ROOFTOP AIR CONDITIONER
İmbat roo�ops participates in the Eurovent certification programme. The models are listed in theEurovent directory, please check website:www.eurovent-certification.com
1
MAIN SPECIFICATIONS
The external coils are made of aluminium fin with are
hydromechanically overlayed on the copper tube. The external coil is tested
against leakage under 150 Psig and against pressure under 450 Psig.
According to the unit size, the base is at 10-20 cm height, made of electrostatic painted galvanized steel.
R-410a environment friendly refrigerant is used.
Axial type, silent and high e�iciency fans are used as standard, while EC type fans and fans with speed control are applied on demand.
Silent and high e�icient scroll type compressors are used. On models with multiple compressors, asymmetric compressor application is available. In asymmetric compressor application, multiple compressors at di�erent capacities are connected as tandem type which results in e�iciency increase under partial loads and obtains stepped capacity control.
Rem
ote
cont
rol a
nd co
ntro
l pan
el
Exte
rnal
coil
(con
dens
er)
Base
R-41
0a
Scro
ll ty
pe co
mpr
esso
rs
Condenser fan
The unit is controlled by an advanced microprocessor that provides full automatic operation and daily or weekly programmability. With remote control and controller, the unit can be connected to a building automation system. All the connection cables are
colored, cable inputs and outpouts are IP65 standard plastic and leakproof. There is an on/o� swith on both
the remote controller and the control panel. The set parameters can be observed and adjusted with the
wired remote controller panel.
ISO-14 000 ISO-9001
2
The internal coils are made of aluminium fin with are
hydromechanically overlayed on copper tube. The internal coil is
tested against leakage under 150 Psig and against pressure under 450 Psig. It is tested against leakage under 150 Psig and against pressure under 450
Psig. There is also a condenser pan made of stainless steel that has an
inclined drainage outlet.
Operating integrated with the economizer, the CO2 sensor keeps the
indoor air quality at maximum.
Radial type, statically and dynamically balanced, silent and high e�icient fans are used standard, while variable speed
plug, AC or EC type fans are applied on demand.
Radial type, static and dynamically balanced, silent and high e�icient fans are used as standard, while
variable speed plug, AC or EC type fans are applied on demand.
High e�icient G4 filter and dirty filter alarm is standard, while three step
filtration can be applied on demand by adding F7 and F9 filters.
Made of aluminium and has an appropriate profile for 100% outdoor air, the fresh air, mixture and
exhaust dampers are leakproof. Dampers are working full automatic with servo motors and
microprocessor controls and automatically adjust the amount of outdoor air by making free cooling
according to outside temperature. The dampers are turned o� with spring return at electric cuts and at
the turned o� position.
The body of İmbat’s units are insulated with a dual skin panel of 70kg/m3 density stonewool between two galvanized electrostatically painted plate sheets. Easy opening service and maintenance doors as well as handling holes for easy li�ing is already on. Unit joints are assembled together with stainless steel rivet with fittings durable against corrosion and outdoor conditions within a leakproof structure.
Unit body
CO2 indoor air quality sensor
Inte
rnal
coil
(eva
pora
tor)
Filte
rMixing air box
Supply fan (vantilator)
Return fan (aspirator)
İmbat roo�ops participates in theEurovent certification programme.The models are listed in theEurovent directory, please check website:www.eurovent-certification.com
STANDARD
Kw CapacityRange
7-350
R-410 A
RefrigerantFluid
ScrollCompressor
Heating Cooling WiredRemote
Controller
AsymmetricCooling
Dual SkinPanel Body
Cooling+Heatpump
Cooling+Heatpump+Gas Burner
ThermodynamicHeat
Recovery
RadialFan
Plug&Operate
FullAutomatic
full automatic
LCDDisplay
DISPLAY
AutomaticDefrost
IntelligentDefrostSystem
eevElectronicExpansion
Valve
EasyService&
Maintenance
FreeCooling
InsideAir
Quality
3
Thermal or Enthalpic Free Cooling (Economizer)
It is standard in all models with a dual (supply and return fans) fan. On the condition that the outside temperature and the relative humidity rate is suitable, the unit creates climatization by using 100% fresh air without using cooling circuit, therefore saving energy.
