/MB15/ES00 A6254002

00 150A-1A M B/T15min With Without AC23 1 00-50/1W150-1M/SKL/MB15/SÖ A6250002

00 150A-1A M B/T15min With With AC23 1 00-50/1W150-1M/SKL/MB15/SÖ/ES00 A6258003

00 150A-1A M I Without Without AC23 1 00-50/1W150-1M/MD A6206068

00 150A-1A M I Without With AC23 1 00-50/1W150-1M/SKL/MD/ES00 A6230009

00 150A-1A M I With Without AC23 1 00-50/1W150-1M/SKL/MD/SÖ A6221006

00 150A-1A M I With With AC23 1 00-50/1W150-1M/SKL/MD/SÖ/ES00 A6238011

00 150A-1A S Without Without Without AC23 1 00-50/1W150-1S/SKL A6207002

00 150A-1A S Without Without With AC23 1 00-50/1W150-1S/SKL/ES00 A6226001

00 150A-1A S Without With Without AC23 1 00-50/1W150-1S/SKL/SÖ A6218007

00 150A-1A S Without With With AC23 1 00-50/1W150-1S/SKL/SÖ/ES00 A6235027

00 150A-1A M / strip B/T15min Without Without AC23 1 00-50/1W150-1MS/SKL/MB15 A6246001

00 150A-1A M / strip B/T15min Without With AC23 1 00-50/1W150-1MS/SKL/MB15/ES00 A6254004

00 150A-1A M / strip B/T15min With Without AC23 1 00-50/1W150-1MS/SKL/MB15/SÖ A6250023

00 150A-1A M / strip B/T15min With With AC23 1 00-50/1W150-1MS/SKL/MB15/SÖ/ES00 A6258024

00 150A-1A M / strip I Without Without AC23 1 00-50/1W150-1MS/SKL/MD A6212005

00 150A-1A M / strip I Without With AC23 1 00-50/1W150-1MS/SKL/MD/ES00 A6230003

00 150A-1A M / strip I With Without AC23 1 00-50/1W150-1MS/SKL/MD/SÖ A6221003

00 150A-1A M / strip I With With AC23 1 00-50/1W150-1MS/SKL/MD/SÖ/ES00 A6238006

00 150A-5A M B/T15min Without Without AC23 1 00-50/1W150-5M/MB15 A6216055

00 150A-5A M B/T15min Without With AC23 1 00-50/1W150-5M/SKL/MB15/ES00 A6253003

00 150A-5A M B/T15min With Without AC23 1 00-50/1W150-5M/SKL/MB15/SÖ A6249005

00 150A-5A M B/T15min With With AC23 1 00-50/1W150-5M/SKL/MB15/SÖ/ES00 A6257004

00 150A-5A M I Without Without AC23 1 00-50/1W150-5M/MD A6201025

00 150A-5A M I Without With AC23 1 00-50/1W150-5M/SKL/MD/ES00 A6229006

00 150A-5A M I With Without AC23 1 00-50/1W150-5M/SKL/MD/SÖ A6209010

00 150A-5A M I With With AC23 1 00-50/1W150-5M/SKL/MD/SÖ/ES00 A6210005

00 150A-5A S Without Without Without AC23 1 00-50/1W150-5S/SKL A6202003

00 150A-5A S Without Without With AC23 1 00-50/1W150-5S/SKL/ES00 A6225005

00 150A-5A S Without With Without AC23 1 00-50/1W150-5S/SKL/SÖ A6211001

00 150A-5A S Without With With AC23 1 00-50/1W150-5S/SKL/SÖ/ES00 A6234005

00 150A-5A MS B/T15min Without Without AC23 1 00-50/1W150-5MS/SKL/MB15 A6245058

00 150A-5A MS B/T15min Without With AC23 1 00-50/1W150-5MS/SKL/MB15/ES00 A6253005

00 150A-5A MS B/T15min With Without AC23 1 00-50/1W150-5MS/SKL/MB15/SÖ A6249007

00 150A-5A MS B/T15min With With AC23 1 00-50/1W150-5MS/SKL/MB15/SÖ/ES00 A6257005

00 150A-5A MS I Without Without AC23 1 00-50/1W150-5MS/SKL/MD A6203009

00 150A-5A MS I Without With AC23 1 00-50/1W150-5MS/SKL/MD/ES00 A6229026

00 150A-5A MS I With Without AC23 1 00-50/1W150-5MS/SKL/MD/SÖ A6209012

00 150A-5A MS I With With AC23 1 00-50/1W150-5MS/SKL/MD/SÖ/ES00 A6210004

1 250A-1A M B/T15min Without Without AC23 1 1/1W250-1M/MB15 A1217122

1 250A-1A M B/T15min Without With AC23 1 1/1W250-1M/SKL/MB15/ES00 A1254009

1 250A-1A M B/T15min With Without AC23 1 1/1W250-1M/SKL/MB15/SÖ A1250009

1 250A-1A M B/T15min With With AC23 1 1/1W250-1M/SKL/MB15/SÖ/ES00 A1258009

1 250A-1A M I Without Without AC23 1 1/1W250-1M/MD A1206003

1 250A-1A M I Without With AC23 1 1/1W250-1M/SKL/MD/ES00 A1230007

1 250A-1A M I With Without AC23 1 1/1W250-1M/SKL/MD/SÖ A1221007

1 250A-1A M I With With AC23 1 1/1W250-1M/SKL/MD/SÖ/ES00 A1238011

1-7

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 9: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transfor-mer ratio,class 1

Transfor-mer wiring(M: mea-suringdeviceS: terminalstrip)

Measuringdevice(B: bime-tallicI: movingiron)

Positionindicator,1M+1B

FusemonitorES00,AC400V-690V

Utilizationcategory,AC500V/690V

Std.P Type Article No.

SASIL...

1 250A-1A S Without Without Without AC23 1 1/1W250-1S/SKL A1207169

1 250A-1A S Without Without With AC23 1 1/1W250-1S/SKL/ES00 A1226005

1 250A-1A S Without With Without AC23 1 1/1W250-1S/SKL/SÖ A1218009

1 250A-1A S Without With With AC23 1 1/1W250-1S/SKL/SÖ/ES00 A1235163

1 250A-1A MS B/T15min Without Without AC23 1 1/1W250-1MS/SKL/MB15 A1246004

1 250A-1A MS B/T15min Without With AC23 1 1/1W250-1MS/SKL/MB15/ES00 A1254012

1 250A-1A MS B/T15min With Without AC23 1 1/1W250-1MS/SKL/MB15/SÖ A1250012

1 250A-1A MS B/T15min With With AC23 1 1/1W250-1MS/SKL/MB15/SÖ/ES00 A1258161

1 250A-1A MS I Without Without AC23 1 1/1W250-1MS/SKL/MD A1212196

1 250A-1A MS I Without With AC23 1 1/1W250-1MS/SKL/MD/ES00 A1230002

1 250A-1A MS I With Without AC23 1 1/1W250-1MS/SKL/MD/SÖ A1221010

1 250A-1A MS I With With AC23 1 1/1W250-1MS/SKL/MD/SÖ/ES00 A1238058

1 250A-5A M B/T15min Without Without AC23 1 1/1W250-5M/MB15 A1216135

1 250A-5A M B/T15min Without With AC23 1 1/1W250-5M/SKL/MB15/ES00 A1253011

1 250A-5A M B/T15min With Without AC23 1 1/1W250-5M/SKL/MB15/SÖ A1249012

1 250A-5A M B/T15min With With AC23 1 1/1W250-5M/SKL/MB15/SÖ/ES00 A1257011

1 250A-5A M I Without Without AC23 1 1/1W250-5M/MD A1201021

1 250A-5A M I Without With AC23 1 1/1W250-5M/SKL/MD/ES00 A1229010

1 250A-5A M I With Without AC23 1 1/1W250-5M/SKL/MD/SÖ A1209007

1 250A-5A M I With With AC23 1 1/1W250-5M/SKL/MD/SÖ/ES00 A1210014

1 250A-5A S Without Without Without AC23 1 1/1W250-5S/SKL A1202040

1 250A-5A S Without Without With AC23 1 1/1W250-5S/SKL/ES00 A1225006

1 250A-5A S Without With Without AC23 1 1/1W250-5S/SKL/SÖ A1211001

1 250A-5A S Without With With AC23 1 1/1W250-5S/SKL/SÖ/ES00 A1234005

1 250A-5A MS B/T15min Without Without AC23 1 1/1W250-5MS/SKL/MB15 A1245054

1 250A-5A MS B/T15min Without With AC23 1 1/1W250-5MS/SKL/MB15/ES00 A1253002

1 250A-5A MS B/T15min With Without AC23 1 1/1W250-5MS/SKL/MB15/SÖ A1249014

1 250A-5A MS B/T15min With With AC23 1 1/1W250-5MS/SKL/MB15/SÖ/ES00 A1257001

1 250A-5A MS I Without Without AC23 1 1/1W250-5MS/SKL/MD A1203041

1 250A-5A MS I Without With AC23 1 1/1W250-5MS/SKL/MD/ES00 A1229004

1 250A-5A MS I With Without AC23 1 1/1W250-5MS/SKL/MD/SÖ A1209085

1 250A-5A MS I With With AC23 1 1/1W250-5MS/SKL/MD/SÖ/ES00 A1210054

2 400A-1A M B/T15min Without Without AC23 1 2/1W400-1M/MB15 A2217111

2 400A-1A M B/T15min Without Without AC22 1 2N/1W400-1M/MB15 A2217500

2 400A-1A M B/T15min Without With AC23 1 2/1W400-1M/SKL/MB15/ES00 A2254013

2 400A-1A M B/T15min Without With AC22 1 2N/1W400-1M/SKL/MB15/ES00 A2254511

2 400A-1A M B/T15min With Without AC23 1 2/1W400-1M/SKL/MB15/SÖ A2250012

2 400A-1A M B/T15min With Without AC22 1 2N/1W400-1M/SKL/MB15/SÖ A2250512

2 400A-1A M B/T15min With With AC23 1 2/1W400-1M/SKL/MB15/SÖ/ES00 A2258014

2 400A-1A M B/T15min With With AC22 1 2N/1W400-1M/SKL/MB15/SÖ/ES00 A2258511

2 400A-1A M I Without Without AC23 1 2/1W400-1M/MD A2206077

2 400A-1A M I Without Without AC22 1 2N/1W400-1M/MD A2206500

2 400A-1A M I Without With AC23 1 2/1W400-1M/SKL/MD/ES00 A2230011

2 400A-1A M I Without With AC22 1 2N/1W400-1M/SKL/MD/ES00 A2230503

2 400A-1A M I With Without AC23 1 2/1W400-1M/SKL/MD/SÖ A2221014

2 400A-1A M I With Without AC22 1 2N/1W400-1M/SKL/MD/SÖ A2221503

2 400A-1A M I With With AC23 1 2/1W400-1M/SKL/MD/SÖ/ES00 A2238005

2 400A-1A M I With With AC22 1 2N/1W400-1M/SKL/MD/SÖ/ES00 A2238503

1-8

Page 10: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transfor-mer ratio,class 1

Transfor-mer wiring(M: mea-suringdeviceS: terminalstrip)

Measuringdevice(B: bime-tallicI: movingiron)

Positionindicator,1M+1B

FusemonitorES00,AC400V-690V

Utilizationcategory,AC500V/690V

Std.P Type Article No.

SASIL...

2 400A-1A S Without Without Without AC23 1 2/1W400-1S/SKL A2207152

2 400A-1A S Without Without Without AC22 1 2N/1W400-1S/SKL A2207500

2 400A-1A S Without Without With AC23 1 2/1W400-1S/SKL/ES00 A2226004

2 400A-1A S Without Without With AC22 1 2N/1W400-1S/SKL/ES00 A2226503

2 400A-1A S Without With Without AC23 1 2/1W400-1S/SKL/SÖ A2218006

2 400A-1A S Without With Without AC22 1 2N/1W400-1S/SKL/SÖ A2218503

2 400A-1A S Without With With AC23 1 2/1W400-1S/SKL/SÖ/ES00 A2235054

2 400A-1A S Without With With AC22 1 2N/1W400-1S/SKL/SÖ/ES00 A2235503

2 400A-1A MS B/T15min Without Without AC23 1 2/1W400-1MS/SKL/MB15 A2246003

2 400A-1A MS B/T15min Without Without AC22 1 2N/1W400-1MS/SKL/MB15 A2246507

2 400A-1A MS B/T15min Without With AC23 1 2/1W400-1MS/SKL/MB15/ES00 A2254017

2 400A-1A MS B/T15min Without With AC22 1 2N/1W400-1MS/SKL/MB15/ES00 A2254515

2 400A-1A MS B/T15min With Without AC23 1 2/1W400-1MS/SKL/MB15/SÖ A2250016

2 400A-1A MS B/T15min With Without AC22 1 2N/1W400-1MS/SKL/MB15/SÖ A2250516

2 400A-1A MS B/T15min With With AC23 1 2/1W400-1MS/SKL/MB15/SÖ/ES00 A2258155

2 400A-1A MS B/T15min With With AC22 1 2N/1W400-1MS/SKL/MB15/SÖ/ES00 A2258515

2 400A-1A MS I Without Without AC23 1 2/1W400-1MS/SKL/MD A2212170

2 400A-1A MS I Without Without AC22 1 2N/1W400-1MS/SKL/MD A2212503

2 400A-1A MS I Without With AC23 1 2/1W400-1MS/SKL/MD/ES00 A2230006

2 400A-1A MS I Without With AC22 1 2N/1W400-1MS/SKL/MD/ES00 A2230507

2 400A-1A MS I With Without AC23 1 2/1W400-1MS/SKL/MD/SÖ A2221002

2 400A-1A MS I With Without AC22 1 2N/1W400-1MS/SKL/MD/SÖ A2221507

2 400A-1A MS I With With AC23 1 2/1W400-1MS/SKL/MD/SÖ/ES00 A2238060

2 400A-1A MS I With With AC22 1 2N/1W400-1MS/SKL/MD/SÖ/ES00 A2238507

2 400A-5A M B/T15min Without Without AC23 1 2/1W400-5M/MB15 A2216099

2 400A-5A M B/T15min Without Without AC22 1 2N/1W400-5M/MB15 A2216500

2 400A-5A M B/T15min Without With AC23 1 2/1W400-5M/SKL/MB15/ES00 A2253014

2 400A-5A M B/T15min Without With AC22 1 2N/1W400-5M/SKL/MB15/ES00 A2253511

2 400A-5A M B/T15min With Without AC23 1 2/1W400-5M/SKL/MB15/SÖ A2249002

2 400A-5A M B/T15min With Without AC22 1 2N/1W400-5M/SKL/MB15/SÖ A2249511

2 400A-5A M B/T15min With With AC23 1 2/1W400-5M/SKL/MB15/SÖ/ES00 A2257014

2 400A-5A M B/T15min With With AC22 1 2N/1W400-5M/SKL/MB15/SÖ/ES00 A2257511

2 400A-5A M I Without Without AC23 1 2/1W400-5M/MD A2201020

2 400A-5A M I Without Without AC22 1 2N/1W400-5M/MD A2201500

2 400A-5A M I Without With AC23 1 2/1W400-5M/SKL/MD/ES00 A2229003

2 400A-5A M I Without With AC22 1 2N/1W400-5M/SKL/MD/ES00 A2229500

2 400A-5A M I With Without AC23 1 2/1W400-5M/SKL/MD/SÖ A2209006

2 400A-5A M I With Without AC22 1 2N/1W400-5M/SKL/MD/SÖ A2209503

2 400A-5A M I With With AC23 1 2/1W400-5M/SKL/MD/SÖ/ES00 A2210004

2 400A-5A M I With With AC22 1 2N/1W400-5M/SKL/MD/SÖ/ES00 A2210501

2 400A-5A S Without Without Without AC23 1 2/1W400-5S/SKL A2202039

2 400A-5A S Without Without Without AC22 1 2N/1W400-5S/SKL A2202505

2 400A-5A S Without Without With AC23 1 2/1W400-5S/SKL/ES00 A2225005

2 400A-5A S Without Without With AC22 1 2N/1W400-5S/SKL/ES00 A2225503

2 400A-5A S Without With Without AC23 1 2/1W400-5S/SKL/SÖ A2211001

2 400A-5A S Without With Without AC22 1 2N/1W400-5S/SKL/SÖ A2211503

2 400A-5A S Without With With AC23 1 2/1W400-5S/SKL/SÖ/ES00 A2234004

2 400A-5A S Without With With AC22 1 2N/1W400-5S/SKL/SÖ/ES00 A2234503

1-9

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 11: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transfor-mer ratio,class 1

Transfor-mer wiring(M: mea-suringdeviceS: terminalstrip)

Measuringdevice(B: bime-tallicI: movingiron)

Positionindicator,1M+1B

FusemonitorES00,AC400V-690V

Utilizationcategory,AC500V/690V

Std.P Type Article No.

SASIL...

