24
T T E E C C H H N N I I C C A A L L M M A A N N U U A A L L R R E E F F R R I I G G E E R R A A T T E E D D A A I I R R D D R R Y Y E E R R NC SERIES NON-CYCLING NCG MODELS 75 - 150 T ABLE OF CONTENTS P AGE 1. INTRODUCTION 1 2. ABBREVIATED WARRANTY 1 3. REFRIGERATED DRYER NOMENCLATURE 2 4. RECEIVING AND INSPECTION 2 5. SAFETY AND OPERATION PRECAUTIONS 4 6. PRINCIPLES OF OPERATION 7 7. INSTALLATION AND INITIAL START-UP 10 8. SCHEDULED MAINTENANCE 12 9. TROUBLESHOOTING 14 10. WIRING DIAGRAMS 16 11. GENERAL ARRANGEMENT 21 12. PARTS IDENTIFICATION 22 13. ENGINEERING SPECIFICATIONS 23 ZEKS Compressed Air Solutions 1302 Goshen Parkway West Chester, Pennsylvania 19380 610-692-9100 800-888-2323 FAX 610-692-9192 WWW.ZEKS.COM NCTM 75-150G-CSTAT V03/04 COMPRESSED AIR SOLUTIONS TM PATENT # 6,186,223 C

REFRIGERATED AIR DRYER TECHNICAL MANUAL · entire air system of pressure. 6. Do not attempt to remove any part of the refrigeration system without removing and containing refrigerant

  • Upload
    others

  • View
    17

  • Download
    0

Embed Size (px)

Citation preview

TTEECCHHNNIICCAALL MMAANNUUAALLRREEFFRRIIGGEERRAATTEEDD AAIIRR DDRRYYEERR

NC SERIES NON-CYCLINGNCG MODELS 75 - 150

TABLE OF CONTENTS PAGE

1. INTRODUCTION 12. ABBREVIATED WARRANTY 13. REFRIGERATED DRYER NOMENCLATURE 24. RECEIVING AND INSPECTION 25. SAFETY AND OPERATION PRECAUTIONS 46. PRINCIPLES OF OPERATION 77. INSTALLATION AND INITIAL START-UP 108. SCHEDULED MAINTENANCE 129. TROUBLESHOOTING 14

10. WIRING DIAGRAMS 1611. GENERAL ARRANGEMENT 2112. PARTS IDENTIFICATION 2213. ENGINEERING SPECIFICATIONS 23

ZEKS Compressed Air Solutions1302 Goshen Parkway

West Chester, Pennsylvania 19380

610-692-9100 800-888-2323 FAX 610-692-9192WWW.ZEKS.COM

NCTM 75-150G-CSTAT V03/04

COMPRESSED AIR SOLUTIONSTM

PATENT # 6,186,223

C

1

1. INTRODUCTION

ZEKS Non-Cycling refrigerated air dryers remove moisture, oil vapor and other contaminantsfrom compressed air. These contaminants are detrimental to pneumatically operatedappliances, controls, instruments, machinery and tools. The dryer cools compressed air witha refrigeration unit to a temperature at which moisture in the air is condensed and separatedfrom the air stream. This temperature is approximately 36°F (2.2°C), and is known as dewpoint. This dryer can be easily installed in various pneumatic systems in which dry air isrequired or desired. Please refer to Principles of Operation for complete operating details.• For warning label information with French translations, refer to pages 4 & 5.• Pur obtenir i’informatione des etiquettes dangereuses avec la traductione en francais, s’il vous plait consul

ter les pages 4 & 5.

2. ABBREVIATED WARRANTY

Standard ZEKS Non-Cycle refrigerated dryers are warrantied to be free of defects in materialand workmanship for a period of 12 months from the date of start-up or 18 months from thedate of shipment. To validate the warranty, the registration card must be completed andreturned to ZEKS at the time of unit start-up. If no registration information is returned, thewarranty becomes effective on the original date of shipment from ZEKS Compressed AirSolutions.

Equipment must be installed and operated in accordance with ZEKS’ recommendations.ZEKS’ liability is limited to repair, replacement, or refund of purchase price, in kind, during thewarranty time period stated above. In no event shall ZEKS be liable for incidental orconsequential damages, even if the possibility of such incidental or consequential damageshas been made known to ZEKS Compressed Air Solutions. Normal maintenance andconsumable parts are not covered by this warranty.

