P O R TA B L E M E T H A N E D E T E C T O R

SENSIT® PMD

I N S T R U C T I O N M A N UA LR E A D A N D U N D E R S T A N D I N S T R U C T I O N S B E F O R E U S E

851 Transport DriveValparaiso, IN 46383-8432

Phone: 888 473 6748 219 465 2700Fax: 219 465 2701

Email: [email protected]: www.gasleaksensors.com

Page 2: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

Warnings:

• Topreventignitionofflammableorcombustible atmospheresdisconnectpowerbeforeservicing.

• Removeandchargebatterypackinanareaknowntobe freeofcombustiblegases.

• UseonlySensitTechnologiesbatterypack.

• Servicemayonlybeperformedbyfactoryauthorized servicetechnicians

• Notforuseinenvironmentsgreaterthan21%oxygen.

Safety Precautions:

• Readandunderstandinstructionspriortouse.

• AlwaysstartthePMDinanareaknowntobegasfree.

• Tamperingwiththisproductmayvoidthewarranty.

• UseonlySensitTechnologiesapprovedparts andaccessories.

• Neveruseaninstrumentknowntobedamaged, operatingunusually,oroutofcalibration.

For further information contact Sensit Technologies.

SensitTechnologies851TransportDriveValparaiso,Indiana46383USA

Tel:219/465-2700Fax:219/465-2701

Email:[email protected]:www.gasleaksensors.com

Page 3: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

TABLE OF CONTENTS Section Title Page

GeneralDescription......................................................4

PartsandAccessories..................................................5

ProductSpecifications..................................................6

ProductFeatures..........................................................6

ElectronicFeatures......................................................7

DisplayFeatures...........................................................8

HousingFeatures.........................................................9-10

Filters............................................................................11

FieldOperations...........................................................12

QuickMenu..................................................................13

UserMenu....................................................................14

Calibration....................................................................15

AdjustableFeatures......................................................16-17

Warranty.......................................................................20

Page 4: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

4

TELESCOPICSURVEY BOOTand PROBE ROD

GRAPHIC DISPLAY INFRAREDCOMMUNICATIONS

ALARM LEDSOUNDER

FILTER

OPERATIONBUTTONS

BACKLIGHTSENSOR

“D”RING

General Description

TheSensit®PMD,referredtoasthe“PMD”,isdesignedtodetectmethanegasfrom1ppmupto100%volume.ThePMDmaybeusedforwalkingsurveysandvehiclesurveys(whenproperlyinstalled)forundergroundnaturalgaspipingsystems.Otherapplicationsincludelandfillmonitoringandcheckingpipingsystemswhereotherinterferinggasesmayprovideinaccuratereadings.

ThePMDsensesgasusingInfrared(IR)AbsorptionSpectroscopyincombinationwithanelectronicnarrowbandpassfilter.Thistechnologyutilizesaninfraredlightsourcewithanoutputthatischangedwhen certain gasesabsorb the light output. The filter only allows specific lightwavelengths to bemonitoredandmeasured.TheconcentrationofgasisproportionaltotheamountofspecificIRlightabsorbedandisdisplayedinPPM,%LELand/or%Vol.

ThePMDhasalargedisplayindicatingconcentrationandotherinstrumentfunctionssuchasbatterychargeandperformance.Aninternalpumpprovidesrapidsamplingintothedetectionchamber.Audibleandvisualalarmsindicatewhenpresetalarmsareexceeded.Bluetoothdatatransmissionprovidescommunicationofrealtimeandstoreddata.OptionalGPSandDataLoggingallowforfurtherrecordingoftime,dateandlocationdata.

Page 5: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

5

Accessories

Standard Accessories

TelescopicSurveyProbe Part#883-00029Shoulder(Carrying)Strap Part#360-00238LithiumRechargeableBatteryPack Part#871-00017UniversalWallCharger Part#871-00025BatteryDoorRemovalTool Part#360-00249InstructionManual Part#750-00045HydrophobicFilterRingAssembly(10Pack) Part#873-00033SurveyProbeFilter(Blue)(1Filter) Part#360-00064