2 400A-5A MS B/T15min Without Without AC23 1 2/1W400-5MS/SKL/MB15 A2245057

2 400A-5A MS B/T15min Without Without AC22 1 2N/1W400-5MS/SKL/MB15 A2245500

2 400A-5A MS B/T15min Without With AC23 1 2/1W400-5MS/SKL/MB15/ES00 A2253016

2 400A-5A MS B/T15min Without With AC22 1 2N/1W400-5MS/SKL/MB15/ES00 A2253515

2 400A-5A MS B/T15min With Without AC23 1 2/1W400-5MS/SKL/MB15/SÖ A2249017

2 400A-5A MS B/T15min With Without AC22 1 2N/1W400-5MS/SKL/MB15/SÖ A2249515

2 400A-5A MS B/T15min With With AC23 1 2/1W400-5MS/SKL/MB15/SÖ/ES00 A2257001

2 400A-5A MS B/T15min With With AC22 1 2N/1W400-5MS/SKL/MB15/SÖ/ES00 A2257515

2 400A-5A MS I Without Without AC23 1 2/1W400-5MS/SKL/MD A2203001

2 400A-5A MS I Without Without AC22 1 2N/1W400-5MS/SKL/MD A2203504

2 400A-5A MS I Without With AC23 1 2/1W400-5MS/SKL/MD/ES00 A2229021

2 400A-5A MS I Without With AC22 1 2N/1W400-5MS/SKL/MD/ES00 A2229501

2 400A-5A MS I With Without AC23 1 2/1W400-5MS/SKL/MD/SÖ A2209016

2 400A-5A MS I With Without AC22 1 2N/1W400-5MS/SKL/MD/SÖ A2209507

2 400A-5A MS I With With AC23 1 2/1W400-5MS/SKL/MD/SÖ/ES00 A2210136

2 400A-5A MS I With With AC22 1 2N/1W400-5MS/SKL/MD/SÖ/ES00 A2210500

3 600A-1A M B/T15min Without Without AC23 1 3/1W600-1M/MB15 A3217001

3 600A-1A M B/T15min Without Without AC22 1 3N/1W600-1M/MB15 A3217505

3 600A-1A M B/T15min Without With AC23 1 3/1W600-1M/SKL/MB15/ES00 A3254009

3 600A-1A M B/T15min Without With AC22 1 3N/1W600-1M/SKL/MB15/ES00 A3254508

3 600A-1A M B/T15min With Without AC23 1 3/1W600-1M/SKL/MB15/SÖ A3250009

3 600A-1A M B/T15min With Without AC22 1 3N/1W600-1M/SKL/MB15/SÖ A3250508

3 600A-1A M B/T15min With With AC23 1 3/1W600-1M/SKL/MB15/SÖ/ES00 A3258011

3 600A-1A M B/T15min With With AC22 1 3N/1W600-1M/SKL/MB15/SÖ/ES00 A3258508

3 600A-1A M I Without Without AC23 1 3/1W600-1M/MD A3206055

3 600A-1A M I Without Without AC22 1 3N/1W600-1M/MD A3206500

3 600A-1A M I Without With AC23 1 3/1W600-1M/SKL/MD/ES00 A3230003

3 600A-1A M I Without With AC22 1 3N/1W600-1M/SKL/MD/ES00 A3230502

3 600A-1A M I With Without AC23 1 3/1W600-1M/SKL/MD/SÖ A3221006

3 600A-1A M I With Without AC22 1 3N/1W600-1M/SKL/MD/SÖ A3221502

3 600A-1A M I With With AC23 1 3/1W600-1M/SKL/MD/SÖ/ES00 A3238007

3 600A-1A M I With With AC22 1 3N/1W600-1M/SKL/MD/SÖ/ES00 A3238502

3 600A-1A S Without Without Without AC23 1 3/1W600-1S/SKL A3207117

3 600A-1A S Without Without Without AC22 1 3N/1W600-1S/SKL A3207500

3 600A-1A S Without Without With AC23 1 3/1W600-1S/SKL/ES00 A3226024

3 600A-1A S Without Without With AC22 1 3N/1W600-1S/SKL/ES00 A3226502

3 600A-1A S Without With Without AC23 1 3/1W600-1S/SKL/SÖ A3218001

3 600A-1A S Without With Without AC22 1 3N/1W600-1S/SKL/SÖ A3218502

3 600A-1A S Without With With AC23 1 3/1W600-1S/SKL/SÖ/ES00 A3235004

3 600A-1A S Without With With AC22 1 3N/1W600-1S/SKL/SÖ/ES00 A3235502

3 600A-1A MS B/T15min Without Without AC23 1 3/1W600-1MS/SKL/MB15 A3246007

3 600A-1A MS B/T15min Without Without AC22 1 3N/1W600-1MS/SKL/MB15 A3246505

3 600A-1A MS B/T15min Without With AC23 1 3/1W600-1MS/SKL/MB15/ES00 A3254012

3 600A-1A MS B/T15min Without With AC22 1 3N/1W600-1MS/SKL/MB15/ES00 A3254511

3 600A-1A MS B/T15min With Without AC23 1 3/1W600-1MS/SKL/MB15/SÖ A3250012

3 600A-1A MS B/T15min With Without AC22 1 3N/1W600-1MS/SKL/MB15/SÖ A3250511

3 600A-1A MS B/T15min With With AC23 1 3/1W600-1MS/SKL/MB15/SÖ/ES00 A3258119

3 600A-1A MS B/T15min With With AC22 1 3N/1W600-1MS/SKL/MB15/SÖ/ES00 A3258511

1-10

Page 12: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transfor-mer ratio,class 1

Transfor-mer wiring(M: mea-suringdeviceS: terminalstrip)

Measuringdevice(B: bime-tallicI: movingiron)

Positionindicator,1M+1B

FusemonitorES00,AC400V-690V

Utilizationcategory,AC500V/690V

Std.P Type Article No.

SASIL...

3 600A-1A MS I Without Without AC23 1 3/1W600-1MS/SKL/MD A3212146

3 600A-1A MS I Without Without AC22 1 3N/1W600-1MS/SKL/MD A3212502

3 600A-1A MS I Without With AC23 1 3/1W600-1MS/SKL/MD/ES00 A3230002

3 600A-1A MS I Without With AC22 1 3N/1W600-1MS/SKL/MD/ES00 A3230505

3 600A-1A MS I With Without AC23 1 3/1W600-1MS/SKL/MD/SÖ A3221008

3 600A-1A MS I With Without AC22 1 3N/1W600-1MS/SKL/MD/SÖ A3221505

3 600A-1A MS I With With AC23 1 3/1W600-1MS/SKL/MD/SÖ/ES00 A3238001

3 600A-1A MS I With With AC22 1 3N/1W600-1MS/SKL/MD/SÖ/ES00 A3238505

3 600A-5A M B/T15min Without Without AC23 1 3/1W600-5M/MB15 A3216094

3 600A-5A M B/T15min Without Without AC22 1 3N/1W600-5M/MB15 A3216500

3 600A-5A M B/T15min Without With AC23 1 3/1W600-5M/SKL/MB15/ES00 A3253011

3 600A-5A M B/T15min Without With AC22 1 3N/1W600-5M/SKL/MB15/ES00 A3253511

3 600A-5A M B/T15min With Without AC23 1 3/1W600-5M/SKL/MB15/SÖ A3249010

3 600A-5A M B/T15min With Without AC22 1 3N/1W600-5M/SKL/MB15/SÖ A3249508

3 600A-5A M B/T15min With With AC23 1 3/1W600-5M/SKL/MB15/SÖ/ES00 A3257011

3 600A-5A M B/T15min With With AC22 1 3N/1W600-5M/SKL/MB15/SÖ/ES00 A3257508

3 600A-5A M I Without Without AC23 1 3/1W600-5M/MD A3201015

3 600A-5A M I Without Without AC22 1 3N/1W600-5M/MD A3201500

3 600A-5A M I Without With AC23 1 3/1W600-5M/SKL/MD/ES00 A3229005

3 600A-5A M I Without With AC22 1 3N/1W600-5M/SKL/MD/ES00 A3229502

3 600A-5A M I With Without AC23 1 3/1W600-5M/SKL/MD/SÖ A3209004

3 600A-5A M I With Without AC22 1 3N/1W600-5M/SKL/MD/SÖ A3209503

3 600A-5A M I With With AC23 1 3/1W600-5M/SKL/MD/SÖ/ES00 A3210006

3 600A-5A M I With With AC22 1 3N/1W600-5M/SKL/MD/SÖ/ES00 A3210500

3 600A-5A S Without Without Without AC23 1 3/1W600-5S/SKL A3202031

3 600A-5A S Without Without Without AC22 1 3N/1W600-5S/SKL A3202503

3 600A-5A S Without Without With AC23 1 3/1W600-5S/SKL/ES00 A3225004

3 600A-5A S Without Without With AC22 1 3N/1W600-5S/SKL/ES00 A3225502

3 600A-5A S Without With Without AC23 1 3/1W600-5S/SKL/SÖ A3211001

3 600A-5A S Without With Without AC22 1 3N/1W600-5S/SKL/SÖ A3211502

3 600A-5A S Without With With AC23 1 3/1W600-5S/SKL/SÖ/ES00 A3234003

3 600A-5A S Without With With AC22 1 3N/1W600-5S/SKL/SÖ/ES00 A3234502

3 600A-5A MS B/T15min Without Without AC23 1 3/1W600-5MS/SKL/MB15 A3245043

3 600A-5A MS B/T15min Without Without AC22 1 3N/1W600-5MS/SKL/MB15 A3245500

3 600A-5A MS B/T15min Without With AC23 1 3/1W600-5MS/SKL/MB15/ES00 A3253013

3 600A-5A MS B/T15min Without With AC22 1 3N/1W600-5MS/SKL/MB15/ES00 A3253513

3 600A-5A MS B/T15min With Without AC23 1 3/1W600-5MS/SKL/MB15/SÖ A3249011

3 600A-5A MS B/T15min With Without AC22 1 3N/1W600-5MS/SKL/MB15/SÖ A3249511

3 600A-5A MS B/T15min With With AC23 1 3/1W600-5MS/SKL/MB15/SÖ/ES00 A3257001

3 600A-5A MS B/T15min With With AC22 1 3N/1W600-5MS/SKL/MB15/SÖ/ES00 A3257511

3 600A-5A MS I Without Without AC23 1 3/1W600-5MS/SKL/MD A3203032

3 600A-5A MS I Without Without AC22 1 3N/1W600-5MS/SKL/MD A3203505

3 600A-5A MS I Without With AC23 1 3/1W600-5MS/SKL/MD/ES00 A3229002

3 600A-5A MS I Without With AC22 1 3N/1W600-5MS/SKL/MD/ES00 A3229505

3 600A-5A MS I With Without AC23 1 3/1W600-5MS/SKL/MD/SÖ A3209067

3 600A-5A MS I With Without AC22 1 3N/1W600-5MS/SKL/MD/SÖ A3209506

3 600A-5A MS I With With AC23 1 3/1W600-5MS/SKL/MD/SÖ/ES00 A3210005

3 600A-5A MS I With With AC22 1 3N/1W600-5MS/SKL/MD/SÖ/ES00 A3210505

1-11

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 13: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Current distributioncomponents

Switch-disconnector-fuses (SASIL), LV HRCsystem

3-pole, 185mm busbarsystem

Strip, sizes 00 to 3, w.manually-op. mech.,w. 3 transformers

1-12

Product definition

SASIL strips are 3-polepluggable strip-typeswitch-disconnector-fuses.The strips are equippedwith an operator-independ-ent snap-action mechanismand manually-operatedmechanism for clear posi-tion indication andaccomodate 3 LV HRCfuse-links in accordancewith DIN 43620, sizes00/160A to 3/630A, and 3current transformers.All SASIL strips have plug-incontacts and can be se-curely plugged in an uprightfield distributor busbar sys-tem of 10mm thickness and185mm distance betweenbusbar centres using thecorresponding strip guides.A screw terminal for cablelug connection is availableat the output side.The interlocking mecha-nism in the handle pre-vents the strip cover fromopening in the connectedstate. A double-break fea-ture (upstream and down-stream of the fuse) allows asafe exchange of the fuse.

Applications

SASIL strips are mainlyused for system, cable andmotor protection inthree-phase systems up to690V in main andsubdistribution boards oflow voltage assemblies inaccordance with IEC/EN60439-1 (TTA/PTTA), for in-

dustrial, power station andbuilding services applica-tions. Their horizontal fit-ting and compact dimen-sions allow a large numberof cable outlets to be fittedin a limited space.A uniform width, depth andgrid dimension of 25mm ofthe strip height (50mm,75mm, 150mm) enable arapid engineering andmounting of the strips withdifferent component sizesused in the switchgear cab-inet.

The control line and auxil-iary circuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.

Product construction

The device accessories arefactory-fitted in the SASILstrip.

CURRENT MEASUREMENT3-phase current measure-ment by N/1A or N/5Atransformers, class 1 orclass 0.5, in accordancewith VDE 0414. Class 0.5transformers can be certi-fied. The following trans-former ratios are available:50A/75A/100A/150A/200A/250A/400A/600A. Thetransformers can be wiredup either internally on ameasuring device or exter-nally on a push-on terminalstrip.

All transformers can be op-erated open for an unlim-ited period of time.In the case of a cable infeed(Z version), the transform-ers are installed „back tofront“ (turned through180°).

MEASURING DEVICESIt is possible to use 48mm x48mm measuring devicesas class 1.5 moving iron cur-rent meters or bimetalliccurrent meters (from atransformer ratio of 150A)with an average value dis-play of T=8min. or T=15min.Bimetallic current metersprovide a maximum valuedisplay by resettable slavepointers.Moving iron current metershave a dial with 2-fold over-load area, while bimetalliccurrent meters have a dialwith 1.2-fold overload area.

POSITION INDICATOR1 make contact and 1 breakcontact, wired up on apush-on terminal strip, forexternal indication.

PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.

ELECTRONIC FUSE MONI-TORIndicates fuse failure by afrontal LED and relays thefault signal to the push-onterminal strip viamake/break contacts.

To order strips with othertransformer ratios or measu-ring devices, use type key onpage 1-36

Page 14: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transfor-mer ratio

Transformerclass

Transfor-merwiring(M: mea-suringdeviceS: termi-nal strip)

Measuringdevice(B: bime-tallicI: movingiron)

Positionindicator,1M+1B

FusemonitorES00,AC400V-690V

Utilizati-on cate-gory,AC500V/690V

Std.P Type Article No.

SASIL...

00 150A-1A 1 S Without Without Without AC23 1 00-50/3W150-1S/SKL A6214002

00 150A-1A 1 S Without Without With AC23 1 00-50/3W150-1S/SKL/ES00 A6228008

00 150A-1A 1 S Without With Without AC23 1 00-50/3W150-1S/SKL/SÖ A6220005

00 150A-1A 1 S Without With With AC23 1 00-50/3W150-1S/SKL/SÖ/ES00 A6237001

00 150A-1A 1 MS B/T15min Without Without AC23 1 00-50/3W150-1MS/SKL/MB15 A6248001

00 150A-1A 1 MS B/T15min Without With AC23 1 00-50/3W150-1MS/SKL/MB15/ES00 A6256002

00 150A-1A 1 MS B/T15min With Without AC23 1 00-50/3W150-1MS/SKL/MB15/SÖ A6252002

00 150A-1A 1 MS B/T15min With With AC23 1 00-50/3W150-1MS/SKL/MB15/SÖ/ES00 A6260002

00 150A-1A 1 MS I Without Without AC23 1 00-50/3W150-1MS/SKL/MD A6215005

00 150A-1A 1 MS I Without With AC23 1 00-50/3W150-1MS/SKL/MD/ES00 A6232004

00 150A-1A 1 MS I With Without AC23 1 00-50/3W150-1MS/SKL/MD/SÖ A6223005

00 150A-1A 1 MS I With With AC23 1 00-50/3W150-1MS/SKL/MD/SÖ/ES00 A6240005

00 150A-5A 1 S Without Without Without AC23 1 00-50/3W150-5S/SKL A6208044

00 150A-5A 1 S Without Without With AC23 1 00-50/3W150-5S/SKL/ES00 A6227005

00 150A-5A 1 S Without With Without AC23 1 00-50/3W150-5S/SKL/SÖ A6219005

00 150A-5A 1 S Without With With AC23 1 00-50/3W150-5S/SKL/SÖ/ES00 A6236004

00 150A-5A 1 MS B/T15min Without Without AC23 1 00-50/3W150-5MS/SKL/MB15 A6247002

00 150A-5A 1 MS B/T15min Without With AC23 1 00-50/3W150-5MS/SKL/MB15/ES00 A6255002

00 150A-5A 1 MS B/T15min With Without AC23 1 00-50/3W150-5MS/SKL/MB15/SÖ A6251002

00 150A-5A 1 MS B/T15min With With AC23 1 00-50/3W150-5MS/SKL/MB15/SÖ/ES00 A6259002

00 150A-5A 1 MS I Without Without AC23 1 00-50/3W150-5MS/SKL/MD A6213004

00 150A-5A 1 MS I Without With AC23 1 00-50/3W150-5MS/SKL/MD/ES00 A6231004

00 150A-5A 1 MS I With Without AC23 1 00-50/3W150-5MS/SKL/MD/SÖ A6222004

00 150A-5A 1 MS I With With AC23 1 00-50/3W150-5MS/SKL/MD/SÖ/ES00 A6239005

1 250A-1A 1 S Without Without Without AC23 1 1/3W250-1S/SKL A1214068

1 250A-1A 1 S Without Without With AC23 1 1/3W250-1S/SKL/ES00 A1228005

1 250A-1A 1 S Without With Without AC23 1 1/3W250-1S/SKL/SÖ A1220005

1 250A-1A 1 S Without With With AC23 1 1/3W250-1S/SKL/SÖ/ES00 A1237001

1 250A-1A 1 MS B/T15min Without Without AC23 1 1/3W250-1MS/SKL/MB15 A1248006

1 250A-1A 1 MS B/T15min Without With AC23 1 1/3W250-1MS/SKL/MB15/ES00 A1256006

1 250A-1A 1 MS B/T15min With Without AC23 1 1/3W250-1MS/SKL/MB15/SÖ A1252006

1 250A-1A 1 MS B/T15min With With AC23 1 1/3W250-1MS/SKL/MB15/SÖ/ES00 A1260006

1 250A-1A 1 MS I Without Without AC23 1 1/3W250-1MS/SKL/MD A1215070

1 250A-1A 1 MS I With Without AC23 1 1/3W250-1MS/SKL/MD/SÖ A1223002

1 250A-1A 1 MS I Without With AC23 1 1/3W250-1MS/SKL/MD/ES00 A1232005

1 250A-1A 1 MS I With With AC23 1 1/3W250-1MS/SKL/MD/SÖ/ES00 A1240001

1 250A-5A 1 S Without Without Without AC23 1 1/3W250-5S/SKL A1208084

1 250A-5A 1 S Without Without With AC23 1 1/3W250-5S/SKL/ES00 A1227191

1 250A-5A 1 S Without With Without AC23 1 1/3W250-5S/SKL/SÖ A1219001

1 250A-5A 1 S Without With With AC23 1 1/3W250-5S/SKL/SÖ/ES00 A1236004

1 250A-5A 1 MS B/T15min Without Without AC23 1 1/3W250-5MS/SKL/MB15 A1247190

1 250A-5A 1 MS B/T15min Without With AC23 1 1/3W250-5MS/SKL/MB15/ES00 A1255006

1 250A-5A 1 MS B/T15min With Without AC23 1 1/3W250-5MS/SKL/MB15/SÖ A1251006

1 250A-5A 1 MS B/T15min With With AC23 1 1/3W250-5MS/SKL/MB15/SÖ/ES00 A1259006

1 250A-5A 1 MS I Without Without AC23 1 1/3W250-5MS/SKL/MD A1213003

1 250A-5A 1 MS I Without With AC23 1 1/3W250-5MS/SKL/MD/ES00 A1231001

1 250A-5A 1 MS I With Without AC23 1 1/3W250-5MS/SKL/MD/SÖ A1222004

1 250A-5A 1 MS I With With AC23 1 1/3W250-5MS/SKL/MD/SÖ/ES00 A1239005

1-13

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 15: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transfor-mer ratio

Transformerclass

Transfor-merwiring(M: mea-suringdeviceS: termi-nal strip)

Measuringdevice(B: bime-tallicI: movingiron)

Positionindicator,1M+1B

FusemonitorES00,AC400V-690V

Utilizati-on cate-gory,AC500V/690V

Std.P Type Article No.

