108
Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount 3051SMV MultiVariable Transmitter with FOUNDATION Fieldbus protocol

Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

May 2016

Rosemount™ 3051SMV MultiVariable™ Transmitterwith FOUNDATION™ Fieldbus protocol

Page 2: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with
Page 3: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

ContentsMay 2016

Contents

1Section 1: Introduction

1.1 Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.2 Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.3 Product recycling/disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2Section 2: Configuration2.1 Section overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.3 Flow configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.3.1 Engineering Assistant 5.5.1 ver. 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.3.2 Installing Engineering Assistant 5.5.1 ver. 2 Stand-Alone. . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.3.3 Launching Engineering Assistant 5.5.1 ver. 2 and connecting to the transmitter . . . . . 6

2.3.4 Creating a flow configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

2.3.5 Sending a flow configuration to the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.3.6 Mass flow test calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.4 Variable configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.4.1 Units configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.4.2 Mass flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2.4.3 Differential pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2.4.4 Static pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2.4.5 Process temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

2.4.6 Variable simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

2.5 Device configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

2.5.1 Display configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

2.5.2 Write lock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

2.6 Device capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

2.6.1 General block information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

2.6.2 Link active scheduler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

2.6.3 Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

2.6.4 Node address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

2.6.5 Block instantiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

3Section 3: Installation3.1 Section overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

3.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

iiiContents

Page 4: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

ContentsMay 2016

3.3 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

3.3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

3.3.2 Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

3.3.3 Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

3.4 Steps required for quick installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

3.4.1 Mount the transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

3.4.2 Tagging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

3.4.3 Consider housing rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

3.4.4 Rotate the LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

3.4.5 Set the switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

3.4.6 Wire, ground, and power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

3.4.7 Signal wiring and shield grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

3.4.8 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

3.4.9 Power conditioner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

3.4.10 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

3.4.11 Signal termination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

3.4.12 Install optional process temperature input (Pt 100 RTD Sensor) . . . . . . . . . . . . . . . . . . 30

3.5 Rosemount 305 and 304 Manifolds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

3.5.1 Rosemount 305 Integral Manifold installation procedure . . . . . . . . . . . . . . . . . . . . . . . . 32

3.5.2 Rosemount 304 Traditional Manifold installation procedure . . . . . . . . . . . . . . . . . . . . . 32

3.5.3 Manifold operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

4Section 4: Operation and Maintenance4.1 Section overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

4.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

4.3 Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

4.3.1 Calibration overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

4.3.2 Sensor trim overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

4.3.3 Determining necessary sensor trims. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

4.3.4 Types of pressure trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

4.3.5 Restore factory calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

4.3.6 Differential pressure sensor calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

4.3.7 Static pressure sensor calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

4.3.8 Process temperature sensor calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

4.4 Field upgrades and replacements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

4.4.1 Disassembly considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

4.4.2 Housing assembly including electronics board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

4.4.3 Terminal block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

iv Contents

Page 5: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

ContentsMay 2016

4.4.4 LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

4.4.5 Flange and drain vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

5Section 5: Troubleshooting5.1 Section overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

5.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

5.3 Measurement troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

5.3.1 Fill fluid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

5.4 Communication troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

5.4.1 Alarms and conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

5.5 Service support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

AAppendix A: Specifications and Reference DataA.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

A.1.1 Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

A.1.2 Functional specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

A.1.3 Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

A.2 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

A.3 Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

A.4 Spare parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

A.5 Function block information and location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

BAppendix B: Product CertificationsB.1 European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

B.2 Ordinary Location Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

B.3 Installing Equipment in North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

B.4 USA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

B.5 Canada . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

B.6 Europe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

B.7 International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

B.8 Brazil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

B.9 China . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

B.10 EAC – Belarus, Kazakhstan, Russia. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

B.11 Japan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

B.12 Republic of Korea . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

B.13 Combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

B.14 Additional certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

B.15 Installation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

vContents

Page 6: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

vi

Reference Manual00809-0100-4853, Rev AA

ContentsMay 2016

Contents

Page 7: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

Title PageMay 2016

Rosemount™ 3051S MultiVariable™ Transmitter

The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.

For information on Rosemount nuclear-qualified products, contact the local Emerson™ Process Management Sales Representative.

Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of and understand the hazard. If the product being returned was exposed to a hazardous substance as defined by OSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardous substance identified must be included with the returned goods.

iTitle Page

Page 8: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

Title PageMay 2016

Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure the contents are fully understood before installing, using, or maintaining this product.

For technical assistance, contacts are listed below:

Technical support, quoting, and order-related questions

United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)

Asia Pacific- 65 777 8211

Europe/ Middle East/ Africa - 49 (8153) 9390

Equipment service needs

North American Response Center

1-800-654-7768 (24 hours—includes Canada)

Outside of these areas, contact the local Emerson Process Management representative.

Explosions could result in death or serious injury.

Do not remove the transmitter cover in explosive atmospheres when the circuit is live.

Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.

Before connecting a communicator in an explosive atmosphere, make sure the instruments in the segment are installed in accordance with intrinsically safe or non-incendive field wiring practices.

Both transmitter covers must be fully engaged to meet explosion-proof requirements.

Failure to follow these installation guidelines could result in death or serious injury.

Make sure only qualified personnel perform the installation.

Electrical shock could cause death or serious injury.

If the sensor is installed in a high-voltage environment and a fault or installation error occurs, high voltage may be present on the transmitter leads and terminals.

Use extreme caution when making contact with the leads and terminals.

Process leaks could result in death or serious injury.

Install and tighten all four flange bolts before applying pressure.

Do not attempt to loosen or remove flange bolts while the transmitter is in service.

Replacement equipment or spare parts not approved by Emerson Process Management for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.

Use only bolts supplied or sold by Emerson Process Management as spare parts.

Improper assembly of manifolds to traditional flange can damage sensor module.

For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact module housing.

Sensor module and electronics housing must have equivalent approval labeling in order to maintain hazardous location approvals.

When upgrading, verify sensor module and electronics housing certifications are equivalent. Differences in temperature class ratings may exist, in which case the complete assembly takes the lowest of the individual component temperature classes (for example, a T4/T5 rated electronics housing assembled to a T4 rated sensor module is a T4 rated transmitter.)

ii Title Page

Page 9: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

IntroductionMay 2016

Section 1 Introduction

1.1 Using this manualThe sections in this manual provide information on installing, operating, and maintaining the Rosemount™ 3051S MultiVariable™ FOUNDATION™ Fieldbus Transmitter (3051SMV). The sections are organized as follows:

Section 2: Configuration provides instruction on commissioning and operating the Rosemount 3051SMV and information on flow configuration and device configuration.

Section 3: Installation contains mechanical and electrical installation instructions.

Section 4: Operation and Maintenance contains operation and maintenance techniques.

Section 5: Troubleshooting provides troubleshooting techniques for the most common operating problems.

Appendix A: Specifications and Reference Data supplies reference and specification data, as well as ordering information.

Appendix B: Product Certifications contains intrinsic safety approval information, European ATEX directive information, and approval drawings.

1.2 Product overviewThis manual covers the Rosemount 3051SMV FOUNDATION Fieldbus Transmitter. The device measures differential pressure, static pressure and process temperature and has the capability to calculate mass flow.

The following transmitters are covered in this manual.

Table 1-1. Rosemount 3051SMV Fully Compensated Mass Flow (M) Transmitter

Measurement type Description

1 Differential Pressure, Static Pressure, Temperature

2 Differential Pressure and Static Pressure

Table 1-2. Rosemount 3051SMV Process Variables Only (P) Transmitter

Measurement type Description

1 Differential Pressure, Static Pressure, Temperature

2 Differential Pressure and Static Pressure

3Introduction

Page 10: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

IntroductionMay 2016

Table 1-3. Device Driver Information

Figure 1-1. Transmitter Data Flow

1.3 Product recycling/disposalRecycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations.

Release date

Device identification Device driver identificationReview

instructionsReview

functionality

NAMUR hardware revision(1)

1. NAMUR Revision is located on the hardware tag of the device. Differences in level 3 changes, signified above by xx, represent minor product changes as defined per NE53. Compatibility and functionality are preserved and product can be used interchangeably.

NAMUR software

revision(1)

FOUNDATION Fieldbus

software revision

FOUNDATION Fieldbus universal revision

Device revision(2)(3)

2. FOUNDATION Fieldbus device revision can be read using a FOUNDATION Fieldbus capable configuration tool. Value shown is minimum revision that could correspond to NAMUR Revisions.

3. Device driver file names use device and DD revision. To access new functionality, the new Device Driver must be downloaded. It is recommended to download new Device Driver files to ensure full functionality.

Manual document

number

Change description

May-16 1.0.xx 1.0.xx 1.0.2 6.1.2 1 00809-0100-4853None: Initial

Product Release

Measuredprocessinputs

DPPT

A/D Micro FF communications output

4 Introduction

Page 11: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

ConfigurationMay 2016

Section 2 Configuration

Flow configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6Variable configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11Device configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14Device capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15Node address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16Block instantiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16

2.1 Section overviewThis section contains information for the flow and device configuration of the Rosemount™ 3051S MultiVariable™ FOUNDATION™ Fieldbus Transmitter (3051SMV). Each FOUNDATION Fieldbus host or configuration tool has different ways of displaying and performing operations. Some hosts will use Device Descriptions (DD) and DD methods to complete device configuration and will display data consistently across platforms.

The DD can be found on the FieldComm Group website at FieldCommGroup.org. There is no requirement that a host or configuration tool support the features in the DD. For DeltaV™ users, the DD can be found at EasyDeltaV.com. This section will describe how to use the basic methods.

2.2 Safety messagesInstructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation.

Explosions could result in death or serious injury. Do not remove the transmitter cover in explosive atmospheres when the circuit is live.

Before connecting an Emerson Field Communicator in an explosive atmosphere, make sure the instruments in the segment are installed in accordance with intrinsically safe or non-incendive field wiring practices.

Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.

Both transmitter covers must be fully engaged to meet flameproof/explosion-proof requirements.

Failure to follow these installation guidelines could result in death or serious injury. Make sure only qualified personnel perform the installation.

Electrical shock could cause death or serious injury. If the sensor is installed in a high-voltage environment and a fault or installation error occurs, high

voltage may be present on the transmitter leads and terminals.

Use extreme caution when making contact with the leads and terminals.

5Configuration

Page 12: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

ConfigurationMay 2016

2.3 Flow configuration

2.3.1 Engineering Assistant 5.5.1 ver. 2Engineering Assistant 5.5.1 ver. 2 is PC-based software that performs flow configuration for the Rosemount 3051SMV with the fully compensated mass flow feature board. It is available as a standalone application or as an AMS™ SNAP-ON™, and is required to complete the flow configuration for the Rosemount 3051SMV Transmitter.

The following are the minimum system requirements to install the Engineering Assistant 5.5.1 ver. 2 software:

Intel® Core™ Duo, 2.4 GHz

600 MB of available hard disk space

2GB RAM

Microsoft® Windows™ 7 Operating System (32 or 64 bit)

FOUNDATION Fieldbus interfaceLearn more about the Emerson USB Fieldbus Interface device and its configuration here: EmersonProcess.com/AMS/USB-Fieldbus-Interface.

2.3.2 Installing Engineering Assistant 5.5.1 ver. 2 Stand-Alone

NoteIf using full AMS Device Manager, do not uninstall it. Obtain the SNAP-ON version of EA or install Engineering Assistant 5.5.1 ver. 2 Stand-Alone on another PC.

1. Insert Rosemount Engineering Assistant (EA) Software disk into the DVD-ROM.

2. Right-click Setup.exe, select Run as Administrator.

3. Reboot the PC when prompted.

NoteAfter the reboot installation will continue. The disk should remain in the drive.

4. If there are old versions of EA 5, uninstall them by selecting Remove when prompted. Once uninstalled, right-click Setup.exe, then select Run as Administrator.

NoteDo NOT uninstall Engineering Assistant 6. Engineering Assistant 5 is not a replacement for Engineering Assistant 6.

2.3.3 Launching Engineering Assistant 5.5.1 ver. 2 and connecting to the transmitterConnect the FOUNDATION Fieldbus interface from the PC to the Rosemount 3051SMV Fieldbus Transmitter.

1. Open the transmitter cover on the side marked “Field Terminals”.

2. Connect the communication wires to the terminals labeled “Fieldbus Wiring”.

6 Configuration

Page 13: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

ConfigurationMay 2016

3. If the device is at a non-commissioned address, use the Emerson USB Fieldbus Interface’s Configuration Utility to “Commission” the Device.

NoteThe Emerson USB Fieldbus Interface can be configured to power the connected fieldbus device. Never attempt to use two power sources at the same time. Doing so can disrupt communications and may compromise automation safety. Refer to the Emerson USB Fieldbus Interface user manual (AW7060MNL) for further information.

4. Connect the Rosemount 3051SMV Transmitter to a computer (see Figure 2-1).

Figure 2-1. Connecting a PC to the Rosemount 3051SMV Using the USB Fieldbus Interface

A. USB Fieldbus Interface

5. Launch the Rosemount 3051SMV Engineering Assistant for FOUNDATION Fieldbus program by selecting MV Engineering Assistant from the Start menu.

OR

6. Launch AMS Device Manager if using the SNAP-ON Engineering Assistant.

a. Right click the device to be configured.b. Select SNAP-ON/Linked Apps > MV Engineering Assistant 5.5.1 ver. 2.

Rosemount 3051SMV without optional process temperature connection

Rosemount 3051SMV with optional process temperature connection

A A

7Configuration

Page 14: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

ConfigurationMay 2016

7. Start a new configuration or load a saved configuration from a file.

8. Perform the steps outlined in the “Creating a flow configuration”section.

9. Once the configuration is complete, disconnect MV Engineering Assistant and the USB Fieldbus Interface. Then, attach the housing cover and tighten so that metal contacts metal to meet flame-proof/explosion-proof requirements.

2.3.4 Creating a flow configurationEngineering Assistant 5.5.1 ver. 2 is designed to guide the user through the setup of the flow configuration for the Rosemount 3051SMV. This information will be used by the Engineering Assistant to create the flow configuration parameters that can be sent to the transmitter or saved for future use.

1. Select the fluid designation category.

2. Select the fluid type.

3. Select Next.

8 Configuration

Page 15: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

ConfigurationMay 2016

Depending on the fluid selected, Engineering Assistant 5.5.1 ver. 2 may bring up a screen for entering additional fluid information.

4. Select a primary element type, then enter the sizing information in the fields provided.

5. Select Next.

6. Enter the operating conditions for the fluid.

a. Choose the pressure and temperature range based on the operating conditions of the process, not the sensor range of the transmitter.

NoteAn extremely large or small operating range may increase the uncertainty of the flow calculation.

The units used for flow configuration are only used in the Engineering Assistant software. For configuration of device variable units, see “Units configuration” on page 11.

7. Enter the atmospheric pressure.

The transmitter needs absolute pressure to calculate flow. If gage pressure is measured,the transmitter will calculate absolute pressure based on the user-defined atmospheric pressure. Atmospheric pressure can be changed in the screen below. This setting may also be configured per the atmospheric offset configuration (see “Static pressure” on page 12) in the Sensor Transducer Block.

9Configuration

Page 16: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

ConfigurationMay 2016

8. Select Next.

9. Review fluid properties of the configuration.

10.Sele ct Finish.

11.When prompted, save the flow configuration to the computer. The file must be saved for review or to edit the mass flow configuration in the future.

NoteFOUNDATION Fieldbus mass flow configuration files cannot be uploaded from the Rosemount 3051SMV. If the file is not saved, it cannot be retrieved.

10 Configuration

Page 17: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

ConfigurationMay 2016

2.3.5 Sending a flow configuration to the transmitterSelect the Send button to download the mass flow configuration file to the transmitter. Sending the mass flow configuration file will overwrite the existing configuration in the transmitter. Engineering Assistant will put the Mass Flow Transducer Block out of service when sending the mass flow configuration.

1. Select the Send button. A confirmation message will display .

2. At the end of the download, choose which mode to put the Mass Flow Transducer Block into, and then select Continue.

2.3.6 Mass flow test calculationThe Mass Flow Test Calculation method allows the user to verify the flow configuration of the Rosemount 3051SMV by entering expected values for the differential pressure, absolute pressure, and process temperature variables. Test calculation units are always in inH2O @ 68 °F for differential pressure, psi for static pressure and °F for temperature.

To perform a test calculation, select Actions > Methods > Methods > Mass Flow Test Calculation and follow the on-screen prompts.

2.4 Variable configuration

2.4.1 Units configurationUnits for transmitter variables are configured in the XD Scale parameter in each AI Block. Each AI Block is connected to a transmitter variable according to the Channel parameter in the AI Block. When the units in an AI Block are changed, the units of the connected channel variable will be changed in the Sensor Transducer Block or the Mass Flow Transducer Block accordingly. If multiple AI Blocks are set to the same channel, the XD Scale units must be manually synchronized to resolve configuration errors.

11Configuration

Page 18: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

ConfigurationMay 2016

2.4.2 Mass flowThe following configuration items are found in the Mass Flow Transducer Block.

NoteThese configuration items only apply to the Fully Compensated Mass Flow transmitter.

Low flow cutoffIf the measured differential pressure value is less than the low flow cutoff value, the transmitter will calculate the flow rate value as zero.

The unit for this value is always inH2O at 68 °F.

Process temperature modeThe mass flow calculation can use a live process temperature reading or a fixed value based on the selected process temperature mode. To configure it, select Actions > Methods > Methods > Mass Flow PT Mode Setup and follow the on-screen prompts.

NoteThe unit for the fixed process temperature value always matches the process temperature primary value unit. To change this unit setting, see Units configuration .

2.4.3 Differential pressureThe following configuration items are found in the Sensor Transducer Block.

DampingThe damping setting changes the response time of the transmitter; higher values can smooth variations in output readings caused by rapid input changes. Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements.

The setting for differential pressure damping also affects the mass flow.

2.4.4 Static pressureThe following configuration items are found in the Sensor Transducer Block.

DampingThe damping setting changes the response time of the transmitter; higher values can smooth variations in output readings caused by rapid input changes. Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements.

The setting for static pressure damping affects both absolute and gage pressure measurements.

Mode Description

Normal The transmitter will only use the actual measured Process Temperature value. If the temperature sensor fails, the Flow output will go to Bad status.

Backup The transmitter will use the actual measured Process Temperature value. If the temperature sensor fails, the transmitter will use the value shown in Fixed PT.

Fixed The transmitter will always use the temperature value shown in Fixed PT.

12 Configuration

Page 19: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

ConfigurationMay 2016

Atmospheric offsetBoth absolute and gage pressure are available as variables. The type of transmitter ordered will determine which variable is measured. The transmitter will calculate either absolute or gage pressure based on the user-defined atmospheric offset.

2.4.5 Process temperatureThe following configuration items are found in the Sensor Transducer Block.

DampingThe damping setting changes the response time of the transmitter; higher values can smooth variations in output readings caused by rapid input changes. Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements.

Callendar-Van Dusen Coefficients

The Rosemount 3051SMV accepts Callendar-Van Dusen constants from a calibrated RTD schedule and generates a special custom curve to match that specific sensor resistance vs. temperature performance. Matching the specific sensor curve with the transmitter configuration enhances the temperature measurement accuracy. Under Actions > Methods > Methods, the Callendar-Van Dusen constants R0, A, B, and C can be viewed. If the Callendar-Van Dusen constants are known for the user’s specific Pt 100 RTD sensor, the constants R0, A, B, and C may be edited by selecting the Callendar-Van Dusen Setup method and following the on-screen prompts. The user may also view the , , and coefficients by selecting the View Alpha, Beta, Delta button. The constants R0, , , and may be edited by selecting the Callendar-Van Dusen Setup and following the on-screen prompts. To reset the transmitter to the IEC 751 Defaults, select the Reset to IEC 751 Defaults method.

