Setting the system 2. Wiring option screen 3. Select either 3PT-Y or 2PT-D Always select 3PT-Y except using 2PT-D Rated primary input Secondary phase-voltage coefficient input Select ‘1’ if secondary voltage is 110V Select ‘1’ 1/r3 if secondary voltage is 110/r3 3. Third zero-phase voltage input 2. Rated secondary input 5-1 1. Phase voltage transformer setting 1. Current transformer setting Current transformer setting 1-1 Phase current transformer setting 1-2 Ground current transformer 1-3 Zero phase current transformer 1-4 Current input Setting system and setting PT/CT CB ON control using the front key. CB ON control using the front key. Use of password Lamp indicating relay operation Circuit breaker close POWER LED (Green) Indicating Power is on REMOTE/LOCAL & LED (Green/Red) Used for switching between Remote and Local : Remote is Green, Local is Red RESET KEY & LED (Red) Used for resetting the relay : Red light is on when resetting is needed COMM.LED (Orange) Indicating remote communication is OK Diar/Err (Red) Indicating there is a problem on the device Pick-up/Trip (Red) Indicating pick-up or trip of relay elements 1-1. Example for phase current transformer when using 1000/5 CT, input ‘1000’ for the primary side, the secondary side is 5A fixed 1-2. Example for ground transformer setting When 100/5, 50/2 NGR, input ‘100’, ‘50’ for the primary side, and the secondary side is fixed. 1-3. Example for zero-phase current transformer setting Zero-phase current transformer is 200/1.5 mA fixed, so it needs no setting. 1-4. [Zero-phase current transformer], [Zero- phase current input] There is not setting item in the group. Used when uploading/ downloading setting files with USB memory Used when connecting Manager port PC manager to the device POWER LED COMM.LED Diar/Err Pick-up/Trip Remote/Local switch Circuit breaker close/ open PLC port is used for connecting PLC to the device RESET KEY&LED TFT-LCD Panel TOUCH Screen 3. When the control is achieved, press “OK” button. 1. Press “CLOSE” on the front of HMI 2. “CLOSE” key should be pressed within ten seconds or else it is canceled automatically. 1. Touch green CB symbol on the front of HMI a. Monitoring status menu, SUB2 b. Line graph of the system c. Indicating the status change 2. Once SW control is popped up, select one of the control options(OPEN/CLOSE) and press “Apply” button. 1. In case the control order is the same as CB status, an error occurs a. Setting the device b. Security setting c. Password 2. In case CB status is “fail” or “Error Unknown”, an error occurs. 3PT-Y primary femininity MMI structure

Setting system and setting PT/CT MMI structure...1. Phase voltage transformer setting 1. Current transformer setting Current transformer setting 1-1 Phase current transformer setting

  • Upload
    others

  • View
    17

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Setting system and setting PT/CT MMI structure...1. Phase voltage transformer setting 1. Current transformer setting Current transformer setting 1-1 Phase current transformer setting

Setting the system 2. Wiring option screen 3. Select either 3PT-Y or 2PT-D

Always select 3PT-Y except using 2PT-D

Rated primary input

Secondary phase-voltage coefficient inputSelect ‘1’ if secondary voltage is 110VSelect ‘1’ 1/r3 if secondary voltage is 110/r3

3. Third zero-phase voltage input

2. Rated secondary input

5-1

1. Phase voltage transformer setting

1. Current transformer setting

Current transformer setting1-1 Phase current transformer setting 1-2 Ground current transformer

1-3 Zero phase current transformer 1-4 Current input

Setting system and setting PT/CT

① CB ON control using the front key. ② CB ON control using the front key. ③ Use of password

Lamp indicating relay operation

Circuit breaker close

POWER LED (Green)Indicating Power is on

REMOTE/LOCAL & LED (Green/Red)Used for switching between Remote and Local : Remote is Green, Local is Red

RESET KEY & LED (Red)Used for resetting the relay : Red light is on when resetting is needed

COMM.LED (Orange)Indicating remote communication is OK

Diar/Err (Red)Indicating there is a problem on the device

Pick-up/Trip (Red)Indicating pick-up or trip of relay elements

1-1. Example for phase current transformerwhen using 1000/5 CT, input ‘1000’ for the primary side, the secondary side is 5A fixed1-2. Example for ground transformer settingWhen 100/5, 50/2 NGR, input ‘100’, ‘50’ for the primary side, and the secondary side is fixed.1-3. Example for zero-phase current transformer setting Zero-phase current transformer is 200/1.5 mA fixed, so it needs no setting.1-4. [Zero-phase current transformer], [Zero-phase current input] There is not setting item in the group.

