Capacitive Level Sensor SC 400 / LV 400 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS: The SC400 is a very compact switch, made with 316 S.S, and available in threaded, flanged or sanitary process connections. The LV400 controller is available with 24 VDC, 115 VAC or 220 VAC supply voltage, and a relay output.
Citation preview
INSTALLATION, OPERATION ANDMAINTENANCE INSTRUCTIONS
Capacitive Level Sensor SC 400 / LV 400
2Phone (516) 935-8001 / Fax (516) 935-6001
3456789
101112
Contents
Introduction .............................................................................Features & Dimensions .......................................................... Handling .................................................................................Installation .............................................................................. Wiring diagram .......................................................................Calibration ..............................................................................Maintenance ...........................................................................Technical specifications ..........................................................Trouble shooting .....................................................................Ordering information ..............................................................
Introduction
3
The SC400 point level detection probe, along with the LV400 controller, are designed to control the level of a wide variety of materials, such as water, oils, corrosives, solids, powders, grains, etc. The SC400's sensing capability provides reliable point level indication in high-pressure tanks, as well as in extreme high/low temperature ranges.
The SC400 is a very compact switch, made with 316 S.S, and available in threaded, flanged or sanitary process connections. The LV400 controller is available with 24 VDC, 115 VAC or 220 VAC supply voltage, and a relay output.
SC 400 + LV 400
4
Features and Dimensions
Phone (516) 935-8001 / Fax (516) 935-6001
L
3/8”
00 2525 5050 7575 100%100%
SetSet
FlowFlow
AdjustAdjust
4/20mA4/20mAOutOut
SondaSonda
SC400SC400
5 A 250V AC5 A 250V AC
PowerPower
LV 400/2LV 400/2
11++__
22 SS
4 3/8” (34,5mm)
3 1
/4”
(81
,5m
m)
1 3/4” (44mm)
Wide range of applications/industries such as:water, oils, corrosives, solids, powders, grains, etc.Functions on conductive as well as non-conductive mediasNo moving partsRugged constructionUnaffected by coating media or agressive productsCan operate at high temperatures and pressure
LV 400/2
2 1
/2”
( 6
4 m
m )
L
3/8”
3 1/2” ( 88 mm )
SC 400
SC 400 EX
3 1/2” ( 88 mm )
4 1
/4”
( 11
4 m
m )
5
Handling
Do not turn or handle by the housing
Seal the threadwith Teflon tapebefore screwing
Use the correct tool to screw the switch
Installation
6Phone (516) 935-8001 / Fax (516) 935-6001
1- Pre-Installation Checks: 1) Before installing the SC/400 probe and LV400 controller, check that the wire connections are correct and that the available power supply is compatible according to the label shown.
2) Confirm that the operating pressure and temperature of the process corresponds to the indicated specifications of the model to be installed.
2- Installation:
The SC400 level probe must be installed utilizing the type of connection provided. The tank must be free from turbulence or vortices throughout use. When tightening the sensor, only use the 316S.S. hexagon fitting to achieve a seal, do not twist with body of the sensor.Note: As achieving proper seal is very important for high pressures and explosion proof applications, care should be taken when tightening the connection.When installing the sensor either directly to the tank, or utilizing a “T” connection, make sure that that the rod extends beyond the inner wall of the tank so that internal build up or other debris does not interfere with sensor's performance. Care should also be taken when handling and installing sensors with coated rods. Any scratch can compromise the performance of the sensor.
CorrectIncorrect
7
Wiring Diagram
--
5
0 10
LE
D
Ad
just
3 1
/4”
1 3/4”
SC400
5 A 250V AC
Power
LV 400/2
11++__
22 SS
3 1
/4”
1 3/4”
SC400
5 A 250V AC
Power
LV 400/2
11++__
22 SS
SC 400
OBS.:CONNECT LV 400
+ - s+ - s
SC 400 “EX”
SC 400
8Phone (516) 935-8001 / Fax (516) 935-6001
Calibration
1) Fill up the thank until the medium touches the tip of the rod.
2) Adjust the set point of the electronic module that is contained within the enclosure. Turn the potentiometer clockwise until achieving the controlleris activated.
