Route your Schneider TAC Xenta 411 pulse readings to Wattics Wattics Ltd | wattics.com | [email protected] | 1 Are you ready for energy savings? Enable our cloud-based energy analytics and dashboard for your pulse meters connected to a Schneider TAC Xenta 411 module , to discover, measure and verify savings in the premises you manage. The Schneider TAC Xenta 411 digital input modules are used as expansion modules for the TAC Xenta controller. They have ten digital inputs generally used as pulse counters for pulse meters deployed within your site. You can now reroute your Xenta 411’s pulse readings to Wattics via our Octopus gateway in a few steps. It is assumed that your meters and Xenta 411 are already wired and collecting measurements. If not, read and understand Schneider manuals for installing, operating, or maintaining your Xenta 411. Installation and program procedures must be carried out and inspected by qualified personnel. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with this product. 1 Pulse connection

Route your Schneider TAC Xenta 411 pulse readings to Wattics

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 1

Are you ready for energy savings Enable our cloud-based energy analytics and dashboardfor your pulse meters connected to a Schneider TAC Xenta 411 module to discover measureand verify savings in the premises you manage

The Schneider TAC Xenta 411 digital input modules are used as expansion modules for theTAC Xenta controller They have ten digital inputs generally used as pulse counters for pulsemeters deployed within your site You can now reroute your Xenta 411rsquos pulse readings toWattics via our Octopus gateway in a few steps

It is assumed that your meters and Xenta 411 are already wired and collectingmeasurements If not read and understand Schneider manuals for installing operating ormaintaining your Xenta 411 Installation and program procedures must be carried out andinspected by qualified personnel Qualified personnel are those who based on their trainingand experience are capable of identifying risks and avoiding potential hazards when workingwith this product

1 Pulse connection

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 2

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 3

Make sure that all devices are powered off before any wiring is done

1 Power Octopus and Xenta 411 off2 Connect the GND from Octopus to the GND of Xenta 411 (Xenta 411 power supply mustnot exceed 24VDC or that could damage the Octopus)3 Wire pulse lines from Xenta 411 XN inputs to Octopus inputs (X1 to X10)4 Power up both units

The Octopus Gateway comes with 6 inputs If more than 6 pulse meters are connected toyour Xenta 411 or if you have multiple Xenta 411 modules you can use an Octopus IOextension module to enable an additional 16 inputs

2 Octopus Software Configuration

21 Download the Octopus Software Tool (Windows)

Request the Octopus Software Tool Download Link

22 Connect your Octopus to your computerConnect your computer running the Octopus Software Tool to the same network as theOctopus

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 4

23 Configure your deployment setup Launch the WatticsToolexe Software Tool and create a new Branch using the ldquo+rdquo button Fillthe ldquoBranch Namerdquo field with a short name for your project and insert the serial number ofyour Octopus Gateway that you can find on its sticker or on its box

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 5

Select the correct timezone in the Timezone dropdown menu If you cannot find your cityselect the closest city to your site location which is in the same timezone

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 6

Click on Network Configuration to enable Internet access for your Octopus You can enableDHCP to get the Octopus to connect to the Internet automatically (Tick DHCP click onDiscover and click on Set when the Octopus IP address is shown) For LAN access withmanually assigned static IP addresses you will need to get network parameters from your ITdepartment and enter them here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 7

If you use a GPRS sim card for Internet access you must enter your APN name and APNcredentials here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 8

You must now set up the Wattics URL where data collected will be sent to Click on Servicesbutton and set the following

Enable Service 1Set Wattics as Service NameEnter octopuswatticscom as Service Host Address (IMPORTANT When using GPRSSim cards or when your firewall does not support the use of URLs you must enter5250202103 as Service Host Address)Set 4401 as PortClick OK

You must click OK to create the Branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 9

Once back to the Octopus Software Tool landing page you can select your Branch and clickthe ldquoAddrdquo button on the right side to register the pulse meters connected to the Octopus

Select the suitable entry in the drop-down menu and click Add You should select Electricity ifelectrical meters are connected to the Xenta 411 and Generic for other types of metersChoosing Interval will get the Octopus to push interval pulse counts to Wattics whileAccumulated will get the Octopus to push total pulse counts to Wattics Unless specifiedchoose the Interval entry

