    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 1 of 24

    KARIMUN YARD CONSTRUCTION PROJECT

    SITE ACCEPTANCE TEST

    Contract No.: 537856

    863013-VPS-PQM-E-DS-0002

    21-12-2010 A Issue for REVIEW HFZ MPS JBS

    Date Revision Revision description Prepared Checked Approved

    This document is the property ofSaipem.; all rights reserved. Violators will be pursued under civil and criminal law

  • 8/7/2019 SAT Renew Karimun

    2/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 2 of 24

    SUMMARY OF REVISION

    Revision Revision description Prepared Checked Approved

    21-12-2010 A Issue for REVIEW HFZ MPS JBS

  • 8/7/2019 SAT Renew Karimun

    3/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 3 of 24

    CONTENTS

    Description Page No

    SUMMARY OF REVISION ...2

    CONTENTS .....3

    INTRODUCTION.....................................................................................................................4

    SYSTEM DESCRIPTION........................................................................................................5

    PURPOSE ....5

    EQUIPMENT REQUIRED ..5

    COMMISSIONING METHODE ..6

    1. PARTICULARS ..6

    1.1 Ventilation Fan 3608 VPS 01 ....6

    1.2 Ventilation Fan 3616 VPS 02 ...7

    1.3 Electrical Control Panel VPS 01 ..7

    1.4 Electrical Control Panel VPS 02 ..8

    2. VENTILATION FAN TEST ......8

    3. STARTING TEST......8

    4. PREPARATION CHECK 10

    4.1System Checklist .......10

    4.2Mechanical Installation ..10

    4.3Electrical Installation ..10

    4.4 Inspection by Vendor Service Engineer or Technical Representative ........11

  • 8/7/2019 SAT Renew Karimun

    4/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 4 of 24

    5. PRE-COMMISSIONING PROCEDURE CHECKLIST 12

    5.1Air Duct ....12

    5.2 Fans .12

    5.3Electrical Control Panel ....13

    6. COMMISSIONING PROCEDURE ...14

    6.1Operational Test ....14

    6.2Air Duct, Enclosure, and Fans performance Test ....14

    7. APPENDICE ....15

    7.1Functional Checklist VFD Control Panel Fan 3608 VPS 01 ...16

    7.2 Functional Checklist VFD Control Panel Fan 3608 VPS 01 ...17

    7.3Commissioning Checklist and Record Fan 3608 - VPS 01 18

    7.3.1 Commissioning Record Fan 3608 VPS 01 .....18

    7.3.2 Running Record Fans 3608 VPS 01 ...........19

    7.4Commissioning Checklist and Record Fan 3616 VPS 02 ...20

    7.4.1 Commissioning Record Fan 3608 VPS 01 .....20

    7.4.2 Running Record Fans 3608 VPS 01 ...21

    ACCEPTANCE ..22

  • 8/7/2019 SAT Renew Karimun

    5/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 5 of 24

    SYSTEM DESCRIPTION

    The ventilation requirements of a space will be largest air flow of the three quantities determined by:

    1. The rate of air change.

    2. The required fresh air flow per equipment.

    3. The limiting temperature rise.

    The requirement of rate of outside air change for all specs, and allowable temperature rise are given in table in

    table 7.0 at appendices rise as general guideline.

    This procedure covers Engine/ Generator area.

