1 © 2009 IBM Corporation STG Technical Conferences 2009 SMP14 Racking your Power System Hardware … Without Aspirin Mark Olson IBM WW Power Systems Product Manager © 2009 IBM Corporation 2 STG Technical Conferences 2009 Racking Your Power System … Without Aspirin Current Hardware Can Be Racked Power 560 POWER5 570 POWER5 550 POWER5 520/515/525 Power 570 Power 550 Power 520 #5802 (12X DDR I/O) 7212/7214 (tape/DVD drawer) #5886 (SAS Disk drawer) #5786, (SCSI Disk drawer) #0588 (HSL/RIO I/O) RPQ #5094/5096 (HSL/RIO I/O) #5294/5296 (HSL/RIO I/O) #0595, 5711-D20 (HSL/RIO I/O) #5790, 5711-D11 (HSL/RIO I/O) #5796, 5714-G30 (12X I/O) 19-inch System Units 19-inch I/O Drawers

Racking Your System

Embed Size (px)

DESCRIPTION

 

Citation preview

Page 1: Racking Your System

1

© 2009 IBM CorporationSTG Technical Conferences 2009

SMP14Racking your Power System Hardware …Without Aspirin

Mark OlsonIBM WW Power Systems Product Manager

© 2009 IBM Corporation2

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Current Hardware Can Be Racked

Power 560

POWER5 570

POWER5 550

POWER5 520/515/525

Power 570

Power 550

Power 520 #5802 (12X DDR I/O)

7212/7214 (tape/DVD drawer)

#5886 (SAS Disk drawer)

#5786, (SCSI Disk drawer)

#0588 (HSL/RIO I/O)

RPQ#5094/5096 (HSL/RIO I/O)

#5294/5296 (HSL/RIO I/O)

#0595, 5711-D20 (HSL/RIO I/O)

#5790, 5711-D11 (HSL/RIO I/O)

#5796, 5714-G30 (12X I/O)

19-inch System Units 19-inch I/O Drawers

Page 2: Racking Your System

2

© 2009 IBM Corporation3

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Three 19-inch Rack Sizes (Power Systems)

2m

42U

1.8m

36U

1.3m

25U

“Standard” 19-inch racks

Note the term “standard” can be wildly misleading when looking across vendors. Though the width of 19”between holes in the vertical support posts is standard, many other aspects follow guidelines/standards which

are open to considerable differences in interpretation.

© 2009 IBM Corporation4

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Agenda

• Racking 19-inch IBM System Units: 520, 550, 560, 570

• Racking 19-inch IBM I/O Drawers :

– With PCI slots: #5802, #5790, #5796, #0595, #0588, #5294/96, #5094/96

– Disk only drawer: #5786, #5886

• IBM Power System 19-inch Racks 1.8m, 2m, 1.3m

• IBM Rack Options

• IBM Power Distribution Units (PDU) #7188, #7109

• IBM Rack UPS

• IBM Tape and racks

• Nuts & bolts

• Using different IBM or OEM Racks

Page 3: Racking Your System

3

© 2009 IBM Corporation5

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Power 520 Tower & Rack-mount

Order rackmount using– #7200 rack-mount specify

– #7114 bezel, adjust depth rails,

Order tower using

– #7112 Covers & door (lockable)

Must also order for rackmount:• Ops panel cable #1877• #7114 rail kit• Probably PDU power cords• Rack/PDU if needed

Must also order for tower:• Ops panel cable #1843• Non-PDU power cords

#7112 �������� #7200 conversion ships hardware, BUT

Conversions announced Feb 2009

4 U

8203-E4A

© 2009 IBM Corporation6

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Power 550 Rack-mount & Tower

4 U

Order rackmount using

– #7360 rack-mount specify

– #7146 bezel, adjust depth rails,

Order tower using

– #7292 Covers & door (lockable)

No field conversions

FYI - The vast majority of Power 550 shipped from IBM are rackmount. Almost zero requests for footprint conversions have been received for either POWER5 550 or POWER6 550. Therefore IBM has not created the ordering/shipping/billing structure to do sucha conversion and has no plans at this time to create this structure.

8204-E8A

Page 4: Racking Your System

4

© 2009 IBM Corporation7

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Model 560/570 - Racking Insights

• All 560/570 are 19” rackmount only. Adjustable depth rails are included

• 560/570 bigger than 1 drawer has rack implications, both for IBM and OEM racks.

4U (4 EIA)

Processor drawer

If creating 2-drawer, 3-drawer or 4-drawer configuration, processor drawers must be installed adjacent to one another.