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 10

At the next screen you must enter a device name and select the input number to which thepulse line is connected

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 11

The device name must be a unique name identifier Unless a convention has been pre-agreedwith us we ask you to use the following naming convention for choosing your unique nameidentifiers

OctopusID-counter nameofdevice

(for example use 230007E7-1 Plantroom for the Plantroom meter if this is the first deviceconfigured via the Octopus Gateway ID 230007E7 and if Plantroom is the name you want tosee in the dashboard for that meter The next device will use the -2 counter extension etc)

Make sure to insert a space between OctopusID-counter and nameofdevice

Click OK to save your configuration The device now appears in the list of devices registeredwithin your branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 2: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 2

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 3

Make sure that all devices are powered off before any wiring is done

1 Power Octopus and Xenta 411 off2 Connect the GND from Octopus to the GND of Xenta 411 (Xenta 411 power supply mustnot exceed 24VDC or that could damage the Octopus)3 Wire pulse lines from Xenta 411 XN inputs to Octopus inputs (X1 to X10)4 Power up both units

The Octopus Gateway comes with 6 inputs If more than 6 pulse meters are connected toyour Xenta 411 or if you have multiple Xenta 411 modules you can use an Octopus IOextension module to enable an additional 16 inputs

2 Octopus Software Configuration

21 Download the Octopus Software Tool (Windows)

Request the Octopus Software Tool Download Link

22 Connect your Octopus to your computerConnect your computer running the Octopus Software Tool to the same network as theOctopus

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 4

23 Configure your deployment setup Launch the WatticsToolexe Software Tool and create a new Branch using the ldquo+rdquo button Fillthe ldquoBranch Namerdquo field with a short name for your project and insert the serial number ofyour Octopus Gateway that you can find on its sticker or on its box

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 5

Select the correct timezone in the Timezone dropdown menu If you cannot find your cityselect the closest city to your site location which is in the same timezone

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 6

Click on Network Configuration to enable Internet access for your Octopus You can enableDHCP to get the Octopus to connect to the Internet automatically (Tick DHCP click onDiscover and click on Set when the Octopus IP address is shown) For LAN access withmanually assigned static IP addresses you will need to get network parameters from your ITdepartment and enter them here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 7

If you use a GPRS sim card for Internet access you must enter your APN name and APNcredentials here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 8

You must now set up the Wattics URL where data collected will be sent to Click on Servicesbutton and set the following

Enable Service 1Set Wattics as Service NameEnter octopuswatticscom as Service Host Address (IMPORTANT When using GPRSSim cards or when your firewall does not support the use of URLs you must enter5250202103 as Service Host Address)Set 4401 as PortClick OK

You must click OK to create the Branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 9

Once back to the Octopus Software Tool landing page you can select your Branch and clickthe ldquoAddrdquo button on the right side to register the pulse meters connected to the Octopus

Select the suitable entry in the drop-down menu and click Add You should select Electricity ifelectrical meters are connected to the Xenta 411 and Generic for other types of metersChoosing Interval will get the Octopus to push interval pulse counts to Wattics whileAccumulated will get the Octopus to push total pulse counts to Wattics Unless specifiedchoose the Interval entry

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 10

At the next screen you must enter a device name and select the input number to which thepulse line is connected

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 11

The device name must be a unique name identifier Unless a convention has been pre-agreedwith us we ask you to use the following naming convention for choosing your unique nameidentifiers

OctopusID-counter nameofdevice

(for example use 230007E7-1 Plantroom for the Plantroom meter if this is the first deviceconfigured via the Octopus Gateway ID 230007E7 and if Plantroom is the name you want tosee in the dashboard for that meter The next device will use the -2 counter extension etc)

Make sure to insert a space between OctopusID-counter and nameofdevice

Click OK to save your configuration The device now appears in the list of devices registeredwithin your branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 3: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 3

