June 25, 2020
Ms. Tamelia Hinson
Universal Companies
1427 Catharine Street, 4th Floor
Philadelphia, PA 19146
Re: Summary Report for Lead in Water Sampling
Universal Charter Schools – Creighton & Creighton Annex
5401 Tabor Road, Philadelphia, PA Synertech Project No. 675-213-4
Dear Ms. Hinson:
I. Executive Summary
At the request of the Universal Charter Schools, Synertech Incorporated performed lead in water at the
Universal Creighton Charter School located at 5401 Tabor Road, Philadelphia, Pennsylvania. The water
sampling was conducted as a proactive effort by the Universal Charter Schools to evaluate, document, and
ensure an acceptable water quality for all potable water outlets throughout the each of the buildings on the
school’s campus. The project included the collection of samples for analysis for lead in drinking water.
This report is a summary of the sampling protocols and testing data.
The water sampling was performed and this report was prepared by Mr. John P. Fiorelli a Pennsylvania
certified Lead Inspector/Risk Assessor at Synertech Incorporated.
II. Methodologies and Acceptable Standards
Synertech Incorporated performed sampling for the parameters listed below. Analysis was performed by
EMSL Analytical located in Cinnaminson, New Jersey.
The quantity of samples collected from each location varied depending on the number of possible potable
water outlets present at each building. A total of eighty-two (82) samples were collected from different
outlet locations throughout the building. The sampling consisted of “first draw” samples collected at each
sample location and various “flush draw” for most outlets. However, where multiple outlets are present,
such as bathroom sinks, a single representative “flush” sample was collected to represent all of the outlets
that have the same supply piping.
II. Methodologies and Acceptable Standards
Synertech Incorporated performed sampling for the parameters listed below. Analysis was performed by
EMSL Analytical located in Cinnaminson, New Jersey.
Summary Report for Lead in Water Sampling
Universal Charter Schools – Creighton & Creighton Annex
5401 Tabor Road, Philadelphia, PA
Synertech Project No. 675-213-4
The quantity of samples collected from each location varied depending on the number of possible potable
water outlets present at each building. A total of eighty-two (82) samples were collected from different
outlet locations throughout the building. The sampling consisted of “first draw” samples collected at each
sample location and various “flush draw” for most outlets. However, where multiple outlets are present,
such as bathroom sinks, a single representative “flush” sample was collected to represent all of the outlets
that have the same supply piping.
Laws and Regulations
There is no federal law requiring testing of drinking water in schools, except for schools that have their
own water supply and are thus regulated under the Safe Drinking Water Act (SDWA). The vast majority
of public water suppliers do not include schools in their sampling plans because regulations (specifically
the Lead and Copper Rule) require sampling of single-family dwellings. However, Section A-703.2; B. of
the City of Philadelphia Code does require the following:
¤ “The Health Department or a testing agency certified by the Pennsylvania Department of
Environmental Protection has certified, within the previous five years, that the building is
in substantial compliance with applicable water quality requirements of the Board of
Health, provided that in no event shall applicable water quality requirements be deemed to
permit lead in water at an outlet such as a sink or water fountain that is in service at 10 ppb
or more. Any water outlet determined to exceed any such water quality requirements shall
be taken out of service within 24 hours of notification of the relevant test. The owner of
the educational occupancy shall post the results of the most recent water quality testing at
each particular educational occupancy to a generally available website within ten days of
receipt of the results.”
The Board of Health regulation describes your responsibility for testing your water outlets. Results of the
testing for each potable water outlet in your facility should be reported to the health department by email
to [email protected]. The submission of results should include the following information:
1. A cover letter that identifies the name, address, and contact information for your facility.
2. A laboratory report that shows the date of sampling, the name of the laboratory performing
the analysis, and the lead result for each potable (drinkable) water outlet.
3. If any lead results are reported to be equal to or exceeding the action level of 10 parts per
billion (ug/L), you must discontinue use of the outlet immediately (within 24 hours).
Report your response action(s) associated with an outlet with an elevated lead level in the
cover letter. Any outlet with an elevated lead level may be put back into service only after
corrective action has been taken and a repeat lead test has shown the level to be less than
10 parts per billion(ug/L).
In addition to the requirements by the City of Philadelphia, the EPA does recommend that schools
implement programs for reducing lead in drinking water as part of the school’s overall plan for reducing
environmental threats. Safe and healthy school environments foster healthy children, and may improve
students’ general performance.