User-defined process temperature sensor limitsProcess temperature sensor limits can be changed to allow early detection of RTD failures. When the limits are exceeded, the transmitter will display a Process Temperature Out of Limits alert in the transmitter status, set the PT measurement status to uncertain, and will stop using the measured temperature value in the flow calculation. See “Mass flow” on page 12 for more information on configuring the process temperature mode for mass flow.

Enable/disable process temperatureUsing the PT Measurement parameter, the process temperature measurement can be disabled to prevent undesired diagnostic alarms and local display screens. This feature may be useful if the process temperature option was ordered but will not be used or if the RTD in use has failed and a replacement is not readily available.

When the process temperature measurement is disabled, the process temperature measurement status will be “bad”. If using mass flow calculations, set the mass flow’s process temperature mode to Fixed to allow calculations to continue. Once an RTD is available and wired, set the PT Measurement to Enabled and the process temperature mode to Normal to allow the live reading to be used for mass flow calculations.

2.4.6 Variable simulationThe following configuration items are found in the AI Block.

Simulate replaces the channel value coming from the Sensor Transducer Block. For testing purposes, it is possible to manually drive the output of the Analog Input Block to a desired value. There are two ways to do this.

13Configuration

Page 20: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

ConfigurationMay 2016

Manual modeComplete the steps below to change only the OUT_VALUE and not the OUT_STATUS of the AI Block.

1. Set the block mode to Manual.

2. Change the Output Value to the desired value.

3. Restore the original block mode when finished.

Simulate1. If the simulate switch on the electronics board is in the Disabled position, move it to the Enabled

position. See “Set the switches” on page 25 for more information.

2. Set the Simulate En/Disable parameter to Active.

3. Enter the desired Simulate Value and Status. Make sure the block mode is Auto to see the value propagate through the block.

4. Set the Simulate En/Disable parameter back to Disabled when finished simulating.

2.5 Device configuration

2.5.1 Display configurationThe following configuration items are found in the LCD display Transducer Block.

The transmitter features a three-line display. The first line of five characters displays the output description, the second line of seven digits displays the actual value, and the third line of six characters displays engineering units. The LCD display meter can also display diagnostic messages.

Each parameter configured for display will appear on the LCD display for a brief period before the next parameter is displayed. Up to four different variables may be shown on the display.

The LCD display meter is preconfigured to show the measured variables that correspond to the transmitter configuration. It can be configured to display any measured or calculated value that has a status parameter with it (i.e. FOUNDATION Fieldbus DS-65 parameter type). Configure each parameter for display as stated below.

Display parameter selectThe display of each configured parameter can be turned on or off by editing the Display Parameter Select parameter.

Block type Enter the Block Type for the block that contains the parameter to be displayed.

Block tag Enter the Block Tag of the block that contains the parameter to be displayed.

Parameter index Enter the Block Index of the parameter to be displayed.

14 Configuration

Page 21: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

ConfigurationMay 2016

15Configuration

Custom tag Enter up to five characters to be displayed on the top line of the LCD display when this parameter is displayed.

Units type Select auto when the parameter to be displayed is pressure, temperature, mass flow, or percent. The units of the parameter will be read and automatically displayed on the LCD display.

Select custom to display up to six characters as configured in the Custom Units parameter.

Select none if the parameter is to be displayed without associated units.

Custom units If the Units Type is set to custom specify up to six characters here to be displayed with the configured parameter.

2.5.2 Write lockThe following configuration items are found in the Resource Block.

The Rosemount 3051SMV Transmitter supports both hardware and software write lock. Locking the transmitter will prevent configuration changes until it is unlocked again.

Software write lockTo configure software write lock, select Actions > Methods > Methods > Write Lock Setup and follow the on-screen prompts for software write lock. The security switch on the electronics board must be in the unlocked position to use software write lock.

To unlock the transmitter, run the write lock setup method again and follow the on-screen prompts.

Hardware write lockTo configure hardware write lock, select Actions > Methods > Methods > Write Lock Setup and follow the on-screen prompts for hardware write lock. This method must be run twice if software write lock is already configured, first to unlock the device, then to switch to hardware write lock.

To lock or unlock the transmitter, set the security switch on the electronics board as shown in Figure 3-8 on page 26. Note that the hardware security switch is only followed if the transmitter has been configured to use hardware write lock as described above.

The state of the security switch can be read in the Device Switches State parameter.

2.6 Device capabilities

2.6.1 General block informationReference information on the process control function blocks can be found in the Function Block Reference Manual.

2.6.2 Link active schedulerThe Rosemount 3051SMV can be designated to act as the backup Link Active Scheduler (LAS) in the event that the LAS is disconnected from the segment. As the backup LAS, the Rosemount 3051SMV will take over the management of communications until the host is restored. The host system may provide a configuration tool specifically designed to designate a particular device as a backup LAS.

Page 22: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

ConfigurationMay 2016

2.6.3 CapabilitiesThere are a total of 20 Virtual Communication Relationships (VCRs). Two are permanent and 18 are fully configurable by the host system. Twenty-five link objects are available.

Host timer recommendationsT1 = 96000T2 = 9600000T3 = 480000

2.6.4 Node addressThe transmitter is shipped at a temporary (248+) address. This enables FOUNDATION Fieldbus host systems to automatically recognize the device and move it to a permanent address.

2.6.5 Block instantiationThe Rosemount 3051SMV supports the use of function block instantiation. When a device supports block instantiation, the number of blocks and block types can be defined to match specific application needs. The number of blocks that can be instantiated is only limited by the amount of memory within the device and the block types that are supported by the device. Instantiation does not apply to standard device blocks like the Resource or Transducer Blocks. Block instantiation is done by the host control system or configuration tool, but not all hosts are required to implement this functionality. Refer to the specific host or configuration tool manual for more information.

Table 2-1. Network Parameters

Network parameter Value

Slot Time 6

Maximum Response Delay 4

Maximum Inactivity to Claim LAS Delay 5

Minimum Inter DLPDU Delay 7

Time Sync class 4 (1ms)

Maximum Scheduling Overhead 10

Per CLPDU PhL Overhead 4

Maximum Inter-channel Signal Skew 0

Required Number of Post-transmission-gap-ext Units 0

Required Number of Preamble-extension Units 1

Table 2-2. Block Execution Times

Block Time (in ms)

Analog Input 20

PID 25

Arithmetic 20

Input Selection 20

Signal Characterizer 20

Integrator 20

Output Splitter 20

Control Selector 20

16 Configuration

Page 23: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

InstallationMay 2016

Section 3 Installation

Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 18Steps required for quick installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19Tagging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 24Consider housing rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 24Set the switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 25Wire, ground, and power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26Rosemount 305 and 304 Manifolds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 31

3.1 Section overviewThe information in this section covers installation considerations for the Rosemount™ 3051S MultiVariable™ FOUNDATION™ Fieldbus Transmitter (3051SMV). A Quick Start Guide is shipped with every transmitter to describe basic installation, wiring, and startup procedures (document number 00825-0100-4853). Dimensional drawings for each transmitter variation and mounting configuration are included in Appendix A: Specifications and Reference Data.

3.2 Safety messagesProcedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operation. Information that raises potential safety issues is indicated with a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.

Explosions can result in death or serious injury.

Do not remove the transmitter covers in explosive environments when the circuit is live.

Fully engage both transmitter covers to meet explosion-proof requirements.

Before connecting a communicator in an explosive atmosphere, make sure the instruments in the segment are installed in accordance with intrinsically safe or non-incendive field wiring practices.

Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.

17Installation

Page 24: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

InstallationMay 2016

3.3 Considerations

3.3.1 GeneralMeasurement performance depends upon proper installation of the transmitter and impulse piping. Mount the transmitter close to the process and use minimum piping to achieve best performance. Also, consider the need for easy access, personnel safety, practical field calibration, and a suitable transmitter environment. Install the transmitter to minimize vibration, shock, and temperature fluctuation.

ImportantInstall the enclosed pipe conduit plug (found in the box) in the unused conduit plug opening. For straight threads, a minimum of seven threads must be engaged. For tapered threads, a minimum of five threads must be engaged; install the plug wrench-tight.

For material compatibility considerations, see the Material Selection Technical Note.

3.3.2 Mechanical

Steam serviceFor steam service or for applications with process temperatures greater than the limits of the transmitter, do not blow down impulse piping through the transmitter. Flush lines with the blocking valves closed and refill lines with water before resuming measurement.

Electrical shock can result in death or serious injury.

Avoid contact with the leads and terminals.

Process leaks could result in death or serious injury.

Install and tighten all four flange bolts before applying pressure.

Do not attempt to loosen or remove flange bolts while the transmitter is in service.

Use only bolts supplied or sold by Emerson Process Management as spare parts.

Replacement equipment or spare parts not approved by Emerson Process Management for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.

Improper assembly of manifolds to traditional flange can damage sensor module.

For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e. bolt hole) but must not contact module housing.

Sensor module and electronics housing must have equivalent approval labeling in order to maintain hazardous location approvals.

When upgrading, verify sensor module and electronics housing certifications are equivalent. Differences in temperature class ratings may exist, in which case the complete assembly takes the lowest of the individual component temperature classes (for example, a T4/T5 rated electronics housing assembled to a T4 rated sensor module is a T4 rated transmitter.)

18 Installation

Page 25: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

InstallationMay 2016

Side mounting

When the transmitter is mounted on its side, position the coplanar flange to ensure proper venting or draining. Mount the flange as shown in “Mount the transmitter” on page 20, keeping drain/vent connections on the bottom for gas service and on the top for liquid service.

3.3.3 Environmental Best practice is to mount the transmitter in an environment that has minimal ambient temperature change. The transmitter electronics temperature operating limits are –40 to 185 °F (–40 to 85 °C). Appendix A: Specifications and Reference Data lists the sensing element operating limits. Mount the transmitter so it is not susceptible to vibration and mechanical shock and does not have external contact with corrosive materials.

3.4 Steps required for quick installationStart >

Mount the transmitter

Tagging

Set the switches

Wire, ground, and power

> Finish

19Installation

Page 26: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

InstallationMay 2016

3.4.1 Mount the transmitter

Liquid flow applications1. Place taps to the side of the line.

2. Mount beside or below the taps.

3. Mount the transmitter so that the drain/vent valves are oriented upward.

Gas flow applications1. Place taps in the top or side of the line.

2. Mount beside or above the taps.

Steam flow applications1. Place taps to the side of the line.

2. Mount beside or below the taps.

3. Fill impulse lines with water.

20 Installation

Page 27: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

InstallationMay 2016

Figure 3-1. Mounting Bracket - Coplanar Flange

Figure 3-2. Mounting Brackets - Traditional Flange

Bolting considerationsIf the transmitter installation requires assembly of a process flange, manifold, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitter. Only use bolts supplied with the transmitter or sold by Emerson™ Process Management as spare parts. Figure 3-3 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.

Panel mount Pipe mount

Panel mount Pipe mount

C

21Installation

Page 28: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

InstallationMay 2016

Figure 3-3. Common Transmitter Assemblies

A. Transmitter with coplanar flangeB. Transmitter with coplanar flange and optional flange adaptersC. Transmitter with traditional flange and optional flange adaptersD. Transmitter with coplanar flange and optional Rosemount Conventional Manifold and flange adapters

NoteFor all other manifolds, contact Customer Central technical support.

Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Table 3-1. If bolt material is not shown in Table 3-1, contact the local Emerson Process Management representative for more information.

Use the following bolt installation procedure.

1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt.

2. Finger-tighten the bolts.

3. Torque the bolts to the initial torque value using a crossing pattern. See Figure 3-1 for initial torque value.

4. Torque the bolts to the final torque value using the same crossing pattern. See Table 3-1 for final torque value.

5. Verify the flange bolts are protruding through the sensor module before applying pressure (see Figure 3-4).

A

4 × 1.75-in. (44 mm)

D

4 × 1.75-in. (44 mm)

4 × 2.25-in. (57 mm)

C

4 × 1.75-in. (44 mm)

4 × 1.50-in. (38 mm)

B

4 × 2.88-in. (73 mm)

22 Installation

Page 29: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

InstallationMay 2016

Figure 3-4. Proper Bolt Installation

A. BoltB. Sensor module

O-rings with flange adapters

Table 3-1. Torque Values for the Flange and Flange Adapter Bolts

Bolt material Head markings Initial torque Final torque

Carbon Steel (CS) 300 in-lb 650 in-lb

Stainless Steel (SST) 150 in-lb 300 in-lb

Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. Only use the O-ring that is designed for its specific flange adapter.

A. Flange adapterB. O-ringC. PTFE based profile is squareD. Elastomer profile is round

Whenever the flange or adapters are removed, visually inspect the O-rings. Replace them if there are any signs of damage, such as nicks or cuts. If the O-rings are replaced, re-torque the flange bolts and alignment screws after installation to compensate for seating of the O-rings.

B7M

316316

316SW

316STM316

R

B8M

AB

AB

CD

23Installation

Page 30: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

InstallationMay 2016

3.4.2 Tagging

Commissioning (paper) tagTo identify which device is at a particular location use the removable tag provided with the transmitter. Ensure the physical device tag (PD Tag field) is properly entered in both places on the removable commissioning tag and tear off the bottom portion for each transmitter.

Figure 3-5. Commissioning Tag

3.4.3 Consider housing rotationTo improve field access to wiring or to better view the optional LCD display:

1. Loosen the housing rotation set screw.

2. Turn the housing up to 180° left or right of its original (as shipped) position.

3. Re-tighten the housing rotation set screw to 30 in-lb.

Figure 3-6. Transmitter Housing Set Screw

A. Housing rotation set screw (3/32-in.)

NoteDo not rotate the housing more than 180° without first performing a disassembly procedure. Over-rotation may sever the electrical connection between the sensor module and the electronics.

Commissioning Tag

DEVICE ID:001151AB00010001440-121698091725

DEVICE REVISION: 1.0

PHYSICAL DEVICE TAG

DEVICE ID:001151AB00010001440-121698091725

DEVICE REVISION: 1.0

S / N :

PHYSICAL DEVICE TAG

Device Barcode

A

24 Installation

Page 31: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

InstallationMay 2016

3.4.4 Rotate the LCD displayTransmitters ordered with the LCD display will be shipped with the display installed.

In addition to housing rotation, the optional LCD display can be rotated in 90-degree increments by squeezing the two tabs, pulling out, rotating and snapping back into place.

If LCD display pins are inadvertently removed from the interface board, carefully re-insert the pins before snapping the LCD display back into place.

Use the following procedure and Figure 3-7 to install the LCD display:

1. If the transmitter is installed in a segment, secure the segment and disconnect power.

2. Remove the transmitter cover opposite the field terminal side. Do not remove the instrument covers in explosive environments when the circuit is live.

3. Engage the four-pin connector into the LCD display and snap into place.

4. Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover in order to meet explosion proof requirements.

5. If the transmitter was installed, reapply power.

Figure 3-7. Optional LCD Display

A. LCD displayB. Meter cover

3.4.5 Set the switchesSet Simulate and Security switch position before installation (location of switches shown in Figure 3-8), as desired.

The Simulate switch enables or disables the ability to set simulated alerts or simulated measured value and status.

The Security switch allows (unlocked symbol) or prevents (locked symbol) any configuration of the transmitter.

Further security settings are available in the software, including settings which use a software lock. Additionally, these settings can be used to disable both hardware and software locks.

Use the following procedure to change the switch configuration:

1. If the transmitter is installed, secure the segment, and remove power.

2. Remove the housing cover opposite the field terminal side. Do not remove the instrument cover in explosive atmospheres when the circuit is live.

3. Slide the security and simulate switches into the preferred position.

4. Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover in order to meet explosion proof requirements.

5. If the transmitter was installed, reapply power.

A

B

25Installation

Page 32: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

InstallationMay 2016

Figure 3-8. Simulate and Security Switches

3.4.6 Wire, ground, and powerUse a copper wire of sufficient size to ensure the voltage across the transmitter power terminals does not drop below 9 Vdc. Power supply voltage can be variable, especially under abnormal conditions such as when operating on battery backup. A minimum of 12 Vdc under normal operating conditions is recommended. Shielded twisted pair Type A cable is recommended.

NoteThe power terminals are polarity insensitive, which means the electrical polarity of the power leads does not matter when connecting to the power terminals. If polarity sensitive devices are connected to the segment, terminal polarity should be followed.

3.4.7 Signal wiring and shield groundingDo not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when transient protection terminal blocks are installed or to fulfill local regulations.

1. Remove the field terminals housing cover.

2. To power the transmitter, connect the power leads to the terminals indicated on the terminal block label.

3. Tighten the terminal screws to ensure full contact with terminal block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw. When wiring to the screw terminals, the use of crimped legs is recommended.

NoteThe use of a pin or ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time.

A. Security unlocked positionB. Security switchC. Security locked position

D. Simulate disabled positionE. Simulate switchF. Simulate enabled position

SECURITY SIMULATE

ENABLE

DISABLE

C

D

E

F

B

A

26 Installation

Page 33: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

InstallationMay 2016

4. Trim the cable shield as short as practical and insulate from touching the transmitter housing as indicated in Figure 3-9 and Figure 3-10.

NoteDo NOT ground the cable shield at the transmitter; if the cable shield touches the transmitter housing, it can create ground loops and interfere with communications. To protect the fieldbus segment from noise, grounding techniques for shield wire require a single grounding point for shield wire to avoid creating a ground loop. The cable shield should maintain a continuous connection to the power supply ground.

Connect cable shields for entire segment to a single good earth ground at power supply.

Improper grounding is the most frequent cause of poor segment communications.

5. Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover in order to meet explosion proof requirements.

6. Plug and seal unused conduit connections.

Figure 3-9. Wiring Terminals with RTD

NOTICE

When the enclosed threaded plug is utilized in the conduit opening, it must be installed with a minimum thread engagement in order to comply with explosion-proof requirements. For straight threads, a minimum of seven threads must be engaged. For tapered threads, a minimum of five threads must be engaged.

A. Protective grounding terminal (do not ground cable shield at the transmitter)B. Trim shield and insulate

C. Minimize distanceD. Insulate shieldE. Connect shield back to the power supply ground

DP

C

C

DE

B

A

27Installation

Page 34: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

InstallationMay 2016

Figure 3-10. Wiring Terminals without RTD

3.4.8 Power supply The transmitter requires between 9 and 32 Vdc (9 and 30 Vdc for intrinsic safety, and 9 and 17.5 Vdc for FISCO intrinsic safety) to operate and provide complete functionality.

3.4.9 Power conditionerA fieldbus segment requires a power conditioner to isolate the power supply, filter, and decouple the segment from other segments attached to the same power supply.

3.4.10 GroundingSignal wiring of the fieldbus segment can not be grounded. Grounding one of the signal wires will shut down the entire fieldbus segment.

Transmitter case groundingAlways ground the transmitter case in accordance with national and local electrical codes. The most effective transmitter case grounding method is a direct connection to earth ground with minimal impedance. Methods for grounding the transmitter case are listed below.

Internal ground connection

The internal ground connection screw is inside the FIELD TERMINALS side of the electronics housing. This screw is identified by a ground symbol ( ). The ground connection screw is standard on all Rosemount 3051SMV Transmitters (see Figure 3-11).