Used when uploading/downloading setting files with USB memory

Used when connecting Manager port PC manager to the device

POWER LED

COMM.LED

Diar/Err

Pick-up/Trip

Remote/Local switch

Circuit breaker close/open

PLC port is used for connecting PLC to the device

RESET KEY&LED

TFT-LCDPanel TOUCHScreen

3. When the control is achieved, press “OK” button.

1. Press “CLOSE” on the front of HMI

2. “CLOSE” key should be pressed within ten seconds or else it is canceled automatically.

1. Touch green CB symbol on the front of HMI

a. Monitoring status menu, SUB2b. Line graph of the systemc. Indicating the status change

2. Once SW control is popped up, select one of the control options(OPEN/CLOSE) and press “Apply” button.

1. In case the control order is the same as CB status, an error occurs

a. Setting the deviceb. Security settingc. Password

2. In case CB status is “fail” or “Error Unknown”, an error occurs.

3PT-Y primary femininity

MMI structure

Page 2: Setting system and setting PT/CT MMI structure...1. Phase voltage transformer setting 1. Current transformer setting Current transformer setting 1-1 Phase current transformer setting

“DI/DO status window displays the status of every DI, DO port for every slot which can be installed in a module. Uninstalled slots are gray, “SLOT#N” button shows “No module”, the status of ever port for the module is not displayed. (But, the signal is fixed with “OPEN”)

Select “Comprehensive measurements”

5. Section of Vector diagram• According to the measurement menu, vector of the major item is represented by a thick line,

and the minor item is represented by a thin line. • Display, at the bottom of the vector diagram, phase difference calculated in Va for the major

items in the measurement menu.(Currently, Vo-lo phase difference value display is added)

Note) that in case of faulty wiring, PF, Wh etc. can be changed, so they should be checked (But it can be checked after normal voltage and current is certified.)

OPEN3. Load status is displayed in the window “Comprehensive measurements,” and in the window for voltage, current measurements, VECTOR DIAGRAM is shown as graphics.

■ CT비 입력

5-2

DI, DO Monitoring(Input, output contacts monitoring)

Language setting

▒ Menu window for Monitoring status ▒ Indications of the status of each port

1. Setting the device 2. Language setting(ENG ↔ Korean)

CLOSE

4. “Power factor” as well as “Amount of power” window is sectionalized from the entire display.•�Grouping is made by PF, DPF, and LEAD/LAG are displayed with symbols, and directions are

expressed with FORWARD/REVERSE.

1. Measurements for the items selected in the window SUB1 is displayed in the left area, correlated items are displayed in a box.

※ In the window “Comprehensive measurements”, items of voltage/ current/power are categorized

2. If graphics of comprehensive measurements, voltage, current are shown at the same time, they are on the right side with clearly

Comprehensive

Power factor window

Page 3: Setting system and setting PT/CT MMI structure...1. Phase voltage transformer setting 1. Current transformer setting Current transformer setting 1-1 Phase current transformer setting

5-3

How to set relay elements [Common setting] There is no setting items on the group. Corrections

OCR Instantaneous element display

① 50 : Show instantaneous elements

② Display instantaneous operation time and correction rage is 50 ~ 300 ms

③ Display instantaneous current TAP value, and selected by the same method as ③-1

③-1 Display time delay current TAP value, and means a multiple number of CT rated current

EX) CT rate 100/correction value is 0.8 In In is CT rated current, and 0.8 is a multiple number, so the correction is …•CT primary standard : 0.8 × 100(CT rated primary) = 80A•CT primary standard : 0.8 × 100(CT rated primary) = 80A

④ 51 : Displays time delay elements.

