154
Relion ® 615 Series Transformer Protection and Control RET615 ANSI Application Manual

Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

  • Upload
    vocong

  • View
    229

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Relion® 615 Series

Transformer Protection and ControlRET615 ANSIApplication Manual

Page 2: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI
Page 3: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Document ID: 1MAC201230-MBIssued: 3/7/2011

Revision: BProduct version: 4.0

© Copyright 2011 ABB. All rights reserved.

Page 4: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Copyright

This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.

Trademarks

ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.

Warranty

Please inquire about the terms of warranty from your nearest ABB representative.

ABB Inc.Distribution Automation4300 Coral Ridge DriveCoral Springs, FL 33065, USAToll-free: 1 (800) 523-2620Phone: +1 954-752-6700Fax: +1 954 345-5329http://www.abb.com/substationautomation

Page 5: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Disclaimer

The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.

Page 6: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Conformity

This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-6 and EN 60255-27 for the low voltage directive. The IED is designed in accordance with the international standards of the IEC 60255 series and ANSI C37.90. This IED complies with the UL 508 certification.

Page 7: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section

RET615 ANSI 1Application Manual

Section 1 Introduction ...........................................................................5This manual ..............................................................................................5Intended audience ....................................................................................5Product documentation.............................................................................6

Product documentation set..................................................................6Document revision history ...................................................................7Related documentation........................................................................7

Symbols and conventions.........................................................................7Safety indication symbols ....................................................................7Manual conventions.............................................................................8Functions, codes and symbols ............................................................9

Section 2 RET615 overview................................................................15Overview.................................................................................................15

Product version history ......................................................................15PCM600 and IED connectivity package version................................15

Operation functionality ............................................................................16Optional features ...............................................................................16

Physical hardware ..................................................................................16Local HMI................................................................................................19

LCD ...................................................................................................19LEDs..................................................................................................20Keypad ..............................................................................................20

Web HMI.................................................................................................21Authorization...........................................................................................22Communication.......................................................................................23

Section 3 RET615 configurations .......................................................25RET615 variant list .................................................................................25Presentation of standard configurations .................................................25

Standard configurations.....................................................................26Standard Configuration for Order Code Functional Application AA........30

Applications .......................................................................................30 Functions ..........................................................................................31Default Input/Output (I/O) assignments .............................................34Typical connection diagrams .............................................................36Functional diagrams ..........................................................................37

Functional diagrams for protection ...............................................37Functional diagrams for control functions ....................................45Functional diagrams for condition monitoring ..............................47Functional diagrams for Measurements .......................................49Functional diagrams for other functions .....................................49Functional diagrams for logging functions ..................................49

Page 8: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 1MAC201230-MB B

2 RET615 ANSIApplication Manual

Functional diagrams for I/O and Alarm LEDs .............................50Standard Configuration for Order Code Functional Application BA and CA ..............................................................................................53

Applications ......................................................................................53 Functions ..........................................................................................54Default Input/Output (I/O) assignments .............................................57Typical connection diagrams .............................................................59Functional diagrams ..........................................................................61

Functional diagrams for protection ...............................................61Functional diagrams for control functions ....................................72Functional diagrams for condition monitoring ..............................73Functional diagrams for Measurements .......................................75Functional diagrams for other functions .....................................76Functional diagrams for logging functions ..................................77Functional diagrams for I/O and Alarm LEDs .............................77

Standard Configuration for Order Code Functional Application BB/CB..82Applications .......................................................................................82Functions ...........................................................................................83Default Input/Output (I/O) assignments .............................................86 Typical connection diagrams ............................................................88Functional diagrams ..........................................................................89

Functional diagrams for protection ...............................................89Functional diagrams for control functions ..................................100Functional diagrams for condition monitoring ............................102Functional diagrams for Measurements .....................................104Functional diagrams for other functions ...................................105Functional diagrams for logging functions ................................105Functional diagrams for I/O and Alarm LEDs ...........................106

Standard Configuration for Order Code Functional Application DA......110Applications .....................................................................................110Functions .........................................................................................111Default Input/Output (I/O) assignments ...........................................114Typical connection diagrams ...........................................................116Functional diagrams ........................................................................117

Functional diagrams for protection .............................................117Functional diagrams for control functions ..................................128Functional diagrams for condition monitoring ............................129Functional diagrams for Measurements .....................................132Functional diagrams for other functions ...................................132Functional diagrams for logging functions ................................133Functional diagrams for I/O and Alarm LEDs ...........................134

Page 9: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section

RET615 ANSI 3Application Manual

Section 4 IED physical connections..................................................139Inputs ....................................................................................................139

Auxiliary supply voltage input ..........................................................139Binary inputs....................................................................................139Optional light sensor inputs .............................................................141

Outputs .................................................................................................141Outputs for tripping and controlling..................................................141Outputs for signalling.......................................................................142IRF...................................................................................................143

Section 5 Glossary............................................................................145

Page 10: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 1MAC201230-MB B

4 RET615 ANSIApplication Manual

Page 11: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 1Introduction

RET615 ANSI 5Application Manual

Section 1 Introduction

1.1 This manual

The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings.

1.2 Intended audience

This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering.

The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology, such as communication and protocols.

Page 12: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 1 1MAC201230-MB B

Introduction

6 RET615 ANSIApplication Manual

1.3 Product documentation

1.3.1 Product documentation set

Figure 1: The intended use of manuals in different lifecyclesThe engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also recommends a sequence for engineering of protection and control functions, LHMI functions as well as communication engineering for IEC 61850 and DNP3.

The installation manual contains instructions on how to install the IED. The manual provides procedures for mechanical and electrical installation. The chapters are organized in chronological order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED. Themanual can also be used by system engineers and maintenance personnel for assistance during the testing phase. The manual provides procedures for checking of external circuitry and energizing the IED, parameter setting and configuration as well as verifying settings by secondary injection. The manual describes the process of testing an IED in a substation which is not in service. The chapters are organized in chronological order in which the IED should be commissioned.

The operation manual contains instructions on how to operate the IED once it has been commissioned. The manual provides instructions for monitoring, controlling and setting

Pla

nn

ing

& p

urc

has

e

En

gin

eeri

ng

Inst

allin

g

Co

mm

issi

on

ing

Op

erat

ion

Mai

nte

nan

ce

Dec

om

mis

sio

nin

gD

ein

stal

lin

g &

Dis

po

sal

Application manual

Operation manual

Installation manual

Engineering manual

Communication Protocol manual

Technical manual

Protocol Points List manual

Page 13: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 1Introduction

RET615 ANSI 7Application Manual

the IED. The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault.

The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings.

The technical manual contains application and functionality descriptions and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data sorted per function. The manual can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service.

The communication protocol manual describes a communication protocol supported by the IED. The manual concentrates on vendor-specific implementations.

The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual.

1.3.2 Document revision history

1.3.3 Related documentation

1.4 Symbols and conventions

1.4.1 Safety indication symbols

Document revision/date Product version HistoryA/01/20/2010 2.0 First release

B/03/01/2011 4.0 Second release

Download the latest documents from the ABB web site http://www.abb.com/substation automation.

Name of the document Document IDModbus Communication Protocol Manual 1MAC052634-MB

DNP3 Communication Protocol Manual 1MAC052460-MB

IEC 61850 Engineering Guide 1MAC106231-MB

Installation Manual 1MAC051065-MB

Operation Manual 1MAC050592-MB

Technical Manual 1MAC050144-MB

The electrical warning icon indicates the presence of a hazard which could result in electrical shock.

Page 14: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 1 1MAC201230-MB B

Introduction

8 RET615 ANSIApplication Manual

Although warning hazards are related to personal injury, it should be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.

1.4.2 Manual conventionsConventions used in IED manuals. A particular convention may not be used in this manual.

• Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms.

• Push button navigation in the LHMI menu structure is presented by using the push button icons, for example:

To navigate between the options, use and .

• HMI menu paths are presented in bold, for example:

Select Main menu > Settings.

• LHMI messages are shown in Courier font, for example:

To save the changes in non-volatile memory, select Yes and press .

• Parameter names are shown in italics, for example:

The function can be enabled and disabled with the Operation setting.

• Parameter values are indicated with quotation marks, for example:

The corresponding parameter values are "Enabled" and "Disabled".

• IED input/output messages and monitored data names are shown in Courier font, for example:

When the function picks up, the PICKUP output is set to TRUE.

• Dimensions are provided both in inches and mm. If it is not specifically mentioned then the dimension is in mm.

The warning icon indicates the presence of a hazard which could result in personal injury.

The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.

The information icon alerts the reader to important facts and conditions.

The tip icon indicates advice on, for example, how to design your project or how to use a certain function.

Page 15: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 1Introduction

RET615 ANSI 9Application Manual

1.4.3 Functions, codes and symbolsAll available functions are listed in the table. All of them may not be applicable to all products.

Page 16: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 1 1MAC201230-MB B

Introduction

10 RET615 ANSIApplication Manual

Table 1: Functions included in the RET615 standard configurations

Function IEC61850 ANSI/C37.2 IEC60617

Protection

Three-phase non-directional overcurrent protection, low stage, instance 1

PHLPTOC1 51P (1) 3I> (1)

Three-phase non-directional overcurrent protection, low stage, instance 2

PHLPTOC2 51P (2) 3I> (2)

Three-phase non-directional overcurrent protection, high stage, instance 1

PHHPTOC1 50P-1 (1) 3I>> (1)

Three-phase non-directional overcurrent protection, high stage, instance 2

PHHPTOC2 50P-1 (2) 3I>> (2)

Three-phase non-directional overcurrent protection, high stage, instance 3

PHHPTOC3 50P-2 (1) 3I>> (3)

Three-phase non-directional overcurrent protection, high stage, instance 4

PHHPTOC4 50P-2 (2) 3I>> (4)

Three-phase directional overcurrent protection, low stage, instance 1

DPHLPDOC1 67/51P (2) 3I> -> (1)

Three-phase directional overcurrent protection, low stage, instance 2

DPHLPDOC2 67/51P (1) 3I> -> (2)

Non-directional ground-fault protection, low stage, instance 1

EFLPTOC1 51N (1) Io> (1)

Non-directional ground-fault protection, low stage, instance 2

EFLPTOC2 51N (2) Io> (2)

Non-directional ground-fault protection, low stage, instance 3

EFLPTOC3 51G Io> (3)

Non-directional ground-fault protection, high stage, instance 1

EFHPTOC1 50G-1 Io>> (1)

Non-directional ground-fault protection, high stage, instance 2

EFHPTOC2 50G-2 Io>> (2)

Non-directional ground-fault protection, high stage, instance 3

EFHPTOC3 50N-1 (1) Io>> (3)

Non-directional ground-fault protection, high stage, instance 4

EFHPTOC4 50N-1 (2) Io>> (4)

Non-directional ground-fault protection, high stage, instance 5

EFHPTOC5 50N-2 (1) Io>> (5)

Non-directional ground-fault protection, high stage, instance 6

EFHPTOC6 50N-2 (2) Io>> (6)

Directional ground-fault protection, low stage, instance 1

DEFLPDEF1 67/51N (2) Io> -> (1)

Directional ground-fault protection, low stage, instance 2

DEFLPDEF2 67/51N (1) Io> -> (2)

Negative-sequence overcurrent protection, instance 1 NSPTOC1 46 (1) I2> (1)

Negative-sequence overcurrent protection, instance 2 NSPTOC2 46 (2) I2> (2)

Residual overvoltage protection, instance 1 ROVPTOV1 59G (2) Uo> (1)

Residual overvoltage protection, instance 2 ROVPTOV2 59N (2) Uo> (2)

Residual overvoltage protection, instance 3 ROVPTOV3 59N (1) Uo> (3)

Residual overvoltage protection, instance 4 ROVPTOV4 59G (1) Uo> (4)

Three-phase undervoltage protection, instance 1 PHPTUV1 27 (2) 3U< (1)

Page 17: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 1Introduction

RET615 ANSI 11Application Manual

Three-phase undervoltage protection, instance 2 PHPTUV2 27 (1) 3U< (2)

Three-phase overvoltage protection, instance 1 PHPTOV1 59 (2) 3U> (1)

Three-phase overvoltage protection, instance 2 PHPTOV2 59 (1) 3U> (2)

Negative-sequence overvoltage protection, instance 1

NSPTOV1 47 (2) U2> (1)

Negative-sequence overvoltage protection, instance 2

NSPTOV2 47 (1) U2> (2)

Frequency protection, instance 1 FRPFRQ1 81-1 (2) f>/f<,df/dt (1)

Frequency protection, instance 2 FRPFRQ2 81-2 (2) f>/f<,df/dt (2)

Frequency protection, instance 3 FRPFRQ3 81-1 (1) f>/f<,df/dt (3)

Frequency protection, instance 4 FRPFRQ4 81-2 (1) f>/f<,df/dt (4)

Voltage per hertz protection, instance 1 OEPVPH1 24-1 (2) U/f> (1)

Voltage per hertz protection, instance 2 OEPVPH2 24-2 (2) U/f> (2)

Voltage per hertz protection, instance 3 OEPVPH3 24-1 (1) U/f> (3)

Voltage per hertz protection, instance 4 OEPVPH4 24-2 (1) U/f> (4)

Three-phase thermal overload protection for power transformers, two time constants

T2PTTR1 49T (1) 3Ith>T

Restrained (Low Stage) and unrestrained (High Stage) differential protection for 2W –transformers

TR2PTDF1 87T 3dI>T

Numerical restrained (low stage) low impedance restricted ground-fault protection

LREFPNDF1 87LOZREF (2) dIoLo>

Circuit breaker failure protection, instance 1 CCBRBRF1 50BF (2) 3I>/Io>BF (1)

Circuit breaker failure protection, instance 2 CCBRBRF2 50BF (1) 3I>/Io>BF (2)

Master trip, instance 1 TRPPTRC1 86/94-1 Master Trip (1)

Master trip, instance 2 TRPPTRC2 86/94-2 Master Trip (2)

Arc protection, instance 1 ARCSARC1 AFD-1 (2) ARC (1)

Arc protection, instance 2 ARCSARC2 AFD-2 (2) ARC (2)

Arc protection, instance 3 ARCSARC3 AFD-3 (2) ARC (3)

Load shedding and restoration, instance 1 LSHDPFRQ1 81LSH-1 (2) UFLS/R (1)

Load shedding and restoration, instance 2 LSHDPFRQ2 81LSH-2 (2) UFLS/R (2)

Load shedding and restoration, instance 3 LSHDPFRQ3 81LSH-1 (1) UFLS/R (3)

Load shedding and restoration, instance 4 LSHDPFRQ4 81LSH-2 (1) UFLS/R (4)

Loss of phase, instance 1 PHPTUC1 37 (1) 3I< (1)

Control

Circuit-breaker control, instance 1 CBXCBR1 52 (2) I <-> O CB (1)

Circuit-breaker control, instance 2 CBXCBR2 52 (1) I <-> O CB (2)

Tap changer position indication TPOSSLTC1 84T TPOSM

Function IEC61850 ANSI/C37.2 IEC60617

Page 18: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 1 1MAC201230-MB B

Introduction

12 RET615 ANSIApplication Manual

Condition Monitoring

Circuit-breaker condition monitoring, instance 1 SSCBR1 52CM (2) CBCM (1)

Circuit-breaker condition monitoring, instance 2 SSCBR2 52CM (1) CBCM (2)

Trip circuit supervision, instance 1 TCSSCBR1 TCM-1 TCS (1)

Trip circuit supervision, instance 2 TCSSCBR2 TCM-2 TCS (2)

Advanced current circuit supervision for transformers CTSRCTF1 MCS 3I, I2 MCS 3I, I2

Fuse failure supervision, instance 1 SEQRFUF1 60 (2) FUSEF (1)

Fuse failure supervision, instance 2 SEQRFUF2 60 (1) FUSEF (2)

Measurement

Three-phase current measurement, instance 1 CMMXU1 IA, IB, IC (2) 3I

Three-phase current measurement, instance 2 CMMXU2 IA, IB, IC (1) 3I(B)

Sequence current measurement, instance 1 CSMSQI1 I1, I2, I0 (2) I1, I2, I0

Sequence current measurement, instance 2 CSMSQI2 I1, I2, I0 (1) I1, I2, I0(B)

Residual current measurement, instance 1 RESCMMXU1 IG Io

Three-phase voltage measurement, instance 1 VMMXU1 VA, VB, VC (2)

3U

Three-phase voltage measurement, instance 2 VMMXU2 VA, VB, VC (1)

3U(B)

Residual voltage measurement RESVMMXU1 VG Uo

Sequence voltage measurement, instance 1 VSMSQI1 V1, V2, V0 (2) U1, U2, U0

Sequence voltage measurement, instance 2 VSMSQI2 V1, V2, V0 (1) U1, U2, U0(B)

Single-phase power and energy measurement, instance 1

SPEMMXU1 SP, SE (2) SP, SE

Single-phase power and energy measurement, instance 2

SPEMMXU2 SP, SE (1) SP, SE(B)

Three-phase power and energy measurement, instance 1

PEMMXU1 P, E (2) P, E

Three-phase power and energy measurement, instance 2

PEMMXU2 P, E (1) P, E(B)

Frequency measurement FMMXU1 f f

Recorder

Disturbance recorder RDRE1 DFR -

Fault recorder FLMSTA1 FR -

Sequence event recorder SER SER -

Other Functions

Minimum pulse timer (2 pcs), instance 1 TPGAPC1 TP-1 TP (1)

Minimum pulse timer (2 pcs), instance 2 TPGAPC2 TP-2 TP (2)

Minimum pulse timer (2 pcs), instance 3 TPGAPC3 TP-3 TP (3)

Function IEC61850 ANSI/C37.2 IEC60617

Page 19: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 1Introduction

RET615 ANSI 13Application Manual

Minimum pulse timer (2 pcs), instance 4 TPGAPC4 TP-4 TP (4)

Pulse timer (8 pcs), instance 1 PTGAPC1 PT-1 PT (1)

Pulse timer (8 pcs), instance 2 PTGAPC2 PT-2 PT (2)

Time delay off (8 pcs), instance 1 TOFGAPC1 TOF-1 TOF (1)

Time delay off (8 pcs), instance 2 TOFGAPC2 TOF-2 TOF (2)

Time delay on (8 pcs), instance 1 TONGAPC1 TON -1 TON (1)

Time delay on (8 pcs), instance 2 TONGAPC2 TON -2 TON (2)

Set reset (8 pcs), instance 1 SRGAPC1 SR-1 SR (1)

Set reset (8 pcs), instance 2 SRGAPC2 SR-2 SR (2)

Move (8 pcs), instance 1 MVGAPC1 MV-1 MV (1)

Move (8 pcs), instance 2 MVGAPC2 MV-2 MV (2)

Function IEC61850 ANSI/C37.2 IEC60617

Page 20: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 1 1MAC201230-MB B

Introduction

14 RET615 ANSIApplication Manual

Page 21: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 2RET615 overview

RET615 ANSI 15Application Manual

Section 2 RET615 overview

2.1 Overview

RET615 is a dedicated transformer protection and control IED (Intelligent Electronic Device) for power transformers, unit and step-up transformers including power generatortransformer blocks in utility and industry power distribution systems. RET615 is a member of ABB’s Relion® product family and part of its 615 protection and control product series. The 615 series IEDs are characterized by their compactness and withdrawable design.

Re-engineered from the ground up, the 615 series has been designed to unleash the full potential of the IEC 61850 standard for communication and interoperability between substation automation devices. Once the standard configuration IED has been given the application-specific settings, it can directly be put into service.

The 615 series IEDs support a range of communication protocols including IEC 61850 with GOOSE messaging, Modbus® and DNP3.

2.1.1 Product version history

2.1.2 PCM600 and IED connectivity package version• Protection and Control IED Manager PCM600 Ver. 2.3 (plus PCM600 rollup

20110126 2.3) or later.

• IED Connectivity Package RET615 Ver. 4.0 ANSI

• Parameter Setting • Application configuration• Firmware Update • Disturbance Handling • Signal Monitoring

Product version Product history1.0.1

1.1

2.0

4.0 • User programming through Application Configuration tool• Frequency measurement protection • Load shedding and restoration• Single phase power and energy measurement• Load profile recorder

Page 22: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 2 1MAC201230-MB B

RET615 overview

16 RET615 ANSIApplication Manual

• Life cycle Traceability • Signal Matrix • Communication Management • Configuration Wizard• Label Printing• IED User Management• IED Users

2.2 Operation functionality

2.2.1 Optional features• High speed BIO cards

• The regular 8BI+4BO cards can be replaced with optional binary cards with high speed output (8BI+3HSO). These cards will be replaced at the X110 slot.