Although drinking water often incorporates low levels of some contaminants as it flows in rivers and
collects in aquifers, these materials usually are not detected at harmful levels. Public water suppliers must
monitor their water to make sure it complies with science-based public health standards. The EPA sets these
maximum allowable levels of contaminants in drinking water under The Safe Drinking Water Act (SDWA).
Summary Report for Lead in Water Sampling
Universal Charter Schools – Creighton & Creighton Annex
5401 Tabor Road, Philadelphia, PA
Synertech Project No. 675-213-4
The health effects language mentioned in this report is not intended to catalog all possible health effects for
the following drinking water contaminant. Rather, it is intended to inform consumers of some of the
possible health effects associated with drinking water contaminants when the EPA rule and regulations was
finalized. A medical doctor is to be consulted if further information is required.
National Primary Drinking Water Regulations
The U.S. Environmental Protection Agency (EPA) has established National Primary Drinking Water
Regulations that set mandatory water quality standards for drinking water contaminants. These are
enforceable standards called Maximum Contaminant Levels (MCL), which are established to protect the
public against consumption of drinking water contaminants that present a risk to human health. An MCL is
the maximum allowable amount of a contaminant in drinking water which is delivered to the consumer.
MCLs are set as close to the health goals as possible, considering cost, benefits and the ability of public
water systems to detect and remove contaminants using suitable treatment technologies. The EPA has set
this level of protection based on the best available science to prevent potential health problems. The
following paragraphs contain MCLs and brief health effects of those reported to be associated with the
samples collected at this time.
¤ Lead, a metal found in natural deposits, is commonly used in household plumbing materials
and water service lines. Most lead contamination occurs at some point in the water delivery
system. Materials in the water delivery system may include service connections, pipes,
brass fixtures, and solder. If subsequent samples yield elevated levels of lead action may
require the replacement of water delivery parts with ‘non-leaded’ parts. Homes built before
1986 are more likely to have lead pipes, fixtures and solder. However, new homes are also
at risk: even legally “lead-free” plumbing may contain up to eight (8) percent lead. The
most common problem is with brass or chrome-plated brass faucets and fixtures which can
leach significant amounts of lead into the water, especially hot water.
There is no safe level of lead. Lead toxicity affects the nervous system, both in adults and
children. Long-term exposure can result in decreased performance in cognitive ability and
functions of the nervous system. Lead exposure also causes small increases in blood
pressure, particularly in middle-aged and older people and can cause anemia. Exposure to
high lead levels can severely damage the brain and kidneys in adults or children and
ultimately cause death. Lead does not noticeably alter the color, taste, or odor of water. The
effects of low level toxicity of lead in water may not be obvious. There may be no
symptoms or the symptoms may be mistaken as flu or other illness. Many domestic water
treatment systems remove the majority of lead from drinking water.
The Action Level (AL) of Lead (Pb) in accordance with the City of Philadelphia Code is
“threshold” is 10 micrograms per liter (µg/L), while the Environmental Protection
Agency (EPA) drinking water standard is 15 micrograms per liter (µg/L). The Action Level
(threshold) is defined as the concentration of lead in water that may trigger requirements
for corrosion control, source water treatment, lead service line replacement, and public
education. Compliance with an action level is based on multiple samples.
III. Sampling Results
The following tables outline the sample results for each building where water samples were collected during
this project. Those sample results reported above the City of Philadelphia action level will appear in bold
lettering below.
