1  PRE-TREATMENT  2008 Oil separators Large flows 25 > 250 l/sec OIL SEPARATORS LARGE FLOWS      I      N      T      R       O       C      L      A       S       S      E       S       C      H       O       O       S      E       C       O      N      F       O      R      M      I      T      Y      T      E       S      T       S      T      A      N      K       O      P      E      R      A      T      I       O      N      A      L      A      R      M      A       C       C      E       S       S       O      R      I      E       S      I      N       S      T      A      L      L      A      T      I       O      N      T      E       C      H      N      I       C      A      L       S      P      E       C      I      F      I       C      A      T      I       O      N

Separatoare Web Gd Uk

  • View
    212

  • Download
    0

Embed Size (px)

Text of Separatoare Web Gd Uk

  • 8/10/2019 Separatoare Web Gd Uk

    1/15

    11 PRE-TREATMENT 2008

    Oil separatorsLarge f lows 25 > 250 l/sec

    OIL SEPARATORS LARGE FLOWS

    INTRO

    CLASSES

    CHOOSE

    CONFORMITY

    TES

    TS

    TANK

    OPERATION

    ALARM

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

  • 8/10/2019 Separatoare Web Gd Uk

    2/15

    2

    EN858-1

    PRE-TREATMENT 2008

    CLASSES

    CHOOSE

    CONFORMITY

    TES

    TS

    TANK

    OPERATION

    ALARM

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    INTRO

    Oil separators

    RequirementsAn oil separator is designed to catch the source of pollutants

    carried by run-off waters.We offer a wide range of oil separators conform to standardsEN 858-1.

    Fields of applicationAccording to current rules, the oil separators have to be used

    for the pre-treatment of surface waters carrying hydrocar-bons, for example:

    To treat waters stemming from industrialprocesses, from the washing of vehicles, fromthe cleaning of oil coated elements.

    To treat rainy waters (drainage waters)contaminated by the oil resulting from waterproof

    zones (car parks, roads, factories, ).To hold wide-spread light liquids and to protect

    the surrounding zone (gas stations)

    Advices

    The rule becomes more and more strict as regards the1.

    quantity of hydrocarbons rejected in natural environ-ment. It is the reason why we advise to rather use de-vices provided with a coalescing filter which assures ahydrocarbon discharge lower than 5 mg/l.The good working of the separator imposes a sludge2.trap large enough for allowing the settling of muds (seefollowing page).The installation of the separator will largely be facili-3.tated if the level of water has been correctly measured.We propose, for that purpose, fixed or adjustable exten-sion shafts which allow to position the device withoutproblem.

  • 8/10/2019 Separatoare Web Gd Uk

    3/15

    3 PRE-TREATMENT 2008

    INTRO

    CHOOSE

    CONFORMITY

    TES

    TS

    TANK

    OPERATION

    ALARM

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    CLASSES

    Classes of separators

    There are 2 classes of separators:

    Class 1: with coalescing filter Residual content lower than 5 mg/l according to essay standard EN 858.

    Class 2: without coalescing filter

    Residual content lower than 100 mg/l according to essay standard EN 858.

    Choice of the treatment

    1. Total treatment (device without by-pass storm overflow)

    Installation straight on the net

    For large surfaces with risk of accidentalpollution.

    Example : hydrocarbons storage areas,

    fuel distribution centers.

    Installation right after the storm basin

    with flow regulator

    with risk of accidental pollution.The basin requires a lot of space.

    2. Partial treatment (device with by-pass storm overflow)

    Installation straight on the net,

    with by-pass device in the separator

    For large surfaces with risk of accidentallimited pollution.

    Example: parking areas, roads.

    Installation in by-pass on the net,with by-pass device upstream the separator

    For very large surfaces and on an existing net.