3) The red LED will light and the LV400 controller will be activated.
4) Turn the potentiometer clockwise two more points.
9
Maintenance
When cleaning the rod use a soft brush or any other similar object.
PROBES:
Care should be taken when handling and installing probes with coated rodsto avoid scratching them.Scratching the coating could interfere with the probe performance.
10
Technical Specifications
Phone (516) 935-8001 / Fax (516) 935-6001
SC 400 SC 400
Application
OperatingVoltage
Current Consumption
Adjustment
Sensibilityrange
Frequencyoscilation
0,1 to 5pF 0,1 to 5pF
2 VA 2 VA
-- --
Relay LV 400/2115 or 230 Vac (50/60Hz)24 Vdc (+/- 10%)
Relay LV 400/2115 or 230 Vac (50/60Hz)24 Vdc (+/- 10%)
Level switch for liquidssolids and granular
Level switch for liquidssolids and granular
Potentiometerswitch point
Potentiometerswitch point
Output Relay (NO + NC)5A max (250Vac)
Relay (NO + NC)5A max (250Vac)
Repeatability
Level indication
Max pressure 290 PSI (20 Bar) 290 PSI (20 Bar)
Probe: IP 65Relay: IP 40 Eex II B,C
Accuracy -- --
-- --
LED LED
Enclosure material
Glass fillednylon
Alluminum Die CastExplosion Proof
Wetted material
316 SS 316 SS
Class Protection
Processconnection
3/4” to 1 1/2” BSP or NPTflange or sanitary connections
3/4” to 1 1/2” BSP or NPTflange or sanitary connections
Operatingtemperature
Probe: 14 to 248ºF (-10 to 120ºC)Relay: 14 to 140ºF (-10 to 60ºC)
14 to 248º F(-10 to 120ºC)
MODELS
Electricalconnection
½”NPT Cable gland or M12 connector
1/2” or 3/4” NPT
11
Trouble shooting
Fault
Does not switch
Continuously switching
No LED, no power
Build up on the rod
Build up on the rod
when the rod is coatedcheck if exists some scratchon the rod
Clean the rod
Clean the rod
Fix the rod, changing it
Check power supply
Cause Solution
12
Ordering Information
CodeSC400
Code123
CodeBN0
CodeL
CodeNA
CodeC MT
CodePTFE
0X
Code
P50
0
- - - - - - -
CodeLV400/2
Code241123
-
CodeSC700
SC700ACSC700U
Code123
CodeBN0
CodeCMT
CodeC R
CodeSL
Code
PT
- - - - - -
Process Connection
Supply Voltage24 VDC + / - 10%115 VAC (50/60 Hz)230 VAC (50/60Hz)
Type of ThreadBSP
POINT LEVEL DETECTION - CAPACITIVEORDERING INFORMATION
Specifications
Process Connection
Probe to be used along with LV400/2 controller (see specs. below)
NOTE: RODS MUST BE COATED WHEN USING THE PROBE WITH CONDUCTIVE MEDIUMS.
Not a thread
Rod's lengthSpecify length
3/4" Thread
Type of Thread
Controller to be used along with SC400 probe
BSP
Specifications
NPT
1" ThreadOther - Specify
Cable gland with 1/2"NPT conduit entryM12 connector1/2" NPT conduit entry
EnclosureGlass filled nylonAluminum die cast
PTFE
1/2" NPT conduit entry
Type
Sensor´s Material
Rigid Rod
M12 connector
Supply voltage: 115 or 230 VAC - alum. enclosureUniversal power supply: 24 to 230Vac/dc - alum. enclosure
NPTNot a thread
3/4" Thread
Electrical ConnectionCable gland with 1/2"NPT conduit entry
1" ThreadOther - Specify
Electrical Connection
Polyacethal Delrin (Standard)
Insertion LengthL = 4 3/4" (120mm) - StandardSpecify length
CoatingHallar / TefzelNone
Cable
SpecificationsSupply voltage: 24 VDC - nylon - enclosure
Other - Specify
Neck/ temp up to356°F (180°C)None