Summary Report for Lead in Water Sampling
Universal Charter Schools – Creighton & Creighton Annex
5401 Tabor Road, Philadelphia, PA
Synertech Project No. 675-213-4
Main School Building
Lead in Drinking Water
Sample
# Location Draw
Sampling
Method
CoP Action Level
(AL)
Results
(ug/L)
Basement
01 Fountains o/s Boiler Room - Left First
ICP - MS,
USEPA 200.8
10ug/L
(milligrams per
Liter)
4.66
02 Fountains o/s Boiler Room-Center First 5.09
03 Fountains o/s Boiler Room-Right First 5.06
04 Fountains o/s Boiler Room - Left Flush ND
05 Fountains o/s Boiler Room-Center Flush ND
06 Fountains o/s Boiler Room-Right Flush 1.06
07 Kitchen – Left Sink First 1.36
08 Kitchen – Right Sink First ND
09 Kitchen – Left Sink Flush ND
10 Kitchen – Right Sink Flush ND
11 Fountain o/s Art Room-Left First 28.1
12 Fountain o/s Art Room-Center First 5.45
13 Fountain o/s Art Room-Right First ND
14 Fountain o/s Art Room-Left Flush 2.15
15 Fountain o/s Art Room-Center Flush ND
16 Fountain o/s Art Room-Right Flush ND
1st Floor
17 Hall Fountain o/s Boy’s Bathroom First ICP - MS,
USEPA 200.8
10ug/L
(milligrams per
Liter)
1.32
18 Hall Fountain o/s Boy’s Bathroom Flush
ND
19 Fountain o/s Rm. 104 First 1.31
20 Fountain o/s Rm. 104 Flush ND
2nd Floor
21 Fountain o/s Rm. 204 First
ICP - MS,
USEPA 200.8
10ug/L
(milligrams per
Liter)
1.81
22 Fountain o/s Rm. 204 Flush 3.02
23 Fountain o/s Rm. 207 First 3.31
24 Fountain o/s Rm. 207 Flush 1.03
3rd Floor
25 Fountain o/s Rm. 307 First
ICP - MS,
USEPA 200.8
10ug/L
(milligrams per
Liter)
1.14
26 Fountain o/s Rm. 307 Flush 1.53
27 Fountain o/s Rm. 307 First 12.3
28 Fountain o/s Rm. 307 Flush 2.52
ND = No Lead Detected in Sample
Annex Building
Lead in Drinking Water
Sample
# Location Draw
Sampling
Method
CoP Action Level
(AL)
Results
(ug/L)
01 High Fountain across from Kitchen First
ICP - MS,
USEPA 200.8
10ug/L
(milligrams per
Liter)
ND
02 High Fountain across from Kitchen Flush ND
03 Kitchen Sink - Left First ND
04 Kitchen Sink - Right First ND
05 Kitchen Sink - Left Flush ND
06 Kitchen Sink - Right Flush ND
07 Room 401 Fountain First ND
08 Room 401 Fountain Flush 5.49
09 Room 401 Sink First ND
10 Room 401 Sink Flush 5.31
Summary Report for Lead in Water Sampling
Universal Charter Schools – Creighton & Creighton Annex
5401 Tabor Road, Philadelphia, PA
Synertech Project No. 675-213-4
Lead in Drinking Water
Sample
# Location Draw
Sampling
Method
CoP Action Level
(AL)
Results
(ug/L)
11 Room 402 Fountain First
ICP - MS,
USEPA 200.8
10ug/L
(milligrams per
Liter)
ND
12 Room 402 Fountain First ND
13 Room 402 Sink Flush ND
14 Room 402 Sink Flush ND
15 Room 404 Fountain First 10.2
16 Room 404 Fountain First 13.0
17 Room 404 Sink Flush ND
18 Room 404 Sink Flush ND
19 Room 403 Fountain First ND
20 Room 403 Fountain First ND
21 Room 403 Sink Flush ND
22 Room 403 Sink Flush ND
23 Room 405 Fountain First 2.39
24 Room 405 Fountain First 9.52
25 Room 405 Sink Flush ND
26 Room 405 Sink Flush 3.95
27 Room 406 Fountain First 1.11
28 Room 406 Fountain First 10.3
29 Room 406 Sink Flush ND
30 Room 406 Sink Flush ND
31 Room 407 Fountain First 1.13
32 Room 407 Fountain First 9.36
33 Room 407 Sink Flush ND
34 Room 407 Sink Flush 1.04
35 Counselor’s Office Fountain First ND
36 Counselor’s Office Sink First 12.5
37 Counselor’s Office Fountain Flush ND
38 Counselor’s Office Sink Flush ND
39 Room 408 Fountain First ND
40 Room 408 Fountain First 2.91
41 Room 408 Sink Flush ND
42 Room 408 Sink Flush ND
43 Room 410 Fountain First ND
44 Room 410 Fountain First ND
45 Room 410 Sink Flush ND
46 Room 410 Sink Flush ND
47 Room 411 Fountain First ND
48 Room 411 Fountain First 4.56
49 Room 411 Sink Flush ND
50 Room 411 Sink Flush ND
51 Room 409 Fountain First ND
52 Room 409 Fountain First ND
53 Room 409 Sink Flush ND
54 Room 409 Sink Flush ND
ND = No Lead Detected in Sample
IV. Recommendations
A. Outlets not sampled and outlets with reported lead levels but below the Action Level
1. Lead-bearing plumbing materials in contact with drinking water pose a risk at all times
(not just when there is a lead action level (LAL) exceeded); therefore, Synertech
Incorporated recommends labeling all bathroom outlets with signage indicating that these
outlets are “not for drinking”.