SASIL...

2 400A-1A 1 S Without Without Without AC23 1 2/3W400-1S/SKL A2214068

2 400A-1A 1 S Without Without Without AC22 1 2N/3W400-1S/SKL A2214500

2 400A-1A 1 S Without Without With AC23 1 2/3W400-1S/SKL/ES00 A2228008

2 400A-1A 1 S Without Without With AC22 1 2N/3W400-1S/SKL/ES00 A2228500

2 400A-1A 1 S Without With Without AC23 1 2/3W400-1S/SKL/SÖ A2220005

2 400A-1A 1 S Without With Without AC22 1 2N/3W400-1S/SKL/SÖ A2220503

2 400A-1A 1 S Without With With AC23 1 2/3W400-1S/SKL/SÖ/ES00 A2237001

2 400A-1A 1 S Without With With AC22 1 2N/3W400-1S/SKL/SÖ/ES00 A2237503

2 400A-1A 1 MS B/T15min Without Without AC23 1 2/3W400-1MS/SKL/MB15 A2248001

2 400A-1A 1 MS B/T15min Without Without AC22 1 2N/3W400-1MS/SKL/MB15 A2248507

2 400A-1A 1 MS B/T15min Without With AC23 1 2/3W400-1MS/SKL/MB15/ES00 A2256008

2 400A-1A 1 MS B/T15min Without With AC22 1 2N/3W400-1MS/SKL/MB15/ES00 A2256507

2 400A-1A 1 MS B/T15min With Without AC23 1 2/3W400-1MS/SKL/MB15/SÖ A2252008

2 400A-1A 1 MS B/T15min With Without AC22 1 2N/3W400-1MS/SKL/MB15/SÖ A2252507

2 400A-1A 1 MS B/T15min With With AC23 1 2/3W400-1MS/SKL/MB15/SÖ/ES00 A2260008

2 400A-1A 1 MS B/T15min With With AC22 1 2N/3W400-1MS/SKL/MB15/SÖ/ES00 A2260507

2 400A-1A 1 MS I Without Without AC23 1 2/3W400-1MS/SKL/MD A2215071

2 400A-1A 1 MS I Without Without AC22 1 2N/3W400-1MS/SKL/MD A2215500

2 400A-1A 1 MS I Without With AC23 1 2/3W400-1MS/SKL/MD/ES00 A2232004

2 400A-1A 1 MS I Without With AC22 1 2N/3W400-1MS/SKL/MD/ES00 A2232503

2 400A-1A 1 MS I With Without AC23 1 2/3W400-1MS/SKL/MD/SÖ A2223001

2 400A-1A 1 MS I With Without AC22 1 2N/3W400-1MS/SKL/MD/SÖ A2223504

2 400A-1A 1 MS I With With AC23 1 2/3W400-1MS/SKL/MD/SÖ/ES00 A2240006

2 400A-1A 1 MS I With With AC22 1 2N/3W400-1MS/SKL/MD/SÖ/ES00 A2240503

2 400A-5A 1 S Without Without Without AC23 1 2/3W400-5S/SKL A2208012

2 400A-5A 1 S Without Without Without AC22 1 2N/3W400-5S/SKL A2208501

2 400A-5A 1 S Without Without With AC23 1 2/3W400-5S/SKL/ES00 A2227001

2 400A-5A 1 S Without Without With AC22 1 2N/3W400-5S/SKL/ES00 A2227503

2 400A-5A 1 S Without With Without AC23 1 2/3W400-5S/SKL/SÖ A2219001

2 400A-5A 1 S Without With Without AC22 1 2N/3W400-5S/SKL/SÖ A2219503

2 400A-5A 1 S Without With With AC23 1 2/3W400-5S/SKL/SÖ/ES00 A2236005

2 400A-5A 1 S Without With With AC22 1 2N/3W400-5S/SKL/SÖ/ES00 A2236500

2 400A-5A 1 MS B/T15min Without Without AC23 1 2/3W400-5MS/SKL/MB15 A2247120

2 400A-5A 1 MS B/T15min Without Without AC22 1 2N/3W400-5MS/SKL/MB15 A2247500

2 400A-5A 1 MS B/T15min Without With AC23 1 2/3W400-5MS/SKL/MB15/ES00 A2255008

2 400A-5A 1 MS B/T15min Without With AC22 1 2N/3W400-5MS/SKL/MB15/ES00 A2255507

2 400A-5A 1 MS B/T15min With Without AC23 1 2/3W400-5MS/SKL/MB15/SÖ A2251008

2 400A-5A 1 MS B/T15min With Without AC22 1 2N/3W400-5MS/SKL/MB15/SÖ A2251507

2 400A-5A 1 MS B/T15min With With AC23 1 2/3W400-5MS/SKL/MB15/SÖ/ES00 A2259001

2 400A-5A 1 MS B/T15min With With AC22 1 2N/3W400-5MS/SKL/MB15/SÖ/ES00 A2259507

2 400A-5A 1 MS I Without Without AC23 1 2/3W400-5MS/SKL/MD A2213126

2 400A-5A 1 MS I Without Without AC22 1 2N/3W400-5MS/SKL/MD A2213503

2 400A-5A 1 MS I Without With AC23 1 2/3W400-5MS/SKL/MD/ES00 A2231001

2 400A-5A 1 MS I Without With AC22 1 2N/3W400-5MS/SKL/MD/ES00 A2231503

2 400A-5A 1 MS I With Without AC23 1 2/3W400-5MS/SKL/MD/SÖ A2222124

2 400A-5A 1 MS I With Without AC22 1 2N/3W400-5MS/SKL/MD/SÖ A2222503

2 400A-5A 1 MS I With With AC23 1 2/3W400-5MS/SKL/MD/SÖ/ES00 A2239001

2 400A-5A 1 MS I With With AC22 1 2N/3W400-5MS/SKL/MD/SÖ/ES00 A2239503

1-14

Page 16: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transfor-mer ratio

Transformerclass

Transfor-merwiring(M: mea-suringdeviceS: termi-nal strip)

Measuringdevice(B: bime-tallicI: movingiron)

Positionindicator,1M+1B

FusemonitorES00,AC400V-690V

Utilizati-on cate-gory,AC500V/690V

Std.P Type Article No.

SASIL...

3 600A-1A 1 S Without Without Without AC23 1 3/3W600-1S/SKL A3214051

3 600A-1A 1 S Without Without Without AC22 1 3N/3W600-1S/SKL A3214500

3 600A-1A 1 S Without Without With AC23 1 3/3W600-1S/SKL/ES00 A3228142

3 600A-1A 1 S Without Without With AC22 1 3N/3W600-1S/SKL/ES00 A3228502

3 600A-1A 1 S Without With Without AC23 1 3/3W600-1S/SKL/SÖ A3220004

3 600A-1A 1 S Without With Without AC22 1 3N/3W600-1S/SKL/SÖ A3220502

3 600A-1A 1 S Without With With AC23 1 3/3W600-1S/SKL/SÖ/ES00 A3237002

3 600A-1A 1 S Without With With AC22 1 3N/3W600-1S/SKL/SÖ/ES00 A3237506

3 600A-1A 1 MS B/T15min Without Without AC23 1 3/3W600-1MS/SKL/MB15 A3248011

3 600A-1A 1 MS B/T15min Without Without AC22 1 3N/3W600-1MS/SKL/MB15 A3248505

3 600A-1A 1 MS B/T15min Without With AC23 1 3/3W600-1MS/SKL/MB15/ES00 A3256006

3 600A-1A 1 MS B/T15min Without With AC22 1 3N/3W600-1MS/SKL/MB15/ES00 A3256505

3 600A-1A 1 MS B/T15min With Without AC23 1 3/3W600-1MS/SKL/MB15/SÖ A3252006

3 600A-1A 1 MS B/T15min With Without AC22 1 3N/3W600-1MS/SKL/MB15/SÖ A3252505

3 600A-1A 1 MS B/T15min With With AC23 1 3/3W600-1MS/SKL/MB15/SÖ/ES00 A3260006

3 600A-1A 1 MS B/T15min With With AC22 1 3N/3W600-1MS/SKL/MB15/SÖ/ES00 A3260505

3 600A-1A 1 MS I Without Without AC23 1 3/3W600-1MS/SKL/MD A3215054

3 600A-1A 1 MS I Without Without AC22 1 3N/3W600-1MS/SKL/MD A3215502

3 600A-1A 1 MS I Without With AC23 1 3/3W600-1MS/SKL/MD/ES00 A3232001

3 600A-1A 1 MS I Without With AC22 1 3N/3W600-1MS/SKL/MD/ES00 A3232502

3 600A-1A 1 MS I With Without AC23 1 3/3W600-1MS/SKL/MD/SÖ A3223004

3 600A-1A 1 MS I With Without AC22 1 3N/3W600-1MS/SKL/MD/SÖ A3223503

3 600A-1A 1 MS I With With AC23 1 3/3W600-1MS/SKL/MD/SÖ/ES00 A3240005

3 600A-1A 1 MS I With With AC22 1 3N/3W600-1MS/SKL/MD/SÖ/ES00 A3240502

3 600A-5A 1 S Without Without Without AC23 1 3/3W600-5S/SKL A3208016

3 600A-5A 1 S Without Without Without AC22 1 3N/3W600-5S/SKL A3208500

3 600A-5A 1 S Without Without With AC23 1 3/3W600-5S/SKL/ES00 A3227113

3 600A-5A 1 S Without Without With AC22 1 3N/3W600-5S/SKL/ES00 A3227502

3 600A-5A 1 S Without With Without AC23 1 3/3W600-5S/SKL/SÖ A3219144

3 600A-5A 1 S Without With Without AC22 1 3N/3W600-5S/SKL/SÖ A3219501

3 600A-5A 1 S Without With With AC23 1 3/3W600-5S/SKL/SÖ/ES00 A3236004

3 600A-5A 1 S Without With With AC22 1 3N/3W600-5S/SKL/SÖ/ES00 A3236500

3 600A-5A 1 MS B/T15min Without Without AC23 1 3/3W600-5MS/SKL/MB15 A3247044

3 600A-5A 1 MS B/T15min Without Without AC22 1 3N/3W600-5MS/SKL/MB15 A3247505

3 600A-5A 1 MS B/T15min Without With AC23 1 3/3W600-5MS/SKL/MB15/ES00 A3255006

3 600A-5A 1 MS B/T15min Without With AC22 1 3N/3W600-5MS/SKL/MB15/ES00 A3255505

3 600A-5A 1 MS B/T15min With Without AC23 1 3/3W600-5MS/SKL/MB15/SÖ A3251006

3 600A-5A 1 MS B/T15min With Without AC22 1 3N/3W600-5MS/SKL/MB15/SÖ A3251505

3 600A-5A 1 MS B/T15min With With AC23 1 3/3W600-5MS/SKL/MB15/SÖ/ES00 A3259006

3 600A-5A 1 MS B/T15min With With AC22 1 3N/3W600-5MS/SKL/MB15/SÖ/ES00 A3259505

3 600A-5A 1 MS I Without Without AC23 1 3/3W600-5MS/SKL/MD A3213099

3 600A-5A 1 MS I Without Without AC22 1 3N/3W600-5MS/SKL/MD A3213502

3 600A-5A 1 MS I Without With AC23 1 3/3W600-5MS/SKL/MD/ES00 A3231003

3 600A-5A 1 MS I Without With AC22 1 3N/3W600-5MS/SKL/MD/ES00 A3231502

3 600A-5A 1 MS I With Without AC23 1 3/3W600-5MS/SKL/MD/SÖ A3222003

3 600A-5A 1 MS I With Without AC22 1 3N/3W600-5MS/SKL/MD/SÖ A3222502

3 600A-5A 1 MS I With With AC23 1 3/3W600-5MS/SKL/MD/SÖ/ES00 A3239004

3 600A-5A 1 MS I With With AC22 1 3N/3W600-5MS/SKL/MD/SÖ/ES00 A3239502

1-15

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 17: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Current distributioncomponents

Switch-disconnector-fuses (SASIL), LV HRCsystem

3-pole, 185mm busbarsystem

Strip, sizes 00 to 3, w.manually-op. mech.,w. EE measuringmodule

1-16

Product definition

SASIL strips are 3-polepluggable strip-typeswitch-disconnector-fuses.The strips are equippedwith an operator-independ-ent snap-action mechanismand manually-operatedmechanism for clear posi-tion indication andaccomodate 3 LV HRCfuse-links in accordancewith DIN 43620, sizes00/160A to 3/630A.

MEASURING MODULE EEThe strip is equipped withan electronic monitoringmodule EE for connectionto the PLMaster energymanagement system. Linevoltage to be monitored:3AC400V-690V; controlvoltage: DC24V. The moni-toring module is equippedwith an additional relay out-put for external indicationof fuse/phase failure to thepush-on terminal strip.

All SASIL strips have plug-incontacts and can be se-curely plugged in an uprightfield distributor busbar sys-tem of 10mm thickness and185mm distance betweenbusbar centres using thecorresponding strip guides.A screw terminal for cable

lug connection is availableat the output side.The interlocking mecha-nism in the handle pre-vents the strip cover fromopening in the connectedstate. A double-break fea-ture (upstream and down-stream of the fuse) allows asafe exchange of the fuse.

Applications

SASIL strips with EE moni-toring module are mainlyused for system, cable andmotor protection inthree-phase systems up to690V in main andsubdistribution boards oflow voltage assemblies inaccordance with IEC/EN60439-1 (TTA/PTTA), for in-dustrial, power station andbuilding services applica-tions in which ongoing pro-cesses have to be moni-tored, particularly in thechemical industry, automo-tive industry, public build-ings and system manufac-turing. Their horizontal fit-ting and compact dimen-sions allow a large numberof cable outlets to be fittedin a limited space.

A uniform width, depth andgrid dimension of 25mm ofthe strip height (50mm,75mm, 150mm) enable a

rapid engineering andmounting of the strips withdifferent component sizesused in the switchgear cab-inet.

The control line and auxil-iary circuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.

Product construction

The device accessories arefactory-fitted in the SASILstrip.

CURRENT MEASUREMENT3-phase current measure-ment by N/1A transformers,class 1, in accordance withVDE 0414. The followingtransformer ratios are avail-able:50A/75A/100A/150A/200A/250A/400A/600A. Trans-formers are wired up inter-nally on the EE measuringmodule.

POSITION INDICATOR1 make contact and 1 breakcontact, wired up on apush-on terminal strip, forexternal indication.

PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.

To order strips with othertransformer ratios or measu-ring devices, use type key onpage 1-36

Page 18: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transformer ratio,class 1

Position indicator,1M+1B

Utilization category,AC500V/690V

Std.P Type Article No.

SASIL...

