RL-Series pole mounted load break switch / sectionaliser

recloser nulec 2

Embed Size (px)

Citation preview

Page 1: recloser nulec 2

RL-Series pole mounted load break switch / sectionaliser

Page 2: recloser nulec 2

2

The Nu-Lec Industries RL27 pole mountedgas insulated load break switch is availablein manual and automatic models. Theautomatic model can be configured as aremotely controlled switch, or as asectionaliser. These automatic switchesprovide the features of traditional loadbreak switches and sectionalisers, plus thebenefits of an up to date design optimisedfor automation, remote control andmonitoring, now or in the future.

The development of these new productswas driven by customer demand forimproved return on capital investment inthe distribution network. After carefullyevaluating customers needs, the Nu-LecIndustries RL27 was developed to achieveoptimum performance and reliability,making use of the very latest in availabletechnology in SF6 arc interruption andmicroelectronics. The result is acompetitive world class product of whichwe are justly proud.

Today, your customers, the electricityconsumers, are demanding reducedoutages, and lower tariffs. We at Nu-LecIndustries are continually working toprovide advanced equipment needed fortomorrow’s competitive electricitydistribution system.

In the past, distribution equipment such asload break switches has been purchasedonly to support load growth. Now by usingthis technologically advanced equipment,operating costs will be reduced andrevenue will be increased through bettermanagement of existing plant.

In addition to pole mounted load breakswitches and sectionalisers, Nu-LecIndustries also manufactures a range ofremotely controlled and monitored 12kV,24kV and 36kV automatic circuit reclosers(circuit breakers), and remote control andmonitoring software.This product family isa complete solution for distribution systemautomation.

Reduced Purchase Cost• The RL27 is offered in a modular concept that allows you to purchase a basic

switch and upgrade it in the future to achieve remote control or automationdepending on which model you choose.

• Remote terminal unit (RTU) and modem is included in the standardequipment for the automated switch. No additional RTU, modem, radio powersupply, batteries, wiring, connectors or enclosures are required.

Reduced Installation Costs• For the 15kV product bare terminals are provided and for the 27kV product a

400A insulated cable tail kit.• A cross arm mounting bracket is provided in the standard package.• Commissioning of the unit is simple. Configuration of the automated switch is

menu driven from the Operator Control Panel in the control cubicle (ifordered).

Reduced Operating Costs• In the case of sectionalisers, the integral current sensing logic provides fast

isolation of the fault, reducing damage.• The automatic load break switch or sectionaliser constantly monitors line

current, without the need for additional statistical measurement devices. Thisdata can then be used for forward planning and optimisation of existing plant.This will reduce distribution system losses.

• Long Lifetime, low maintenance equipment reduces lifetime cost.

Remote Control & MonitoringWhen used with a compatible Distribution Automation System (DSA), or SCADAsystem, the Nu-Lec Industries pole mounted load break switches andsectionalisers, support remote control and monitoring to provide the followingadvantages:• Information on load break switch and sectionaliser states and fault current

values transmitted to system control allows fast location of the faulted linesection which reduces travelling time of line crews.

• This same information allows informed remote switching which reduces theaffected area, and quickly restores supply, thus improving quality of supply.

• The load break switch and sectionalisers can be configured and settingsmanaged from system control, without technicians having to visit eachindividual device in the field, to change configuration settings, withconsequent reduction in staffing, and improved system integrity.

Increased Revenue• Supply can be quickly restored to unaffected areas, which results in less

outage time and therefore increased revenue.

Deferred Capital Works• Remotely controlled and monitored load break switches and sectionalisers

give an improved knowledge of the system, and improved system control.Feeder and substation load can then be remotely managed and switched,providing cross re-inforcement of substations, and improving utilisation ofexisting plant. Purchase of new plant can most likely be deferred for aconsiderable period of time.