    PURPOSE

    1. To ensure proper installation of fans, short duct, flexible duct, discharge attenuator, silencer box.

    2. To demonstrate the operational of equipments.

    3. To ensure functionality of equipment control and device.

    EQUIPMENT REQUIRED

    1. Ammeter.

    2. Voltmeter.

    3. Anemometer.

    4. Megger Tester

    5. Thermometer

    6. Sound meter

  • 8/7/2019 SAT Renew Karimun

    6/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 6 of 24

    COMMISSIONIN G METHODE

    1. Particulars

    1.1 Ventilation Fan 3608 VPS 01Fan Unit : 1 Set

    Fan

    Manufacture : Viking Engineering / Meta Vent

    No. of Unit : 1 Set

    Model : Meta Vent 1400/11-11/D-36

    Air Volume : 120,000 Cmh

    Static Pressure : 350 Pa

    Fan Electric Motor

    Power Output : 37 kw

    Electric Source : 400V/3Ph/50Hz

    Speed : 960 rpm

    Space heater : 230V/1Ph/50Hz/60w

    C/W PTC Thermistor

    1.2 Ventilation Fan 3616 VPS 02

    Fan Unit : 1 Set

    Fan

    Manufacture : Viking Engineering / Meta Vent

    No. of Unit : 1 Set

    Fan Model : Meta Vent 1900/11-11/DX-29

  • 8/7/2019 SAT Renew Karimun

    7/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 7 of 24

    Air Volume : 200,000 Cmh

    Static Pressure : 350 Pa

    Fan Electric Motor

    Power Output : 55 kw

    Electric Source : 400V/3Ph/50Hz

    Speed : 720 rpm

    Space heater : 230V/1Ph/50Hz/80w

    C/W PTC Thermistor

    1.3 Electrical control panel fan 3608 VPS 01

    Electrical Control panel Unit : 1 Set

    Manufacture : Viking Engineering / Viking instrument

    No. of Unit : 1 Set

    Voltage : 400 Volt

    Current Amp : 66.5 Amp

    C/w Variable frequency drive Altivar 61 to control speed motor fan include

    temperature sensor, will be install on inside enclosure and outlet air on room.

    1.4 Electrical control panel fan 3616 VPS 02

    Electrical Control panel Unit : 1 Set

    Manufacture : Viking Engineering / Viking instrument

    No. of Unit : 1 Set

    Voltage : 400 Volt

    Current Amp : 99.4 Amp

    C/w Variable frequency drive Altivar 61 to control speed motor fan include

    temperature sensor, will be install on inside enclosure and outlet air on room.

  • 8/7/2019 SAT Renew Karimun

    8/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 8 of 24

    2. VENTILATION FAN TESTING

    After each mechanical ventilation system having been finished fan installation, power feeder termination

    and louver, silencer box, wire mash, short duct, flexible duct and discharge attenuator, pre-commissioning

    shall be performed clamp skid fan, fan rotation etc.

    The following ventilation items shall be observed under system operation:

    a) Working condition (vibration, noisy etc)

    b) Fan motor voltage

    c) Fan motor running current

    d) Running air flow

    e) Noisy running fan

    f) Temperature

    Before the ventilation test shall be proceed, to confirm the integrity of duct installation, inlet louver and

    discharge attenuator ventilating unit installation.

    During the above start up, air inlet louver, discharge attenuator to be kept fully open. After the supply fan

    start up, the supply air quantity to supply engine /generator. The air flow to be taken record air flow on

    outlet enclosure fan, the air flow obtained shall not be less than 90% of the design data.

    3. STARTING TEST

    Preparation of test: Before Start the ventilation fan check power voltage, 400AC must be

    powered up to the panel.

    Ventilation fan control Panel is Controlled by Schneider Electric Altivar 61, VFD Altivar 61 comes

    along with a display unit.

    The display unit with start/ stop buttons, but were disabled due to requirement of the Main

    Generator and Emergency Generator override control.

    Nevertheless, should there is requirement to stop of the fan in case Emergency. The Emergency

    push button can be use.

    No Out side

    temperature

    As per Required: 10C less

    than Outside Temperature

    Remarks

  • 8/7/2019 SAT Renew Karimun

    9/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 9 of 24

    1 35C 25C

    2 34C 24C

    3 33C 23C

    4 32C 22C

    5 31C 21C

    6 30C 20C Fan will run at minimum

    7 29C 20C Speed when the internal

    8 28C 20C Temperature reaches 20C

    9 27C 20C

    The fan speed will remain at 50Hz at all condition till the above required temperature is

    achieved. Once the internal temperature is achieved, the fan will run at 30Hz.

  • 8/7/2019 SAT Renew Karimun

    10/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 10 of 24

    ITEM DESCRIPTION CHECK

    4 .0 PREPARATION CHECK

    4.1 System checklist

    Refer to enclosure Air duct, discharge attenuator, silencer, fans and drawing

    before any checking.