EXCHANGERSNCG series dryers that utilize CFX® heat exchanger technology are covered by a prorated warranty for the replacement of the exchanger extending a maximum of 120 months(10 years). Following the standard warranty terms, the available warranty is as stated below.This prorated warranty applies to replacement of exchangers only and does not cover anylabor expense.

Prorated coverage of list prices: 13 to 48 months 100%49 to 60 months 70%61 to 72 months 50%73 to 84 months 30%85 to 96 months 20%97 to 120 months 10%

2

REFRIGERANT COMPRESSORSZEKS’ refrigerated dryer warranty includes prorated warranty for the replacement of therefrigerant compressor extending a maximum of 60 months (5 years). Following the standardwarranty terms, the available prorated warranty is as stated below. This prorated warrantyapplies to replacement compressors only and does not cover any labor expense.

Prorated coverage of list prices: 13 to 18 months 100%19 to 24 months 70%25 to 36 months 50%37 to 48 months 30%49 to 60 months 10%

Freight and labor coverage varies internationally. Contact your distributor for WarrantyPolicy limitations and additional information regarding warranty coverage.

The warranties expressed above are in lieu of and exclusive of all other warranties. Thereare no other warranties, expressed or implied, except as stated herein. There are no impliedwarranties of merchantability or fitness for a particular purpose, which are specificallydisclaimed.

3. REFRIGERATED DRYER NOMENCLATURE

NOMINAL*FLOW DESIGN CONDENSERSCFM TYPE SERIES TYPE POWER OPTIONS75 thru 150 NC = Non-Cycle G A=Air Cooled 1=115-1-60

2=230-1-603=220-1-50

O = STANDARD O = STANDARDW = WEATHERPROOF 1 = DPC™ Controller

* Nominal flows indicated are for 100°F inlet temperature,100°F ambient temperature and 100psig compressed air pressure.

3

4. RECEIVING AND INSPECTION

4.1 INSPECTIONUpon receiving your ZEKS air dryer, please inspect the unit closely. If rough handlinghas been detected, please note it on your delivery receipt, especially if the dryer will notbe uncrated immediately. Obtaining the delivery person’s signed agreement to anynoted damage will facilitate insurance claims.

4.2 UNPACKING AND HANDLING

To facilitate handling during shipment, all dryer packages have been mounted on a basethat provides for forklifting between two base channels. Forks should extend all the waythrough forklift channels to reduce unnecessary forces to the dryer during moving.Slings can be used to lift the crates, but spreader bars must be used to prevent theslings from exerting a force against the sides of the crate or the dryer.

Under no circumstances should any person attempt to lift heavy objects withoutproper lifting equipment (i.e. crane, hoist, slings or fork truck). Lifting any unitwithout proper lifting equipment may cause serious injury.

4

OSHA HeadingDescriptions

“Warning” is used to indicate ahazardous situation which has someprobability of death or severe injury.Warning should not be considered forproperty damage accidents unlesspersonal injury risk is present.

“Notice” is used to indicate a statement ofcompany policy as the message relatesdirectly or indirectly to the safety ofpersonnel or protection of property.Notice should not be associated directlywith a hazard or hazardous situation andmust not be used in place of “Danger,”“Warning,” or “Caution.”

“Caution” is used to indicate a hazardoussituation which may result in minor ormoderate injury.

CAUTION

NOTICE

1. Only qualified personnel shall be permitted to adjust, performmaintenance or repair this air dryer.

2. Read all instructions completely before operating unit.

3. Pull main electrical disconnect switch and disconnect anyseparate controls lines, if used, before attempting to work orperform maintenance on the unit.

4. Do not attempt to service any part while machine is in anoperational mode.

5. Do not attempt to remove any parts without first relieving theentire air system of pressure.

6. Do not attempt to remove any part of the refrigeration systemwithout removing and containing refrigerant in accordance withEPA and local regulations.