• RTD measurement inputs

• A two channel/six channel RTD measurement inputs can be connected to X130 slot.

• Additional BIOs, 6BI+3BO

• Additional binary cards can be used if needed at the X130 slot (See Table 2).

2.3 Physical hardware

The IED consists of two main parts: plug-in unit and case. The plug-in unit content depends on the ordered functionality.

Download connectivity packages from the ABB web site http://www.abb.com/substationautomation

Page 23: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 2RET615 overview

RET615 ANSI 17Application Manual

Table 2: Plug-in unit and case

The rated input levels are selected in the IED software for phase current and ground current. The binary input thresholds 18...176 V DC are selected by adjusting the IED's parameter settings.

The connection diagrams of different hardware modules are presented in this manual.

Main unit Slot ID Module ID Content optionsPlug in unit - DISxxxx HMI 128/128 LCD large display with text and graphics

X100 PSMxxxx Auxiliary power/BO module

48-250V DC/ 80-240V AC; or 24-60V DC2 normally-open PO contacts2 normally-closed SO contacts2 double-pole PO contacts with TCS1 dedicated internal fault output contact

X110 BIOxxxx BI/O module All Configurations (A,B,C,D)8 Binary Inputs4 Binary Outputs

Can be replaced with optional high-speed BIO card for all configurations.8 Binary Inputs3 High speed SO contacts

X120 AIMxxxx AI/BI module All Configurations (A,B,C,D)7 Current Inputs with Io

Case X130 AIMxxxx AI/BI module With Configuration A, Optional BIO(6BI + 3BO) card can be used.

With Configuration B, 5 Voltage Inputs(Winding2), 4 Binary Inputs(Or)5 Voltage Inputs(Winding1) & 4 Binary Inputs

With Configuration C,5 Voltage Inputs(Winding2), 2 RTD & 1 low current (0.1mA - 20mA) inputs(Or)5 Voltage Inputs (Winding1),2 RTD & 1 low current (0.1mA - 20mA) inputs

With Configuration D, 6 Voltage Inputs (Winding 2 &1)3 Binary Inputs

X000 COMxxxx Communication module

See technical manual for details about different type of communication modules.

The optional BIO module can be added in the IED to all standard configurations.

See the installation manual for more information about the case and the plug-in unit.

Page 24: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 2 1MAC201230-MB B

RET615 overview

18 RET615 ANSIApplication Manual

Table 3: Number of physical connections in standard configurations

Functional application configuration.

Analog channels Binary channels

CT VT RTD mA BI BOA 7 0 0 0 Min –8

Max - 14Min – 10Max - 13

B 7 5(Winding 2, or, Winding 1)

0 0 12 9-10

C 7 5(Winding 2, or, Winding 1)

2 1 8 9-10

D 7 6 0 0 11 10

Page 25: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 2RET615 overview

RET615 ANSI 19Application Manual

2.4 Local HMI

Figure 2: LHMIThe LHMI of the IED contains the following elements:

• Display

• Buttons

• LED indicators

• Communication port

The LHMI is used for setting, monitoring and controlling.

2.4.1 LCDThe LHMI includes a graphical LCD that supports two character sizes. The character size depends on the selected language.

Page 26: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 2 1MAC201230-MB B

RET615 overview

20 RET615 ANSIApplication Manual

Table 4: Characters and rows on the view

The display view is divided into four basic areas.

Figure 3: Display layout1 Header

2 Icon

3 Content

4 Scroll bar (displayed when needed)

2.4.2 LEDsThe LHMI includes three protection indicators above the display: Normal, Pickup and Trip.

There are also 11 matrix programmable alarm LEDs on front of the LHMI. The LEDs can be configured with PCM600 and the operation mode can be selected with the LHMI, WHMI or PCM600.

There are two additional LEDs which are embedded into the control buttons and . They represent the status of the circuit breaker.

2.4.3 KeypadThe LHMI keypad contains push-buttons which are used to navigate in different views or menus. With the push-buttons you can give open or close commands to one primary object, for example, a circuit breaker, disconnector or switch. The push-buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode.

Character size Rows in view Characters on rowLarge, variable width (13x14 pixels)

10 rows min 8

1 2

3 4

Page 27: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 2RET615 overview

RET615 ANSI 21Application Manual

Figure 4: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port

2.5 Web HMI

The WHMI enables the user to access the IED via a web browser. The supported web browser version is Internet Explorer 7.0 or later.

WHMI offers several functions.

• Alarm indications and event lists

• System supervision

• Parameter settings

• Measurement display

• Oscillographic records

• Phasor diagram

The menu tree structure on the WHMI is almost identical to the one on the LHMI.

WHMI is enabled by default.

Page 28: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 2 1MAC201230-MB B

RET615 overview

22 RET615 ANSIApplication Manual

Figure 5: Example view of the WHMIThe WHMI can be accessed locally and remotely.

• Locally by connecting your laptop to the IED via the front communication port.

• Remotely over LAN/WAN.

2.6 Authorization

The user categories have been predefined for the LHMI and the WHMI, each with different rights and default passwords.

The default passwords can be changed with Administrator user rights.

User authorization is disabled by default but WHMI always uses authorization.

Page 29: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 2RET615 overview

RET615 ANSI 23Application Manual

Table 5: Predefined user categories

2.7 Communication

The IED supports different communication protocols: IEC 61850, Modbus® and DNP 3.0 Level 2 - all using TCP/IP. DNP3 and Modbus also support serial communication. Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal peer-to-peer communication between the IEDs and parameters setting, is only enabled by the IEC 61850 communication protocol.

The IEC 61850 communication implementation supports all monitoring and control functions. Additionally, parameter setting and DFR records can be accessed using the IEC 61850 protocol. Oscillographic files are available to any Ethernet-based application in the standard COMTRADE format. Further, the IED can send and receive binary signals from other IEDs (so called horizontal communication) using the IEC61850-8-1 GOOSE profile, where the highest performance class with a total transmission time of 3 ms is supported. Also, the IED supports sending and receiving of analog values using GOOSE messaging. The IED meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard. The IED can simultaneously report events to five different clients on the station bus.

All communication connectors, except for the front port connector, are placed on integrated optional communication modules. The IED can be connected to Ethernet-based communication systems via the RJ-45 connector (100BASE-TX) or the fiber-optic LC connector (100BASE-FX).

Username User rightsVIEWER Read only access

OPERATOR• Selecting remote or local state with (only locally) • Changing setting groups• Controlling• Clearing alarm and indication LEDs and textual indications

ENGINEER • Changing settings• Clearing event list• Clearing DFRs• Changing system settings such as IP address, serial baud rate or

DFR settings• Setting the IED to test mode • Selecting language

ADMINISTRATOR • All listed above • Changing password• Factory default activation

For user authorization for PCM600, see PCM600 documentation.

Page 30: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 2 1MAC201230-MB B

RET615 overview

24 RET615 ANSIApplication Manual

Page 31: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 25Application Manual

Section 3 RET615 configurations

3.1 RET615 variant list

RET615 is intended for protection and control mainly in MV transformer applications. The product has four standard configurations covering a wide range of primary circuit configurations in distribution networks based on different system grounding methods.

Some of the functions included in the IED's standard configurations are optional at the time of placing the order. The description of standard configurations covers the full functionality including options, presenting the functionality, flexibility and external connections of RET615 with a specific configuration as delivered from the factory.

3.2 Presentation of standard configurations

Functional diagrams

The functional diagrams describe the IED's functionality from the protection, measuring, condition monitoring, recording, control and interlocking perspective. Diagrams show the default functionality with simple symbol logics forming principle diagrams. The external connections to primary devices are also shown, stating the default connections to measuring transformers. The positive measuring direction is towards the outgoing feeder, away from the bus bar.

The functional diagrams are divided into sections with each section constituting one functional entity. The external connections are also divided into sections. Only the relevant connections for a particular functional entity are presented in each section.

Protection function blocks are part of the functional diagram. They are identified based on their ANSI function number/acronym, but the IEC based symbol and the IEC 61850 names are also included. Some function blocks are used several times in the configuration. To separate the blocks from each other, the IEC 61850 name and ANSI function number are appended with a running number, that is an instance number, from one upwards. The IED’s internal functionality and the external connections are separated with a dashed line presenting the IED’s physical casing.

Signal Matrix

With Signal Matrix in PCM600 the user can modify the standard configuration according to the actual needs. The IED is delivered from the factory with default connections described in the functional diagrams for BI's, BO's, function to function connections and alarm LEDs. Signal Matrix has a number of different page views, designated as follows:

Page 32: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

26 RET615 ANSIApplication Manual

• Binary input

• Binary output

• Functions

There are four IED variant-specific setting groups. Parameters can be set independently for each setting group.

The active setting group (1...4,6) can be changed with a parameter. The active setting group can also be changed via a binary input if the binary input is enabled for this. To enable the change of the active setting group via a binary input, connect a free binary input with PCM600 to the BI_SG_x input of the Protection block.

Table 6: Binary input states and corresponding active setting groups

The active setting group defined by a parameter is overridden when a binary input is enabled for changing the active setting group.

3.2.1 Standard configurationsThe motor protection IED RET615 is available with six different functional application configurations. Table 7 shows the different configurations available for the IED.

Table 7: Standard configurations

BI state Active setting groupOFF 1

ON 2

DescriptionFunctional application configuration

Differential and over-current protection for two-winding transformers. AA

Differential, over-excitation, over-current, voltage (winding 1 or 2) and frequency protection and power system metering for two-winding transformers.

BA/BB

Differential, over-excitation over-current, voltage (winding 1 or 2), frequency and RTD protection and power system metering for two-winding transformers.

CA/CB

Differential, over-excitation, over-current, voltage (windings 1 and 2) and frequency protection and power system metering for two-winding transformers.

DA

Page 33: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 27Application Manual

Table 8: Supported functions

Software ConfigurationStd

config.A

Std config.B/C

Std config.B/C

Std config.

DANSI

Function AA BA CA BB CB DA RET

Protection

Three-phase non-directional overcurrent protection, low stage, instance 1

● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 51P (1)

Three-phase non-directional overcurrent protection, low stage, instance 2

● 4) ● 4) ● 4) ● 4) ● 4) ● 4) 51P (2)

Three-phase non-directional overcurrent protection, high stage, instance 1

● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 50P-1 (1)

Three-phase non-directional overcurrent protection, high stage, instance 2

● 4) ● 4) ● 4) ● 4) ● 4) ● 4) 50P-1 (2)

Three-phase non-directional overcurrent protection, high stage, instance 3

● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 50P-2 (1)

Three-phase non-directional overcurrent protection, high stage, instance 4

● 4) ● 4) ● 4) ● 4) ● 4) ● 4) 50P-2 (2)

Three-phase directional overcurrent protection, low stage, instance 1

- ● 4) ● 4) - - ● 4) 67/51P (2)

Three-phase directional overcurrent protection, low stage, instance 2

- - - ● 5) ● 5) ● 5) 67/51P (1)

Non-directional ground-fault protection, low stage, instance 1 ● ● ● ● ● ● 51G

Non-directional ground-fault protection, low stage, instance 2 ● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 51N (1)

Non-directional ground-fault protection, low stage, instance 3 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) 51N (2)

Non-directional ground-fault protection, high stage, instance 1 ● ● ● ● ● ● 50G-1

Non-directional ground-fault protection, high stage, instance 2 ● ● ● ● ● ● 50G-2

Non-directional ground-fault protection, high stage, instance 3 ● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 50N-1 (1)

Non-directional ground-fault protection, high stage, instance 4 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) 50N-1 (2)

Non-directional ground-fault protection, high stage, instance 5 ● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 50N-2 (1)

Non-directional ground-fault protection, high stage, instance 6 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) 50N-2 (2)

Directional ground-fault protection, low stage, instance 1 - ● 1,2,4)

● 1,2,4)

- - ● 1,2,4)

67/51N (2)

Directional ground-fault protection, low stage, instance 2 - - - ● 1,2,5)

● 1,2,5)

● 1,2,5)

67/51N (1)

Negative-sequence overcurrent protection, instance 1 ● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 46 (1)

Negative-sequence overcurrent protection, instance 2 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) 46 (2)

Residual overvoltage protection, instance 1 - ● 4) ● 4) - - - 59G (2)

Residual overvoltage protection, instance 2 - ● 4) ● 4) - - ● 3,4) 59N (2)

Residual overvoltage protection, instance 3 - - - ● 5) ● 5) ● 3,5) 59N (1)

Residual overvoltage protection, instance 4 - - - ● 5) ● 5) - 59G (1)

Three-phase undervoltage protection, instance 1 - ● 4) ● 4) - - ● 4) 27 (2)

Three-phase undervoltage protection, instance 2 - - - ● 5) ● 5) ● 5) 27 (1)

Page 34: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

28 RET615 ANSIApplication Manual

Three-phase overvoltage protection, instance 1 - ● 4) ● 4) - - ● 4) 59 (2)

Three-phase overvoltage protection, instance 2 - - - ● 5) ● 5) ● 5) 59 (1)

Negative-sequence overvoltage protection, instance 1 - ● 4) ● 4) - - ● 4) 47 (2)

Negative-sequence overvoltage protection, instance 2 - - - ● 5) ● 5) ● 5) 47 (1)

Frequency protection, instance 1 - ● 4) ● 4) - - ● 4) 81-1 (2)

Frequency protection, instance 2 - ● 4) ● 4) - - ● 4) 81-2 (2)

Frequency protection, instance 3 - - - ● 5) ● 5) - 81-1 (1)

Frequency protection, instance 4 - - - ● 5) ● 5) - 81-2 (1)

Voltage per hertz protection, instance 1 - ● 4) ● 4) - - - 24-1 (2)

Voltage per hertz protection, instance 2 - ● 4) ● 4) - - - 24-2 (2)

Voltage per hertz protection, instance 3 - - - ● 5) ● 5) ● 5) 24-1 (1)

Voltage per hertz protection, instance 4 - - - ● 5) ● 5) ● 5) 24-2 (1)

Three-phase thermal overload protection for power transformers, two time constants

● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 49T (1)

Restrained (Low Stage) and unrestrained (High Stage) differential protection for 2W –transformers

● ● ● ● ● ● 87T

Numerical restrained (low stage) low impedance restricted ground-fault protection

● 4) ● 4) ● 4) ● 4) ● 4) ● 4) 87LOZREF (2)

Circuit breaker failure protection, instance 1 ● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 50BF (1)

Circuit breaker failure protection, instance 2 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) 50BF (2)

Master trip, instance 1 ● ● ● ● ● ● 86/94-1

Master trip, instance 2 ● ● ● ● ● ● 86/94-2

Arc protection, instance 1 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) AFD-1 (2)

Arc protection, instance 2 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) AFD-2 (2)

Arc protection, instance 3 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) AFD-3 (2)

Multi-purpose protection, instance 1 6) - - ● - ● - MAP-1

Multi-purpose protection, instance 2 6) - - ● - ● - MAP-2

Multi-purpose protection, instance 3 6) - - ● - ● - MAP-3

Load shedding and restoration, instance 1 - ● 4) ● 4) - - ● 4) 81LSH-1 (2)

Load shedding and restoration, instance 2 - ● 4) ● 4) - - ● 4) 81LSH-2 (2)

Load shedding and restoration, instance 3 - - - ● 5) ● 5) - 81LSH-1 (1)

Load shedding and restoration, instance 4 - - - ● 5) ● 5) - 81LSH-2 (1)

Loss of phase, instance 1 ● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 37 (1)

Control

Circuit-breaker control, instance 1 ● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 52 (1)

Software ConfigurationStd

config.A

Std config.B/C

Std config.B/C

Std config.

DANSI

Function AA BA CA BB CB DA RET

Page 35: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 29Application Manual

Circuit-breaker control, instance 2 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) 52 (2)

Tap changer position indication ● ● ● ● ● ● 84T

Condition Monitoring

Circuit-breaker condition monitoring, instance 1 ● 5) ● 5) ● 5) ● 5) ● 5) ● 5) 52CM (1)

Circuit-breaker condition monitoring, instance 2 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) 52CM (2)

Trip circuit supervision, instance 1 ● ● ● ● ● ● TCM-1

Trip circuit supervision, instance 2 ● ● ● ● ● ● TCM-2

Advanced current circuit supervision for transformers ● ● ● ● ● ● MCS 3I, I2

Fuse failure supervision, instance 1 - - - ● 5) ● 5) ● 5) 60 (1)

Fuse failure supervision, instance 2 - ● 4) ● 4) - - ● 4) 60 (2)

Measurement

Three-phase current measurement, instance 1 ● 5) ● 5) ● 5) ● 5) ● 5) ● 5) IA, IB, IC (1)

Three-phase current measurement, instance 2 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) IA, IB, IC (2)

Sequence current measurement, instance 1 ● 5) ● 5) ● 5) ● 5) ● 5) ● 5) I1, I2, I0 (1)

Sequence current measurement, instance 2 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) I1, I2, I0 (2)

Residual current measurement, instance 1 ● 4) ● 4) ● 4) ● 4) ● 4) ● 4) IG

Three-phase voltage measurement, instance 1 - - - ● 5) ● 5) ● 5) VA, VB, VC (1)

Three-phase voltage measurement, instance 2 - ● 4) ● 4) - - ● 4) VA, VB, VC (2)

Residual voltage measurement, instance 1 - - - ● 5) ● 5) - VG

Residual voltage measurement, instance 2 - ● 4) ● 4) - - - VG

Sequence voltage measurement, instance 1 - - - ● 5) ● 5) ● 5) V1, V2, V0 (1)

Sequence voltage measurement, instance 2 - ● 4) ● 4) - - ● 4) V1, V2, V0 (2)

Single-phase power and energy measurement, instance 1 - - - ● 5) ● 5) - SP, SE (1)

Single-phase power and energy measurement, instance 2 - ● 4) ● 4) - - ● 4) SP, SE (2)

Three-phase power and energy measurement, instance 1 - - - ● 5) ● 5) - P, E (1)

Three-phase power and energy measurement, instance 2 - ● 4) ● 4) - - ● 4) P, E (2)

2 RTD +1 mA - - ● - ● -

Frequency measurement, instance 1 - - - ● 5) ● 5) - f

Frequency measurement, instance 2 - ● 4) ● 4) - - ● 4) f

Other Functions

Minimum pulse timer (2 pcs), instance 1 ● ● ● ● ● ● TP-1

Minimum pulse timer (2 pcs), instance 2 ● ● ● ● ● ● TP-2

Minimum pulse timer (2 pcs), instance 3 ● ● ● ● ● ● TP-3

Software ConfigurationStd

config.A

Std config.B/C

Std config.B/C

Std config.

DANSI

Function AA BA CA BB CB DA RET

Page 36: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

30 RET615 ANSIApplication Manual

3.3 Standard Configuration for Order Code Functional Application AA

3.3.1 ApplicationsThe standard configuration is mainly intended for two-winding transformers and two breakers with phase differential, restricted ground fault and overcurrent protection. The standard configuration is mainly intended for protection of the power transformer between current transformers.

The IED with this standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enable this configuration to be further adapted to different primary power system layouts and the related functionality needs by modifying the internal functionality using PCM600.

Minimum pulse timer (2 pcs), instance 4 ● ● ● ● ● ● TP-4

Pulse timer (8 pcs), instance 1 ● ● ● ● ● ● PT-1

Pulse timer (8 pcs), instance 2 ● ● ● ● ● ● PT-2

Time delay off (8 pcs), instance 1 ● ● ● ● ● ● TOF-1

Time delay off (8 pcs), instance 2 ● ● ● ● ● ● TOF-2

Time delay on (8 pcs), instance 1 ● ● ● ● ● ● TON -1

Time delay on (8 pcs), instance 2 ● ● ● ● ● ● TON -2

Set reset (8 pcs), instance 1 ● ● ● ● ● ● SR-1

Set reset (8 pcs), instance 2 ● ● ● ● ● ● SR-2

Move (8 pcs), instance 1 ● ● ● ● ● ● MV-1

Move (8 pcs), instance 2 ● ● ● ● ● ● MV-2

Logging Functions

Disturbance recorder ● ● ● ● ● ● DFR

Fault recorder ● ● ● ● ● ● FR

Sequence event recorder ● ● ● ● ● ● SER

1) Io selectable by parameter, I2 as default2) Vo calculated and negative sequence voltage selectable by parameter, V2 as default3) Vo calculated is always used4) The function block is to be used on the low voltage side in the application5) The function block is to be used on the high voltage side in the application6) Multi-purpose protection is used for, for example, RTD/mA

Software ConfigurationStd

config.A

Std config.B/C

Std config.B/C

Std config.

