Rockwell/TIA Portal Comparison TIA Portal software introduction for Rockwell Studio 5000 users.

Rockwell/TIA Portal Comparison

  • Upload
    vukhanh

  • View
    248

  • Download
    5

Embed Size (px)

Citation preview

Page 1: Rockwell/TIA Portal Comparison

Rockwell/TIA Portal Comparison

TIA Portal software introduction for Rockwell Studio 5000 users.

Page 2: Rockwell/TIA Portal Comparison

DISCLAIMER/ TERMS OF USE:

THE INFORMATION PROVIDED HEREIN IS PROVIDED AS A GENERAL REFERENCE REGARDING THE USE OF THE APPLICABLE PRODUCTS IN GENERIC APPLICATIONS. THIS INFORMATION IS PROVIDED WITHOUT WARRANTY. IT IS YOUR RESPONSIBILITY TO ENSURE THAT YOU ARE USING ALL MENTIONED PRODUCTS PROPERLY IN YOUR SPECIFIC APPLICATION. ALTHOUGH THIS PRESENTATION STRIVES TO MAINTAIN ACCURATE AND RELEVANT INFORMATION, THERE IS NO OFFICIAL GUARANTEE THAT THE INFORMATION PROVIDED HEREIN IS ACCURATE. IF YOU USE THE INFORMATION PROVIDED HEREIN IN YOUR SPECIFIC APPLICATION, PLEASE DOUBLE CHECK ITS APPLICABILITY AND BE ADVISED THAT YOU ARE USING THIS INFORMATION AT YOUR OWN RISK. THE PURCHASER OF THE PRODUCT MUST CONFIRM THE SUITABILITY OF THE PRODUCT FOR THE INTENDED USE, AND ASSUME ALL RISK AND LIABILITY IN CONNECTION WITH THE USE.

Page 3: Rockwell/TIA Portal Comparison

Webinar Design• Slides will go through the steps of creating a new project in TIA Portal and Studio 5000

• Differences between the two architectures are highlighted

• Webinar assumes a high level of competency in Studio 5000

Page 4: Rockwell/TIA Portal Comparison

Webinar Design Part 1 (February 11, 2015)• Create a new project in programming software

• Establish communications to processor

• Configure I/O modules and assign I/O tagnames

• Download to processor

• Go online with processor

• Create other tagnames, structures, user‐defined types, etc.

• Performing “online” edits

Page 5: Rockwell/TIA Portal Comparison

Webinar Design Part 2 (March 11, 2015)• Creating functions and function blocks

• Using functions from other projects (libraries)

• Configuring an operator interface

• Configuring a VFD

• Troubleshooting using system diagnostics

• Troubleshooting using traces• PLC to PLC Communications

Page 6: Rockwell/TIA Portal Comparison

Studio 5000 V24 FactoryTalk View Studio

Logix Designer Logix Designer for Drives

TIA Portal V13

Step 7 StartDrive WinCC

Software Comparison

Page 7: Rockwell/TIA Portal Comparison

Studio 5000 Logix Layout Title Bar

Menu Bar

Instruction Toolbox

StandardToolbar

Controller Organizer

Logic View

Results Window

Page 8: Rockwell/TIA Portal Comparison

TIA Portal Step 7 Layout – Network View

Project Tree

Title BarMenu BarTool Bar

Inspector Window

Task Cards

Work Area

Editor Bar Status Bar

Page 9: Rockwell/TIA Portal Comparison

TIA Portal Step 7 Layout – Ladder View

Project Tree

Title BarMenu BarTool Bar

Task Cards

Work Area

Editor Bar Status Bar

Page 10: Rockwell/TIA Portal Comparison

TIA Portal Step 7 Layout – HMI View

Project Tree

Title BarMenu BarTool Bar

Task Cards

Work Area

Editor Bar Status Bar

Page 11: Rockwell/TIA Portal Comparison

Projects in Studio 5000 (V24)• Single ACD file

• Single controller per project

• HMIs require separate software package (FT View Studio)

• Drives are integrated into controller

• Limited library support (export and import)