  • 8/10/2019 Separatoare Web Gd Uk

    4/15

    4 PRE-TREATMENT 2008

    INTRO

    CLASSES

    CONFORMITY

    TES

    TS

    TANK

    OPERATION

    ALARM

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    CHOOSE

    1 to 500 1,5

    501 to 1500 3

    1501 to 3000 6

    3001 to 5000 10

    5001 to 8000 15

    8001 to 15000 20

    1 to 100 1,5

    101 to 200 3 1 to 600 3

    201 to 400 6 601 to 1200 6

    401 to 670 10 1201 to 2000 10

    671 to 1000 15 2001 to 3000 15

    1001 to 1400 20 3001 to 4200 20

    How to choose your device

    The choice of an oi l separ ator is often relate d to specif ic constrai nts of the consider ed case. We

    give hereafter a summary of the cr i ter ia which can help to dimension the separator. As you can

    easi ly understand, these tables do not consider the part icular cases which can ar ise: please take

    contact with our off ices in case of doubt.

    Covered surfacesIn case of covered surfaces, rejected waters primarily come

    from cleaning. The flow rate of the device will thus be cal-culated according to the number of taps, heads, and all thehydrocarbon rejects. For covered carparks, the table opposite

    gives the size of the device according to the surface.

    Uncovered surfacesThe flow is directly related to the pluviometry, to the surface

    of the catchment area and to the slope of the network.

    Separator without by-pass

    For areas smaller than 1.400 m2, youll find in the table oppo-

    site the flow rate and the type of separator taking into accounta pluviometry of 150 l/ha/sec. In this case the device treatsthe totality of the incoming flow.

    Separator with by-pass

    In this case the device treats 1/3 of the total incoming flow,it allows to absorb an important flow in the event of storm, it

    is especially adapted to treat water from uncovered carparks.We strongly disadvise the use of an oil separator with by-passin an area where hydrocarbon is stored.

    Parameters

    peak flow

    polluted load to treat

    density of the hydrocarbons

    compulsory output level

    surface to be treated (covered and/or uncovered)

    implantation site (load class of the lids).

    Surface parkingm2

    Flowl/sec

    For larger surfaces, please contact us.

    Without by-pass With by-pass

    Surfacem2

    Flowl/sec

    Surfacem2

    Flowl/sec

    For larger surfaces, please contact us.

    Caution:

    For the Large Flows separators (larger than 20 l/s) it is

    advised to take into account the return 10 years formula.

    Please contact us for calculations of flows.

  • 8/10/2019 Separatoare Web Gd Uk

    5/15

    5

    EN858-1

    Dbi t

    N S

    Cl .

    Type

    Capacit sparateur

    Capacit dbourbeur

    Capacit stockage

    Epaisseur couche

    Anne de fabrication

    L/S Ref.

    # SrieSerial #

    Capacity separator

    Capacity sludge trap

    Storage hydrocarbons

    Thickness layerhydrocarbons

    Manufacturing year

    850 l

    150 l

    223 l

    180 mm

    2008

    EN858 Sparateur hydrocarbures Oil separator

    1,5

    1

    SKPE1,5/150

    3930

    PARC INDUS. DES HAUTS-SARTS B-4040 HERSTAL BELGIUMTEL +32 (0)4.256.56.10 FAX +32 (0)4.256.56.19 www.collinet.eu

    P.I.Hauts-SartsB-4040Herst[email protected]collinet.euwww.collinet.eu

    ECdeclarationofconformityWeherebyguaranteeanddeclarethattheCEmarkedproduct, SEPARATOR,fulfilstheappli-

    cableprovisionsoftheDirective89/106/EECconcerningseparatorsystemforlightliquidsas

    wellastheEuropeannormeEN858-1Separatorsystemsfor light liquids(e.g.oil andpetrol).

    Principlesofproductdesign, performanceandtesting,markingandqualitycontrol.ThiscertificateisvalidforalldevicesdescribedhereaboveandbearingtheCEmarkingo

    rigi-

    natingfromthefollowingsites: COLLINETAssainissements.a.,Herstal,Belgiumandforan

    undeterminedperiodoftime.