Summary Report for Lead in Water Sampling
Universal Charter Schools – Creighton & Creighton Annex
5401 Tabor Road, Philadelphia, PA
Synertech Project No. 675-213-4
2. Flushing of all water outlets for at least 30 seconds prior to drinking or cooking. The more
time water has been sitting in the pipes, the more lead it is likely to contain. Anytime the
water in a particular faucet has not been used for six hours or longer, "flush" your cold-
water pipes by running the water until it becomes as cold as it will get.
B. Outlets with Reported lead levels at or Above the Action Level
The outlets that had lead concentrations at or above the City of Philadelphia Action Level (samples
36,39,53,55) are required to be taken out of service until corrective actions have been taken and re-
testing shows the lead concentration to be less than 10 ug/L. The following corrective actions are
recommended.
1. Consult a licensed and insured plumbing contractor to determine the source of the elevated
sample results. Potential sources of lead contamination are as follows:
a. Water service lines;
b. Lead soldered joints and fittings;
c. Lead faucets/fixtures.
Synertech Incorporated is pleased to have had the opportunity to provide Universal Charter Schools with
our professional environmental services. If you have any questions or would like to discuss this matter
further, please do not hesitate to call at 215-755-2305.
Prepared by:
Synertech Incorporated
John P. Fiorelli, CIE
Certified Indoor Environmentalist
Attachment 1
Lab Results
&
Chain of Custody Forms
Phillip Worby, Environmental Chemistry Laboratory Director
Approved By:
Fax: (215) 755-2405Phone: (215) 755-2305
The following analytical report covers the analysis performed on samples submitted to EMSL Analytical, Inc. on 5/29/2020. The results are tabulated on the attached data pages for the following client designated project:
Universal Creighton Main School Building; 675-213-
The reference number for these samples is EMSL Order #012005307. Please use this reference when calling about these samples. If you have any questions, please do not hesitate to contact me at (856) 303-2500.
6/15/2020Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
The test results contained within this report meet the requirements of NELAP and/or the specific certification program that is applicable, unless otherwise noted.NELAP Certifications: NJ 03036, NY 10872, PA 68-00367, CA ELAP 1877
The samples associated with this report were received in good condition unless otherwise noted. This report relates only to those items tested as received by the laboratory. The QC data associated with the sample results meet the recovery and precision requirements established by the NELAP, unless specifically indicated. All results for soil samples are reported on a dry weight basis, unless otherwise noted. This report may not be reproduced except in full and without written approval by EMSL Analytical, Inc.
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone: (856) 303-2500 Fax: (856) 858-4571 Email: [email protected]
Page 1 of 7
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005307CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Main School Building; 675-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:01 012005307-0001Basement O/S Boiler Room - Fountains (3) - Left; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD4.66 µg/L 06/11/20 14:051.00 6/11/2020 VD
Client Sample Description Lab ID:02 012005307-0002Basement O/S Boiler Room - Fountains (3) - Center; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD5.09 µg/L 06/11/20 14:101.00 6/11/2020 VD
Client Sample Description Lab ID:03 012005307-0003Basement O/S Boiler Room - Fountains (3) - Right; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD5.06 µg/L 06/11/20 14:121.00 6/11/2020 VD
Client Sample Description Lab ID:04 012005307-0004Basement O/S Boiler Room - Fountains (3) - Left; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 14:181.00 6/11/2020 VD
Client Sample Description Lab ID:05 012005307-0005Basement O/S Boiler Room - Fountains (3) - Center; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 14:191.00 6/11/2020 VD
Page 2 of 7ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:45:37 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005307CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Main School Building; 675-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:06 012005307-0006Basement O/S Boiler Room - Fountains (3) - Right; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD1.06 µg/L 06/11/20 14:211.00 6/11/2020 VD
Client Sample Description Lab ID:07 012005307-0007Kitchen Sink Left Sink; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD1.36 µg/L 06/11/20 14:231.00 6/11/2020 VD
Client Sample Description Lab ID:08 012005307-0008Kitchen Sink Right Sink; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 14:251.00 6/11/2020 VD
Client Sample Description Lab ID:09 012005307-0009Kitchen Sink Left Sink; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 14:271.00 6/11/2020 VD