Make sure that all devices are powered off before any wiring is done

1 Power Octopus and Xenta 411 off2 Connect the GND from Octopus to the GND of Xenta 411 (Xenta 411 power supply mustnot exceed 24VDC or that could damage the Octopus)3 Wire pulse lines from Xenta 411 XN inputs to Octopus inputs (X1 to X10)4 Power up both units

The Octopus Gateway comes with 6 inputs If more than 6 pulse meters are connected toyour Xenta 411 or if you have multiple Xenta 411 modules you can use an Octopus IOextension module to enable an additional 16 inputs

2 Octopus Software Configuration

21 Download the Octopus Software Tool (Windows)

Request the Octopus Software Tool Download Link

22 Connect your Octopus to your computerConnect your computer running the Octopus Software Tool to the same network as theOctopus

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 4

23 Configure your deployment setup Launch the WatticsToolexe Software Tool and create a new Branch using the ldquo+rdquo button Fillthe ldquoBranch Namerdquo field with a short name for your project and insert the serial number ofyour Octopus Gateway that you can find on its sticker or on its box

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 5

Select the correct timezone in the Timezone dropdown menu If you cannot find your cityselect the closest city to your site location which is in the same timezone

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 6

Click on Network Configuration to enable Internet access for your Octopus You can enableDHCP to get the Octopus to connect to the Internet automatically (Tick DHCP click onDiscover and click on Set when the Octopus IP address is shown) For LAN access withmanually assigned static IP addresses you will need to get network parameters from your ITdepartment and enter them here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 7

If you use a GPRS sim card for Internet access you must enter your APN name and APNcredentials here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 8

You must now set up the Wattics URL where data collected will be sent to Click on Servicesbutton and set the following

Enable Service 1Set Wattics as Service NameEnter octopuswatticscom as Service Host Address (IMPORTANT When using GPRSSim cards or when your firewall does not support the use of URLs you must enter5250202103 as Service Host Address)Set 4401 as PortClick OK

You must click OK to create the Branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 9

Once back to the Octopus Software Tool landing page you can select your Branch and clickthe ldquoAddrdquo button on the right side to register the pulse meters connected to the Octopus

Select the suitable entry in the drop-down menu and click Add You should select Electricity ifelectrical meters are connected to the Xenta 411 and Generic for other types of metersChoosing Interval will get the Octopus to push interval pulse counts to Wattics whileAccumulated will get the Octopus to push total pulse counts to Wattics Unless specifiedchoose the Interval entry

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 10

At the next screen you must enter a device name and select the input number to which thepulse line is connected

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 11

The device name must be a unique name identifier Unless a convention has been pre-agreedwith us we ask you to use the following naming convention for choosing your unique nameidentifiers

OctopusID-counter nameofdevice

(for example use 230007E7-1 Plantroom for the Plantroom meter if this is the first deviceconfigured via the Octopus Gateway ID 230007E7 and if Plantroom is the name you want tosee in the dashboard for that meter The next device will use the -2 counter extension etc)

Make sure to insert a space between OctopusID-counter and nameofdevice

Click OK to save your configuration The device now appears in the list of devices registeredwithin your branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 4: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 4

23 Configure your deployment setup Launch the WatticsToolexe Software Tool and create a new Branch using the ldquo+rdquo button Fillthe ldquoBranch Namerdquo field with a short name for your project and insert the serial number ofyour Octopus Gateway that you can find on its sticker or on its box

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 5

Select the correct timezone in the Timezone dropdown menu If you cannot find your cityselect the closest city to your site location which is in the same timezone

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 6

Click on Network Configuration to enable Internet access for your Octopus You can enableDHCP to get the Octopus to connect to the Internet automatically (Tick DHCP click onDiscover and click on Set when the Octopus IP address is shown) For LAN access withmanually assigned static IP addresses you will need to get network parameters from your ITdepartment and enter them here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 7

If you use a GPRS sim card for Internet access you must enter your APN name and APNcredentials here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 8

You must now set up the Wattics URL where data collected will be sent to Click on Servicesbutton and set the following

Enable Service 1Set Wattics as Service NameEnter octopuswatticscom as Service Host Address (IMPORTANT When using GPRSSim cards or when your firewall does not support the use of URLs you must enter5250202103 as Service Host Address)Set 4401 as PortClick OK