DANSI

Function AA BA CA BB CB DA RET

Page 37: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 31Application Manual

3.3.2 FunctionsTable 9: Functions included in the RET615 standard configuration

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA01

AAProtection

Three-phase non-directional overcurrent protection, low stage, instance 1

PHLPTOC1 51P (1) 3I> (1) ●

Three-phase non-directional overcurrent protection, low stage, instance 2

PHLPTOC2 51P (2) 3I> (2) ●

Three-phase non-directional overcurrent protection, high stage, instance 1

PHHPTOC1 50P-1 (1) 3I>> (1) ●

Three-phase non-directional overcurrent protection, high stage, instance 2

PHHPTOC2 50P-1 (2) 3I>> (2) ●

Three-phase non-directional overcurrent protection, high stage, instance 3

PHHPTOC3 50P-2 (1) 3I>> (3) ●

Three-phase non-directional overcurrent protection, high stage, instance 4

PHHPTOC4 50P-2 (2) 3I>> (4) ●

Non-directional ground-fault protection, low stage, instance 1

EFLPTOC1 51G Io> (1) ●

Non-directional ground-fault protection, low stage, instance 2

EFLPTOC2 51N (1) Io> (2) ●

Non-directional ground-fault protection, low stage, instance 3

EFLPTOC3 51N (2) Io> (3) ●

Non-directional ground-fault protection, high stage, instance 1

EFHPTOC1 50G-1 Io>> (1) ●

Non-directional ground-fault protection, high stage, instance 2

EFHPTOC2 50G-2 Io>> (2) ●

Non-directional ground-fault protection, high stage, instance 3

EFHPTOC3 50N-1 (1) Io>> (3) ●

Non-directional ground-fault protection, high stage, instance 4

EFHPTOC4 50N-1 (2) Io>> (4) ●

Non-directional ground-fault protection, high stage, instance 5

EFHPTOC5 50N-2 (1) Io>> (5) ●

Non-directional ground-fault protection, high stage, instance 6

EFHPTOC6 50N-2 (2) Io>> (6) ●

Negative-sequence overcurrent protection, instance 1

NSPTOC1 46 (1) I2> (1) ●

Negative-sequence overcurrent protection, instance 2

NSPTOC2 46 (2) I2> (2) ●

Three-phase thermal overload protection for power transformers, two time constants

T2PTTR1 49T (1) 3Ith>T ●

Restrained (Low Stage) and unrestrained (High Stage) differential protection for 2W –transformers

TR2PTDF1 87T 3dI>T ●

Numerical restrained (low stage) low impedance restricted ground-fault protection

LREFPNDF1 87LOZREF (2) dIoLo> ●

Circuit breaker failure protection, instance 1 CCBRBRF1 50BF (1) 3I>/Io>BF (1) ●

Circuit breaker failure protection, instance 2 CCBRBRF2 50BF (2) 3I>/Io>BF (2) ●

Master trip, instance 1 TRPPTRC1 86/94-1 Master Trip (1) ●

Master trip, instance 2 TRPPTRC2 86/94-2 Master Trip (2) ●

Page 38: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

32 RET615 ANSIApplication Manual

Arc protection, instance 1 ARCSARC1 AFD-1 (2) ARC (1) ●

Arc protection, instance 2 ARCSARC2 AFD-2 (2) ARC (2) ●

Arc protection, instance 3 ARCSARC3 AFD-3 (2) ARC (3) ●

Loss of phase, instance 1 PHPTUC1 37 (1) 3I< (1) ●

Control

Circuit-breaker control, instance 1 CBXCBR1 52 (1) I <-> O CB (1) ●

Circuit-breaker control, instance 2 CBXCBR2 52 (2) I <-> O CB (2) ●

Tap changer position indication TPOSSLTC1 84T TPOSM ●

Condition Monitoring

Circuit-breaker condition monitoring, instance 1

SSCBR1 52CM (1) CBCM (1) ●

Circuit-breaker condition monitoring, instance 2

SSCBR2 52CM (2) CBCM (2) ●

Trip circuit supervision, instance 1 TCSSCBR1 TCM-1 TCS (1) ●

Trip circuit supervision, instance 2 TCSSCBR2 TCM-2 TCS (2) ●

Advanced current circuit supervision for transformers

CTSRCTF1 MCS 3I, I2 MCS 3I, I2 ●

Measurements

Three-phase current measurement, instance 1

CMMXU1 IA, IB, IC (1) 3I ●

Three-phase current measurement, instance 2

CMMXU2 IA, IB, IC (2) 3I(B) ●

Sequence current measurement, instance 1 CSMSQI1 I1, I2, I0 (1) I1, I2, I0 ●

Sequence current measurement, instance 2 CSMSQI2 I1, I2, I0 (2) I1, I2, I0(B) ●

Residual current measurement, instance 1 RESCMMXU1 IG Io ●

Other Functions

Minimum pulse timer (2 pcs), instance 1 TPGAPC1 TP-1 TP (1) ●

Minimum pulse timer (2 pcs), instance 2 TPGAPC2 TP-2 TP (2) ●

Minimum pulse timer (2 pcs), instance 3 TPGAPC3 TP-3 TP (3) ●

Minimum pulse timer (2 pcs), instance 4 TPGAPC4 TP-4 TP (4) ●

Pulse timer (8 pcs), instance 1 PTGAPC1 PT-1 PT (1) ●

Pulse timer (8 pcs), instance 2 PTGAPC2 PT-2 PT (2) ●

Time delay off (8 pcs), instance 1 TOFGAPC1 TOF-1 TOF (1) ●

Time delay off (8 pcs), instance 2 TOFGAPC2 TOF-2 TOF (2) ●

Time delay on (8 pcs), instance 1 TONGAPC1 TON -1 TON (1) ●

Time delay on (8 pcs), instance 2 TONGAPC2 TON -2 TON (2) ●

Set reset (8 pcs), instance 1 SRGAPC1 SR-1 SR (1) ●

Set reset (8 pcs), instance 2 SRGAPC2 SR-2 SR (2) ●

Move (8 pcs), instance 1 MVGAPC1 MV-1 MV (1) ●

Move (8 pcs), instance 2 MVGAPC2 MV-2 MV (2) ●

Logging Functions

Disturbance recorder RDRE1 DFR - ●

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA01

AA

Page 39: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 33Application Manual

Fault recorder FLMSTA1 FR - ●

Sequence event recorder SER SER - ●

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA01

AA

Page 40: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

34 RET615 ANSIApplication Manual

3.3.3 Default Input/Output (I/O) assignmentsTable 10: Analog input connections for CTs

Table 11: Binary input connections

Table 12: Binary output connections

Analog input Default usage Connector pinsX120 – IA(2) Current input for phase IA, low voltage side X120 – 1, 2

X120 - IB(2) Current input for phase IB, low voltage side X120 – 3,4

X120 - IC(2) Current input for phase IC, low voltage side X120 – 5,6

X120 - IA(1) Current input for phase IA, high voltage side X120 – 7,8

X120 - IB(1) Current input for phase IB, high voltage side X120 – 9,10

X120 - IC(1) Current input for phase IC, high voltage side X120 – 11,12

X120 - IG(2) Ground current input IG, low voltage side X120 – 13,14

Binary input Default usage Connector pinsX110-BI1 X110-1, 2

X110-BI2 X110-3, 4

X110-BI3 X110-5, 6

X110-BI4 X110-7, 6

X110-BI5 Circuit breaker (2) closed position X110-8, 9

X110-BI6 Circuit breaker (2) open position X110-10,9

X110-BI7 Circuit breaker (1) closed position X110-11, 12

X110-BI8 Circuit breaker (1) open position X110-13, 12

Binary output Default usage Connector pinsX100-PO1 Close circuit breaker (1) X100 – 6,7

X100-PO2 Close circuit breaker (2) X100 – 8,9

X100-SO1 Breaker failure backup trip to upstream breaker X100 – 11/12, 10

X100-SO2 X100 – 13, 14

X100-PO3 Open circuit breaker / Master Trip -1 X100 – 15,19

X100-PO4 Open circuit breaker / Master Trip -2 X100 – 20,24

X110-SO1* X110 – 15/16, 14

X110-SO2* X110 – 18/19, 17

X110-SO3* X110 – 21/22, 20

X110-SO4* X110 – 23,24

*Not available if IED has been ordered with High speed binary output (HSO) card

Page 41: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 35Application Manual

Table 13: High speed binary output connections*

Table 14: Default LED assignment and label names

Binary output Default usage Connector pinsX110-HSO1 Trip from ARC-1 protection X110 – 15,16

X110-HSO2 Trip from ARC-2 protection X110 – 19,20

X110-HSO3 Trip from ARC-3 protection X110 – 23,24

*Available only if IED has been ordered with High speed binary output (HSO) card

LED LED labelLED 1 Phase A

LED 2 Phase B

LED 3 Phase C

LED 4 Neutral / Ground

LED 5 Time

LED 6 Instantaneous

LED 7 Differential / REF

LED 8 Breaker 1 Failure/Alarm

LED 9 Breaker 2 Failure/Alarm

LED 10 Overload Alarm/Trip

LED 11 Arc Flash Detection

Page 42: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

36 RET615 ANSIApplication Manual

3.3.4 Typical connection diagrams

Page 43: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 37Application Manual

3.3.5 Functional diagramsThe functional diagrams describe the default input, output, RTD inputs, alarm LED and function-to-function connections. The default connections can be viewed with and changed with PCM 600 according to the application requirements, if necessary.

The analog channels, measurements from CTs and PTs, have fixed connections to the different function blocks inside the IED’s standard configuration.

The analog channels are assigned to different functions as shown in functional diagrams. The function and analog signal marked with (1) represents the function and analog signals (three phase currents/voltages) on the high-voltage side of the transformer and (2) represents the function and analog signals (three phase currents/voltage) on the low-voltage side of the transformer. The signal marked with IG represents the ground current measured between the start point of the transformer and grounding.

RET615 offers six different settings group which the user can set based on individual needs. Each group can then, be activated/ deactivated by using the setting group settings available in RET615.

3.3.5.1 Functional diagrams for protectionThe functional diagrams for protection describe the IED’s protection functionality in detail and according to the factory set default connections.

Three stages for both high-voltage and low-voltage side as a total of six, three-phase overcurrent protection (51P(1), 50P-1(1), 50P-2(1), 51P(2), 50P-1(2), 50P-2(2)) stages are provided for overcurrent and short-circuit protection.

The operation of these functions is not blocked as default by any functionality and so setting should be set such as to avoid unnecessary false trip or alarm.

The operation of 51P(1) and 51P(2) is connected to alarm LED 5, and 50P-1(1), 50P-2(1), 50P-1(2) and 50P-2(2) is connected to alarm LED 6.

Figure 6: Three phase overcurrent protection – HV side

Page 44: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

38 RET615 ANSIApplication Manual

Figure 7: Three phase overcurrent protection – LV side

Alarm LEDs 1, 2 and 3 are configured so as to indicate which phase has resulted into tripping of overcurrent protection. Overcurrent faults in Phase A, B and C is mapped to Alarm LEDs 1, 2 and 3 respectively.

Three stages for both high-voltage and low-voltage side as a total of six, ground fault (51N(1), 50N-1(1), 50N-2(1), 51N(2), 50N-1(2), 50N-2(2)) stages are provided for ground fault protection.

Figure 8: ground fault protection – HV side

Page 45: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 39Application Manual

Figure 9: Ground fault protection – LV side

Configuration also includes three stages of ground fault protection (51G, 50G-1 and 50G-2).

The operation of these functions is not blocked as default by any functionality. The operation of 51N(1), 51N(2) and 51G is connected to alarm LED 4 and 5, and 50N-1(1), 50N-2(1), 50N-1(2), 50N-2(2), 50G-1 and 50G-2 is connected to alarm LED 4 and 6.

Figure 10: Non-directional ground fault protection

One stage of negative-sequence overcurrent protection (46(1) and 46(2)) for both high-voltage and low-voltage sides is provided for protecting transformer against thermal stress and damage. The operation of 46(1) and 46(2) is not blocked as default by any functionality.

Page 46: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

40 RET615 ANSIApplication Manual

Figure 11: Negative sequence protection –HV and LV side

Configuration also includes high side as well as low side pickup alarm, the pickup outputs from respective 50P-1, 50P-2, 51P, 51N, 50N-1, 50N-2, and 46 are connected together to have a combined overcurrent high voltage side and low voltage side pickup alarm which is connected to disturbance recorder as default.

Figure 12: Overcurrent pickup alarms – HV side

Figure 13: Overcurrent pickup alarms – LV side

Page 47: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 41Application Manual

The configuration includes restricted low-impedance ground-fault (87LOZREF(2)) protection function for low-voltage side of two-winding power transformers. The numerical differential current stage operates exclusively on ground faults occurring in the protected area, that is, in the area between the phase and neutral current transformers. An ground fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and ground.

The operation of 87LOZREF(2) is not blocked as default by any functionality. The operation of 87LOZREF(2) is connected to alarm LED 7.

Figure 14: Restricted low impedance ground fault protection – LV side

The restrained (Low Stage) and unrestrained (High Stage) differential protection for two winding transformers (87T) provides protection of power transformer unit including, for example, winding short-circuit and inter-turn faults. The IED compares the phase currents on both sides of the transformer. If the differential current of the phase currents in one of the phases exceed the setting of the restrained (low stage) operation characteristic or the instantaneous protection stage of the function, the function provides a trip signal.

Figure 15: Transformer differential protection

For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in 87T.

The operation of 87LOZREF(2) and 87T is not blocked as default by any functionality. The operation of these protection functions is connected to alarm LED 7.

The thermal overload protection function (49T(1)) on HV side detects short and long term overloads under varying load conditions.

The alarm and operation of thermal overload protection function is connected to alarm LED 10.

Page 48: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

42 RET615 ANSIApplication Manual

Figure 16: Transformer thermal overload protection – HV side

Loss of load protection (37(1)) is provided on HV side of the transformer for detecting sudden loss of load on the transformer.

The operation of 37(1) is not blocked as default by any functionality.

Figure 17: Loss of load protection - HV side

The circuit-breaker failure protection (50BF(1) and 50BF(2)) for both high-voltage and low-voltage side is initiated via the pickup input by a number of different protection functions in the IED. 50BF(1) and 50BF(2) offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents.

50BF(1) and 50BF(2) has two operating outputs: TRRET and TRBU. The TRBU output from both the high voltage and low-voltage side is used to give a backup trip to the circuit breaker feeding upstream. For this purpose, the TRBU output signal from both the function is connected to the output SO1 (X100: 10-11).

The TRBU output from 50BF(1) and 50BF(2) is connected to alarm LED 8 and 9 respectively.

By default 49T(1) is not configured to trip the circuit breaker.

By default 37(1) is not configured in the configuration.

Page 49: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 43Application Manual

Figure 18: Circuit breaker failure protection – HV side

Figure 19: Circuit breaker failure protection – LV side

Three arc protection (AFD-1(2), AFD-2(2) and AFD-3(2)) stages are included as an optional function on low-voltage side of the transformer. The arc protection offers individual function blocks for three ARC sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check.

The TRRET operate output can be used for retripping its own circuit breaker through the Master Trip again. However this is not connected in present configuration.

Page 50: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

44 RET615 ANSIApplication Manual

Figure 20: Arc protection – LV sideTrip signal from AFD-1(2) is connected to master trip on high voltage side, available at PO3 (X100: 15-19). Whereas the trip signal from AFD-2(2) is connected to master trip on low voltage side, available at PO4 (X100:20-24).

If the IED has been ordered with high speed binary outputs, then trip signal from AFD-1(2), AFD-2(2) and AFD-3(2) are also connected directly to high speed output HS01(X110:15-16), HS02 (X110:19-20) and HS03(X110:23-24) respectively.

The detection of arc fault is connected to alarm LED 11.

Two master trip logics (86/94-1 and 86/94-2) are provided as a trip command collector. 86/94-1 collects the trip signals from 51P(1), 50P-1(1), 50P-2(1), 46(1), 50N-1(1), 50N-2(1), 50G-1, 50G-2, 51N(1), 51G, 87T, 87LOZREF(2), and AFD-1(2) protection functions and is connected to provide high voltage side trip to binary output PO3 (X100:16-19).

Open control commands to the high voltage circuit breaker from the local or remote is also connected directly to the output PO3 (X100:16-19) from high voltage circuit breaker control (52(1)) function block.

86/94-2 collects the trip signals from 51P(2), 50P-1(2), 50P-2(2), 46(2), 50N-1(2), 50N-2(2), 50G-1, 50G-2, 51N(2), 51G, 87T, 87LOZREF(2), and AFD-2(2) protection functions and is connected to provide low voltage side trip to binary output contact PO4 (X100:20-24).

Open control commands to the low voltage circuit breaker from the local or remote is also connected directly to the output PO4 (X100:20-24) from low voltage circuit breaker control (52(2)) function block.

AFD-3(2) is not connected to any binary outputs for IED ordered without high speed binary outputs.

Page 51: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 45Application Manual

Figure 21: Master trip logic – HV side

Figure 22: Master trip logic – LV side

86/94-1 and 86/94-2 provides the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

3.3.5.2 Functional diagrams for control functions The functional diagrams for control describe the IED’s control functionality in detail and according to the factory set default connections.

The high voltage and low voltage side circuit breaker closing is enabled when the respective ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and ground switch position status and the status of the Master Trip logics, gas pressure alarm and circuit-breaker spring charging. With the present configuration, the activation of

Page 52: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

46 RET615 ANSIApplication Manual

respective ENA_CLOSE input is configured using only Master Trip logic 86/94-1(1) and 86/94-2(2) i.e. the circuit breaker cannot be closed in case master trip is active.

When all conditions of the high voltage circuit breaker closing are fulfilled, the EXE_CL output of the 52(1) and PO1 output (X100:6-7) is closed if closing command is given. Similarly when all the conditions of the low voltage circuit breaker closing are fulfilled, the EXE_CL output of the 52(2) and PO2 output (X100:8-9) is closed if closing command is given.

The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position.

Figure 23: Circuit breaker control – HV side

Figure 24: Circuit breaker control – LV side

Configuration also includes tap changer position indicator (84T), however by default it is not configured.

If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block 52 with PCM600, the function assumes that the breaker close commands are allowed continuously.

Page 53: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 47Application Manual

Figure 25: Tap changer position indicator

3.3.5.3 Functional diagrams for condition monitoring The functional diagrams for condition monitoring describe the IED’s condition monitoring functionality in detail and according to the factory set default connections.

Two trip circuit monitoring (TCM-1 and TCM-2) stages are provided to supervise the trip circuit of the high voltage and low voltage circuit breaker connected at PO3 (X100:15-19) and PO4 (X100:20-24) respectively.

Figure 26: Trip circuit monitoring HV and LV- side

The TCM-1 and TCM-2 functions are blocked by respective 86/94-1(1) and, 86/94-2(2) function block and the respective circuit-breaker open position signal.

The supervision alarm from TCM-1 and TCM-2 is connected to alarm LED 8 and 9 respectively

A failure in current measuring circuits is detected by current circuit supervision function (MCS 3I, I2). When a failure is detected, function activates and can be used to block protection functions for example 87T, thus avoiding mal-operation.

By default it is expected that there is no external resistor in the circuit breaker tripping/closing coil circuit connected parallel with circuit breaker normally open/closed auxiliary contact.

Page 54: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

48 RET615 ANSIApplication Manual

Figure 27: Current circuit supervision

Two circuit breaker condition monitoring function (52CM(1) and 52CM(2)) one each is configured to supervise high voltage side and low voltage side circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision alarms.