    Placeanddateof issue

    Signatureofanauthorisedperson

    Herstal,11/09/2006

    MrPierreANDRE

    AdministrateurDlgu

    PRE-TREATMENT 2008

    INTRO

    CLASSES

    CHOOSE

    TES

    TS

    TANK

    OPERATION

    ALARM

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    CONFORMITY

    Conformity oil separatorsTests made in keeping with standards EN858 (DIN 1999)

    Results between 0,16 and 2,2 mg

    Identification plate affixed inside and outside each device.

  • 8/10/2019 Separatoare Web Gd Uk

    6/15

    6 PRE-TREATMENT 2008

    INTRO

    CLASSES

    CHOOSE

    CONFORMITY

    TANK

    OPERATION

    ALARM

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    TES

    TS

    Tests reports

  • 8/10/2019 Separatoare Web Gd Uk

    7/15

    7

    3

    15 15

    8

    14

    6

    11

    9

    51394

    12

    PRE-TREATMENT 2008

    INTRO

    CLASSES

    CHOOSE

    CONFORMITY

    TES

    TS

    OPERATION

    ALARM

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    TANK

    Simulation

    Advantages

    Type Standard: Tank outof not recycled pure HDPE,manufactured by spiral weldingon mandrel. Resistance SN2.

    Type Super: Tank out of not recycled

    pure HDPE, manufactured by spiralwelding on mandrel. Resistance SN4.

    Double wall tank with spiralreinforcement. Wall thickness: 48, 72, 90 or 130 mmdepending on the flow of the device.

    In and outlet in HDPE adaptable with PVC.

    Sludge trap really proportioned inaccordance with standard EN858-1.

    The polycarbonate coalescing filter in its stainlesssteel frame (Aisi 304L) is easily removable and has ahight level of separation. Hydrocarbons output lowerthan 5 mg/liter for hydrocarbons

    of density 0,85 according to testsconditions of standard EN858-1.

    HDPE float calibrated at 0,85 isfixed on a mobility bar in stainlesssteel, it does not require any humaninterference during filling operation. Itensures the automatic shutting of the

    separator as soon as the retention capacity is reached.Through its position in the separator, this capacity ismaximal and so enables to reduce the draining.

    Waterproof guarantee: no outer screws.

    Pre set-up of the sampling unit. Antisplash partition.

    The separator includes a part being used for the decantation of muds and a secondpart for separation of hydrocarbons.

    Accessories in High Density Polyethylenof in stainless steel.

    Automatic obturator in stainless steelwith polyethylene float calibrated at 0,85.

    Antisplash partition.

    Partition between the sludge trap compartmentand the separator compartment.

    Sifon at the exit of the separator.

    Device fitted with 2 or 3 cylindrical openings

    with ventilation - 630 mm.The device can be equipped with a systemof leak detection.

    The tank

  • 8/10/2019 Separatoare Web Gd Uk

    8/15

    8 PRE-TREATMENT 2008

    INTRO

    CLASSES

    CHOOSE

    CONFORMITY

    TES

    TS

    OPERATION

    ALARM

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    TANK

    Options

    Optical and audible alarm N8 VARS

    Anchoring belts

    Anchorings in stainless steel

    Ladder in the sludge trap

    Ladder in the separator

    Leak detection

    Automatic obturation of the by-pass channel

    Cast iron covers (p. 30)

    Cylindrical shaft + ventilation

    Coalescing cel: hydrocarbons output < 5 mg/l

    Sludge trap

    The tank

  • 8/10/2019 Separatoare Web Gd Uk

    9/15

    9 PRE-TREATMENT 2008

    INTRO

    CLASSES

    CHOOSE

    CONFORMITY

    TES

    TS

    TANK

    ALARM

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    OPERATION

    Operation of the oil separator

    1/ Separator WITHOUT by-pass

    The first part of the separator (sludge trap)retains the mud and other particles. Mudsaccumulate at the bottom of the sludge trap.