Client Sample Description Lab ID:10 012005307-0010Kitchen Sink Right Sink; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 14:291.00 6/11/2020 VD
Page 3 of 7ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:45:37 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005307CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Main School Building; 675-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:11 012005307-0011Basement Fountain O/S Art Room - Left; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead KB28.1 µg/L 06/15/20 14:561.00 6/12/2020 KB
Client Sample Description Lab ID:12 012005307-0012Basement Fountain O/S Art Room - Center; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD5.45 µg/L 06/11/20 14:301.00 6/11/2020 VD
Client Sample Description Lab ID:13 012005307-0013Basement Fountain O/S Art Room - Right; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 14:401.00 6/11/2020 VD
Client Sample Description Lab ID:14 012005307-0014Basement Fountain O/S Art Room - Left; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD2.15 µg/L 06/11/20 14:411.00 6/11/2020 VD
Client Sample Description Lab ID:15 012005307-0015Basement Fountain O/S Art Room - Center; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 14:431.00 6/11/2020 VD
Page 4 of 7ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:45:37 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005307CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Main School Building; 675-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:16 012005307-0016Basement Fountain O/S Art Room - Right; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 14:451.00 6/11/2020 VD
Client Sample Description Lab ID:17 012005307-00171st Fl. Hall Fountain O/S Boy's Bathroom; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD1.32 µg/L 06/11/20 14:471.00 6/11/2020 VD
Client Sample Description Lab ID:18 012005307-00181st Fl. Hall Fountain O/S Boy's Bathroom; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 14:491.00 6/11/2020 VD
Client Sample Description Lab ID:19 012005307-0019Fountain O/S Rm. 104; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD1.31 µg/L 06/11/20 14:511.00 6/11/2020 VD
Client Sample Description Lab ID:20 012005307-0020Fountain O/S Rm. 104; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 14:521.00 6/11/2020 VD
Page 5 of 7ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:45:37 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005307CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Main School Building; 675-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:21 012005307-0021Fountain O/S Rm. 204; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD1.81 µg/L 06/11/20 14:541.00 6/11/2020 VD
Client Sample Description Lab ID:22 012005307-0022Fountain O/S Rm. 204; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD3.02 µg/L 06/11/20 15:051.00 6/11/2020 VD
Client Sample Description Lab ID:23 012005307-0023Fountain O/S Rm. 207; 1st
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD3.31 µg/L 06/11/20 15:111.00 6/11/2020 VD
Client Sample Description Lab ID:24 012005307-0024Fountain O/S Rm. 207; Flush
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD1.03 µg/L 06/11/20 15:121.00 6/11/2020 VD
Client Sample Description Lab ID:25 012005307-0025Fountain O/S Rm. 307
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD1.14 µg/L 06/11/20 15:141.00 6/11/2020 VD
Page 6 of 7ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:45:37 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005307CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Main School Building; 675-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:26 012005307-0026Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD1.53 µg/L 06/11/20 15:161.00 6/11/2020 VD
Client Sample Description Lab ID:27 012005307-0027Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD12.3 µg/L 06/11/20 15:181.00 6/11/2020 VD
Client Sample Description Lab ID:28 012005307-0028Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD2.52 µg/L 06/11/20 15:231.00 6/11/2020 VD
MDL - method detection limitJ - Result was below the reporting limit, but at or above the MDLND - indicates that the analyte was not detected at the reporting limitRL - Reporting Limit (Analytical)D - Dilution Sample required a dilution which was used to calculate final results
Definitions:
Page 7 of 7ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:45:37 PM
Phillip Worby, Environmental Chemistry Laboratory Director
Approved By:
Fax: (215) 755-2405Phone: (215) 755-2305
The following analytical report covers the analysis performed on samples submitted to EMSL Analytical, Inc. on 5/29/2020. The results are tabulated on the attached data pages for the following client designated project:
Universal Creighton Annex Building; 676-213-
The reference number for these samples is EMSL Order #012005303. Please use this reference when calling about these samples. If you have any questions, please do not hesitate to contact me at (856) 303-2500.