Figure 28: Circuit breaker condition monitoring HV side

Figure 29: Circuit breaker condition monitoring LV side

The supervision alarm from 52CM(1) and 52CM(2) is connected to alarm LED 8 and 9 respectively.

By default the FAIL output from MCS 3I, I2 function is only connected to disturbance recorder.

By default only POSOPEN and POSCLOSE information is available to 52CM(1) and 52CM(2).

Page 55: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 49Application Manual

3.3.5.4 Functional diagrams for MeasurementsThe functional diagrams for measurement describe the IED’s measurement functionality in detail and according to the factory set default connections

The phase current inputs from high voltage and low voltage side are connected to the IED and are measured by high voltage and low voltage side three-phase current measurement (IA, IB, IC(1) and IA,IB,IC(2)) function block respectively. The current input is connected to the X120 card in the back panel. Similarly the sequence current component for both high voltage and low voltage side is measured by sequence current measurement (I1, I2, I0(1) and I1,I2,I0(2)) function block respectively. The residual current is measured by residual current measurement (IG) function block.

The measurements can be seen from the LHMI and is available using the measurement option in the menu selection. Based on the settings, “IA, IB, IC(1)”, “IA,IB, IC(2)”and IG function block can generate low alarm/warning, high alarm/warning signals for the measured current values.

Figure 30: Measurements

3.3.5.5 Functional diagrams for other functions Configuration also includes other miscellaneous basic functions which are not configured, but can be used for creating general purpose logics. These functions include:

• Four instance of Minimum Pulse Timer TP-1, TP-2, TP-3 and TP-4,

• Two instance of Pulse Timer PT-1 and PT-2,

• Two instance of Time delay off TOF-1 and TOF-2,

• Two instance of Time delay on TON-1 and TON-2,

• Two instance of Set reset logic SR-1 and SR-2 and

• Two instance of Move logic MV-1 and MV-2

3.3.5.6 Functional diagrams for logging functions The functional diagrams for logging describe the IED’s default disturbance recorder connections.

The disturbance recorder DFR consists of 64 channels. However as default few channel are connected to trigger the digital fault recorder are as shown in Figure 31. More

Page 56: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

50 RET615 ANSIApplication Manual

connection can be made as per individual need. Also when disturbance recorder is trigger the analog values available at the analog inputs are recorded by fault recorder FR.

Figure 31: 64 channel Disturbance and fault recorder

3.3.5.7 Functional diagrams for I/O and Alarm LEDs The functional diagrams for I/O and Alarm LEDs describe the IED’s default input/output and alarm LEDs connections.

The default binary I/O connected in the configuration and Alarm LEDs are indicated in Figure 32 to Figure 34.

Page 57: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 51Application Manual

Figure 32: Binary inputs

Figure 33: Binary outputs

Page 58: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

52 RET615 ANSIApplication Manual

High speed binary outputs (HSO) are available only if IED with High speed binary card has been ordered.

Page 59: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 53Application Manual

Figure 34: Alarm LED

3.4 Standard Configuration for Order Code Functional Application BA and CA

3.4.1 ApplicationsThe standard configuration is mainly intended for two-winding transformers and two breakers. This configuration includes phase differential, restricted ground fault, over excitation, current, voltage, frequency protection and power and energy metering. The winding that supports the directional overcurrent, voltage and frequency protection and power and energy metering is an ordering option. The IED with this standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enable this configuration to be further adapted to different primary power system layouts and the related functionality needs by modifying the internal functionality using PCM600.

Page 60: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

54 RET615 ANSIApplication Manual

3.4.2 FunctionsTable 15: Functions included in the RET615 standard configuration

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA02

BA CAProtection

Three-phase non-directional overcurrent protection, low stage, instance 1

PHLPTOC1 51P (1) 3I> (1) ● ●

Three-phase non-directional overcurrent protection, low stage, instance 2

PHLPTOC2 51P (2) 3I> (2) ● ●

Three-phase non-directional overcurrent protection, high stage, instance 1

PHHPTOC1 50P-1 (1) 3I>> (1) ● ●

Three-phase non-directional overcurrent protection, high stage, instance 2

PHHPTOC2 50P-1 (2) 3I>> (2) ● ●

Three-phase non-directional overcurrent protection, high stage, instance 3

PHHPTOC3 50P-2 (1) 3I>> (3) ● ●

Three-phase non-directional overcurrent protection, high stage, instance 4

PHHPTOC4 50P-2 (2) 3I>> (4) ● ●

Non-directional ground-fault protection, low stage, instance 1

EFLPTOC1 51G Io> (1) ● ●

Three-phase directional overcurrent protection, low stage, instance 2

DPHLPDOC1 67/51P (2) 3I> -> (1) ● ●

Non-directional ground-fault protection, low stage, instance 2

EFLPTOC2 51N (1) Io> (2) ● ●

Non-directional ground-fault protection, low stage, instance 3

EFLPTOC3 51N (2) Io> (3) ● ●

Non-directional ground-fault protection, high stage, instance 1

EFHPTOC1 50G-1 Io>> (1) ● ●

Non-directional ground-fault protection, high stage, instance 2

EFHPTOC2 50G-2 Io>> (2) ● ●

Non-directional ground-fault protection, high stage, instance 3

EFHPTOC3 50N-1 (1) Io>> (3) ● ●

Non-directional ground-fault protection, high stage, instance 4

EFHPTOC4 50N-1 (2) Io>> (4) ● ●

Non-directional ground-fault protection, high stage, instance 5

EFHPTOC5 50N-2 (1) Io>> (5) ● ●

Non-directional ground-fault protection, high stage, instance 6

EFHPTOC6 50N-2 (2) Io>> (6) ● ●

Directional ground-fault protection, low stage, instance 2

DEFLPDEF1 67/51N (2) Io> -> (1) ●1)

●1)

Negative-sequence overcurrent protection, instance 1

NSPTOC1 46 (1) I2> (1) ● ●

Negative-sequence overcurrent protection, instance 2

NSPTOC2 46 (2) I2> (2) ● ●

Residual overvoltage protection, instance 1

ROVPTOV1 59N (2) Uo> (1) ● ●

Residual overvoltage protection, instance 2

ROVPTOV2 59G (2) Uo> (2) ● ●

Three-phase undervoltage protection, instance 1

PHPTUV1 27 (2) 3U< (1) ● ●

Three-phase overvoltage protection, instance 1

PHPTOV1 59 (2) 3U> (1) ● ●

Page 61: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 55Application Manual

Negative-sequence overvoltage protection, instance 1

NSPTOV1 47 (2) U2> (1) ● ●

Frequency protection, instance 1 FRPFRQ1 81-1 (2) f>/f<,df/dt (1) ● ●

Frequency protection, instance 2 FRPFRQ2 81-2 (2) f>/f<,df/dt (2) ● ●

Voltage per hertz protection, instance 1 OEPVPH1 24-1 (2) U/f> (1) ● ●

Voltage per hertz protection, instance 2 OEPVPH2 24-2 (2) U/f> (2) ● ●

Three-phase thermal overload protection for power transformers, two time constants

T2PTTR1 49T (1) 3Ith>T ● ●

Restrained (Low Stage) and unrestrained (High Stage) differential protection for 2W –transformers

TR2PTDF1 87T 3dI>T ● ●

Numerical restrained (low stage) low impedance restricted ground-fault protection

LREFPNDF1 87LOZREF (2) dIoLo> ● ●

Circuit breaker failure protection, instance 1

CCBRBRF1 50BF (1) 3I>/Io>BF (1) ● ●

Circuit breaker failure protection, instance 2

CCBRBRF2 50BF (2) 3I>/Io>BF (2) ● ●

Master trip, instance 1 TRPPTRC1 86/94-1 Master Trip (1) ● ●

Master trip, instance 2 TRPPTRC2 86/94-2 Master Trip (2) ● ●

Arc protection, instance 1 ARCSARC1 AFD-1 (2) ARC (1) ● ●

Arc protection, instance 2 ARCSARC2 AFD-2 (2) ARC (2) ● ●

Arc protection, instance 3 ARCSARC3 AFD-3 (2) ARC (3) ● ●

Multi-purpose protection, instance 1 MAPGAPC1 MAP-1 MAP (1) - ●2)

Multi-purpose protection, instance 2 MAPGAPC2 MAP-2 MAP (2) - ●2)

Multi-purpose protection, instance 3 MAPGAPC3 MAP-3 MAP (3) - ●2)

Load shedding and restoration, instance 1

LSHDPFRQ1 81LSH-1 (2) UFLS/R (1) ● ●

Load shedding and restoration, instance 2

LSHDPFRQ2 81LSH-2 (2) UFLS/R (2) ● ●

Loss of phase, instance 1 PHPTUC1 37 (1) 3I< (1) ● ●

Control

Circuit-breaker control, instance 1 CBXCBR1 52 (1) I <-> O CB (1) ● ●

Circuit-breaker control, instance 2 CBXCBR2 52 (2) I <-> O CB (2) ● ●

Tap changer position indication TPOSSLTC1 84T TPOSM ● ●

Condition Monitoring

Circuit-breaker condition monitoring, instance 1

SSCBR1 52CM (1) CBCM (1) ● ●

Circuit-breaker condition monitoring, instance 2

SSCBR2 52CM (2) CBCM (2) ● ●

Trip circuit supervision, instance 1 TCSSCBR1 TCM-1 TCS (1) ● ●

Trip circuit supervision, instance 2 TCSSCBR2 TCM-2 TCS (2) ● ●

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA02

BA CA

Page 62: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

56 RET615 ANSIApplication Manual

Advanced current circuit supervision for transformers

CTSRCTF1 MCS 3I, I2 MCS 3I, I2 ● ●

Fuse failure supervision, instance 2 SEQRFUF2 60 (2) FUSEF (2) ● ●

Measurements

Three-phase current measurement, instance 1

CMMXU1 IA, IB, IC (1) 3I ● ●

Three-phase current measurement, instance 2

CMMXU2 IA, IB, IC (2) 3I(B) ● ●

Sequence current measurement, instance 1

CSMSQI1 I1, I2, I0 (1) I1, I2, I0 ● ●

Sequence current measurement, instance 2

CSMSQI2 I1, I2, I0 (2) I1, I2, I0(B) ● ●

Residual current measurement, instance 1

RESCMMXU1 IG Io ● ●

Three-phase voltage measurement, instance 2

VMMXU2 VA, VB, VC (2) 3U(B) ● ●

Residual voltage measurement, instance 2

RESVMMXU2 VG Uo ● ●

Sequence voltage measurement, instance 2

VSMSQI2 V1, V2, V0 (2) U1, U2, U0(B) ● ●

Single-phase power and energy measurement, instance 2

SPEMMXU2 SP, SE (2) SP, SE(B) ● ●

Three-phase power and energy measurement, instance 2

PEMMXU2 P, E (2) P, E(B) ● ●

2 RTD +1 mA XARGGIO130 X130 (AIM+RTD)

- ●

Frequency measurement, instance 2 FMMXU2 f f ● ●

Other Functions

Minimum pulse timer (2 pcs), instance 1 TPGAPC1 TP-1 TP (1) ● ●

Minimum pulse timer (2 pcs), instance 2 TPGAPC2 TP-2 TP (2) ● ●

Minimum pulse timer (2 pcs), instance 3 TPGAPC3 TP-3 TP (3) ● ●

Minimum pulse timer (2 pcs), instance 4 TPGAPC4 TP-4 TP (4) ● ●

Pulse timer (8 pcs), instance 1 PTGAPC1 PT-1 PT (1) ● ●

Pulse timer (8 pcs), instance 2 PTGAPC2 PT-2 PT (2) ● ●

Time delay off (8 pcs), instance 1 TOFGAPC1 TOF-1 TOF (1) ● ●

Time delay off (8 pcs), instance 2 TOFGAPC2 TOF-2 TOF (2) ● ●

Time delay on (8 pcs), instance 1 TONGAPC1 TON -1 TON (1) ● ●

Time delay on (8 pcs), instance 2 TONGAPC2 TON -2 TON (2) ● ●

Set reset (8 pcs), instance 1 SRGAPC1 SR-1 SR (1) ● ●

Set reset (8 pcs), instance 2 SRGAPC2 SR-2 SR (2) ● ●

Move (8 pcs), instance 1 MVGAPC1 MV-1 MV (1) ● ●

Move (8 pcs), instance 2 MVGAPC2 MV-2 MV (2) ● ●

Logging Functions

Disturbance recorder RDRE1 DFR - ● ●

Fault recorder FLMSTA1 FR - ● ●

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA02

BA CA

Page 63: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 57Application Manual

3.4.3 Default Input/Output (I/O) assignmentsTable 16: Analog input connections for CTs

Table 17: Analog input connections for VTs

Table 18: Analog input connections for RTDs*

Table 19: Binary input connections

Sequence event recorder SER SER - ● ●1) Vo calculated and negative sequence voltage selectable by parameter, V2 as default Io selectable by parameter, I2 as default2) Multi-purpose protection is used for, for example, RTD/mA

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA02

BA CA

Analog input Default usage Connector pinsX120 – IA(2) Current input for phase IA, low voltage side X120 – 1, 2

X120 – IB(2) Current input for phase IB, low voltage side X120 – 3,4

X120 – IC(2) Current input for phase IC, low voltage side X120 – 5,6

X120 – IA(1) Current input for phase IA, high voltage side X120 – 7, 8

X120 – IB(1) Current input for phase IB, high voltage side X120 – 9,10

X120 – IC(1) Current input for phase IC, high voltage side X120 – 11,12

X120 – IG(2) Ground current input IG, low voltage side X120 – 13,14

Analog input Default usage Connector pinsX130 – VA(2) Voltage input for phase VA, low voltage side X130 – 11,12

X130 – VB(2) Voltage input for phase VB, low voltage side X130 – 13,14

X130 – VC(2) Voltage input for phase VC, low voltage side X130 – 15,16

X130 – VG(2) Voltage input for phase VG, low voltage side X130 – 17,18

RTD input Default usage Connector pinsX130-RTD1 Winding temperature X130-3,4,5

X130-RTD2 Top oil temperature X130-6,7,8

*Available only for IED ordered with Application “CA”

Binary input Default usage Connector pins

X110-BI1 X110-1, 2

X110-BI2 X110-3, 4

X110-BI3 X110-5, 6

X110-BI4 X110-7, 6

X110-BI5 Circuit breaker (2) closed position X110-8, 9

X110-BI6 Circuit breaker (2) open position X110-10,9

X110-BI7 Circuit breaker (1) closed position X110-11, 12

X110-BI8 Circuit breaker (1) open position X110-13, 12

Page 64: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

58 RET615 ANSIApplication Manual

Table 20: Binary output connections

Table 21: High speed binary output connections*

Table 22: Default connections for LEDs

Binary output Default usage Connector pinsX100-PO1 Close circuit breaker (1) X100 – 6,7

X100-PO2 Close circuit breaker (2) X100 – 8,9

X100-SO1 Breaker failure backup trip to upstream breaker X100 – 11/12, 10

X100-SO2 X100 – 13, 14

X100-PO3 Open circuit breaker / Master Trip -1 X100 – 15,19

X100-PO4 Open circuit breaker / Master Trip -2 X100 – 20,24

X110-SO1* Winding RTD Alarm X110 – 15/16, 14

X110-SO2* Top Oil RTD Alarm X110 – 18/19, 17

X110-SO3* X110 – 21/22, 20

X110-SO4* X110 – 23,24

*Not available if IED has been ordered with High speed binary output (HSO) card

Binary output Default usage Connector pinsX110-HSO1 Trip from ARC-1 protection X110 – 15,16

X110-HSO2 Trip from ARC-2 protection X110 – 19,20

X110-HSO3 Trip from ARC-3 protection X110 – 23,24

*Available only if IED has been ordered with High speed binary output (HSO) card

LED LED labelLED 1 Phase A

LED 2 Phase B

LED 3 Phase C

LED 4 Neutral / Ground

LED 5 Time

LED 6 Instantaneous

LED 7 Differential / REF

LED 8 Voltage / Frequency

LED 9 Breaker Failure/Alarm

LED 10 Thermal Alarm/Trip

LED 11 Arc Flash Detection

Page 65: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 59Application Manual

3.4.4 Typical connection diagrams

Page 66: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

60 RET615 ANSIApplication Manual

Page 67: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 61Application Manual

3.4.5 Functional diagramsThe functional diagrams describe the default input, output, RTD inputs, alarm LED and function-to-function connections. The default connections can be viewed with and changed with PCM 600 according to the application requirements, if necessary.

The analog channels, measurements from CTs and PTs, have fixed connections to the different function blocks inside the IED’s standard configuration.

The analog channels are assigned to different functions as shown in functional diagrams. The function and analog signal marked with (1) represents the function and analog signals (three phase currents/voltages) of the high-voltage side of the transformer and (2) represents the function and analog signals (three phase currents/voltage) on the low-voltage side of the transformer. The signal marked with IG represents the ground current measured between the start point of the transformer and grounding. The signal marked with VG represents the ground voltage measured between the start point of the transformer and grounding.

RET615 offers six different settings group which the user can set based on individual needs. Each group can then, be activated/ deactivated by using the setting group settings available in RET615.

3.4.5.1 Functional diagrams for protectionThe functional diagrams for protection describe the IED’s protection functionality in detail and according to the factory set default connections.

Three stages for both high-voltage and low-voltage sides as a total of six, three-phase overcurrent protection (51P(1), 50P-1(1), 50P-2(1), 51P(2), 50P-1(2), 50P-2(2)) stages are provided for overcurrent and short-circuit protection.

The operation of these functions is not blocked as default by any functionality and so setting should be set such as to avoid unnecessary false trip or alarm.

Figure 35: Three phase overcurrent protection – HV side

Page 68: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

62 RET615 ANSIApplication Manual

Figure 36: Three phase overcurrent protection – LV side

Configuration also includes one stages of three-phase directional overcurrent protection (67/51P(2)) on low-voltage side. The operation of directional overcurrent protection is blocked by fuse failure supervision function (60(2)).

The operation of 51P(1), 51P(2) and 67/51P(2) is connected to alarm LED 5, and 50P-1(1), 50P-2(1), 50P-1(2) and 50P-2(2) is connected to alarm LED 6.

Figure 37: Three phase directional overcurrent protection – LV side

Alarm LEDs 1, 2 and 3 are configured so as to indicate which phase has resulted into tripping of overcurrent protection. Overcurrent faults in Phase A, B and C is mapped to Alarm LEDs 1, 2 and 3 respectively.

Three stages for both high-voltage and low-voltage side as a total of six, ground fault (51N(1), 50N-1(1), 50N-2(1), 51N(2), 50N-1(2), 50N-2(2)) stages are provided for ground fault protection.

Page 69: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 63Application Manual

Figure 38: Ground fault protection – HV side

Figure 39: Ground fault protection – LV sideConfiguration also includes three stages of ground fault protection (51G, 50G-1 and 50G-2).

Figure 40: Non-directional ground fault protection

The operation of these functions is not blocked as default by any functionality.

Page 70: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

64 RET615 ANSIApplication Manual

One stages of directional ground fault protection (67/51N(2)) on low-voltage is also included in the configuration. The operation of directional ground fault protection is blocked by fuse failure supervision function (60(2)).

Figure 41: Directional ground fault protection – LV side

The operation of 51N(1), 51N(2), 51G, and 67/51N(2) is connected to alarm LED 4 and 5, and 50N-1(1), 50N-2(1), 50N-1(2), 50N-2(2), 50G-1 and 50G-2 is connected to alarm LED 4 and 6.

One stage of negative-sequence overcurrent protection (46(1) and 46(2)) for both high-voltage and low-voltage sides is provided for protecting transformer against thermal stress and damage. The operation of 46(1) and 46(2) is not blocked as default by any functionality.

Figure 42: Negative sequence protection –HV and LV side

Configuration also includes high side as well as low side pickup alarm, the pickup outputs from respective 50P-1, 50P-2, 51P, 51N, 50N-1, 50N-2, 46, 67/51P and 67/51N are connected together to have a combined overcurrent high voltage side and low voltage side pickup alarm which is connected to disturbance recorder as default.

Figure 43: Overcurrent pickup alarms – HV side

Page 71: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 65Application Manual

Figure 44: Overcurrent pickup alarms – LV side

The configuration includes restricted low-impedance ground-fault (87LOZREF(2)) protection function for low-voltage side of two-winding power transformers. The numerical differential current stage operates exclusively on ground faults occurring in the protected area, that is, in the area between the phase and neutral current transformers. An ground fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and ground.