    4.2 Mechanical Installation

    4.2.1 Mechanical completion reports (Enclosure)

    4.2.2 Mechanical completion reports (Discharge Attenuator)

    4.2.3 Mechanical Completion reports (Insulation Enclosure)

    4.2.4 Mechanical Completion reports (Clamp Skid Fans)

    4.3 Electrical Installation

    4.3.1 Electrical Completion reports (Cables Clamping)

    4.3.2 Electrical Completion reports (Cable Marking)

    4.3.3 Electrical Completion Reports (Cable Ladder)

    4.3.4 Electrical Completion reports (Cable Arrangement)

    4.4 Inspection by Vendor Service Engineer or Technical Representative

    The following checks and inspections shall be carried out by

    vendor or service engineer

    4.4.1 All the mechanical components of the system are installed to vendors

    specification

    4.4.2 All the electrical components of the system are installed to vendor

    specification

    4.3.3 Vendors service engineer or technical representative to verified that the system

    is ready and safe to be start-up and commissioning

  • 8/7/2019 SAT Renew Karimun

    11/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 11 of 24

    ITEM DESCRIPTION CHECK

    5.0

    PRE-COMMISSIONING PROCEDURE CHEKLIST

    5. 1 Air Duct

    5.1.1 Check enclosure leg mounting bolt should be fix and tight

    5.1.2 Check air inlet louver connection mounting bolt should be fix

    and tight

    5.1.3 Check perforated plate cover insulation enclosure should be fix

    5.1.4 Check silencer box connection should be fix and tight

    5.1.5 Check discharge attenuator connection should be fix and tight

    5 .2 Fans

    5.2.1 Check and confirm installation of fans.

    5.2.2 Verify nameplate for fans.

    5.2.3 Check fan housing and duct grounded should be properly, fix

    and tight.

    5.2.4 The fans and the other duct work accessories have been

    correctly/properly

  • 8/7/2019 SAT Renew Karimun

    12/23

  • 8/7/2019 SAT Renew Karimun

    13/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 13 of 24

    ITEM DESCRIPTION

    6.0 COMMISSIONING PROCEDURE

    6 .1 Operational Test

    By referring to the table 7.3 - 7.4 carry out the following procedures

    and record data.

    6 .2 Air Duct, Enclosure and Fans Performance Test

    6.2.1 Run the fans for a sufficient period of time

    6.2.2 Energize and check operation fans (see table 7.3.1, 7.3.2 and 7.4.1,

    7.4.2)

    6.2.3 Check for abnormal vibration and noise of fans

    6.2.4 The reading to be recorded after 1 hours of continuous operating the

    system.

  • 8/7/2019 SAT Renew Karimun

    14/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 14 of 24

    7.0 APPENDICES

  • 8/7/2019 SAT Renew Karimun

    15/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 15 of 24

    7.1 Functional Check list VFD Control Panel VPS 01 .

    N

    o.

    Description Che

    ck

    Remarks

    1 Power Supply:

    4 Ph, 400VAC, 220VAC, 50 Hz

    2 Each point function test with signal injection

    4-20mA Signal is injected to simulate the

    temperature Read out.

  • 8/7/2019 SAT Renew Karimun

    16/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 16 of 24

    3 Key button 0peration:

    Start, Stop, E-Stop, and all Other button

    tested.

    4 Alarm test to all point:

    Motor Overload, Motor Open Circuit, PTC

    Thermistor.

    5 Output Test for all points including trip and

    alarm lights:

    Light and Indication.

    6 Input test for signal:

    Motor speed test for High and Low Speed with

    simulated input current.

    7 Completed system function test:

    Yes / No

    8 Total number of point tested

    The output reflects as required 50Hz and

    30Hz.

    9 Test sticker applied:

    OK.

    7.2 Functional Check List VFD Control Panel VPS 02.

    N

    o.

    Description Che

    ck

    Remarks

    1 Power Supply:

    4 Ph, 400VAC, 220VAC, 50 Hz

    2 Each point function test with signal injection:

    4-20mA Signal is injected to simulate the

  • 8/7/2019 SAT Renew Karimun

    17/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 17 of 24

    temperature Read out.

    3 Key button 0peration:

    Start, Stop, E-Stop, and all Other button

    tested.

    4 Alarm test to all point:

    Motor Overload, Motor Open Circuit, PTC

    Thermistor.

    5 Output Test for all points including trip and

    alarm lights:

    Light and Indication.

    6 Input test for signal:

    Motor speed test for High and Low Speed with

    simulated input current.

    7 Completed system function test:

    Yes / No

    8 Total number of point tested

    The output reflects as required 50Hz and

    30Hz.

    9 Test sticker applied:

    OK.