7. Do not operate the dryer at pressures in excess of its rating.

8. Do not operate the dryer without guards, shields and screen inplace.

9. Inspect unit daily to observe and correct any unsafe operatingconditions.

The user of any air dryer manufactured by ZEKS Compressed Air Solutions is herebywarned that failure to follow the above Safety and Operation Precautions may result inpersonal injuries or equipment damage. However, ZEKS Compressed Air Solutions doesnot state as fact, nor does it mean to imply, that the preceding list of Safety and OperatingPrecautions is all inclusive, and further, that the observance of this list will prevent allpersonal injury or equipment damage.

5. SAFETY AND OPERATION PRECAUTIONS

Because an air dryer is pressurized and contains rotating parts, the same precautions should be observed as with any piece of machinery of this type where carelessness in operation ormaintenance could be hazardous to personnel. In addition to obvious safety rules thatshould be followed with this type of machinery, safety precautions as listed below mustbe observed:

5

Air Under Pressure Will CauseInjury, Death Or Property Damage.• Do Not Exceed Pressure Rating.• Relieve Press. Before Servicing.• Do Not Modify/Repair/Rework

ASME Coded Pressure VesselsAs Insurance Rating Affected.

! READ INSTRUCTION MANUAL !

HIGH VOLTAGE Can Cause SevereInjury Or Death.• Some circuits may be energized

when switch is off.• Disconnect and lockout ALL

power sources before servicing.

! READ INSTRUCTION MANUAL !

Air Under Pressure Will CauseInjury, Death Or Property Damage• Relieve Press. Before Servicing.• Condensate Drain Discharges

Under Pressure.• Drain Requires Periodic

Cleaning (Service).

! READ INSTRUCTION MANUAL !

L'air sous pression causerades blessures graves, desdégats matériels et peutmême entrainer la mort

Ne pas excéder le taux depression

Relâcher la pression avant lamise en service de l'appareil

Ne pas modifier/réparer ouretravailler

Le taux de pression desvaisseaux est conforme auxrecommendations de l' ASME( American Society ofMechanical Engineers) et peutêtre vérifié lors d'un controle.

LIRE LE MANUELD'INSTRUCTIONS!

La haute tension peutentrainer des blessures gravesou même la mort

Certains circuits peuvent êtrechargés lorsque l'interrupteurest en position "fermé" (off)

· Déconnecter et vérouillerTOUTES les sourcesd'électricité avant la mise enservice de l'appareil

LIRE LE MANUELD'INSTRUCTIONS!

L'air sous pression causerades blessures graves, desdégats matériels ou mêmela mort

Relâcher la pression avantla mise en service del'appareil

· Condenser les tuyaux dedécharges sous pression

· Les tuyaux doivent êtrenettoyés régulièrement(service)

LIRE LE MANUELD'INSTRUCTIONS!

6

Removing fuses will notdisconnect power fromdryer. Always disconnectpower from ALL sourcesbefore performing service.

! READ INSTRUCTION MANUAL !

WARNING ATTENTION !

Retirer les fusibles ne déconnectera pas l'électricitéde l'appareil

TOUJOURS déconnecter toutes les sourcesd'électricité avant la mise en marche de l'appareil

LIRE LE MANUEL D'INSTRUCTIONS!

7

6. PRINCIPLES OF OPERATION

6.1 INTRODUCTIONZEKS Non-Cycling dryers remove moisture, oil vapor and other contaminants fromcompressed air by cooling the air temperature to 36°F (2.2°C). This cooling processcondenses the contaminants into liquid droplets which can then be easily removed fromthe air. The major systems of the dryer which contribute to its operation are thefollowing: Air System, Moisture Removal System, Refrigeration System and theControls System. The following paragraphs describe each of the systems in greaterdetail.

6.2 AIR SYSTEMThis system consists of the dryer components which are in contact with the compressedair. Referring to Figure 1 and following the bold “AIR FLOW”, hot saturated air from thecompressor enters the precooler/reheater where the air temperature is reduced prior toentering the chiller by the cool air exiting the air/moisture separator. This precoolingallows for the use of a smaller refrigeration system. The air then goes into the chillersection where it is further cooled to the desired dew point through direct heat transferwith evaporating refrigerant. The air continues to the separator where the moisture isremoved, thereby allowing the cool, dry air to return to the precooler/reheater. As the airpasses through the precooler/reheater the air temperature is elevated by the warm, wetinlet air. The air exiting the reheater portion of the dryer should be approximately 15-20°F lower than the inlet air temperature based on standard conditions at full rated flow.