Introduction and Features

Nu-Lec IndustriesRL-Series

Page 3: recloser nulec 2

3

Nu-Lec Industries’ range of RL series SF6 gas switches aredesigned to meet the growing requirements for oil free,maintenance free, long life, maximum safety and future feederautomation. The SF6 gas as the insulating and arc quenching media together with puffingprinciple ensure the positive breaking of small current, mainly active load current,cable charging current and magnetising current. The extremely short arcing times(within half a cycle) plus tulip type contacts with arc resistant (Cu-W) materialensure the long switching life and extended short circuit making capability.

The interrupters are ganged together and driven by an over-centering springmechanism. This is operated either manually or by a DC motor in a motorcompartment below the tank.

A manual operating arm allows hookstick operation from ground level. By pulling onthe appropriate side of the arm the load break switch can be tripped or closed. Themechanism is "operator independent" so that it does not matter how fast or slowthe arm is moved by the operator. A motor mechanism is used in feederautomation schemes to facilitate remote control.

Modular designProduct Type MR and RC

Product Type MR comprises an operating mechanism as described above. Anoptional motor pack can be purchased to upgrade from Product type MR to RC.This allows the unit to be interfaced to a Nu-Lec Industries or third party controlcubicle to provide local and/or remote control.

Product Type MA, A and FA

Product type MA comprises an operating mechanism as described above andCurrent Transformers (CTs) and Capacitive Voltage Transformers (CVTs) are builtinto the tank. The CTs and CVTs are available for line sensing in Product Type FA.To provide local and/or remote control, an optional motor pack can be purchased toupgrade from Product type MA to A.

Product type FA includes all options. The CTs and CVTs are connected to thecontrol electronics to provide fault detection, line sensing, measurement andsectionaliser functionality. The control cubicle houses the Operator Control Panel,microelectronics and the electronic controller that monitors the load break switchand provides sectionaliser functions. Combined together, the load break switch andcontrol cubicle form a remotely controlled and monitored pole mounted load breakswitch / sectionaliser.

In Product type FA the control electronics measures the making/breaking currentevery time the load break switch operates. This measured current is then used tocalculate the amount of contact wear each interrupter has suffered and the contactlife remaining is reduced accordingly. The remaining contact life is held in theswitchgear memory and can be displayed on the Operator Control Panel.

Safe designIn the event of an internal arc fault, a vent on the side of the load break switchruptures to vent the over-pressure. This eliminates the risk of explosion ordetachment from the power pole and since the unit is not oil filled, a major firehazard is eliminated.

Product Type MA, A and FA includes two additional safety features. Firstly a LowPressure Interlock which locks the operating mechanism if the gas pressure in thetank drops below a pre-set threshold. Secondly a Mechanical Locking Ring isprovided to lock the operating mechanism when the ring is pulled to the lockposition using a hookstick. The MR and RC products do not include the gaspressure interlock or mechanical locking ring but does include the over-pressurevent.

Easy InstallationHigh voltage connections on the 27kV models are made with insulated cable tailsterminated on epoxy bushings. The cable and bushings are covered by a grippingelastomeric boot that is filled with silicone grease to form an insulated system.

Bare terminals instead of covered assemblies are used on the standard 15kVmodels.

The switch is mounted using the standard cross arm mounting bracket.

Gas Insulated SwitchOverview and Operation

Nu-Lec Industries RL-Series

Modular design

Load Break Switch

SF6 switch

Motor Control Cubicle

CVTCVT

CT

SF6 switch

Motor Control Cubicle

Localcontrol

Localcontrol

Product type MR and RC

Product type MA, A and FA

Remotecontrol

Product Type MR

Product Type RC

Optional userremote control

Product Type MA

Product Type A

Product Type FA

Operator controlpanel

Mechanismcontrol

Sectionaliser &Fault detection

ElectricalMeasurement

RTU andmodem

Page 4: recloser nulec 2

The advanced fault detection, data logging and communicationsabilities of the RL-Series load break switch / sectionaliser aremade possible by the technology housed in the control andcommunications cubicle (suppllied with Product Type FA only). Ithas been designed especially for outdoor, pole mounted operationand is normally mounted low on the pole for ease of access bymaintenance personnel.The cubicle is insulated and designed to minimise any temperature rise resultingfrom solar heating. An internal equipment panel is used to mount all the equipment,including the batteries, storage capacitors, mains transformer, low voltage circuitbreakers, Control And Protection Module (CAPM), operator control panel and radioor modem. These components are carefully located so that the heat generatingparts are at the top, while the battery is at the bottom to keep it cool. In this waybattery life in excess of 5 years can be achieved.