    Hydrocarbon charged water is directed towards thesecond part of the separator and forwards frombottom to top towards the coalescing cell. Thevery small hydrocarbon particles are stuck on thewalls of the cell before going up on the surface.

    The layer of hydrocarbons grows thicker in time,which causes to push the float towards thebottom until closing the exit of the separator,then the retention capacity is reached.

    2/ Separator WITH by-pass

    Especially for places where there is no storageof hydrocarbons (for example carparks), theseparators fitted WITH the by-pass deviceenables not to treat the entire flow.

    When the entering flow is higher than the processingcapacity of the separator, the effluent goes through theby-pass device and directly runs out of the apparatus.

  • 8/10/2019 Separatoare Web Gd Uk

    10/15

    10

    1

    5 5

    4

    3

    2

    6

    1

    2

    3

    4

    5

    6

    PRE-TREATMENT 2008

    INTRO

    CLASSES

    CHOOSE

    CONFORMITY

    TES

    TS

    TANK

    ALARM

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    OPERATION

    Sludge trap compartment (muds ans sand)

    Separator compartment (hydrocarbons)

    Coalescing cel

    Ventilation

    Cylindrical openings 630 mm

    Automatic obturator

    3/ The automatic obturation

    In the event of problems, the automatic obturationis a safety device preventing from the evacuation ofhydrocarbons towards the draining network (for example:in case of lack of maintenance or accidental discharge).

    The obturation of the separator is carried out by a discassembled on a float tared to the density of hydrocarbons.The float follows the layer of hydrocarbons untilobturation when the storage capacity is reached. Eachcompartment is accessible by an inspection chamber.

    Maintenance instructions

    Empty sludge and hydrocarbons.

    The frequency of emptying depends on thequantity of polluted matters in the separators.

    The sludge trap will be emptied once a year.

    The separator compartment will be checkedonce a year. If the layer of hydrocarbons isthicker tan 10 cm, it has then to be removed.

    In case of accidental heavier flow ofhydrocarbons, the separator has to be totallyemptied and the filled up with clear water.

    Inside sight of the separator compartment:

    coalescing cel + automatic obturator

    Operation of the oil separator

  • 8/10/2019 Separatoare Web Gd Uk

    11/15

    11 PRE-TREATMENT 2008

    INTRO

    CLASSES

    CHOOSE

    CONFORMITY

    TES

    TS

    TANK

    OPERATION

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    ALARM

    Level alarm

    Hydrocarbon alarm in the separator: OILSET-1000

    Hydrocarbon/mud alarm equipped with 2 probes: SANDOILSET-2000

    Hydrocarbon/mud alarm fitted with 2probes : SANDOILSET-2000

    One probe gives a signal when the layer ofhydrocarbon has been reached. The other

    probe generates an alarm when the de-canted sand or mud level arises betweenthe two sensitive elements of the probe.

    Approved: II (1) G, [EEx ia] II C, VTT 04

    ATEX 031X

    The level alarm OILSET-1000 has espe-cially been developed to detect an inter-face water/hydrocarbon in a separator.

    It signals the right moment to carry outthe draining of the separator in order to

    avoid rejecting hydrocarbons in the sew-ers. The control unit and probe SET-DM3are in accordance with directive ATEX

    94/9/EC.

    Approved: II (1) G, [EEx ia] II C, VTT 04ATEX 031X.

    Control unit

    Control unit

    Hydrocarbons

    Water

    Hydrocarbons

    Mud

    Control unit

    Hydrocarbons

    Mud

    Control unit

    Hydrocarbons

    Box IP65 (175 x125 x 75mm)Connection with cable 3 x 0,5 mm2

    Box IP65 (175 x125 x 75mm)Connection with cable 3 x 0,5 mm2

    Water

    Water

    Water

  • 8/10/2019 Separatoare Web Gd Uk

    12/15

    12 PRE-TREATMENT 2008

    INTRO

    CLASSES

    CHOOSE

    CONFORMITY

    TES

    TS

    TANK

    OPERATION

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    ALARM

    Level alarm

    Mud/sand level alarm in the sludge trap: SANDSET-1000

    The SANDSET-1000 is a complete system which makes it possible to detect a decanted sand or mud level at the bottom of a

    tank. The ultrasound probe generates an alarm when the sand or mud level arises between the two sensitive elements of theprobe.