You must click OK to create the Branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 9

Once back to the Octopus Software Tool landing page you can select your Branch and clickthe ldquoAddrdquo button on the right side to register the pulse meters connected to the Octopus

Select the suitable entry in the drop-down menu and click Add You should select Electricity ifelectrical meters are connected to the Xenta 411 and Generic for other types of metersChoosing Interval will get the Octopus to push interval pulse counts to Wattics whileAccumulated will get the Octopus to push total pulse counts to Wattics Unless specifiedchoose the Interval entry

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 10

At the next screen you must enter a device name and select the input number to which thepulse line is connected

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 11

The device name must be a unique name identifier Unless a convention has been pre-agreedwith us we ask you to use the following naming convention for choosing your unique nameidentifiers

OctopusID-counter nameofdevice

(for example use 230007E7-1 Plantroom for the Plantroom meter if this is the first deviceconfigured via the Octopus Gateway ID 230007E7 and if Plantroom is the name you want tosee in the dashboard for that meter The next device will use the -2 counter extension etc)

Make sure to insert a space between OctopusID-counter and nameofdevice

Click OK to save your configuration The device now appears in the list of devices registeredwithin your branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 5: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 5

Select the correct timezone in the Timezone dropdown menu If you cannot find your cityselect the closest city to your site location which is in the same timezone

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 6

Click on Network Configuration to enable Internet access for your Octopus You can enableDHCP to get the Octopus to connect to the Internet automatically (Tick DHCP click onDiscover and click on Set when the Octopus IP address is shown) For LAN access withmanually assigned static IP addresses you will need to get network parameters from your ITdepartment and enter them here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 7

If you use a GPRS sim card for Internet access you must enter your APN name and APNcredentials here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 8

You must now set up the Wattics URL where data collected will be sent to Click on Servicesbutton and set the following

Enable Service 1Set Wattics as Service NameEnter octopuswatticscom as Service Host Address (IMPORTANT When using GPRSSim cards or when your firewall does not support the use of URLs you must enter5250202103 as Service Host Address)Set 4401 as PortClick OK

You must click OK to create the Branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 9

Once back to the Octopus Software Tool landing page you can select your Branch and clickthe ldquoAddrdquo button on the right side to register the pulse meters connected to the Octopus

Select the suitable entry in the drop-down menu and click Add You should select Electricity ifelectrical meters are connected to the Xenta 411 and Generic for other types of metersChoosing Interval will get the Octopus to push interval pulse counts to Wattics whileAccumulated will get the Octopus to push total pulse counts to Wattics Unless specifiedchoose the Interval entry

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 10

At the next screen you must enter a device name and select the input number to which thepulse line is connected

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 11

The device name must be a unique name identifier Unless a convention has been pre-agreedwith us we ask you to use the following naming convention for choosing your unique nameidentifiers

OctopusID-counter nameofdevice

(for example use 230007E7-1 Plantroom for the Plantroom meter if this is the first deviceconfigured via the Octopus Gateway ID 230007E7 and if Plantroom is the name you want tosee in the dashboard for that meter The next device will use the -2 counter extension etc)

Make sure to insert a space between OctopusID-counter and nameofdevice

Click OK to save your configuration The device now appears in the list of devices registeredwithin your branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 6: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 6

Click on Network Configuration to enable Internet access for your Octopus You can enableDHCP to get the Octopus to connect to the Internet automatically (Tick DHCP click onDiscover and click on Set when the Octopus IP address is shown) For LAN access withmanually assigned static IP addresses you will need to get network parameters from your ITdepartment and enter them here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 7

If you use a GPRS sim card for Internet access you must enter your APN name and APNcredentials here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 8

You must now set up the Wattics URL where data collected will be sent to Click on Servicesbutton and set the following

Enable Service 1Set Wattics as Service NameEnter octopuswatticscom as Service Host Address (IMPORTANT When using GPRSSim cards or when your firewall does not support the use of URLs you must enter5250202103 as Service Host Address)Set 4401 as PortClick OK

You must click OK to create the Branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 9