00 50A-1A Without AC23 1 00-50/3W50-1S/SKL/EE05 A6298016

00 50A-1A With AC23 1 00-50/3W50-1S/SKL/SÖ/EE05 A6298031

00 75A-1A Without AC23 1 00-50/3W75-1S/SKL/EE05 A6298015

00 75A-1A With AC23 1 00-50/3W75-1S/SKL/SÖ/EE05 A6298032

00 100A-1A Without AC23 1 00-50/3W100-1S/SKL/EE05 A6298014

00 100A-1A With AC23 1 00-50/3W100-1S/SKL/SÖ/EE05 A6298033

00 150A-1A Without AC23 1 00-50/3W150-1S/SKL/EE05 A6298019

00 150A-1A With AC23 1 00-50/3W150-1S/SKL/SÖ/EE05 A6298034

1 100A-1A Without AC23 1 1/3W100-1S/SKL/EE05 A1298045

1 100A-1A With AC23 1 1/3W100-1S/SKL/SÖ/EE05 A1298047

1 150A-1A Without AC23 1 1/3W150-1S/SKL/EE05 A1298101

1 150A-1A With AC23 1 1/3W150-1S/SKL/SÖ/EE05 A1298048

1 200A-1A Without AC23 1 1/3W200-1S/SKL/EE05 A1298020

1 200A-1A With AC23 1 1/3W200-1S/SKL/SÖ/EE05 A1298049

1 250A-1A Without AC23 1 1/3W250-1S/SKL/EE05 A1298021

1 250A-1A With AC23 1 1/3W250-1S/SKL/SÖ/EE05 A1298050

2 150A-1A Without AC23 1 2/3W150-1S/SKL/EE05 A2298031

2 150A-1A Without AC22 1 2N/3W150-1S/SKL/EE05 A2298550

2 150A-1A With AC23 1 2/3W150-1S/SKL/SÖ/EE05 A2298034

2 150A-1A With AC22 1 2N/3W150-1S/SKL/SÖ/EE05 A2298551

2 200A-1A Without AC23 1 2/3W200-1S/SKL/EE05 A2298032

2 200A-1A Without AC22 1 2N/3W200-1S/SKL/EE05 A2298552

2 200A-1A With AC23 1 2/3W200-1S/SKL/SÖ/EE05 A2298046

2 200A-1A With AC22 1 2N/3W200-1S/SKL/SÖ/EE05 A2298553

2 250A-1A Without AC23 1 2/3W250-1S/SKL/EE05 A2298033

2 250A-1A Without AC22 1 2N/3W250-1S/SKL/EE05 A2298554

2 250A-1A With AC23 1 2/3W250-1S/SKL/SÖ/EE05 A2298047

2 250A-1A With AC22 1 2N/3W250-1S/SKL/SÖ/EE05 A2298555

2 400A-1A Without AC23 1 2/3W400-1S/SKL/EE05 A2298014

2 400A-1A Without AC22 1 2N/3W400-1S/SKL/EE05 A2298556

2 400A-1A With AC23 1 2/3W400-1S/SKL/SÖ/EE05 A2298037

2 400A-1A With AC22 1 2N/3W400-1S/SKL/SÖ/EE05 A2298557

3 250A-1A Without AC23 1 3/3W250-1S/SKL/EE05 A3298028

3 250A-1A Without AC22 1 3N/3W250-1S/SKL/EE05 A3298515

3 250A-1A With AC23 1 3/3W250-1S/SKL/SÖ/EE05 A3298031

3 250A-1A With AC22 1 3N/3W250-1S/SKL/SÖ/EE05 A3298504

3 400A-1A Without AC23 1 3/3W400-1S/SKL/EE05 A3298029

3 400A-1A Without AC22 1 3N/3W400-1S/SKL/EE05 A3298502

3 400A-1A With AC23 1 3/3W400-1S/SKL/SÖ/EE05 A3298032

3 400A-1A With AC22 1 3N/3W400-1S/SKL/SÖ/EE05 A3298505

3 600A-1A Without AC23 1 3/3W600-1S/SKL/EE05 A3298030

3 600A-1A Without AC22 1 3N/3W600-1S/SKL/EE05 A3298503

3 600A-1A With AC23 1 3/3W600-1S/SKL/SÖ/EE05 A3298033

3 600A-1A With AC22 1 3N/3W600-1S/SKL/SÖ/EE05 A3298506

1-17

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 19: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Current distributioncomponents

Switch-disconnector-fuses (SASIL), LV HRCsystem

3-pole, 185mm busbarsystem

Strip, sizes 00 to 3, w.motor-op. mech.

1-18

Product definition

SASIL strips with motor-op-erated mechanism are3-pole pluggable strip-typeswitch-disconnector-fuses.The strips are equippedwith a mechanism whichcan be operated remotely,DC24V power supply, andaccomodate 3 LV HRCfuse-links in accordancewith DIN 43620, sizes00/160A to 3/630A.

All SASIL strips have plug-incontacts and can be se-curely plugged in an uprightfield distributor busbar sys-tem of 10mm thickness and185mm distance betweenbusbar centres using thecorresponding strip guides.A screw terminal for cablelug connection is availableat the output side.The interlocking mecha-nism in the motor unit pre-vents the strip cover fromopening in the connectedstate. A double-break fea-ture (upstream and down-stream of the fuse) allows asafe exchange of the fuse.All SASIL-MOT strips areequipped with an electronicfuse monitor and a positionindicator. Versionsequipped with an EE mea-suring module provide 1make contact to this pur-pose, all other versions, 1make contact and 1 breakcontact.

Applications

SASIL-MOT strips are mainlyused for system, cable and

motor protection inthree-phase systems up to690V in main andsubdistribution boards oflow voltage assemblies inaccordance with IEC/EN60439-1 (TTA/PTTA), for in-dustrial, power station andbuilding services applica-tions. Their horizontal fit-ting and compact dimen-sions allow a large numberof cable outlets to be fittedin a limited space.A uniform width, depth andgrid dimension of 25mm ofthe strip height (50mm,75mm, 150mm) enable arapid engineering andmounting of the strips withdifferent component sizesused in the switchgear cab-inet.

The control line and auxil-iary circuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.

Product construction

The device accessories arefactory-fitted in the SASILstrip.

CURRENT MEASUREMENT1-phase current measure-ment by N/1A or N/5Atransformers, class 1, in ac-cordance with VDE 0414, fit-ted in phase L1. 3-phaseN/1A current measurementonly in conjunction with EEmeasuring module. The fol-lowing transformer ratiosare available:50A/75A/100A/150A/200A

/250A/400A/600A.1-phase transformers arewired up externally on apush-on terminal strip. Alltransformers can be oper-ated open for an unlimitedperiod of time.In the case of a cable infeed(Z version), the transform-ers are installed „back tofront“ (turned through180°).

POSITION INDICATOR1 make contact and 1 breakcontact (with EE measuringmodule, 1 make contact),wired up on a push-on ter-minal strip, for external in-dication.

PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.

ELECTRONIC FUSE MONI-TORIndicates fuse failure by afrontal LED and relays thefault signal to the push-onterminal strip via change-over contacts.

MEASURING MODULE EEThe strip can be equippedwith an electronic monitor-ing module EE for connec-tion to the PLMaster energymanagement system. Linevoltage to be monitored:3AC400V-690V; controlvoltage: DC24V. The moni-toring module is equippedwith an additional relay out-put for external indicationof fuse/phase failure to thepush-on terminal strip.

To order strips with othertransformer ratios or measu-ring devices, use type key onpage 1-36

Page 20: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transformerratio, class 1

Current measure-ment

Measuringsensor EE05,AC400V-690V

Utilizationcategory,AC500V/690V

Std.P Type Article No.

SASIL-MOT...

00 Without Without Without AC23 1 00-50/SKL/SÖ/ES05 A6224401

00 50A-1A 1 transformer Without AC23 1 00-50/1W50-1S/SKL/SÖ/ES05 A6235401

00 50A-1A 3 transformers With AC23 1 00-50/3W50-1S/SKL/1S/EE05 A6298401

00 50A-5A 1 transformer Without AC23 1 00-50/1W50-5S/SKL/SÖ/ES05 A6234401

00 75A-1A 1 transformer Without AC23 1 00-50/1W75-1S/SKL/SÖ/ES05 A6235402

00 75A-1A 3 transformers With AC23 1 00-50/3W75-1S/SKL/1S/EE05 A6298402

00 75A-5A 1 transformer Without AC23 1 00-50/1W75-5S/SKL/SÖ/ES05 A6234402

00 100A-1A 1 transformer Without AC23 1 00-50/1W100-1S/SKL/SÖ/ES05 A6235403

00 100A-1A 3 transformers With AC23 1 00-50/3W100-1S/SKL/1S/EE05 A6298403

00 100A-5A 1 transformer Without AC23 1 00-50/1W100-5S/SKL/SÖ/ES05 A6234403

00 150A-1A 1 transformer Without AC23 1 00-50/1W150-1S/SKL/SÖ/ES05 A6235404

00 150A-1A 3 transformers With AC23 1 00-50/3W150-1S/SKL/1S/EE05 A6298404

00 150A-5A 1 transformer Without AC23 1 00-50/1W150-5S/SKL/SÖ/ES05 A6234404

1 Without Without Without AC23 1 1/SKL/SÖ/ES05 A1224401

1 100A-1A 1 transformer Without AC23 1 1/1W100-1S/SKL/SÖ/ES05 A1235401

1 100A-1A 3 transformers With AC23 1 1/3W100-1S/SKL/1S/EE05 A1298401

1 100A-5A 1 transformer Without AC23 1 1/1W100-5S/SKL/SÖ/ES05 A1234401

1 150A-1A 1 transformer Without AC23 1 1/1W150-1S/SKL/SÖ/ES05 A1235402

1 150A-1A 3 transformers With AC23 1 1/3W150-1S/SKL/1S/EE05 A1298402

1 150A-5A 1 transformer Without AC23 1 1/1W150-5S/SKL/SÖ/ES05 A1234402

1 200A-1A 1 transformer Without AC23 1 1/1W200-1S/SKL/SÖ/ES05 A1235403

1 200A-1A 3 transformers With AC23 1 1/3W200-1S/SKL/1S/EE05 A1298403

1 200A-5A 1 transformer Without AC23 1 1/1W200-5S/SKL/SÖ/ES05 A1234403

1 250A-1A 1 transformer Without AC23 1 1/1W250-1S/SKL/SÖ/ES05 A1235404

1 250A-1A 3 transformers With AC23 1 1/3W250-1S/SKL/1S/EE05 A1298404

1 250A-5A 1 transformer Without AC23 1 1/1W250-5S/SKL/SÖ/ES05 A1234404

2 Without Without Without AC23 1 2/SKL/SÖ/ES05 A2224401

2 150A-1A 1 transformer Without AC23 1 2/1W150-1S/SKL/SÖ/ES05 A2235401

2 150A-1A 3 transformers With AC23 1 2/3W150-1S/SKL/1S/EE05 A2298401

2 150A-5A 1 transformer Without AC23 1 2/1W150-5S/SKL/SÖ/ES05 A2234401

2 200A-1A 1 transformer Without AC23 1 2/1W200-1S/SKL/SÖ/ES05 A2235402

2 200A-1A 3 transformers With AC23 1 2/3W200-1S/SKL/1S/EE05 A2298402

2 200A-5A 1 transformer Without AC23 1 2/1W200-5S/SKL/SÖ/ES05 A2234402

2 250A-1A 1 transformer Without AC23 1 2/1W250-1S/SKL/SÖ/ES05 A2235403

2 250A-1A 3 transformers With AC23 1 2/3W250-1S/SKL/1S/EE05 A2298403

2 250A-5A 1 transformer Without AC23 1 2/1W250-5S/SKL/SÖ/ES05 A2234403

2 400A-1A 1 transformer Without AC23 1 2/1W400-1S/SKL/SÖ/ES05 A2235404

2 400A-1A 3 transformers With AC23 1 2/3W400-1S/SKL/1S/EE05 A2298404

2 400A-5A 1 transformer Without AC23 1 2/1W400-5S/SKL/SÖ/ES05 A2234404

3 Without Without Without AC23 1 3/SKL/SÖ/ES05 A3224401

3 250A-1A 1 transformer Without AC23 1 3/1W250-1S/SKL/SÖ/ES05 A3235401

3 250A-1A 3 transformers With AC23 1 3/3W250-1S/SKL/1S/EE05 A3298401

3 250A-5A 1 transformer Without AC23 1 3/1W250-5S/SKL/SÖ/ES05 A3234401

3 400A-1A 1 transformer Without AC23 1 3/1W400-1S/SKL/SÖ/ES05 A3235402

3 400A-1A 3 transformers With AC23 1 3/3W400-1S/SKL/1S/EE05 A3298402

3 400A-5A 1 transformer Without AC23 1 3/1W400-5S/SKL/SÖ/ES05 A3234402

3 600A-1A 1 transformer Without AC23 1 3/1W600-1S/SKL/SÖ/ES05 A3235403

3 600A-1A 3 transformers With AC23 1 3/3W600-1S/SKL/1S/EE05 A3298403

3 600A-5A 1 transformer Without AC23 1 3/1W600-5S/SKL/SÖ/ES05 A3234403

1-19

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 21: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Current distributioncomponents

Switch-disconnector-fuses (SASIL), LV HRCsystem

3-pole, 185mm busbarsystem

Coupling strip, size 3,w. manually-op. mech.

1-20

Product definition

SASIL coupling strips are3-pole pluggable strip-typeswitch-disconnector-fusesfor the disconnection of twofield distributor busbar sys-tems without cable connec-tion. The strips areequipped with an opera-tor-independent snap-ac-tion mechanism and manu-ally-operated mechanismfor clear position indicationand accomodate 3 LV HRCfuse-links in accordancewith DIN 43620, size3/630A.All SASIL coupling stripshave 6 plug-in contacts andcan be securely plugged inan upright field distributorbusbar system of 10mmthickness and 185mm dis-tance between busbar cen-tres using the correspond-ing strip guides. The inter-locking mechanism in thehandle prevents the stripcover from opening in theconnected state. A dou-ble-break feature (upstreamand downstream of thefuse) allows a safe ex-change of the fuse.

Applications

SASIL coupling strips areused in three-phase sys-

tems up to 690V in mainand subdistribution boardsof low voltage assembliesin accordance with IEC/EN60439-1 (TTA/PTTA). Theirhorizontal fitting and com-pact dimensions allowbusbar disconnection in alimited space.

The control line and auxil-iary circuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.

Product construction

The device accessories arefactory-fitted in the SASILstrip.

CURRENT MEASUREMENT3-phase current measure-ment by N/1A or N/5Atransformers, class 1, in ac-cordance with VDE 0414.The following transformerratios are available:250A/400A/600A. Trans-formers are wired up exter-nally on a push-on terminalstrip. All transformers canbe operated open for anunlimited period of time.

The current transformersare integrated with respectto its current direction from

top to bottom of thedistributionfield (Horizontalmounting).

POSITION INDICATOR1 make contact and 1 breakcontact, wired up on apush-on terminal strip, forexternal indication.

PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.

ELECTRONIC FUSE MONI-TORIndicates fuse failure by afrontal LED and relays thefault signal to the push-onterminal strip viamake/break contacts.

MEASURING MODULE EEThe strip can be equippedwith an electronic monitor-ing module EE for connec-tion to the PLMaster energymanagement system. Linevoltage to be monitored:3AC400V-690V; controlvoltage: DC24V. The moni-toring module is equippedwith an additional relay out-put for external indicationof fuse/phase failure to thepush-on terminal strip.

To order strips with othertransformer ratios or measu-ring devices, use type key onpage 1-36

Page 22: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transfor-mer ratio,class 1

Current measu-rement

Positionindicator,1M+1B

Fuse moni-tor ES00,AC400V-690V

MeasuringsensorEE05,AC400V-690V

Utilizationcategory,AC500V/690V

Std.P Type Article No.

SASIL3K...

3 Without Without Without Without Without AC23 1 A3500002

3 Without Without With Without Without AC23 1 /SKL/SÖ A3504002

3 Without Without With With Without AC23 1 /SKL/SÖ/ES00 A3524005

3 250A-1A 3 transformers Without Without Without AC23 1 /3W250-1S/SKL A3514005

3 250A-1A 3 transformers Without Without With AC23 1 /3W250-1S/SKL/EE05 A3598001

3 250A-1A 3 transformers Without With Without AC23 1 /3W250-1S/SKL/ES00 A3528004

3 250A-1A 3 transformers With Without Without AC23 1 /3W250-1S/SKL/SÖ A3520004

3 250A-1A 3 transformers With Without With AC23 1 /3W250-1S/SKL/SÖ/EE05 A3598004

3 250A-1A 3 transformers With With Without AC23 1 /3W250-1S/SKL/SÖ/ES00 A3537004

3 250A-5A 3 transformers Without Without Without AC23 1 /3W250-5S/SKL A3508004

3 250A-5A 3 transformers Without With Without AC23 1 /3W250-5S/SKL/ES00 A3527001

3 250A-5A 3 transformers With Without Without AC23 1 /3W250-5S/SKL/SÖ A3519004

3 250A-5A 3 transformers With With Without AC23 1 /3W250-5S/SKL/SÖ/ES00 A3536001

3 400A-1A 3 transformers Without Without Without AC23 1 /3W400-1S/SKL A3514006

3 400A-1A 3 transformers Without Without With AC23 1 /3W400-1S/SKL/EE05 A3598002

3 400A-1A 3 transformers Without With Without AC23 1 /3W400-1S/SKL/ES00 A3528005

3 400A-1A 3 transformers With Without Without AC23 1 /3W400-1S/SKL/SÖ A3520005

3 400A-1A 3 transformers With Without With AC23 1 /3W400-1S/SKL/SÖ/EE05 A3598005

3 400A-1A 3 transformers With With Without AC23 1 /3W400-1S/SKL/SÖ/ES00 A3537005

3 400A-5A 3 transformers Without Without Without AC23 1 /3W400-5S/SKL A3508005

3 400A-5A 3 transformers Without With Without AC23 1 /3W400-5S/SKL/ES00 A3527002

3 400A-5A 3 transformers With Without Without AC23 1 /3W400-5S/SKL/SÖ A3519005

3 400A-5A 3 transformers With With Without AC23 1 /3W400-5S/SKL/SÖ/ES00 A3536002

3 600A-1A 3 transformers Without Without Without AC23 1 /3W600-1S/SKL A3514007

3 600A-1A 3 transformers Without Without With AC23 1 /3W600-1S/SKL/EE05 A3598003

3 600A-1A 3 transformers Without With Without AC23 1 /3W600-1S/SKL/ES00 A3528006

3 600A-1A 3 transformers With Without Without AC23 1 /3W600-1S/SKL/SÖ A3520006

3 600A-1A 3 transformers With Without With AC23 1 /3W600-1S/SKL/SÖ/EE05 A3598006

3 600A-1A 3 transformers With With Without AC23 1 /3W600-1S/SKL/SÖ/ES00 A3537006

3 600A-5A 3 transformers Without Without Without AC23 1 /3W600-5S/SKL A3508006

3 600A-5A 3 transformers Without With Without AC23 1 /3W600-5S/SKL/ES00 A3527003

3 600A-5A 3 transformers With Without Without AC23 1 /3W600-5S/SKL/SÖ A3519006

3 600A-5A 3 transformers With With Without AC23 1 /3W600-5S/SKL/SÖ/ES00 A3536003

3 Without Without Without With Without AC23 1 /SKL/ES00 A3505005

1-21

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 23: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Current distributioncomponents

Switch-disconnector-fuses (SASIL), LV HRCsystem

3-pole, 185mm busbarsystem

Double strip, sizes 00to 3, w. manually-op.mech.