6/15/2020Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
The test results contained within this report meet the requirements of NELAP and/or the specific certification program that is applicable, unless otherwise noted.NELAP Certifications: NJ 03036, NY 10872, PA 68-00367, CA ELAP 1877
The samples associated with this report were received in good condition unless otherwise noted. This report relates only to those items tested as received by the laboratory. The QC data associated with the sample results meet the recovery and precision requirements established by the NELAP, unless specifically indicated. All results for soil samples are reported on a dry weight basis, unless otherwise noted. This report may not be reproduced except in full and without written approval by EMSL Analytical, Inc.
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone: (856) 303-2500 Fax: (856) 858-4571 Email: [email protected]
Page 1 of 12
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005303CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Annex Building; 676-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:01 012005303-0001High Fountain across from Kitchen (low broken)
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 15:251.00 6/11/2020 VD
Client Sample Description Lab ID:02 012005303-0002High Fountain across from Kitchen (low broken)
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 15:271.00 6/11/2020 VD
Client Sample Description Lab ID:03 012005303-0003Kitchen Sink - Left
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 15:291.00 6/11/2020 VD
Client Sample Description Lab ID:04 012005303-0004Kitchen Sink - Right
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 15:311.00 6/11/2020 VD
Client Sample Description Lab ID:05 012005303-0005Kitchen Sink - Left
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 15:361.00 6/11/2020 VD
Page 2 of 12ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:43:20 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005303CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Annex Building; 676-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:06 012005303-0006Kitchen Sink - Right
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 15:381.00 6/11/2020 VD
Client Sample Description Lab ID:07 012005303-0007Room 401 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 15:401.00 6/11/2020 VD
Client Sample Description Lab ID:08 012005303-0008Room 401 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD5.49 µg/L 06/11/20 15:451.00 6/11/2020 VD
Client Sample Description Lab ID:09 012005303-0009Room 401 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 15:471.00 6/11/2020 VD
Client Sample Description Lab ID:10 012005303-0010Room 401 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD5.31 µg/L 06/11/20 15:491.00 6/11/2020 VD
Page 3 of 12ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:43:20 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005303CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Annex Building; 676-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:11 012005303-0011Room 402 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 15:511.00 6/11/2020 VD
Client Sample Description Lab ID:12 012005303-0012Room 402 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 15:531.00 6/11/2020 VD
Client Sample Description Lab ID:13 012005303-0013Room 402 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 15:541.00 6/11/2020 VD
Client Sample Description Lab ID:14 012005303-0014Room 402 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 16:101.00 6/11/2020 VD
Client Sample Description Lab ID:15 012005303-0015Room 404 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD10.2 µg/L 06/11/20 16:161.00 6/11/2020 VD
Page 4 of 12ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:43:20 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005303CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Annex Building; 676-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:16 012005303-0016Room 404 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD13.0 µg/L 06/11/20 16:181.00 6/11/2020 VD
Client Sample Description Lab ID:17 012005303-0017Room 404 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 16:191.00 6/11/2020 VD
Client Sample Description Lab ID:18 012005303-0018Room 404 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 16:211.00 6/11/2020 VD
Client Sample Description Lab ID:19 012005303-0019Room 403 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 16:271.00 6/11/2020 VD
Client Sample Description Lab ID:20 012005303-0020Room 403 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 16:291.00 6/11/2020 VD
Page 5 of 12ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:43:20 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005303CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Annex Building; 676-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:21 012005303-0021Room 403 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 16:301.00 6/11/2020 VD
Client Sample Description Lab ID:22 012005303-0022Room 403 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 16:321.00 6/11/2020 VD
Client Sample Description Lab ID:23 012005303-0023Room 405 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD2.39 µg/L 06/11/20 16:341.00 6/11/2020 VD
Client Sample Description Lab ID:24 012005303-0024Room 405 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD9.52 µg/L 06/11/20 16:361.00 6/11/2020 VD
Client Sample Description Lab ID:25 012005303-0025Room 405 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 16:411.00 6/11/2020 VD
Page 6 of 12ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:43:20 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005303CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Annex Building; 676-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:26 012005303-0026Room 405 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD3.95 µg/L 06/11/20 16:431.00 6/11/2020 VD