Optional Accessories

FiberglassBarHoleProbe Part#883-00019BrassBarHoleProbe Part#883-00018HDFiberglassBarHoleProbe Part#883-00021PMDManualCalibrationKit Part#881-00070BumpGasCylinder(50ppmCH4) Part#315-030004DeluxHardCarryingCase Part#872-00010CompactCarryingCase Part#872-00013ShippingBoxandFoam Part#872-00017HotSwapVehicleBattery Part#871-00030RemovableMemoryCard Part#360-00243PMDHarness Part#870-00046

Replacement Parts

Shoulder(Carrying)Strap Part#360-00238FilterCapAssembly“O”Rings Part#870-00034SurveyProbeFilter(Blue)(1Filter) Part#360-00064

Page 6: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

6

Product Specifications

Operational Specifications

Temperature: -4to122FDutyCycle: ~7hoursResponsetime: T50<3secondsAlarms: Audible-95db@15inches Visual–Redbacklightondisplay Visual–Displayinfo Visual–Failureindicators Settings–PPMandLELPower: LithiumIonRechargeablebatterypack OptionalVehiclepoweradapterPumpFlow: 1lpmDetectionRange: 0-5000ppm 10–100%LEL 5-100%V/V

Physical Specifications

Size: 11”x4.5”x6.5”(Approximate)Weight: 6.1LbsConstruction: CastAluminum/ABSPlastic

Sensor Specifications

IRSensor: Wavelength–3.4m DetectionRange1ppm–100%v/v Warmup<10min Calibrationrequired-3months

Product Features• ThePMDisconstructedofdurableABSplastic• ThehousingisdesignedtomeetIP54protection• ThePMDisdesignedtomeetCat3IntrinsicSafetyrequirements• Batterypackisdesignedforeasyfieldreplacement• FieldorSmartCalcalibrationiseasilyperformed• Externalfiltersareinexpensiveeasytochange• TheLCDdisplayiseasytoread• ThePMDusesasimple“SensitStyle”userinterface• CommunicationwithotherdevicesiseasywithBluetoothinterface• RealtimeGPSisoptional• RealtimeDataloggingwithremovablestorageoption

Page 7: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

7

Electronic Features

User Interface

Theuserinterfaceincludesthefollowingfeatures:• Threebuttonoperation• LEDStatusindicators• Sounder• Photocell(automaticbacklighting)• IRcommunicationport• LCD

Button Operation

TheSensitPMDisoperatedwiththeuseofthreebuttonsbelowthedisplay.

TheyarelabeledA,B,C.

The“A”button:• activates/deactivatestheinstrument• mutestheaudiblealarms• accessSmart-Calcommunication

The“B”button:• Accessesthequickmenuandusermenu• DigitallyadjuststheTICKsoundforleaklocating

The“C”button:• Savesdisplayedreadingstotheinternalmemory• Performsamanualzero.

Page 8: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

8

Display Features

Thedisplayprovidesallinformationincluding:• GasconcentrationinPPM,LELAND%Vol• Batteryvoltagestatus• PumpStatus• GPSactivationandcoordinates• Bluetoothoperation• Dataloggingoperation• Warningindication• Tickoperation

Iconsonthedisplayindicatethestatusofvariousfunctions.

-FlowOK -Flowblocked

-Alarmnotmuted -PPMalarmmuted

-%LELalarmmuted -%GASalarmmuted

-Warning/trouble/failuresymbol

-BluetoothOnandConnected -Bluetoothonbutnotconnected

-TickON

-Dataloggingon–flashoncefordatasave

-DataSaved–flashonceformanualdatasave

-GPSConnected -GPSenabled-notconnected

Page 9: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

9

Alarm settings

Thereare3adjustablealarmsettings.

1. PPM a. Default:10ppm b. LowLimit:0 c. Highlimit=500 d. DisablePPMalarm:SetthePPMalarmto0 e. Alarm:Audible,LED,Redbacklightifunitindark

2. %LEL a. Default:50%LEL b. LowLimit:10%LEL c. Highlimit=90%LEL(Ifnoautorangeto%gas) d. DisableLELalarm:Cannotdisablethisalarm(muteonly) e. Alarm:Audible,LED,Redbacklightifunitindark

3. %GAS a. Default17%Vol b. LowLimit:5%Vol c. HighLimit:50%Vol d. Disable%GASalarm:Cannotdisablethisalarm c. Alarm:LED,Redbacklightifunitindark

AdjustmentoftheppmalarmiscoveredintheUserMenuportionofthismanual.