6.3 MOISTURE REMOVAL SYSTEMLiquid droplets are removed from the air stream in the separator. As the air andliquid mixture passes through the separator it spins, slows down and then changesdirection. This causes the condensate to fall out of the air stream and collect in thebottom of the separator. The collected liquid is removed from the separator by atimed electric drain. On units equipped with the Z-Trol™ Controller, the electric drainvalve is replaced by a timed solenoid drain valve which is controlled by the Z-Trol™Controller. For units equipped with the solenoid drain valve, refer to the Z-TrolAddendum for details on setting the solenoid valve using the Z-Trol Controller.

FIGURE 1 - FLOW DIAGRAM

8

The standard timed electric drain valve is operated by a solid state timer located on thedrain assembly.

• To obtain the optimum time values for operation of the electric drain valve, set the off-time adjustment knob to five minutes and the on-time adjustment knob to ten seconds.

• After running the unit under full rated flow for approximately 30 minutes, verify thatwhen the electric drain opens, all of the accumulated liquid is discharged and then asmall burst of air.

• If a small amount of liquid and a large amount of air is discharged, decrease the on-time setting or increase the off-time setting. If there is all liquid and no air has beendischarged, increase the on-time setting or decrease the off-time setting.

• The on/off-time settings will vary accordingly to seasonal conditions. During thesummer when more moisture is present in the air system, a shorter on-timeincreasing the valve opening frequency is required. A longer valve off-time may beused during the winter months when moisture levels are lower.

6.4 REFRIGERATION SYSTEMThe Refrigeration System consists of all the components which handle refrigerantR404A. This is a hermetically sealed closed-loop system. Referring to Figure 1 andfollowing the dot-dash “REFRIGERANT FLOW,” refrigerant is shown leaving the chillerevaporator section, which in the process of removing heat is changed from a lowpressure liquid to a low pressure gas. This gas enters the suction side of thecompressor where it is compressed into a high pressure gas. The high pressure gas iscooled in the air or water cooled condenser section becoming a high pressure liquid. Itthen goes through a permanent filter-dryer that ensures the refrigerant system is free ofcontaminants. A small diameter capillary tube meters the refrigerant into the chiller’sevaporator. The pressure is reduced upon entering the chiller evaporator where itremoves heat from the air system. When there are low loads (low air flow rate or inlettemperature), a hot gas valve by-passes the condenser and throttling device (capillarytube). This valve maintains a minimum evaporator pressure of 76 psig, whichcorresponds to a chiller temperature of 34°F, thus preventing freeze-up.

TIMED ELECTRIC DRAIN -FIGURE 2

9

FIGURE 3 - HOT GAS BY-PASS VALVE

Do not rotate Hot Gas By-Pass valve adjustment nut fully clockwise. Full clockwise rotationmay result in refrigerant compressor damage. Any suction pressure setting above 90 psigis not recommended.

CAUTION

For Hot Gas By-Pass Valve adjustment note thefollowing:

• Turning the adjustment screw clockwise raisessuction pressure and exchanger temperature.

• Turning the adjustment screw counter-clockwisereduces suction pressure and exchangertemperature.

• All adjustments should be made without air flow(load) on the dryer.

6.5 CONTROLSZEKS’ Non-Cycling dryers incorporate automatic controls for proper operation. All dryercontrols are preset at the factory. A refrigerant suction pressure gauge is provided asstandard equipment. This gauge monitors the pressure of the refrigerant gas before itenters the compressor. When the refrigeration system is running, the suction pressurewill be controlled between 76 to 85 psig.

Note that for all models with the optional “Compustat™” microprocessor, refer to theCompustat™ Addendum

ZEKS air cooled models utilize a fan cycling switch to control the condensing temperature.This switch controls the condensing temperature by cycling the fan based on refrigerantdischarge pressure. When the unit reaches 275 psig, the fan cycling switch will run thefan until the discharged pressure is reduced to 195 psig.