A. Protective grounding terminal (do not ground cable shield at the transmitter)

B. Trim shield and insulate

C. Minimize distanceD. Insulate shieldE. Connect shield back to the power supply ground

DP

B

A

D

C

C

E

28 Installation

Page 35: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

InstallationMay 2016

Figure 3-11. Internal Ground Connection

A. Ground screw

External ground connection

The external ground connection is located on the exterior of the transmitter housing (see Figure 3-12). This connection is only available with option D4 and T1.

Figure 3-12. External Ground Connection

A. External ground lug locationB. External ground assembly (03151-9060-0001)

NoteGrounding the transmitter case via threaded conduit connection may not provide sufficient ground continuity.

Transient protection terminal block groundingThe transmitter can withstand electrical transients of the energy level usually encountered in static discharges or induced switching transients. However, high-energy transients, such as those induced in wiring from nearby lightning strikes, can damage the transmitter.

The transient protection terminal block can be ordered as an installed option (option code T1) or as a spare part to retrofit existing Rosemount 3051SMV Transmitters in the field. The lightning bolt symbol shown in Figure 3-13 identifies the transient protection terminal block.

A

A

B

29Installation

Page 36: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

InstallationMay 2016

Figure 3-13. Transient Protection Terminal Block

A. Lightning bolt symbol location

NoteThe transient protection terminal block does not provide transient protection unless the transmitter case is properly grounded. Use the guidelines to ground the transmitter case (see “Grounding” on page 28).

3.4.11 Signal terminationA terminator should be installed at the beginning and end of every fieldbus segment.

3.4.12 Install optional process temperature input (Pt 100 RTD Sensor)

NoteTo meet ATEX/IECEx Flameproof certification, only ATEX/IECEx Flameproof cables (temperature input code C30, C32, C33, or C34) may be used.

1. Mount the Pt 100 RTD Sensor in the appropriate location.

NoteUse shielded four-wire cable for the process temperature connection.

2. Connect the RTD cable to the Rosemount 3051SMV Transmitter by inserting the cable wires through the unused housing conduit and connect to the four screws on the transmitter terminal block. An appropriate cable gland should be used to seal the conduit opening around the cable.

3. Connect the RTD cable shield wire to the ground lug in the housing.

with RTD without RTD

AA

30 Installation

Page 37: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

InstallationMay 2016

Figure 3-14. Transmitter RTD Wiring Connection

A. Ground lugB. RTD cable assembly wiresC. Pt 100 RTD sensor

Three-wire RTD A four-wire Pt 100 RTD is required to maintain published performance specifications. A three-wire Pt 100 RTD may be used with degraded performance. If connecting to a three-wire RTD, use a four-wire cable to connect the Rosemount 3051SMV terminal block to the RTD connection head. Within the RTD connection head, connect two of the same colored wires from the Rosemount 3051SMV to the single colored wire of the RTD sensor.

3.5 Rosemount 305 and 304 ManifoldsThe Rosemount 305 Integral Manifold is available in two designs: coplanar and traditional. The traditional Rosemount 305 Integral Manifold can be mounted to most primary elements with mounting adapters.

Figure 3-15. Rosemount 305 Manifold StylesIntegral coplanar Integral traditional

C

B

Red

Red

Whi

teW

hite

A

31Installation

Page 38: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

InstallationMay 2016

32 Installation

The Rosemount 304 comes in two basic styles: traditional (flange x flange and flange x pipe) and wafer. The traditional manifold comes in two-, three-, and five-valve configurations. The wafer manifold comes in three- and five-valve configurations.

Figure 3-16. Rosemount 304 Manifold Styles

3.5.1 Rosemount 305 Integral Manifold installation procedureTo install a Rosemount 305 Integral Manifold to a 3051SMV:

1. Inspect the PTFE SuperModule™ O-rings. If the O-rings are undamaged, reusing them is recommended. If the O-rings are damaged (e.g. nicks), replace them with new O-rings.

NoteIf replacing the O-rings, be careful not to scratch or deface the O-ring grooves or the surface of the isolating diaphragm when removing the damaged O-rings.

2. Install the Integral manifold on the SuperModule process connection. Use the four manifold bolts for alignment. Finger tighten the bolts, then tighten the bolts incrementally in a cross pattern to final torque value. See Table 3-1 on page 23 for complete bolt installation information and torque values. When fully tightened, the bolts should extend through the top of the SuperModule housing.

3. If the PTFE SuperModule O-rings have been replaced, the flange bolts should be re-tightened after installation to compensate for seating of the O-rings.

4. If applicable, install flange adapters on the process end of the manifold using the 1.5-in. flange bolts supplied with the transmitter.

3.5.2 Rosemount 304 Traditional Manifold installation procedure

To install a traditional manifold to a Rosemount 3051SMV:

1. Align the traditional manifold with the transmitter flange. Use the four manifold bolts for alignment.

2. Finger tighten the bolts, then tighten the bolts incrementally in a cross pattern to final torque value. See Table 3-1 on page 23 for complete bolt installation information and torque values. When fully tightened, the bolts should extend through the top of the SuperModule assembly bolt hole but must not contact the SuperModule housing.

3. If applicable, install flange adapters on the process end of the manifold using the 1.75-in. flange bolts supplied with the transmitter.

Traditional Wafer

Improper installation or operation of manifolds may result in process leaks, which may cause death or serious injury.

Page 39: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

InstallationMay 2016

3.5.3 Manifold operationAlways perform a zero trim on the transmitter/manifold assembly after installation to eliminate any shift due to mounting effects. See Section 4: Operation and Maintenance, “Sensor trim overview” on page 38.

Coplanar transmitters

3-valve and 5-valve manifolds

Performing zero trim at static line pressure

In normal operation the two isolate (block) valves between the process ports and transmitter will be open and the equalize valve will be closed.

1.To zero trim the transmitter, close the isolate valve on the low side (downstream) side of the transmitter.

2.Open the equalize valve to equalize the pressure on both sides of the transmitter. The manifold is now in the proper configuration for performing a zero trim on the transmitter.

3.After performing a zero trim on the transmitter, close the equalize valve.

H L

Drain/Vent valve

Drain/Vent valve

Isolate(open)

Isolate(open)

Process

Equalize(closed)

H L

Drain/Vent valve

Isolate(open)

Drain/Vent valve

Isolate(closed)

Process

Equalize(closed)

H L

Drain/Vent valve

Isolate(open)

Drain/Vent valve

Isolate(closed)

Process

Equalize(open)

H L

Drain/Vent valve

Isolate(open)

Drain/Vent valve

Isolate(closed)

Process

Equalize(closed)

33Installation

Page 40: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

InstallationMay 2016

5-valve natural gas manifold

Performing zero trim at static line pressure

5-valve natural gas configurations shown:

4.Finally, to return the transmitter to service, open the low side isolate valve.

In normal operation, the two isolate (block) valves between the process ports and transmitter will be open, and the equalize valves will be closed. Vent valves may be opened or closed.

1.To zero trim the transmitter, first close the isolate valve on the low pressure (downstream) side of the transmitter and the vent valve.

2.Open the equalize valve on the high pressure (upstream) side of the transmitter.

H L

Drain/Vent valve

Drain/Vent valve

Isolate(open)

Isolate(open)

Process

Equalize(closed)

H L

Test(Plugged)

Isolate(open)

Isolate(open)

Test(Plugged)

Equalize(closed)

Equalize(closed)

Process ProcessDrain vent(closed)

H L

Test(Plugged)

Isolate(open)

Isolate(closed)

Test(Plugged)

Process ProcessDrain vent(closed)

Equalize(closed)

Equalize(closed)

Test(Plugged)

Isolate(open)

Equalize(open)

Equalize(closed)

Process ProcessDrain vent(closed)

Isolate(closed)

Test(Plugged)

H L

34 Installation

Page 41: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

InstallationMay 2016

3.Open the equalize valve on the low pressure (downstream) side of the transmitter. The manifold is now in the proper configuration for performing a zero trim on the transmitter.

4.After performing a zero trim on the transmitter, close the equalize valve on the low pressure (downstream) side of the transmitter.

5.Close the equalize valve on the high pressure (upstream) side.

6.Finally, to return the transmitter to service, open the low side isolate valve and vent valve. The vent valve can remain open or closed during operation.

Test(Plugged)

Isolate(open)

Equalize(open)

Equalize(open)

Process ProcessDrain vent(closed)

Isolate(closed)

Test(Plugged)

H L

Test(Plugged)

Isolate(open)

Equalize(open)

Equalize(closed)

Process ProcessDrain vent(closed)

Isolate(closed)

Test(Plugged)

H L

H L

Test(Plugged)

Isolate(open)

Isolate(closed)

Test(Plugged)

Process ProcessDrain vent(closed)

Equalize(closed)

Equalize(closed)

H L

Test(Plugged)

Isolate(open)

Isolate(open)

Test(Plugged)

Equalize(closed)

Equalize(closed)

Process ProcessDrain vent(closed)

35Installation

Page 42: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

InstallationMay 2016

Adjusting valve packingOver time, the packing material inside a manifold may require adjustment in order to continue to provide proper pressure retention. Not all manifolds have this adjustment capability. The manifold model number will indicate what type of stem seal or packing material has been used.

The following steps are provided as a procedure to adjust valve packing.

1. Remove all pressure from device.

2. Loosen manifold valve jam nut.

3. Tighten manifold valve packing adjuster nut 1/4 turn.

4. Tighten manifold valve jam nut.

5. Re-apply pressure and check for leaks.

6. Above steps can be repeated, if necessary.

If the above procedure does not result in proper pressure retention, the complete manifold should be replaced.

Figure 3-17. Adjusting Valve Packing

A. BonnetB. Ball seatC. PackingD. Stem

E. Packing adjusterF. Jam nutG. Packing follower

A

D

C

B

E

F

G

36 Installation

Page 43: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

Operation and MaintenanceMay 2016

Section 4 Operation and Maintenance

Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 38Field upgrades and replacements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 41

4.1 Section overviewThis section contains information on operating and maintaining the Rosemount™ 3051S MultiVariable™ FOUNDATION™ Fieldbus Transmitter (3051SMV). Each FOUNDATION Fieldbus host or configuration tool has different ways of displaying and performing operations. Some hosts will use Device Descriptions (DD) and DD Methods to complete device configuration and will display data consistently across platforms. The DD can be found on the FieldComm Group website at FieldCommGroup.org. There is no requirement that a host or configuration tool support the features in the DD. For DeltaV™ users, the DD can be found at EasyDeltaV.com. The information in this section will describe how to use the basic methods.

Based on the configuration ordered, some measurements (e.g. process temperature) and/or calculation types (e.g. fully compensated mass flow, process variables only) may not be available. Available measurements and/or calculation types are determined by the multivariable type and measurement type codes ordered. See “Ordering information” on page 64 for more information.

4.2 Safety messagesProcedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operation. Information that raises potential safety issues is indicated with a

warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.

37Operation and Maintenance

Page 44: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

Operation and MaintenanceMay 2016

4.3 Calibration

4.3.1 Calibration overviewBefore calibrating the sensor complete configuration of the device in Section 2: Configuration. Calibration of the 3051SMV involves the following tasks.

Sensor trim

Zero or lower sensor trim

4.3.2 Sensor trim overviewTrim the sensors using either upper or lower sensor or zero trim functions. Trim functions vary in complexity and are application-dependent.

Failure to follow these installation guidelines could result in death or serious injury.

Make sure only qualified personnel perform the installation.

Explosions could result in death or serious injury.

Do not remove the transmitter cover in explosive atmospheres when the circuit is live.

Before connecting an Emerson™ Field Communicator in an explosive atmosphere, make sure the instruments in the segment are installed in accordance with intrinsically safe or non-incendive field wiring practices.

Both transmitter covers must be fully engaged to meet flameproof/ explosion-proof requirements.

Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.

Electrical shock could cause death or serious injury.

If the sensor is installed in a high-voltage environment and a fault or installation error occurs, high voltage may be present on the transmitter leads and terminals.

Use extreme caution when making contact with the leads and terminals.

Process leaks could result in death or serious injury.

Install and tighten all four flange bolts before applying pressure.

Do not attempt to loosen or remove flange bolts while the transmitter is in service.

Replacement equipment or spare parts not approved by Emerson Process Management for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.

Use only bolts supplied or sold by Emerson Process Management as spare parts.

Improper assembly of manifolds to traditional flange can damage the device.

For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact the sensor module.

Static electricity can damage sensitive components.

Observe safe handling precautions for static-sensitive components.

38 Operation and Maintenance

Page 45: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

Operation and MaintenanceMay 2016

NoteWhen performing a sensor trim on a pressure sensor, it is possible to degrade the performance of the sensor if inaccurate calibration equipment is used. Use calibration equipment that is at least three times as accurate as the pressure sensor of the Rosemount 3051SMV Transmitter.

4.3.3 Determining necessary sensor trims Bench calibration is not recommended for new instruments. The transmitter can be set back to factory settings using the Restore Factory Calibration. For transmitters that are field installed, the manifolds discussed in “Manifold operation” on page 33 allow the differential transmitter to be zeroed using the zero trim function. Both 3-valve and 5-valve manifolds are discussed. This field calibration will eliminate any pressure offsets caused by mounting effects and static pressure effects of the process. Determine the necessary trims with the following steps.

1. Complete a zero trim.

2. Apply pressure.

3. Check the pressure, if the pressure does not match the applied pressure, perform a sensor trim (see Full trim ).

4.3.4 Types of pressure trim

Zero trimZero trim is a single-point offset adjustment. It is useful for compensating for mounting position effects and is most effective when performed with the transmitter installed in its final mounting position. When performing a zero trim with a manifold, refer to “Rosemount 305 and 304 Manifolds” on page 31.

Note To perform a zero trim function, the measured value of transmitter can be no larger than five percent of the upper sensor limit from zero. The transmitter will not allow the user to perform a zero trim on an absolute static pressure sensor. To correct mounting position effects on the absolute static pressure sensor, perform a sensor trim. The lower sensor trim function provides an offset correction similar to the zero trim function, but it does not require zero-based input.

Full trimFull sensor trim is a two-point sensor calibration where two end-point pressures are applied, and all output is linearized between them. Always adjust the lower sensor trim value first to establish the correct offset. Adjustment of the upper sensor trim value provides a slope correction to the characterization curve based on the lower sensor trim value. The trim values allow the user to optimize performance over a specified measuring range at the calibration temperature.

4.3.5 Restore factory calibrationThe factory calibration recall feature will restore the transmitter to the original factory calibration. This feature can be useful for recovering from an inadvertent zero trim or inaccurate pressure source. When this feature is used, the transmitter’s upper and lower trim values are set to the values configured at the factory. If custom trim values were specified when the transmitter was ordered, the device will recall those values. If custom trim values were not specified, the device will recall the default upper and lower sensor limits.

39Operation and Maintenance

Page 46: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

Operation and MaintenanceMay 2016

4.3.6 Differential pressure sensor calibrationNavigate to the differential pressure calibration to complete a zero trim procedure or a full DP sensor trim. Differential pressure sensor calibration units can be set in the Sensor Transducer Block.

Zero trimTo perform a DP sensor zero trim, select Actions > Methods > Methods > Zero Differential Pressure Trim and follow the on-screen prompts. To perform a zero trim function, the measured value of transmitter can be no larger than five percent of the upper sensor limit from zero.

NoteWhen performing a DP sensor zero trim, ensure that the equalizing valve is open and all wet legs are filled to the correct levels.

Upper and lower sensor trim

NoteWhen performing a sensor trim on a pressure sensor, it is possible to degrade the performance of the sensor if inaccurate calibration equipment is used. Use calibration equipment that is at least three times as accurate as the pressure sensor of the Rosemount 3051SMV Transmitter.

A reference pressure device is required to perform a full sensor trim. Allow the pressure input to stabilize for ten seconds before entering any values. To perform a DP full trim, select Actions > Methods > Methods > Lower Differential Pressure Trim, follow the on-screen prompts, and then select Actions > Methods > Methods > Upper Differential Pressure Trim and follow the on-screen prompts.

Note The transmitter allows approximately five percent URL deviation from the characterized curve established at the factory.

4.3.7 Static pressure sensor calibrationThe static pressure calibration allows the user to complete either a zero trim procedure or a full SP sensor trim. Static pressure sensor calibration units can be set in the Sensor Transducer Block.

Zero trim and lower sensor trim A zero trim can be performed on a gage sensor and a lower sensor trim can be performed on an absolute sensor to correct for mounting position effects. To perform a zero trim on a gage static pressure sensor, select Actions > Methods > Methods > Zero Static Pressure Trim and follow the on-screen prompts.

To correct for mounting position effects on transmitters equipped with an absolute static pressure sensor, perform a lower sensor trim. This is accomplished by selecting Actions > Methods > Methods > Lower Static Pressure Trim and follow the on-screen prompts. The lower sensor trim function provides an offset correction similar to the zero trim function, but it does not require a zero-based input.

Upper and lower sensor trim

NoteWhen performing a sensor trim on a pressure sensor, it is possible to degrade the performance of the sensor if inaccurate calibration equipment is used. Use calibration equipment that is at least three times as accurate as the pressure sensor of the Rosemount 3051SMV Transmitter.

40 Operation and Maintenance

Page 47: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

Operation and MaintenanceMay 2016

A reference pressure device is required to perform a full sensor trim. Allow the pressure input to stabilize for ten seconds before entering any values. To perform a SP full trim select Actions > Methods > Methods > Lower Static Pressure Trim and follow the on-screen prompts then select Actions > Methods > Methods > Upper Static Pressure Trim and follow the on-screen prompts.

4.3.8 Process temperature sensor calibrationThe Temperature Calibration allows the user to perform a sensor trim of a process temperature sensor. Process temperature sensor calibration units can be set in the Sensor Transducer Block.

Process temperature trim

NoteWhen performing a sensor trim on a sensor, it is possible to degrade the performance of the sensor if inaccurate calibration equipment is used. Use calibration equipment that is at least three times as accurate as the sensor of the Rosemount 3051SMV Transmitter.

To calibrate the Process Temperature Input using the sensor trim, use the following procedure.

1. Set up a Temperature Calibrator to simulate a Pt 100 (100-ohm platinum, alpha 385 RTD) per manufacture recommendations. See “Install optional process temperature input (Pt 100 RTD Sensor)” on page 30 for wiring information.

2. Select Actions > Methods > Methods > Trim Process Temperature and select the type of calibration. Adjust the calibrator/RTD simulator to a test point temperature value that represents a minimum process temperature (for example, 32 °F or 0 °C) if completing a lower sensor trim. Adjust the calibrator/RTD simulator to a test point temperature value that represents the maximum process temperature (for example, 140 °F or 60 °C) if completing an upper sensor trim.

4.4 Field upgrades and replacements

4.4.1 Disassembly considerationsDuring disassembly, do not remove the instrument cover in explosive atmospheres when the circuit is live as this may result in serious injury or death. Also, be aware of the following:

Follow all plant safety rules and procedures.

Isolate and vent the process from the transmitter before removing the transmitter from service.

Disconnect optional process temperature sensor leads and cable.

Remove all other electrical leads and conduit.

Detach the process flange by removing the four flange bolts and two alignment screws that secure it.

Do not scratch, puncture, or depress the isolating diaphragms.

Clean isolating diaphragms with a soft rag and a mild cleaning solution, then rinse with clear water.

Whenever the process flange or flange adapters are removed, visually inspect the PTFE O-rings. Emerson Process Management recommends reusing O-rings if possible. If the O-rings show any signs of damage, such as nicks or cuts, they should be replaced.