The operation of 87LOZREF(2) is not blocked as default by any functionality. The operation of 87LOZREF(2) is connected to alarm LED 7.

Figure 45: Restricted low impedance ground fault protection – LV side

The restrained (Low Stage) and unrestrained (High Stage) differential protection for two winding transformers (87T) provides protection of power transformer unit including, for example, winding short-circuit and inter-turn faults. The IED compares the phase currents on both sides of the transformer. If the differential current of the phase currents in one of the phases exceed the setting of the restrained (low stage) operation characteristic or the instantaneous protection stage of the function, the function provides a trip signal.

Figure 46: Transformer differential protection

Page 72: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

66 RET615 ANSIApplication Manual

For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in 87T.

The operation of 87LOZREF(2) and 87T is not blocked as default by any functionality. The operation of these protection functions is connected to alarm LED 7.

The thermal overload protection function (49T(1)) on HV side detects short and long term overloads under varying load conditions.

The alarm and operation of thermal overload protection function is connected to alarm LED 10.

Figure 47: Transformer thermal overload protection – HV side

Loss of load protection (37(1)) is provided on HV side of the transformer for detecting sudden loss of load on the transformer.

The operation of 37(1) is not blocked as default by any functionality.

Figure 48: Loss of load protection - HV side

For voltage protection, three-phase undervoltage (27(2), three-phase overvoltage (59(2)), residual overvoltage (59N(2) and 59G(2)) and negative-sequence overvoltage (47(2)) protection functions are offered on low-voltage side. The 27(2), 47(2), and 59N(2) protection functions are blocked if the fuse failure is detected.

By default 49T(1) is not configured to trip the circuit breaker.

By default 37(1) is not configured in the configuration.

Page 73: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 67Application Manual

Figure 49: Voltage protection – LV side

Configuration also includes two stages of Volts per Hertz protection (24-1(2) and 24-2(2)) function block on low voltage side to protect transformer under excessive flux density and saturation of the magnetic core. Function is not blocked by default.

Figure 50: Over excitation protection – LV side

Two stages of frequency protection (81-1(2) and 81-2(2)) and load shedding (81LSH-1(2), and 81LSH-2(2)) function block are also available on low voltage side. 81-1(2) and 81-2(2) can be set to operate as under frequency or over frequency or as rate of change of frequency protection, whereas 81LSH-1(2) and 81LSH-2(2) can be set to operate as independent under frequency or as rate of change of frequency or under frequency with rate of change of frequency protection.

Page 74: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

68 RET615 ANSIApplication Manual

Figure 51: Frequency protection – LV side

Figure 52: Load shedding protection – LV sideThe operation of voltage and frequency protection functions is connected to alarm LED 8.

The circuit-breaker failure protection (50BF(1) and 50BF(2)) for both high-voltage and low-voltage side is initiated via the pickup input by a number of different protection functions in the IED. 50BF(1) and 50BF(2) offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents.

50BF(1) and 50BF(2) has two operating outputs: TRRET and TRBU. The TRBU output from both the high voltage and low-voltage side is used to give a backup trip to the circuit

By default voltage and frequency protection functions are not configured to trip the circuit breaker.

Page 75: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 69Application Manual

breaker feeding upstream. For this purpose, the TRBU output signal from both the function is connected to the output SO1 (X100: 10-11).

The TRBU output from 50BF(1) and 50BF(2) is connected to alarm LED 9.

Figure 53: Circuit breaker failure protection – HV side

Figure 54: Circuit breaker failure protection – LV side

Three multipurpose analog protection (MAP-1, MAP-2, and MAP-3) functions are included as an optional function, in the configuration which can be used as an under-protection or overprotection. In the present configuration MAP-1 and MAP-2 functions are used to provide thermal protection using RTD/mA, where as MAP-3 is not configured.

Winding temperature is measured with inputs RTD-1 (X130:3,4,5) and is connected to the multipurpose analog protection block MAP-1.

The TRRET operate output can be used for retripping its own circuit breaker through the Master Trip again. However this is not connected in present configuration.

Page 76: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

70 RET615 ANSIApplication Manual

Figure 55: General purpose protection function and associated RTD inputsTop oil temperature is measured with inputs RTD-2 (X130:6,7,8). The protection functionality for rotor temperatures is provided by MAP-2 functions.

Trip signals from MAP-1 and MAP-2 are connected directly to binary output S01 (X110:14,15), and S02 (X110:17,18) respectively if the IED has been ordered without high speed binary output

Three arc protection (AFD-1(2), AFD-2(2) and AFD-3(2)) stages are included as an optional function on low-voltage side of the transformer. The arc protection offers individual function blocks for three ARC sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check.

Figure 56: Arc protection – LV side

By default MAP-3 is not configured in the configuration.

Page 77: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 71Application Manual

Trip signal from AFD-1(2) is connected to master trip on high voltage side, available at PO3 (X100: 15-19). Whereas the trip signal from AFD-2(2) is connected to master trip on low voltage side, available at PO4 (X100:20-24).

If the IED has been ordered with high speed binary outputs, then trip signal from AFD-1(2), AFD-2(2) and AFD-3(2) are also connected directly to high speed output HS01(X110:15-16), HS02 (X110:19-20) and HS03(X110:23-24) respectively.

The detection of arc fault is connected to alarm LED 11.

Two master trip logics (86/94-1 and 86/94-2) are provided as a trip command collector. 86/94-1 collects the trip signals from 51P(1), 50P-1(1), 50P-2(1), 46(1), 50N-1(1), 50N-2(1), 50G-1, 50G-2, 51N(1), 51G, 87T, 87LOZREF(2) and AFD-1(2) protection functions and is connected to provide high voltage side trip to binary output PO3 (X100:16-19).

Open control commands to the high voltage circuit breaker from the local or remote is also connected directly to the output PO3 (X100:16-19) from high voltage circuit breaker control (52(1)) function block.

86/94-2 collects the trip signals from 51P(2), 50P-1(2), 50P-2(2), 46(2), 50N-1(2), 50N-2(2), 50G-1, 50G-2, 51N(2), 51G, 87T, 87LOZREF(2), 67/51P(2), 67/51N(2) and AFD-2(2) protection functions and is connected to provide low voltage side trip to binary output contact PO4 (X100:20-24).

Open control commands to the low voltage circuit breaker from the local or remote is also connected directly to the output PO4 (X100:20-24) from low voltage circuit breaker control (52(2)) function block.

Figure 57: Master trip logic – HV side

AFD-3(2) is not connected to any binary outputs for IED ordered without high speed binary outputs.

Page 78: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

72 RET615 ANSIApplication Manual

Figure 58: Master trip logic – LV side

86/94-1 and 86/94-2 provides the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

3.4.5.2 Functional diagrams for control functions The functional diagrams for control describe the IED’s control functionality in detail and according to the factory set default connections.

The high voltage and low voltage side circuit breaker closing is enabled when the respective ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and ground switch position status and the status of the Master Trip logics, gas pressure alarm and circuit-breaker spring charging. With the present configuration, the activation of respective ENA_CLOSE input is configured using only Master Trip logic 86/94-1(1) and 86/94-2(2) i.e. the circuit breaker cannot be closed in case master trip is active.

When all conditions of the high voltage circuit breaker closing are fulfilled, the EXE_CL output of the 52(1) and PO1 output (X100:6-7) is closed if closing command is given. Similarly when all the conditions of the low voltage circuit breaker closing are fulfilled, the EXE_CL output of the 52(2) and PO2 output (X100:8-9) is closed if closing command is given.

The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position.

Page 79: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 73Application Manual

Figure 59: Circuit breaker control – HV side

Figure 60: Circuit breaker control – LV side

Configuration also includes tap changer position indicator (84T), however by default it is not configured.

Figure 61: Tap changer position indicator

3.4.5.3 Functional diagrams for condition monitoring The functional diagrams for condition monitoring describe the IED’s condition monitoring functionality in detail and according to the factory set default connections.

Two trip circuit monitoring (TCM-1 and TCM-2) stages are provided to supervise the trip circuit of the high voltage and low voltage circuit breaker connected at PO3 (X100:15-19) and PO4 (X100:20-24) respectively.

If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block 52 with PCM600, the function assumes that the breaker close commands are allowed continuously.

Page 80: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

74 RET615 ANSIApplication Manual

Figure 62: Trip circuit monitoring HV and LV- side

The TCM-1 and TCM-2 functions are blocked by respective 86/94-1(1) and, 86/94-2(2) function block and the respective circuit-breaker open position signal.

The supervision alarm from TCM-1 and TCM-2 is connected to alarm LED 9.

A failure in current measuring circuits is detected by current circuit supervision function (MCS 3I, I2). When a failure is detected, function activates and can be used to block protection functions for example 87T, thus avoiding mal-operation.

Figure 63: Current circuit supervision

Similar to MCS 3I I2 function, a failure in voltage measurement circuit is detected by fuse failure supervision function (60(2)) available on low voltage side. The function is used to block the voltage protection and directional protection functions at failures in the secondary circuits between the voltage transformer and IED to avoid mal operation.

By default it is expected that there is no external resistor in the circuit breaker tripping/closing coil circuit connected parallel with circuit breaker normally open/closed auxiliary contact.

By default the FAIL output from MCS 3I, I2 function is only connected to disturbance recorder

Page 81: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 75Application Manual

Figure 64: Fuse failure supervision - LV sideTwo circuit breaker condition monitoring function (52CM(1) and 52CM(2)) one each is configured to supervise high voltage side and low voltage side circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision alarms.

Figure 65: Circuit breaker condition monitoring HV side

Figure 66: Circuit breaker condition monitoring LV side

The supervision alarm from 52CM(1) and 52CM(2) is connected to alarm LED 9.

3.4.5.4 Functional diagrams for MeasurementsThe functional diagrams for measurement describe the IED’s measurement functionality in detail and according to the factory set default connections

The phase current inputs from high voltage and low voltage side are connected to the IED and are measured by high voltage and low voltage side three-phase current measurement

By default only POSOPEN and POSCLOSE information is available to 52CM(1) and 52CM(2).

Page 82: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

76 RET615 ANSIApplication Manual

(IA,IB,IC(1) and IA,IB,IC(2)). The three-phase voltage inputs from high voltage side are measured by high voltage side voltage measurement (VA,VB,VC(2)) function block respectively. The current input is connected to the X120 card in the back panel, whereas voltage input is connected to X130 card in the back panel. Similarly the sequence current for both high voltage and low voltage side and sequence voltage from high voltage side are measured by sequence current measurement (I1, I2, I0(1) and I1,I2,I0(2)) and sequence voltage measurement (V1,V2,V0(2)) function block respectively. The residual current and voltage is measured by residual current measurement (IG) and residual voltage measurement (VG) function block.

Apart from current and voltage measurement, configuration also provides single phase (SP, SE(2)) and three phase power and energy measurement (P,E(2)) along with frequency measurement (f) function block.

The measurements can be seen from the LHMI and is available using the measurement option in the menu selection. Based on the settings, ‘IA, IB, IC(1)’, IA,IB,IC(2), ‘VA,VB,VC(2)’,‘IG’ and ‘VG’ function blocks can generate low alarm/warning, high alarm/warning signals for the measured current values.

Figure 67: Measurements

3.4.5.5 Functional diagrams for other functions Configuration also includes other miscellaneous basic functions which are not configured, but can be used for creating general purpose logics. These functions include:

• Four instance of Minimum Pulse Timer TP-1, TP-2, TP-3 and TP-4,

• Two instance of Pulse Timer PT-1 and PT-2,

• Two instance of Time delay off TOF-1 and TOF-2,

• Two instance of Time delay on TON-1 and TON-2,

• Two instance of Set reset logic SR-1 and SR-2 and

• Two instance of Move logic MV-1 and MV-2

Page 83: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 77Application Manual

3.4.5.6 Functional diagrams for logging functions The functional diagrams for logging describe the IED’s default disturbance recorder connections.

The disturbance recorder DFR consists of 64 channels. However as default few channel are connected to trigger the digital fault recorder are as shown in Figure 68. More connection can be made as per individual need. Also when disturbance recorder is trigger the analog values available at the analog inputs are recorded by fault recorder FR.

Figure 68: 64 channel Disturbance and fault recorder

3.4.5.7 Functional diagrams for I/O and Alarm LEDs The functional diagrams for I/O and Alarm LEDs describe the IED’s default input/output and alarm LEDs connections.

The default binary I/O connected in the configuration and Alarm LEDs are indicated in Binary inputs to Alarm LED

Page 84: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

78 RET615 ANSIApplication Manual

Figure 69: Binary inputs

Page 85: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 79Application Manual

Figure 70: Binary outputs

High speed binary outputs (HSO) are available only if IED with High speed binary card has been ordered.

Page 86: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

80 RET615 ANSIApplication Manual

Page 87: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 81Application Manual

Figure 71: Alarm LEDs

Page 88: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

82 RET615 ANSIApplication Manual

3.5 Standard Configuration for Order Code Functional Application BB/CB

3.5.1 ApplicationsThe standard configuration is mainly intended for two-winding transformers and two breakers. This configuration includes phase differential, restricted ground fault, over excitation, current, voltage, frequency protection, power and energy metering and two RTD inputs for top oil and winding temperature monitoring. The winding that supports the directional overcurrent, voltage and frequency protection and power and energy metering is an ordering option.

The IED with this standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enable this configuration to be further adapted to different primary power system layouts and the related functionality needs by modifying the internal functionality using PCM600.

Page 89: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 83Application Manual

3.5.2 FunctionsTable 23: Functions included in the RET615 standard configuration

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA03

BB CBProtection

Three-phase non-directional overcurrent protection, low stage, instance 1

PHLPTOC1 51P (1) 3I> (1) ● ●

Three-phase non-directional overcurrent protection, low stage, instance 2

PHLPTOC2 51P (2) 3I> (2) ● ●

Three-phase non-directional overcurrent protection, high stage, instance 1

PHHPTOC1 50P-1 (1) 3I>> (1) ● ●

Three-phase non-directional overcurrent protection, high stage, instance 2

PHHPTOC2 50P-1 (2) 3I>> (2) ● ●

Three-phase non-directional overcurrent protection, high stage, instance 3

PHHPTOC3 50P-2 (1) 3I>> (3) ● ●

Three-phase non-directional overcurrent protection, high stage, instance 4

PHHPTOC4 50P-2 (2) 3I>> (4) ● ●

Non-directional ground-fault protection, low stage, instance 1

EFLPTOC1 51G Io> (1) ● ●

Three-phase directional overcurrent protection, low stage, instance 2

DPHLPDOC2 67/51P (1) 3I> -> (2) ● ●

Non-directional ground-fault protection, low stage, instance 2

EFLPTOC2 51N (1) Io> (2) ● ●

Non-directional ground-fault protection, low stage, instance 3

EFLPTOC3 51N (2) Io> (3) ● ●

Non-directional ground-fault protection, high stage, instance 1

EFHPTOC1 50G-1 Io>> (1) ● ●

Non-directional ground-fault protection, high stage, instance 2

EFHPTOC2 50G-2 Io>> (2) ● ●

Non-directional ground-fault protection, high stage, instance 3

EFHPTOC3 50N-1 (1) Io>> (3) ● ●

Non-directional ground-fault protection, high stage, instance 4

EFHPTOC4 50N-1 (2) Io>> (4) ● ●

Non-directional ground-fault protection, high stage, instance 5

EFHPTOC5 50N-2 (1) Io>> (5) ● ●

Non-directional ground-fault protection, high stage, instance 6

EFHPTOC6 50N-2 (2) Io>> (6) ● ●

Directional ground-fault protection, low stage, instance 2

DEFLPDEF2 67/51N (1) Io> -> (2) ●1)

●1)

Negative-sequence overcurrent protection, instance 1

NSPTOC1 46 (1) I2> (1) ● ●

Negative-sequence overcurrent protection, instance 2

NSPTOC2 46 (2) I2> (2) ● ●

Residual overvoltage protection, instance 3 ROVPTOV3 59N (1) Uo> (3) ● ●

Residual overvoltage protection, instance 4 ROVPTOV4 59G (1) Uo> (4) ● ●

Three-phase undervoltage protection, instance 2

PHPTUV2 27 (1) 3U< (2) ● ●

Three-phase overvoltage protection, instance 2

PHPTOV2 59 (1) 3U> (2) ● ●

Negative-sequence overvoltage protection, instance 2

NSPTOV2 47 (1) U2> (2) ● ●

Page 90: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

84 RET615 ANSIApplication Manual

Frequency protection, instance 3 FRPFRQ3 81-1 (1) f>/f<,df/dt (3) ● ●

Frequency protection, instance 4 FRPFRQ4 81-2 (1) f>/f<,df/dt (4) ● ●

Voltage per hertz protection, instance 3 OEPVPH3 24-1 (1) U/f> (3) ● ●

Voltage per hertz protection, instance 4 OEPVPH4 24-2 (1) U/f> (4) ● ●

Three-phase thermal overload protection for power transformers, two time constants

T2PTTR1 49T (1) 3Ith>T ● ●

Restrained (Low Stage) and unrestrained (High Stage) differential protection for 2W –transformers

TR2PTDF1 87T 3dI>T ● ●

Numerical restrained (low stage) low impedance restricted ground-fault protection

LREFPNDF1 87LOZREF (2)

dIoLo> ● ●

Circuit breaker failure protection, instance 1 CCBRBRF1 50BF (1) 3I>/Io>BF (1) ● ●

Circuit breaker failure protection, instance 2 CCBRBRF2 50BF (2) 3I>/Io>BF (2) ● ●

Master trip, instance 1 TRPPTRC1 86/94-1 Master Trip (1) ● ●

Master trip, instance 2 TRPPTRC2 86/94-2 Master Trip (2) ● ●

Arc protection, instance 1 ARCSARC1 AFD-1 (2) ARC (1) ● ●

Arc protection, instance 2 ARCSARC2 AFD-2 (2) ARC (2) ● ●

Arc protection, instance 3 ARCSARC3 AFD-3 (2) ARC (3) ● ●

Multi-purpose protection, instance 1 MAPGAPC1 MAP-1 MAP (1) ●2)

Multi-purpose protection, instance 2 MAPGAPC2 MAP-2 MAP (2) ●2)

Multi-purpose protection, instance 3 MAPGAPC3 MAP-3 MAP (3) ●2)

Load shedding and restoration, instance 3 LSHDPFRQ3 81LSH-1 (1) UFLS/R (3) ● ●

Load shedding and restoration, instance 4 LSHDPFRQ4 81LSH-2 (1) UFLS/R (4) ● ●

Loss of phase, instance 1 PHPTUC1 37 (1) 3I< (1) ● ●

Control

Circuit-breaker control, instance 1 CBXCBR1 52 (1) I <-> O CB (1) ● ●

Circuit-breaker control, instance 2 CBXCBR2 52 (2) I <-> O CB (2) ● ●

Tap changer position indication TPOSSLTC1 84T TPOSM ● ●

Condition Monitoring

Circuit-breaker condition monitoring, instance 1

SSCBR1 52CM (1) CBCM (1) ● ●

Circuit-breaker condition monitoring, instance 2

SSCBR2 52CM (2) CBCM (2) ● ●

Trip circuit supervision, instance 1 TCSSCBR1 TCM-1 TCS (1) ● ●

Trip circuit supervision, instance 2 TCSSCBR2 TCM-2 TCS (2) ● ●

Advanced current circuit supervision for transformers

CTSRCTF1 MCS 3I, I2 MCS 3I, I2 ● ●

Fuse failure supervision, instance 1 SEQRFUF1 60 (1) FUSEF (1) ● ●

Measurements

Three-phase current measurement, instance 1

CMMXU1 IA, IB, IC (1) 3I ● ●

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA03

BB CB

Page 91: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 85Application Manual

Three-phase current measurement, instance 2

CMMXU2 IA, IB, IC (2) 3I(B) ● ●

Sequence current measurement, instance 1 CSMSQI1 I1, I2, I0 (1) I1, I2, I0 ● ●

Sequence current measurement, instance 2 CSMSQI2 I1, I2, I0 (2) I1, I2, I0(B) ● ●

Residual current measurement, instance 1 RESCMMXU1 IG Io ● ●

Three-phase voltage measurement, instance 1

VMMXU1 VA, VB, VC (1)