    The probe does not require any calibration, nor particular maintenance. It only needs to be installed at the right level and to be

    set under tension. It is in conformity with directive ATEX 94/9/EC for a use in a potentially explosive atmosphere.

    Control unit

    Mud

    Control unit

    Hydrocarbon alarm in the separator: SOLARSET

    Communication and warning system supplied with solar energy allowing to detect the hydrocarbon level and to send a SMSalert message.

    Water

    Water

  • 8/10/2019 Separatoare Web Gd Uk

    13/15

    13

    610

    F600 D-400 62 610 850 x 850

    90

    100

    + 30 mm

    PRE-TREATMENT 2008

    INTRO

    CLASSES

    CHOOSE

    CONFORMITY

    TES

    TS

    TANK

    OPERATION

    ALARM

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    ACCESSORIES

    Accessories

    Extension shaftsThe whole range is equipped with a sole circular extension

    shaft. They can be stackedtogether (maximum 2) and can beadjustedby sections of 90 mm.

    Ref:RRR630

    :630 mm

    Weight:14 kg

    Height 1 extension shaft:360 mm

    Height 2 extension shafts:720 mm

    Ref. Loadclass

    Weightkg

    Openingmm

    Basemm

    Cast iron cover

    PE Cover

    Ref. E630

    Load : classe A-15 kN

    Weight : 10 kg

    : 630 mm

    Screwed on the separator: 3 x M10

    With waterproof seal

    Adaptable with or without extension shaftCircular extensionshaft 630 mm

    For l ight f lows

    For l ight and large f lows

  • 8/10/2019 Separatoare Web Gd Uk

    14/15

    14 PRE-TREATMENT 2008

    INTRO

    CLASSES

    CHOOSE

    CONFORMITY

    TES

    TS

    TANK

    OPERATION

    ALARM

    ACCESSORIES

    TECHNICAL

    SPECIFICATION

    INSTALLATION

    Installation

    Off-the-road

    The separator has to be buried.1.Place the separator horizontally at the bot-2.tom of the excavation (lean concrete).Connect in/outlet on the pipe.3.Connect ventilation.4.Place extension shaft (if necessary) and5.adjust it to the floor level.Fill up the separator with clear water.6.At the same time backfill with sand.If several extension shafts are needed,7.a self-holding slab has to be foreseen(thickness and reinforcement to be defined).

    In carriage zone

    The separator has to be buried.1.Place the separator horizontally at the bot-2.tom of the excavation (lean concrete).Connect in/outlet on the pipe.3.Connect ventilation.4.Place extension shaft (if necessary) and5.adjust it to the floor level.

    Fill up the separator with clear water.6.At the same time backfill with sand.In case of placing underneath road traffic,7.separators have to be convered with castiron covers (class D-400 kN).The covers will be sealed in the self-holdingconcrete slab, which will be supported bythe edge of the excavation (thickness andreinforcement to be defined).

    Caution: in case of ground water tableFirst of all, build the ballast concrete plate

    on which the separator will be installed.Dont forget the reinforcing rods to anchor theseparator.

    The concrete mass has to be calculated to

    compensate fot the vertical push of the waterwhen the separator is empty.

    Finally the separator has to be strapedwith anchoring belts.