1-22

Product definition

SASIL double strips consistof two 3-pole pluggablestrip-typeswitch-disconnector-fuseswith a common manu-ally-operated mechanism.The strips are equippedwith an operator-independ-ent snap-action mechanismand accomodate six LV HRCfuse-links in accordancewith DIN 43620, sizes00/160A to 3/630A.All SASIL strips have plug-incontacts and can be se-curely plugged in an uprightfield distributor busbar sys-tem of 10mm thickness and185mm distance betweenbusbar centres using thecorresponding strip guides.A screw terminal for cablelug connection is availableat the output side.The interlocking mecha-nism in the handle pre-vents the strip cover fromopening in the connectedstate. A double-break fea-ture (upstream and down-stream of the fuse) allows asafe exchange of the fuse.

Applications

SASIL double strips aremainly used for loads with

parallel supply inthree-phase systems up to690V in main andsubdistribution boards oflow voltage assemblies inaccordance with IEC/EN60439-1 (TTA/PTTA), for in-dustrial, power station andbuilding services applica-tions.

The control line and auxil-iary circuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.

Product construction

The device accessories arefactory-fitted in the SASILstrip.

CURRENT MEASUREMENT3-phase current measure-ment by N/1A or N/5Atransformers, class 1, in ac-cordance with VDE 0414.The following transformerratios are available:150A/250A/400A/600A.The transformers can bewired up either internally ona measuring device or ex-ternally on a push-on termi-nal strip. All transformerscan be operated open foran unlimited period of time.

In the case of a cable infeed(Z version), the transform-ers are installed „back tofront“ (turned through180°).

MEASURING DEVICESIt is possible to use 48mm x48mm measuring devicesas class 1.5 moving iron cur-rent meters or bimetalliccurrent meters (from atransformer ratio of 150A)with an average value dis-play of T=8min. or T=15min.Bimetallic current metersprovide a maximum valuedisplay by resettable slavepointers. Moving iron cur-rent meters have a dial with2-fold overload area, whilebimetallic current metershave a dial with 1.2-foldoverload area.

POSITION INDICATOR1 make contact and 1 breakcontact, wired up on apush-on terminal strip, forexternal indication.

PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.

To order strips with othertransformer ratios or measu-ring devices, use type key onpage 1-36

Page 24: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transformer ratio,6 transformers,class 1

Transformerwiring(M: measuringdeviceS: terminalstrip)

Measuring device(B: bimetallicI: moving iron)

Utilizationcategory,AC500V/690V

Std.P Type Article No.

SASIL...

00 Without Without Without AC23 1 00-50D/SKL/SÖ A6204600

00 150A-1A MS B/T15min AC23 1 00-50D/6W150-1MS/SKL/MB15/SÖ A6252601

00 150A-1A MS B/T8min AC23 1 00-50D/6W150-1MS/SKL/MB8/SÖ A6252600

00 150A-1A MS I AC23 1 00-50D/6W150-1MS/SKL/MD/SÖ A6223600

00 150A-1A S Without AC23 1 00-50D/6W150-1S/SKL/SÖ A6220600

00 150A-5A MS B/T15min AC23 1 00-50D/6W150-5MS/SKL/MB15/SÖ A6251601

00 150A-5A MS B/T8min AC23 1 00-50D/6W150-5MS/SKL/MB8/SÖ A6251600

00 150A-5A MS I AC23 1 00-50D/6W150-5MS/SKL/MD/SÖ A6222600

00 150A-5A S Without AC23 1 00-50D/6W150-5S/SKL/SÖ A6219600

1 Without Without Without AC23 1 1D/SKL/SÖ A1204600

1 150A-1A S Without AC23 1 1D/6W150-1/SKL/SÖ A1220600

1 150A-1A MS B/T15min AC23 1 1D/6W150-1MS/SKL/MB15/SÖ A1252602

1 150A-1A MS B/T8min AC23 1 1D/6W150-1MS/SKL/MB8/SÖ A1252600

1 150A-1A MS I AC23 1 1D/6W150-1MS/SKL/MD/SÖ A1223601

1 150A-5A MS B/T15min AC23 1 1D/6W150-5MS/SKL/MB15/SÖ A1251602

1 150A-5A MS B/T8min AC23 1 1D/6W150-5MS/SKL/MB8/SÖ A1251600

1 150A-5A S Without AC23 1 1D/6W150-5S/SKL/SÖ A1219601

1 150A-5A MS I AC23 1 1D/6W150-MS/SKL/MD/SÖ A1222600

1 250A-1A MS B/T15min AC23 1 1D/6W250-1MS/SKL/MB15/SÖ A1252603

1 250A-1A MS B/T8min AC23 1 1D/6W250-1MS/SKL/MB8/SÖ A1252601

1 250A-1A MS I AC23 1 1D/6W250-1MS/SKL/MD/SÖ A1223600

1 250A-1A S Without AC23 1 1D/6W250-1S/SKL/SÖ A1220601

1 250A-5A MS B/T15min AC23 1 1D/6W250-5MS/SKL/MB15/SÖ A1251603

1 250A-5A MS B/T8min AC23 1 1D/6W250-5MS/SKL/MB8/SÖ A1251601

1 250A-5A MS I AC23 1 1D/6W250-5MS/SKL/MD/SÖ A1222601

1 250A-5A S Without AC23 1 1D/6W250-5S/SKL/SÖ A1219600

2 Without Without Without AC23 1 2D/SKL/SÖ A2204600

2 150A-1A MS B/T15min AC23 1 2D/6W150-1MS/SKL/MB15/SÖ A2252603

2 150A-1A MS B/T8min AC23 1 2D/6W150-1MS/SKL/MB8/SÖ A2252600

2 150A-1A MS I AC23 1 2D/6W150-1MS/SKL/MD/SÖ A2223601

2 150A-1A S Without AC23 1 2D/6W150-1S/SKL/SÖ A2220600

2 150A-5A MS B/T15min AC23 1 2D/6W150-5MS/SKL/MB15/SÖ A2251603

2 150A-5A MS B/T8min AC23 1 2D/6W150-5MS/SKL/MB8/SÖ A2251600

2 150A-5A MS I AC23 1 2D/6W150-5MS/SKL/MD/SÖ A2222600

2 150A-5A S Without AC23 1 2D/6W150-5S/SKL/SÖ A2219601

2 250A-1A MS B/T15min AC23 1 2D/6W250-1MS/SKL/MB15/SÖ A2252604

2 250A-1A MS B/T8min AC23 1 2D/6W250-1MS/SKL/MB8/SÖ A2252601

2 250A-1A MS I AC23 1 2D/6W250-1MS/SKL/MD/SÖ A2223602

2 250A-1A S Without AC23 1 2D/6W250-1S/SKL/SÖ A2220601

2 250A-5A MS B/T15min AC23 1 2D/6W250-5MS/SKL/MB15/SÖ A2251604

2 250A-5A MS B/T8min AC23 1 2D/6W250-5MS/SKL/MB8/SÖ A2251601

2 250A-5A MS I AC23 1 2D/6W250-5MS/SKL/MD/SÖ A2222601

2 250A-5A S Without AC23 1 2D/6W250-5S/SKL/SÖ A2219602

2 400A-1A MS B/T15min AC23 1 2D/6W400-1MS/SKL/MB15/SÖ A2252605

2 400A-1A MS B/T8min AC23 1 2D/6W400-1MS/SKL/MB8/SÖ A2252602

2 400A-1A MS I AC23 1 2D/6W400-1MS/SKL/MD/SÖ A2223600

2 400A-1A S Without AC23 1 2D/6W400-1S/SKL/SÖ A2220602

2 400A-5A MS B/T15min AC23 1 2D/6W400-5MS/SKL/MB15/SÖ A2251605

2 400A-5A MS B/T8min AC23 1 2D/6W400-5MS/SKL/MB8/SÖ A2251602

2 400A-5A MS I AC23 1 2D/6W400-5MS/SKL/MD/SÖ A2222602

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix1-23

Page 25: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Transformer ratio,6 transformers,class 1

Transformerwiring(M: measuringdeviceS: terminalstrip)

Measuring device(B: bimetallicI: moving iron)

Utilizationcategory,AC500V/690V

Std.P Type Article No.

SASIL...

2 400A-5A S Without AC23 1 2D/6W400-5S/SKL/SÖ A2219600

3 Without Without Without AC23 1 3D/SKL/SÖ A3204600

3 250A-1A MS B/T15min AC23 1 3D/6W250-1MS/SKL/MB15/SÖ A3252603

3 250A-1A MS B/T8min AC23 1 3D/6W250-1MS/SKL/MB8/SÖ A3252600

3 250A-1A MS I AC23 1 3D/6W250-1MS/SKL/MD/SÖ A3223600

3 250A-1A S Without AC23 1 3D/6W250-1S/SKL/SÖ A3220600

3 250A-5A MS B/T15min AC23 1 3D/6W250-5MS/SKL/MB15/SÖ A3251603

3 250A-5A MS B/T8min AC23 1 3D/6W250-5MS/SKL/MB8/SÖ A3251600

3 250A-5A MS I AC23 1 3D/6W250-5MS/SKL/MD/SÖ A3222600

3 250A-5A S Without AC23 1 3D/6W250-5S/SKL/SÖ A3219600

3 400A-1A MS B/T15min AC23 1 3D/6W400-1MS/SKL/MB15/SÖ A3252604

3 400A-1A MS B/T8min AC23 1 3D/6W400-1MS/SKL/MB8/SÖ A3252601

3 400A-1A MS I AC23 1 3D/6W400-1MS/SKL/MD/SÖ A3223601

3 400A-1A S Without AC23 1 3D/6W400-1S/SKL/SÖ A3220601

3 400A-5A MS B/T15min AC23 1 3D/6W400-5MS/SKL/MB15/SÖ A3251604

3 400A-5A MS B/T8min AC23 1 3D/6W400-5MS/SKL/MB8/SÖ A3251601

3 400A-5A MS I AC23 1 3D/6W400-5MS/SKL/MD/SÖ A3222601

3 400A-5A S Without AC23 1 3D/6W400-5S/SKL/SÖ A3219601

3 600A-1A MS B/T15min AC23 1 3D/6W600-1MS/SKL/MB15/SÖ A3252605

3 600A-1A MS B/T8min AC23 1 3D/6W600-1MS/SKL/MB8/SÖ A3252602

3 600A-1A MS I AC23 1 3D/6W600-1MS/SKL/MD/SÖ A3223602

3 600A-1A S Without AC23 1 3D/6W600-1S/SKL/SÖ A3220602

3 600A-5A MS B/T15min AC23 1 3D/6W600-5MS/SKL/MB15/SÖ A3251605

3 600A-5A MS B/T8min AC23 1 3D/6W600-5MS/SKL/MB8/SÖ A3251602

3 600A-5A MS I AC23 1 3D/6W600-5MS/SKL/MD/SÖ A3222602

3 600A-5A S Without AC23 1 3D/6W600-5S/SKL/SÖ A3219602

1-24

Page 26: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-25

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 27: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Current distributioncomponents

Switch-disconnector-fuses (SASIL), LV HRCsystem

2-pole, 185mm busbarsystem

Strip, sizes 00 to 3, w.manually-op. mech.,w/o current msrmnt

1-26

Product definition

SASIL strips are 2-polepluggable strip-typeswitch-disconnector-fuses.The strips are equippedwith an operator-independ-ent snap-action mechanismand manually-operatedmechanism for clear posi-tion indication andaccomodate 2 LV HRCfuse-links in accordancewith DIN 43620, sizes00/160A to 3/630A.All SASIL strips have plug-incontacts and can be se-curely plugged in an uprightfield distributor busbar sys-tem of 10mm thickness and370mm distance betweenbusbar centres using thecorresponding strip guides.A screw terminal for cablelug connection is availableat the output side.The interlocking mecha-nism in the handle pre-vents the strip cover from

opening in the connectedstate. A double-break fea-ture (upstream and down-stream of the fuse) allows asafe exchange of the fuse.

Applications

SASIL strips are mainlyused for system, cable andmotor protection in directcurrent systems up toDC440V in main andsubdistribution boards oflow voltage assemblies inaccordance with IEC/EN60439-1 (TTA/PTTA), for in-dustrial, power station andbuilding services applica-tions. Their horizontal fit-ting and compact dimen-sions allow a large numberof cable outlets to be fittedin a limited space.

A uniform width, depth andgrid dimension of 25mm ofthe strip height (50mm,75mm, 150mm) enable a

rapid engineering andmounting of the strips withdifferent component sizesused in the switchgear cab-inet.The control line and auxil-iary circuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.

Product construction

The device accessories arefactory-fitted in the SASILstrip.

POSITION INDICATOR1 make contact and 1 breakcontact, wired up on apush-on terminal strip, forexternal indication.

PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.

Page 28: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Size Position indicator, 1M+1B Utilization category,DC220V/440V

Std.P Type Article No.

SASIL...

00 Without DC22/21 1 00-50-2 A6200020

00 With DC22/21 1 00-50-2/SKL/SÖ A6204001

1 Without DC22/21 1 1-2 A1200081

1 With DC22/21 1 1-2/SKL/SÖ A1204067

2 Without DC22/21 1 2-2 A2200084

2 With DC22/21 1 2-2/SKL/SÖ A2204001

3 Without DC22/21 1 3-2 A3200066

3 With DC22/21 1 3-2/SKL/SÖ A3204001

1-27

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 29: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Current distributioncomponents

Switch-disconnector-fuses (SASIL), LV HRCsystem

SASIL accessories

SASIL systemaccessories

1-28

Product definition

The SASIL system accesso-ries allow a wide range ofswitchgear cabinets to beprepared for easy fitting ofSASILswitch-disconnector-fuses.Simple profiles and coversdivide the cabinets into de-vice, busbar and cablecompartments.

Applications

Fitting of components inswitchgear cabinets for lowvoltage assemblies(TTA/PTTA in accordancewith IEC/EN 60439-1) incompliance with system en-gineering specifications.

Product construction

SWITCHING CABINET PRO-FILE KITThis kit is required for theexpansion of switchgearcabinet systems whichhave not been prepared forthe fitting of SASIL compo-nents during manufacture.It consists of four sectionsand serves as a base sup-port for all built-in compo-nents of the system acces-sories.

BUSBAR SUPPORTThe 3-pole type-testedbusbar support is used toaccomodate the field dis-

tributor busbar system. It issuitable for flat copperbusbars with cross-sectionsof 40mm x 10mm to100mm x 10mm. The sup-port is fixed at theswitchgear cabinet usingfixing plates or fixing brack-ets.A special version with clos-ing plate for the bottombusbar support is alsoavailable.

BUSBAR COVERThe 150mm high busbarcover or cable compartmentcover is used for probe-safeIP20 separation of the cabi-net busbar compartmentfrom the device compart-ment and cable compart-ment. Thiscompartmentalization pro-vides increased personneland operational safety ofthe switching station andallows working while thesystem is energized.

BUSBAR DISCONNECTIONKITThe kit is used with lowvoltage assemblies, forsectionalizing the field dis-tributor busbars. It is in-serted in the busbar sup-ports SST-185/10010.

STRIP GUIDEStrip guides allow easymounting of the SASILstrips in the switchgear cab-

inet using their push-in de-sign. They enable theSASIL strips to be mountedwhile the system is ener-gized.Each SASIL strip is securedwith four M5x20 screws(not included).The strip guides alsoaccomodate the socketconnector, cable separatorand closing lock-out.

CABLE SEPARATORThe cable separator kit isused for IP20 separation ofthe cabinet cable compart-ment from the device com-partment.

SOCKET CONNECTORThe 16-pole socket connec-tor is the customer terminalof the SASIL strips for con-trol and auxiliary circuit wir-ing. The independentmounting of the socket con-nector at the strip guidealso allows unequipped re-serve spaces to beprewired.

CLOSING LOCK-OUTThe closing lock-out pre-vents incorrectly mountedSASIL strips from beingconnected. All closinglock-outs are clipped intothe respective strip guides.

Page 30: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Switching cabinet profile kit, for non-prepared system cabi-nets

Std.P Type Article No.

Kit, 4 individual profiles of 2023mm length 1 SSP/SASIL A8017256

Busbar support, 3-pole, 185mm busbar system Std.P Type Article No.

Busbar support, 40mm x 10mm 1 SST-185/4010 A8017272

Busbar support, 50mm x 10mm 1 SST-185/5010 A8017273

Busbar support, 60mm x 10mm 1 SST-185/6010 A8017274

Busbar support, 80mm x 10mm 1 SST-185/8010 A8017275

Busbar support, 100mm x 10mm 1 SST-185/10010 A8017276

Busbar support, 3-pole, 185mm busbar system Std.P Type Article No.