All weather access is provided to the Operator Control Panel through a lockabledoor on the front of the control cubicle. Vents are screened against vermin entryand the door is sealed against the outer with a rubber extrusion. All electronic partsare well protected from entry of moisture and condensation ensuring a long lifetime.

Three models of control and communications cubicle are available, Tropical,Moderate and Temperate. The Tropical version is well ventilated and is suitable forclimates where the ambient temperature can reach 50°C and only occasionallygoes below 0°C, with a lower limit of -10°C.

The Moderate version has reduced ventilation and is used where temperaturesrarely go above 40°C and occasionally go below -5°C, with a lower limit of -15°C.

The Temperate model has a heater installed, making it suitable for climates wherethe temperature rarely goes above 40°C but can fall as low as -30°C.

All three cubicles are fitted with the same electronics and incorporate the functionsof an overcurrent through-fault detector, a sensitive earth fault relay and a remoteterminal unit. Additionally, the electronics measure line current, voltage, real andreactive power, fault currents, and stores these for transmission or off-line analysis.

A unique feature of the RL-Series pole mounted load break switch / sectionaliser isthe built in microprocessor controlled power supply. This provides uninterruptedoperation of not only the load break switch and fault detector, but also thecommunications radio or modem. No other power supplies are required forconnection into your SCADA or Distribution Automation System.

Due to careful design the efficiency of all parts is extremely high, allowing a batteryhold up time of five days after auxiliary supply failure (from fully charged battery,excluding telemetry radio or modem usage). The architecture used has theadvantage that the switch operation is independent of the high voltage supply,relying on a set of batteries charged by the auxiliary supply.

Due to sophisticated power supply management techniques, a switch operation isalways guaranteed when attempted and alarms are raised over the telemetry whenauxiliary power is lost.

A communications radio or special modem can be mounted within the control andcommunications cubicle. A V23 FSK modem is included as standard equipment.

4

Communications CubicleOverview (Type FA only)

Pole Top Control & Communications Cubicle

Control and Protection Module (CAPM) Circuit Board

Nu-Lec IndustriesRL-Series

Page 5: recloser nulec 2

The fully automated (Product Type FA) pole mounted load breakswitches / sectionalisers provide many outstanding advantages tothe user. New and innovative features have been made possibleby the intimate way the pole mounted switch and communicationscubicle work together. The block diagram below shows how thetwo items can be interfaced. The heart of the unit is the Controland Protection Module (CAPM) and the intelligent OperatorControl Panel.HV Line signals are connected into the electronics module by direct connection tothe analogue front end. Special extended range current transformers provide arange from 10A to 16,000A for measurement and fault detection. Embeddedvoltage screens accurately image the primary voltage value and phase relationship,allowing measurement of voltage, current and phase angle in the electronicmodule.

Each load break switch / sectionaliser is provided with an operator control panelwhich has a four line liquid crystal display with back lighting for night operation.From here a user can access and program the many measurement and faultdetection features available.

Three levels of user interface with the operator control panel are provided asfollows:

1. Operator Level

This allows basic operation like Trip, Close and display of settings, such as:• Sectionaliser settings and fault history• Line measurements and historical data• Alarms/Status such as:

Auxiliary supply fail, Battery failGas lossLive LineRemote/Local Control

2. Technician Level

This level is password protected at the user’s discretion in the “Engineer Level” andallows the setting of all sectionaliser related parameters.