• One project open at a time

Page 12: Rockwell/TIA Portal Comparison

Projects in TIA Portal• Multiple files in multiple folders

• Multiple controllers per project

• Multiple HMIs per project

• Multiple drives per project

• Projects can be archived down to a single file for e‐mailing and sharing

• Reference projects allow quick drag‐and‐drop of objects

• Mature library functionality 

Page 13: Rockwell/TIA Portal Comparison

Projects in Studio 5000 (V24) Demonstration

Page 14: Rockwell/TIA Portal Comparison

Projects in Studio 5000 (V24) Demonstration

Auto‐generated Project Structure

Blank I/O Configuration

One Controller

Page 15: Rockwell/TIA Portal Comparison

Projects in TIA Portal Demonstration

Page 16: Rockwell/TIA Portal Comparison

Projects in TIA Portal Demonstration

No controller!  Why?

Page 17: Rockwell/TIA Portal Comparison

Hardware Configuration in TIA Portal

Hardware Configuration in Studio 5000• Non‐graphical tree interface

• I/O tagnames tied to module location

• I/O tagnames based on module type

• “Nice” I/O tagnames assigned using aliasing or buffering

• Graphical interface

• I/O addresses auto‐assigned independent of module location

• “Nice” I/O tagnames assigned at module level

Page 18: Rockwell/TIA Portal Comparison

Hardware Configuration in Studio 5000

Page 19: Rockwell/TIA Portal Comparison

Hardware Configuration in Studio 5000

Page 20: Rockwell/TIA Portal Comparison

Hardware Configuration in Studio 5000

“Ugly” tag

Page 21: Rockwell/TIA Portal Comparison

I/O tags in Studio 5000 ‐ Aliasing

“Nice” Alias Tag

“Ugly” I/O Tag

<Chassis Name>:<Slot Number>:<Data Type>.<Member>(.<Submember>)

Page 22: Rockwell/TIA Portal Comparison

I/O alias tags in Studio 5000

Page 23: Rockwell/TIA Portal Comparison

I/O tags in Studio 5000 ‐ Buffering

“Ugly” tag

“Nice” tag

Page 24: Rockwell/TIA Portal Comparison

Hardware Configuration in TIA Portal

Page 25: Rockwell/TIA Portal Comparison

Hardware Configuration in TIA Portal

Page 26: Rockwell/TIA Portal Comparison

I/O tags in TIA Portal

“Ugly” I/O Tag“Nice” I/O Tag

Page 27: Rockwell/TIA Portal Comparison

I/O tags in TIA Portal

Rewire tag – no stop necessary

Page 28: Rockwell/TIA Portal Comparison
Page 29: Rockwell/TIA Portal Comparison

TIA Portal Communications

Studio 5000 Communications• BOOTP or DHCP

• Onboard Communication options (USB, RS‐232)

• RSLinx

• Programming station must be on same subnet for Ethernet communications

• Accessible Devices

• Onboard Communication options (Profibus, Profinet)

• No additional software required (i.e. RSLinx)

• Additional IP address added to programming station to allow immediate Ethernet communications

Page 30: Rockwell/TIA Portal Comparison

Studio 5000 Communications

Page 31: Rockwell/TIA Portal Comparison

TIA Portal Communications

Page 32: Rockwell/TIA Portal Comparison

Studio 5000 Download• Path set via “Who Active” and RSLinx

• Project compile occurs automatically

• Processor stopped during download

Page 33: Rockwell/TIA Portal Comparison

TIA Portal Download• Path set as part of download process

• Project compile occurs automatically

• Processor stopped during download only if hardware configuration has changed

Page 34: Rockwell/TIA Portal Comparison

TIA Portal Getting Online

Studio 5000 Getting Online• Path set via “Who Active” and RSLinx

• Offline and Online projects are compared and user is asked either to upload, download, or create new project

• Offline and Online differences are not highlighted without utilizing offline tools.