8234-EMA, 9117-MMA

© 2009 IBM Corporation8

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Agenda

• Racking 19-inch IBM System Units: 520, 550, 560, 570

• Racking 19-inch IBM I/O Drawers :

– With PCI slots: #5802, #5790, #5796, #0595, #0588, #5294/96, #5094/96

– Disk only drawer: #5786, #5886

• IBM Power System 19-inch Racks 1.8m, 2m, 1.3m

• IBM Rack Options

• IBM Power Distribution Units (PDU) #7188, #7109

• IBM Rack UPS

• IBM Tape and racks

• Nuts & bolts

• Using different IBM or OEM Racks

Page 5: Racking Your System

5

© 2009 IBM Corporation9

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

#5802/5877 12X I/O Drawer (for POWER6 servers)

#5802/5877 12X I/O Drawer• 4U or 4 EIA

• Adjustable depth rails

• 10 PCIe slots, 18 or 0 SFF disk bays

• 12X attach

• PDU optional

No #5802-equivalent deskside packaging option available

5877 no disk bays5802 with disk bays

© 2009 IBM Corporation10

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

#5796 12X I/O Drawer (for POWER6 servers)

#5796 12X I/O Drawer• Fits in ½ of 4U enclosure

• 6 PCI-X DDR slots per 5796

• 12X attach

• PDU optional

#7314 Enclosure• 4U or 4 EIA

• 1 or 2 5796 per #7314– adjustable depth rails

No #5796-equivalent deskside packaging option available

#5796 #5796

#5796 is System i heritage, but

7314-G30 drawer is essentially

equivalent.

Page 6: Racking Your System

6

© 2009 IBM Corporation11

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

#5790 I/O Drawer

#5790 I/O Drawer• Fits in ½ of 4U enclosure

• 6 PCI-X slots per 5790

• HSL/RIO attach

• PDU optional

#5790 #5790

#7307 Enclosure• 4U or 4 EIA

• 1 or 2 5790 per #7311/7307

– adjustable depth rails

– Earlier #7311 enclosure has fixed depth rails

No #5790-equivalent deskside packaging option

#5790 is System i heritage, but

7311-D11 drawer is nearly

equivalent

© 2009 IBM Corporation12

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

#0595 I/O Drawer

#0595• 5U or 5 EIA

• 7 PCI-X slots and 12 disk bays

• HSL/RIO attach

• PDU optional

• Adjustable depth rails included

Rackmount to deskside (or vice versa) conversions not available

#0595 #5095

withdrawn from marketing Aug 2009

#0595 is System i heritage, but

7311-D20 drawer is nearly

equivalent, but only 4U

Page 7: Racking Your System

7

© 2009 IBM Corporation13

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

#0588 I/O Drawer

#0588• 8U or 8 EIA

• 14 PCI-X slots and 0 disk bays

• HSL/RIO attach

• PDU required

• Fixed depth rails included – Adjustable rails not available

• Previous generation = #0578

Rackmount to deskside (or vice versa) conversions not available

#0588 #5094

#5088

Withdrawn from marketing mid 2006

© 2009 IBM Corporation14

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Racked I/O Tower

#5294/5296• 36U 1.8m rack

• Total 28 PCI-X slots

• Total 90 (#5294) or 0 (#5296) disk bays

• HSL/RIO attach

• PDU not used

• Really two #5094/5096s installed inside a 1.8m rack and ordered as just #5294/5296

#8294 Same thing as 5294, but for 595

#5079 Same thing, but older generation #5074

Withdrawn from marketing May 2009

Page 8: Racking Your System

8

© 2009 IBM Corporation15

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Single #5094/5096 I/O Tower in a Rack

• Chargeable RPQ 847215

• IBM Manufacturing Plant only. Not installable at customer site.

– Weight of #5094/5096 prohibits this being done at customer site

• For model 520/525/550/570/595 & 800/810/825/870/890

• Once done, no IBM structure in place to remove #5094 from rack

#5094 � 14 PCI-X slots and 15 + opt 30 disk slots � #5094 uses 18U of rack space

Rack� 36U #0551 � 42U #0553

Can put 520/525, 550, 570, I/O, etc here

Withdrawn from marketing May 2009

© 2009 IBM Corporation16

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

#5786 EXP24 SCSI Disk Drawer

#5786• 4U or 4 EIA

• 24 3.5” disk bays and 0 PCI-X slots

– 12 slots in front, 12 slots in back

– 4 disk slot enablers in back

• PDU optional

• Adjustable depth rails included

Rackmount to tower (or vice versa) conversions not available

#5786

#5787

Tower withdrawn from marketing in

2008

SCSI disk withdrawn from marketing Aug 2009

#5786 is System i heritage, but

7031-D24 drawer is equivalent

Page 9: Racking Your System

9

© 2009 IBM Corporation17

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

EXP 12S SAS Disk Drawer #5886

• 2U or 2EIA disk drawer

• 12 SAS 3.5” disk bays and 0 PCI slots per drawer

• Adjustable depth rails included

• Dual power supplies (two power cords)

• Rack only …. No tower option

© 2009 IBM Corporation18

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Agenda

• Racking 19-inch IBM System Units: 520, 550, 560, 570

• Racking 19-inch IBM I/O Drawers :

– With PCI slots: #5802, #5790, #5796, #0595, #0588, #5294/96, #5094/96

– Disk only drawer: #5786, #5886

• IBM Power System 19-inch Racks 1.8m, 2m, 1.3m

• IBM Rack Options

• IBM Power Distribution Units (PDU) #7188, #7109

• IBM Rack UPS

• IBM Tape and racks

• Nuts & bolts

• Using different IBM or OEM Racks

Page 10: Racking Your System

10

© 2009 IBM Corporation19

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Power Systems Racking

System iFeature coded racks(#055x)

System pMachine type/model (7014-xxx)

Power SystemsFeature coded & machine type/model(#055x & 7014-xxx)

• Use 7014-xxx if ordering a new

server. Can order along with server

MES order if don’t need integrated at

IBM plant with MES.