3. Engineer Level

This is accessible through a laptop or desktop computer and allows setting of thepassword and access to all the Operator and Technician Level functions.

Telemetry InterfaceThe RL-Series pole mounted load break switch / sectionaliser can be interfaced toyour SCADA system either through its built-in V23 modem and a radio, or itsRS232 port and a modem of your choice. A variable voltage uninterruptable powersupply is included for the radio or modem, which can be mounted inside thecommunications cubicle. Almost all telemetry protocols can be supported. DNP3and IEC870 are two of the available protocols.

Computer InterfaceThe Windows Switchgear Operating System (WSOS) is an advanced personalcomputer based software package to allow off-line and on-line programming,monitoring and control of a load break switch /sectionaliser via the RS232 port.This is available as an option to the basic RL-Series load break switch /sectionaliser.

Remote ControlAs an additional option, Nu-Lec Industries offers the WSOS multiple connect PCbased software package to individually remote control and monitor a population offield mounted reclosers and/or load break switches. The system communicates withthe control cubicle by either cable, fibre optic, telephone line or radio. WSOSprovides additional features such as alarm and event handling, dial in and dial outfacilities and report generation.

5

Block Diagram & Features(Type FA only)

Operator Control Panel

Load break switch / sectionaliser block diagram

PRES

SUR

ESE

NSO

R

AU

XILI

AR

YSW

ITC

HES

SF6

INTE

RR

UPT

ER

MEM

OR

Y

HV LINE 3 PHASES CVTCT

LOAD BREAK SWITCH

CVT

CO

NTR

OL

CA

BLE

RA

DIO

MO

DEM

REM

OTE

I/O C

AR

D

OPE

RA

TOR

SUB

SYS

TEM

PAN

EL

BA

TTER

Y

AN

ALO

GU

E FR

ON

T EN

D

AN

ALO

GU

E TO

DIG

ITA

LC

ON

VER

SIO

N

DIGITAL INTERFACE

MICROPROCESSOR

MO

DEM SERIAL

INTERFACE

MO

TOR

PO

WER

SUPP

LY

UN

-INTE

RR

UPT

AB

LEPO

WER

SU

PPLY

WSOSOPERATOR

PC

AUXPOWERSUPPLY

CONTROL CUBICLE

CONTROL &PROTECTION

MODULE (CAPM)SPI

V23

FSK

RS2

32

RS2

32

CONTROL CUBICLE ENTRY MODULE

TRIP /CLOSEMOTOR

CLO

SEC

APA

CIT

OR

TRIP

CA

PAC

ITO

R

Nu-Lec Industries RL-Series

--------- OOPPEERRAATTOORR SSEETTTTIINNGGSS --------SSLLooccaall CCoonnttrrooll OONNSSeeccttiioonnaalliisseerr OOFFFF CCoolldd LLooaadd IIDDLLEE

DDeett ‘‘AA’’ AAccttiivvee

Page 6: recloser nulec 2

Fault Detection Functions(Type FA only)

Live Load Blocking

Inrush Restraint

Cold Load Pickup

Multiple Detection Groups

Automatic Detection Group Selection

6

Phase Fault DetectionPhase fault detection monitors all three phases and makes event log entries onthrough-fault detection.

Phase Faults Setting Range: 10 - 1260AResolution of Setting: 1ADetection Time: 0.05 - 100 secDetection Time Resolution: 0.01 sec

Live Load Blocking detection operates independently of the detection elements.Live Load Threshold Voltage Range: 2 - 15kV

Inrush Restraint raises the phase and earth threshold currents for a short period oftime to allow for short duration inrush currents when closing onto a load.

Multiplier Range: 1 - 30Multiplier Resolution: 0.1Time Range: 0.05 - 30 secTime Resolution: 0.05 sec

Cold Load Pickup allows for a loss of diversity when a load has been withoutsupply for a period of time.