Indoor Air Quality
Indoor air quality is preserved by high e�iciency filters, filter alarm and CO2 indoor air quality sensor. Controlling the pollution rate of the return air, the CO2 indoor air quality sensor works integrated with the economizer and saves energy by aspirating fresh air at deficient amount. With the automated, full automatic return, fresh air and exhaust dampers, the return air is mixed with fresh air and a quality air mixture is obtained. While some amount of the air to be refreshed is used in mixture, some amount of return air is exhausted out by the exhaust damper.
Gas Fired Heating
With the roo�op air conditioners with gas burner, independent heating is possible without the necessity of any connection to a central system, even in the coolest climates. Maximum e�iciency is obtained with the burner capable of working 17-55 mbar range and aluminated steel pipe heat exchanger.
4
WHAT MAKES İMBAT DIFFERENT
On our units with mixed air, heat recovery is provided by transmitting all the exhaust air over the condenser. Since there is a lower temperature air flow then the actual air temperature passed through the condenser, the condensation occurs at lower temperatures, the e�iciency of compressors increase and up to %30 energy is saved.
THERMODYNAMIC HEAT RECOVERY
The body of our units is insulated with a dual skin panel of 70kg/m3 density stonewool between two galvanized and electrostatically painted plate sheets. This type of body structure o�ers better insulation and fire resistance.
DUAL SKIN INSULATED PANEL BODY
It is the technology of using multiple compressors at di�erent capacities in a single cooling circuit. In cooling systems, the condensation temperature rate of refrigerant which alters according to the outside air temperature e�ects the e�iciency of the system. Likewise, the increase on the evaporation temperature increases the e�iciency of compressor.
Since multiple compressors at di�erent capacities are conntected to a single evapo-rator and condenser circuit, under partial load, condensation temperature is perfor-med at low temperatures and evaporation is performed at high temperatures. In this system, three steps capacity control and up to 35% e�iciency increase under partial load is obtained. Multiple compressor systems tend to have a longer life span and energy saving features due to it’s steps capacity control abilities.
In only a very small amount of time the units operate at maximum capacity. Thus, asymmetric cooling application is vital for energy e�iciency.
ASYMMETRIC COOLING
İmbat roo�ops participates in theEurovent certification programme.The models are listed in theEurovent directory, please check website:www.eurovent-certification.com
5
Ability to work with %100 fresh airRotary and plate heat recoveryVariable air flow with AC plug or EC fan modelsElectronic expansion valveSmoke detectorFilter alarmHot water, steam and electric heatingGas fired heaterAutomatic adjustment of fresh air ratio between %0-100Thermal and enthalpic free cooling (economizer)CO2 indoor air controlCondenser fan speed controlAbility to connect to building automation systemThree steps filtration (G4+F7+F9)Digital and inverter scroll compressorsHydrophilic/epoxy coating on evaporator and condenser surfaceProtection mesh for condenser surfaceWater-cooled modelsAbility to operate at high ambient temperaturesLow sound levelsCustom designs for special projects and flexible production
OPTIONAL
İmbat reserves the right to make modifications on models, capacities, dimensions and specifications without prior notice.
In single fan roo�op air conditioners, the return air or fresh air is at first filtered to eliminate dust and particules. Then this
air is passed through the cooler/heater direct expansion exchanger and supply inside the area by high e�icient fans already conditioned according to the desgin parameters .
Enthalpic or thermal free cooling (termal or enthalpy economizer) is standard in all our dual (return and supply fans) fan models. On condition that the outside temperature and relative humidity are
suitable, our units make climitisation by using 100% fresh air without making cooling, thus saving energy.
Dual fan/Free coolingSingle fan
Thermodynamic heat recovery
With the roo�op air conditioners with gas burner, independ-ent heating is possible without the necessity of any
connection to a central system, even in the coolest climates. Maximum e�iciency is obtained with the burner capable of working 17-55 mbar range with aluminated steel pipe heat
exchanger.