Busbar support, 40mm x 10mm, with seal plate 1 SST-185/A1/4010 A8017278

Busbar support, 50mm x 10mm, with seal plate 1 SST-185/A1/5010 A8017279

Busbar support, 60mm x 10mm, with seal plate 1 SST-185/A1/6010 A8017280

Busbar support, 80mm x 10mm, with seal plate 1 SST-185/A2/8010 A8017281

Busbar support, 100mm x 10mm, with seal plate 1 SST-185/A2/10010 A8017282

Busbar support fixing kit Std.P Type Article No.

Fixing plate kit (2 pcs) 1 BP1/SST A8017286

Fixing bracket for RITTAL cabinet PS4015 1 BW1/SST A8017315

Busbar cover, type of protection IP20 Std.P Type Article No.

Fastening rail kit (2x1850mm) 1 BS1/SST A8017285

Cable compartment cover, height of module 150mm 1 KA/SSA-185 A8017284

Busbar cover, height of module 150mm 1 SSA-185 A8017283

Busbar disconnection kit, for inserting in SST185/10010 Std.P Type Article No.

Bus disconnecting element, 60mm x 10mm 1 STE60/SST A8017309

Bus disconnecting element, 80mm x 10mm 1 STE80/SST A8017310

Bus disconnecting element, 100mm x 10mm 1 STE100/SST A8017311

Strip guide, kit for fitting a SASIL strip Std.P Type Article No.

Sizes 00-50 / height of module 50mm (2 pieces) 1 LF01/SASIL00-50 A8500300

Size 1 / height of module 75mm (2 pieces) 1 LF01/SASIL1 A8600066

Sizes 2-3 / height of module 150mm (2 pieces) 1 LF01/SASIL2-3 A8700074

1-29

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 31: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Cable separator, kit for separating cable compartment of cabi-net

Std.P Type Article No.

Sizes 00-50 (3 pieces) 1 KSH/SASIL00-50 A8500308

Size 1 (3 pieces) 1 KSH/SASIL1 A8600139

Sizes 2-3 with mounting frame (3 pieces) 1 KSH/SASIL2-3 A8700140

Socket connector, customer control circuit terminal Std.P Type Article No.

Socket connector, 16-pole 1 BL/SASIL00-3 A8016141

Closing lock-out, retrofittable in strip guide Std.P Type Article No.

Sizes 00-50 / height of module 50mm 1 ESS/SASIL00-50 A8517305

Size 1 / height of module 75mm 1 ESS/SASIL1 A8617306

Sizes 2-3 / height of module 150mm 1 ESS/SASIL2-3 A8717307

Drawing tool, for drawing out SASIL strips Std.P Type Article No.

Drawing tool 1 AW/SASIL00-3 A8000005

Reserve panel cover, transparent Std.P Type Article No.

Sizes 00-50 / height of module 50mm 1 LFA-D3/SASIL00-50 A8500313

Size 1 / height of module 75mm 1 LFA-D3/SASIL1 A8600142

Sizes 2-3 / height of module 150mm 1 LFA-D3/SASIL2-3 A8700143

Reserve panel covers, transparent, w. ventilation elmnts, IP30 Std.P Type Article No.

Size 1 / height of module 75mm, horizontal fitting 1 LFALH/SASIL1 A8600258

Sizes 2-3 / height of module 150mm, horizontal fitting 1 LFALH/SASIL2-3 A8700260

Size 1 / height of module 75mm, vertical fitting 1 LFALV/SASIL1 A8600259

Sizes 2-3 / height of module 150mm, vertical fitting 1 LFALV/SASIL2-3 A8700261

Reserve panel cover, sheet steel Std.P Type Article No.

Height of module 50mm, RAL7035 1 LFA050/25 A8500003

Height of module 75mm, RAL7035 1 LFA075/25 A8600005

Height of module 150mm, RAL7035 1 LFA150/25 A8700001

Height of module 300mm, RAL7035 1 LFA300/25 A8900002

Height of module 50mm, RAL7032 1 LFA050/25/7032 A8500030

Height of module 75mm, RAL7032 1 LFA075/25/7032 A8600032

Height of module 150mm, RAL7032 1 LFA150/25/7032 A8700037

Height of module 300mm, RAL7032 1 LFA300/25/7032 A8900036

1-30

Page 32: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Reserve panel cover, sheet steel, ventilation slots, IP30 Std.P Type Article No.

Height of module 50mm, RAL7035 1 LFA050L/25 A8500004

Height of module 75mm, RAL7035 1 LFA075L/25 A8600006

Height of module 150mm, RAL7035 1 LFA150L/25 A8700005

Height of module 300mm, RAL7035 1 LFA300L/25 A8900003

Height of module 50mm, RAL7032 1 LFA050L/25/7032 A8500031

Height of module 75mm, RAL7032 1 LFA075L/25/7032 A8600033

Height of module 150mm, RAL7032 1 LFA150L/25/7032 A8700035

Height of module 300mm, RAL7032 1 LFA300L/25/7032 A8900037

Strip cover with operating handle Std.P Type Article No.

Sizes 00-50 / height of module 50mm 1 LD/SASIL00-50/D3 A8500148

Size 1 / height of module 75mm 1 LD/SASIL1/D3 A8100270

Size 2 / height of module 150mm 1 LD/SASIL2/D3 A8200149

Size 3 / height of module 150mm 1 LD/SASIL3/D3 A8300271

Strip cover with operating handle for double strip Std.P Type Article No.

Size 00-50/height of module 100mm 1 LD/SASIL00-50D/D3 A8500000

Size 1/height of module 150mm 1 LD/SASIL1D/D3 A8100000

Size 2-3/height of module 300mm 1 LD/SASIL2-3D/D3 A8300000

Fastener for strip cover, kit Std.P Type Article No.

7mm square, for fitting in SASIL00-3 5 V7/SASIL00-3 A8008008

8mm square, for fitting in SASIL00-3 5 V8/SASIL00-3 A8008004

LV HRC fuse-link, low-los, characteristic gL/gG Std.P Type Article No.

Size 3, 630A, 400V, 32W 1 M3GL630/32W N3016949

1-31

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 33: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Current distributioncomponents

Switch-disconnector-fuses (SASIL), LV HRCsystem

SASIL accessories

SASIL device moun-ting system, 185mm

1-32

Product definition

The SASIL device mountingsystem extends the fusecombination system by an-other module. Mountingplates and device mountingmodules, available with orwithout voltage tap andwith various moduleheights ranging from100mm to 600mm, enablelow voltage assemblies tobe expanded as required.

Thus other devices such ascircuit-breakers, motorstarter combinations, mod-ular installation devices etc.can be positioned in thesame switchgear cabinet inwhich SASIL strips are fit-ted, which saves consider-able space in the cabinet.

Applications

The SASIL device mountingsystem is mounted in allcommercially availableswitchgear cabinets inwhich SASIL strips can bemounted. It allows SASILstrips, mounting plates, de-vice mounting modules andsupply modules to bemounted in the sameswitchgear cabinet andwith a common field dis-tributor busbar system. Thisenables a state-of-the-artmodular construction of

low voltage assemblies inaccordance with IEC/EN60439-1.

Product construction

MOUNTING PLATESMounting plates arescrew-fixed at the two rearswitching cabinet profiles.There are closed versionswith aperture for the volt-age tap kit and versionswith system holes (5.3mmdrill holes and 12.5mmspacing).

SUPPLY MODULEThe supply module allowsthe field distributor busbarsystem to be supplied. Theplug-in contacts are de-signed for rated currents upto 630A. Higher supply cur-rents require two or moremodules.

DEVICE MOUNTING MOD-ULEDevice mounting moduleswith integrated mountingplate are available for dif-ferent expansion versions.From a module height of200mm, they can be pro-vided with a voltage tap tothe field distributor busbar.The supplied guides alloweasy contacting of the fielddistributor busbar. Themodules are fixed at thetwo frontal cabinet profiles.

Prepared modules for mod-ular installation devicesand bus-mounting fuse-ele-ments are also available.

DEVICE DOORDoors for mounting platesand device mounting mod-ules are available withmodule heights of 100mmto 600mm. Versions withinspection window are alsoavailable.The doors are fixed at thefrontal left cabinet profileusing the supplied hingesand are locked using a3mm two-way key bit.

TERMINAL COMPARTMENTSEPARATORTerminal compartment sep-arators and flange platesprovide IP20 separation ofthe cabinet device compart-ment from the cable com-partment. Separators mustbe ordered separately withmounting plates, but aresupplied with devicemounting modules. Theyare fixed at the two rightcabinet profiles.

VOLTAGE TAP KITTwo kits for 100A and 630Aare available. The 100A ver-sion can only be mountedwith device mounting mod-ules, while the 630A ver-sion is also available formounting plates.

Page 34: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Mounting plate without hole grid Std.P Type Article No.

Height of module 100mm 1 MP100/SASIL A8030000

Height of module 150mm 1 MP150/SASIL A8030001

Height of module 200mm 1 MP200/SASIL A8030002

Height of module 300mm 1 MP300/SASIL A8030003

Height of module 450mm 1 MP450/SASIL A8030004

Height of module 600mm 1 MP600/SASIL A8030005

Mounting plate with hole grid Std.P Type Article No.

Height of module 100mm 1 MPL100/SASIL A8030006

Height of module 150mm 1 MPL150/SASIL A8030007

Height of module 200mm 1 MPL200/SASIL A8030008

Height of module 300mm 1 MPL300/SASIL A8030009

Height of module 450mm 1 MPL450/SASIL A8030010

Height of module 600mm 1 MPL600/SASIL A8030011

Mounting plate prepared for voltage tap, without hole grid Std.P Type Article No.

Height of module 200mm 1 MP200/E/SASIL A8030100

Height of module 300mm 1 MP300/E/SASIL A8030101

Mounting plate prepared for voltage tap, with hole grid Std.P Type Article No.

Height of module 200mm 1 MPL200/E/SASIL A8030102

Height of module 300mm 1 MPL300/E/SASIL A8030103

Supply module, 630A Std.P Type Article No.

Height of module 100mm 1 EM100/E/SASIL A8030300

Terminal compartment separator w / w/o flange opening Std.P Type Article No.

Height of module 100mm 1 ASG100/SASIL A8030501

Height of module 150mm (1xFP1.. required) 1 ASG150/SASIL A8030502

Height of module 200mm (1xFP2.. required) 1 ASG200/SASIL A8030503

Height of module 300mm (2xFP1.. required) 1 ASG300/SASIL A8030504

Height of module 450mm (3xFP1.. required) 1 ASG450/SASIL A8030505

Height of module 600mm (4xFP1.. required) 1 ASG600/SASIL A8030506

Height of module 100mm, without flange opening 1 ASGG100/SASIL A8030500

Device mounting module without voltage tap Std.P Type Article No.

Height of module 150mm 1 GEM150/SASIL A8030200

1-33

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 35: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Device mounting module prepared for voltage tap Std.P Type Article No.

Height of module 200mm 1 GEM200/SASIL A8030201

Height of module 300mm 1 GEM300/SASIL A8030202

Height of module 450mm 1 GEM450/SASIL A8030203

Height of module 600mm 1 GEM600/SASIL A8030204

Device mounting module for modular installation, withoutvoltage tap

Std.P Type Article No.

Height of module 150mm, 1x18 TE 1 GEM150/RE/SASIL A8030205

Device mounting module for modular installation, withoutvoltage tap, tier spacing 125mm

Std.P Type Article No.

Height of module 200mm, 1x18 TE 1 GEM200/RE/SASIL A8030206

Height of module 300mm, 2x18 TE 1 GEM300/RE/SASIL A8030207

Height of module 450mm, 3x18 TE 1 GEM450/RE/SASIL A8030208

Height of module 600mm, 4x18 TE 1 GEM600/RE/SASIL A8030209

For bus-mounting fuse-bases, with voltage tap, 60mm busbarsystem

Std.P Type Article No.

Height of module 450mm, incl. 60mm busbar system 1 GEM450/RS/SASIL A8030210

Cover plate for modular installation devices, tier spacing150mm

Std.P Type Article No.

Height of module 300mm, 2x18 TE 1 BSAP/300/RE2X150/SASIL A8030810

Height of module 450mm, 3x18 TE 1 BSAP/450/RE-3X150/SASIL A8030811

Height of module 600mm, 4x18 TE 1 BSAP/600/RE-4X150/SASIL A8030812

Door without inspection window, D3 fastener Std.P Type Article No.

Height of module 100mm, RAL7035 1 T100/D3/SASIL A8030400

Height of module 150mm, RAL7035 1 T150/D3/SASIL A8030401

Height of module 200mm, RAL7035 1 T200/D3/SASIL A8030402

Height of module 300mm, RAL7035 1 T300/D3/SASIL A8030403

Height of module 450mm, RAL7035 1 T450/D3/SASIL A8030404

Height of module 600mm, RAL7035 1 T600/D3/SASIL A8030405

Height of module 100mm, RAL7032 1 T100/D3/SASIL/7032 A8030411

Height of module 150mm, RAL7032 1 T150/D3/SASIL/7032 A8030412

Height of module 200mm, RAL7032 1 T200/D3/SASIL/7032 A8030413

Height of module 300mm, RAL7032 1 T300/D3/SASIL/7032 A8030414

Height of module 450mm, RAL7032 1 T450/D3/SASIL/7032 A8030415

Height of module 600mm, RAL7032 1 T600/D3/SASIL/7032 A8030416

1-34

Page 36: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

Door with inspection window, D3 fastener Std.P Type Article No.

Height of module 150mm, RAL7035 1 TS150/D3/SASIL A8030406

Height of module 200mm, RAL7035 1 TS200D3/SASIL A8030407

Height of module 300mm, RAL7035 1 TS300/D3/SASIL A8030408

Height of module 450mm, RAL7035 1 TS450/D3/SASIL A8030409

Height of module 600mm, RAL7035 1 TS600/D3/SASIL A8030410

Height of module 150mm, RAL7032 1 TS150/D3/SASIL/7032 A8030417

Height of module 200mm, RAL7032 1 TS200/D3/SASIL/7032 A8030418

Height of module 300mm, RAL7032 1 TS300/D3/SASIL/7032 A8030419

Height of module 450mm, RAL7032 1 TS450/D3/SASIL/7032 A8030420

Height of module 600mm, RAL7032 1 TS600/D3/SASIL/7032 A8030421

Flange plate, closed Std.P Type Article No.

Height of module 150mm 1 FP1/SASIL A8030600

Height of module 200mm (for ASG200) 1 FP2/SASIL A8030601

Flange plate for cable covers KSH/SASIL1 Std.P Type Article No.

Height of module 150mm 1 FP1/KSH/SASIL A8030602

Height of module 200mm (for ASG200) 1 FP2/KSH/SASIL A8030603

Voltage tap kit, 100A Std.P Type Article No.

For device mounting module (25mm² cable), M6 1 BSE/100A/SASIL A8030701

Voltage tap kit, 630A Std.P Type Article No.

For mounting plates and device mounting module, M10 1 BSE/630A/SASIL A8030700

1-35

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Page 37: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-36

Type SASIL 185mmType key for SASIL strips

Type of operation

Size

Design

Number of poles

CTs

Accuracy class rating of the CTs to VDE 0414

Order exampleSASIL strip, size 2

1

2

3

4

5

6

*MOT

00-5012

2N3

3NA1BXB1B2B4B6

*DK

*-2

*1W3W6W

1WZ3WZ6WZ

*V

VB

Manual operationMotor operation, DC24V

DIN LV HRC size 00 Utilization category: 400V/AC23 500V/AC23 690V/AC23DIN LV HRC size 1 Utilization category: 400V/AC23 500V/AC23 690V/AC23DIN LV HRC size 2 Utilization category: 400V/AC23 500V/AC23 690V/AC23DIN LV HRC size 2 Utilization category: 400V/AC23 500V/AC22 690V/AC22DIN LV HRC size 3 Utilization category: 400V/AC23 500V/AC23 690V/AC23DIN LV HRC size 3 Utilization category: 400V/AC23 500V/AC22 690V/AC22BS88, size A1/20A (63A), module height 50 mmBS88, size non-standard/125A, module height 50 mmBS88, size B1/100A, module height 75 mmBS88, size B2/200A, module height 75 mmBS88, size B4/400A, module height 150 mmBS88, size non-standard/630A, module height 150 mm

StripDouble strip, 2 strips w. a common manually-op. mech.Coupling strip for coupling of two field distributor busbar systems (for DIN LV HRC size 3)

3-pole2-pole

Without transformers fitted in the strip1 transformer, fitted in strip to phase L1, feeding through field distribution busbars3 transformers, fitted in strip, feeding through field distribution busbars6 transformers, fitted in double strip, feeding through field distribution busbars1 current transformer, built-in strip on phase L1, feeding through cable terminal3 current transformers, built-in strip, feeding through cable terminal6 current transformers, built-in strip, feeding through cable terminal

Class 1Class 0.5, with certification mark (for transformers from 150A)Class 0.5, with certification mark, individuallycertified (for transformers from 150A)

➤ Strip, manually op., 3-pole➤ Utilization category, AC23V / 690V➤ 3 current-transformers (CT), 250A-1A, class 0.5, with certification mark, individually certified,

wired up on measuring device and push-on terminal strip➤ Ammeter, bimetallic, max. demand indicator / setting time 8 min. ➤ Position indicator, 1 make and 1 break contact➤ Electronic fuse monitor

➤ Please adhere to the order given here

Order example SASIL 2 / 3W VB 250 - 1 MS / SKL / MB8 / SÖ / ES001 2 3 4 5 6 7 8 9 10 11 12 13

Page 38: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-37

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Type SASIL 185mmType key for SASIL strips

* No type ID must be stated for these versions.