• Use #055x if ordering as MES. IBM

plan can integrate with other I/O

drawer or system upgrade MES on

the same order.

Note: in 2009 maintenance pricing for #0551/0553/0554/0555 on POWER6 8203/8204/8234/9117/91119 was added to make it consistent with maintenance pricing on 7014 racks.

© 2009 IBM Corporation20

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Four/Three Power Systems Racks

2m(79”)42U

#0553

1.8m(71”)36U

#0551

1.3m(49”)25U

#0555

0.6m (24”)11U

#0554

Withdrawn

From

marketing

7014-T42#05537014-B42

7014-S25#0555*

7014-T00#0551

7014-S11#0554

* not orderable as #0555 for most servers

Page 11: Racking Your System

11

© 2009 IBM Corporation21

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

2 Meter Rack (42U)

• 42 EIA or 42U • 28-inch depth between vertical supports• EIA 310-D mounting hole pattern • Frame is 36U rack with 6U extension

• Same basic rack (i, p, TS), ordered differently• #0553 Power Systems MES & System i

• 7014-T42 Power Systems & System p

• 7014-B42 for BladeCenter

• 9308-42S/4P_ System x

• 2101-N42 TotalStorage

• Different rack accessories offered between #055x, 7104,

9308

• 19-inch, industry standard rack. BUT other vendors’ depth and hole patterns can vary

28 inDEPTH – interior (rail to rail)

1042 mm (41.0 in)Rear door only (front trim kit)

261 kg (575 lb)WEIGHT empty

2015 mm (79.3 in)HEIGHT

1098 mm (43.3 in)Regular front & rear doors

DEPTH - exterior

623 mm (24.5 in)Without side panels

644 mm (25.4 in)With side panels

WIDTH - exterior

© 2009 IBM Corporation22

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

1.8 Meter Rack (36U)

• 36 EIA or 36U • 28-inch depth between vertical supports• EIA 310-D mounting hole pattern

• Same basic rack (i, p, TS), ordered differently• #0551 Power Systems MES & System i

• 7014-T00 Power Systems & System p

• 2101-200, -N00 TotalStorage

• n/a System x

• Different rack accessories offered between #055x, 7104,

& 2101

• 19-inch, industry standard rack. BUT other vendors’ depth and hole patterns can vary

244 kg (535 lb)

1804 mm (71.0 in)

1098 mm (43.3 in)

1042 mm (41.0 in)

28 in

623 mm (24.5 in)

644 mm (25.4 in)

DEPTH – interior (rail to rail)

Rear door only (front trim kit)

WEIGHT empty

HEIGHT

Regular front & rear doors

DEPTH - exterior

Without side panels

With side panels

WIDTH - exterior

Page 12: Racking Your System

12

© 2009 IBM Corporation23

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

1.3 Meter Rack (25U)

• 25 EIA or 25U • 28-inch depth between vertical supports• EIA 310-D mounting hole pattern

• But square holes, unlike 1.8m or 2m rack

• Same basic rack (i, p, x), ordered differently• #0555 System i, feature code

• 7014-S25 System p

• 9308-2SX System x

• No accessories - base includes: • Front & rear lockable doors

• Front filler panels if empty from plant

• Narrower than 1.8 or 2 meter rack• PDU placement impacted

• Model 570 processor drawer restriction

102 kg (221 lb)

1240 mm (49 in)

1000 mm (39.4 in)

28 in

590 mm (23.2 in)

610 mm (24.0 in)

DEPTH – interior (rail to rail)

WEIGHT empty

HEIGHT

Regular front & rear doors

DEPTH - exterior

Without side panels

With side panels

WIDTH - exterior

© 2009 IBM Corporation24

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Agenda

• Racking 19-inch IBM System Units: 520, 550, 560, 570

• Racking 19-inch IBM I/O Drawers :

– With PCI slots: #5802, #5790, #5796, #0595, #0588, #5294/96, #5094/96

– Disk only drawer: #5786, #5886

• IBM Power System 19-inch Racks 1.8m, 2m, 1.3m

• IBM Rack Options

• IBM Power Distribution Units (PDU) #7188, #7109

• IBM Rack UPS

• IBM Tape and racks

• Nuts & bolts

• Using different IBM or OEM Racks

Page 13: Racking Your System

13

© 2009 IBM Corporation25

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

42U/36U Rack Options (2m/1.8m)Base Definition Includes

7014-T42/T00

Perforated rear door*

No side panels (optional)