Client Sample Description Lab ID:27 012005303-0027Room 406 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD1.11 µg/L 06/11/20 16:491.00 6/11/2020 VD
Client Sample Description Lab ID:28 012005303-0028Room 406 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD10.3 µg/L 06/11/20 16:511.00 6/11/2020 VD
Client Sample Description Lab ID:29 012005303-0029Room 406 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 16:521.00 6/11/2020 VD
Client Sample Description Lab ID:30 012005303-0030Room 406 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 16:541.00 6/11/2020 VD
Page 7 of 12ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:43:20 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005303CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Annex Building; 676-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:31 012005303-0031Room 407 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD1.13 µg/L 06/11/20 16:561.00 6/11/2020 VD
Client Sample Description Lab ID:32 012005303-0032Room 407 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD9.36 µg/L 06/11/20 16:581.00 6/11/2020 VD
Client Sample Description Lab ID:33 012005303-0033Room 407 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:001.00 6/11/2020 VD
Client Sample Description Lab ID:34 012005303-0034Room 407 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead KB1.04 µg/L 06/15/20 16:201.00 6/12/2020 KB
Client Sample Description Lab ID:35 012005303-0035Counselor Office Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:111.00 6/11/2020 VD
Page 8 of 12ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:43:20 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005303CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Annex Building; 676-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:36 012005303-0036Conselor Office Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD12.5 µg/L 06/11/20 17:161.00 6/11/2020 VD
Client Sample Description Lab ID:37 012005303-0037Conselor Office Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:181.00 6/11/2020 VD
Client Sample Description Lab ID:38 012005303-0038Conselor Office Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:201.00 6/11/2020 VD
Client Sample Description Lab ID:39 012005303-0039Room 408 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:221.00 6/11/2020 VD
Client Sample Description Lab ID:40 012005303-0040Room 408 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD2.91 µg/L 06/11/20 17:231.00 6/11/2020 VD
Page 9 of 12ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:43:20 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005303CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Annex Building; 676-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:41 012005303-0041Room 408 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:251.00 6/11/2020 VD
Client Sample Description Lab ID:42 012005303-0042Room 408 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:271.00 6/11/2020 VD
Client Sample Description Lab ID:43 012005303-0043Room 410 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:331.00 6/11/2020 VD
Client Sample Description Lab ID:44 012005303-0044Room 410 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:341.00 6/11/2020 VD
Client Sample Description Lab ID:45 012005303-0045Room 410 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:361.00 6/11/2020 VD
Page 10 of 12ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:43:20 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005303CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Annex Building; 676-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:46 012005303-0046Room 410 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:421.00 6/11/2020 VD
Client Sample Description Lab ID:47 012005303-0047Room 411 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:431.00 6/11/2020 VD
Client Sample Description Lab ID:48 012005303-0048Room 411 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VD4.56 µg/L 06/11/20 17:451.00 6/11/2020 VD
Client Sample Description Lab ID:49 012005303-0049Room 411 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:471.00 6/11/2020 VD
Client Sample Description Lab ID:50 012005303-0050Room 411 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:491.00 6/11/2020 VD
Page 11 of 12ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:43:20 PM
EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (856) 303-2500 / (856) 858-4571http://www.EMSL.com [email protected]
012005303CustomerID: SYNE50CustomerPO:ProjectID:
EMSL Order:
Analytical Results
Attn: John FiorelliSynertech, Inc.228 Moore StreetPhiladelphia, PA 19148
Received: 05/29/20 9:00 AM
Universal Creighton Annex Building; 676-213-
Fax: (215) 755-2405Phone: (215) 755-2305
Project:
Client Sample Description Lab ID:51 012005303-0051Room 409 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:541.00 6/11/2020 VD
Client Sample Description Lab ID:52 012005303-0052Room 409 Fountain
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:561.00 6/11/2020 VD
Client Sample Description Lab ID:53 012005303-0053Room 409 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 17:581.00 6/11/2020 VD
Client Sample Description Lab ID:54 012005303-0054Room 409 Sink
Collected: 5/28/2020
Method Parameter Result UnitsAnalysis
Date & AnalystRLPrep
Date & Analyst
METALS
200.8 Lead VDND µg/L 06/11/20 18:001.00 6/11/2020 VD
MDL - method detection limitJ - Result was below the reporting limit, but at or above the MDLND - indicates that the analyte was not detected at the reporting limitRL - Reporting Limit (Analytical)D - Dilution Sample required a dilution which was used to calculate final results
Definitions:
Page 12 of 12ChemSmplw/RDL/NELAC-7.52.0 Printed: 6/15/2020 5:43:20 PM
OrderID: 012005307
Page 1 Of 2
OrderID: 012005307
Page 2 Of 2
OrderID: 012005303
Page 1 Of 3
OrderID: 012005303
Page 2 Of 3
OrderID: 012005303
Page 3 Of 3