Multiplier Range: 1 - 5Multiplier Resolution: 0.1Time Constant Range: 1 - 480 minTime Constant Resolution: 1 min

The CAPM supports up to 10 Detection Groups, each of which can be configuredwith completely separate detection characteristics with different inverse time curvesand setting currents. The number of detection groups available to the operator canbe configured using the Windows Switchgear Operating System thereby restrictingor enabling access to detection settings as required.

Range of Detection Groups: A - J

Automatic Detection Group Selection is used to change the detectioncharacteristics depending on the direction of power flow. This allows the load breakswitch / sectionaliser to be correctly graded with devices downstream regardless ofthe power flow direction.

Range of Detection Group Pairs: A&B, C&D, E&F, G&H, I&J

RL-Series - Product Type FA automaticload break switches / sectionalisers areequipped with fault current sensingelements for phase and earth faults. Thefault settings are set from the OperatorPanel in the “Technician Level”. This faultdetection system monitors all threephases, earth fault, and sensitive earthfault, and makes event log entries onthrough-fault detection. In addition, detailsof the through-fault can be transmitted overthe SCADA or remote control WSOSsoftware.

Earth Fault DetectionEarth fault detection monitors earth faults and makes event log entries on through-fault detection.

Earth Faults Setting Range: 10 - 1260AResolution of Setting: 1ADetection Time: 0.05 - 100 secDetection Time Resolution: 0.01 sec

Sensitive Earth Fault DetectionSensitive Earth Fault (SEF) detection monitors all three phases and makes eventlog entries on through-fault detection.

SEF Current Setting Range: 4 - 20ASEF Operating Time: 0.05 - 100 secSEF Current Setting Resolution: 1 A

Nu-Lec IndustriesRL-Series

Page 7: recloser nulec 2

Sequence Reset Time

Sectionalising Functions(Type FA only)

7

A sequence reset timer is used to reset the supply interrupt counters to zero so thatthe next supply interrupt count starts again at one.

Sequence Reset Time: 5 - 180 secTiming Resolution: 1 sec

Fault InterruptionFault interruption Count Range: 1 - 10

The sectionaliser logic included in ProductType FA opens the load break switchduring the deadtime of an upstream circuitbreaker, after the circuit breaker hasopened a user configured number of times.The sectionaliser logic relies upon currentsensing to detect the fault, and opens theswitch after the current has beeninterrupted.

Phase Current SettingPhase Current Setting Range: 10 - 1260AResolution of Setting: 1A

Earth Current SettingEarth Current Setting Range: 10 - 1260AResolution of Setting: 1A

Nu-Lec Industries RL-Series

Page 8: recloser nulec 2

8

Measurement Features(Type FA only)

True RMS voltage is measured on all six terminals. A user configured thresholdindicates live terminal (accuracy ±2.5%).

Voltage

Current

Real Power (signed or unsigned)

Power Factor

RMS current is measured on three phases (accuracy ±2.5%, reading2.5-800A).

Determined by multiplying V x I in real time and averaging over 2 seconds(accuracy ±5% of reading, within limits of V and I above).

Determined from line voltage and line current phase relationship and the previouslycalculated real power (accuracy ±5% of reading, within limits of V and I above).

Event HistoryMinimum number of typical events 3,000 eventsstored in the event history:

Gas Pressure MeasurementGas Pressure Display Resolution: 5kPaGas Pressure Display Accuracy: ±10kPaGas Low Alarm Setting: 65kPa Gauge @ 20°CGas Low Alarm/Interlock Accuracy: ±10kPa

Default Historical MeasurementsPower flow is integrated over 5, 15, 30, or 60 minute intervals (kWH) and recordedfor 2 months at the default setting. This can be viewed on the operator Controlpanel, computer, or compatible SCADA system. Additionally, data can be uploadedinto a portable computer or a compatible SCADA system.

Configurable Historical MeasurementsAverage Demand Profiles may be configured using WSOS. Customisedconfiguration enables the user to specify only the parameters that are requirednegating unnecessary information capture.