• Software clearly indicates the online state

• Path set as part of download process

• Offline and Online projects are compared and user is encouraged to rectify differences

• Offline and Online differences are clearly highlighted• Software clearly indicates the online state

Page 35: Rockwell/TIA Portal Comparison

Studio 5000 Getting Online with Changes

Page 36: Rockwell/TIA Portal Comparison

Studio 5000 Getting Online with Changes

Page 37: Rockwell/TIA Portal Comparison

TIA Portal Getting Online with Changes

Exist offline only

Offline and Online are Different

Page 38: Rockwell/TIA Portal Comparison

TIA Portal Getting Online with Changes

Page 39: Rockwell/TIA Portal Comparison

TIA Portal Getting Online with Changes

Page 40: Rockwell/TIA Portal Comparison

TIA Portal Tags

Studio 5000 Tags• Controller Scope or Program Scope

• Alias tags• 40 character limit

• Not case sensitive• No special characters (numbers, letters, and underscores only)

• Tags must be defined in Controller Tags or Program Tags 

• All tags are global scope (controller)

• Alias tags (via PLC tags)

• 128 character limit

• Not case sensitive

• Special characters allowed (except quotation marks)• User‐definable tag tables  (data blocks and PLC tags) for increased organization

Page 41: Rockwell/TIA Portal Comparison

IEC 61131‐3 RegulationsData Type Studio 5000 TIA PortalBoolean BOOL BoolCounter COUNTER IEC_COUNTERDouble Integer DINT DintInteger INT IntReal REAL RealSmall Integer SINT ByteString STRING StringTimer TIMER IEC_TIMERDate DateDate/Time Date_And_TimeTime TimeUser Defined Yes YesArrays Yes Yes

IEC 61131‐3 Language Studio 5000 TIA PortalLadder Logic Ladder Diagram LADFunction Block Diagram Function Block Diagram FBDSequential Function Chart Sequential Function Chart GRAPHStructured Text Structured Text SCLInstruction List STL

IEC 61131‐3 I/O Addresses Studio 5000 TIA PortalInputs (I) <Name>:<Slot>:I.Member %I<#>Outputs (Q) <Name>:<Slot>:O.Member %Q<#>

Page 42: Rockwell/TIA Portal Comparison

Studio 5000 Controller Tags ExampleSort Columns

Page 43: Rockwell/TIA Portal Comparison

TIA Portal Tags Example

Page 44: Rockwell/TIA Portal Comparison

Studio 5000 Online Editing• Start edits

• Perform edits

• Accept edits (compile)

• Test edits (download)

• Assemble edits

Page 45: Rockwell/TIA Portal Comparison

Studio 5000 Online Editing• Start edits

Page 46: Rockwell/TIA Portal Comparison

Studio 5000 Online Editing• Perform edits

Page 47: Rockwell/TIA Portal Comparison

Studio 5000 Online Editing• Accept edits

Page 48: Rockwell/TIA Portal Comparison

Studio 5000 Online Editing• Test edits

Page 49: Rockwell/TIA Portal Comparison

Studio 5000 Online Editing• Assemble edits

Page 50: Rockwell/TIA Portal Comparison

Studio 5000 Online Editing• Or, Finalize All

Page 51: Rockwell/TIA Portal Comparison

TIA Portal Online Editing• Edits are performed offline 

• Compile edits (offline)

• Download edits (processor is NOT stopped)

• Next scan, new edits are executed (i.e. bumpless)

Page 52: Rockwell/TIA Portal Comparison

TIA Portal Online EditingOnline Indication

Page 53: Rockwell/TIA Portal Comparison

TIA Portal Online Editing

Change Made

Taken Offline

Page 54: Rockwell/TIA Portal Comparison

TIA Portal Online Editing

Compile Changes

Online vs. Offline Comparison

Page 55: Rockwell/TIA Portal Comparison

TIA Portal Online Editing

Download Changes

Page 56: Rockwell/TIA Portal Comparison

TIA Portal Online Editing

Page 57: Rockwell/TIA Portal Comparison

TIA Portal Online Editing

Complete

Online vs. Offline Comparison

Page 58: Rockwell/TIA Portal Comparison

Questions?