3U ● ●

Residual voltage measurement, instance 1 RESVMMXU1 VG Uo ● ●

Sequence voltage measurement, instance 1 VSMSQI1 V1, V2, V0 (1)

U1, U2, U0 ● ●

Single-phase power and energy measurement, instance 1

SPEMMXU1 SP, SE (1) SP, SE ● ●

Three-phase power and energy measurement, instance 1

PEMMXU1 P, E (1) P, E ● ●

2 RTD +1 mA XARGGIO130 X130 (AIM+RTD)

Frequency measurement, instance 1 FMMXU1 f f ● ●

Other Functions

Minimum pulse timer (2 pcs), instance 1 TPGAPC1 TP-1 TP (1) ● ●

Minimum pulse timer (2 pcs), instance 2 TPGAPC2 TP-2 TP (2) ● ●

Minimum pulse timer (2 pcs), instance 3 TPGAPC3 TP-3 TP (3) ● ●

Minimum pulse timer (2 pcs), instance 4 TPGAPC4 TP-4 TP (4) ● ●

Pulse timer (8 pcs), instance 1 PTGAPC1 PT-1 PT (1) ● ●

Pulse timer (8 pcs), instance 2 PTGAPC2 PT-2 PT (2) ● ●

Time delay off (8 pcs), instance 1 TOFGAPC1 TOF-1 TOF (1) ● ●

Time delay off (8 pcs), instance 2 TOFGAPC2 TOF-2 TOF (2) ● ●

Time delay on (8 pcs), instance 1 TONGAPC1 TON -1 TON (1) ● ●

Time delay on (8 pcs), instance 2 TONGAPC2 TON -2 TON (2) ● ●

Set reset (8 pcs), instance 1 SRGAPC1 SR-1 SR (1) ● ●

Set reset (8 pcs), instance 2 SRGAPC2 SR-2 SR (2) ● ●

Move (8 pcs), instance 1 MVGAPC1 MV-1 MV (1) ● ●

Move (8 pcs), instance 2 MVGAPC2 MV-2 MV (2) ●

Logging Functions

Disturbance recorder RDRE1 DFR - ● ●

Fault recorder FLMSTA1 FR - ● ●

Sequence event recorder SER SER - ● ●1) Vo calculated and negative sequence voltage selectable by parameter, V2 as default Io selectable by parameter, I2 as default2) Multi-purpose protection is used for, for example, RTD/mA

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA03

BB CB

Page 92: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

86 RET615 ANSIApplication Manual

3.5.3 Default Input/Output (I/O) assignmentsTable 24: Analog input connections for CTs

Table 25: Analog input connections for VTs

Table 26: Analog input connections for RTDs*

Table 27: Binary input connections

Analog input Default usage Connector pinsX120 – IA(2) Current input for phase IA, low voltage side X120 – 1, 2

X120 – IB(2) Current input for phase IB, low voltage side X120 – 3,4

X120 – IC(2) Current input for phase IC, low voltage side X120 – 5,6

X120 – IA(1) Current input for phase IA, high voltage side X120 – 7, 8

X120 – IB(1) Current input for phase IB, high voltage side X120 – 9,10

X120 – IC(1) Current input for phase IC, high voltage side X120 – 11,12

X120 – IG(2) Ground current input IG, low voltage side X120 – 13,14

Analog input Default usage Connector pinsX130 – VA(1) Voltage input for phase VA, high voltage side X130 – 11,12

X130 – VB(1) Voltage input for phase VB, high voltage side X130 – 13,14

X130 – VC(1) Voltage input for phase VC, high voltage side X130 – 15,16

X130 – VG(1) Voltage input for phase VG, high voltage side X130 – 17,18

RTD input Default usage Connector pinsX130-RTD1 Winding temperature X130-3,4,5

X130-RTD2 Top oil temperature X130-6,7,8

*Available only for IED ordered with Application “CB”

Binary input Default usage Connector pinsX110-BI1 X110-1, 2

X110-BI2 X110-3, 4

X110-BI3 X110-5, 6

X110-BI4 X110-7, 6

X110-BI5 Circuit breaker (2) closed position X110-8, 9

X110-BI6 Circuit breaker (2) open position X110-10,9

X110-BI7 Circuit breaker (1) closed position X110-11, 12

X110-BI8 Circuit breaker (1) open position X110-13, 12

Page 93: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 87Application Manual

Table 28: Binary output connections

Table 29: Table 7: High speed binary output connections*

Table 30: Table 8: Default connections for LEDs

Binary output Default usage Connector pinsX100-PO1 Close circuit breaker (1) X100 – 6,7

X100-PO2 Close circuit breaker (2) X100 – 8,9

X100-SO1 Breaker failure backup trip to upstream breaker X100 – 11/12, 10

X100-SO2 X100 – 13, 14

X100-PO3 Open circuit breaker / Master Trip -1 X100 – 15,19

X100-PO4 Open circuit breaker / Master Trip -2 X100 – 20,24

X110-SO1* Winding RTD Alarm X110 – 15/16, 14

X110-SO2* Top Oil RTD Alarm X110 – 18/19, 17

X110-SO3* X110 – 21/22, 20

X110-SO4* X110 – 23,24

*Not available if IED has been ordered with High speed binary output (HSO) card

Binary output Default usage Connector pinsX110-HSO1 Trip from ARC-1 protection X110 – 15,16

X110-HSO2 Trip from ARC-2 protection X110 – 19,20

X110-HSO3 Trip from ARC-3 protection X110 – 23,24

*Available only if IED has been ordered with High speed binary output (HSO) card

LED LED labelLED 1 Phase A

LED 2 Phase B

LED 3 Phase C

LED 4 Neutral / Ground

LED 5 Time

LED 6 Instantaneous

LED 7 Differential / REF

LED 8 Voltage / Frequency

LED 9 Breaker Failure/Alarm

LED 10 Thermal Alarm/Trip

LED 11 Arc Flash Detection

Page 94: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

88 RET615 ANSIApplication Manual

3.5.4 Typical connection diagrams

Page 95: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 89Application Manual

3.5.5 Functional diagramsThe functional diagrams describe the default input, output, RTD inputs, alarm LED and function-to-function connections. The default connections can be viewed with and changed with PCM 600 according to the application requirements, if necessary.

The analog channels, measurements from CTs and PTs, have fixed connections to the different function blocks inside the IED’s standard configuration.

The analog channels are assigned to different functions as shown in functional diagrams. The function and analog signal marked with (1) represents the function and analog signals (three phase currents/voltages) of the high-voltage side of the transformer and (2) represents the function and analog signals (three phase currents/voltage) on the low-voltage side of the transformer. The signal marked with IG represents the ground current measured between the start point of the transformer and grounding. The signal marked with VG represents the ground voltage measured between the start point of the transformer and grounding.

RET615 offers six different settings group which the user can set based on individual needs. Each group can then, be activated/ deactivated by using the setting group settings available in RET615.

3.5.5.1 Functional diagrams for protectionThe functional diagrams for protection describe the IED’s protection functionality in detail and according to the factory set default connections.

Three stages for both high-voltage and low-voltage sides as a total of six, three-phase overcurrent protection (51P(1), 50P-1(1), 50P-2(1), 51P(2), 50P-1(2), 50P-2(2)) stages are provided for overcurrent and short-circuit protection.

The operation of these functions is not blocked as default by any functionality and so setting should be set such as to avoid unnecessary false trip or alarm.

Figure 72: Three phase overcurrent protection – HV side

Page 96: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

90 RET615 ANSIApplication Manual

Figure 73: Three phase overcurrent protection – LV sideConfiguration also includes one stages of three-phase directional overcurrent protection (67/51P(1)) on high-voltage side. The operation of directional overcurrent protection is blocked by fuse failure supervision function (60(1)).

The operation of 51P(1), 51P(2) and 67/51P(1) is connected to alarm LED 5, and 50P-1(1), 50P-2(1), 50P-1(2) and 50P-2(2) is connected to alarm LED 6.

Figure 74: Three phase directional overcurrent protection – HV sideAlarm LEDs 1, 2 and 3 are configured so as to indicate which phase has resulted into tripping of overcurrent protection. Overcurrent faults in Phase A, B and C is mapped to Alarm LEDs 1, 2 and 3 respectively.

Three stages for both high-voltage and low-voltage side as a total of six, ground fault (51N(1), 50N-1(1), 50N-2(1), 51N(2), 50N-1(2), 50N-2(2)) stages are provided for ground fault protection.

Figure 75: Ground fault protection – HV side

Page 97: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 91Application Manual

Figure 76: Ground fault protection – LV side

Configuration also includes three stages of ground fault protection (51G, 50G-1 and 50G-2).

Figure 77: Non-directional ground fault protection

The operation of these functions is not blocked as default by any functionality.

One stages of directional ground fault protection (67/51N(1)) on high-voltage is also included in the configuration. The operation of directional ground fault protection is blocked by fuse failure supervision function (60(1)).

Figure 78: Directional ground fault protection – HV side

Page 98: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

92 RET615 ANSIApplication Manual

The operation of 51N(1), 51N(2), 51G, and 67/51N(1) is connected to alarm LED 4 and 5, and 50N-1(1), 50N-2(1), 50N-1(2), 50N-2(2), 50G-1 and 50G-2 is connected to alarm LED 4 and 6.

One stage of negative-sequence overcurrent protection (46(1) and 46(2)) for both high-voltage and low-voltage sides is provided for protecting transformer against thermal stress and damage. The operation of 46(1) and 46(2) is not blocked as default by any functionality.

Figure 79: Negative sequence protection –HV and LV side

Configuration also includes high side as well as low side pickup alarm, the pickup outputs from respective 50P-1, 50P-2, 51P, 51N, 50N-1, 50N-2, 46, 67/51P and 67/51N are connected together to have a combined overcurrent high voltage side and low voltage side pickup alarm which is connected to disturbance recorder as default.

Figure 80: Overcurrent pickup alarms – HV side

Page 99: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 93Application Manual

Figure 81: Overcurrent pickup alarms – LV side

The configuration includes restricted low-impedance ground-fault (87LOZREF(2)) protection function for low-voltage side of two-winding power transformers. The numerical differential current stage operates exclusively on ground faults occurring in the protected area, that is, in the area between the phase and neutral current transformers. An ground fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and ground.

The operation of 87LOZREF(2) is not blocked as default by any functionality. The operation of 87LOZREF(2) is connected to alarm LED 7.

Figure 82: Restricted low impedance ground fault protection – LV sideThe restrained (Low Stage) and unrestrained (High Stage) differential protection for two winding transformers (87T) provides protection of power transformer unit including, for example, winding short-circuit and inter-turn faults. The IED compares the phase currents on both sides of the transformer. If the differential current of the phase currents in one of the phases exceed the setting of the restrained (low stage) operation characteristic or the instantaneous protection stage of the function, the function provides a trip signal.

Figure 83: Transformer differential protection

Page 100: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

94 RET615 ANSIApplication Manual

For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in 87T.

The operation of 87LOZREF(2) and 87T is not blocked as default by any functionality. The operation of these protection functions is connected to alarm LED 7.

The thermal overload protection function (49T(1)) on HV side detects short and long term overloads under varying load conditions.

The alarm and operation of thermal overload protection function is connected to alarm LED 10.

Figure 84: Transformer thermal overload protection – HV side

Loss of load protection (37(1)) is provided on HV side of the transformer for detecting sudden loss of load on the transformer.

The operation of 37(1) is not blocked as default by any functionality.

Figure 85: Loss of load protection - HV side

For voltage protection, three-phase undervoltage (27(1)), three-phase overvoltage (59(1)), residual overvoltage (59N(1) and 59G(1)) and negative-sequence overvoltage (47(1)) protection functions are offered on high-voltage side. The 27(1), 47(1), and 59N(1) protection functions are blocked if the fuse failure is detected.

By default 49T(1) is not configured to trip the circuit breaker.

By default 37(1) is not configured in the configuration.

Page 101: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 95Application Manual

Figure 86: Voltage protection – HV side

Configuration also includes two stages of Volts per Hertz protection (24-1(1) and 24-2(1)) function block on high voltage side to protect transformer under excessive flux density and saturation of the magnetic core. Function is not blocked by default.

Figure 87: Over excitation protection – HV side

Two stages of frequency protection (81-1(1) and 81-2(1)) and load shedding (81LSH-1(1), and 81LSH-2(1)) function block are also available on high voltage side. 81-1(1) and 81-2(1) can be set to operate as under frequency or over frequency or as rate of change of frequency protection, whereas 81LSH-1(1) and 81LSH-2(1) can be set to operate as independent under frequency or as rate of change of frequency or under frequency with rate of change of frequency protection.

Page 102: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

96 RET615 ANSIApplication Manual

Figure 88: Frequency protection – LV side

Figure 89: Load shedding protection – LV side

The operation of voltage and frequency protection functions is connected to alarm LED 8.

The circuit-breaker failure protection (50BF(1) and 50BF(2)) for both high-voltage and low-voltage side is initiated via the pickup input by a number of different protection functions in the IED. 50BF(1) and 50BF(2) offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents.

50BF(1) and 50BF(2) has two operating outputs: TRRET and TRBU. The TRBU output from both the high voltage and low-voltage side is used to give a backup trip to the circuit breaker feeding upstream. For this purpose, the TRBU output signal from both the function is connected to the output SO1 (X100: 10-11).

The TRBU output from 50BF(1) and 50BF(2) is connected to alarm LED 9.

By default voltage and frequency protection functions are not configured to trip the circuit breaker.

Page 103: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 97Application Manual

Figure 90: Circuit breaker failure protection – HV side

Figure 91: Circuit breaker failure protection – LV side

Three multipurpose analog protection (MAP-1, MAP-2, and MAP-3) functions are included as an optional function, in the configuration which can be used as an underprotection or over-protection. In the present configuration MAP-1 and MAP-2 functions are used to provide thermal protection using RTD/mA, where as MAP-3 is not configured.

Winding temperature is measured with inputs RTD-1 (X130:3,4,5) and is connected to the multipurpose analog protection block MAP-1.

The TRRET operate output can be used for retripping its own circuit breaker through the Master Trip again. However this is not connected in present configuration.

Page 104: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

98 RET615 ANSIApplication Manual

Figure 92: General purpose protection function and associated RTD inputs

Top oil temperature is measured with inputs RTD-2 (X130:6,7,8). The protection functionality for rotor temperatures is provided by MAP-2 functions.

Trip signals from MAP-1 and MAP-2 are connected directly to binary output S01 (X110:14,15), and S02 (X110:17,18) respectively if the IED has been ordered without high speed binary output

Three arc protection (AFD-1(2), AFD-2(2) and AFD-3(2)) stages are included as an optional function on low-voltage side of the transformer. The arc protection offers individual function blocks for three ARC sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check.

By default MAP-3 is not configured in the configuration.

Page 105: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 99Application Manual

Figure 93: Arc protection – LV side

Trip signal from AFD-1(2) is connected to master trip on high voltage side, available at PO3 (X100: 15-19). Whereas the trip signal from AFD-2(2) is connected to master trip on low voltage side, available at PO4 (X100:20-24).

If the IED has been ordered with high speed binary outputs, then trip signal from AFD-1(2), AFD-2(2) and AFD-3(2) are also connected directly to high speed output HS01(X110:15-16), HS02 (X110:19-20) and HS03(X110:23-24) respectively.

The detection of arc fault is connected to alarm LED 11.

Two master trip logics (86/94-1 and 86/94-2) are provided as a trip command collector. 86/94-1 collects the trip signals from 51P(1), 50P-1(1), 50P-2(1), 46(1), 50N-1(1), 50N-2(1), 50G-1, 50G-2, 51N(1), 51G, 87T, 87LOZREF(2), 67/51P(1), 67/51N(1) and AFD-1(2) protection functions and is connected to provide high voltage side trip to binary output PO3 (X100:16-19).

Open control commands to the high voltage circuit breaker from the local or remote is also connected directly to the output PO3 (X100:16-19) from high voltage circuit breaker control (52(1)) function block.

86/94-2 collects the trip signals from 51P(2), 50P-1(2), 50P-2(2), 46(2), 50N-1(2), 50N-2(2), 50G-1, 50G-2, 51N(2), 51G, 87T, 87LOZREF(2) and AFD-2(2) protection functions and is connected to provide low voltage side trip to binary output contact PO4 (X100:20-24).

Open control commands to the low voltage circuit breaker from the local or remote is also connected directly to the output PO4 (X100:20-24) from low voltage circuit breaker control (52(2)) function block.

AFD-3(2) is not connected to any binary outputs for IED ordered without high speed binary outputs.

Page 106: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

100 RET615 ANSIApplication Manual

Figure 94: Master trip logic – HV side

Figure 95: Master trip logic – LV side

86/94-1 and 86/94-2 provides the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

3.5.5.2 Functional diagrams for control functions The functional diagrams for control describe the IED’s control functionality in detail and according to the factory set default connections.

The high voltage and low voltage side circuit breaker closing is enabled when the respective ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and ground switch position status and the status of the Master Trip logics, gas pressure alarm

Page 107: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 101Application Manual

and circuit-breaker spring charging. With the present configuration, the activation of respective ENA_CLOSE input is configured using only Master Trip logic 86/94-1(1) and 86/94-2(2) i.e. the circuit breaker cannot be closed in case master trip is active.

When all conditions of the high voltage circuit breaker closing are fulfilled, the EXE_CL output of the 52(1) and PO1 output (X100:6-7) is closed if closing command is given. Similarly when all the conditions of the low voltage circuit breaker closing are fulfilled, the EXE_CL output of the 52(2) and PO2 output (X100:8-9) is closed if closing command is given.

The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position.

Figure 96: Circuit breaker control – HV side

Figure 97: Circuit breaker control – LV side

Configuration also includes tap changer position indicator (84T), however by default it is not configured.

If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block 52 with PCM600, the function assumes that the breaker close commands are allowed continuously.

Page 108: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

102 RET615 ANSIApplication Manual

Figure 98: Tap changer position indicator

3.5.5.3 Functional diagrams for condition monitoring The functional diagrams for condition monitoring describe the IED’s condition monitoring functionality in detail and according to the factory set default connections.

Two trip circuit monitoring (TCM-1 and TCM-2) stages are provided to supervise the trip circuit of the high voltage and low voltage circuit breaker connected at PO3 (X100:15-19) and PO4 (X100:20-24) respectively.

Figure 99: Trip circuit monitoring HV and LV- side

The TCM-1 and TCM-2 functions are blocked by respective 86/94-1(1) and, 86/94-2(2) function block and the respective circuit-breaker open position signal.

The supervision alarm from TCM-1 and TCM-2 is connected to alarm LED 9.

A failure in current measuring circuits is detected by current circuit supervision function (MCS 3I, I2). When a failure is detected, function activates and can be used to block protection functions for example 87T, thus avoiding mal-operation.

By default it is expected that there is no external resistor in the circuit breaker tripping/closing coil circuit connected parallel with circuit breaker normally open/closed auxiliary contact.

Page 109: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 103Application Manual

Figure 100: Current circuit supervision

Similar to MCS 3I I2 function, a failure in voltage measurement circuit is detected by fuse failure supervision function (60(1)) available on high voltage side. The function is used to block the voltage protection and directional protection functions at failures in the secondary circuits between the voltage transformer and IED to avoid mal operation.

Figure 101: Fuse failure supervision - HV side

Two circuit breaker condition monitoring function (52CM(1) and 52CM(2)) one each is configured to supervise high voltage side and low voltage side circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision alarms.

Figure 102: Circuit breaker condition monitoring HV side

By default the FAIL output from MCS 3I, I2 function is only connected to disturbance recorder

Page 110: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

104 RET615 ANSIApplication Manual

Figure 103: Circuit breaker condition monitoring LV side

The supervision alarm from 52CM(1) and 52CM(2) is connected to alarm LED 9.