Housing Features

Battery Pack

Thebatterypackislocatedonthebacksideoftheinstrumenthousing.ThebatteriesareLithiumIonrechargeable.ThebatteriesareonlyavailablefromSensitTechnologies.

Toremovethebatterypackturntheretainingscrews¼turn.Pullthebottomofthepackawayfromthemainhousing.Rechargingofthebatterypackrequiresremovalfromthemainhousing.

Toreplaceslidethetoptabsofthebatterypackintotheretainersatthetopofthemainhousing.Pushthebottomintoplaceandturnandlocktheretainingscrews.

Page 10: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

10

ChargeComplete

(Green)

Charging

(Red)

Status

(Yellow)

ChargerConnection

Gas Inlet and Outlet

Locatedonthefrontofthemainhousingisthegasinletandoutlet.Botharefittedwithluer-styleconnectionsforeasyconnectiontoprobeaccessories.

Thecenterconnectionisthegasinlet.Totherightistheoutlet.Donotblockgasoutlet.

Shoulder Strap attachment

“D”ringsarelocatedoneachsideofthemainhousingforshoulderstrapattachment.Clipsonthestrapwillattachsecurely.

ThebatterypackhasLED’stoindicatechargestatus.Chargingshouldonlybeperformedinanareaknowtobefreeofcombustiblegases.

Page 11: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

11

Hydrophobic Filter Assembly

WARNING:Donotoperatewithoutproperfilter.Damagemayoccurtothepumpandotherinternalparts.Onlychangefilterwithpumporinstrumentoff.

Thegasinletisprotectedbyahydrophobicfilter.

Itisaccessedby:1. Detachanyprobeassembly2. Twistandremovefiltercap3. Removeandreplacefilterdisc4. Check“O”ringinsidecap5. Replacefiltercap6. Performedflowblocktest

Additionalfiltersarelocatedineachoftheaccessoryprobeassemblies.

Page 12: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

12

Operation and Field Use

ToactivateinstrumentpushPOWERbutton.Thefollowingwarm-upsequencewilloccur:

1. Warm-upsequence(a-i)withinfobelow.

a. Logo b.SerialNumber c.Revision d. SystemCheck i. LEDcheck ii. Backlightcheck iii. Date/Time e. Caldue(upcoming)orCalPastDue f. ActivationAcknowledgments i. Pump ii. Dataglog iii. GPS g. Sensorwarm-up(7-10Min)and“PleaseWait” h. Autozero i. Workingdisplay 2. Attachtheappropriateprobeassemblyandperformaflowblockcheck.An alarmsound,displayindicationandflowiconwillindicateafailedtest. 3. Followcompanyproceduresforperformingleaksurvey/investigation

4. Ifthealarmsettinghasbeenexceededpressandreleasethe“A”buttonto disablethealarm.Thealarmsoundwillautomaticallyresetwhenthe concentrationhasgonebelowthethresholdvalue.Secondaryalarmsathigher concentrationwillactivatewhenvaluesareexceeded.Pressandreleasethe“A” buttonagaintomutesecondaryalarms.Duringanyalarm,thedisplaybacklight willbeREDincolor.

5. Checkfiltersdailyforbestresults.

6. Batterypowerisdisplayedusingabatteryvoltageicon.Fullbatteryis12.0v. BATLOWVOLTwillbedisplayedat8vwheninsufficientbatterypowerisavailable.

7. Toturnofforputintostandbymodepushandholdthe“A”button.Itwill display“SHUTDOWN”onleftsideand“STANDBY”onrightsideofthedisplay. Pressthe‘A’buttontoturntheinstrumentoff.Press‘C’toputunitinstandby modewhichwillreducepowerconsumptionandwillallowyoutoreducethe warmuptimetoapproximatelytwominutes.Werecommendusingstandby modeforlessthan1hour.

Page 13: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

13

QUICK MENU

Pressandrelease‘B’button.Thiswillprovideaccesstothefollowingfunctions.Pressthe“C”buttontoscrollthroughtheoptions.Use‘B’buttontoselect.Use‘B’buttonagaintoturnitOFFor‘C’buttontoturnON.Press‘A’buttontoselectyourchoiceandexitmenu.

