NEHA KARDAM (11/PPS/010) FARHEEN KHAN (11/PPS/005) SURGE DIVERTER

surge diverters

Embed Size (px)

DESCRIPTION

surge diverters

Citation preview

Page 1: surge diverters

NEHA KARDAM(11/PPS/010)

FARHEEN KHAN (11/PPS/005)

SURGE DIVERTER

Page 2: surge diverters

WHAT IS SURGE ? Surges, or transients, are brief

overvoltage spikes or disturbances on a power waveform that can damage, degrade, or destroy electronic equipment within any home, commercial building, or manufacturing facility.

Transients can reach amplitudes of tens of thousands of volts.

Surges are measured in microseconds.

Page 3: surge diverters

SURGE DIVERTERS A surge diverter is a piece of equipment that

diverts excess voltages (caused by spikes in the electrical supply) to earth, thus protecting sensitive electrical and electronic equipment.

The surge diverter is normally installed in the main switchboard.

The surge diverter ‘shunts’ voltages over 260 volts AC to ground, stopping most power spikes from causing any damage.

 

Page 4: surge diverters

PRACTICAL SURGE DIVERTER :

Page 5: surge diverters

REQUIREMENT OF SURGE DIVERTER : It should not pass any current at normal and

abnormal power frequency voltage.

It should breakdown as quickly as possible after the abnormal high frequency voltage arrives.

It should not only protect the equipment for which it is used but should discharge current without damaging itself.

It should interrupt power frequency follow current after the surge is discharge to ground.

Page 6: surge diverters

TYPES OF SURGE DIVERTERS Rod gap

Protector tube or expulsion type surge diverter

Valve type surge diverter

Page 7: surge diverters

ROD GAP : It is a very simple type of diverter and

consists of two 1.5 cm rods, which are bent at right angles with a gap in between.

One rod is connected to the line circuit and the other rod is connected to earth.

The distance between gap and insulator must not be less than one third of the gap length so that the arc may not reach the insulator and damage it.

The rod gap should be so set that it breaks down to a voltage not less than 30% below the voltage withstand level of the equipment to be protected.

Page 8: surge diverters

The string of insulators for an overhead line on the bushing of transformer has frequently a rod gap across it.

Under normal operating conditions, the gap remains non-conducting.

On the occurrence of a high voltage surge on the line, the gap sparks over and the surge current is conducted to earth.

In this way excess charge on the line due to the surge is harmlessly conducted to earth

Page 9: surge diverters

ROD GAP TYPE SURGE DIVERTER :

Page 10: surge diverters

LIMITATIONS : After the surge is over, the arc in the

gap is maintained by the normal supply voltage, leading to short-circuit on the system.

The rods may melt or get damaged due to excessive heat produced by the arc.

The climatic conditions (e.g. rain, humidity, temperature etc.) affect the performance of rod gap arrester.

The polarity of the surge also affects the performance of this arrester.

Page 11: surge diverters

EXPULSION TYPE SURGE DIVERTER: This type of arrester is also called

‘protector tube’ and is commonly used on system operating at voltages up to 33kV.

It essentially consists of a rod gap in series with a second gap enclosed within the fiber tube.

The gap in the fiber tube is formed by two electrodes.

The upper electrode is connected to rod gap and the lower electrode to the earth.

Page 12: surge diverters

EXPULSION TYPE LIGHTNING ARRESTER

Page 13: surge diverters

The series gap is set to arc over at a specified voltage lower than the withstand voltage of the equipment to be protected.

The follow-on current is confined to the space inside the relatively small fibre tube.

Part of the tube material vaporizes, and the high pressure gases so formed are expelled through the vent at the lower end of the tube, causing the power follow-in arc to be extinguished.

The device, therefore, has the desired self-clearing property.

Page 14: surge diverters

ADVANTAGES They are not very expensive.

They can be easily installed.

They are improved form of rod gap arresters as they block the flow of power frequency follow currents.

Page 15: surge diverters

LIMITATIONS An expulsion type arrester can perform

only limited number of operations as during each operation some of the fiber material is used up.

This type of arrester cannot be mounted on enclosed equipment due to discharge of gases during operation.

Due to the poor volt/amp characteristic of the arrester, it is not suitable for protection of expensive equipment

Page 16: surge diverters

VALVE TYPE Valve type arresters incorporate non linear

resistors and are extensively used on systems, operating at high voltages.

It consists of two assemblies (i) series spark gaps and (ii) non-linear resistor discs

The non-linear elements are connected in series with the spark gaps. Both the assemblies are accommodated in tight porcelain container.

The spark gap is a multiple assembly consisting of a number of identical spark gaps in series.

Each gap consists of two electrodes with fixed gap spacing.

Page 17: surge diverters

The spacing of the series gaps is such that it will withstand the normal circuit voltage.

An over voltage will cause the gap to break down causing the surge current to ground via the non-linear resistors.

The non-linear resistor discs are made of inorganic compound such as thyrite or metrosil.

These discs are connected in series. The non-linear resistors have the property of

offering a high resistance to current flow when normal system voltage is applied, but a low resistance to the flow of high surge currents.

Page 18: surge diverters

When the surge is over the non linear resistor assume high resistance to stop the flow of current.

Page 19: surge diverters

Under normal conditions, the normal system voltage is insufficient to cause the breakdown of air gap assembly.

On the occurrence of an over voltage, the breakdown of the series spark gap takes place and the surge current is conducted to earth via the nonlinear resistances.

Since the magnitude of surge current is very large, the nonlinear elements will offer a very low resistance to the passage of surge.

The surge will rapidly go to earth instead of being sent back over the line.

Page 20: surge diverters

ADVANTAGES : They provide very effective protection

against surges. They operate very rapidly taking less

than a second The impulse ratio is practically unity.

Page 21: surge diverters

LIMITATIONS :

They may fail to check the surge of very steep wave front reaching the terminal apparatus. This calls for additional steps to check steep fronted waves.

Their performance is adversely affected by the entry of moisture into the enclosure. This necessitates effective sealing of the enclosure at all times.

Page 22: surge diverters

SURGE DIVERTER OPERATION:

As a voltage surge travelling on the line reaches the surge diverter, it breaks down at a specified voltage Vbd.

The voltage across the diverter instantly dips and as the surge current show discharges through it, a constant voltage of value Vr(residual voltag) is maintained across it.

Page 23: surge diverters