Front filler panes (if space empty when shipped)

One PDU (rest optional)

Choose #9188 or #5889

Anti-tip plate

#0553/0551

Perforated rear door*

Side panels

Front filler panes (if space empty when shipped)

No PDU (all optional)

Anti-tip plate

* regular rear door not shipped if acoustic doors option ordered

7014-B42 basically the same as 7014-T42 but all PDU optional

© 2009 IBM Corporation26

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

42U/36U Rack Options Must Choose: Trim Kit or Front Door

Trim kit#6246/6247

Regular Front door#6068/6069

Acoustic Front door*#6248/6249

Easy accessGood visibility

Perforated steelSecurity option: door

lock & side panel

lock #6580

~6 dB(A) quieterSecurity option: door

lock & side panel

lock #6580

* Acoustic doors feature ships both front & back door

Page 14: Racking Your System

14

© 2009 IBM Corporation27

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

42U/36U Racks Other Options

• Side Panel #6098 for 7014

• Suite Attach #7780/7840 for server (existing), #6104/6086 for 7014 (new or existing)

• Attaches multiple racks of same size, side-to-side• Remove side panels – connect rack frames• Additional stability

• Ruggedized Rack #7841 for server (existing), #6080 for 7014 (new or existing)

• Allows bolting rack to floor and additional rack strengthening• Usually considered for earthquake zones

• Spare front filler panels #0599 server feat code

• Helps maintain proper airflow (and looks better)• Package of (3) 1U and (1) 3U snap-on/off black filler panels

• Rack extender #6257 42U 7014

• Adds 20” depth for cable management of InfiniBand switches

• Shelf• Not ordered as a feature of 7014 or of server• Ordered as feature of the I/O unit which will sit on the shelf, example:

some tape drives

© 2009 IBM Corporation28

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

42U/36U/25U Rack Option Rack Modem Tray #6586

•1U tray for 19” rack

•Holds up to two external modems …. This is NOT a shelf•Convenient for external modems of

– rackmount HMC

– system

•Also supported in 25U and 11U racks

Tray with modem installed

Page 15: Racking Your System

15

© 2009 IBM Corporation29

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

“Cool Blue” Rear Door Option #6858 Rear Door Heat Exchanger (RDX)

• Option for the 7014-T42 2m rack– Not an orderable feature for #0553 – though

would physically work

• Water cooled rear door removes heat from exhaust air flow.

• Can help eliminate hot spots from computer room.

• Can help avoid adding more air conditioning.

© 2009 IBM Corporation30

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Agenda

• Racking 19-inch IBM System Units: 520, 550, 560, 570

• Racking 19-inch IBM I/O Drawers :

– With PCI slots: #5802, #5790, #5796, #0595, #0588, #5294/96, #5094/96

– Disk only drawer: #5786, #5886

• IBM Power System 19-inch Racks 1.8m, 2m, 1.3m

• IBM Rack Options

• IBM Power Distribution Units (PDU) #7188, #7109

• IBM Rack UPS

• IBM Tape and racks

• Nuts & bolts

• Using different IBM or OEM Racks

Page 16: Racking Your System

16

© 2009 IBM Corporation31

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

#7188 Power Distribution Unit (PDU)

#1422 or #6458 IEC 320 C13/C14 PDU Cord connects PDU to

many racked devices.

# 6459 or #6664 right angle PDU cord used for #5790

Other power cords connect the PDU to the “wall/UPS” power.

• #7188 PDU• Like a power strip on massive steroids • 12 outlets per PDU (six circuit breakers – 2 outlets per breaker)• Up to 48 amps per PDU (depends on power cord from PDU to wall), up to 15 amps per breaker & 10 amps per outlet

• PDU power cords (equipment to PDU)

In 7014-T00 or T42 rack, first

PDU can be no charge #9188

© 2009 IBM Corporation32

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

• Placed horizontally, require 1U space

• Up to four #7188 can be placed vertically in “side pockets” of 1.8 or 2m rack and use zero U space. (note eConfig doesn’t track the horizontal PDUs)

• For power redundancy, recommend • Two PDU per rack for equipment with dual power cords• Plug the equipment with dual power cords into different PDUs• Plug the PDUs into different power sources

#7188 Power Distribution Unit (PDU)

Drawer

See planning web site for details

http://publib.boulder.ibm.com/infocenter/eserver/v1r2s/en_US/index.htm?info/iphad/f0551_pdu.htm

Page 17: Racking Your System

17

© 2009 IBM Corporation33

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

#7109 Intelligent PDU+

• Physically/electrically very much like #7188 PDU

• #7109 provides continuous power usage data. Data sent to PC attached via Ethernet connection

• PC running Active Energy Manager can monitor / display information.