41Operation and Maintenance

Page 48: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

Operation and MaintenanceMay 2016

4.4.2 Housing assembly including electronics board

Field device labelsThe sensor module label reflects the replacement model code for reordering a complete transmitter. Replacement model codes are also viewable in the host by selecting Overview > Device Information > Identification.

Replacing housing assembly including electronics board

Removing the electronics board

During disassembly, do not remove the instrument cover in explosive atmospheres when the circuit is live as this may result in serious injury or death.

The 3051SMV Transmitter electronics board is located opposite the field terminal side in the housing. To remove the electronics board, perform the following procedure:

1. Remove the housing cover opposite the field terminal side.

2. Remove the LCD display, if applicable. Hold in the two clips and pull outward. This will provide better access to the two screws located on the electronics board.

3. Loosen the two captive screws located on the electronics board.

4. Pull out the electronics board to expose and locate the sensor module connector, (Figure 4-1).

5. Press the locking tabs and pull the sensor module connector upwards (avoid pulling wires). Housing rotation may be required to access locking tabs. See “Consider housing rotation” on page 24 for more information.

Figure 4-1. Sensor Module Connector View

A. Electronics boardB. Sensor module connector

Separate the sensor module assembly from the housingTo prevent damage to the sensor module connector, remove the electronics board from the sensor module assembly and remove the connector before separating the sensor module assembly from the housing.

1. Loosen the housing rotation set screw by one full turn with a 3/32-in. hex wrench (see Figure 4-2).

2. Unscrew the housing from the sensor module threads.

A

B

42 Operation and Maintenance

Page 49: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

Operation and MaintenanceMay 2016

Figure 4-2. Set Screw

A. Housing rotation set screw (3/32-in.)

Attach the sensor module assembly to the housing1. Apply a light coat of low temperature silicon grease to the sensor module threads and O-ring.

2. Install the V-Seal (03151-9061-0001) at the bottom of the housing (Figure 4-3).

3. Thread the housing completely onto the sensor module assembly. The housing must be no more than one full turn from flush with the sensor module assembly to comply with flame-proof/explosion-proof requirements.

4. Tighten the housing rotation set screw using a 3/32-in. hex wrench to a recommended torque of 30 in-lbs (3.4 N-m).

Figure 4-3. V-Seal

A. Black rubber V-seal

Install electronics board in the housing1. Apply a light coat of low temperature silicon grease to the sensor module connector O-ring.

2. Insert the sensor module connector into the top of the sensor module assembly. Ensure the locking tabs are fully engaged.

3. Gently slide the electronics board into the housing, making sure the pins from the housing properly engage the receptacles on the electronics board.

4. Tighten the captive screws. If using an LCD display, see “LCD display” on page 44.

5. Attach the housing cover and tighten so that metal contacts metal to meet flame-proof/explosion-proof requirements.

A

A

43Operation and Maintenance

Page 50: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

Operation and MaintenanceMay 2016

4.4.3 Terminal blockElectrical connections are located on the terminal block in the compartment labeled “FIELD TERMINALS.” The terminal block may be replaced or upgraded to add transient protection. If the device has a transient terminal block, the terminal block must be replaced with another transient terminal block. When installing a transient terminal block refer to grounding procedures in Section 3: Installation. Part numbers can be found in “Spare parts list” on page 72. Loosen the two captive screws (Figure 4-4), and pull the entire terminal block out.

NoteThe terminal block does not identify FISCO.

Figure 4-4. Terminal Blocks

1. Gently slide the terminal block into the housing, making sure the pins from the Rosemount 3051SMV housing properly engage the receptacles on the terminal block.

2. Tighten the captive screws on the terminal block.

3. Attach the Rosemount 3051SMV housing cover and tighten so metal contacts metal to meet flame-proof/explosion-proof requirements.

4.4.4 LCD displayTransmitters ordered with the LCD display will be shipped with the display installed. Installing the display on an existing transmitter requires the LCD display kit (part number 00753-9004-0001 for aluminum housing and 00753-9004-0004 for stainless steel housing).

Use the following procedure and Figure 4-5 to install the LCD display:

1. If the transmitter is installed on a segment, then secure the segment and disconnect power.

2. Remove the transmitter cover on the electronics board side (opposite the field terminals side). Do not remove instrument covers in explosive environments when circuit is live.

3. Engage the four-pin connector into the electronics board and snap LCD display into place.

4. To meet explosion-proof requirements, reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover.

Without optional process temperature connections

With optional process temperature connections

44 Operation and Maintenance

Page 51: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

Operation and MaintenanceMay 2016

Figure 4-5. Optional LCD Display

A. Electronics boardB. LCD displayC. Display cover

4.4.5 Flange and drain ventThe Rosemount 3051SMV Transmitter is attached to the process connection flange by four bolts and two alignment cap screws.

1. Remove the two alignment cap screws.

Figure 4-6. Alignment Cap Screws

A. Alignment cap screw

2. Remove the four bolts and separate the transmitter from the process connection, but leave the process connection flange in place and ready for re-installation.

NoteIf installation uses a manifold, see “Manifold operation” on page 33.

3. Inspect the sensor module PTFE O-rings. If the O-rings are undamaged, they may be reused. Emerson Process Management recommends reusing O-rings if possible. If the O-rings show any signs of damage, such as nicks or cuts, they should be replaced (part number 03151-9042-0001 for glass-filled PTFE and part number 03151-9042-0002 for graphite-filled PTFE).

NoteIf replacing the O-rings, be careful not to scratch or deface the O-ring grooves or the surface of the isolating diaphragm when removing the damaged O-rings.

4. Install the process flange on the sensor module process connection. To hold the process flange in place, install the two alignment cap screws finger tight (these screws are not pressure retaining). Do not overtighten; this will affect module-to-flange alignment.

5. Install the appropriate flange bolts.

a. If the installation requires a 1/4–18 NPT connection(s), use four 1.75-in. flange bolts. Finger tighten the bolts. Go to Step d.

B

C

A

A

45Operation and Maintenance

Page 52: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

Operation and MaintenanceMay 2016

b. If the installation requires a 1/2–14 NPT connection(s), use flange adapters and four 2.88-in. process flange/adapter bolts.

c. Hold the flange adapters and adapter O-rings in place while finger-tightening the bolts. d. Tighten the bolts to the initial torque value using a crossed pattern. See Table 4-1 for appropriate

torque values. e. Tighten the bolts to the final torque value using a crossed pattern. See Table 4-1 for appropriate

torque values. When fully tightened, the bolts should extend through the top of the module housing.

f. Torque alignment screws to 30 in-lbs. (3.4 N-m). If the installation uses a conventional manifold, then install flange adapters on the process end of the manifold using the 1.75-in. flange bolts supplied with the transmitter.

Table 4-1. Bolt Installation Torque Values

6. If the sensor module PTFE O-rings are replaced, re-torque the flange bolts and alignment cap screws after installation to compensate for seating of the PTFE O-ring.

7. Install the drain/vent valve.

a. Apply sealing tape to the threads on the seat. Starting at the base of the valve with the threaded end pointing toward the installer, apply two clockwise turns of sealing tape.

b. Take care to place the opening on the valve so that process fluid will drain toward the ground and away from human contact when the valve is opened.

c. Tighten the drain/vent valve to 250 in-lb. (28.25 N-m). d. Tighten the stem to 70 in-lb. (8 N-m).

NoteDue to the Range 1 DP Sensor's high accuracy at low pressures, extra steps are required to optimize performance. It is necessary to temperature soak the assembly using the following procedure.

8. After replacing O-rings on DP Range 1 transmitters and re-installing the process flange, expose the transmitter to a temperature of 185 °F (85 °C) for two hours.

9. Re-tighten the flange bolts in a cross pattern.

10.Again, expose the transmitter to a temperature of 185 °F (85 °C) for two hours before calibration.

Bolt material Initial torque value Final torque value

CS-ASTM-A449 Standard 300 in-lb (34 N-m) 650 in-lb (73 N-m)

316 SST—Option L4 150 in-lb (17 N-m) 300 in-lb (34 N-m)

ASTM-A-193-B7M—Option L5 300 in-lb (34 N-m) 650 in-lb (73 N-m)

Alloy K-500—Option L6 300 in-lb (34 N-m) 650 in-lb (73 N-m)

ASTM-A-453-660—Option L7 150 in-lb (17 N-m) 300 in-lb (34 N-m)

ASTM-A-193-B8M—Option L8 150 in-lb (17 N-m) 300 in-lb (34 N-m)

46 Operation and Maintenance

Page 53: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

TroubleshootingMay 2016

47Troubleshooting

Section 5 Troubleshooting

Measurement troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 48 Communication troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 50Service support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 53

5.1 Section overviewThis section provides summarized troubleshooting suggestions for the most common operating problems on the Rosemount™ 3051S MultiVariable™ FOUNDATION™ Fieldbus Transmitter (3051SMV).

If a malfunction is suspected despite the absence of any diagnostic messages on the communicator display, follow the procedures described to verify transmitter hardware and process connections are in good working order. Always deal with the most likely and easiest-to-check conditions first.

5.2 Safety messagesProcedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.

Explosions could result in death or serious injury.

Do not remove the transmitter cover in explosive atmospheres when the circuit is live.

Before connecting an Emerson Field Communicator in an explosive atmosphere, make sure the instruments in the segment are installed in accordance with intrinsically safe or non-incendive field wiring practices.

Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.

Both transmitter covers must be fully engaged to meet flameproof/explosion-proof requirements.

Failure to follow these installation guidelines could result in death or serious injury.

Make sure only qualified personnel perform the installation.

Electrical shock could cause death or serious injury.

If the sensor is installed in a high-voltage environment and a fault or installation error occurs, high voltage may be present on the transmitter leads and terminals.

Use extreme caution when making contact with the leads and terminals.

Static electricity can damage sensitive components.

Observe safe handling precautions for static-sensitive components.

Page 54: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

TroubleshootingMay 2016

5.3 Measurement troubleshootingThe transmitter provides a means to display the current process variables and flow calculations. If the process variable reading is unexpected, this section provides the symptoms and possible corrective actions.

Table 5-1. Unexpected Process Variable (PV) Readings

Symptom Corrective action

High PV Reading, Erratic PV Reading, Low or no PV reading

Primary element• Check for restrictions at the primary element.

• Check the installation and condition of the primary element.

• Note any changes in process fluid properties that may affect output.

Impulse piping • Check to ensure the pressure connection is correct.

• Check for leaks or blockage.

• Check to ensure that blocking valves are fully open.

• Check for entrapped gas in liquid lines or for liquid in gas lines.

• Check to ensure the density of fluid in impulse lines is unchanged.

• Check for sediment in the transmitter process flange.

• Make sure that process fluid has not frozen within the process flange.

Power Supply• Check the output voltage of the power supply at the transmitter. It should be 9–30 V dc (9 to 17.5

V dc for FISCO)

Flow configuration (fully compensated mass flow feature board only) • Verify flow configuration is correct for current application

Process Temperature RTD Input• Verify the PT Mode (Normal, Fixed, Back-up)

• Verify the correct Callendar-Van Dusen coefficients

• Verify all wire terminations

• Verify sensor is a Pt 100 RTD

• Replace Pt 100 sensor

Sensor module • Check for obvious defects, such as a punctured isolating diaphragm or fill fluid loss, and if

replacement is needed, contact the nearest Emerson Process Management Service Center.

• Check for proper fill fluid characteristics (see Fill fluid for more information).

48 Troubleshooting

Page 55: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

TroubleshootingMay 2016

5.3.1 Fill fluidThe following performance limitations may inhibit efficient or safe operation. Critical applications should have appropriate diagnostic and backup systems in place.

Pressure transmitters contain an internal fill fluid. It is used to transmit the process pressure through the isolating diaphragms to the pressure sensor module. In rare cases, oil loss paths in oil-filled pressure transmitters can be created. Possible causes include: physical damage to the isolator diaphragms, process fluid freezing, isolator corrosion due to an incompatible process fluid, etc.

A transmitter with oil fill fluid loss may continue to perform normally for a period of time. Sustained oil loss will eventually cause one or more of the operating parameters to exceed published specifications as the operating point output continues to drift. Symptoms of advanced oil loss and other unrelated problems include:

Sustained drift rate in true zero and span or operating point output or both

Sluggish response to increasing or decreasing pressure or both

Limited output rate or very nonlinear output or both

Change in output process noise

Noticeable drift in operating point output

Abrupt increase in drift rate of true zero or span or both

Unstable output

Output saturated high or low

49Troubleshooting

Page 56: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

TroubleshootingMay 2016

5.4 Communication troubleshooting

NoteUse this section if other devices appear on the segment, communicate, and remain on the segment. If other devices don't appear on the segment, communicate, or stay on the segment the electrical characteristics of the segment should be checked.

Table 5-2. Troubleshooting Guide

Symptom Recommended actions(1)

1. The corrective actions should be done with consultation of the system integrator.

Device does not show up on segment

Device power1. Cycle power to device.

2. Ensure the device is connected to the segment.

3. Check voltage at terminals. There should be 9–30V or 17.5V for FISCO.

4. Check to ensure the device is drawing current. There should be approximately 17 mA.

Segment1. Remove other devices from segment to check for interfering devices.

Incompatible network settings1. Change host network parameters. Refer to host documentation for procedure.

Electronics failing1. Electronics board loose in housing.

2. Replace electronics.

Device does not stay on segment

Signal levels(2)

1. Check for two terminators.

2. Check for excess cable length.

3. Check for bad power supply or conditioner.

2. Refer to wiring and installation 31.25 kbit/s, voltage mode, wire medium application guide AG-140 available from the FieldComm Group.

Segment noise(2)

1. Check for incorrect grounding.

2. Check for correct shielded wire.

3. Tighten all wiring and shield connections on the affected part of the segment.

4. Check for corrosion or moisture on terminals.

5. Check for bad power supply.

6. Check for electrically noisy equipment attached to the instrument ground.

Electronics failure1. Check for loose electronics board in housing.

2. Replace electronics.

3. Check for water in the terminal housing.

50 Troubleshooting

Page 57: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

TroubleshootingMay 2016

5.4.1 Alarms and conditionsDetailed tables of the possible messages that will appear on either the LCD display, a Field Communicator, or a PC-based configuration and maintenance system are listed in the section below. Use the table below to diagnose particular status messages.

Table 5-3. Failed–Fix Now

Alert labelLCD display

messageDescription Recommended action

Electronic Circuit Board

Failure

FAILBOARD ERROR

Failure has been detected in the electronic circuit board

1. Replace the electronic circuit board.

Sensor Module Failure

FAILSENSOR ERROR

Failure has been detected in the sensor module

1. Replace the sensor module.

Sensor Module Communication

Failure

SNSRCOMM ERROR

Electronic circuit board has stopped receiving updates from the sensor module

1. Verify the device is receiving adequate supply voltage.

2. Remove front housing cover (considering hazardous location requirements) and check the cable and cable connection between sensor module and electronic circuit board.

3. Replace LCD display.

4. Replace the sensor module.

5. Replace the electronic circuit board.

Sensor Module Incompatibility

SNSR INCOMP ERROR

Sensor module is not compatible with the electronic circuit board

1. Replace the sensor with a multivariable sensor module.

Process Temperature Sensor Failure

FAILPT

ERROR

Failure has been detected in the process temperature sensor

1. Verify the conditions of the process where the transmitter is installed.

Note: If a junction box is installed/utilized, check the connections for the RTD sensor.

2. Remove back housing cover (considering hazardous location requirements) and check the cable and cable connection between terminal block and RTD sensor.

3. Replace the RTD sensor.

4. Replace the electronic circuit board.

Table 5-4. Out of Specification–Fix Soon

Alert labelLCD display

messageDescription Recommended action

Differential Pressure Out of

Limits

DP LIMIT

Differential pressure has exceeded the transmitter's maximum measurement range

1. Verify conditions of the process where the transmitter is installed.

2. Check transmitter pressure connection to make sure it is not plugged and isolating diaphragms are not damaged.

3. Replace the sensor module.

Static Pressure Out of Limits

AP GP LIMIT

Static pressure has exceeded the transmitter's maximum measurement range

1. Verify conditions of the process where the transmitter is installed.

2. Check transmitter pressure connection to make sure it is not plugged and isolating diaphragms are not damaged.

3. Replace the sensor module.

51Troubleshooting

Page 58: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

TroubleshootingMay 2016

Process Temperature Out of Limits

PTLIMIT

Process temperature has exceeded the transmitter's maximum configured measurement range

1. Verify conditions of the process where the transmitter is installed.

Note: If a junction box is installed/utilized, check the connections for the RTD sensor.

2. Remove back housing cover (considering hazardous location requirements) and check the cable and cable connection between terminal block and the RTD sensor.

3. Replace the RTD sensor.

4. Replace the electronic circuit board.

Module Temperature Out of Limits

SNSRTLIMIT

Module temperature sensor has exceeded its normal range

1. Check process and ambient temperatures where the transmitter is installed to ensure they are within specifications.

2. Replace the sensor module.

Table 5-5. Maintenance Required

Alert labelLCD display

messageDescription Recommended action

Mass Flow Missing Process

Temperature

PTCONFIG ERROR

Process temperature measurement is not available for mass flow calculations

1. If using a temperature sensor in the process, enable the process temperature measurement.

2. Otherwise, configure mass flow to use backup or fixed process temperature.

Mass Flow Out of Limits

FLOWLIMIT

Mass flow has exceeded the transmitter's maximum measurement range

1. Verify conditions of the process where the transmitter is installed.

2. Verify operating ranges used in the flow configuration.

3. Check transmitter pressure connection to make sure it is not plugged and isolating diaphragms are not damaged.

Display Update Error

LCDUPDATE ERROR

Electronic circuit board has lost communication with the display

1. Remove front housing cover (considering hazardous location requirements) and check the 4-pin connector between the display and electronic circuit board.

2. Check cable and cable connection between the sensor module and electronic circuit board.

3. Replace the display.

4. Replace electronic circuit board.

Table 5-6. Function Check

Alert labelLCD display

messageDescription Recommended action

Check Function [None] Transducer block mode is not in auto

1. Check if any transducer block is currently under maintenance.

2. If no transducer block is under maintenance, follow site procedures to change affected transducer block's actual mode to auto.

Table 5-4. Out of Specification–Fix Soon

Alert labelLCD display

messageDescription Recommended action

52 Troubleshooting

Page 59: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual 00809-0100-4853, Rev AA

TroubleshootingMay 2016

5.5 Service supportTo expedite the return process outside of the United States, contact the nearest Emerson Process Management representative.

Within the United States, call the Emerson Process Management Instrument and Valves Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assists with any needed information or materials.

The center will ask for product model and serial numbers, and will provide a Return Material Authorization (RMA) number. The center will also ask for the process material to which the product was last exposed.

Emerson Process Management Instrument and Valves Response Center representatives will explain the additional information and procedures necessary to return goods exposed to hazardous substances.

Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of and understand the hazard. If the product being returned was exposed to a hazardous substance as defined by OSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardous substance identified must be included with the returned goods.

53Troubleshooting

Page 60: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

TroubleshootingMay 2016

54 Troubleshooting

Page 61: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

Appendix A Specifications and Reference Data

Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 55Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 58Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 60Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 62Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 64Spare parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 72Function block information and location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 78

A.1 Specifications

A.1.1 Performance specifications

For zero-based spans, reference conditions, silicone oil fill, glass-filled PTFE O-rings, SST materials and coplanar flange process connections.

Conformance to specification (±3 [Sigma])

Technology leadership, advanced manufacturing techniques, and statistical process control ensure measurement specification conformance to ±3or better.