  • 8/7/2019 SAT Renew Karimun

    18/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 18 of 24

  • 8/7/2019 SAT Renew Karimun

    19/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 19 of 24

    7.3. COMMISSIONING CHECKLIST AND RECORD FAN 3608 VPS 01

    NO DESCRIPTION Check/Supply REMARKS

    1Power supply (24VDC / 110VAC / 220 VAC/Other - state

    400VAC

    2 Key Button & OperationStart

    Stop

    Main Gen Stop.

    EmergencyGen. StopOverload

    Motor O/C

    ThermistorOpen/High(3K)

    ThermistorShort/toolow(50)

    3 Each Point function test with signal injectionExternal SensorInternal SensorMotor Speed

    33 33 33

    24 23 22

    External SensorInternal SensorMotor Speed

    30 30 30

    21 20 19

    External SensorInternal SensorMotor Speed

    29 29 29

    20 19 18

  • 8/7/2019 SAT Renew Karimun

    20/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 20 of 24

    INSPECTION RESULT

    PASS WITHIN LIMITS PASS BY CONCESSION RELEASED FOR

    USE/DELIVERYYES NO YES NO YES NO

    7.3.1 Commissioning Record Fan 3608 -

    VPS 01

    Item Description

    Insulat

    ion

    Resistan

    t

    Remark

    s

    Design

    Data Measured M

    Fan Motor Power (Kw) 37.0

    Fan Motor Power

    supply (V/ph/Hz)400/3/50

    Fan Motor Current (A) 66.8

    7.3.2 Running Record Fan 3608 - VPS 01

    Frequency Voltage Current Velocity VolumeNoise(dbB)

    ( Hz ) ( Volt )

    ( Amp

    ) ( m/s )

    ( Cmh

    ) 0 - 5 m 0-10 m 0 - 15 m 0 - 20 m

  • 8/7/2019 SAT Renew Karimun

    21/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 21 of 24

    TESTED BY APPROVED BY (if applicable)

    Name & Signature Date & StampName & Signature Date

    & Stamp

    7.4 COMMISSIONING CHECKLIST AND RECORD FAN 3616 VPS 02

    NO DESCRIPTION Check/Supply REMARKS

    1Power supply (24VDC / 110VAC / 220 VAC/Other - state

    400VAC

    2 Key Button & OperationStart

    Stop

    Main Gen Stop.

    EmergencyGen. Stop

    Overload

    Motor O/C

    ThermistorOpen/High(3K)

    ThermistorShort/toolow(50)

    3 Each Point function test with signal injectionExternal Sensor

    Internal SensorMotor Speed

    33 33 33

    24 23 22

    External SensorInternal SensorMotor Speed

    30 30 30

    21 20 19

    External SensorInternal SensorMotor Speed

    29 29 29

    20 19 18

    7.4.1 Commissioning Record Fan 3616 -

    VPS 02

    Item Description Insulat

    ion

    Resistan

    t

    Remark

    s

    Design

    Data

    Measured M

    Fan Motor Power (Kw) 55.0

    Fan Motor Power

    supply (V/ph/Hz)400/3/50

    Fan Motor Current (A) 99.4

  • 8/7/2019 SAT Renew Karimun

    22/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 22 of 23

    INSPECTION RESULT

    PASS WITHIN LIMITS PASS BY CONCESSION RELEASED FORUSE/DELIVERY

    YES NO YES NO YES NO

    7.4.2 Running Record Fan 3616 - VPS 02

    Freque

    ncy

    Volta

    ge

    Curre

    nt

    Veloci

    ty

    Volu

    meNoise

    (dbB)

    ( Hz ) ( Volt )

    ( Amp

    ) ( m/s )

    ( Cmh

    ) 0 - 5 m 0-10 m 0 - 15 m 0 - 20 m

    TESTED BY APPROVED BY (if applicable)

    Name & Signature Date & StampName & Signature Date

    & Stamp

  • 8/7/2019 SAT Renew Karimun

    23/23

    PT.VIKING

    ENGINEERING

    KARIMUN YARD CONSTRUCTIONPROJECT

    SITE ACCEPTANCE TEST

    (AIR VANTILATION SYSTEM FOR POWERPLANT)

    Date: 21-12-2010 Doc no. 863013-VPS-PQM -C-DS-0002 Rev. 0 Page 23 of 23

    ACCEPTANCE

    The Equipments/ system covered under this commissioning procedure has been

    tested and found to be working satisfactory manner in accordance with the test and

    inspection herein.

    Representative Name Signature Date

    Owner : ______________ ___________________ _________________

    Viking : ______________ ___________________ _________________