⑤ Select characteristic curves, and there are 7 curves of long-time(DT) and Inverse time

(SI, VI, EI, KSI, KVI) in X-GIPAM.

⑥ Select inverse time characteristics, and the correction rage is 0.05 ~ 1.2 (with a unit of 0.01)

(Only in case of inverse time curve selections)

⑦ Displays definition time characteristics, and the correction range is 0.05 ~ 300.00 sec.

If definition time is selected in ⑤ the correction of the inverse time characteristics can not be

possible.

If inverse time(SI, VI, EI, LI, KVI) is selected, constant delay time ranging 0.0 ~ 10.00sec can be selected. When Time Lever is selected, even if the maximum value of Lever is selected, and relay movement characteristic curve is trapped by load characteristic curve, as much delay effect as the correction time in this item can be achieved.

③� ③-1�

OCR time delay(51)element display

Page 4: Setting system and setting PT/CT MMI structure...1. Phase voltage transformer setting 1. Current transformer setting Current transformer setting 1-1 Phase current transformer setting

5-4

Storage for 1000 items

Menu screen for reading records Basic code analysis

Menu SUB2 for reading records – recording events – Wave form storage process

Status change general item

Relayelement stage

Status changespecific item

Relay input TIME TAG

TIME TAG

Status changed

Status of operation of

relay elements

SLOT#01 Va: 0.000 VSLOT#01 Vb: 0.000 VSLOT#01 Vc: 0.000 V

SLOT#04 DO 02 : Close2010/11/30 08:50:42.060 [LOCAL]

2

27 Stg1 : AN#1 PU AN#2_PU AN#3_PU2010/11/30 08:50:41.096 [LOCAL]

3

Ext. Value

Previous Value :300.000 sec

Ext. Value :Value before change

SLOT#05 DO 03 : Pulse Out : EXECUTE2010/12/01 10:05:21.788 [LOCAL]

1

27 S.Grp#1 Stg1 T.Delay : 1.000 sec2010/11/30 08:49:41.021 [LOCAL]

4

Setting change Category, General

item

Setting change, and specific

items

changed setting values

Control items

Contents of the control

Results of the control

Types of events Event display

Type Event content Event Value Ext. Value

DI/DO

SLOT#04~07

DI01~10,DO01~06

OPEN / CLOSE Display “user input name” string for the relevant port.

Content Status of DI(or DO) port 01(or ~ 10, DO : ~ 06) of SLOT#4(or 5,6,7) is Open(or Close)

SWSW#01~04 Status

OPEN / CLOSE /Fail(Error) / Earth

Display “user input name” string for relevant SW

Content Status of SW#01(or ~ 04) is Open(or Close, Fail, Earth)

Types of events Relay elements Event display

50

Eventvalue

50 Stg1 :AN#1_OPAN#2_OPAN#3_OP

Operation elements Stage 1 of 50(OCR instantaneous time)

Causes of the Ia(AN#1), Ib(AN#2), Ic(AN#3)

Status Operation

Ext.value

SLOT#01 Ia :0.000 ASLOT#01 Ib :0.000 ASLOT#01 Ic :0 000 0.000 A

A phase current 0.000 A

B phase current 0.000 A

C phase current 0.000 A

5151 Stg1 : AN#1_OPAN#2_OP AN#3_OP

Operation elements Stage 1 of 50(OCR instantaneous time)

Causes of the Ia(AN#1), Ib(AN#2), Ic(AN#3)

Status Operation

Types of events Event display

Category Control Type Control items Control information Event Value Ext. Value

Control Type(CONTROL COMMAND)

Control Type

Signals SW#01 Control : CLOSE

Content Order “CLOSE” to SW#01

Signals SLOT#05 DO03 Pulse Out : EXECUTE

Signals 500 ms pulse is emitted from D003 port of Slot #05

Types of events Event display

Category Setting change general items Setting change specific items Event value Ext. Value

Example. 1Signals 27 S.Grp#1 Stg1 T.Delay : 1.000 sec

Content Time delay setting value is changed to 1.000 sec in Setting Group#1 of 27 (UVR)

Example. 2Signals 67N CMN Characteristic Angle : 90°

Content Characteristic Angle setting value is changed to “90°” in 67N(DGR) elements’ common

Page 5: Setting system and setting PT/CT MMI structure...1. Phase voltage transformer setting 1. Current transformer setting Current transformer setting 1-1 Phase current transformer setting

5-5

Accident display(during relay operation) - store 200 items.