Reference accuracy

Models Classic Ultra for Flow

3051SMV_ _1: Differential pressure, static pressure, and temperature3051SMV_ _2: Differential pressure and static pressure

DP Ranges 2–3

±0.04% of span;For spans less than 10:1,

±0.04% of reading up to 8:1 DP turndown from URL; ±(0.04 + 0.0023[URL/RDG(1)])% reading to 200:1 DP turndown from URL(2)

DP Range 4 ±0.055% of spanFor spans less than 10:1,±(0.015 + 0.005[URL/Span])% of span

±0.05% of reading up to 3:1 DP turndown from URL±(0.05 + 0.0145[URL/RDG])% of reading to 100:1 DP turndownfrom URL

DP Range 5 ±0.065% of spanFor spans less than 10:1,±(0.015 + 0.005[URL/Span])% of span

N/A

DP Range 1 ±0.10% of span;For spans less than 15:1,

N/A

AP and GP Ranges 3–4(3)

±0.055% of span;For spans less than 10:1,

±0.025% of span;For spans less than 10:1,

Process Temp. RTD Interface(4)

±0.67 °F (0.37 °C) ±0.67 °F (0.37 °C)

1. RDG refers to transmitter DP reading.

2. Ultra for Flow is only available for Rosemount™ 3051SMV DP Ranges 2–3. For calibrated spans from 1:1 to 2:1 of URL.

3. For DP range 1, 4 or 5, Classic MV and Ultra for Flow static pressure accuracy is ±0.055% of span on SP Range 4 only. For spans less than 5:1, ±(0.013[URL/Span])% of span.

4. Specifications for process temperature are for the transmitter portion only. The transmitter is compatible with any Pt 100 (100 ohm platinum) RTD. Examples of compatible RTDs include Rosemount Series 68 and 78 RTD Temperature Sensors.

0.01 0.004+ URLspan-------------

% of span

0.025 0.005+ URLspan-------------

% of span

0.0065 URLspan-------------

% of span 0.004 URLspan-------------

% of span

55Specifications and Reference Data

Page 62: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

Long term stability

Total performance(1)

Models Classic Ultra for Flow(2)

3051SMV DP Ranges 2–3 ±0.14% of span; for ±50 °F (28 °C) temperature changes; 0-100% relative humidityfrom 1:1 to 5:1 rangedown

±0.15% of reading; for ±50 °F (28 °C) temperature changes; 0-100% relative humidityover 8:1 DP turndown from URL

1. Total performance is based on combined errors of reference accuracy, ambient temperature effect, and line pressure effect. Specifications apply only to differential pressure measurement.

2. Ultra for Flow is only available for Rosemount 3051SMV DP Ranges 2–3.

Multivariable flow performance(1)

Mass Flow Reference Accuracy(2)

Models(1)(2) Ultra for Flow Classic(3)

3051SMV DP Ranges 2–3

±0.65% of Flow Rate over a 14:1 flow range (200:1 DP range)

±0.70% of Flow Rate over 8:1 flow range (64:1 DP range)

DP Range 1 N/A ±0.90% of Flow Rate over 8:1 flow range (64:1 DP range)

1. Flow performance specifications assume device is configured for full compensation of static pressure, process temperature, density, viscosity, gas expansion, discharge coefficient, and thermal correction variances over the specified process operating range using multivariable type M or flowmeter measurement types 1 through 4.

2. Uncalibrated differential producer (0.2 < beta < 0.6 Orifice) installed per ASME MFC 3M or ISO 5167-1. Uncertainties for discharge coefficient, producer bore, tube diameter, and gas expansion factor as defined in ASME MFC 3M or ISO 5167-1. Reference accuracy does not include RTD sensor accuracy.

3. Differential pressure calibrated at up to 1/10th full scale for optimum flow accuracy/rangeability.

Models Ultra for Flow Classic

3051SMV DP Ranges 2–5AP & GP Ranges 3–4

±0.15% of URL for 15 years; for ±50 °F (28 °C) temperature changes, up to 1000 psi (68,9 bar) line pressure

±0.20% of URL for 15 years;for ±50 °F (28 °C) temperature changes,up to 1000 psi (68,9 bar) line pressure

Process TemperatureRTD Interface(1)

1. Specifications for process temperature are for the transmitter portion only. The transmitter is compatible with any Pt 100 (100 ohm platinum) RTD. Examples of compatible RTDs include Rosemount Series 68 and 78 RTD Temperature Sensors.

The greater of ±0.185 °F (0.103 °C) or 0.1% of reading per 5 years (excludes RTD sensor stability).

Warranty(1)

Models Ultra for Flow Classic

3051S Scalable Products 15-year limited warranty(2) 1-year limited warranty(3)

1. Warranty details can be found in Emerson™ Process Management Terms & Conditions of Sale, Document 63445, Rev G (10/06).

2. Rosemount Ultra for Flow transmitters have a limited warranty of fifteen (15) years from date of shipment. All other provisions of Emerson Process Management standard limited warranty remain the same.

3. Goods are warranted for one (1) year from the date of initial installation or eighteen (18) months from the date of shipment by seller, whichever period expires first.

56 Specifications and Reference Data

Page 63: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

Ambient temperature effect

Mounting position effects

Vibration effect

Less than ±0.1% of URL when tested per the requirements of IEC60770-1 field or pipeline with high vibration level (10–60 Hz 0.21mm displacement peak amplitude/60–2000 Hz 3g).

For Housing Style codes 1J, 1K, and 1L:Less than ±0.1% of URL when tested per the requirements of IEC60770-1 field with general application or pipeline with low vibration level (10–60 Hz 0.15mm displacement peak amplitude/60–500 Hz 2g).

Models Classic per 50 °F (28 °C)

Ultra for Flow(1)

-40 to 185 °F (-40 to 85 °C)

1. Ultra for Flow is only available for Rosemount 3051SMV DP Ranges 2–3.

3051SMV_ _1: Differential pressure, static pressure, and temperature3051SMV_ _2: Differential pressure and static pressure

DP Ranges 2–3 ± (0.0125% URL + 0.0625% span) from 1:1 to 5:1;± (0.025% URL + 0.125% span) for > 5:1

±0.13% reading up to 8:1 DP turndown from URL; ±(0.13 + 0.0187 [URL/RDG(2)])% reading to 100:1 DP turndown from URL

2. RDG refers to transmitter DP reading.

DP Range 4±(0.025% URL + 0.125% span) from 1:1 to 30:1±(0.035% URL + 0.125% span) from 30:1 to 100:1

±0.130% of reading less than or equal to 3:1±(0.050 + 0.065 [URL/RDG])% of reading greater than 3:1

DP Range 5 ±(0.025% URL + 0.125% span) from 1:1 to 30:1±(0.035% URL + 0.125% span) from 30:1 to 100:1

N/A

DP Range 1 ± (0.1% URL + 0.25% Span) from 1:1 to 50:1

N/A

AP and GP ± (0.0125% URL + 0.0625% span) from 1:1 to 10:1;± (0.025% URL + 0.125% span) for >10:1

± (0.009% URL + 0.025% span) from 1:1 to 10:1;± (0.018% URL + 0.08% span) for >10:1

Process temperature RTD interface

±0.39 °F (0,216 °C) per 50 °F (28 °C) ±0.39 °F (0,216 °C) per 50 °F (28 °C)

Models Ultra for Flow and Classic

3051SMV_ _ 1, 2DP: Zero shifts up to ±1.25 inH2O (3,11 mbar), which can be zeroed; no span effect

AP/GP: Zero shifts to ±2.5 inH2O (6,22 mbar), which can be zeroed; no span effect

57Specifications and Reference Data

Page 64: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

Electromagnetic compatibility (EMC) Transient protection (option T1)

Tested in accordance with IEEE C62.41.2-2002, Location Category B

6 kV crest (0.5 s–100 kHz)

3 kA crest (8 � 20 s)

6 kV crest (1.2 � 50 s)

Range and sensor limits

Meets all industrial environment requirements of EN61326 and NAMUR NE-21. Maximum deviation < 1% Span during EMC disturbance.(1)

1. Rosemount 3051SMV and 3051SF_1, 3, 5, 7 require shielded cable for the process temperature connection.

Ran

ge

Rosemount 3051SMV Differential pressure range and sensor limits

Minimum span Range limits

Ultra for Flow Classic Lower (LRL)(1)

1. Lower (LRL) is 0 inH2O (0 mbar) for Ultra for Flow.

Upper (URL)

1 N/A 0.50 inH2O (1,24 mbar) -25.00 inH2O (-62,16 mbar) 25.00 inH2O (62,16 mbar)

2 1.30 inH2O (3,11 mbar) 2.50 inH2O (4,14 mbar) -250.00 inH2O (-621,60 mbar) 250.00 inH2O (621,60 mbar)

3 5.00 inH2O (12,43 mbar) 10.00 inH2O (16,58 mbar) -1000.00 inH2O (-2,48 bar) 1000.00 inH2O (2,48 bar)

4 1.50 psi (103,4 mbar) 3.00 psi (137,90 mbar) -150.00 psi (-10,34 bar) 150.00 psi (10,34 bar)

5 N/A 20.00 psi (919,30 mbar) -2000.00 psi (137,89 bar) 2000.00 psi (137,89 bar)

Ran

ge

Rosemount 3051SMV Static pressure range and sensor limits

Minimum span Range limits

Ultra for Flow Classic Upper (URL)Lower (LRL) (Absolute)

Lower (LRL) (Gage)(1)(2)

1. Assumes atmospheric pressure of 14.7 psig (1 bar).

2. Inert Fill: Minimum pressure = 1.5 psia (0,10 bar) or -13.2 psig (-0,91 bar).

3 4.0 psi (275,79 mbar) 8.0 psi (551,58 mbar) 800.00 psig (55,15 bar) 0.50 psia (34,47 mbar) -14.20 psig (-0,97 bar)

4 18.13 psi (1,25 bar) 36.26 psi (2,50 bar) 3626 psia (250.00 bar)(3)

3. For SP Range 4 and DP Range 1, the URL is 2000 psi (137,9 bar).

0.50 psia (34,47 mbar) -14.20 psig (-0,97 bar)

Process temperature RTD interface range limits(1)

1. Designed to accommodate a Pt 100 RTD sensor. Examples of compatible RTDs include Rosemount Series 68 and 78 RTD Temperature Sensors.

Minimum span Upper (URL) Lower (LRL)

50 °F (28 °C) 1562 °F (850 °C) -328 °F (-200 °C)

58 Specifications and Reference Data

Page 65: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

Service

Rosemount 3051SMV_P (direct process variable output) and 3051SMV_M (mass flow output)

Liquid, gas, and vapor applications

Overpressure limits

Transmitters withstand the following limits without damage:

Coplanar multivariable sensor module

Rosemount 3051SMV_ _1 or 2, 3051SF_1, 2, 5, or 6

Static pressure limit

Rosemount 3051SMV_ _1: Differential and static pressure, temperature

3051SMV_ _2: Differential pressure and static pressure

Operates within 0.5 psia (0,03 bar) and the values in the table below:

Burst pressure limits

3051SMV with coplanar or traditional process flange

10000 psig (689,5 bar)

Temperature limits

Humidity limits

0–100% relative humidity

Turn-on time

Performance within specifications less than ten seconds for Rosemount 3051SMV (typical) after power is applied to the transmitter.

Volumetric displacement

Less than 0.005 in3 (0,08 cm3)

Damping

Output response to a step change is user-selectable from 0 to 60 seconds for one time constant. Each variable can be individually adjusted. This software damping is in addition to sensor module response time.

DP Range

Static pressure range (GP/AP)

3 4

1 1600 psi (110,32 bar) 2000 psi (137,90 bar)

2 1600 psi (110,32 bar) 3626 psi (250,00 bar)

3 1600 psi (110,32 bar) 3626 psi (250,00 bar)

4 N/A 3626 psi (250,00 bar)

5 N/A 3626 psi (250,00 bar)

DP Range

Static pressure range (GP/AP)

3 4

1 800 psi (55,15 bar) 2000 psi (137,90 bar)

2 800 psi (55,15 bar) 3626 psi (250,00 bar)

3 800 psi (55,15 bar) 3626 psi (250,00 bar)

4 N/A 3626 psi (250,00 bar)

5 N/A 3626 psi (250,00 bar)

Ambient

-40 to 185 °F (-40 to 85 °C)With LCD display (1): -40 to 175 °F (-40 to 80 °C)

1. LCD display may not be readable and LCD display updates will be slower at temperatures below -4 °F (-20 °C).

Storage

-50 to 185 °F (-46 to 85 °C)With LCD display: -40 to 185 °F (-40 to 85 °C)

Process temperature limits

At atmospheric pressures and above:

Silicone fill sensor(2)(3)

2. Process temperatures above 185 °F (85 °C) require derating the ambient limits by a 1.5:1 ratio. For example, for process temperature of 195 °F (91 °C), new ambient temperature limit is equal to 170 °F (77 °C). This can be determined as follows: (195 °F - 185 °F) x 1.5 = 15 °F,185 °F - 15 °F = 170 °F

3. 212 °F (100 °C) is the upper process temperature limit for DP Range 0.

with coplanar flange -40 to 250 °F (-40 to 121 °C)(4)

4. 220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for pressures below 0.5 psia.

with traditional flange -40 to 300 °F (-40 to 149 °C)(4)

with level flange -40 to 300 °F (-40 to 149 °C)(4)

with Rosemount 305 Integral Manifold

-40 to 300 °F (-40 to 149 °C)(4)(5)

Inert fill sensor(2) -40 to 185 °F (-40 to 85 °C)(5)

5. For 3051SMV_ _ 1, 2, 140 ° F (60 °C) limit in vacuum service.

59Specifications and Reference Data

Page 66: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

A.1.3 Physical specifications

Electrical connections

1/2–14 NPT, G1/2, and M20 � 1.5 (CM20) conduit. Fieldbus interface connections fixed to terminal block.

Process connections

1/4–18 NPT on 21/8-in. centers

1/2–14 NPT and RC 1/2 on 2-in.(50.8 mm), 21/8-in. (54.0 mm), or 21/4-in. (57.2 mm) centers (process adapters)

Process-wetted parts

Process isolating diaphragms

– 316L SST (UNS S31603)

– Alloy C-276 (UNS N10276)

– Alloy 400 (UNS N04400)

– Tantalum (UNS R05440)

– Gold-plated Alloy 400

– Gold-plated 316L SST

Drain/vent valves

316 SST, Alloy C-276, or Alloy 400/K-500 material (Drain vent seat: Alloy 400, Drain vent stem: Alloy K-500)

Process flanges and adapters

– Plated carbon steel

– SST: CF-8M (Cast 316 SST) per ASTM A743

– Cast C-276: CW-12MW per ASTM A494

– Cast Alloy 400: M-30C per ASTM A494

Wetted O-rings

Glass-filled PTFE

Graphite-filled PTFE

Non-wetted parts

Electronics housing

– Low-copper aluminum alloy or CF-8M (Cast 316 SST)

– Enclosures meet NEMA® 4X, IP66, and IP68 when properly installed (66 ft [20 m] for 168 hours)

Coplanar sensor module housing

SST: CF-3M (Cast 316L SST)

Bolts

– Plated carbon steel per ASTM A449, Type 1

– Austenitic 316 SST per ASTM F593

– ASTM A453, Class D, Grade 660 SST

– ASTM A193, Grade B7M alloy steel

– ASTM A193, Class 2, Grade B8M SST

– Alloy K-500

Sensor module fill fluid

Silicone is standard.

Inert is available as option code (L1).

Inert for in-line series uses Fluorinert™ FC-43.

Inert for coplanar series uses Halocarbon.

Paint

Polyurethane

Cover O-rings

Buna-N

Shipping weights for Rosemount 3051S MultiVariable™ Transmitter (3051SMV)

Rosemount 3051SMV with PlantWeb™ housing: 6.7 lb (3,1 kg)

Table A-1. Transmitter Option Weights

Option code

OptionAdd

lb (kg)

1J, 1K, 1L SST PlantWeb housing 3.5 (1,6)

1A, 1B, 1C Aluminum PlantWeb housing 1.1 (0,5)

M5(1)

LCD display for Aluminum PlantWeb housing

0.8 (0,4)

LCD display for SST PlantWeb housing 1.6 (0,7)

B4SST mounting bracket for coplanar flange

1.2 (0,5)

B1, B2, B3 Mounting Bracket for traditional flange 1.7 (0,8)

B7, B8, B9Mounting Bracket for traditional flange with SST bolts

1.7 (0,8)

BA, BC SST bracket for traditional flange 1.6 (0,7)

B4 SST mounting bracket for In-Line 1.3 (0,6)

F12, F22(2) SST traditional flange with SST drain vents

3.2 (1,5)

F13, F23(2) Cast C-276 traditional flange with Alloy C-276 drain vents

3.6 (1,6)

E12, E22(2) SST coplanar flange with SST drain vents

1.9 (0,9)

F14, F24(2) Cast Alloy 400 traditional flange with Alloy 400/K-500 drain vents

3.6 (1,6)

F15, F25(2) SST traditional flange with Alloy C-276 drain vents

3.2 (1,5)

G21 Level flange—3-in., 150 12.6 (5,7)

G22 Level flange—3-in., 300 15.9 (7,2)

G11 Level flange—2-in., 150 6.8 (3,1)

60 Specifications and Reference Data

Page 67: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

G12 Level flange—2-in., 300 8.2 (3,7)

G31DIN Level flange, SST, DN 50, PN 40

7.8 (3,5)

G41DIN Level flange, SST, DN 80, PN 40

13.0 (5,9)

1. Includes LCD display and display cover.

2. Includes mounting bolts.

Item Weight in lb. (kg)

Aluminum standard cover 0.4 (0,2)

SST standard cover 1.3 (0,6)

Aluminum display cover 0.7 (0,3)

SST display cover 1.5 (0,7)

LCD display(1)

1. Display only.

0.1 (0,04)

PlantWeb terminal block 0.2 (0,1)

Table A-1. Transmitter Option Weights

Option code

OptionAdd

lb (kg)

61Specifications and Reference Data

Page 68: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

A.2 Dimensional drawingsProcess adapters (option D2) and Rosemount 305 Integral Manifolds must be ordered with the transmitter.

Figure A-1. Transmitter with Coplanar Sensor Module and Coplanar Flange

Dimensions are in inches (millimeters).

Figure A-2. Transmitter with Coplanar Sensor Module and Traditional Flange

Dimensions are in inches (millimeters).

4.51 (115)

6.55 (166)

4.20 (107)

8.53(217)

9.63(245)

1.63(41)

2.13 (54)

9.26(235)

3.40 (86)1.10(28)

62 Specifications and Reference Data

Page 69: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

Figure A-3. Coplanar Flange Mounting Configurations

Dimensions are in inches (millimeters).

Figure A-4. Traditional Flange Mounting Configurations

Dimensions are in inches (millimeters).

Pipe mount Panel mount

6.25 (159)

5.17 (131)

3.54 (90)

4.73 (120)

4.51 (115)

2.58 (66)

6.15(156)

2.71(71)

Pipe mount Pipe mount (flat bracket) Panel mount

0.93(24)

2.62(67)

3.40(86)

8.10(205)

10.71(272)

2.62(67)

7.70(196)

8.10(205)

4.85(123)3.40

(86)

63Specifications and Reference Data

Page 70: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

A.3 Ordering information

Specification and selection of product materials, options, or components must be made by the purchaser of the equipment.