Nu-Lec IndustriesRL-Series

Product Type FA utilises the CTs, CVTsand advanced control electronics toprovide the measurement features asdescribed in the section.

Page 9: recloser nulec 2

9

Pole Mounting Details

1. Details given in this illustration are subject to change without notice. For fulldetails refer the separate Technical Manual.

Note:

Surge Arrester

Antenna (if fitted)earthed to tank

Control Cable (optional)

Control Cubicle(optional)

Earth stud

Earth Stud

Main Earth Bond

Control Cubicle Earth

Tee Off

Surge Arresters alwaysearthed to tank, even ifmounted separately

Two M20 bolts fortimber pole mounting(not supplied)

or

Two clamp bands forconcrete pole mounting(optional)

Motor

Nu-Lec Industries RL-Series

Common Grounding for all Installations

Bare Terminal 15kV 630A - Creepage distance = 500mm

Cable terminated with threaded end (630A) - Creepagedistance = 770mm

Cable terminated with standard lug (250&400A) -Creepage distance = 770mm

To H.V.

Mounting BracketAUX. Supply Cable

Mounting Arrangement

Optional AUX. Supply Voltage Transformer (Phase toPhase)

Earth bond

Factory fittedbare terminal

Standard lug

Bushing Threaded end

Silicone grease

Boot

Clamp ring

Palm factoryfitted to bushing

Standard lug

Silicone grease

BootBushing

Clamp ring

Page 10: recloser nulec 2

Maximum System Voltage . . . . . . . . . . . . . . . .15kV 15kV 27kV 27kVRated Continuous Current . . . . . . . . . . . . . . . .630A 630A 630A 630AFault Make Capacity (RMS) . . . . . . . . . . . . . . .12.5kA 16kA 12.5kA 16kAFault Make Capacity (Peak) . . . . . . . . . . . . . . .31.5kA 40kA 31.5kA 40kAMechanical Operations . . . . . . . . . . . . . . . . . .3000 3000 3000 3000Rated Full Load Operations . . . . . . . . . . . . . . .600 600 600 600Short Time Current (4s RMS) . . . . . . . . . . . . .12.5kA 16kA 12.5kA 16kA

RL-Series specifications

15kV 15kV 27kV 27kVRatings 12.5kA 16kA 12.5kA 16kA

Breaking Capacity

Impulse Insulation Level

Power Frequency Insulation Level

Environmental

Net Weights

Crate Dimensions

1 -30 to +50°C available as option when heater fitted to control cubicle.2 For altitudes above 1000m, derate in accordance with ANSI C37.63 Table 13 For Gross Weights add 75kg

10

Mainly Active (0.7pf) . . . . . . . . . . . . . . . . . . . .630A 630A 630A 630ACable Charging . . . . . . . . . . . . . . . . . . . . . . . .25A 25A 25A 25ATransformer Magnetising . . . . . . . . . . . . . . . . .22A 22A 22A 22A

Phase to Phase . . . . . . . . . . . . . . . . . . . . . . . .125kV 125kV 150kV 150kVPhase to Earth . . . . . . . . . . . . . . . . . . . . . . . . .125kV 125kV 150kV 150kVAcross Interrupter . . . . . . . . . . . . . . . . . . . . . .145kV 145kV 170kV 170kVOn Loss of SF6 . . . . . . . . . . . . . . . . . . . . . . . .50kV 50kV 70kV 70kV

Phase to Earth . . . . . . . . . . . . . . . . . . . . . . . . .40kV 40kV 60kV 60kVAcross Interrupter . . . . . . . . . . . . . . . . . . . . . .50kV 50kV 60kV 60kV

Ambient Temperature (1) . . . . . . . . . . . . . . . . . .-10 to +50°C -10 to +50°C -10 to +50°C -10 to +50°CRadiation (Max) . . . . . . . . . . . . . . . . . . . . . . . .1.1kW/m² 1.1kW/m² 1.1kW/m² 1.1kW/m²Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0 to 100% 0 to 100% 0 to 100% 0 to 100%Altitude (Max) (2) . . . . . . . . . . . . . . . . . . . . . . . .3000m 3000m 3000m 3000m