In 7014-T00 or T42 rack, first

PDU can be partial charge #5889

© 2009 IBM Corporation34

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

#7188 vs #7109 PDU Comparison

YesYesHeight/Width: 43.9mm(1.73 in) / 447mm(17.6 in)

YesYesSupported on model 5xx & 8xx systems

YesNoEthernet connection for sending usage data

YesYes200-240 Volts AC, 1-phase

YesNoContinuously monitors power usage by outlet

350mm (13.8in)232mm (9.13in)Depth

YesYesi5/OS release independent

YesYesHorizontal mount taking 1U

YesYesSide pocket mount #0551, #0553 racks

YesYes10 Amps per outlet, 16 Amps per pair of outlets

YesYes12 client usable IEC 320-C13 outlets

#7109 PDU+#7188 PDU

Newer

Other PDUs can be ordered from IBM, but not as part of feature code racks

Page 18: Racking Your System

18

© 2009 IBM Corporation35

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Additional PDU Points

• 7014-B42 has a couple additional PDU options designed to support BladeCenter options

• System x also has additional PDU offerings.

• Temperature/Humidity probe is supported on System x equivalent of #7109 PDU. Being considered for 7014 racks. Demand TBD. Thusfuture support TBD.

© 2009 IBM Corporation36

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Uninterruptible Power Supply (UPS)

9910 UPS rack solutions offered through IBM

For details see: http://www.powerware.com/ibm

3U each (max qty 4)6U9910-E83

3U each (max qty 4)6U9910-E82

3U each (max qty 2)3U9910-E65

3U

2U

U (EIA) UPS

3U each (max qty 4)9910-E50

9910-E33

Model

2U each (max qty 4)

U (EIA) extra battery modules

Until January 2008, used “Pxx” models. Pxx and Exx models have

same specifications (wattage, EIA, extra battery)

Details you’ll want to review on Powerware site include Watts available, number of power

receptacles provided on UPS, PDU needed or not, etc

Page 19: Racking Your System

19

© 2009 IBM Corporation37

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Agenda

• Racking 19-inch IBM System Units: 520, 550, 560, 570

• Racking 19-inch IBM I/O Drawers :

– With PCI slots: #5802, #5790, #5796, #0595, #0588, #5294/96, #5094/96

– Disk only drawer: #5786, #5886

• IBM Power System 19-inch Racks 1.8m, 2m, 1.3m

• IBM Rack Options

• IBM Power Distribution Units (PDU) #7188, #7109

• IBM Rack UPS

• IBM Tape and racks

• Nuts & bolts

• Using different IBM or OEM Racks

© 2009 IBM Corporation38

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Tape/Optical Rack Enclosure

• For SCSI: 7212 – 103 (newer) or 7212 – 102 (earlier)• 1 U rack enclosure which holds up to 2 drives in 19-inch rack

– QIC 30GB or 50GB, VXA- 2 or 320, 4mm, DVD, LTO-2

• Adjustable depth rails -- 27 to 30.5 inch

• For SAS: 7214 – 1U2

• 1 U rack enclosure which holds up to 2 drives in 19-inch rack

– DAT72, DAT160,LTO-4, DVD

• Adjustable depth rails

Picture is of 7212

Functionally equivalent to tape/optical drives sitting on rack shelf (see next slide) … but rack optimized (space, power, cooling)

Page 20: Racking Your System

20

© 2009 IBM Corporation39

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

The following drives can sit on a 19” rack shelf which is ordered as feature code #8723 of the drive (device not the system).

7207-122 4GB QIC tape drive7207-330 30GB QIC tape drive7208-345 60GB 8mm tape drive7206-336 36GB 4mm tape drive7210-025 & -030 DVD-RAM drive358x LTO tape not listed here

All of the above drives have: Width 250mm / 9.8in Height 55mm / 2.2in

Tape/Optical Rack Kit (Shelf)

© 2009 IBM Corporation40

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

LTO Tape Libraries – all are full rack width

TS3100 3573 L2U (also HVEC models) Library with single drive and 24 cartridge slots, 2 EIA

Rack mount kit is 3573 feat code #7002, rack power cord is 3573 feat code #9848

TS3200 3573 L4U (also HVEC models) Library with 1 or 2 drives and 48 cartridge slots, 4 EIARack mount kit is 3573 feat code #7002, rack power cord is 3573 feat code #9848

Specify Qty:2 of feat code #9848 if select optional additional power supply

TS3310 3576 L5B Library base unit with 1 or 2 drives and 36 cartridge slots, 5 EIA

3576 L5B + (1) E9U Library base and one expansion, up to 6 drives, 128 cartridge slots, 14 EIA

3576 L5B + (2) E9U Library base and two expansions, up to 10 drives, 218 cartridge slots, 23 EIA

3576 L5B + (3) E9U Library base and three expansions, up to 14 drives, 310 cartridge slots, 32 EIA

3576 L5B + (4) E9U Library base and four expansions, up to 18 drives, 402 cartridge slots, 41 EIA

A single rack mount kit 3576 feat code #7003 supports the L5B and all attached E9U’s.

Specify one rack power cord 3576 feat code #9848 in each unit (base and expansions).