On air cooled units with mixed air, heat recovery is provided by transmitting all the exhaust air over the condenser. Since there is a lower temperature air flow then the actual air temperature passed
through the condenser, the condensation occurs at lower temperatures, which leads to e�iciency on compressors and energy
saving up to %30 .
Gas fired heating-
6İmbat roo�ops participates in theEurovent certification programme.The models are listed in theEurovent directory, please check website:www.eurovent-certification.com
MAIN SPECIFICATIONS
Cooling Conditions Rated at Indoor Temperature: 27°C DB - Indoor RH: %50, Outside Temperature: 35°C DB - Heat Pump Heating Conditions Rated at Indoor Temperature: 20°C DB, Outside Temperature: +7°C DBFor units at di�erent capacities, on di�erent operation conditions and for more information, please apply to İmbat.
İmbat roo�ops participates in theEurovent certification programme.The models are listed in theEurovent directory, please check website:www.eurovent-certification.com
MODEL HSE... 21 31 41 51 61 71 81 91 101 121CoolingCooling capacity Kw 7,26 10,9 13,65 15,35 19,15 21,7 23,4 26,5 31,5 35,1Power input Kw 2,4 3,68 4,58 5,22 6,43 7,26 7,93 8,95 10,64 11,9EER (EN 14511) 3,03 2,96 2,98 2,94 2,98 2,99 2,95 2,96 2,96 2,95Eurovent energy class A B B B B B B B B BHeating-Heat PumpHeating capacity Kw 7,74 11,2 14,55 16,45 19,85 22,7 24,6 27,8 32,9 37,1Power input Kw 2,26 3,46 4,19 4,71 6,15 6,84 7,39 8,1 9,4 10,51COP (EN 14511) 3,42 3,24 3,47 3,49 3,23 3,32 3,33 3,43 3,5 3,53Eurovent energy class A B A A B B B A A ACompressorRefrigantNumber of compressor pcs 1 1 1 1 1 1 1 1 1 1Compressor typeCompressor connection typeCooling circuit pcs 1 1 1 1 1 1 1 1 1 1Capacity control step 1 1 1 1 1 1 1 1 1 1Vantilator
Fan type RadialAir flow rate m3 / h 1100 1600 2050 2300 2660 3100 3400 3900 4650 5250Static pressure Pa 150 150 200 200 250 250 250 250 250 300Number of fan pcs 1 1 1 1 1 1 1 1 1 1
Fan typeAir flow rateStatic pressureNumber of fanAir flow rateStatic pressureNumber of fanAir flow rateStatic pressureNumber of fan
Air flow rate m3 / h 1400 2000 2550 2900 3350 3900 4300 4900 5850 6600Static pressure Pa 150 150 200 200 250 250 250 250 250 300Number of fan pcs 1 1 1 1 1 1 1 1 1 1Air flow rateStatic pressureNumber of fan
m3 / h 1550 2300 2900 3350 3800 4400 4800 5500 6600 7400Pa 150 150 200 200 250 250 250 250 250 300pcs 1 1 1 1 1 1 1 1 1 1 3/4
Radialm3 / h 1100 1600 2050 2300 2660 3100 3400 3900 4650 5250
Pa 100 100 150 150 200 200 200 200 200 250pcs 1 1 1 1 1 1 1 1 1 1
m3 / h 1400 2000 2550 2900 3350 3900 4300 4900 5850 6600Pa 100 100 150 150 200 200 200 200 200 250pcs 1 1 1 1 1 1 1 1 1 1
m3 / h 1550 2300 2900 3300 3800 4400 4800 5500 6600 7400Pa 100 100 150 150 200 200 200 200 200 250pcs 1 1 1 1 1 1 1 1 1 1
Heating-Gas Burner
Aspirator
Capacity Kw 25 25 25 25 25 25 25 25 30 43Gas flow rate Nm3 / h 2,61 2,61 2,61 2,61 2,61 2,61 2,61 2,61 3,13 4,48Burner pressure (Min/Max) m/barPower input w 550 550 550 550 550 550 550 550 550 550Heating- Electric ResistanceCapacity (ΔT=15 C) Kw 8 11 13 15 18 20 22 25 30 34Capacity (ΔT=30 C) Kw 15 22 27 31 36 42 46 52 62 70Heating- Hot WaterCapacity Kw 21,7 27,6 37,6 41 47,7 52,7 56,2 61,1 80,8 87,4Hot water fluctuation °CHeating-SteamCapacity Kw 25,6 31,6 43,4 46,8 56,3 61,4 64,9 69,8 95,5 102,3Steam pressure barCondenserFan typeNumber of fan pcs 1 1 1 1 2 2 2 2 2 2Air flow rate (Cooling) m3 / h 8150 7890 8210 8120 14620 14300 13700 13200 15500 15200
17/55
80/60
3
Axial
R-410a
ScrollStandard
MIN
.ST
ND.