Load break switch (3) . . . . . . . . . . . . . . . . . . . .110kg 110kg 110kg 110kgGross weight with control cubicle . . . . . . . . . . .210kg 210kg 210kg 210kg

Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . .W=1200mm D=1150mm H=755mm

Nu-Lec IndustriesRL-Series

Page 11: recloser nulec 2

11Nu-Lec Industries RL-Series

Ambient TemperatureTropical = -10 to 50°CModerate = -15 to 40°CTemperate = -30 to 40°C

Auxiliary Supply Voltage110 = 110V AC240 = 240V ACInt = Integral supplyInt/110 = Integral and 110V ACInt/240 = Integral and 240V ACDual = 110 & 240V AC

Control Cable Length4 = 4m 7 = 7m11 = 11m

PTCC - - -

Ordering Information

1. Model:RL27 is the current model

RL-Series LBS

4. System Voltage:15 = 15kV,27 = 27kV

5. Fault Make Capacity:12 = 12.5kA16 = 16kA

2. Product Type:MR = Manual excl. motorRC = Remote, incl. motorMA = Manual excl. MotorA = Automated excl. PTCCFA = Automated incl. PTCC

7. Cable Rating:250 = 250A, 400 = 400A630 = 630A630-BT = 630A Bare

Terminal (BT)(15kV max.)

The RL-Series LBS ordering information comprises two part numbers. The load break switch part numberincludes a Model Identifier and fields describing the Product Type, Insulation Medium, System Voltage, FaultMake Capacity, Insulation Level and Cable Rating. The Pole Top Control Cubicle (PTCC) comprises temperaturerange, cable length and auxiliary supply. The part numbers do not include measurement units and is constructedusing only one option per field in the selection chart below. A part number example is shown below:

Nu-Lec-RL27-LBS-FA-SF6-27-16-150-400 and Nu-Lec-PTCC-Moderate-240-11

Nu-Lec - RL27-LBS 2 - 4 - 5 - 6

Fielddescriptions

Control cubicle forProduct type FA:Specify the temperaturerange, auxiliary supplyvoltage and control cablelength for the Pole TopControl Cubicle (PTCC).Communication Protocoland radio/modem cabletype must be separatelyspecified at time of order.

Nu-Lec PTCC - - -

and

16

12

27

630

400

250

- 7-

RL27-LBS

3. Insulation Medium:SF6 gas insulated loadbreak switch

SF6

A

FA

MA

6. Insulation Level:125 = 125kV (15kV only)150 = 150kV (27kV only) 150

- SF6

Control Cubicle forProduct Type FA only

15

125

630-BT 15kV

15kV

16

12

15

RC

630-BT

RL27-LBS

MR

630

400

250

15kV

27

SF6

125

15015kV

27kV 27kV

CTs & CVTs not included.Mechanical & Low gasinterlocks not included.Switch only.

As per type MR with DCmotor included.

CTs & CVTs included.Mechanical & Low gasinterlocks included.DC motor not included.

As per type MA with DCmotor included.

As per type A with Nu-LecPTCC included.

Product Type MR & RC: Product Type MA, A & FA:

Page 12: recloser nulec 2

Copyright 2004 Nu-Lec Industries Pty Ltd. No responsibility for loss incurred by any person acting or refraining from actionin reliance upon any material in this brochure can be accepted by Nu-Lec Industries Pty Ltd.

Your local contact:

Brochure Part Number: N00-597

CORPORATE OFFICE & FACTORY

35-37 South Street, Lytton, 4178Queensland, Australia

PO Box 761, Edith StreetWynnum, Queensland, 4178Telephone (07) 3249 5444

Intl +61 7 3249 5444Facsimile (07) 3249 5888

Intl +61 7 3249 5888E-mail: [email protected]

http://www.nulec.com.au