Table A-2. Rosemount 3051SMV HART® and Fieldbus Ordering Information

Model Transmitter type

3051SMV Scalable multivariable transmitter

Performance class(1)

Measurement Types 1 and 2

3(2) Ultra for Flow: 0.04% reading DP accuracy, 200:1 rangedown,15-year stability, 15-year limited warranty ★

5 Classic MV: 0.04% span DP accuracy, 100:1 rangedown, 15-year stability ★

Measurement Types 3 and 4

1 Ultra: 0.025% span DP accuracy, 200:1 rangedown, 15-year stability, 15-year limited warranty ★

2 Classic: 0.035% span DP accuracy, 150:1 rangedown, 15-year stability ★

3(2) Ultra for Flow: 0.04% reading DP accuracy, 200:1 rangedown,15-year stability, 15-year limited warranty ★

Multivariable type

M Measurement with fully compensated mass and energy(3) flow calculations ★

P Measurement of process variables only (no flow calculations) ★

Measurement type

1 Differential pressure, static pressure, and temperature ★

2 Differential pressure and static pressure ★

3 Differential pressure and temperature ★

4 Differential pressure ★

Differential pressure range(4)

0(5) -3 to 3 inH2O (-7,46 to 7,46 mbar) ★

1 -25 to 25 inH2O (-62,16 to 62,16 mbar) ★

2 -250 to 250 inH2O (-621,60 to 621,60 mbar) ★

3 -1000 to 1000 inH2O (-2,48 to 2,48 bar) ★

4-150 to 150 psi (-10,34 to 10,34 bar) for measurement types 1 and 2; -300 to 300 psi (-20,68 to 20,68 bar) for measurement types 3 and 4

5 -2000 to 2000 psi (-137,89 to 137,89 bar) ★

Static pressure type

N(6) None ★

A Absolute ★

G Gage ★

Static pressure range Absolute Gage

N(6) None N/A N/A ★

3 Range 3 0.5 to 800 psia (0,03 to 55,15 bar) -14.2 to 800 psig (-0,98 to 55,15 bar) ★

4(7) Range 4 0.5 to 3626 psia (0,03 to 250,00 bar) -14.2 to 3626 psig (-0,98 to 250,00 bar) ★

64 Specifications and Reference Data

Page 71: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

Temperature input

N(8) None ★

R(9) RTD input (type Pt 100, -328 to 1562 °F [-200 to 850 °C]) ★

Isolating diaphragm

2(10) 316L SST ★

3(10) Alloy C-276 ★

5(11) Tantalum

7(10) Gold-plated 316L SST

Process connection Size

Material type

Flange material

Drain vent Bolting

000 None (no process flange) N/A N/A N/A N/A ★

A11(12) Assemble to Rosemount 305/306 integral manifold

N/A N/A N/A N/A ★

A12(12)Assemble to Rosemount 304 or AMF manifold with SST traditional flange

N/A N/A N/A N/A ★

A15(12)

Assemble to Rosemount 304 or AMF manifold to SST traditional flange with Alloy C-276 drain vents

N/A N/A N/A N/A ★

A16(12) Assemble to 304 or AMF manifold to DIN SST traditional flange

N/A N/A N/A N/A ★

A22Assemble AMF manifold to SST coplanar flange

N/A N/A N/A N/A ★

B11(12)(13) Assemble to one Rosemount 1199 seal

N/A N/A N/A N/A ★

B12(12)(13) Assemble to two Rosemount 1199 seals

N/A N/A N/A N/A ★

C11(12) Assemble to Rosemount 405C or 405P primary element

N/A N/A N/A N/A ★

D11(12)Assemble to Rosemount 1195 integral orifice and Rosemount 305 integral manifold

N/A N/A N/A N/A ★

EA2(12)Assemble to Rosemount 485 or 405A Annubar primary element with coplanar flange

N/A SST 316 SST N/A ★

EA3(12)Assemble to Rosemount 485 or 405A Annubar primary element with coplanar flange

N/A Cast C-276 Alloy C-276 N/A ★

EA5(12)Assemble to Rosemount 485 or 405A Annubar primary element with coplanar flange

N/A SST Alloy C-276 N/A ★

E11 Coplanar flange 1/4–18 NPT Carbon steel 316 SST N/A ★

E12 Coplanar flange 1/4–18 NPT SST 316 SST N/A ★

65Specifications and Reference Data

Page 72: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

E13(10) Coplanar flange 1/4–18 NPT Cast C-276 Alloy C-276 N/A ★

E14 Coplanar flange 1/4–18 NPT Cast Alloy 400 Alloy 400/K-500 N/A ★

E15(10) Coplanar flange 1/4–18 NPT SST Alloy C-276 N/A ★

E16(10) Coplanar flange 1/4–18 NPT Carbon steel Alloy C-276 N/A ★

E21 Coplanar flange RC 1/4 Carbon steel 316 SST N/A ★

E22 Coplanar flange RC 1/4 SST 316 SST N/A ★

E23(10) Coplanar flange RC 1/4 Cast C-276 Alloy C-276 N/A ★

E24 Coplanar flange RC 1/4 Cast Alloy 400 Alloy 400/K-500 N/A ★

E25(10) Coplanar flange RC 1/4 SST Alloy C-276 N/A ★

E26(10) Coplanar flange RC 1/4 Carbon steel Alloy C-276 N/A ★

F12 Traditional flange 1/4–18 NPT SST 316 SST N/A ★

F13(10) Traditional flange 1/4–18 NPT Cast C-276 Alloy C-276 N/A ★

F14 Traditional flange 1/4–18 NPT Cast Alloy 400 Alloy 400/K-500 N/A ★

F15(10) Traditional flange 1/4–18 NPT SST Alloy C-276 N/A ★

F22 Traditional flange RC 1/4 SST 316 SST N/A ★

F23(10) Traditional flange RC 1/4 Cast C-276 Alloy C-276 N/A ★

F24 Traditional flange RC 1/4 Cast Alloy 400 Alloy 400/K-500 N/A ★

F25(10) Traditional flange RC 1/4 SST Alloy C-276 N/A ★

F52 DIN-compliant traditional flange 1/4–18 NPT SST 316 SST 7/16-in. bolting ★

G11 Vertical mount level flange 2-in. ANSI class 150 SST N/A N/A ★

G12 Vertical mount level flange 2-in. ANSI class 300 SST N/A N/A ★

G14(10) Vertical mount level flange 2-in. ANSI class 150 Cast C-276 N/A N/A ★

G15(10) Vertical mount level flange 2-in. ANSI class 300 Cast C-276 N/A N/A ★

G21 Vertical mount level flange 3-in. ANSI class 150 SST N/A N/A ★

G22 Vertical mount level flange 3-in. ANSI class 300 SST N/A N/A ★

G31 Vertical mount level flange DIN- DN 50 PN 40 SST N/A N/A ★

EB6Assemble to primary element with manifold and coplanar flange, CS, Alloy C-276

N/A N/A N/A N/A

F32 Bottom vent traditional flange 1/4–18 NPT SST 316 SST N/A

F42 Bottom vent traditional flange RC 1/4 SST 316 SST N/A

F62 DIN-compliant traditional flange 1/4–18 NPT SST 316 SST M10 bolting

F72 DIN-compliant traditional flange 1/4–18 NPT SST 316 SST M12 bolting

G41 Vertical mount level flange DIN- DN 80 PN 40 SST N/A N/A

Transmitter output

A 4–20 mA with digital signal based on HART protocol ★

X(14) Wireless (requires wireless options and wireless PlantWeb housing) ★

F(15) FOUNDATION Fieldbus ★

66 Specifications and Reference Data

Page 73: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

Housing style Material Conduit entry size

1A PlantWeb housing Aluminum 1/2–14 NPT ★

1B PlantWeb housing Aluminum M20 � 1.5 ★

1J PlantWeb housing SST 1/2–14 NPT ★

1K PlantWeb housing SST M20 � 1.5 ★

5A(16) Wireless PlantWeb housing Aluminum 1/2–14 NPT ★

5J(16) Wireless PlantWeb housing SST 1/2–14 NPT ★

1C PlantWeb housing Aluminum G1/2

1L PlantWeb housing SST G1/2

Wireless options (requires option code X and wireless PlantWeb housing)

Update rate

WA User configurable update rate ★

Operating frequency and protocol

3 2.4 GHz DSSS, IEC 62591 (WirelessHART®) ★

Omni-directional wireless antenna

WK External antenna ★

WM Extended range, external antenna ★

WN High-gain, remote antenna

SmartPower(17)

1 Adapter for Black Power Module (I.S. Power Module sold separately) ★

Other options (include with selected model number)

Extended product warranty

WR3 3-year limited warranty ★

WR5 5-year limited warranty ★

RTD cable (RTD sensor must be ordered separately)

C12 RTD Input with 12 ft (3,66 m) of shielded cable ★

C13 RTD Input with 24 ft (7,32 m) of shielded cable ★

C14 RTD Input with 75 ft (22,86 m) of shielded cable ★

C22 RTD Input with 12 ft (3,66 m) of armored shielded cable ★

C23 RTD Input with 24 ft (7,32 m) of armored shielded cable ★

C24 RTD Input with 75 ft (22,86 m) of armored shielded cable ★

C32 RTD Input with 12 ft (3,66 m) of ATEX/IECEx Flameproof cable ★

C33 RTD Input with 24 ft (7,32 m) of ATEX/IECEx Flameproof cable ★

C34 RTD Input with 75 ft (22,86 m) of ATEX/IECEx Flameproof cable ★

PlantWeb control functionality

A01 FOUNDATION Fieldbus advanced control function block suite ★

67Specifications and Reference Data

Page 74: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

Mounting brackets(18)

B4 Coplanar flange bracket, all SST, 2-in. pipe and panel ★

B1 Traditional flange bracket, Carbon steel, 2-in. pipe ★

B2 Traditional flange bracket, Carbon steel, panel ★

B3 Traditional flange flat bracket, Carbon steel, 2-in. pipe ★

B7 Traditional flange bracket, B1 with SST bolts ★

B8 Traditional flange bracket, B2 with SST bolts ★

B9 Traditional flange bracket, B3 with SST bolts ★

BA Traditional flange bracket, B1, all SST ★

BC Traditional flange bracket, B3, all SST ★

Software configuration

C1(19) Custom software configuration (Rosemount 3051SMV Configuration Data Sheet must be completed.) ★

C2(20) Custom flow configuration (Rosemount 3051SMV Configuration Data Sheet must be completed for HART devices or Rosemount 3051SMV Configuration Data Sheet for Fieldbus devices.)

C4(19)(20) NAMUR alarm and saturation levels, high alarm ★

C5(19)(20) NAMUR alarm and saturation levels, low alarm ★

C6(19)(20) Custom alarm and saturation signal levels, high alarm ★

C7(19)(20) Custom alarm and saturation signal levels, low alarm ★

C8(19)(20) Low alarm (standard Rosemount alarm and saturation levels) ★

Flange adapter(21)

D2 1/2–14 NPT flange adapter ★

D9 RC 1/2 SST flange adapter

Ground screw(22)

D4 External ground screw assembly ★

Drain/vent valve(21)

D5 Delete transmitter drain/vent valves (install plugs) ★

D7 Coplanar flange without drain/vent ports

Conduit plug(23)

DO 316 SST conduit plug ★

Product certifications

E1 ATEX Flameproof ★

I1 ATEX Intrinsic Safety ★

IA(24) ATEX FISCO Intrinsic Safety ★

N1 ATEX Type n ★

ND ATEX Dust ★

K1 ATEX Flameproof, Intrinsic Safety, Type n, Dust (combination of E1, I1, N1, and ND) ★

E4 TIIS Flameproof ★

E5 FM Explosion-proof, Dust Ignition-proof ★

68 Specifications and Reference Data

Page 75: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

I5 FM Intrinsically Safe; Nonincendive ★

IE(24) FM FISCO Intrinsic Safety ★

K5 FM Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5 and I5) ★

E6(25) CSA Explosion-proof, Dust Ignition-proof, Division 2 ★

I6 CSA Intrinsically Safe ★

IF(24) CSA FISCO Intrinsic Safety ★

K6(25) CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E6 and I6) ★

E7 IECEx Flameproof, Dust Ignition-proof ★

I7 IECEx Intrinsic Safety ★

IG(24) IECEx FISCO Intrinsic Safety ★

N7 IECEx Type n ★

K7 IECEx Flameproof, Dust Ignition-proof, Intrinsic Safety, and Type n (combination of E7, I7, and N7) ★

E2 INMETRO Flameproof ★

I2 INMETRO Intrinsic Safety ★

E3 China Flameproof ★

I3 China Intrinsic Safety ★

EM Technical Regulations Customs Union (EAC) Flameproof ★

IM Technical Regulations Customs Union (EAC) Intrinsic Safety ★

KM Technical Regulations Customs Union (EAC) Flameproof, Intrinsic Safety ★

KA(25)(26) ATEX and CSA Explosion-proof, Intrinsically Safe, Division 2 (combination of E1, E6, I1, and I6) ★

KB(25)(26) FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2 (combination of E5, E6, I5, and I6) ★

KC FM and ATEX Explosion-proof, Intrinsically Safe, Division 2 (combination of E5, E1, I5, and I1) ★

KD(25)(26) FM, CSA, and ATEX Explosion-proof, Intrinsically Safe (combination of E5, E6, E1, I5, I6, and I1) ★

KG(24) ATEX, FM, CSA, and IECEx FISCO Intrinsic Safety (combination of IA, IE, IF, and IG) ★

Drinking water approval(27)

DW NSF drinking water certification ★

Shipboard approvals(19)

SBS American Bureau of Shipping ★

SBV Bureau Veritas (BV) Type Approval ★

SDN Det Norske Veritas (DNV) Type Approval ★

SLL Lloyds Register (LR) Type Approvals ★

Alternate materials of construction

L1 Inert sensor fill fluid (differential and gage sensors only) Note: Silicone fill fluid is standard. ★

L2 Graphite-filled PTFE O-ring ★

L4(21) Austenitic 316 SST bolts ★

L5(21) ASTM A193, Grade B7M bolts ★

L6(21) Alloy K-500 bolts ★

L7(21)(28) ASTM A453, Class D, Grade 660 bolts ★

L8(21) ASTM A193, Class 2, Grade B8M bolts ★

69Specifications and Reference Data

Page 76: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

Digital display

M5 PlantWeb LCD display ★

Wireless assembly options(3)

WTA Integral assembly to Smart Wireless THUM™ Adapter (specified separately) ★

Special procedures

P1(29) Hydrostatic testing with certificate ★

P9(30)(31) 4500 psig (310 bar) static pressure limit ★

P0(30)(32) 6092 psig (420 bar) static pressure limit ★

P2(21) Cleaning for special services

P3(21) Cleaning for special services with testing for <1PPM chlorine/fluorine

Special certifications

Q4 Calibration Certificate ★

QP Calibration Certificate and Tamper Evident Seal ★

Q8 Material Traceability Certification per EN 10204 3.1B ★

Q16 Surface Finish Certification for Sanitary Remote Seals ★

QZ Remote seal system performance calculation report ★

Transient protection(33)

T1 Transient terminal block ★

Conduit electrical connector(34)

GE M12, 4-pin, male connector (eurofast®) ★

GM A size mini, 4-pin, male connector (minifast®) ★

NACE certificate(35)

Q15 Certificate of compliance to NACE MR0175/ISO 15156 for wetted materials ★

Q25 Certificate of compliance to NACE MR0103 for wetted materials ★

Cold temperature(19)

BRR -58 °F (-50 °C) cold temperature start-up ★

Typical model number: 3051SMV 3 M 1 2 G 4 R 2 E12 A 1A B4 C2 M5

1. For detailed specifications see “Specifications” on page 55.

2. For Measurement Types 1 and 2, only available with DP range codes 2, 3, and 4, 316L SST and Alloy C-276 isolating diaphragm and silicone fill fluid.For Measurements Types 3 and 4, only available with DP range codes 2 and 3, 316L SST and Alloy C-276 isolating diaphragm and silicone fill fluid.

3. Only available with Transmitter output code A.

4. If ordering measurement type code M, DP Range 4 and 5 are not available.

5. DP Range 0 is only available with Measurement Type 3 or 4 and traditional flange, 316L SST diaphragm material, and Bolting option L4.

6. Required for Measurement Type codes 3 and 4.

7. For Measurement Type codes 1 and 2 with DP range 1, absolute limits are 0.5 to 2000 psi (0,03 to 137,9 bar) and gage limits are -14.2 to 2000 psig (-0,98 to 137,9 bar).

8. Required for Measurement Type codes 2 and 4.

9. Required for Measurement Type codes 1 and 3. RTD Sensor must be ordered separately.

10. Materials of Construction comply with metallurgical requirements highlighted within NACE® MR0175/ISO 15156 for sour oil field production environments Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments. Order with Q15 or Q25 to receive a NACE certificate.

70 Specifications and Reference Data

Page 77: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

11. Tantalum diaphragm material is only available for DP ranges 2-5.

12. “Assemble to” items are specified separately and require a completed model number.

13. Consult an Emerson Process Management representative for performance specifications.

14. Only available with Measurement Type 2 and multivariable type P.

15. Transmitter output code F is not available with Performance Class 1 and 2 and Measurement Type 3 and 4.

16. Only available with output code X.

17. Long-Life Power Module must be shipped separately, order Power Module 701PBKKF.

18. For process connection option code A11, the mounting bracket must be ordered as part of the manifold model number.

19. Not available with transmitter output code F.

20. Not available with transmitter output code X.

21. Not available with process connection option code A11.

22. This assembly is included with certification options EP, KP, E1, N1, K1, ND, E4, E7, N7, K7, E2, E3, KA, KC, KD, EM, KM, IA, IE, IF, IG, KG.

23. Transmitter is shipped with 316 SST conduit plug (uninstalled) in place of standard carbon steel conduit plug.

24. FISCO is only available with transmitter output code F.

25. Not available with M20 or G 1/2 conduit entry size.

26. RTD cable not available with this option.

27. Requires 316L SST diaphragm material, glass-filled PTFE O-ring (standard), and Process Connection code E12 or F12.

28. Bolts are not considered process wetted. In instances where NACE MR0175/ISO 15156 and NACE MR0103 conformance is required for bolting, L7 is the recommended bolting option.

29. Not available with DP range 0.

30. Only available with Measurement Type codes 3 and 4.

31. When assembled to remote diaphragm seal system using B11 or B12 process connections, the maximum working pressure of the system may be limited by the rating of the Rosemount 1199 Seal System selected.

32. Requires 316L SST or Alloy C-276 diaphragm material, assemble to Rosemount 305 Integral Manifold or DIN-compliant traditional flange process connection, andbolting option L8. Limited to differential pressure ranges 2-5.

33. The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification codes IA, IB, IE, IF, IG, and KG.

34. Available with Intrinsically Safe approvals only. For FM Intrinsically Safe; Nonincendive approval (option code I5), install in accordance with Rosemount drawing 03151-1009.