1. TICK–Audibleleakdetectionmode.NOTE:Activatingthetickwilldisable soundalarm.

a. Whenactivatedatickwillbeheardeverysecond.Frequencyoftickwill increaseasgasconcentrationincrease. b. Pressandrelease‘B’buttonwillresetthetickfrequencyto1tickper second. Thetickfrequencywillincreaseifgasconcentrationincreasefrom thatconcentration. c. Toturnthetickoff,pressandrelease‘A’button.Pressandrelease‘A’button againtoactivatethealarmsound.

WhenviewingthefollowingselectionsUse‘B’buttontoselect.Use‘B’button againtoturnitOFFor‘C’buttontoturnON.Press‘A’buttontoselectyourchoice andexitmenu. 2. BHTest–Barholetestfunction 3. PUMP-Use‘B’buttontoselect.Use‘B’buttonagaintoturnitOFFor‘C’ buttontoturnON.Press‘A’buttontoselectyourchoiceandexitmenu. 4. GPS–RealtimeGPSX/Ycoordinates 5. SmartLink-UseBluetoothtodownloadlogs(Calibration,QuickCal,Session,Barhole,Autologs) 6.Warning-Usethisfeaturetolistcurrentfailuremode.

Bluetooth Activation

WhentheBluetoothisactivatedthedisplayreadingscanbetransmittedtoanydevicecapableofreceivingBluetoothdata.Thedatamayalsobeviewedbyusing“HyperTerminal”.Thewebsiteiswww.lgraeve.com

BluetoothPasskey:5DigitSerialNumber

SerialCommunicationsSettings:BitsPerSecond:57600Databits:8Parity:NoneStopbits:1Flowcontrol:None

DataStreamcanbeadjustedtosenddataevery1-10sec.youcanfindsettingstochangethisinExpertMenu->DataStream.YouneedtoturnDataStreamONinUserMenu.

OnceconnectedtotheBluetoothdevice,PMDsendsthe7digitPPMreading.

Page 14: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

14

USER MENU

Toaccesstheusermenupushandholdthe“B”buttonuntilUSERMENUisdisplayed.Fromthismenuthefollowingfeaturescanbeviewedbypressingthe“C”buttontoscrollthroughtheoptions.Entertheselectionbypressingthe“B”buttonandadjustingbyusingthe“C”buttonortheonscreenprompts.Pressingthe“A”buttonrepeatedwillreturnyoutotheworkingdisplay.

Date and Time Viewthedateandtime. Timeisin24hourformat.Dateismm/dd/yyformat.

Print Menu Allowsaccesstoprintmenuforcalibrationandoperationalsessions.

Bump Test Performtimedtestforgasresponseinppmrange.Pumpmaybe selectedONorOFFforthisfunction.

Calib Menu CalibrationtoZeroAir,1000ppm,2.5%and100%methanegasconcentrations. ForinstructionrefertoCALIBRATIONsectionofthismanual. •ZeroAir-ToSetZeroPoint PumpOn/Off OnscreenInstruction •1000PPM-Tocalibrate1000ppmlevelonly (ZeroAircalibrationrequiredfirst-automatic) •2.5%V/V-toCal2.5%(50LEL)CH4 Only (ZeroAircalibrationrequiredfirst-automatic) •100%V/V-toCal100%(100LEL)CH4 Only (ZeroAircalibrationrequiredfirst-automatic) •FullCalib-Automaticallysequencezero,1000,2.5%V/V,100%V/V (ThisupdatesCalDue)

Datalog Activatesthedataloggingsystem.(IfActivatedw/memorycard)

Data Stream Activatesrealtimedatastreamingofdisplayreadingseverysecondto anotherrecordingdeviceusingBluetooth.Settingsonpage13.

Alarm PPM AdjustmentforPPMalarmvalue. Settingat0disablesalarm. Rangeis0-500ppm

Set Clock Adjustdateandtime.View Sess Log Viewmanuallysaveddata.View BHLOG Viewthebarholetestlogs(IfActivated).View Auto ViewAutologdataofoperationalpeakvalues.View Cal Log Viewcalibrationlog.QCal Log Viewrecordingofindividualcalibration(NotFullCalib)

Page 15: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

15

Calibration Check

Toverifytheproperoperationofthisinstrumentapplyaknownconcentrationof50-1000ppmmethanetothesamplesystempriortouse.

Thisisnotarequiredprocessbutisrecommendediftheproducthasnotbeenusedformorethan30days.