Order example SASIL 2 / 3W VB 250 - 1 MS / SKL / MB8 / SÖ / ES001 2 3 4 5 6 7 8 9 10 11 12 13

5075

100125150200250300400500600

15

SM

MS

*SKL

*MD

MB8MB15

*SÖ1S

*ES00EE05

ES05

CT primary current

CT secondary current

CT wiring

Push-on terminal stripfor auxiliary circuits

Measuring device

Auxiliary switch for position indication

Electronic modules

7

8

9

10

11

12

13

50A75A100A125A150A200A250A300A400A500A600A

1A5A

On push-on terminal strip, for external connectionOn measuring device (1 transformer)On measuring device and push-on terminal strip

For strips without device accessories and for internal current measurement and indicationPush-on terminal strip required for 3-pole current measurement, auxiliary switches and electronic modules,and for 1-pole current measurement with external terminal connection

Without measuring deviceMoving iron current meterBimetallic, with slave pointer, setting time 8min. (for transformers from 125A)Bimetallic, with slave pointer, setting time 15min. (for transformers from 125A)

Without position indicator1 make and 1 break1 make (in conjunction with electronic module ES05)

Without electronic modulesElectronic fuse monitorElectronic monitoring module EE for PLMaster energy management system, supply voltage DC24VElectronic fuse monitor, for SASIL-MOT strips, supply voltage DC24V

Page 39: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-38

SASIL...1W...M/SKL/M.../SÖ/ES00

Ordering details see pages 1-7; 1-11

Q1 Lastrennschalter mit Sicherung / NH vertical switch-disconnector-fuseQ1-S1 Hilfsschalter Schaltstellungsanzeige / Auxillary switchF1, F2, F3 Sicherungen / FusesF4 Sicherungsüberwachung ES00 / Electronic fuse monitor ES00V1-V3 Störmeldungsanzeige F1-F3 Sicherungsüberwachung / Phase-related LED fault indicator F1-F3V4 Bereitschaftsanzeige Sicherungsüberwachung / Ready signal-fuse monitoringX1 Steckerleiste / Connection stripT1 Stromwandler / Current transformerP1 Strommesser / Ammeter

3/N/PE 50Hz AC380-690VL1L2L3(N)PE(N)

Darstellung im ausgeschalteten Zustand /Off-state view

Einspeisung /Incoming unit

AP1T1

Q1

F1 F2 F3

L1 L2 L3Abgang / Outgoing unit

V4 V1 V2 V3

Q1-S1

F4

X1

2

1

4

3

6

5

1615

97

810

1311

1214

Sicherungsüberwachung ES00(Arbeitsstromprinzip) /Electronic fuse monitor ES00(in working current concept)

Schaltstellunganzeige /Indicator for switchoperating position

Schließer /Normallyopencontact

Öffner(bei StörungKontaktgeöffnet) /Contact breakes(on operationfault)

Öffner /Normallyclosedcontact

Schließer(bei StörungKontaktgeschlossen) /Contact makes (on operation fault)

Q1 Lastrennschalter mit Sicherung / NH vertical switch-disconnector-fuseQ1-S1 Hilfsschalter Schaltstellungsanzeige / Auxillary switchF1, F2, F3 Sicherungen / FusesF4 Sicherungsüberwachung ES00 / Electronic fuse monitor ES00V1-V3 Störmeldungsanzeige F1-F3 Sicherungsüberwachung / Phase-related LED fault indicator F1-F3V4 Bereitschaftsanzeige Sicherungsüberwachung / Ready signal-fuse monitoringX1 Steckerleiste / Connection stripT1, T2, T3 Stromwandler / Current transformerP1 Strommesser / Ammeter

3/N/PE 50Hz AC380-690VL1L2L3(N)PE(N)

Darstellung im ausgeschalteten Zustand /Off-state view

Einspeisung /Incoming unit

AP1T1

Q1

F1 F2 F3

L1 L2 L3Abgang / Outgoing unit

V4 V1 V2 V3

Q1-S1

F4

X1

2

1

4

3

6

5

1516

97

810

1311

1214

Sicherungsüberwachung ES00(Arbeitsstromprinzip) /Electronic fuse monitor ES00(in working current concept)

Schaltstellunganzeige /Indicator for switchoperating position

Schließer /Normallyopencontact

Öffner(bei StörungKontaktgeöffnet) /Contact breakes(on operationfault)

Öffner /Normallyclosedcontact

Schließer(bei StörungKontaktgeschlossen) /Contact makes (on operation fault)

T2

T3 Option

S1

S1

S1

S2

S2

S2

SASIL...3W...MS/SKL/M.../SÖ/ES00

Ordering details see pages 1-13; 1-15

Page 40: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-39

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

SASIL...3W...-1..../SKL/M.../SÖ/EE05

Ordering details see page 1-17

Q1 Lastrennschalter mit Sicherung / NH vertical switch-disconnector-fuseQ1-S1 Hilfsschalter Schaltstellungsanzeige / Auxillary switchQ1-S2 Hilfsschalter Schaltstellungsanzeige / Auxillary SwitchQ1-S3 Hilfsschalter für EE-Modul / Auxillary SwitchF1, F2, F3 Sicherungen / FusesF4 Maßwertaufnehmer Sicherungsüber- wachung EE05 / Reading recorder with fuse monitor EE05X1 Steckerleiste / Connection stripV1 LED / Anzeigeneinheit / LED / Display unitT1, T2, T3 Stromwandler / Current transformerP7 Stromwandler / Current transformer

3/N/PE 50Hz 400V-690VL1L2L3NPE

Darstellung im ausgeschalteten Zustand / Off state viewEinspeisung /Incoming unit

T1

F1 F2 F3

L1 L2 L3Abgang / Outgoing unit

Q1-S1

F4

X1

Öffner(bei Störung Kontakt geöffnet) /Contact breakes(on operation fault)

146

10

+ -24V DC

Q1-S3

EE05

V1

T2

T3

1

3

4

5

GND

Data A

Data B

EMD-Bus

COM

7

8

9

Schließer(bei Störung Kontakt geschlossen) /Contact makes(on operation fault)

Option

Option

213

111516

Q1-S2

P7

Q1

Q1 Lastrennschalter mit Sicherung / NH vertical switch-disconnector-fuseQ1-S1 Hilfsschalter Schaltstellungsanzeige / Auxillary switchF1, F2, F3 Sicherungen / FusesF4 Sicherungsüberwachung ES05 / Electronic fuse monitor ES05F5 Motorsteuerungselektronik Electronic motor controlsV1 Störmeldungsanzeige Sicherungsüberwachung / Phase-related LED fault indicator V2 Betriebszustandanzeige der Leiste / Operating status indicator of SASILX1 Steckerleiste / Connection stripT1 Stromwandler / Current transformer

3/N/PE 50Hz AC 400V-690VL1L2L3(N)PE Darstellung im ausgeschalteten Zustand /

Off-state viewEinspeisung /Incoming unit

T1

F5

F1 F2 F3

L1 L2 L3 Abgang / Outgoing unit

Q1-S1

F4

X1

2

1

14131211

7

S1

S2

1 pol.Wandler-messung /Single poleCT-metering

externeMotoran-steuerungDC 24V /External motorcontrol unit

Störmelde-relais /fault statussignal relay

Schließer /Normallyoprencontact

Öffner /Normallyclosedcontact

Schaltstellungsanzeige /Indicator for switch operating position

Fremdversorgung/PE /Externalpower supply

Öffner(bei StörungKontaktgeöffnet) /Contact breakes(on operation fault)Schließer(bei Störung Kontakt geschlossen) /Contact makes(on operation fault)COM

EIN / on

AUS / off

N

+24V

GND+24V

(AC 400V-690V)

8

9

35

64

151610

+- DC 24V

PE

Q1-S3

ES05

V1

off

on

V2

SASIL-MOT.../1W...S/SKL/SÖ/ES05

Ordering details see page 1-19

Page 41: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-40

SASIL-MOT...3W...-1/SKL/1S/EE05

Ordering details see page 1-19

Q1 Lastrennschalter mit Sicherung / NH vertical switch-disconnector-fuseQ1-S1 Hilfsschalter Schaltstellungsanzeige / Auxillary switchQ1-S2 Hilfsschalter für EE-Modul / Auxillary SwitchF1, F2, F3 Sicherungen / FusesF4 Maßwertaufnehmer Sicherungsüber- wachung EE05 / Reading recorder with fuse monitor EE05F5 Motorsteuerungselektronik Electronic motor controlsV1 Störmeldungsanzeige Sicherungsüberwachung / Phase-related LED fault indicator V2 Betriebszustandanzeige der Leiste / Operating status indicator of SASILX1 Steckerleiste / Connection stripT1, T2, T3 Stromwandler / Current transformer

3/N/PE 50Hz AC 400V-690VL1L2L3(N)PE Darstellung im ausgeschalteten Zustand /

Off-state viewEinspeisung /Incoming unit

T1

F5

F1 F2 F3

L1 L2 L3 Abgang / Outgoing unit

Q1-S1

F4

X1

14131211

7

externeMotoran-steuerungDC 24V /External motorcontrol unit

Schließer /Normallyopencontact

Schaltstellungsanzeige /Indicator for switch operating position

Fremdversorgung/PE /External power supply

Öffner(bei StörungKontaktgeöffnet) /Contactbreakes(on operation fault)

ON

OFF

N

+24VGND

+24V

(AC 400V-690V)

8

9

2

151610

+- DC 24V

PE

Q1-S2

EE05

V1

off

on

V2

T2

T3

1345

6

GND

Data A

Data BEMD-Bus

Schließer(bei StörungKontaktgeschlossen) /Contact makes(on operation fault)

COMMON

Stör-melde-relais /Faultstatussignalrelay

M

Page 42: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-41

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

SASIL00-50/...

Ordering details see page 1-7

25

X

X

590

10

260 2

30

155

96

136

180

81

75

544

185 1.5

M10

185 1.5

3mm DB

SASIL1...

Ordering details see page 1-7

Page 43: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-42

SASIL2...

Ordering details see page 1-19

25

X

X

590

10

260

230

155

96

145

81

150

542

185 1.5

37.5

185 1.5

3mm DB

M12

25

X

X

590

10

260

230

155

96

145

81

150

542

185 1.5

37.5

185 1.5

3mm DB

M12

SASIL3...

Ordering details see page 1-19

Page 44: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-43

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

SASIL-MOT00-50/SKL/SÖ/ES05

Ordering details see page 1-19

X

X

590

10

230

81

50

542

185 1.5

11.5

185 1.5

3mm DB

M8 72

260

108

145

X

X

590

10

230

81

75

544

185 1.5

M10

185 1.5

3mm DB

96

260

135

180

SASIL-MOT1/SKL/SÖ/ES05

Ordering details see page 1-19

Page 45: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-44

SASIL-MOT2/SKL/SÖ/ES05

Ordering details see page 1-19

X

X

590

10

230

81

150

542

185 1.5

M12

185 1.5

3mm DB

96

260

145

37.5

150

260

230

80.5

37.5185 1.5

590

M12

3mm DB

X

10

X

96

145

185 1.5

SASIL-MOT3/SKL/SÖ/ES05

Ordering details see page 1-19

Page 46: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-45

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

SASIL3K

Ordering details see page 1-21

150

260

155

230

25

77

75

185 1.5

590

3mm DB

X

10

X

37.5

185 1.5

590

100

3mm DB

185 1.5

25

260

189

230

72

108

542

50

11.510

115

185 1.5

X

X

145

M8

SASIL00-50D/SKL/SÖ

Ordering details see page 1-23

Page 47: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-46

SASIL1D/SKL/SÖ...

Ordering details see page 1-23

25

X

X

590

10

260 230

189

96

136

115

150

544

M10

185 1.5

3mm DB

75185 1.5

180

25

X

X

590

10

260 230

189

96

145

115

300

542

M12

185 1.5

3mm DB

37.5185 1.5

150

SASIL2D/SKL/SÖ...

Ordering details see page 1-23

Page 48: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-47

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

SASIL3D/SKL/SÖ...

Ordering details see page 1-24

185 1.5

590

25

260

300

189

230

96

145

542 150

M12

37.5

10

3mm DB

115

185 1.5

X

X

25

X

X

590

10

260 2

30

155

72

145

81

50

542

11.5

M8

370 1.5

3mm DB

SASIL00-50-2

Ordering details see page 1-27

Page 49: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-48

SASIL1-2...

Ordering details see page 1-27

25

X

X

590

10

260 230

155

96

180

81

75

544

M10

370 1.5

3mm DB

25

X

X

590

10

260 230

155

96

145

81

150

542

M12

370 1.5

3mm DB

37.5

SASIL2-2...

Ordering details see page 1-27

Page 50: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-49

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

SASIL3-2...

Ordering details see page 1-27

150

260

155

230

25

77

36.5

370 1.5

590

M12

3mm DB

X

10

X

96

144.5

Page 51: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-50

SSP/SASIL

Ordering details see page 1-29

SST-185/...

Ordering details see page 1-30

2023

11.5

25 24.8

O 5.3 12.5

4x

24.8

25

50

25

12.5

Typ A SST-185/4010 40SST-185/5010 50SST-185/6010 60SST-185/8010 80SST-185/10010 100

A24

185

495

10

185

O6.

5

SW6

10

A 15

185

406

495

185

450

2932

12.5 Typ A

SST-185/A1/4010 40SST-185/A1/5010 50SST-185/A1/6010 60SST-185/A2/8010 80SST-185/A2/10010 100

6.5

50

9

58.5

46.5

34.5

12.5

18.8

6.5

12.5

12.5

12.5

Ordering details see page 1-31 Ordering details see page 1-29

SST-185/A1/... BP1/SST

4

M6

46.5

12.5

40

39

25

36.5

90

6.5

24

19.5

1.51850

12.5 104.3

BW1/SST BS1/SST

Ordering details see page 1-29 Ordering details see page 1-29

48

48

152.7

149.5

25.2

2.2

50

50

64.4

456,5

185

149,5

185

KA/SSA-185 SSA-185

Ordering details see page 1-29 Ordering details see page 1-29

Page 52: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-51

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

STE.../SST

Ordering details see page 1-29

LF01/SASIL00-50

Ordering details see page 1-29

C

61

C-D

Typ A Ma§STE 60/SST A1 60STE 80/SST A2 80STE 100/SST A3 100 123.3

A3

A2

A1

36

31

24

D46

39.5

29.5

25

57.5

49.5 25

234.5

175

M5

25

40 4.8

25

4.8

12.5

14158.5

25

48

50

75

125149.5

40 4.8

25

12.5

234.5

175

4.8

M5

50

125

Ordering details see page 1-29 Ordering details see page 1-29

LF01/SASIL1 LF01/SASIL2-3

200

43

35.5

48

6.5

2006,5

70

63

39

KSH/SASIL00-50 KSH/SASIL1

Ordering details see page 1-29 Ordering details see page 1-29

54.5

205

68

32

6.5

12

37

45

62.5

49.5

37

KSH/SASIL2-3 BL/SASIL00-3

Ordering details see page 1-29 Ordering details see page 1-31

Page 53: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-52

ESS/SASIL00-50

Ordering details see page 1-29

ESS/SASIL1

Ordering details see page 1-29

43

136

22

B

20

62.5

122.5

21.5

113

AA-B

24

118

130 23

25

85

29.5

43

141

51.5

Ordering details see page 1-29 Ordering details see page 1-29

ESS/SASIL2-3 AW/SASIL00-3

3mm DB

25

590

A

Typ ASASIL 00-50 49SASIL 1 74.5SASIL 2-3 149.5

35.7

3mm DB

A

590

25

Typ ASASIL 1 74.5SASIL 2-3 149.5

LFA/... LFALH/...

Ordering details see page 1-29 Ordering details see page 1-29

35.7

3mm DB

A

590

25

Typ ASASIL 1 74.5SASIL 2-3 149.5

590

A

536

Typ A

LFA50/25 50LFA75/25 75LFA150/25 150LFA300/25 300

O7

23

LFALV/... LFA.../25

Ordering details see page 1-30 Ordering details see page 1-30

Page 54: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-53

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

LFA...L/...

Ordering details see page 1-30

LD/SASIL00-50

Ordering details see page 1-30

590

A

536

Typ A

LFA50L/25 50LFA75L/25 75LFA150L/25 150LFA300L/25 300

26.7

23

50

590

56

3mm DB

75

590

56

150

590

56

Ordering details see page 1-30 Ordering details see page 1-30

LD/SASIL1 LD/SASIL...

25

M6

7

16

8

7

25

M6

7

16

8

8

V7/SASIL00-3 V8/SASIL00-3

Ordering details see page 1-30 Ordering details see page 1-30

Typ A B

MP100 98 75

MP150 148 75

MP200 198 125

MP300 298 225

MP450 448 375

MP600 598 525

B

493

540

12.5

A

525

B

493

540

12.5

A

525

Typ A B

MP100 98 75

MP150 148 75

MP200 198 125

MP300 298 225

MP450 448 375

MP600 598 525

MP.../SASIL MPL.../SASIL

Ordering details see page 1-33 Ordering details see page 1-33

Page 55: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-54

MP.../E/SASIL

Ordering details see page 1-33

MPL.../E/SASIL

Ordering details see page 1-33

CC

493

540

12.5

B A

525

Typ A B C

MP200/E 198 125 50

MP300/E 298 225 75

Typ A B C

MPL200/E 198 125 50

MPL300/E 298 225 75

493

540

CC

12.5

B A

525

185

53

75

540

98

185

525

Ordering details see page 1-33 Ordering details see page 1-33

EM100/E/SASIL ASG.../SASIL

Typ A

GEM150 148

GEM200 198

GEM300 298

GEM450 448

GEM600 598

190

A

553

GEM.../SASIL GEM.../RE/SASIL

Ordering details see page 1-34 Ordering details see page 1-34

Typ A GEM150 148 1xZGEM200 198 1xZGEM300 298 2xZGEM450 448 3xZGEM600 598 4xZ

553

190

A

Z

18TE=324mm

553

285

230

448

195

GEM450/RS/SASIL T.../D3/SASIL

Ordering details see page 1-34 Ordering details see page 1-34

Page 56: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-55

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

FP.../SASIL

Ordering details see page 1-35

FP.../KSH/SASIL

Ordering details see page 1-35

Typ A B

FP1 119 110

FP2 169 160

110

119

A B

GEM...