35. NACE compliant wetted materials are identified by Footnote 10.

71Specifications and Reference Data

Page 78: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

A.4 Spare parts list

Feature board and housing assembly Part number

Feature board kit without temperature input, direct process variable output 03151-9020-1000

Feature board kit without temperature input, mass flow output 03151-9020-1001

Feature board kit with temperature input, direct process variable output 03151-9020-1010

Feature board kit with temperature input, mass flow output 03151-9020-1011

LCD display

Aluminum housing

LCD display kit: LCD display assembly, 4-pin interconnection header and aluminum cover assembly 03151-9193-0001

LCD display only: LCD display assembly, 4-pin interconnection header 03151-9193-0002

Cover assembly kit: aluminum cover assembly 03151-9193-0003

SST housing

LCD display kit: LCD display assembly, 4-pin interconnection header, SST cover assembly 03151-9193-0004

LCD display kit: LCD display assembly, 4-pin interconnection header 03151-9193-0002

Cover assembly kit: SST cover assembly 03151-9193-0005

Electrical housing, terminal blocks

Standard terminal block assembly with temperature input 03151-9006-0021

Standard terminal block assembly with temperature input and FISCO/Transient 03151-9006-0023

Covers

Aluminum electronics cover; cover and O-ring 03151-9030-0001

SST electronics cover; cover and O-ring 03151-9030-0002

Housing miscellaneous

External ground screw assembly (Option D4): screw, clamp, washer 03151-9060-0001

Housing V-seal for both PlantWeb™ and junction box housings 03151-9061-0001

PlantWeb housing header cable O-ring (package of 12) 03151-9011-0001

Flanges

Differential coplanar flange

Nickel-plated carbon steel 03151-9200-0025

SST 03151-9200-0022

Cast C-276 03151-9200-0023

Cast alloy 400 03151-9200-0024

Gage/absolute coplanar flange

Nickel-plated carbon steel03151-9200-1025

SST 03151-9200-1022

Cast C-276 03151-9200-1023

Cast alloy 400 03151-9200-1024

Coplanar flange alignment screw (package of 12) 03151-9202-0001

72 Specifications and Reference Data

Page 79: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

Traditional flange

SST 03151-9203-0002

Cast C-276 03151-9203-0003

Cast alloy 400 03151-9203-0004

Flange adapter kits (each kit contains adapters, bolts, and O-ring for one DP transmitter or two GP/AP transmitters)

Part number

CS bolts, glass filled PTFE O-rings

SST adapters 03031-1300-0002

Cast C-276 adapters 03031-1300-0003

Cast alloy 400 adapters 03031-1300-0004

Ni Plated CS adapters 03031-1300-0005

SST bolts, glass filled PTFE O-rings

SST adapters 03031-1300-0012

Cast C-276 adapters 03031-1300-0013

Cast alloy 400 adapters 03031-1300-0014

Ni Plated CS adapters 03031-1300-0015

CS bolts, graphite PTFE O-rings

SST adapters 03031-1300-0102

Cast C-276 adapters 03031-1300-0103

Cast alloy 400 adapters 03031-1300-0104

Ni Plated CS adapters 03031-1300-0105

SST bolts, graphite PTFE O-rings

SST adapters 03031-1300-0112

Cast C-276 adapters 03031-1300-0113

Cast alloy 400 adapters 03031-1300-0114

Ni Plated CS adapters 03031-1300-0115

Flange adapter union

Nickel-plated carbon steel 03151-9259-0005

SST 03151-9259-0002

Cast C-276 03151-9259-0003

Cast alloy 400 03151-9259-0004

Drain/vent kits (each kit contains parts for one transmitter)

Differential drain/vent kits

SST valve stem and seat kit 03151-9268-0022

Alloy C-276 valve stem and seat kit 03151-9268-0023

Alloy C-276 ceramic ball drain/vent kit 03151-9268-0024

SST ceramic ball drain/vent kit 03151-9268-0122

Alloy C-276 ceramic ball drain/vent kit 03151-9268-0123

Alloy 400/K-500 ceramic ball drain/vent kit 03151-9268-0124

73Specifications and Reference Data

Page 80: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

74 Specifications and Reference Data

Gage/absolute drain/vent kits

SST valve stem and seat kit 03151-9268-0012

Alloy C-276 valve stem and seat kit 03151-9268-0013

Alloy C-276 ceramic ball drain/vent kit 03151-9268-0014

SST ceramic ball drain/vent kit 03151-9268-0112

Alloy C-276 ceramic ball drain/vent kit 03151-9268-0113

Alloy 400/K-500 ceramic ball drain/vent kit 03151-9268-0114

O-ring packages (package of 12)

Electronic housing, cover (standard and LCD display) 03151-9040-0001

Electronic housing, module 03151-9041-0001

Process flange, glass-filled PTFE 03151-9042-0001

Process flange, graphite-filled PTFE 03151-9042-0002

Process adapter, glass-filled PTFE 03151-9043-0001

Process adapter, graphite-filled PTFE 03151-9043-0002

Gland and collar kits Part number

Gland and collar kits 03151-9250-0001

Mounting brackets

Coplanar flange bracket kit

B4 Bracket, SST, 2-in. pipe mount, SST bolts 03151-9270-0001

Traditional flange bracket kit

B1 Bracket, 2-in. pipe mount, CS bolts 03151-9272-0001

B2 Bracket, panel mount, CS bolts 03151-9272-0002

B3 Flat Bracket for 2 in. pipe mount, CS bolts 03151-9272-0003

B7 (B1 style bracket with SST bolts) 03151-9272-0007

B8 (B2 style bracket with SST bolts) 03151-9272-0008

B9 (B3 style bracket with SST bolts) 03151-9272-0009

BA (SST B1 bracket with SST bolts) 03151-9272-0011

BC (SST B3 bracket with SST bolts) 03151-9272-0013

Bolt kits

COPLANAR FLANGE

Flange bolt kit (44 mm [1.75 in.])

Carbon steel (set of 4) 03151-9280-0001

316 SST (set of 4) 03151-9280-0002

ANSI/ASTM-A-193-B7M (set of 4) 03151-9280-0003

Alloy K-500 (set of 4) 03151-9280-0004

Flange/adapter bolt kit (73 mm [2.88 in.])

Carbon steel (set of 4) 03151-9281-0001

316 SST (set of 4) 03151-9281-0002

ANSI/ASTM-A-193-B7M (set of 4) 03151-9281-0003

Alloy K-500 (set of 4) 03151-9281-0004

Page 81: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

Manifold/flange kit (57 mm [2.25 in.])

Carbon steel (set of 4) 03151-9282-0001

316 SST (set of 4) 03151-9282-0002

ANSI/ASTM-A-193-B7M (set of 4) 03151-9282-0003

Alloy K-500 (set of 4) 03151-9282-0004

TRADITIONAL FLANGE

Differential flange and adapter bolt kit

Carbon steel (set of 8) 03151-9283-0001

316 SST (set of 8) 03151-9283-0002

ANSI/ASTM-A-193-B7M (set of 8) 03151-9283-0003

Alloy K-500 (set of 8) 03151-9283-0004

Gage/absolute flange and adapter bolt kit

Carbon steel (set of 6) 03151-9283-1001

316 SST (set of 6) 03151-9283-1002

ANSI/ASTM-A-193-B7M (set of 6) 03151-9283-1003

Alloy K-500 (set of 6) 03151-9283-1004

Manifold/traditional flange bolts

Carbon steel Use bolts supplied with manifold316 SST

Temperature cables Part number

AL housing with 1/2-14 NPT conduit- kit includes cable and cable glands

RTD input with 34 in. (86cm) of shielded cable 03151-9064-0002

RTD input with 12 ft (3.66m) of shielded cable 03151-9064-0012

RTD input with 24 ft (7.32m) of shielded cable 03151-9064-0024

RTD input with 75 ft (22.86m) of shielded cable 03151-9064-0075

RTD input with 27 in. (69cm) of armored cable 03151-9065-0002

RTD input with 4 ft (1.22m) of armored cable 03151-9065-0004

RTD input with 12 ft. (3.66m) of armored cable 03151-9065-0012

RTD input with 24 ft. (7.32m) of armored cable 03151-9065-0024

RTD input with 75 ft. (22.86m) of armored cable 03151-9065-0075

RTD input with 25 in. (64 cm) of ATEX/IEXCEx flameproof cable 03151-9066-0002

RTD input with 12 ft. (3.66m) of ATEX/IEXCEx flameproof cable 03151-9066-0012

RTD input with 24 ft. (7.32m) of ATEX/IEXCEx flameproof cable 03151-9066-0024

RTD input with 75 ft. (22.86m) of ATEX/IEXCEx flameproof cable 03151-9066-0075

RTD input with 34 in. (86.36cm) shielded cable for 24 in. (60.96cm) FM approved coupling flex 03151-9067-0024

RTD input with 40 in. (101.60cm) shielded cable for 30 in. (76.20cm) FM approved coupling flex 03151-9067-0030

SST housing with 1/2-14 NPT conduit- kit includes cable and cable glands

RTD input with 12 ft (3.66m) of shielded cable 03151-9064-0012

RTD input with 24 ft (7.32m) of shielded cable 03151-9064-0024

RTD input with 75 ft (22.86m) of shielded cable 03151-9064-0075

75Specifications and Reference Data

Page 82: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

RTD input with 27 in. (69cm) of armored cable 03151-9065-0102

RTD input with 4 ft (1.22m) of armored cable 03151-9065-0104

RTD input with 12 ft. (3.66m) of armored cable 03151-9065-0112

RTD input with 24 ft. (7.32m) of armored cable 03151-9065-0124

RTD input with 75 ft. (22.86m) of armored cable 03151-9065-0175

RTD input with 25 in. (64 cm) of AATEX/IEXCEx flameproof cable 03151-9066-0102

RTD input with 12 ft. (3.66m) of ATEX/IEXCEx flameproof cable 03151-9066-0112

RTD input with 24 ft. (7.32m) of ATEX/IEXCEx flameproof cable 03151-9066-0124

RTD input with 75 ft. (22.86m) of ATEX/IEXCEx flameproof cable 03151-9066-0175

AL housing with M20 x 1.5 conduit- kit includes cable and cable glands

RTD input with 34 in. (86cm) of shielded cable 03151-9064-0002

RTD input with 12 ft (3.66m) of shielded cable 03151-9064-0012

RTD input with 24 ft (7.32m) of shielded cable 03151-9064-0024

RTD input with 75 ft (22.86m) of shielded cable 03151-9064-0075

RTD input with 27 in. (69cm) of armored cable 03151-9065-0202

RTD input with 4 ft (1.22m) of armored cable 03151-9065-0204

RTD input with 12 ft. (3.66m) of armored cable 03151-9065-0212

RTD input with 24 ft. (7.32m) of armored cable 03151-9065-0224

RTD input with 75 ft. (22.86m) of armored cable 03151-9065-0275

RTD input with 25 in. (64 cm) of ATEX/IEXCEx flameproof cable 03151-9066-0202

RTD input with 12 ft. (3.66m) of ATEX/IEXCEx flameproof cable 03151-9066-0212

RTD input with 24 ft. (7.32m) of ATEX/IEXCEx flameproof cable 03151-9066-0224

RTD input with 75 ft. (22.86m) of ATEX/IEXCEx flameproof cable 03151-9066-0275

SST housing with M20 x 1.5 conduit- kit includes cable and cable glands

RTD input with 34 in. (86cm) of shielded cable 03151-9064-0002

RTD input with 12 ft (3.66m) of shielded cable 03151-9064-0012

RTD input with 24 ft (7.32m) of shielded cable 03151-9064-0024

RTD input with 75 ft (22.86m) of shielded cable 03151-9064-0075

RTD input with 27 in. (69cm) of armored cable 03151-9065-0302

RTD input with 4 ft (1.22m) of armored cable 03151-9065-0304

RTD input with 12 ft. (3.66m) of armored cable 03151-9065-0312

RTD input with 24 ft. (7.32m) of armored cable 03151-9065-0324

RTD input with 75 ft. (22.86m) of armored cable 03151-9065-0375

RTD input with 25 in. (64 cm) of ATEX/IEXCEx flameproof cable 03151-9066-0302

RTD input with 12 ft. (3.66m) of ATEX/IEXCEx flameproof cable 03151-9066-0312

RTD input with 24 ft. (7.32m) of ATEX/IEXCEx flameproof cable 03151-9066-0324

RTD input with 75 ft. (22.86m) of ATEX/IEXCEx flameproof cable 03151-9066-0375

AL housing with G1/2 conduit- kit includes cable and cable glands

RTD input with 34 in. (86cm) of shielded cable 03151-9064-0002

RTD input with 12 ft (3.66m) of shielded cable 03151-9064-0012

76 Specifications and Reference Data

Page 83: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual 00809-0100-4853, Rev AA

RTD input with 24 ft (7.32m) of shielded cable 03151-9064-0024

RTD input with 75 ft (22.86m) of shielded cable 03151-9064-0075

RTD input with 27 in. (69cm) of armored cable 03151-9065-0402

RTD input with 4 ft (1.22m) of armored cable 03151-9065-0404

RTD input with 12 ft. (3.66m) of armored cable 03151-9065-0412

RTD input with 24 ft. (7.32m) of armored cable 03151-9065-0424

RTD input with 75 ft. (22.86m) of armored cable 03151-9065-0475

RTD input with 25 in. (64 cm) of ATEX/IEXCEx flameproof cable 03151-9066-0402

RTD input with 12 ft. (3.66m) of ATEX/IEXCEx flameproof cable 03151-9066-0412

RTD input with 24 ft. (7.32m) of ATEX/IEXCEx flameproof cable 03151-9066-0424

RTD input with 75 ft. (22.86m) of ATEX/IEXCEx flameproof cable 03151-9066-0475

SST housing with G1/2 conduit- kit includes cable and cable glands

RTD input with 34 in. (86cm) of shielded cable 03151-9064-0002

RTD input with 12 ft (3.66m) of shielded cable 03151-9064-0012

RTD input with 24 ft (7.32m) of shielded cable 03151-9064-0024

RTD input with 75 ft (22.86m) of shielded cable 03151-9064-0075

RTD input with 27 in. (69cm) of armored cable 03151-9065-0502

RTD input with 4 ft (1.22m) of armored cable 03151-9065-0504

RTD input with 12 ft. (3.66m) of armored cable 03151-9065-0512

RTD input with 24 ft. (7.32m) of armored cable 03151-9065-0524

RTD input with 75 ft. (22.86m) of armored cable 03151-9065-0575

RTD input with 25 in. (64 cm) of ATEX/IEXCEx flameproof cable 03151-9066-0502

RTD input with 12 ft. (3.66m) of ATEX/IEXCEx flameproof cable 03151-9066-0512

RTD input with 24 ft. (7.32m) of ATEX/IEXCEx flameproof cable 03151-9066-0524

RTD input with 75 ft. (22.86m) of ATEX/IEXCEx flameproof cable 03151-9066-0575

77Specifications and Reference Data

Page 84: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Specifications and Reference DataMay 2016

Reference Manual00809-0100-4853, Rev AA

A.5 Function block information and location

The table below lists many of the device parameters and where to find a detailed description of that parameter in this manual. Resource Block Parameters are described in Fieldbus standards FF-890, FF-891, and FF-912.

Block DD name Label Manual section

Mass Flow Transducer Block

LOW_FLOW_CUTOFF Low Flow CutoffConfiguration, Mass flow, Low flow cutoff

PROCESS_TEMPERATURE_MODE Process Temperature ModeConfiguration, Mass flow, Process temperature

Sensor Transducer Block

DIFFERENTIAL_PRESSURE_DAMPING DP Damping Configuration, Differential pressure, Damping

STATIC_PRESSURE_DAMPING SP DampingConfiguration, Static pressure, Damping

ATMOSPHERIC_OFFSETUser Defined Atmospheric Pressure

Configuration, Static pressure, Atmospheric offset

PROCESS_TEMPERATURE_DAMPING PT Damping Configuration, Process temperature, Damping

CALLENDAR_VAN_DUSEN Callendar-Van DusenConfiguration, Process temperature, Callendar-Van Dusen Coefficients

RTD_LIMITSUser Defined Process Temperature Sensor Limits

Configuration, Process temperature, User-defined process temperature sensor limits

PT_ENABLED PT MeasurementConfiguration, Process temperature, Enable/disable process temperature

Analog Input BlockOUT_VALUE Manual Mode

Configuration, Variable simulation, Manual mode

Simulate En/Disable Simulate Configuration, Variable simulation, Simulate

Sensor Transducer Block

CAL_UNIT_DPDifferential Pressure sensor calibration

Operation and Maintenance, Calibration, Differential pressure sensor calibration

CAL_UNIT_SPStatic Pressure sensor calibration

Operation and Maintenance, Calibration, Static pressure sensor calibration

CAL_UNIT_PTProcess temperature sensor calibration

Operation and Maintenance, Calibration, Process temperature sensor calibration

LCD

DISPLAY_PARAM_SEL Display Parameter SelectConfiguration, Device configuration, Display configuration, Display parameter select

BLK_TYPE_[1, 2, 3, or 4] Block Type [1, 2, 3, or 4]Configuration, Device configuration, Display configuration, Block type

BLK_TAG_[1, 2, 3, or 4] Block Tag [1, 2, 3, or 4]Configuration, Device configuration, Display configuration, Block type

PARAM_INDEX_[1, 2, 3, or 4]Parameter Index [1, 2, 3, or 4]

Configuration, Device configuration, Display configuration, Parameter index

CUSTOM_TAG_[1, 2, 3, or 4] Custom Tag [1, 2, 3, or 4]Configuration, Device configuration, Display configuration, Custom tag

UNITS_TYPE_[1, 2, 3, or 4] Units Type [1, 2, 3, or 4]Configuration, Device configuration, Display configuration, Units type

CUSTOM_UNITS_[1, 2, 3, or 4] Custom Units [1, 2, 3, or 4]Configuration, Device configuration, Display configuration, Custom units

Resource Block WRITE_LOCK Write Lock SetupConfiguration, Write lock, Software write lock

78 Specifications and Reference Data

Page 85: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual 00809-0100-4853, Rev AA

Appendix B Product CertificationsRev 1.13

European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 79Ordinary Location Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 79Installing Equipment in North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 79Europe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 80International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 81Brazil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 82China . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 82EAC – Belarus, Kazakhstan, Russia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 84Japan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 84Republic of Korea . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 84Combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 84Additional certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 84Installation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 85

B.1 European Directive Information

A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at EmersonProcess.com/Rosemount.

B.2 Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

B.3 Installing Equipment in North America

The US National Electrical Code (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.

B.4 USAE5 US Explosionproof (XP) and Dust-Ignitionproof (DIP)

Certificate: 3008216

Standards: FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3616 – 2011, FM Class 3810 – 2005, ANSI/NEMA® 250 – 2003

Markings: XP CL I, DIV 1, GP B, C, D; T5; DIP CL II, DIV 1, GP E, F, G; CL III; T5(–50 °C Ta +85 °C); Factory Sealed; Type 4X

I5 US Intrinsically Safe (IS) and Nonincendive (NI)

Certificate: 3031960

Standards: FM Class 3600 –2011, FM Class 3610 – 2007, FM Class 3611 – 2004, FM Class 3616 – 2006, FM Class 3810 – 2005, NEMA 250 – 1991

Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; Class 1, Zone 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4(–50 °C Ta +70 °C); when connected per Rosemount drawing 03151-1206; Type 4X

NoteTransmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See drawing 03151-1206.

79Product Certifications

Page 86: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual00809-0100-4853, Rev AA

IE US FISCO Intrinsically SafeCertificate: 3031960Standards: FM Class 3600 – 2011, FM Class 3610 – 2010,

FM Class 3611 – 2004, FM Class 3616 – 2006, FM Class 3810 – 2005, NEMA 250 – 1991

Markings: IS CL I, DIV 1, GP A, B, C, D; T4(–50 °C Ta +70 °C); when connected per Rosemount drawing 03051SMV-1206; Type 4X

B.5 CanadaE6 Canada Explosionproof, Dust Ignition-proof,

Division 2Certificate: 1143113Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No.