3582 L23 Library with 1 or 2 drives and 24 cartridge slots, 4 EIA

Rack mount kit is 3582 feat code #7003

3583 L18, L36, L72 Library with up to 6 drives and 72 cartridge slots, 14 EIA

Rack mount kit is 3583 feat code #8006

Enterprise Tape Library – full rack width

TS3400 3577 L5U Library with 1 or 2 TS1120 (3592 E05) drives and 18 cartridge slots, 5 EIA

Rack mount kit is 3577 feat code #7004

LTO and Enterprise Tape Library Rack Mounting Options

Author thanks Brannen Proctor for this foil.

Page 21: Racking Your System

21

© 2009 IBM Corporation41

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

LTO and Enterprise Tape Drive Rack Mounting Options

LTO Tape Drives and Autoloaders

(external attachment – not the LTO-2 drive which goes inside the 520/550 CEC)

3580 H11,H13,H23,L11,L13,L23 two units can sit side-by-side on same shelf

4 EIA = unit (14.6 cm (5.75 in)) + shelf (.7 in)Rack shelf is 3580 feat code #8723

3580 L33, L3H, H3L, H3S, L43, S43, H4S only one unit per shelf (width = 25 cm (9.85 in))

4 EIA = unit (12 cm (4.75 in)) + shelf (.7 in)

Rack shelf is 3580 feat code #7003

3581 F28,L38, F38,L38, F3H, L3H

2 EIA = unit (8.9 cm (3.5 in)) shelf not required one unit per 2U

Rack mount kit is 3581 feat code #7003

3581 H17, L17, H13, L13, H23, L23 two units can sit side-by-side on same shelf

5 EIA = unit (19 cm (7.48 in)) + shelf (.7 in)Rack shelf is 3581 feat code #7003

Enterprise Tape Drives and Autoloaders

3590 B11, E11, H11 (rack mount autoloader)

12 EIA for the shelf/cabinet(s) to hold 1 or 2 drives

3592 J1A, E05 TS1120 (rack mount drive only, no autoloader)

10 EIA for the shelf/cabinet(s) to hold 1 to 4 drives

© 2009 IBM Corporation42

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

“Nuts & Bolts”

“Cage nut” or “nut box” or “grommet”

5 mm bolt

6 mm bolt

Cable hooks

Handy things to have when installing• ratchet• power screw driver/drill• flash light – head lamp best• screw drivers• spare nuts/bolts cable ties• knife, tie cutters

Page 22: Racking Your System

22

© 2009 IBM Corporation43

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Agenda

• Racking 19-inch IBM System Units: 520, 550, 560, 570

• Racking 19-inch IBM I/O Drawers :

– With PCI slots: #5802, #5790, #5796, #0595, #0588, #5294/96, #5094/96

– Disk only drawer: #5786, #5886

• IBM Power System 19-inch Racks 1.8m, 2m, 1.3m

• IBM Rack Options

• IBM Power Distribution Units (PDU) #7188, #7109

• IBM Rack UPS

• IBM Tape and racks

• Nuts & bolts

• Using different IBM or OEM Racks

© 2009 IBM Corporation44

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

A: Yes, but The physical rack frame of the 7014-Txx/#055x (Power), 9308 (System x) and 2101

(TotalStorage) is identical. The equipment will fit into the rack. But there are differences in the rack options offered due to different value propositions of each product line. These differences are reflected in different names of the same physical feature, different features, different ordering rules, different heights, different prices, different PDUs, different options, etc. And the racks have been tested with different combinations of hardware.

If you want to insert a Power System in a 9308 or 2101; AAS/WTAAS or eConfig does not recognize this and does not offer any planning assistance. The customer/sales team must provide the planning expertise. Things to consider include:- PDUs can be different and support different voltage/amperages. Power cords from server equipment to the PDU is

probably the same (especially if Power System, System p and System i), but should be checked.-Standard IBM manufacturing processes do not insert Power Systems into non-Power Systems rack before

shipping out.

Make sure the IBM service organization is aware of what you are doing and agrees IN ADVANCE to support the configuration. The best time to resolve such questions is before a service call is needed. Though IBM Service should have no problem, there can be implications to airflow (cooling), equipment placement (customer/service safety), harmonic vibration, etc depending on what else is installed in the rack. IBM Service has the right to not provide support if they feel there are potential safety, functional or reliability concerns.

Q: Can I put my Power Systems equipment in a System x™ or TotalStorage™ 1.8m or 2m enterprise rack instead of a Power Systems rack? What about vice versa?

Page 23: Racking Your System

23

© 2009 IBM Corporation45

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

A: Probably, but The physical rack frame of these racks is not identical. They are usually narrower

and lighter weight. There are other differences in the rack options offered. These racks have not been tested with Power Systems nor with different combinations of hardware likely to have been ordered with the racks.