3.5.5.4 Functional diagrams for MeasurementsThe functional diagrams for measurement describe the IED’s measurement functionality in detail and according to the factory set default connections

The phase current inputs from high voltage and low voltage side are connected to the IED and are measured by high voltage and low voltage side three-phase current measurement (IA,IB,IC(1) and IA,IB,IC(2)). The three-phase voltage inputs from high voltage side are measured by high voltage side voltage measurement (VA,VB,VC(1)) function block respectively. The current input is connected to the X120 card in the back panel, whereas voltage input is connected to X130 card in the back panel. Similarly the sequence current for both high voltage and low voltage side and sequence voltage from high voltage side are measured by sequence current measurement (I1, I2, I0(1) and I1,I2,I0(2)) and sequence voltage measurement (V1,V2,V0(1)) function block respectively. The residual current and voltage is measured by residual current measurement (IG) and residual voltage measurement (VG) function block.

Apart from current and voltage measurement, configuration also provides single phase (SP, SE(1)) and three phase power and energy measurement (P,E(1)) along with frequency measurement (f) function block.

The measurements can be seen from the LHMI and is available using the measurement option in the menu selection. Based on the settings, ‘IA, IB, IC(1)’, IA,IB,IC(2), ‘VA,VB,VC(1)’,‘IG’ and ‘VG’ function blocks can generate low alarm/warning, high alarm/warning signals for the measured current values.

By default only POSOPEN and POSCLOSE information is available to 52CM(1) and 52CM(2).

Page 111: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 105Application Manual

Figure 104: Measurements

3.5.5.5 Functional diagrams for other functions Configuration also includes other miscellaneous basic functions which are not configured, but can be used for creating general purpose logics. These functions include:

• Four instance of Minimum Pulse Timer TP-1, TP-2, TP-3 and TP-4,

• Two instance of Pulse Timer PT-1 and PT-2,

• Two instance of Time delay off TOF-1 and TOF-2,

• Two instance of Time delay on TON-1 and TON-2,

• Two instance of Set reset logic SR-1 and SR-2 and

• Two instance of Move logic MV-1 and MV-2

3.5.5.6 Functional diagrams for logging functions The functional diagrams for logging describe the IED’s default disturbance recorder connections.

The disturbance recorder DFR consists of 64 channels. However as default few channel are connected to trigger the digital fault recorder are as shown in Figure 105. More connection can be made as per individual need. Also when disturbance recorder is trigger the analog values available at the analog inputs are recorded by fault recorder FR.

Page 112: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

106 RET615 ANSIApplication Manual

Figure 105: 64 channel Disturbance and fault recorder

3.5.5.7 Functional diagrams for I/O and Alarm LEDs The functional diagrams for I/O and Alarm LEDs describe the IED’s default input/output and alarm LEDs connections.

The default binary I/O connected in the configuration and Alarm LEDs are indicated in Figure 106 to Figure 108.

Page 113: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 107Application Manual

Figure 106: Binary inputs

Page 114: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

108 RET615 ANSIApplication Manual

Figure 107: Binary outputs

High speed binary outputs (HSO) are available only if IED with High speed binary card has been ordered.

Page 115: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 109Application Manual

Page 116: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

110 RET615 ANSIApplication Manual

Figure 108: Alarm LEDs

3.6 Standard Configuration for Order Code Functional Application DA

3.6.1 ApplicationsThe standard configuration includes three-phase transformer differential protection for two-winding transformers, numerical restricted ground-fault protection for the low voltage (LV) side. The standard configuration is mainly intended for protection of the power transformer between current transformers.

The IED with this standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enable this configuration to be further adapted to different primary power system layouts and the related functionality needs by modifying the internal functionality using PCM600.

Page 117: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 111Application Manual

3.6.2 FunctionsTable 31: Functions included in the RET615 standard configuration

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA04

DAProtection

Three-phase non-directional overcurrent protection, low stage, instance 1

PHLPTOC1 51P (1) 3I> (1) ●

Three-phase non-directional overcurrent protection, low stage, instance 2

PHLPTOC2 51P (2) 3I> (2) ●

Three-phase non-directional overcurrent protection, high stage, instance 1

PHHPTOC1 50P-1 (1) 3I>> (1) ●

Three-phase non-directional overcurrent protection, high stage, instance 2

PHHPTOC2 50P-1 (2) 3I>> (2) ●

Three-phase non-directional overcurrent protection, high stage, instance 3

PHHPTOC3 50P-2 (1) 3I>> (3) ●

Three-phase non-directional overcurrent protection, high stage, instance 4

PHHPTOC4 50P-2 (2) 3I>> (4) ●

Non-directional ground-fault protection, low stage, instance 1

EFLPTOC1 51G Io> (1) ●

Three-phase directional overcurrent protection, low stage, instance 1

DPHLPDOC1 67/51P (2) 3I> -> (1) ●

Three-phase directional overcurrent protection, low stage, instance 2

DPHLPDOC2 67/51P (1) 3I> -> (2) ●

Non-directional ground-fault protection, low stage, instance 2

EFLPTOC2 51N (1) Io> (2) ●

Non-directional ground-fault protection, low stage, instance 3

EFLPTOC3 51N (2) Io> (3) ●

Non-directional ground-fault protection, high stage, instance 1

EFHPTOC1 50G-1 Io>> (1) ●

Non-directional ground-fault protection, high stage, instance 2

EFHPTOC2 50G-2 Io>> (2) ●

Non-directional ground-fault protection, high stage, instance 3

EFHPTOC3 50N-1 (1) Io>> (3) ●

Non-directional ground-fault protection, high stage, instance 4

EFHPTOC4 50N-1 (2) Io>> (4) ●

Non-directional ground-fault protection, high stage, instance 5

EFHPTOC5 50N-2 (1) Io>> (5) ●

Non-directional ground-fault protection, high stage, instance 6

EFHPTOC6 50N-2 (2) Io>> (6) ●

Directional ground-fault protection, low stage, instance 1

DEFLPDEF1 67/51N (2) Io> -> (1) ●1)

Directional ground-fault protection, low stage, instance 2

DEFLPDEF2 67/51N (1) Io> -> (2) ●1)

Negative-sequence overcurrent protection, instance 1

NSPTOC1 46 (1) I2> (1) ●

Negative-sequence overcurrent protection, instance 2

NSPTOC2 46 (2) I2> (2) ●

Residual overvoltage protection, instance 2 ROVPTOV2 59N (2) Uo> (2) ●2)

Residual overvoltage protection, instance 3 ROVPTOV3 59N (1) Uo> (3) ●2)

Page 118: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

112 RET615 ANSIApplication Manual

Three-phase undervoltage protection, instance 1

PHPTUV1 27 (2) 3U< (1) ●

Three-phase undervoltage protection, instance 2

PHPTUV2 27 (1) 3U< (2) ●

Three-phase overvoltage protection, instance 1

PHPTOV1 59 (2) 3U> (1) ●

Three-phase overvoltage protection, instance 2

PHPTOV2 59 (1) 3U> (2) ●

Negative-sequence overvoltage protection, instance 1

NSPTOV1 47 (2) U2> (1) ●

Negative-sequence overvoltage protection, instance 2

NSPTOV2 47 (1) U2> (2) ●

Frequency protection, instance 1 FRPFRQ1 81-1 (2) f>/f<,df/dt (1) ●

Frequency protection, instance 2 FRPFRQ2 81-2 (2) f>/f<,df/dt (2) ●

Voltage per hertz protection, instance 3 OEPVPH3 24-1 (1) U/f> (3) ●

Voltage per hertz protection, instance 4 OEPVPH4 24-2 (1) U/f> (4) ●

Three-phase thermal overload protection for power transformers, two time constants

T2PTTR1 49T (1) 3Ith>T ●

Restrained (Low Stage) and unrestrained (High Stage) differential protection for 2W –transformers

TR2PTDF1 87T 3dI>T ●

Numerical restrained (low stage) low impedance restricted ground-fault protection

LREFPNDF1 87LOZREF (2) dIoLo> ●

Circuit breaker failure protection, instance 1 CCBRBRF1 50BF (1) 3I>/Io>BF (1) ●

Circuit breaker failure protection, instance 2 CCBRBRF2 50BF (2) 3I>/Io>BF (2) ●

Master trip, instance 1 TRPPTRC1 86/94-1 Master Trip (1) ●

Master trip, instance 2 TRPPTRC2 86/94-2 Master Trip (2) ●

Arc protection, instance 1 ARCSARC1 AFD-1 (2) ARC (1) ●

Arc protection, instance 2 ARCSARC2 AFD-2 (2) ARC (2) ●

Arc protection, instance 3 ARCSARC3 AFD-3 (2) ARC (3) ●

Load shedding and restoration, instance 1 LSHDPFRQ1 81LSH-1 (2) UFLS/R (1) ●

Load shedding and restoration, instance 2 LSHDPFRQ2 81LSH-2 (2) UFLS/R (2) ●

Loss of phase, instance 1 PHPTUC1 37 (1) 3I< (1) ●

Control

Circuit-breaker control, instance 1 CBXCBR1 52 (1) I <-> O CB (1) ●

Circuit-breaker control, instance 2 CBXCBR2 52 (2) I <-> O CB (2) ●

Tap changer position indication TPOSSLTC1 84T TPOSM ●

Condition Monitoring

Circuit-breaker condition monitoring, instance 1

SSCBR1 52CM (1) CBCM (1) ●

Circuit-breaker condition monitoring, instance 2

SSCBR2 52CM (2) CBCM (2) ●

Trip circuit supervision, instance 1 TCSSCBR1 TCM-1 TCS (1) ●

Trip circuit supervision, instance 2 TCSSCBR2 TCM-2 TCS (2) ●

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA04

DA

Page 119: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 113Application Manual

Advanced current circuit supervision for transformers

CTSRCTF1 MCS 3I, I2 MCS 3I, I2 ●

Fuse failure supervision, instance 1 SEQRFUF1 60 (1) FUSEF (1) ●

Fuse failure supervision, instance 2 SEQRFUF2 60 (2) FUSEF (2) ●

Measurements

Three-phase current measurement, instance 1 CMMXU1 IA, IB, IC (1) 3I ●

Three-phase current measurement, instance 2 CMMXU2 IA, IB, IC (2) 3I(B) ●

Sequence current measurement, instance 1 CSMSQI1 I1, I2, I0 (1) I1, I2, I0 ●

Sequence current measurement, instance 2 CSMSQI2 I1, I2, I0 (2) I1, I2, I0(B) ●

Residual current measurement, instance 1 RESCMMXU1 IG Io ●

Three-phase voltage measurement, instance 1 VMMXU1 VA, VB, VC (1) 3U ●

Three-phase voltage measurement, instance 2 VMMXU2 VA, VB, VC (2) 3U(B) ●

Sequence voltage measurement, instance 1 VSMSQI1 V1, V2, V0 (1) U1, U2, U0 ●

Sequence voltage measurement, instance 2 VSMSQI2 V1, V2, V0 (2) U1, U2, U0(B) ●

Single-phase power and energy measurement, instance 2

SPEMMXU2 SP, SE (2) SP, SE(B) ●

Three-phase power and energy measurement, instance 2

PEMMXU2 P, E (2) P, E(B) ●

Frequency measurement, instance 2 FMMXU2 f f ●

Other Functions

Minimum pulse timer (2 pcs), instance 1 TPGAPC1 TP-1 TP (1) ●

Minimum pulse timer (2 pcs), instance 2 TPGAPC2 TP-2 TP (2) ●

Minimum pulse timer (2 pcs), instance 3 TPGAPC3 TP-3 TP (3) ●

Minimum pulse timer (2 pcs), instance 4 TPGAPC4 TP-4 TP (4) ●

Pulse timer (8 pcs), instance 1 PTGAPC1 PT-1 PT (1) ●

Pulse timer (8 pcs), instance 2 PTGAPC2 PT-2 PT (2) ●

Time delay off (8 pcs), instance 1 TOFGAPC1 TOF-1 TOF (1) ●

Time delay off (8 pcs), instance 2 TOFGAPC2 TOF-2 TOF (2) ●

Time delay on (8 pcs), instance 1 TONGAPC1 TON -1 TON (1) ●

Time delay on (8 pcs), instance 2 TONGAPC2 TON -2 TON (2) ●

Set reset (8 pcs), instance 1 SRGAPC1 SR-1 SR (1) ●

Set reset (8 pcs), instance 2 SRGAPC2 SR-2 SR (2) ●

Move (8 pcs), instance 1 MVGAPC1 MV-1 MV (1) ●

Move (8 pcs), instance 2 MVGAPC2 MV-2 MV (2) ●

Logging Functions

Disturbance recorder RDRE1 DFR - ●

Fault recorder FLMSTA1 FR - ●

Sequence event recorder SER SER - ●1) Vo calculated and negative sequence voltage selectable by parameter, V2 as default Io selectable by parameter, I2 as default2) Vo calculated is used.

Function IEC 61850 ANSI C37.2-2008 IEC 60617 TA04

DA

Page 120: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

114 RET615 ANSIApplication Manual

3.6.3 Default Input/Output (I/O) assignmentsTable 32: Analog input connections for CTs

Table 33: Analog input connections for VTs

Table 34: Binary input connections

Analog input Default usage Connector pinsX120 – IA(2) Current input for phase IA, low voltage side X120 – 1, 2

X120 – IB(2) Current input for phase IB, low voltage side X120 – 3,4

X120 – IC(2) Current input for phase IC, low voltage side X120 – 5,6

X120 – IA(1) Current input for phase IA, high voltage side X120 – 7, 8

X120 – IB(1) Current input for phase IB, high voltage side X120 – 9,10

X120 – IC(1) Current input for phase IC, high voltage side X120 – 11,12

X120 – IG(2) Ground current input IG, low voltage side X120 – 13,14

Analog input Default usage Connector pinsX130 – VA(1) Voltage input for phase VA, high voltage side X130 – 7, 8

X130 – VB(1) Voltage input for phase VB, high voltage side X130 – 9,10

X130 – VC(1) Voltage input for phase VC, high voltage side X130 – 11,12

X130 – VA(2) Voltage input for phase VA, low voltage side X130 – 13,14

X130 – VB(2) Voltage input for phase VB, low voltage side X130 – 15,16

X130 – VC(2) Voltage input for phase VC, low voltage side X130 – 17,18

Binary input Default usage Connector pinsX110-BI1 X110-1, 2

X110-BI2 X110-3, 4

X110-BI3 X110-5, 6

X110-BI4 X110-7, 6

X110-BI5 Circuit breaker (2) closed position X110-8, 9

X110-BI6 Circuit breaker (2) open position X110-10,9

X110-BI7 Circuit breaker (1) closed position X110-11, 12

X110-BI8 Circuit breaker (1) open position X110-13, 12

Page 121: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 115Application Manual

Table 35: Binary output connections

Table 36: High speed binary output connections*

Table 37: Default LED assignment and label names

Binary output Default usage Connector pinsX100-PO1 Close circuit breaker (1) X100 – 6,7

X100-PO2 Close circuit breaker (2) X100 – 8,9

X100-SO1 Breaker failure backup trip to upstream breaker X100 – 11/12, 10

X100-SO2 X100 – 13, 14

X100-PO3 Open circuit breaker / Master Trip -1 X100 – 15,19

X100-PO4 Open circuit breaker / Master Trip -2 X100 – 20,24

X110-SO1* X110 – 15/16, 14

X110-SO2* X110 – 18/19, 17

X110-SO3* X110 – 21/22, 20

X110-SO4* X110 – 23,24

*Not available if IED has been ordered with High speed binary output (HSO) card

Binary output Default usage Connector pinsX110-HSO1 Trip from ARC-1 protection X110 – 15,16

X110-HSO2 Trip from ARC-2 protection X110 – 19,20

X110-HSO3 Trip from ARC-3 protection X110 – 23,24

*Available only if IED has been ordered with High speed binary output (HSO) card

LED LED labelLED 1 Phase A

LED 2 Phase B

LED 3 Phase C

LED 4 Neutral / Ground

LED 5 Time

LED 6 Instantaneous

LED 7 Differential / REF

LED 8 Voltage / Frequency

LED 9 Breaker Failure/Alarm

LED 10 Overload Alarm/Trip

LED 11 Arc Flash Detection

Page 122: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

116 RET615 ANSIApplication Manual

3.6.4 Typical connection diagrams

Page 123: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 117Application Manual

3.6.5 Functional diagramsThe functional diagrams describe the default input, output, RTD inputs, alarm LED and function-to-function connections. The default connections can be viewed with and changed with PCM 600 according to the application requirements, if necessary.

The analog channels, measurements from CTs and PTs, have fixed connections to the different function blocks inside the IED’s standard configuration.

The analog channels are assigned to different functions as shown in functional diagrams. The function and analog signal marked with (1) represents the function and analog signals (three phase currents/voltages) of the high-voltage side of the transformer and (2) represents the function and analog signals (three phase currents/voltage) on the low-voltage side of the transformer. The signal marked with IG represents the ground current measured between the start point of the transformer and grounding.

RET615 offers six different settings group which the user can set based on individual needs. Each group can then, be activated/ deactivated by using the setting group settings available in RET615.

3.6.5.1 Functional diagrams for protectionThe functional diagrams for protection describe the IED’s protection functionality in detail and according to the factory set default connections.

Three stages for both high-voltage and low-voltage sides as a total of six, three-phase overcurrent protection (51P(1), 50P-1(1), 50P-2(1), 51P(2), 50P-1(2), 50P-2(2)) stages are provided for overcurrent and short-circuit protection.

The operation of these functions is not blocked as default by any functionality and so setting should be set such as to avoid unnecessary false trip or alarm.

Figure 109: Three phase overcurrent protection – HV side

Page 124: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

118 RET615 ANSIApplication Manual

Figure 110: Three phase overcurrent protection – LV side

Configuration also includes two stages of three-phase directional overcurrent protection (67/51P(1) and 67/51P(2)) one each for high-voltage and low-voltage side. The operation of directional overcurrent protection is blocked by fuse failure supervision function (60(1) and 60(2)) of respective sides.

Figure 111: Three phase directional overcurrent protection – HV and LV side

The operation of 51P(1), 51P(2), 67/51P(1) and 67/51P(2) is connected to alarm LED 5, and 50P-1(1), 50P-2(1), 50P-1(2) and 50P-2(2) is connected to alarm LED 6.

Alarm LEDs 1, 2 and 3 are configured so as to indicate which phase has resulted into tripping of overcurrent protection. Overcurrent faults in Phase A, B and C is mapped to Alarm LEDs 1, 2 and 3 respectively.

Three stages for both high-voltage and low-voltage side as a total of six, ground fault (51N(1), 50N-1(1), 50N-2(1), 51N(2), 50N-1(2), 50N-2(2)) stages are provided for ground fault protection.

Page 125: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 119Application Manual

Figure 112: Ground fault protection – HV side

Figure 113: Ground fault protection – LV side

Configuration also includes three stages of ground fault protection (51G, 50G-1 and 50G-2).

Figure 114: Non-directional ground fault protection

Page 126: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

120 RET615 ANSIApplication Manual

The operation of these functions is not blocked as default by any functionality.

Two stages of directional ground fault protection (67/51N(1) and 67/51N(2)) one each for high-voltage and low-voltage side is included in the configuration. The operation of directional ground fault protection is blocked by fuse failure supervision function (60(1) and 60(2)) from respective sides.

Figure 115: Directional ground fault protection – HV and LV side

The operation of 51N(1), 51N(2), 51G, 67/51N(1) and 67/51N(2) is connected to alarm LED 4 and 5, and 50N-1(1), 50N-2(1), 50N-1(2), 50N-2(2), 50G-1 and 50G-2 is connected to alarm LED 4 and 6.

One stage of negative-sequence overcurrent protection (46(1) and 46(2)) for both high-voltage and low-voltage sides is provided for protecting transformer against thermal stress and damage. The operation of 46(1) and 46(2) is not blocked as default by any functionality.

Figure 116: Negative sequence protection –HV and LV side

Configuration also includes high side as well as low side pickup alarm, the pickup outputs from respective 50P-1, 50P-2, 51P, 51N, 50N-1, 50N-2, 46, 67/51P and 67/51N are connected together to have a combined overcurrent high voltage side and low voltage side pickup alarm which is connected to disturbance recorder as default.

Page 127: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 121Application Manual

Figure 117: Overcurrent pickup alarms – HV side

Figure 118: Overcurrent pickup alarms – LV side

The configuration includes restricted low-impedance ground-fault (87LOZREF(2)) protection function for low-voltage side of two-winding power transformers. The numerical differential current stage operates exclusively on ground faults occurring in the protected area, that is, in the area between the phase and neutral current transformers. An ground fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and ground.