    VentilationPE Cover

    Topoil

    Filling material

    Stabilized sand

    In Out

    Sand bed

    VentilationCast iron cover 400 kN

    Self holding plate

    Filling material

    Stabilized sand

    In Out

    Stabilizedtrench bottom

    VentilationPE or cast iron cover D-400 kNto adapt in function ot the type of installation

    Filling material

    Stabilized sand

    In Out

    Ballastpave concrete

    Anchoring belts

    Anchoring in the paveconcrete

  • 8/10/2019 Separatoare Web Gd Uk

    15/15

    INTRO

    CLASSES

    CHOOSE

    CONFORMITY

    TES

    TS

    TANK

    OPERATION

    ALARM

    ACCESSORIES

    INSTALLATION

    TECHNICAL

    SPECIFICATION

    Oil separator in HDPE Large flowsTechnical Requirements/Specifications

    1. OIL separator in PE with coalescing filter (output class I)and sampling unit

    Type Standard: Tank out of not recycled pureHDPE, manufactured by spiral welding onmandrel, double walled. Resistance SN2.

    Type Super: Tank out of not recycled pureHDPE, manufactured by spiral welding onmandrel double walled. Resistance SN4.

    Accessories are made out of polyethylene high density orstainless steel.

    The separator is in conformity with the regulations ofstandard EN858-1.

    With coalescing filter: hydrocarbon rejection on treatedflow < 5 mg/l for hydrocarbons of density 0,85 accordingto the conditions of standards EN 858-1 (class 1).

    The separator is fitted with an automatic pluggingdevice with stainless steel arm and polyethylene float.

    In and outlet in HDPE adaptable with PVC.

    Apparatus equipped with 2 access openings 630 mmwith percussion caps.

    Fitted with sludge trap really proportionedaccordingto standards EN858-1. The separator includes acompartment for the decantation of muds and a secondcompartment for separation of hydrocarbons.

    Polycarbonate coalescing filter

    placed ina AISI 304 stainless steel framing. Highseparation capacity. Easily removable.

    HDPE float calibrated at 0,85 is fixed on a mobility bar instainless steel, it does not require any human interferenceduring filling operation. It ensures the automatic shuttingof the separator as soon as the retention capacity isreached.

    The separator is waterproof guaranteed because it hasnot been perforated for the fixing of the internal elements.

    Pre set-up of the sampling unit. Antisplash partition .

    The separator is equipped with an alarm system.

    2. OIL separator in PE with coalescing filter (output class I),by-pass channel and sampling unit

    Type Standard: Tank out of not recycled pureHDPE, manufactured by spiral welding onmandrel, double walled. Resistance SN2.

    Type Super: Tank out of not recycled pureHDPE, manufactured by spiral welding onmandrel double walled. Resistance SN4.

    Accessories are made out of polyethylene high density orstainless steel.

    The separator is in conformity with the regulations ofstandard EN858-1.

    With coalescing filter: hydrocarbon rejection on treatedflow < 5 mg/l for hydrocarbons of density 0,85 accordingto the conditions of standards EN 858-1 (class 1).

    The separator is fitted with an automatic pluggingdevice with stainless steel arm and polyethylene float.

    In and outlet in HDPE adaptable with PVC.

    Apparatus equipped with 2 access openings 630 mmwith percussion caps.

    Fitted with sludge trap really proportionedaccordingto standards EN858-1. The separator includes acompartment for the decantation of muds and a secondcompartment for separation of hydrocarbons.

    Polycarbonate coalescing filter

    placed ina AISI 304 stainless steel framing. Highseparation capacity. Easily removable.

    HDPE float calibrated at 0,85 is fixed on a mobility bar instainless steel, it does not require any human interferenceduring filling operation. It ensures the automatic shuttingof the separator as soon as the retention capacity isreached.

    The separator is waterproof guaranteed because it hasnot been perforated for the fixing of the internal elements.

    Pre set-up of the sampling unit. Antisplash partition .

    The separator is equipped with an alarm system.

    With integrated by-pass channel.

    Options

    Anchoring belts

    Anchorings

    Cast iron cover class D-400 kN

    Ladder in the sludge trap compartment

    Hydrocarbon alarm OILSET-1000, or sludge alarmSANDSET-1000, or sludge/hydrocarbon alarmSANDOILSET-2000.Echelle dans la partie sparateur

    The separator can be fitted with a leak detection system.

    HSKPE HSKBPPE