Menu window for accident alarm Basic code analysis

Moved relay elements

Relayinput

TIME TAGStatus of operation of relay�elements

SLOT#01 Va: 0.000 VSLOT#01 Vb: 0.000 VSLOT#01 Vc: 0.000 V

27 Stg1 : AN#1 D.OUT AN#2_D.OUT AN#3_D.OUT2010/11/30 08:50:41.096 [LOCAL]

1

Ext. Value

“Accident record window” is very similar with “Event record window.”Accident record contains basic and additional information of up to 200 items, and a window shows a list of five items. List number change and checking using Page Up/Down button is the same as event record window. Like event record window, if the desired item is selected from accident record list on the right side, additional information is displayed on the left side. But, Additional information of the accident record, unlike event record, records and stores and displays source input value when the accident happened, all the values which were being input into CT, PT channel of the device(a total of 10 channels). And, accident record does not contain wave forms, so the function of saving wave forms or displaying icons is not supported.

Accident elements Window display Window

OCR instantaneous time 50 stg1 ::AN#1_PU50 stg1 ::AN#1_D_OUT

OCR instantaneous time PICK-UPOCR instantaneous time operation

OCR time delay51 stg1 ::AN#1_PU51 stg1 ::AN#1_D_OUT

OCR time delay PICK-UPOCR time delay operation

OCGR instantaneous time50N stg1 ::AN#1_PU50N stg1 ::AN#1_D_OUT

OCGR instantaneous time PICK-UPOCGR instantaneous time operation

OCGR time delay51N stg1 ::AN#1_PU51N stg1 ::AN#1_D_OUT

OCGR time delay PICK-UPOCGR time delay operation

UVR 27 stg1 ::AN#1_PU27 stg1 ::AN#1_D_OUT

UVR PICK-UPUVR operation

OVR 59 stg1 ::AN#1_PU59 stg1 ::AN#1_D_OUT

OVR PICK-UPOVR operation

POR 47 stg1 ::AN#1_PU47 stg1 ::AN#1_D_OUT

POR PICK-UPPOR operation

SGR 67G stg1 ::AN#1_PU67G stg1 ::AN#1_D_OUT

SGR PICK-UPSGR operation

DGR 67N stg1 ::AN#1_PU67N stg1 ::AN#1_D_OUT

DGR PICK-UPDGR time delay operation

NSOVR (Negative phase and voltage)

47 stg1 ::AN#1_PU 47 stg1 ::AN#1_D_OUT

NSOVR PICK-UPNSOVR time delay operation

NSOCR(Negative phase and Current)

46 stg1 ::AN#1_PU46 stg1 ::AN#1_D_OUT

NSOCGR PICK-UPNSOCGR time delay operation

LOCKEDPOTOR(locked)

46 stg1 ::AN#1_PU46 stg1 ::AN#1_D_OUT

LOCKED ROTOR PICK-UPLOCKED ROTOR time delay operation

THR 49 stg1 ::AN#1_PU49 stg1 ::AN#1_D_OUT

THR PICK-UPTHR time delay operation

DFR(87T) 46 stg1 ::AN#1_PU46 stg1 ::AN#1_D_OUT

NSOCGR PICK-UPNSOCGR operation

Page 6: Setting system and setting PT/CT MMI structure...1. Phase voltage transformer setting 1. Current transformer setting Current transformer setting 1-1 Phase current transformer setting

To use this product’s features fully and safely, please read user’s manual thoroughly before operating.

Please keep this instruction near from the product.

Safety instructions

▒� The ‘Safety instructions’ are for using the product properly and safely, in order to prevent accidents or risks. Please follow the instructions.