Calibration

ThePMDrequirescalibrationevery3months.Anautomaticreminderwillnotifytheuserthatcalibrationisdueatstartup.

Calibrationcanonlybeperformediftheinstrumenthasbeenoperationalfor30minutes.

Tocalibratetheareamustbeknowntobegasfree.Ifthereismethaneintheareaabottleofzeroairwillbenecessary.Othergasesrequiredinclude1000ppm,2.5%and100%methane(pipelinegasisalsoacceptable).Somegasescanbecalibratedindividually.ContactSENSITTechnologiesServiceDepartmentformoreinformation.

Calibrationisperformedwiththepumpoffifthereisnoaccesstodemandflowregulatorsforthecalibrationbottles.Turn-offisselectedpriortocalibration.

CalibrationisperformedthroughtheUserMenu.Usingthe“B”buttonaccesstheUserMenu.Usethe“C”buttontoscrollto“CalibMenu”.

Tobeginpressthe“B”button.Iftheinstrumenthasnotoperatedfor30minutesacountdowntimerinsecondswillbedisplayed.Whentheproperamountoftimehasbeenmetthedisplaywillshow“Proceed”.Pressanybutton.Abeepwillbeheard.

SelectCalTypeandfollowon-screenprompts.FullCalibisreccomended.

Applyzeroppmmethaneorcleanair.Press“C”buttontobeginzeroaircalibration.Displaywillshow“waitingforstability”followedby“success”whencompleted.Pressanybuttontocontinue.

Displaywillread“pleaseapply1000ppmmethane”.Attachandapply1000ppmmethane.Theprocessrequires1-5minutes.SearchingOPTTEMPwillbedisplayed,thendisplaywillshow“waitingforstability”followedby“success”whencompleted.

Displaywillread“pleaseapply2.5%methane”.Attachandapply2.5%methane.Theprocessrequires1-5minutes.Displaywillshow“waitingforstability”followedby“success”whencompleted.

Displaywillread“pleaseapply100%methane”.Attachandapply100%methane.Theprocessrequires1-5minutes.Displaywillshow“waitingforstability”followedby“success”whencompleted.

Uponcompletionpressanykeytoexittoworkingdisplay.Activatethepumpandallowtoclearpriortoturningoff.Thecalibrationreminderwillautomaticallyupdateaftersuccessfulcalibration.

Page 16: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

16

Adjustable Features (passwordprotected)ContactSensitTechnologiestogainaccesstothefollowingadjustablefeaturesnotintheusermenu.

Service Contrast: Adjustthedisplaycontrastasneeded.

Quick Scan: OptimumTempAdjust(1000ppmrequired) Orientation Cal: Calibrationoflampoutputindifferentpositions. Cal Flow: Settingflowalarm

Tick SENS Lo,Med,orHigh

Alarm %LEL AdjusttheLELalarmvalue.Defaultis50%.

Alarm %V/V Adjustthepointwhenthealarmdeactivates.Defaultis17%.

Show SESS Allowdisplayofmanuallysaveddata.Defaultisoff.

Show BHLOG AllowdisplayofBHtests.Defaultisoff

Show AUTO AllowdisplayofAutologdata.Displayisoff.

BH Time Setthetimeinsecondsfordurationofthebarholetest. Defaultis15seconds.

Purge Time Setpurgetimeforinstrumentpriortoshutdown. Defaultis10seconds.

Standby Timeofinactivityorlackofmotioninminutesthatwillcausethe instrumenttoautomaticallygointolowpowermode.Defaultisoff.

Shutdown Timeinminutesthatshutdownwilloccurwheninstandbymode. Defaultis60.

Bump Limit Concentrationofgastobeacceptablewhenperformingabumptest. Rangeis5–1000ppm.Defaultis800.SetLowerandUpperLimit.

Bump Time Timerequiredinsecondsforunittopassabumptest. Rangeis10-60.Defaultis45.

Log Period TimebetweenDatalogpointsinseconds.Range1-60.Defaultis1.

Data Stream Timeinsecondsfordatatobestreamedthrough Bluetoothcommunication.Defaultif1second.

Page 17: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

17

Adjustable Features (Continued)Rest UCal Resetcaldatatofactorysettings(PasswordProtected)

Set Cal Due TimeInterval(90Default)

Cal Due Ack RequiresbuttonpushafterCalDuereminder(defaultoff)

DISP Callog Last5calibrationrecords PPM Option: PPMAutorangetoLEL.Defaultison.