MAX
.M
IN.
STN
D.M
AX
WidthLengthHeight
Sound Pressure Level
Dimensions
Sound Pressure Level / 1mt distanceSound Pressure Level / 10mt distance
mm 1800 1800 1800 1800 2100 2100 2100 2100 2150 2150mm 1400 1400 1500 1500 1750 1750 1750 1750 1800 1800mm 1600 1600 1700 1700 1900 1900 1900 1900 2054 2054
dB(A) 74,0 80,0 80,0 81,0 83,0 83,0 83,0 83,0 90,0 90,0dB(A) 56,0 61,0 61,0 63,0 65,0 65,0 65,0 65,0 72,0 72,0
80/60
8
MAIN SPECIFICATIONS
Cooling ConditionsIndoor Temperature: 27°C DBIndoor RH: %50Outside Temperature: 35°C DBHeat Pump Heating ConditionsIndoor Temperature: 20°C DBOutside Temperature: +7°C DBFor units at di�erent capacities, on di�erent operation conditions and for more information, please contact to İmbat.
MIN
.ST
ND.
MAX
.M
IN.
STN
D.M
AX.
MODEL HSE... 131 151 162 182 222 252 272 302
Kw 38,8 45,6 48,45 57 67 78,7 82,3 90,9Kw 13,43 15,94 16,76 19,59 23,18 26,68 28,48 31,67
2,89 2,86 2,89 2,91 2,89 2,95 2,89 2,87
Kw 41 47,8 51 56,4 69,2 81,6 85,7 94,4Kw 11,42 13,28 14,21 16,59 19,55 22,3 23,22 25,58
3,59 3,6 3,59 3,4 3,54 3,66 3,69 3,69A A A B A A A A
B B B B B B B B
pcs 1 1 2 2 2 2 2 2
STND STND STND ASYM ASYM ASYM ASYM STNDpcs 1 1 1 1 1 1 1 1step 1 1 2 3 3 3 3 2
Radial
m3 / h 5850 6900 7300 8000 9900 11550 12100 13500Pa 300 300 300 300 300 300 300 350pcs 1 1 1 1 1 1 1 1
m3 / h 7400 8650 9200 10000 12400 14500 15200 17000Pa 300 300 300 300 300 300 300 350pcs 1 1 1 1 1 1 1 1
m3 / h 8300 9750 10300 11400 14000 16300 17100 19100Pa 300 300 300 300 300 300 300 350pcs 1 1 1 1 1 1 1 1
Radialm3 / h 5850 6900 7300 8000 9900 11550 12100 13500
Pa 150 150 200 200 250 250 250 250
pcs 1 1 1 1 1 1 1 1m3 / h 7400 8650 9200 10000 12400 14500 15200 17000
Pa 150 150 200 200 250 250 250 250pcs 1 1 1 1 1 1 1 1
m3 / h 8300 9750 10300 11400 14000 16300 17100 19100Pa 150 150 200 200 250 250 250 250pcs 1 1 1 1 1 1 1 1
Kw 55 55 55 63 63 86 86 100Nm3 / h 5,73 5,73 5,73 6,57 6,57 8,96 8,96 10,42m/bar
w 1100 1100 1100 1100 1100 1100 1100 1100
Kw 38 45 47 51 64 74 78 87Kw 78 91 97 106 131 153 160 179
Kw 94,1 103,8 118,9 125,4 143,5 207 213,2 228,6° C
Kw 109,13 118,92 142,36 149,25 167,98 241,47 247,76 263,05bar
Axialpcs 2 2 2 2 2 2 2 2
m3 / h 14800 14400 34200 34000 32800 33000 35800 34600
dB(A) 90,0 86,0 86,0 95,0 95,0 92,0 92,0 92,0dB(A) 72,0 68,0 68,0 76,0 76,0 74,0 74,0 74,0
mm 2150 2150 2360 2360 2360 2104 2104 2104mm 1800 1800 2176 2176 2176 3543 3543 3543mm 2054 2054 2346 2346 2346 2487 2487 2487
17/55
80/60
3
R-410a
Scroll