All ZEKS Non-Cycling dryers include a Hot Gas By-Pass Valve to maintain suction pressureand temperature. This valve is necessary during low load applications to prevent freeze-upin the chiller section. The normal suction pressure for no load conditions should never dropbelow 72 psig. *This setting may need adjustment to match the load/ambient conditionsencountered.

*This adjustment is not a procedure covered under warranty as it is typically required for applicationspecific conditions.

10

7. INSTALLATION AND INITIAL START-UP

7.1 LOCATION AND MOUNTINGThe dryer must be located in an area where ambient temperature is not likely to exceed113°F (35°C) or be less than 40°F (4.5°C). The dryer must be located in an area thatprovides sufficient clearance from walls and other adjoining equipment to allow easyaccess for servicing and maintenance requirements. A minimum of 18 inches isrequired to allow free air flow to the condenser. Dryer must be installed on a level (<5°slope) sufrace for proper operation.

On installations with relatively steady flow rate, the dryer is normally connected after theair receiver. If loads fluctuate widely, the dryer should be positioned ahead of thereceiver with sufficient storage capacity downstream to prevent excessive air flowthrough the dryer.

7.2 PIPING AND VALVESInstall piping, fittings and accessory items as indicated in Figure 4. For bypass andisolating purposes, valves (A), (B), and (C) may be field installed (not furnished).

ZEKS 75-150 NCG models equipped with either a timed drain valve or optional solenoiddrain valve are furnished with a drain isolation valve (D). The isolation valve permitsmaintenance of the drain valve without isolating air flow to the dryer. To operate dryer,all valves labeled in Figure 4 are to be closed except valves (B), (C) and (D). Valve (A)is used for bypass purposes and valve (E) is for test and manual drain purposes.

7.3 FILTRATIONTo protect the air dryer from residualcompressor oil and to ensure max-imum dryer performance, a prefilter isrecommended. Highly efficientprefilters and afterfilters sized to yourdrying application can be provided byZEKS and are available factoryinstalled. Call your local distributor toselect the filter that best suits yourfiltration requirements. In addition toair filtration, condensate dischargeoil/water separators are available toaddress stringent EPA regulations.

FIGURE 4 - PIPING DIAGRAM

Failure to comply to the above instructions may result in equipment malfunction andwill void warranty.

NOTICE

Always use a backup wrench when making any threaded connection to the dryer.Failure to use a backup wrench may result in damaged tubing and components internal to the cabinet.

NOTICE

11

7.4 ELECTRICAL CONNECTION

Equipment is available in various electrical configurations. Providing power to these unitsis accomplished as follows:

115V/1/60: These units are supplied with a three-wire, 115V cord assembly asstandard. These units need only be plugged into a suitable 115V/1/60Hz poweroutlet.

230V/1/60 &: 220V/1/50: These units are furnished with a power cord with leads fora field installed plug. L1, L2, N & GND are indicated on the leads. Customer isresponsible for furnishing a suitable plug. This plug shall be wired according to theappropriate wiring diagram included in this manual.

A suitable fused disconnect switch or circuit breaker conforming to national and localcode requirements is recommended for all ZEKS equipment. See Section 13 of thismanual for voltage requirements and load data.

7.5 INITIAL START-UPAfter installation or a prolonged shutdown, start the dryer with no air load (no airflow). This enables the dryer to stabilize at its proper operating pressure andtemperature in the shortest time possible (typically within five minutes).

The following conditions should be observed during start-up:

• The suction pressure gauge will typically pull down to between 76 and 85psig. The Hot Gas By-Pass Valve may require adjustment at start-up. Referto Section 6.5 for details.

• The refrigerant discharge pressure will vary as indicated in the controlssection. Refer to section 6.5 for details.

For models with the optional Compustat Controller, refer to addendum.

NOTICE

Care must be used when choosing the circuit of single phase units to ensure that noexcessive voltage variations occur. This may affect the starting of the compressor andin extreme cases may cause a compressor burn out. Maximum allowable voltagevariation is +15% and -10% from rated voltage. Voltage variations exceeding thespecified tolerances will void warranty.

Never wire directly or connect any additional wires to the compressor junction box. Thiswill cause severe system malfunction.

NOTICE

NOTICE

12

• The “High Temp” alarm light will illuminate. The thermostat for this alarm samplesthe chilled compressed air. Shortly after flow has been introduced, the “High Temp”light will go out.

