Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE ICC Spring Meeting Orlando, Florida May 2007 Presented by Dr. George Anders, Fellow IEEE

Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Rating Under Special Installation Conditions and Uprating of Existing

Cables

Workshop on Cable Ampacity at the IEEE ICC Spring Meeting Orlando, Florida

May 2007

Presented byDr. George Anders, Fellow IEEE

Page 2: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Cables in duct banksWhat is the “best” circuit arrangement?

• The duct bank overall ampacity, i.e. the sum of the ampacities for all circuits, is maximized.

• The duct bank overall ampacity, i.e. the sum of the ampacities for all circuits, is minimized.

• The ampacity of any given circuit is maximized.• The ampacity of any given circuit is minimized.

Page 3: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Cables in BackfillsWhat is the optimal backfill size?

Which parameters are important?

00

0.5

1

1.5

2

2.5

0.2 0.4 0.6 0.8Backfill width (m)

Backf

ill dep

th (m

)

Cost = $50/mCost = $65/m

I = 0.82.A

LG = 0.8m Cost = $75/m

w = 0.6m

w = 0.2mρe = 1.2 K m/W

ρc= 0.6 K m/W

θamb = 15 C

w

h

LG

Optimal depth and width for given minimum current

Page 4: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Rating of Pipe Type Cables with Slow Circulation of Dielectric Fluid

• Dielectric fluid flowing in the pipe with normal environment moves into a hot-spot section at an initial temperature .

• When passing through, the fluid temperature rises at an exponential rate to a maximum value

• As fluid moves again into a long section with normal environment, the temperature decreases at an exponential rate toward an asymptotic value of

infθ

outfθ

infθ

Effect of oil-flow rate on hot spot temperature reduction (Burrell 1965)

infθ

Page 5: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Current Rating of Multicore CablesThe need for bundle rating arises from the fact that modern telecommunication cables or cables installed in aircraft are grouped together for a portion of the cable run. An example of such cable is shown here. In this figure, a bundle of N separate cores is held by means of an aluminum band (static shield) and enclosed by a PVC-sheath.

Page 6: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Calculated vs. experimental results

Dots represent measured values

Permissible total current as a function of ambient air temperature. The dot indicates the measured value

Page 7: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Increasing Ampacity of Cables Increasing Ampacity of Cables byby Application of Application of Ventilated PipesVentilated Pipes

•Continuous current rating as function of the cooling section length l0 for a non-metallic pipe with inner diameter of 300 mm•Dotted lines denote natural air convection with the outlet-height as a parameter•Solid lines denote forced air convection with the flow velocity as a parameter.

Page 8: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Cable Crossings

085

90

95

100

105

110

115

120°C

1 2 3 4 5 6 m

Z

θL

θL [TL→∞]

A=120 mm2

500 mm2

1000 mm2

2500 mm2

Cable 2

Cable 1

Z2Z20

Z20 cosß

X2

X1

y = y1

y = y2

Z1

y

.

.90°-ß

ß

194090-10/97

110 kV LPOF cable fully loaded and heated by an external perpendicular heat source 30 W/m, 30 cm above the cable 194082-10/97

Page 9: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Crossing Unfavorable Regions

Example of the temperature distribution from the center of street crossing

Page 10: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Complex Cable Arrangements

Solved by a combination of a Finite Element method and the Standard approach.

Page 11: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Cables in Tunnels

Example of derating factors depending on the arrangement and the number of cables in a tray

Thermal model

Page 12: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Cables in Covered Troughs

40

50

60

70

80

90

100

0.00E+00 1.00E+01 2.00E+01 3.00E+01 4.00E+01 5.00E+01 6.00E+01 7.00E+01 8.00E+01

Time (hours)Te

mpe

ratu

re (C

)

Cable 750 MCM middle (conductor) Cable 4/O middle (conductor)

Cover temperature

Page 13: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Installations To Be Studied

Utility sidewalk Cables in plastic ducts placed in a steel pipe

Borings with unusual shapes

Page 14: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Cable Uprating

• Sample problemTypical environmental parameters assumed: the ambient soil temperature of 20ºC, native soil thermal resistivity of 1.2 K·m/W and backfill thermal resistivity, in this case, of 2.0 K·m/W. Under the above conditions each cable can carry a maximum steady state current of 800 A

Predicted load growth

Page 15: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Cable Uprating

• Solution to a sample problem-year 2

The critical cable surface temperature is usually in the range of 50 - 60ºC. Assuming the critical value in this study is 50ºC for steady state and 60ºC for transient conditions, respectively, it can be observed that these temperatures are not expected to be reached in that year. Probability distribution of steady state

and emergency hottest cable surface temperatures computed taking into account statistical variations of several parameters

Page 16: Rating Under Special Installation Conditions and Uprating ... · Rating Under Special Installation Conditions and Uprating of Existing Cables Workshop on Cable Ampacity at the IEEE

Cable Uprating• Which year to

select?

Yearly cable surface temperature

Suppose that an acceptable risk of exceeding cable design temperatures is selected. From this figure, a critical year is selected in which either the steady state or emergency cable operating temperature is exceeded. In our case, a new cable has to be installed in year No. 3.

Based on standard deterministic criterion, as discussed, the new cable would have to be installed in the second year.