Spyder Re-flashHow-To

Page 2: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

2

Re-Flash Tool

• Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later)- Only exception is if you desire new features and you have an

earlier firmware Spyder, then you MUST flash forward AND use the new tool to gain those features

• Download the Re-flash tool from the Forum- Run the executable and the re-flash program plus all current re-

flash images will be installed- The re-flash tool will expire on April 1st of every year to ensure that

only current customers have access to flashing Spyder devices. The first date of expiration is 2013

• Re-Flash will erase the control program as well as any bindings or balancing data- Perform an upload of that data if it hasn’t previously been done- Plan sufficient time to re-download/re-bind all re-flashed devices

Page 3: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

3

Re-Flash Tool

• Failure to follow the steps below may result in a Spyder which is not recoverable- Ensure that nothing else is running on the PC used for re-flash- Ensure power will not be interrupted to the PC, Spyders or the rest

of the communication network- Ensure that other PC’s are not flashing the same Spyder at the

same time

Page 4: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

4

Re-Flashing Spyder BACnet

• Ensure your BACnet Router is setup properly

Selecting a higher MS/TP Baudrate will speed up the flashing process but add risk if there are already devices talking on the network

Page 5: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

5

Re-Flashing Spyder BACnet

• Open the tool- A splash screen will display briefly- Then the setup screen will display Select BACNET IP to use a

BACnet router like the Contemporary Controls router

Select Lowest/Highest device ID’s to search for (may speed up discovery of devices)

Select number of retries for discovering devices

Select the Ethernet adapter connected to the router (in this case, the local LAN connection on your PC)

Select the UDP Port (must match UDP port on router). Ensure UDP port not in use by other tools like Niagara

Press Connect once correct choices have been made

Page 6: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

6

Re-Flashing Spyder BACnet

• Discover devices

Select Scan For Devices and only Spyder devices will show up

Page 7: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

7

Re-Flashing Spyder BACnet

• Other Information

Select devices to be re-flashed. Only devices of identical re-flash version can be re-flashed in a single batch job.

Use this button to automatically select all Spyders with identical Reflash versions (useful for batch jobs, limit is 30 devices per batch)

Use this button to automatically de-select all devices

BACnet Device ID

Status, OS Number and Brand

Hardware and Brand ID (not editable)

Firmware and Re-flash image currently loaded in device

Device Name (Blank if new from factory, deleted after re-flash)

BACnet network information

Press this button to select a new firmware image to download (must first select a device)

Page 8: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

8

Re-Flashing Spyder BACnet

• After “Download Firmware to Devices” is pressed

Select Browse to choose firmware to download

Spyder BACnet is the only hardware with more than once choice for firmware. One choice will flash the Spyder forward to modify only the autobaud operation and the other supports the autobaud AND Zio Plus enhancements. A user may desire only the autobaud change when reflashing an existing job in which they don’t want to replace the existing Spyder Tool.

Select folder with appropriate brand. These BACnet Spyder’s were ILC’s, otherwise choose the WEBs folder

Select desired firmware image to download. The list is automatically filtered so only valid selections can be chosen

Page 9: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

9

Re-Flashing Spyder BACnet

• Firmware Image information

A note will tell you what the new firmware image will enable. This Spyder BACnet has new firmware loaded and is being re-flashed backwards

Page 10: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

10

Re-Flashing Spyder BACnet

• Start the download- Re-flash will take about 3 minutes per device

Select Start Downloads to begin

Select whether to stop re-flash operations after any error, or 3 consecutive errors

Status window will pop up and show job activity

Time Remaining is based on previous re-flashes once a re-flash has been completed

A Cancel will stop re-flash operations AFTER the current device has been re-flashed

Page 11: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

11

Re-Flashing Spyder BACnet

• Job Complete

Firmware updated, Device Name Deleted

Pre Re-Flash

Post Re-Flash

Job Summary

Page 12: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

12

Re-Flashing Spyder Lon

• Open the tool- A splash screen will display briefly- Then the setup screen will display Select LON USB to use the

Echelon USB Plug

Select the Correct USB Plug (ensure AX isn’t running a station and occupying the USB Plug)

Select the Node Address of the USB Plug

Select the Domain of the network

Press Connect once correct choices have been made

Page 13: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

13

Re-Flashing Spyder Lon

• Discover devices

Select Scan For Devices and only Spyder devices will show up

These devices were brand new so no Device Name existed

Page 14: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

14

Re-Flashing Spyder Lon

• Other Information

Select devices to be re-flashed. Only devices of identical hardware can be re-flashed in a single batch job.

Use this button to automatically de-select all devices

Neuron ID

Status, OS Number and Brand

Hardware and Brand ID (not editable)

Firmware and Re-flash image currently loaded in device

Device Name (Blank if new from factory, deleted after re-flash)

Lon network information

Press this button to select a new firmware image to download

The flashing tool defaults to finding Lon Spyders with the factory Program ID. If you’ve changed the Program ID of a Lon Spyder within AX, the UserDefinitions.ini file which by default resides in “My Documents” e.g. C:\Users\[UserName]\Documents\ReflashTool1.2 of the re-flash tool must be updated with the Program ID’s of those Spyders or they will not be discovered. See next page for details.

Use this button to automatically select all Spyders with identical Reflash versions (useful for batch jobs, limit is 30 devices per batch)

Page 15: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

15

Re-Flashing Spyder Lon

• Adding a new Program ID to the Device Discovery- Not necessary unless you’ve previously altered the Program

ID

Double click on the UserDefinitions.ini file in C:\Users\[UserName]\Documents\ReflashTool1.2 of the re-flash tool. Copy/Paste the existing programid line below and then change the Program ID to match the Spyder’s new Program ID (use SpyderII section for big Lon Spyders).

“My Documents” Location:For Windows XP its C:\Documents and Settings\[UserName]\My Documents\ReflashTool1.2For Win7/Vista its C:\Users\[UserName]\My Documents\ReflashTool1.2

Page 16: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

16

Re-Flashing Spyder Lon

• After “Download Firmware to Devices” is pressed

Select Browse to choose firmware to download

Select folder with appropriate brand. These Lon Spyders were regular WEBs brand, otherwise choose the ILC folder

Select desired firmware image to download. The list is automatically filtered so only valid selections can be chosen

Page 17: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

17

Re-Flashing Spyder Lon

• Firmware Image information

A note will tell you what the new firmware image will enable. This Spyder Micro Lon has old firmware loaded and is being upgraded.

Page 18: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

18

Re-Flashing Spyder Lon

• Start the download- Re-flash will take about 9 minutes per device

Select Start Downloads to begin

Select whether to stop re-flash operations after any error, or 3 consecutive errors

Status window will pop up and show job activity

Time Remaining is based on previous re-flashes once a re-flash has been completed

A Cancel will stop re-flash operations AFTER the current device has been re-flashed

Page 19: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception

19

Re-Flashing Spyder Lon

• Job Complete

Firmware updated

Post Re-Flash

Pre Re-Flash

Job Summary

Page 20: Spyder Re-flash How-To. 2 Re-Flash Tool Remember that Re-flash can be avoided by using the latest Spyder Tool (version 5.200 or later) - Only exception