• The “Power On” light will illuminate.

• After a sufficient amount of time, air flow may be slowly introduced to the dryer.

• Set and adjust timed drain operation as described in Section 6.3.

8. SCHEDULED MAINTENANCE

8.1 INTRODUCTIONZEKS’ Non-Cycling refrigerated air dryer requires little maintenance. These dryersutilize hermetically sealed compressors and do not require any lubrication. The fanmotor requires lubrication at both oil ports every six months. However, it isrecommended you inspect and service your dryer at regular intervals to obtain maximumperformance.

8.2 REFRIGERANT CONDENSERFor proper operation, it is essential that the condenser fins remain free of dirt and dust. Therefore, regular cleaning is required. If the dryer is located in an area where dust isexcessive, more frequent inspections and cleaning may be required. An optionalambient air filter can be easily installed outside of the condenser. Contact your localZEKS distributor for details.

8.3 CONDENSATE DISCHARGE SYSTEMOn a minimum of a monthly basis, the operation of the drain should be checked.Periodically, the drain should be removed and cleaned to ensure no debris from thesystem is trapped inside. ZEKS NCG dryers are equipped with a drain isolationvalve,enabling the valves to be cleaned during dryer operation after the drain isolationvalve has been manually closed. The drain valve is located near the solenoid valve andrequires a quarter turn to isolate the drain from system pressure.

If your dryer is installed without a drain isolation valve (filter stop), failure todepressurize the dryer may result in serious injury. Do not remove the drain valvewithout depressurizing the unit.

13

CLEANING INSTRUCTIONS - COMPUSTAT EQUIPPED SOLENOID DRAIN

• Be sure dryer is depressurized or isolationvalve is closed.

• Disconnect drain body from filter stop.• Loosen connector screw to allow the electrical

connector assembly to be removed from theD.I.N. unit solenoid.

• Remove retainer nut and separate the valvebody from the D.I.N. unit solenoid.

• Unthread the plunger tube assembly in acounter-clockwise direction until plungerseparates from valve body.

• Clean beveled washer, thread gasket, springassembly and strainer with soap and water. DoNOT use solvents of any kind, as failure to theseals will occur. Be especially careful to cleanthe center brass orifice and the rubber gasketorifice on the orifice cup with a straight pin.

• Reassemble all drain components after the drain has been cleaned and inspected. Repositionthe orifice hole on the rubber gasket of the orifice cup in the line and closest to the arrowindicated on the valve body.

• Reassemble valve and install in reverse order as described above.

CLEANING INSTRUCTIONS - DRAIN STRAINER

• Be sure dryer is depressurized or isolation....valve is closed.• Unscrew strainer end cap from isolation

valve body.• Remove strainer from isolation valve body.• Clean strainer with soap and water. Do not

use solvents when cleaning strainer.• Reinsert strainer into isolation valve body,

insuring strainer is properly seated.• Attach strainer end cap to isolation valve

body.• Figure shows unit with electric timed drain

valve. Solenoid valve similar.

DRAIN STRAINER DETAIL

SOLENOID VALVE DETAIL

14

9.2 PROBLEM / ACTION GUIDE

PROBLEM

Moisture down stream

SYMPTOM(S)

Dryer is properlycooling air stream(Outlet substantiallycooler than inlet)

POSSIBLECAUSE

Drain failure or timeradjustment is required

Excessive flow

CORRECTIVE ACTION

Dismantle and clean drain and / orstrainer. Repair or replace asnecessary.

Depress “Test” button (“Drain”button on optional solenoid drainwith Z-Trol) - if drain valveoperates, adjust timing.

For optional solenoid drain,depress “Drain” button - if red LEDdrain energized indicator comes onbut valve does not open, ensurewiring connections are secure andpower is being applied to thesolenoid coil. If valve continuesnot to open, clean as described inSection 8.3*

Depress “Test” button on drain - if“ON” indicator does not illuminate,ensure wiring connections aresecure. If valve continues to notoperate, Contact distributor.

For optional solenoid drain,depress “Drain” button - if red LEDdrain energized indicator does notcome on, contact distributor.*

Check inlet and outlet pressuresand system design capacity.Correct cause of excessive flow.