Make sure the IBM service organization is aware of what you are doing and agrees IN ADVANCE to support the configuration. The best time to resolve such questions is before a service call is needed. Though IBM Service should have no problem, there can be implications to airflow (cooling), equipment placement (customer/service safety), harmonic vibration, etc depending on what else is installed in the rack. IBM Service has the right to not provide support if they feel there are potential safety, functional or reliability concerns.

Note also that these racks are too narrow for “side pockets” where PDUs can reside without taking up 1 U of space. However, these racks are narrow enough to fit on a 2-foot floor tile without overlapping.

Q: Can I put my Power Systems equipment in a System x™“non-enterprise” rack instead of a Power Systems rack?

© 2009 IBM Corporation46

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Q: Can I put my IBM equipment in an OEM rack?

A: Yes, but…. Recommend contacting IBM Service BEFORE doing this. Though they will

probably support this configuration, key considerations include:

Depth: The IBM 055x & 7014 racks all have a depth of 28 inches between the front and back vertical supports. Other vendors

may have different depths.

- POWER6 520/550 has adjustable depth rails, but POWER5 520/550 originally did not but later changed to a rail design which was had adjustable depth capability.

- POWER5 570 is designed for the #0551/3 & 7014 rack. There are important cabling considerations for connecting multiple processor drawers together.

- POWER6 560/570 is a little more flexible for cabling than POWER5 570, but care must be taken to ensure it will work.

- I/O: Newer I/O drawers come with adjustable depth rails. #0595 adjusts from approximately 26 to 29 inches. #0588 or #0578 were designed for the IBM #055x 28-inch depth rack and do not fit other depths. #5790 fits inside an enclosure which has rails.

#7311 enclosure has fixed depth rails. #7307 enclosure has adjustable depth rails. #5802 has adjustable rails depth rails.

Mounting holes: Other vendors may interpret the EIA 310-D hole standards in a differently than IBM. The vendor may or

may not have adapters to accommodate the mounting hardware of other vendors. Even the OEM rack (rail) features IBM

provides use the same mounting hole pattern as the IBM rack rails. THIS CAN BE A REAL HASSLE OR EVEN A SHOW STOPPER.

General: The 19-inch rack must have the physical strength for what you are planning. Operator/service personnel safety,

accessibility, cooling, electromagnetic interference, harmonic vibration, etc. must be considered. Because of these

considerations, it is recommended that IBM Service be consulted in advance. IBM can refuse to service the equipment and

warranties can be voided if they believe there are likely to be problems. This can even happen after initially accepting the configuration if additional information becomes available.

No Configurator: Also be aware that if you rack IBM servers outside of an #055x or 7014, AAS/WTAAS or eConfig does not

offer any planning assistance. The customer/sales team must provide the planning expertise. Things to consider include: anti-tip plates, doors with adequate airflow capabilities, PDUs, cable management, weight, etc.

Page 24: Racking Your System

24

© 2009 IBM Corporation47

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

A: IBM System i5 is designed to be installed in industry-standard EIA racks. The following resources provide details about

installation in either non-IBM racks or in IBM racks not specifically listed as 'supported' in marketing materials. The customer

should use these resources, and work with their seller (either IBM or Business Partner) to assess whether the proposed rack is

acceptable for the proposed purpose, and to order the materials necessary to mount their system in a particular rack. It is

important to consider that IBM Service's involvement in implementing any solution not specifically supported by IBM's published

marketing materials is considered a billable service. This includes consultation on implementing solutions involving non-IBM

racks or IBM racks which are not specifically listed as 'supported' in the marketing materials for the system in question.

The rack must meet EIA industry standards, and it must meet the technical requirements set out in the eServer Information

Center (http://publib.boulder.ibm.com/infocenter/eserver/v1r2s/en_US/index.htm) in the Non-IBM Rack Specifications of the

Planning section of the InfoCenter. It is the customer's responsibility to ensure that these specifications are met. Planning in

advance, doing one's "homework" and making sure all technical and safety requirements are met are the key to ensuring the

resulting solution can be maintained safely and, therefore, supported by IBM service.

The IBM service representative and Field Manager responsible for the account in question should assess the proposed

scenario based on the information above and based on the customer's assurance that the rack meets EIA industry standards

and other technical and safety requirements as specified in the Information Center documentation. In addition, the device must

be mounted using mounting hardware and rails engineered to meet or exceed the specifications for the rails and mounting

hardware normally provided by IBM for the purpose of mounting the system in a rack.

It is important to understand that for customer set up systems (CSU) such as the model 520, any IBM installation/set up activity

related to a CSU device is for fee only. The device is designed/priced for customer set up/installation. So the customer shouldinstall these CSU devices whether it is installed as a desk-side or rack-mount system, unless the customer has agreed to pay

IBM a fee to install/set up the system.

If the customer is willing to pay IBM for a technical assessment of the rack, and technical assistance is required, contact the

installation planning focal point for the country or area.

Q: What do IBM Service Guidelines Say About non-IBM Racks?

© 2009 IBM Corporation48

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Q: What about exiting cables overhead vs below-floor?