25-1966, CSA Std C22.2 No. 30-M1986, CSA C22.2 No. 94.2-07, CSA Std C22.2 No. 213-M1987, CAN/CSA C22.2 60079-11:14, CAN/CSA-C22.2 No. 61010-1-12, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05 (R2010)

Markings: Explosionproof Class I, Division 1, Groups B, C, D; Dust-Ignitionproof Class II, Division 1, Groups E, F, G; Class III; suitable for Class I, Division 2, Groups A, B, C, D; Type 4X

I6 Canada Intrinsically SafeCertificate: 1143113Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No.

25-1966, CSA Std C22.2 No. 30-M1986, CSA C22.2 No. 94.2-07 , CSA Std C22.2 No. 213-M1987, CAN/CSA C22.2 60079-11:14, CAN/CSA-C22.2 No. 61010-1-12, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05 (R2010)

Markings: Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class 1, Zone 0, IIC, T3C; Ta = 70 °C; when connected per Rosemount drawing 03151-1207; Type 4X

IF Canada FISCO Intrinsically SafeCertificate: 1143113Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No.

25-1966, CSA Std C22.2 No. 30-M1986, CSA C22.2 No. 94.2-07 , CSA Std C22.2 No. 213-M1987, CAN/CSA C22.2 60079-11:14, CAN/CSA-C22.2 No. 61010-1-12, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05 (R2010)

Markings: FISCO Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class I, Zone 0; T3C; Ta = 70 °C; when installed per Rosemount drawing 03151-1207; Type 4X

B.6 EuropeE1 ATEX Flameproof

Certificate: KEMA 00ATEX2143XStandards: EN 60079-0:2012, EN 60079-1: 2007, EN

60079-26:2007 (3051SFx models with RTD are certified to EN 60079-0:2006)

Markings: II 1/2 G Ex d IIC T6…T4 Ga/Gb, T6(–60 °C Ta +70 °C), T5/T4 (–60 °C Ta + 80 °C)

Special Conditions for Safe Use (X):

1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.

2. For information on the dimensions of the flameproof joints the manufacturer shall be contacted.

I1 ATEX Intrinsic SafetyCertificate: Baseefa08ATEX0064XStandards: EN 60079-0: 2012, EN 60079-11: 2012Markings: II 1 G Ex ia IICT4 Ga, T4(–60 °C Ta +70 °C)

Special Conditions for Safe Use (X):

1. If the equipment is fitted with the optional 90 V transient suppressor, it is incapable of withstanding the 500 V isolation from earth test and this must be taken into account during installation.

2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.

IA ATEX FISCOCertificate: Baseefa08ATEX0064XStandards: EN 60079-0: 2012, EN 60079-11: 2012Markings: II 1 G Ex ia IICT4 Ga, T4(–60 °C Ta +70 °C)

Temperature class Process temperature

T6 –60 °C to +70 °C

T5 –60 °C to +80 °C

T4 –60 °C to +120 °C

Parameter HART® FOUNDATION™ Fieldbus

SuperModule™ only

RTD (for 3051SFx)

(HART)

RTD for 3051SFx

(Fieldbus)

Voltage Ui 30 V 30 V 7.14 V 30 V 30 V

Current Ii300 mA 300 mA 300 mA 2.31 mA 18.24 mA

Power Pi 1 W 1.3 W 887 mW 17.32 mW 137 mA

Capacitance Ci 14.8 nF 0 0.11 uF 0 0.8 nF

Inductance Li 0 0 0 0 1.33 mH

80 Product Certifications

Page 87: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual 00809-0100-4853, Rev AA

ND ATEX DustCertificate: BAS01ATEX1374XStandards: EN 60079-0: 2012, EN 60079-31: 2009Markings: II 1 D Ex ta IIIC T105 °C, T500 95 °C Da,

(-20 °C Ta +85 °C), Vmax = 42.4 V

Special Conditions for Safe Use (X):

1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.

2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.

3. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7 J impact test.

4. The SuperModule(s) must be securely screwed in place to maintain the ingress protection of the enclosure(s).

N1 ATEX Type nCertificate: Baseefa08ATEX0065XStandards: EN 60079-0: 2012, EN 60079-15: 2010Markings: II 3 G Ex nA IIC T4 Gc (–40 °C Ta +70 °C),

Vmax = 45 V

Special Condition for Safe Use (X):

1. If fitted with a 90 V transient suppressor, the equipment is not capable of withstanding the 500 V electrical strength test as defined in Clause 6.5.1 of EN 60079-15:2010. This must be taken into account during installation.

B.7 InternationalE7 IECEx Flameproof and Dust

Certificate: IECEx KEM 08.0010X (Flameproof)Standards: IEC 60079-0:2011, IEC 60079-1: 2007, IEC

60079-26:2006 (3051SFx models with RTD are certified to IEC 60079-0:2004)

Markings: Ex d IIC T6…T4 Ga/Gb, T6(–60 °C Ta +70 °C), T5/T4(–60 °C Ta +80 °C)

Special Conditions for Safe Use (X):

1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.

2. For information on the dimensions of the flameproof joints the manufacturer shall be contacted.

Certificate: IECEx BAS 09.0014X (Dust)Standards: IEC 60079-0:2011, IEC 60079-31:2008Markings: Ex ta IIIC T105 °C T500 95 °C Da,

(-20 °C Ta +85 °C), Vmax = 42.4 V

Special Conditions for Safe Use (X):

1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.

2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.

3. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7J impact test.

4. The 3051S- SuperModule must be securely screwed in place to maintain the ingress protection of the enclosure.

I7 IECEx Intrinsic SafetyCertificate: IECEx BAS 08.0025XStandards: IEC 60079-0: 2011, IEC 60079-11: 2011Markings: Ex ia IIC T4 Ga, T4(–60 °C Ta +70 °C)

Special Conditions for Safe Use (X):

1. If the equipment is fitted with the optional 90 V transient suppressor, it is incapable of withstanding the 500 V isolation from earth test and this must be taken into account during installation.

2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.

IG IECEx FISCOCertificate: IECEx BAS 08.0025XStandards: IEC 60079-0: 2011, IEC 60079-11: 2011Markings: Ex ia IIC T4 (–60 °C Ta +70 °C)

Parameter FISCO

Voltage Ui 17.5 V

Current Ii 380 mA

Power Pi 5.32 W

Capacitance Ci 0

Inductance Li 0

Temperature class Process temperature

T6 –60 °C to +70 °C

T5 –60 °C to +80 °C

T4 –60 °C to +120 °C

Parameter HARTFOUNDATION

FieldbusSuperModule

only

RTD (for 3051SFx)

(HART)

RTD for 3051SFx

(Fieldbus)

Voltage Ui 30 V 30 V 7.14 V 30 V 30 V

Current Ii 300 mA 300 mA 300 mA 2.31 mA 18.24 mA

Power Pi 1 W 1.3 W 887 mW 17.32 mW 137 mA

Capacitance Ci 14.8 nF 0 0.11 uF 0 0.8 nF

Inductance Li 0 0 0 0 1.33 mH

81Product Certifications

Page 88: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual00809-0100-4853, Rev AA

N7 IECEx Type nCertificate: IECEx BAS 08.0026XStandards: IEC 60079-0: 2011, IEC 60079-15: 2010Markings: Ex nA IIC T5 Gc (–40 °C Ta +70 °C)

Special Condition for Safe Use (X):

1. If fitted with a 90 V transient suppressor, the equipment is not capable of withstanding the 500 V electrical strength test as defined in Clause 6.5.1 of IEC 60079-15:2010. This must be taken into account during installation.

B.8 BrazilE2 INMETRO Flameproof

Certificate: UL-BR 15.0393XStandards: ABNT NBR IEC 60079-0:2008 + Corrigendum

1:2011, ABNT NBR IEC 60079-1:2009 + Corrigendum 1:2011, ABNT NBR IEC 60079-26:2008 + Corrigendum 1: 2008

Markings: Ex d IICT* Ga/Gb, T6(–60 °C Ta +70 °C), T5/T4(–60 °C Ta +80 °C), IP66

Special Conditions for Safe Use (X):

1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.

2. For information on the dimensions of the flameproof joints, the manufacturer shall be contacted.

I2 INMETRO Intrinsic SafetyCertificate: UL-BR 15.0357XStandards: ABNT NBR IEC 60079-0:2008 + Addendum

1:2011, ABNT NBR IEC 60079-11:2009Markings: Ex ia IICT4 Ga, T4(–60 °C Ta +70 °C)

Special Conditions for Safe Use (X):

1. If the equipment is fitted with the optional 90 V transient suppressor, it is incapable of withstanding the 500 V isolation from earth test and this must be taken into account during installation.

2. For processes with temperatures above 135 °C, the user must assess whether the SuperModule temperature class is suitable for such applications, because in this situation there is a risk of the SuperModule temperature being above T4.

B.9 ChinaE3 China Flameproof and Dust Ignition-proof

Certificate: 3051SMV: GYJ14.1039X [Mfg USA, China, Singapore]3051SFx: GYJ11.1711X [Mfg USA, China, Singapore]

Standards: 3051SMV: GB3836.1-2010, GB3836.2-2010, GB3836.20-20103051SFx: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010, GB12476.1-2000

Markings: 3051SMV: Ex d IIC T6/T5 Ga/Gb 3051SFx: Ex d IIC T6/T5 Ga/Gb; DIP A20 TA105 °C; IP66

Special Conditions for Safe Use (X):

1. Symbol “X” is used to denote specific conditions of use: For information on the dimensions of the flameproof joints the manufacturer shall be contacted.

2. The relationship between T code and ambient temperature range are as follows:

3. The earth connection facility in the enclosure should be connected reliably.

4. During installation, use and maintenance of the product in explosive atmosphere, observe the warning “Do not open cover when circuit is alive”. During installation, use, and maintenance in explosive dust atmosphere, observe the warning “Do not open when an explosive dust atmosphere is present”.

5. During installation there should be no mixture harmful to the housing.

6. During installation, use and maintenance in explosive dust atmosphere, product enclosure should be cleaned to avoid dust accumulation, but compressed air should not be used.

7. During installation in a hazardous location, cable glands and blanking plugs certified by state appointed inspection bodies with Ex d IIC Gb or Ex d IIC Gb DIP A20 [Flowmeters] IP66 type of protection should be used. Redundant cable entries should be blocked with blanking plugs.

Parameter FISCO

Voltage Ui 17.5 V

Current Ii 380 mA

Power Pi 5.32 W

Capacitance Ci 0

Inductance Li 0

ParameterHART Fieldbus

Input RTD Input RTD

Voltage Ui 30 V 30 V 30 V 30 V

Current Ii 300 mA 2.31 mA 300 mA 18.24 mA

Power Pi 1 W 17.32 mW 1.3 W 137 mW

Capacitance Ci 14.8 nF 0 0 0.8 nF

Inductance Li 0 0 0 1.33 mH

T code Process temperature

T6 –50 °C ~+ 65 °C

T5 –50 °C ~+ 80 °C

82 Product Certifications

Page 89: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual 00809-0100-4853, Rev AA

8. End users are not permitted to change any components, but to contact the manufacturer to avoid damage to the product.

9. Maintenance should be done when no explosive gas and dust atmosphere is present.

10. During installation, use and maintenance of this product, observe following standards:GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres” GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)”GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”

I3 China Intrinsic SafetyCertificate: 3051SMV: GYJ14.1040X [Mfg USA, China,

Singapore]3051SFx: GYJ11.1707X [Mfg USA, China, Singapore]

Standards: 3051SMV: GB3836.1-2010, GB3836.4-2010, GB3836.20-20103051SFx: GB3836.1/4-2010, GB3836.20-2010, GB12476.1-2000

Markings: 3051SMV: Ex ia IIC T4 Ga 3051SFx: Ex ia IIC T4 Ga, DIP A20 TA105 °C; IP66

Special Conditions for Safe Use (X):

1. The enclosure may contain light metal, attention should be taken to avoid ignition hazard due to impact or friction.

2. The apparatus is not capable of withstanding the 500 V electrical strength test defined in Clause 6.3.12 of GB3836.4-2010.

3. Ambient temperature range: –60 °C ~+70 °C

4. Intrinsically safe electric parameters:

5. The cables between this product and associated apparatus should be shielded cables. The shield should be grounded reliably in non-hazardous area.

6. The product should be used with Ex certified associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of the product and associated apparatus.

7. End users are not permitted to change any components, contact the manufacturer to avoid damage to the product.

8. During installation in hazardous location, cable glands, conduit, and blanking plugs certified by state-appointed inspection bodies with DIP A20 IP66 type of protection should be used. Redundant cable entries should be blocked with blanking plugs.

9. During installation, use, and maintenance in explosive dust atmosphere, observe the warning “Do not open when an explosive dust atmosphere is present”.

10. Maintenance should be done when no explosive dust atmosphere is present.

11. During installation, use and maintenance of this product, observe following standards:GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres” GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)”GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”.

Maximum input

voltage: Ui (V)

Maximum input

current: Ii (mA)

Maximum input power:

Pi (W)

Maximum internal parameters

Ci(nF) Li( H)

30 300 1.0 14.8 0

Max output

voltage: Ui (V)

Max output

current: Ii (mA)

Max output

power: Pi (W)

Maximum external parameters

Ci(nF) Li( H)

RTD 30 2.31 17.32 0 0

SuperModule 7.14 300 887 110 0

83Product Certifications

Page 90: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual00809-0100-4853, Rev AA

B.10 EAC – Belarus, Kazakhstan, RussiaEM Technical Regulation Customs Union (EAC) Flameproof

Certificate: RU C-US.AA87.B.00094Markings: Ga/Gb Ex d IIC T6…T4 X

IM Technical Regulation Customs Union (EAC) Intrinsic SafetyCertificate: RU C-US.AA87.B.00094Markings: 0Ex ia IIC T4 Ga X

B.11 JapanE4 Japan Flameproof

Certificate: TC19070, TC19071, TC19072, TC19073Markings: Ex d IIC T6

B.12 Republic of Korea EP Republic of Korea Flameproof [HART only]

Certificate: 12-KB4BO-0180X [Mfg USA], 11-KB4BO-0068X [Mfg Singapore]

Markings: Ex d IIC T5 or T6

IP Republic of Korea Intrinsic Safety [HART only]Certificate: 10-KB4BO-0021X [Mfg USA, SMMC] Markings: Ex ia IIC T4

B.13 CombinationsK1 Combination of E1, I1, N1, and ND

K2 Combination of E2 and I2

K5 Combination of E5 and I5

K6 Combination of E6 and I6

K7 Combination of E7, I7, and N7

KA Combination of E1, I1, E6, and I6

KB Combination of E5, I5, E6, and I6

KC Combination of E1, I1, E5, and I5

KD Combination of E1, I1, E5, I5, E6, and I6

KM Combination of EM and IM

KP Combination of EP and IP

B.14 Additional certificationsSBS American Bureau of Shipping (ABS) Type Approval [HART

only]Certificate: 00-HS145383Intended Use: Measure gauge or absolute pressure of liquid,

gas or vapor applications on ABS classed vessels, marine, and offshore installations. [HART only]

SBV Bureau Veritas (BV) Type ApprovalCertificate: 31910 BVRequirements: Bureau Veritas Rules for the Classification of

Steel ShipsApplication: Class Notations: AUT-UMS, AUT-CCS, AUT-PORT

and AUT-IMS. [HART only]

SDN Det Norske Veritas (DNV) Type ApprovalCertificate: A-14186Intended Use: Det Norske Veritas' Rules for Classification of

Ships, High Speed & Light Craft, and Det Norske Veritas' Offshore Standards. [HART only]

Application:

SLL Lloyds Register (LR) Type ApprovalCertificate: 11/60002Application: Environmental categories ENV1, ENV2, ENV3,

and ENV5. [HART only]

Location classes

Type 3051S

Temperature D

Humidity B

Vibration A

EMC A

Enclosure D/IP66/IP68

84 Product Certifications

Page 91: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual 00809-0100-4853, Rev AA

B.15 Installation drawings

Figure B-1. Factory Mutual (FM)

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

85Product Certifications

Page 92: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

86 Product Certifications

Page 93: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual 00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

87Product Certifications

Page 94: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

88 Product Certifications

Page 95: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual 00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

89Product Certifications

Page 96: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

90 Product Certifications

Page 97: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual 00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

91Product Certifications

Page 98: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual00809-0100-4853, Rev AA

92 Product Certifications

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

Page 99: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual 00809-0100-4853, Rev AA

Figure B-2. Canadian Standards Association (CSA)

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

93Product Certifications

Page 100: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

94 Product Certifications

Page 101: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual 00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

95Product Certifications

Page 102: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

96 Product Certifications

Page 103: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual 00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

97Product Certifications

Page 104: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

98 Product Certifications

Page 105: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual 00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

99Product Certifications

Page 106: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Product CertificationsMay 2016

Reference Manual00809-0100-4853, Rev AA

Electronic Master – PRINTED COPIES ARE UNCONTROLLED – Rosemount Proprietary

100 Product Certifications

Page 107: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with
Page 108: Rosemount 3051SMV MultiVariable Transmitter. Pressure... · 2019-05-17 · Reference Manual 00809-0100-4853, Rev AA May 2016 Rosemount ™ 3051SMV MultiVariable™ Transmitter with

Reference Manual00809-0100-4853, Rev AA

May 2016

Global Headquarters

Emerson Process Management 6021 Innovation Blvd.Shakopee, MN 55379, USA

+1 800 999 9307 or +1 952 906 8888+1 952 949 7001 [email protected]

North America Regional OfficeEmerson Process Management 8200 Market Blvd.Chanhassen, MN 55317, USA

+1 800 999 9307 or +1 952 906 8888+1 952 949 7001 [email protected]

Latin America Regional OfficeEmerson Process Management 1300 Concord Terrace, Suite 400Sunrise, FL 33323, USA

+1 954 846 5030+1 954 846 [email protected]

Europe Regional OfficeEmerson Process Management Europe GmbHNeuhofstrasse 19a P.O. Box 1046CH 6340 BaarSwitzerland

+41 (0) 41 768 6111+41 (0) 41 768 6300 [email protected]

Asia Pacific Regional OfficeEmerson Process Management Asia Pacific Pte Ltd

Linkedin.com/company/Emerson-Process-Management

Twitter.com/Rosemount_News

Facebook.com/Rosemount

Youtube.com/user/RosemountMeasurement

Google.com/+RosemountMeasurement

1 Pandan CrescentSingapore 128461

+65 6777 8211+65 6777 0947 [email protected]

Middle East and Africa Regional OfficeEmerson Process Management Emerson FZE P.O. Box 17033Jebel Ali Free Zone - South 2Dubai, United Arab Emirates

+971 4 8118100+971 4 8865465 [email protected]

Standard Terms and Conditions of Sale can be found at: www.Emerson.com/en-us/pages/Terms-of-Use.aspxThe Emerson logo is a trademark and service mark of Emerson Electric Co.MultiVariable, THUM Adapter, AMS, SNAP-ON, SuperModule, PlantWeb, Rosemount, and Rosemount logotype are trademarks of Emerson Process Management.eurofast and minifast are registered trademarks of TURCK.Fluorinert is a trademark of 3M.FOUNDATION Fieldbus is a trademark of the FieldComm Group.HART and WirelessHART are registered trademarks of the FieldComm Group.Intel is a registered trademark of Intel Corporation in the U.S. and/or other countries. Microsoft is a registered trademark of Microsoft Corporation in the United States and other countries.Modbus is a registered trademark of Gould Inc.NACE is a registered trademark of NACE International.NEMA is a registered trademark and service mark of the National Electrical Manufacturers Association.Windows is a trademark of Microsoft Corporation in the United States and other countries.All other marks are the property of their respective owners.© 2016 Emerson Process Management. All rights reserved.