Once back to the Octopus Software Tool landing page you can select your Branch and clickthe ldquoAddrdquo button on the right side to register the pulse meters connected to the Octopus

Select the suitable entry in the drop-down menu and click Add You should select Electricity ifelectrical meters are connected to the Xenta 411 and Generic for other types of metersChoosing Interval will get the Octopus to push interval pulse counts to Wattics whileAccumulated will get the Octopus to push total pulse counts to Wattics Unless specifiedchoose the Interval entry

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 10

At the next screen you must enter a device name and select the input number to which thepulse line is connected

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 11

The device name must be a unique name identifier Unless a convention has been pre-agreedwith us we ask you to use the following naming convention for choosing your unique nameidentifiers

OctopusID-counter nameofdevice

(for example use 230007E7-1 Plantroom for the Plantroom meter if this is the first deviceconfigured via the Octopus Gateway ID 230007E7 and if Plantroom is the name you want tosee in the dashboard for that meter The next device will use the -2 counter extension etc)

Make sure to insert a space between OctopusID-counter and nameofdevice

Click OK to save your configuration The device now appears in the list of devices registeredwithin your branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 7: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 7

If you use a GPRS sim card for Internet access you must enter your APN name and APNcredentials here

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 8

You must now set up the Wattics URL where data collected will be sent to Click on Servicesbutton and set the following

Enable Service 1Set Wattics as Service NameEnter octopuswatticscom as Service Host Address (IMPORTANT When using GPRSSim cards or when your firewall does not support the use of URLs you must enter5250202103 as Service Host Address)Set 4401 as PortClick OK

You must click OK to create the Branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 9

Once back to the Octopus Software Tool landing page you can select your Branch and clickthe ldquoAddrdquo button on the right side to register the pulse meters connected to the Octopus

Select the suitable entry in the drop-down menu and click Add You should select Electricity ifelectrical meters are connected to the Xenta 411 and Generic for other types of metersChoosing Interval will get the Octopus to push interval pulse counts to Wattics whileAccumulated will get the Octopus to push total pulse counts to Wattics Unless specifiedchoose the Interval entry

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 10

At the next screen you must enter a device name and select the input number to which thepulse line is connected

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 11

The device name must be a unique name identifier Unless a convention has been pre-agreedwith us we ask you to use the following naming convention for choosing your unique nameidentifiers

OctopusID-counter nameofdevice

(for example use 230007E7-1 Plantroom for the Plantroom meter if this is the first deviceconfigured via the Octopus Gateway ID 230007E7 and if Plantroom is the name you want tosee in the dashboard for that meter The next device will use the -2 counter extension etc)

Make sure to insert a space between OctopusID-counter and nameofdevice

Click OK to save your configuration The device now appears in the list of devices registeredwithin your branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 8: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 8

You must now set up the Wattics URL where data collected will be sent to Click on Servicesbutton and set the following

Enable Service 1Set Wattics as Service NameEnter octopuswatticscom as Service Host Address (IMPORTANT When using GPRSSim cards or when your firewall does not support the use of URLs you must enter5250202103 as Service Host Address)Set 4401 as PortClick OK

You must click OK to create the Branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 9

Once back to the Octopus Software Tool landing page you can select your Branch and clickthe ldquoAddrdquo button on the right side to register the pulse meters connected to the Octopus

Select the suitable entry in the drop-down menu and click Add You should select Electricity ifelectrical meters are connected to the Xenta 411 and Generic for other types of metersChoosing Interval will get the Octopus to push interval pulse counts to Wattics whileAccumulated will get the Octopus to push total pulse counts to Wattics Unless specifiedchoose the Interval entry

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 10

At the next screen you must enter a device name and select the input number to which thepulse line is connected

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 11

The device name must be a unique name identifier Unless a convention has been pre-agreedwith us we ask you to use the following naming convention for choosing your unique nameidentifiers

OctopusID-counter nameofdevice

(for example use 230007E7-1 Plantroom for the Plantroom meter if this is the first deviceconfigured via the Octopus Gateway ID 230007E7 and if Plantroom is the name you want tosee in the dashboard for that meter The next device will use the -2 counter extension etc)