The operation of 87LOZREF(2) is not blocked as default by any functionality. The operation of 87LOZREF(2) is connected to alarm LED 7.

Figure 119: Restricted low impedance ground fault protection – LV side

The restrained (Low Stage) and unrestrained (High Stage) differential protection for two winding transformers (87T) provides protection of power transformer unit including, for example, winding short-circuit and inter-turn faults. The IED compares the phase currents

Page 128: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

122 RET615 ANSIApplication Manual

on both sides of the transformer. If the differential current of the phase currents in one of the phases exceed the setting of the restrained (low stage) operation characteristic or the instantaneous protection stage of the function, the function provides a trip signal.

Figure 120: Transformer differential protection

For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in 87T.

The operation of 87LOZREF(2) and 87T is not blocked as default by any functionality. The operation of these protection functions is connected to alarm LED 7.

The thermal overload protection function (49T(1)) on HV side detects short and long term overloads under varying load conditions.

The alarm and operation of thermal overload protection function is connected to alarm LED 10.

Figure 121: Transformer thermal overload protection – HV side

Loss of load protection (37(1)) is provided on HV side of the transformer for detecting sudden loss of load on the transformer.

The operation of 37(1) is not blocked as default by any functionality.

Figure 122: Loss of load protection - HV side

By default 49T(1) is not configured in trip the circuit breaker.

Page 129: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 123Application Manual

For voltage protection, three-phase undervoltage (27(1) and 27(2)), three-phase overvoltage (59(1) and 59(2)), residual overvoltage (59N(1) and 59N(2)) and negative-sequence overvoltage (47(1) and 47(2)) protection functions are offered on high-voltage as well as on low-voltage side. The 27(1), 27(2), 47(1), 47(2), 59N(1) and 59N(2) protection functions are blocked if the fuse failure is detected.

Figure 123: Voltage protection – HV side

Figure 124: Voltage protection – LV sideConfiguration also includes two stages of Volts per Hertz protection (24-1(1) and 24-2(1)) function block on high voltage side to protect transformer under excessive flux density and saturation of the magnetic core. Function is not blocked by default.

By default 37(1) is not configured in trip the circuit breaker.

Page 130: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

124 RET615 ANSIApplication Manual

Figure 125: Over excitation protection – HV side

Two stages of frequency protection (81-1(2) and 81-2(2)) and load shedding (81LSH-1(1), and 81LSH-2(2)) function block are also available on low voltage side. 81-1(2) and 81-2(2) can be set to operate as under frequency or over frequency or as rate of change of frequency protection, whereas 81LSH-1(2) and 81LSH-2(2) can be set to operate as independent under frequency or as rate of change of frequency or under frequency with rate of change of frequency protection.

Figure 126: Frequency protection – LV side

Page 131: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 125Application Manual

Figure 127: Load shedding protection – LV sideThe operation of voltage and frequency protection functions is connected to alarm LED 8.

The circuit-breaker failure protection (50BF(1) and 50BF(2)) for both high-voltage and low-voltage side is initiated via the pickup input by a number of different protection functions in the IED. 50BF(1) and 50BF(2) offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents.

50BF(1) and 50BF(2) has two operating outputs: TRRET and TRBU. The TRBU output from both the high voltage and low-voltage side is used to give a backup trip to the circuit breaker feeding upstream. For this purpose, the TRBU output signal from both the function is connected to the output SO1 (X100: 10-11).

The TRBU output from 50BF(1) and 50BF(2) is connected to alarm LED 9.

Figure 128: Circuit breaker failure protection – HV side

By default voltage and frequency protection functions are not configured to trip the circuit breaker.

Page 132: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

126 RET615 ANSIApplication Manual

Figure 129: Circuit breaker failure protection – LV side

Three arc protection (AFD-1(2), AFD-2(2) and AFD-3(2)) stages are included as an optional function on low-voltage side of the transformer. The arc protection offers individual function blocks for three ARC sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check.

Figure 130: Arc protection – LV side

Trip signal from AFD-1(2) is connected to master trip on high voltage side, available at PO3 (X100: 15-19). Whereas the trip signal from AFD-2(2) is connected to master trip on low voltage side, available at PO4 (X100:20-24).

If the IED has been ordered with high speed binary outputs, then trip signal from AFD-1(2), AFD-2(2) and AFD-3(2) are also connected directly to high speed output HS01(X110:15-16), HS02 (X110:19-20) and HS03(X110:23-24) respectively.

The detection of arc fault is connected to alarm LED 11.

The TRRET operate output can be used for retripping its own circuit breaker through the Master Trip again. However this is not connected in present configuration.

Page 133: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 127Application Manual

Two master trip logics (86/94-1 and 86/94-2) are provided as a trip command collector. 86/94-1 collects the trip signals from 51P(1), 50P-1(1), 50P-2(1), 46(1), 50N-1(1), 50N-2(1), 50G-1, 50G-2, 51N(1), 51G, 87T, 87LOZREF(2), 67/51P(1), 67/51N(1) and AFD-1(2) protection functions and is connected to provide high voltage side trip to binary output PO3 (X100:16-19).

Open control commands to the high voltage circuit breaker from the local or remote is also connected directly to the output PO3 (X100:16-19) from high voltage circuit breaker control (52(1)) function block.

86/94-2 collects the trip signals from 51P(2), 50P-1(2), 50P-2(2), 46(2), 50N-1(2), 50N-2(2), 50G-1, 50G-2, 51N(2), 51G, 87T, 87LOZREF(2), 67/51P(2), 67/51N(2) and AFD-2(2) protection functions and is connected to provide low voltage side trip to binary output contact PO4 (X100:20-24).

Open control commands to the low voltage circuit breaker from the local or remote is also connected directly to the output PO4 (X100:20-24) from low voltage circuit breaker control (52(2)) function block.

Figure 131: Master trip logic – HV side

AFD-3(2) is not connected to any binary outputs for IED ordered without high speed binary outputs.

Page 134: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

128 RET615 ANSIApplication Manual

Figure 132: Master trip logic – LV side

86/94-1 and 86/94-2 provides the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button.

3.6.5.2 Functional diagrams for control functions The functional diagrams for control describe the IED’s control functionality in detail and according to the factory set default connections.

The high voltage and low voltage side circuit breaker closing is enabled when the respective ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and ground switch position status and the status of the Master Trip logics, gas pressure alarm and circuit-breaker spring charging. With the present configuration, the activation of respective ENA_CLOSE input is configured using only Master Trip logic 86/94-1(1) and 86/94-2(2) i.e. the circuit breaker cannot be closed in case master trip is active.

When all conditions of the high voltage circuit breaker closing are fulfilled, the EXE_CL output of the 52(1) and PO1 output (X100:6-7) is closed if closing command is given. Similarly when all the conditions of the low voltage circuit breaker closing are fulfilled, the EXE_CL output of the 52(2) and PO2 output (X100:8-9) is closed if closing command is given.

The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position.

Page 135: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 129Application Manual

Figure 133: Circuit breaker control – HV side

Figure 134: Circuit breaker control – LV side

Configuration also includes tap changer position indicator (84T), however by default it is not configured.

Figure 135: Tap changer position indicator

3.6.5.3 Functional diagrams for condition monitoring The functional diagrams for condition monitoring describe the IED’s condition monitoring functionality in detail and according to the factory set default connections.

Two trip circuit monitoring (TCM-1 and TCM-2) stages are provided to supervise the trip circuit of the high voltage and low voltage circuit breaker connected at PO3 (X100:15-19) and PO4 (X100:20-24) respectively.

If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block 52 with PCM600, the function assumes that the breaker close commands are allowed continuously.

Page 136: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

130 RET615 ANSIApplication Manual

Figure 136: Trip circuit monitoring HV and LV- sideThe TCM-1 and TCM-2 functions are blocked by respective 86/94-1(1) and, 86/94-2(2) function block and the respective circuit-breaker open position signal.

The supervision alarm from TCM-1 and TCM-2 is connected to alarm LED 9.

A failure in current measuring circuits is detected by current circuit supervision function (MCS 3I, I2). When a failure is detected, function activates and can be used to block protection functions for example 87T, thus avoiding mal-operation.

Figure 137: Current circuit supervision

Similar to MCS 3I I2 function, a failure in voltage measurement circuit is detected by fuse failure supervision function (60(1) and 60(2)) available for high voltage as well as low voltage side. The function is used to block the voltage protection and directional protection functions at failures in the secondary circuits between the voltage transformer and IED to avoid mal operation.

By default it is expected that there is no external resistor in the circuit breaker tripping/closing coil circuit connected parallel with circuit breaker normally open/closed auxiliary contact.

By default the FAIL output from MCS 3I, I2 function is only connected to disturbance recorder

Page 137: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 131Application Manual

Figure 138: Fuse failure supervision - HV and LV sideTwo circuit breaker condition monitoring function (52CM(1) and 52CM(2)) one each is configured to supervise high voltage side and low voltage side circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision alarms.

Figure 139: Circuit breaker condition monitoring HV side

Figure 140: Circuit breaker condition monitoring LV side

The supervision alarm from 52CM(1) and 52CM(2) is connected to alarm LED 9.

By default only POSOPEN and POSCLOSE information is available to 52CM(1) and 52CM(2).

Page 138: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

132 RET615 ANSIApplication Manual

3.6.5.4 Functional diagrams for MeasurementsThe functional diagrams for measurement describe the IED’s measurement functionality in detail and according to the factory set default connections

The phase current and voltage inputs from high voltage and low voltage side are connected to the IED and are measured by high voltage and low voltage side three-phase current measurement (IA,IB,IC(1) and IA,IB,IC(2)) and three-phase voltage measurement (VA,VB,VC(1) and VA,VB,VC(2)) function block respectively. The current input is connected to the X120 card in the back panel, whereas voltage input is connected to X130 card in the back panel. Similarly the sequence current and voltage for both high voltage and low voltage side is measured by sequence current measurement (I1, I2, I0(1) and I1,I2,I0(2)) and sequence voltage measurement (V1,V2,V0(1) and V1,V2,V0(2))function block respectively. The residual current is measured by residual current measurement (IG) function block.

Apart from current and voltage measurement, configuration also provides single phase (SP, SE(2)) and three phase power and energy measurement (P,E(2)) along with frequency measurement (f) function block.

The measurements can be seen from the LHMI and is available using the measurement option in the menu selection. Based on the settings, ‘IA, IB, IC(1)’, IA,IB,IC(2), ‘VA,VB,VC(1)’, VA,VB,VC(2)’,‘IG’ and ‘VG’ function blocks can generate low alarm/warning, high alarm/warning signals for the measured current values.

Figure 141: Measurements

3.6.5.5 Functional diagrams for other functions Configuration also includes other miscellaneous basic functions which are not configured, but can be used for creating general purpose logics. These functions include:

• Four instance of Minimum Pulse Timer TP-1, TP-2, TP-3 and TP-4,

• Two instance of Pulse Timer PT-1 and PT-2,

• Two instance of Time delay off TOF-1 and TOF-2,

Page 139: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 133Application Manual

• Two instance of Time delay on TON-1 and TON-2,

• Two instance of Set reset logic SR-1 and SR-2 and

• Two instance of Move logic MV-1 and MV-2

3.6.5.6 Functional diagrams for logging functions The functional diagrams for logging describe the IED’s default disturbance recorder connections.

The disturbance recorder DFR consists of 64 channels. However as default few channel are connected to trigger the digital fault recorder are as shown in Figure 142. More connection can be made as per individual need. Also when disturbance recorder is trigger the analog values available at the analog inputs are recorded by fault recorder FR.

Figure 142: 64 channel Disturbance and fault recorder

Page 140: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

134 RET615 ANSIApplication Manual

3.6.5.7 Functional diagrams for I/O and Alarm LEDs The functional diagrams for I/O and Alarm LEDs describe the IED’s default input/output and alarm LEDs connections.

The default binary I/O connected in the configuration and Alarm LEDs are indicated in Figure 143 to Figure 145.

Figure 143: Binary inputs

Page 141: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 135Application Manual

Figure 144: Binary outputs

High speed binary outputs (HSO) are available only if IED with High speed binary card has been ordered.

Page 142: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

136 RET615 ANSIApplication Manual

Page 143: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 3RET615 configurations

RET615 ANSI 137Application Manual

Figure 145: Alarm LEDs

Page 144: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 3 1MAC201230-MB B

RET615 configurations

138 RET615 ANSIApplication Manual

Page 145: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 4IED physical connections

RET615 ANSI 139Application Manual

Section 4 IED physical connections

4.1 Inputs

4.1.1 Auxiliary supply voltage inputThe auxiliary voltage of the IED is connected to terminals X100/1-2. At DC supply, the positive lead is connected to terminal X100-1. The permitted auxiliary voltage range is marked on the LHMI of the IED on the top of the HMI of the plug-in unit.

Table 38: Auxiliary voltage supply

4.1.2 Binary inputsThe binary inputs can be used, for example, to generate a blocking signal, to unlatch output contacts, to trigger the digital fault recorder or for remote control of IED settings.

Terminals X120/1-6 are binary input terminals. An additional BIO module can be included in slot 110.

Terminal DescriptionX100-1 + Input

X100-2 - Input

Page 146: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 4 1MAC201230-MB B

IED physical connections

140 RET615 ANSIApplication Manual

Table 39: Binary input terminals X110-1...13 included in configurations FA01 and FA02

Table 40: Binary input terminals X120-1...6

Terminal DescriptionX110-1 BI1, +

X110-2 BI1, -

X110-3 BI2, +

X110-4 BI2, -

X110-5 BI3, +

X110-6 BI3, -

X110-6 BI4, -

X110-7 BI4, +

X110-8 BI5, +

X110-9 BI5, -

X110-9 BI6, -

X110-10 BI6, +

X110-11 BI7, +

X110-12 BI7, -

X110-12 BI8, -

X110-13 BI8, +

Terminal DescriptionX120-1 BI1, +

X120-2 BI1, -

X120-3 BI2, +

X120-2 BI2, -

X120-4 BI3, +

X120-2 BI3, -

X120-5 BI4, +

X120-6 BI4, -

Page 147: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 4IED physical connections

RET615 ANSI 141Application Manual

Table 41: Binary input terminals X130-1...9, optional configuration FA01

4.1.3 Optional light sensor inputsIf the IED is provided with the optional communication module with light sensor inputs, the pre-manufactured lens-sensor fibers are connected to inputs X13, X14 and X15, see the Connection diagrams for the various configurations. For further information, see arc flash detector.

Table 42: Light sensor input connectors

4.2 Outputs

4.2.1 Outputs for tripping and controllingOutput contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable of controlling most circuit breakers. On delivery from the factory, the trip signals from all the protection stages are routed to PO3 and PO4.

Terminal DescriptionX130-1 BI1, +

X130-2 BI1, -

X130-2 BI2, -

X130-3 BI2, +

X130-4 BI3, +

X130-5 BI3, -

X130-5 BI4, -

X130-6 BI4, +

X130-7 BI5, +

X130-8 BI5, -

X130-8 BI6, -

X130-9 BI6, +

The IED is provided with connection sockets X13, X14 and X15 only if the optional communication module with light sensor inputs has been installed. If the arc flash detector option is selected when ordering an IED, the light sensor inputs are included in the communication module.

Terminal DescriptionX13 Input Light sensor 1

X14 Input Light sensor 2

X15 Input Light sensor 3

Page 148: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 4 1MAC201230-MB B

IED physical connections

142 RET615 ANSIApplication Manual

Table 43: Output contacts

4.2.2 Outputs for signallingOutput contacts SO1 and SO2 in slot X100 or SO1, SO2, SO3 and SO4 in slot X110 or SO1, SO2 and SO3 in slot X130 (optional) can be used for signalling on pickup and tripping of the IED. On delivery from the factory, the pickup and alarm signals from all the protection stages are routed to signalling outputs.

Output contacts of slot X110 are optional. Output contacts of slot X130 are available in the optional BIO module (BIOB02A).

Table 44: Output contacts X100-10...14

Terminal DescriptionX100-6 PO1, NO

X100-7 PO1, NO

X100-8 PO2, NO

X100-9 PO2, NO

X100-15 PO3, NO (TCM resistor)

X100-16 PO3, NO

X100-17 PO3, NO

X100-18 PO3 (TCM1 input), NO

X100-19 PO3 (TCM1 input), NO

X100-20 PO4, NO (TCM resistor)

X100-21 PO4, NO

X100-22 PO4, NO

X100-23 PO4 (TCM2 input), NO

X100-24 PO4 (TCM2 input), NO

Terminal DescriptionX100-10 SO1, common

X100-11 SO1, NC

X100-12 SO1, NO

X100-13 SO2, NO

X100-14 SO2, NO

Page 149: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 4IED physical connections

RET615 ANSI 143Application Manual

Table 45: Output contacts X110-14...24

Table 46: Output contacts X130-10...18

4.2.3 IRFThe IRF contact functions as an output contact for the self-supervision system of the protection IED. Under normal operating conditions, the IED is energized and the contact is closed (X100/3-5). When a fault is detected by the self-supervision system or the auxiliary voltage is disconnected, the output contact drops off and the contact closes (X100/3-4).

Table 47: IRF contact

Terminal DescriptionX110-14 SO1, common

X110-15 SO1, NO

X110-16 SO1, NC

X110-17 SO2, common

X110-18 SO2, NO

X110-19 SO2, NC

X110-20 SO3, common

X110-21 SO3, NO

X110-22 SO3, NC

X110-23 SO4, common

X110-24 SO4, NO

Terminal DescriptionX130-10 SO1, common

X130-11 SO1, NO

X130-12 SO1, NC

X130-13 SO2, common

X130-14 SO2, NO

X130-15 SO2, NC

X130-16 SO3, common

X130-17 SO3, NO

X130-18 SO3, NC

Terminal DescriptionX100-3 IRF, common

X100-4 Closed; IRF, or Vaux disconnected

X100-5 Closed; no IRF, and Vaux connected

Page 150: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 4 1MAC201230-MB B

IED physical connections

144 RET615 ANSIApplication Manual

Page 151: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

1MAC201230-MB B Section 5Glossary

RET615 ANSI 145Application Manual

Section 5 Glossary

100BASE-FX A physical media defined in the IEEE 802.3 Ethernet standard for local area networks (LANs) that uses fibre-optic cabling

100BASE-TX A physical media defined in the IEEE 802.3 Ethernet standard for local area networks (LANs) that uses twisted-pair cabling category 5 or higher with RJ-45 connectors

ANSI American National Standards InstituteBI Binary inputBI/O Binary input/outputBO Binary outputCB Circuit breakerCT Current transformerDFR Digital fault recorderDNP3 A distributed network protocol originally developed by Westronic.

The DNP3 Users Group has the ownership of the protocol and assumes responsibility for its evolution.

EMC Electromagnetic compatibilityGOOSE Generic Object Oriented Substation EventHMI Human-machine interfaceHW HardwareIEC 61850 International standard for substation communication and

modellingIED Intelligent electronic deviceIP address A set of four numbers between 0 and 255, separated by periods.

Each server connected to the Internet is assigned a unique IP address that specifies the location for the TCP/IP protocol.

IRIG-B Inter-Range Instrumentation Group's time code format BLAN Local area networkLC Connector type for glass fiber cableLCD Liquid crystal displayLED Light-emitting diodeLHMI Local human-machine interface

Page 152: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Section 5 1MAC201230-MB B

Glossary

146 RET615 ANSIApplication Manual

Modbus A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices.

MV Medium voltagePCM600 Protection and Control IED ManagerPO Power outputRJ-45 Galvanic connector typeRS-232 Serial interface standardRS-485 Serial link according to EIA standard RS485SO Signal outputTCP/IP Transmission Control Protocol/Internet ProtocolTCS Trip-circuit supervisionWAN Wide area networkWHMI Web human-machine interface

Page 153: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI
Page 154: Relion Transformer Protection and Control RET615 ANSI ... · PDF fileTransformer Protection and Control RET615 ANSI Application Manual. ... Section 1MAC201230-MB B 2 RET615 ANSI

Contact us

ABB Inc.Distribution Automation4300 Coral Ridge DriveCoral Springs, FL 33065, USAPhone:+1 (800) 523-2620Phone:+1 954-752-6700Fax:+1 954 345-5329www.abb.com/substationautomation

1MA

C20

123

0-M

B B

© C

opyr

igh

t 201

1C:\A

BB

\AB

B