PPM Handoff: HandofffromPPMtoLELor%V/Vsetting.(default5000)

% LEL Option: LELfrom0.1-100%.DefaultisOn 100% LEL Equiv: SetLELlimitsfrom4.0–5.0%gasvolume.Defaultis5%. PPM+%LEL: DisplaybothPPMand%LEL.DefaultisOff NG Factor: Automaticcalculationforlowmethanepipelinegas.(default100)

UCal Date Dateoflastfullusercalibration Erase Auto EraseAutolog

Erase Sess ErasemanuallysaveddataLog Erase BHLog Erasebarholetestlog

SCal Pump On/OffDuringCal(foreachgastype)whencalibratingonthecal-station

Rezero REQD DowndriftAlert,On/Off,Value5Default

Language Selectlanguagefordisplay

Auto Bump Requirebumptestbeforeuse(defaultoff,adjustable1-30days)

Erase Bump EraseAutoBumpLog

Page 18: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

Saving SD Card Data Log Information

RemoveSDMemoryCardfrominsidethebatterycompartment.InstallSDMemoryCardincomputer.SaveFileindesiredformatandlocation.Preferredformatis.kml

GPS Data Conversion & Coordinate Mapping

GPSDataconversionandmappingcanbeaccomplishedusingSmart-LinkDataViewerSoftwareandGoogleEarthorgpsvisualizer.com

1.UsingSmartLinkselectthedesiredreports.(See“Howtouse”and“Reports”sectionofSmartLinkHelpfileformoreinformation.)

2.Click“SaveReport”button.Savereportasformat.kmlformat.ThisformatwillonlysaveloginformationforwhichvalidGPScoordinateinformationisavailable.

3.GoogleEarthmustbeinstalled(FreeDownload).Doubleclickthe.kmlfile.ItwillopenGoogleEarthandloadthemap.

Note:IfGoogleEarthisnotinstalled,proceedtonumber4.

4.Goto:http://www.gpsvisualizer.com/Select“Google Maps”.

18

Import your .kml file:

1.Usingbrowsebutton,selectthefileyouwishtoview.

2.Selectthemaptype.

Way-points: To display coordinates, gas concentrationdetectedandtimeatspecificlocations.ItisbesttousewithSession-log,Bar-holelogandAuto-log.

Route points: The “route” would represent the road,trail, path, etc. that you have taken. It also display gasconcentrationdetectedandtimeatspecificlocations.It isbesttousewithData-logtoviewareasurveyed.

3.Click“Drawthemap”button.

Page 19: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

19

GPS Data Conversion & Coordinate MappingSampleofthedatalogreportisdisplayedbelow.

Page 20: SENSIT PMD - equipmentcontrols.com · The Sensit® PMD, referred to as the “PMD”, is designed to detect methane gas from 1ppm up to 100% volume. The PMD may be used for walking

Warranty

YourSensitPMDiswarrantedtobefreefromdefectsinmaterialsandworkmanshipforaperiodoftwoyearsafterpurchase(excludingcalibration).Ifwithinthewarrantyperiodtheinstrumentshouldbecomeinoperativefromsuchdefectstheinstrumentwillberepairedorreplacedatouroption.Thiswarrantycoversnormaluseanddoesnotcoverdamagewhichoccursinshipmentorfailurewhichresultsfromalteration,tampering,accident,misuse,abuse,neglectorimpropermaintenance.Proofofpurchasemayberequiredsbeforewarrantyisrendered.Unitsoutofwarrantywillberepairedforaservicecharge.InternalrepairormaintenancemustbeperformedbyaSensitTechnologiesauthorizedtechnician.Violationwillvoidthewarranty.Unitsmustbereturnedpostpaid,insuredandtotheattentionoftheservicedepartmentforwarrantyorrepair.

Thiswarrantygivesyouspecificlegalrightsandyoumayhaveotherrightswhichvaryfromstatetostate.

SensitTechnologies851TransportDriveValparaiso,Indiana46383USA

Tel:219/465-2700Fax:219/465-2701

Email:[email protected]:www.gasleaksensors.com

SENSIT PMD INSTRUCTION MANUALPart # 750-00045 Revision12-15-17