▒� The instructions are divided into ‘Warning’ and ‘Caution’, and the meanings are as follows.

▒� The meaning of the symbols indicated on the product and the instructions are as follows.

There are possibilities of serious injury or death when the instructions are breached.

is a symbol warns that there are risks under certain condition.

is a symbol warns that there are risks of electric shock under certain condition.

There are possibilities of minor injury or damage to the product when the instructions are breached.

Warning

Caution

www.lsis.comⓒ 2014.08 LSIS Co.,Ltd. All rights reserved.

Specifications in this catalog are subject to change without notice due to continuous product development and improvement.

▒ HEAD OFFICELS-ro 127 (Hogye-dong) dongan-gu Anyang-siGyeonggi-do KoreaTel. (82-2)2034-4887, 4873, 4918, 4148Fax. (82-2)2034-4648

▒ CHEONG-JU PLANTCheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,Cheong Ju, 361-720, Korea

2014. 08 X-GIPAM Manual (E) 2014. 08/(01) 2014. 08 Printed in Korea STAFF

•LSIS USA Inc. ≫ Chicago, AmericaAddress: 2000 Millbrook Drive, Lincolnshire, Chicago, IL 60069, United States of AmericaTel: 847-941-8240 Fax: 847-941-8259 e-mail: [email protected]

•LSIS (Middle East) FZE ≫ Dubai, U.A.E.Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab EmiratesTel: 971 4 886 5360 Fax: 971 4 886 5361 e mail: hschoib@lsis com

•LSIS Europe B.V. ≫ Schiphol-Rijk, NetherlandsAddress: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The NetherlandsTel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: [email protected]

•LSIS-VINA Co., Ltd. ≫ Hanoi, VietnamAddress: Nguyen Khe - Dong Anh - Ha Noi - Viet NamTel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: [email protected]

•LSIS-VINA Co., Ltd. ≫ Hochiminh, VietnamAddress: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, VietnamTel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: [email protected]

•LSIS Gurgaon Office ≫ Gurgaon, IndiaAddress: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, IndiaTel: +0091-124-493-0070 Fax: 91-1244-930-066 e-mail: [email protected]

•LSIS Japan Co., Ltd. ≫ Tokyo, JapanAddress: Toykokurakubu Bldg. 13th floor, 3-2-6, Kasumigaseki, Chiyoda-ku, Tokyo, 100-0013 JapanTEL:+81-3-6268-8241 FAX:+81-3-6268-8240 e-mail: [email protected]

•LSIS Shanghai Office ≫ Shanghai, ChinaAddress: Room 32 floors of the Great Wall Building, No. 3000 North Zhongshan Road, Putuo District, Shanghai, ChinaTel: 86-21-5237-9977 Fax: 89-21-5237-7189 e-mail: [email protected]

•LSIS Beijing Office ≫ Beijing, ChinaAddress: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District, Beijing 100013, P.R. ChinaTel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: [email protected]

•LSIS Guangzhou Office ≫ Guangzhou, ChinaAddress: Room 1403, 14/F, New Poly Tower, No.2 Zhongshan Liu Road, Guangzhou 510180, P.R. ChinaTel: 020-8326-6754 Fax: 020-8326-6287 e-mail: [email protected]

•LSIS Chengdu Office ≫ Chengdu, ChinaAddress: Room 1701 17Floor, huamin hanjun internationnal Building, No1 Fuxing Road Chengdu, 610016, P.R. ChinaTel: 86-28-8670-3201 Fax: 86-28-8670-3203 e-mail: [email protected]

•LSIS Qingdao Office ≫ Qingdao, ChinaAddress: Room 2001,20/F,7B40, Galaxy Building, No.29 Shandong Road, Shinan District, Qingdao 266071, P.R. ChinaTel: 86-532-8501-6058 Fax: 86-532-8501-6057 e-mail: [email protected]

•LSIS (Wuxi) Co., Ltd. ≫ Wuxi, ChinaAddress: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.ChinaTel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: [email protected]

•Dalian LSIS Co., Ltd. ≫ Dalian, ChinaAddress: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, ChinaTel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: [email protected]

▒ Global Network