9. TROUBLESHOOTING

9.1 INTRODUCTIONZEKS Non-Cycling dryers are designed for reliable, trouble-free operation. In the event ofany dryer malfunction, the guide shown on the next page has been developed to facilitate problem identification and corrective actions.

Prior to working on the unit, make sure that all circuit breakers or disconnect switchesare tagged off “OUT OF SERVICE”.

An air dryer always operates under pressure. Before any maintenance procedure thatrequires disassembly of any piping, fittings, valves or other components is performed,the dryer must be isolated from the compressed air stream and fully depressurized.

15

PROBLEM

Moisture downstream

High pressuredrop across dryer

SYMPTOM

Inlet and outlettemperatures arethe same

Outlet pressuresubstantially lowerthan inlet pressure

POSSIBLE CAUSE

Dryer by-pass notclosedNo power to thedryerHigh suctionpressureRefrigerant leak

Compressor notrunning

Inlet and outletvalves notcompletely openInlet and outletfilters blocked upSuction pressurebelow 76 psig andunit operating toocoldNo dryer prefilterand heat exchangerhas becomeclogged

CORRECTIVE ACTION

Close by-pass valve

Check power supply andfuses/circuit breakersClean condenser fins

Check suction pressure gaugeand if 0 psig, turn dryer off andcontact your distributorClean condenser finsCheck ambient temperature andreduce below 120°FCheck fan motor if not running,contact your local distributorContact your local distributor forfurther assistance

Open valves

Change filter elements

Adjust suction pressure perSection 6.5

Flush air system as required.Consult your local distributor.

16

10. WIRING DIAGRAMS

Wiri

ng D

iagr

am75

-150

NC

GA

115/

1/60

HZ

Dra

win

g #

TM50

0135

A

17

Wiri

ng D

iagr

am75

-150

NC

GA

230V

/1/6

0HZ

& 22

0V1/

50H

ZD

raw

ing

# TM

5001

39B

18

Wiri

ng D

iagr

am15

0NC

GA

115V

/1/6

0HZ

With

Com

pust

at™

Con

trolle

rD

raw

ing

# TM

5001

37A

19

Wiri

ng D

iagr

am75

-150

NC

GA

230V

/1/6

0HZ

& 22

0V/1

/50H

ZW

ith C

ompu

stat

™ C

ontro

ller

Dra

win

g #

TM50

0141

B

20

Wiring DiagramSingle Phase 60 HZ

EMBRACO Compressor ConnectionsDrawing # 500100-C

21

11. GENERAL ARRANGEMENT

Gen

eral

Arra

ngem

ent

Dra

win

g #T

M50

0202

22

12.

PAR

TS ID

ENTI

FIC

ATIO

N75

NC

G10

0NC

G12

5NC

G15

0NC

G11

0/1/

6023

0/1/

6022

0/1/

5011

0/1/

6023

0/1/

6022

0/1/

5011

0/1/

6023

0/1/

6022

0/1/

5011

0/1/

6023

0/1/

6022

0/1/

501

Exc

hang

er A

ssy

7477

2574

7725

7477

2574

7725

7477

2574

7725

7477

9174

7791

7477

9174

7791

7477

9174

7791

2E

lect

ric D

rain

Val

ve68

3242

6832

4368

3243

6832

4268

3243

6832

4368

3242

6832

4368

3243

6832

4268

3243

6832

433

Com

pres

sor

6832

1068

3208

6832

0968

3211

6832

7168

3212

6825

8868

2592

6825

8968

2588

6825

9268

2589

4C

ompr

esso

r Ele

ctric

s K

it68

3283

6832

8168

3282

6832

8468

3286

6832

8568

3016

6830

2068

3017

6830

1668

3020

6830

175

Con

dens

er69

7172

6971

7269

7172

6971

7269

7172

6971

7269

7172

6971

7269

7172

6971

7269

7172

6971

726

Fan

Mot

or69

7304

6000

8360

0083

6973

0460

0083

6000

8369

7304

6000

8360

0083

6973

0460

0083

6000

837

Fan

Bla

de69

7186

6971

8669

7186

6971

8669

7186

6971

8669

7186

6971

8669

7186

6971

8669

7186

6971

868

Fan

Bra

cket

7478

9974

7899

7478

9974

7899

7478

9974

7899

7478

9974

7899

7478

9974

7899

7478

9974

7899

9Fi

lter D

ryer

6980

4569

8045

6980

4569

8045

6980

4569

8045

6980

4569

8045

6980

4569

8045

6980

4569

8045

10G

auge

(Suc

tion)