Make sure to insert a space between OctopusID-counter and nameofdevice

Click OK to save your configuration The device now appears in the list of devices registeredwithin your branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 9: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 9

Once back to the Octopus Software Tool landing page you can select your Branch and clickthe ldquoAddrdquo button on the right side to register the pulse meters connected to the Octopus

Select the suitable entry in the drop-down menu and click Add You should select Electricity ifelectrical meters are connected to the Xenta 411 and Generic for other types of metersChoosing Interval will get the Octopus to push interval pulse counts to Wattics whileAccumulated will get the Octopus to push total pulse counts to Wattics Unless specifiedchoose the Interval entry

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 10

At the next screen you must enter a device name and select the input number to which thepulse line is connected

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 11

The device name must be a unique name identifier Unless a convention has been pre-agreedwith us we ask you to use the following naming convention for choosing your unique nameidentifiers

OctopusID-counter nameofdevice

(for example use 230007E7-1 Plantroom for the Plantroom meter if this is the first deviceconfigured via the Octopus Gateway ID 230007E7 and if Plantroom is the name you want tosee in the dashboard for that meter The next device will use the -2 counter extension etc)

Make sure to insert a space between OctopusID-counter and nameofdevice

Click OK to save your configuration The device now appears in the list of devices registeredwithin your branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 10: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 10

At the next screen you must enter a device name and select the input number to which thepulse line is connected

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 11

The device name must be a unique name identifier Unless a convention has been pre-agreedwith us we ask you to use the following naming convention for choosing your unique nameidentifiers

OctopusID-counter nameofdevice

(for example use 230007E7-1 Plantroom for the Plantroom meter if this is the first deviceconfigured via the Octopus Gateway ID 230007E7 and if Plantroom is the name you want tosee in the dashboard for that meter The next device will use the -2 counter extension etc)

Make sure to insert a space between OctopusID-counter and nameofdevice

Click OK to save your configuration The device now appears in the list of devices registeredwithin your branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 11: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 11

The device name must be a unique name identifier Unless a convention has been pre-agreedwith us we ask you to use the following naming convention for choosing your unique nameidentifiers

OctopusID-counter nameofdevice

(for example use 230007E7-1 Plantroom for the Plantroom meter if this is the first deviceconfigured via the Octopus Gateway ID 230007E7 and if Plantroom is the name you want tosee in the dashboard for that meter The next device will use the -2 counter extension etc)

Make sure to insert a space between OctopusID-counter and nameofdevice

Click OK to save your configuration The device now appears in the list of devices registeredwithin your branch

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 12: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 12

You can now add more meters if you have other pulse lines connected to the Octopus

Once you have all your devices created you must deploy your configuration onto theOctopus Gateway Select your branch and click on the Deploy button

On the pop up window leave the default settings and click on Deploy

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 13: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 13

Your Octopus Gateway is now configured for data collection from all the devices connectedWe recommend that you save your project should you need to modify the configuration as alater stage You will then be able to update an existing project when you add new meters

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 14: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 14

5 ndash Check that the Octopus is collecting data from the meter(s)

Launch the CDTexe Software Tool enter your Octopus serial number and click on Connect

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 15: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 15

Once connected click on the Real-Time tab and verify that you are getting new event logsfor the various electrical parameters every few seconds This confirms that the Octopus isgetting the pulse readings from the meter You can then close the CDT tool Verify yourproject file settings if you donrsquot see any data coming in

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17

+353 (0)1415 1242 | infowatticscom | Contact us

Page 16: Route your Schneider TAC Xenta 411 pulse readings to Wattics

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 16

5 ndash Submit your Octopus project to Wattics Submit your Octopus iwtx project file to Wattics via

Octopus iwtx Project File Submission Form

Wattics will use your project file to double check that the setup is correct and that data isbeing received from your Octopus Gateway unit and correctly showing in your dashboardYou will then receive access to your Wattics dashboard and from then on you will be able tolog in to your Wattics Dashboard at httpdashwatticscom and get started

Route your Schneider TAC Xenta 411 pulse readings to Wattics

Wattics Ltd | watticscom | supportwatticscom | 17