CoolingCooling capacityCompressor powerEER (EN 14511)Eurovent energy classHeating-Heat PumpHeating capacityCompressor powerCOP (EN 14511)Eurovent energy classCompressorRefrigantNumber of compressorCompressor typeCompressor connection typeCooling circuitCapacity controlVantilator
Fan typeAir flow rateStatic pressureNumber of fan
Fan typeAir flow rateStatic pressureNumber of fanAir flow rateStatic pressureNumber of fanAir flow rateStatic pressureNumber of fan
Air flow rateStatic pressureNumber of fan
Air flow rateStatic pressureNumber of fan
Heating-Gas Burner
Aspirator
CapacityGas flow rateBurner pressure (Min/Max)Power inputHeating- Electric ResistanceCapacity (ΔT=15 C)Capacity (ΔT=30 C)Heating- Hot WaterCapacityHot water fluctuation
CapacitySteam pressureCondenserFan typeNumber of fanAir flow rate (Cooling)
WidthLengthHeight
Sound Pressure Level
Dimensions
Sound Pressure Level / 1mt distanceSound Pressure Level / 10mt distance
Heating-Steam
DIMENSIONS (mm)
9İmbat reserves the right to make modifications on models, capacities, dimensions and specifications without prior notice.
İmbat roo�ops participates in theEurovent certification programme.The models are listed in theEurovent directory, please check website:www.eurovent-certification.com
21 1690 1400 1600 1800 1310 1373 B+1250 B+1100 B+700
31 1690 1400 1600 1800 1310 1373 B+1250 B+1100 B+700
41 1690 1500 1700 1800 1410 1473 B+1250 B+1100 B+700
51 1690 1500 1700 1800 1410 1473 B+1250 B+1100 B+700
61 1990 1750 1900 2100 1660 1673 B+1250 B+1100 B+700
71 1990 1750 1900 2100 1660 1673 B+1250 B+1100 B+700
81 1990 1750 1900 2100 1660 1673 B+1250 B+1100 B+700
91 1990 1750 1900 2100 1660 1673 B+1250 B+1100 B+700
101 2040 1800 2054 2150 1710 1827 B+1250 B+2500 B+1100 B+1100
121 2040 1800 2054 2150 1710 1827 B+1250 B+2500 B+1100 B+1100
131 2040 1800 2054 2150 1710 1827 B+1250 B+2500 B+1100 B+1100
151 2040 1800 2054 2150 1710 1827 B+1250 B+2500 B+1100 B+1100
GASBURNER
2 GASBURNER
F7FILTER
F9FILTERMODEL
HSE...A B C D E F
10
DIMENSIONS (mm)
MODELHSE...
A B C D E F
252 1994 3543 2487 2104 3453 1767
1767
1767
B+1250 B+2500 B+1100 B+1100
272 1994 3543 2487 2104 3453 B+1250 B+2500 B+1100 B+1100
302 1994 3543 2487 2104 3453 B+1250 B+2500 B+1100 B+1100
MODELHSE...
A B C D E F
162 2250 2176 2346 2360 2086 2132 B+1250 B+2500 B+1100 B+1100
182 2250 2176 2346 2360 2086 2132 B+1250 B+2500 B+1100 B+1100
222 2250 2176 2346 2360 2086 2132 B+1250 B+2500 B+1100 B+1100
GASBURNER
2 GASBURNER
F7FILTER
F9FILTER
GASBURNER
2 GASBURNER
F7FILTER
F9FILTER