6826

0268

2602

6826

0268

2602

6826

0268

2602

6826

0268

2602

6826

0268

2602

6826

0268

2602

11S

witc

h, O

n/O

ff69

9611

6997

5469

9754

6996

1169

9754

6997

5469

9611

6997

5469

9754

6996

1169

9754

6997

5412

Ligh

t, H

i Tem

p69

7297

6973

0069

7300

6972

9769

7300

6973

0069

7297

6973

0069

7300

6972

9769

7300

6973

0013

Tsta

t (H

igh

Tem

p)69

7277

6972

7769

7277

6972

7769

7277

6972

7769

7277

6972

7769

7277

6972

7769

7277

6972

7714

Pow

er C

ord

6815

3268

3232

6832

3268

1532

6832

3268

3232

6815

3268

3232

6832

3268

1532

6832

3268

3232

15H

ot G

as B

y-P

ass

6973

4169

7341

6973

4169

7341

6973

4169

7341

6973

4169

7341

6973

4169

7341

6973

4169

7341

16Fa

n S

witc

h68

2256

6822

5668

2256

6822

5668

2256

6822

5668

2256

6822

5668

2256

6822

5668

2256

6822

56

Part

s O

verv

iew

23

13.

ENG

INEE

RIN

G S

PEC

IFIC

ATIO

NS

MA

XM

IN C

IRC

UIT

MA

XIM

UM

MO

DE

L N

OV

OLT

S/P

H/H

ZH

PR

LALR

AQ

TYH

PR

LALR

ATY

PE

LBS

OZ

KG

SFU

SE

AM

PA

CIT

YLB

SK

GS

WO

RK

ING

PR

ES

SU

RE

75N

CG

A10

011

5/1/

601/

48.

034

.01

1/18

1.80

2.3

R40

41

120.

794

1511

.914

068

.030

0 P

SIG

75N

CG

A20

023

0/1/

601/

44.

015

.31

1/18

0.90

1.2

R40

41

120.

794

156.

014

068

.030

0 P

SIG

100N

CG

A10

011

5/1/

601/

29.

233

.61

1/18

1.80

2.3

R40

41

80.

680

2013

.517

579

.030

0 P

SIG

100N

CG

A20

023

0/1/

601/

24.

924

.81

1/18

0.90

1.2

R40

41

80.

680

107.

117

579

.030

0 P

SIG

125N

CG

A10

011

5/1/

601/

213

.057

.01

1/18

1.80

2.3

R40

42

51.

049

2011

.617

579

.030

0 P

SIG

125N

CG

A20

023

0/1/

601/

26.

530

.01

1/18

0.90

1.2

R40

42

51.

049

159.

117

579

.030

0 P

SIG

150N

CG

A10

011

5/1/

601/

213

.057

.01

1/18

1.80

2.3

R40

42

81.

136

2012

.717

579

.030

0 P

SIG

150N

CG

A20

023

0/1/

601/

26.

530

.01

1/18

0.90

1.2

R40

42

81.

136

159.

117

579

.030

0 P

SIG

CO

MP

RE

SS

OR

FAN

SR

EFR

IGE

RA

NT

WE

IGH

T

Not

e: M

axim

um p

ress

ure

ratin

g of

tim

ed e

lect

ric d

rain

val

ve is

230

psi

g. D

o no

t ope

rate

dry

er a

t pre

ssur

es g

reat

er th

an 2

30 p

sig

onun

its e

quip

ped

with

tim

ed e

lect

ric d

rain

val

ve.

Spec

ifica

tion

info

rmat

ion

abov

e ac

cura

te a

t tim

e of

pub

licat

ion.

Ref

er to

equ

ipm

ent

seria

l lab

el fo

r act

ual r

efrig

eran

t cha

rges

and

spe

cific

atio

ns.

NO

TIC

E