MIN

.50

185 185

10

MIN

.50

Ordering details see page 1-35 Ordering details see page 1-35

BSE/100A/SASIL BSE/630A/SASIL

MPL...GEM...

54.4

185

m.50

m.50

185

10M10

Page 57: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-56

Type SASIL 00 - 50 - 2 SASIL 1- 2Technical data for switch-disconnector-fuse (SASIL), NH fuse system (in accordance with IEC/EN 60947-3 and VDE 0660 Part 107)

Electricalcharacteristics

Fuse-links

Mechanicalcharacteristics

Cableconnection

Type ofprotection

Operatingconditions

1)Without packaging 2)35°C normal temperature, at 55°C with reduced operating current 3)Upright busbar4)Cable connection right5)Cable connection bottom6)maximum cable-lug width 24mm

Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff

Rated short-time withstand current (1 sec) Icw kAeff

Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W

Size to DIN 43 620 - -Max. rated current (gL/gG) IN AMax. permis. power loss per fuse-link Pv W

Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness 3) - mm

Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2

Flat bar - mmTightening torque Ma Nm

Terminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma Nm

Front side Operational state - -Device fitted Front cover open - -

Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -

DC220 DC440 DC220 DC440160 100 250 200160 100 250 200

- - - -- - - -

AC 1000 AC 100025 25 25 25- - - -

DC-22B DC-21B DC-22B DC-21B640 150 1000 375640 150 1000 375

8 8 8 8300 300 150 15032 13 44 44

00 1160 100 250 200

12 23

1700 10004,5 6,75370 37010 10

M8 M101x10 - 956) 1 x25 -150; 2x25 -70

24x5 30x1010 15- -

- -

- -

- -

IP40 IP40IP20 IP20

- 25 bis + 55 - 25 bis + 55Continuous operation Continuous operation

Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)

Up to 2000 Up to 20003 3III III

Page 58: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-57

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Type SASIL 2 - 2 SASIL 3 - 2Technical data for switch-disconnector-fuse (SASIL), NH fuse system (in accordance with IEC/EN 60947-3 and VDE 0660 Part 107)

Electricalcharacteristics

Fuse-links

Mechanicalcharacteristics

Cableconnection

Type ofprotection

Operatingconditions

1)Without packaging 2)35°C normal temperature, at 55°C with reduced operating current 3)Upright busbar4)Cable connection right5)Cable connection bottom

Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff

Rated short-time withstand current (1 sec) Icw kAeff

Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W

Size to DIN 43 620 - -Max. rated current (gL/gG) IN AMax. permis. power loss per fuse-link Pv W

Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness 3) - mm

Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2

Flat bar - mmTightening torque Ma Nm

Terminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma Nm

Front side Operational state - -Device fitted Front cover open - -

Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -

DC220 DC440 DC220 DC440400 400 630 630400 400 630 630

- - - -- - - -

AC 1000 AC 100025 25 25 25- - - -

DC-22B DC-21B DC-22B DC-21B1600 600 2520 9451600 600 2520 945

8 8 8 8200 200 200 20084 84 180 180

2 3400 400 630 630

34 48

1000 100012.4 12.9370 37010 10

M12 M121x35 -300; 2x35 -240 1 x35 -300; 2x35 -240

40x10 40x1030 30- -

- -

- -

- -

IP40 IP40IP20 IP20

- 25 bis +55 - 25 bis +55Continuous operation Continuous operation

Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)

Up to 2000 Up to 20003 3III III

Page 59: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-58

SASIL 1SASIL 00-50Type

Technical data for switch-disconnector-fuse (SASIL), NH fuse system (in accordance with IEC/EN 60947-3 and VDE 0660 Part 107)

Electricalcharacteristics

Fuse-links

Mechanicalcharacteristics

Cableconnection

Type ofprotection

Operatingconditions

1)Without packaging 2)35°C normal temperature, at 55°C with reduced operating current 3)Upright busbar4)Cable connection right5)Cable connection bottom6)maximum cable-lug width 24mm

Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff

Rated short-time withstand current (1 sec) Icw kAeff

Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse with stand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W

Size to DIN 43 620 - -Max. rated current (gL/gG) IN AMax. permis. power loss per fuse-link Pv W

Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness 3) - mm

Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2

Flat bar - mmTightening torque Ma Nm

Terminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma Nm

Front side Operational state - -Device fitted Front cover open - -

Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -

AC500 AC690 DC220 DC440 AC500 AC690 DC220 DC440160 100 160 100 250 200 250 200160 100 160 100 250 200 250 200

- - - - - - - -40-60 40-60 - - 40-60 40-60 - -

AC 1000 AC 100050 80 25 25 50 50 25 25- - - - - - - -

AC-23B AC-23B DC-22B DC-21B AC-23B AC-23B DC-22B DC-21B1600 1000 640 150 2000 1600 1000 3751280 800 640 150 1500 1200 1000 375

8 8 8 8 8 8 8 8300 300 300 300 150 150 150 15048 19 32 13 66 45 44 44

00 1160 100 160 100 250 200 250 200

12 23

1700 10004.75 8.1185 18510 10

M8 M101 x 10 - 956) 1 x 25 - 150; 2 x 25 - 70

24 x 5 30 x 1010 15- -

- -

- -

- -

IP40 IP40IP20 IP20

-25 bis + 55 -25 bis + 55Continuous operation Continuous operation

Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)

Up to 2000 Up to 20003 3III III

Page 60: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-59

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

SASIL 1SASIL 00-50TypTechnical data for switch-disconnector-fuse (SASIL), NH fuse system (in accordance with IEC/EN 60947-3 and VDE 0660 Part 107)

Type SASIL 2 SASIL 2N

1)Without packaging 2)35°C normal temperature, at 55°C with reduced operating current 3)Upright busbar4)Cable connection right5)Cable connection bottom

AC500 AC690 DC220 DC440 AC400 AC500 AC690400 315 400 315 400 400 315400 315 400 315 400 400 315

- - - - - - -40-60 40-60 - - 40-60 40-60 40-60

AC 1000 AC 100080 80 25 25 50 50 50- - - - - - -

AC-23B AC-23B DC-22B DC-21B AC-23B AC-22B AC-22B3200 2520 1600 600 3200 1200 9452400 1890 1600 600 2400 1200 945

8 8 8 8 8 8 8200 200 200 200 200 200 200126 81 84 84 120 120 75

2 2400 315 400 315 400 400 315

34 34

1000 80015.5 15.5185 18510 10

M12 M121x35 -300; 2 x 35 - 240 1 x 35 - 300; 2 x 35 - 240

40 x 10 40 x 1030 30- -

- -

- -

- -

IP40 IP40IP20 IP20

-25 bis +55 -25 bis +55Continuous operation Continuous operation

Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)

Up to 2000 Up to 20003 3III III

Electricalcharacteristics

Fuse-links

Mechanicalcharacteristics

Cableconnection

Type ofprotection

Operatingconditions

Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff

Rated short-time withstand current (1 sec) Icw kAeff

Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W

Size to DIN 43 620 - -Max. rated current (gL/gG) IN AMax. permis. power loss per fuse-link Pv W

Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness 3) - mm

Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2

Flat bar - mmTightening torque Ma Nm

Terminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma Nm

Front side Operational state - -Device fitted Front cover open - -

Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -

Page 61: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-60

SASIL 00-50TypType SASIL 3 SASIL 3N

Technical data for switch-disconnector-fuse (SASIL), NH fuse system (in accordance with IEC/EN 60947-3 and VDE 0660 Part 107)

1)Without packaging 2)35°C normal temperature, at 55°C with reduced operating current 3)Upright busbar4)Cable connection right5)Cable connection bottom

AC500 AC690 DC220 DC440 AC400 AC500 AC690630 500 630 630 630 630 500630 500 630 630 630 630 500

- - - - - - -40-60 40-60 - - 40-60 40-60 40-60

AC 1000 AC 100050 80 25 25 50 50 50- - - - - - -

AC-23B AC-23B DC-22B DC-21B AC-23B AC-22B AC-22B5040 4000 2520 945 6300 1890 15003780 3000 2520 945 5040 1890 1500

8 8 8 8 8 8 8200 200 200 200 200 200 200270 195 180 180 260 260 185

3 3630 500 630 630 630 630 500

48 48

1000 80016.5 16.5185 18510 10

M12 M121 x 35 - 300; 2 x 35 - 240 1 x 35 - 300; 2 x 35 - 240

40 x 10 40 x 1030 30- -

- -

- -

- -

IP40 IP40IP20 IP20

-25 bis +55 -25 bis +55Continuous operation Continuous operation

Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)

Up to 2000 Up to 20003 3III III

Electricalcharacteristics

Fuse-links

Mechanicalcharacteristics

Cableconnection

Type ofprotection

Operatingconditions

Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff

Rated short-time withstand current (1 sec) Icw kAeff

Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W

Size to DIN 43 620 - -Max. rated current (gL/gG) IN AMax. permis. power loss per fuse-link Pv W

Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness 3) - mm

Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2

Flat bar - mmTightening torque Ma Nm

Terminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma Nm

Front side Operational state - -Device fitted Front cover open - -

Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -

Page 62: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-61

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

SASIL 1SASIL 00-50TypTechnical data for switch-disconnector-fuse (SASIL), NH fuse system (in accordance with IEC/EN 60947-3 and VDE 0660 Part 107)

Electricalcharacteristics

Fuse-links

Mechanicalcharacteristics

Cableconnection

Type ofprotection

Operatingconditions

Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff

Rated short-time withstand current (1 sec) Icw kAeff

Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv WCurrent input - ACurrent input during switching operation - A Control voltage - V Max. switching time - sControl pulse for switching operation - -

Size to DIN 43 620 - -Max. rated current (gL/gG) IN AMax. permis. power loss per fuse-link Pv W

Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness 3) - mm

Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2

Flat bar - mmTightening torque Ma Nm

Terminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma Nm

Front side Operational state - -Device fitted Front cover open - -

Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -

AC500 AC690 DC220 DC440 AC500 AC690 DC220 DC440160 100 160 100 250 200 250 250160 100 160 100 250 200 250 250

- - - - - - - -40-60 40-60 - - 40-60 40-60 - -

AC 1000 AC 100050 80 25 25 50 50 25 25- - - - - - - -

AC-23B AC-23B DC-22B DC-21B AC-23B AC-23B DC-22B DC-21B1600 1000 640 150 2000 1600 1000 3751280 800 640 150 1500 1200 1000 375

8 8 8 8 8 8 8 8300 300 300 300 150 150 150 15048 19 32 13 66 45 44 44

0.250.8

DC24V5

DC24V continuous or impulse >300ms

00 1160 100 160 100 250 200 250 250

12 23

1700 10007.2 9.5185 18510 10

M8 M101 x 10 - 95 6) 1 x 25 - 150; 2 x 25 - 70

24 x 5 30 x 1010 15- -

- -

- -

- -

IP40 IP40IP20 IP20

-25 bis +55 -25 bis +55Continuous operation Continuous operation

Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)

Up to 2000 Up to 20003 3III III

Type SASIL-MOT 00-50 SASIL-MOT 1

1)Without packaging 2)35°C normal temperature, at 55°C with reduced operating current 3)Upright busbar4)Cable connection right5)Cable connection bottom6)maximum cable-lug width 24mm

Page 63: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-62

Technical data for switch-disconnector-fuse (SASIL), NH fuse system (in accordance with IEC/EN 60947-3 and VDE 0660 Part 107)

Electricalcharacteristics

Fuse-links

Mechanicalcharacteristics

Cableconnection

Type ofprotection

Operatingconditions

Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff

Rated short-time withstand current (1 sec) Icw kAeff

Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv WCurrent input - ACurrent input during switching operation - A Control voltage - V Max. switching time - sControl pulse for switching operation - -

Size to DIN 43 620 - -Max. rated current (gL/gG) IN AMax. permis. power loss per fuse-link Pv W

Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness 3) - mm

Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2

Flat bar - mmTightening torque Ma Nm

Terminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma NmTerminal Clamping cross-section - mm2

Tightening torque Ma Nm

Front side Operational state - -Device fitted Front cover open - -

Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -

AC500 AC690 DC220 DC440 AC500 AC690 DC220 DC440400 315 400 400 630 500 630 630400 315 400 400 630 500 630 630

- - - - - - - -40-60 40-60 - - 40-60 40-60 - -

AC 1000 AC 100080 80 25 25 50 80 25 25- - - - - - - -

AC-23B AC-23B DC-22B DC-21B AC-23B AC-23B DC-22B DC-21B3200 2520 1600 600 5040 4000 2520 9452400 1890 1600 600 1780 3000 2520 945

8 8 8 8 8 8 8 8200 200 200 200 200 200 200 200126 81 84 84 270 195 180 180

0.250.8

DC24V5

DC24V continuous or impulse >300ms

2 3400 315 400 400 630 500 630 630

34 48

1000 100016.6 17.5185 18510 10

M12 M121 x 135 - 300; 2 x 35 - 240 1 x 35 - 300; 2 x 35 - 240

40 x 10 40 x 1030 30- -

- -

- -

- -

IP40 IP40IP20 IP20

-25 bis + 55 -25 bis + 55Continuous operation Continuous operation

Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)

Up to 2000 Up to 20003 3III III

Type SASIL-MOT 2 SASIL-MOT 3

1)Without packaging 2)35°C normal temperature, at 55°C with reduced operating current 3)Upright busbar4)Cable connection right5)Cable connection bottom

Page 64: Switch-disconnector-fuse (SASIL) NH fuse system...2 CT L1 (S1) 3 CT L2 (S2) 4 CT L2 (S1) 5 CT L3 (S2) 6 CT L3 (S1) 7 ESOO-norm. open contact 8 ESOO-norm. open contact 9 ESOO-norm

1-63

Switch-dis-

connector-fuses

(SASIL) LV HRC

system

Switch-

disconnector

fuses (SASIL)

BS system

Switch-

disconnector(SALIT)

LV

HRC strip-

fuseways

LV HRC

strip-type

fuse switch-

disconnectors

LV HRCfuse-

bases

LV HRC

fuse switch-

disconnectors

C|O|S|M|O®-

60mm Busbar

System

Current

transformers

Consumer

supply technology

Distribution

and instrument

cabinets

Powerlizer

system electronics

Switch-disconnec-

tor-fuses (SASIT)

DIN and BS

systems

Terminals

Appendix

Busbar rated short time withstand current ICW [kAeff]Support spacing

300mm 450mm 600mm 750mm

Type Busbar cross-section[mm x mm]

Busbar current carrying capacity

[A]1) [A]2)

Technical data for busbar supports; Rated short time withstand-current ICW [kAeff] and ID [A] of busbar

SST-185/4010SST-185/5010SST-185/6010SST-185/8010SST-185/10010

40 x 1050 x 1060 x 1080 x 10

100 x 10

1)Continuous current in accordance with DIN 43 670 for indoor use on 35°C of air temperature and 65°C of busbar temperature 2)Continuous current in accordance with DIN 43 670 for indoor use on 55°C of air temperature inside the switchgear cabinet and 105°C of busbar temperature

correction value for other cabinet inside temperature please see appendix

715852985

12401490

9001070123615561870

808080

100100

65658080

100

5050656580

3535405065

CT ratio Class 1 Class 0.5 CT ratio Class 1 Class 0.5Technical data for current transformer (CT) integrated in SASIL

50A - 1A75A - 1A

100A - 1A125A - 1A150A - 1A200A - 1A250A - 1A300A - 1A400A - 1A500A - 1A600A - 1A

Ammeter type Ratio Power consumption [VA] Class according to DIN 43 780Technical data for ammeter integrated in SASIL

Moving iron meterMoving iron meterBimetal meterBimetal meter

N/1AN/5AN/1AN/5A

0.30.50.91.6

1.51.51.51.5

50A - 5A75A - 5A

100A - 5A125A - 5A150A - 5A200A - 5A250A - 5A300A - 5A400A - 5A500A - 5A600A - 5A

0.6VA (Kl.3)0.5VA1.0VA2.0VA2.5VA3.0VA5.0VA

3.75VA5.0VA5.0VA5.0VA

----

1.5VA2.5VA2.5VA2.5VA2.5VA2.5VA2.5VA

----

1.5VA2.5VA2.5VA2.5VA2.5VA2.5VA2.5VA

0.6VA1.0VA1.5VA2.0VA2.5VA

3.75VA5.0VA

3.75VA5.0VA5.0VA5.0VA

Switch type Rated operating current Rated switching capacityTechnical data for auxiliary switch integrated in SASIL

AC250VAC400V

4A3A

10A16A

ParameterTechnical data for fuse monitor integrated in SASIL

Rated operating voltagePower consumption max.Rated frequencyInternal resistanceResponse thresholdResponse timeRated switching capacity AC 24VRated switching capacity AC 230VRated switching capacity DC 24VRated switching capacity DC 220VWorking of relayImpulse voltage 1.2/50µs according to IEC 61000-4-5Transient interference/Burst according to IEC 61000-4-4Display-operating conditionDisplay-fault condition

Ue

Pv

-

Ri

Uo

t

UL-L

UL-L

VVAHz

MV

ms

kVkV

AC400 to AC6901.5

50-60>2>5

>500AC15: 4AAC15: 3ADC13: 1A

DC13: 0.5AWorking current

62

1 LED green3 LED red