A: Officially all cabling from the rack exists from the bottom, but….It’s important to understand that “IBM Support” of a specific configuration can have different a meaning to different IBMers depending on who is asking and in what context. The IBM

Development team would say, “ought to work fine, but we didn’t test and certify an overhead cable

exit and therefore not supported.” IBM Service organization might hear only the “Development

didn’t test and doesn’t support” statement.

Recommend contacting IBM Service BEFORE doing this. Though they will probably support this

configuration, it’s better to have the discussion before installation. IBM Service is the group who

will agree to support (or not support) the hardware even if cabled overhead (or not agree).

So given you understand the above:-- There is a removable plate at the top rear of the 7014-T00/T42/B42 and #0551/0553 racks which will

physically provide a nice exit location for cables out of the top of the rack. The plate was not

originally designed for this purpose, but it works fine. A service engineer can remove the plate

(billable time).

-- All signal-carrying copper cables emit a small amount of radiation (law of physics) unless really

well shielded. Running cables along the real floor and under the raised floor will reduce overall

electro-magnetic radiation levels (from small to smaller). Thus going overhead loses some of that

shielding. Most service organizations would agree it is ok for overhead, but some might not support

the server configured in this fashion.

Page 25: Racking Your System

25

© 2009 IBM Corporation49

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Agenda

• Racking 19-inch IBM System Units: 520, 550, 560, 570

• Racking 19-inch IBM I/O Drawers :

– With PCI slots: #5802, #5790, #5796, #0595, #0588, #5294/96, #5094/96

– Disk only drawer: #5786, #5886

• IBM Power System 19-inch Racks 1.8m, 2m, 1.3m

• IBM Rack Options

• IBM Power Distribution Units (PDU) #7188, #7109

• IBM Rack UPS

• IBM Tape and racks

• Nuts & bolts

• Using different IBM or OEM Racks

© 2009 IBM Corporation50

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

THANKS

Questions?

Evaluations: SMP14

Page 26: Racking Your System

26

© 2009 IBM Corporation51

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

9407-M15 & 9408-M25 Rack-mount & DesksidePOWER6 520 – without unified feature codes

Order rackmount using

– #7251 rack-mount specify

– #7267 bezel, adjust depth rails,

Order deskside using

– #7250 deskside specify

– #7224 front door (lockable)

Field conversions

announced Feb 2009

Order rackmount using– #7200 rack-mount specify

– #7114 bezel, adjust depth rails,

Order deskside using

– #7112 Covers & door (lockable)

© 2009 IBM Corporation52

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

9409-M50 Rack-mount & DesksidePOWER6 550 – without unified feature codes

Order rackmount using– #7229 rack-mount specify

– #7268 bezel, adjust depth rails,

Order deskside using– #7226 deskside specify

– #7227 front door (lockable)

No field conversions

Order rackmount using– #7360 rack-mount specify

– #7146 bezel, adjust depth rails,

Order deskside using

– #7292 Covers & door (lockable)

2008 July 22 announce

Page 27: Racking Your System

27

© 2009 IBM Corporation53

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

POWER5 Model 515/520/525 - Racking Insights

Ordering from IBM

• Specify feat code #7884 for rackmount includes– fixed depth rails for 28” deep racks (IBM rails are 28” deep)

• Also specify #7182 (1.9GHz 520)

– Front black bezel covering front of 520

• Also specify #7198 adjustable rails

– along with #7182 to order adjustable rails for 20.5 – 29.5” deep racks

4U (4 EIA)

9405-515, 9406-520, 9406-525

© 2009 IBM Corporation54

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

POWER5 515/520/525 Deskside to Rackmount

• 1.5/1.65GHz 520 MES ordering

– Convert #7885 to #7884 chargeable, ships fixed 28” depth rails

– If also want rails which are adjustable and can go in racks deeper than 28”, then ALSO order #7198 (additional charge)

• 1.9GHz 520 MES ordering

– Convert #7885 to #7182 chargeable, ships fixed 28” depth rails

– If also want rails which are adjustable and can go in racks deeper than 28”, then ALSO order #7198 (additional charge)

Deskside-to-rackmount is an MES order (Customer Set Up)

9405-515, 9406-520, 9406-525

Page 28: Racking Your System

28

© 2009 IBM Corporation55

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

POWER5 Model 550 - Racking Insights

• #7183 = IBM racking specify– Includes adjustable depth rails for 25.5 – 29.25” deep racks

IBM offers neither a rackmount-to-deskside conversion nor a deskside-to-rackmount conversion

4U (4 EIA)

9406-550

© 2009 IBM Corporation56

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Model 570 - Racking Insights

• All 570 are 19” rackmount only. Adjustable depth rails are included

• 570s bigger than 4-way are multi-drawer. This has rack implications, both IBM and OEM rack.

4U (4 EIA)

Processor drawer

If creating 8-way or 16-way 570, processor drawers must be installed adjacent to one another.

9406-570, 9406-MMA

Page 29: Racking Your System

29

© 2009 IBM Corporation57

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Four/Three Feature Coded Racks

2m(79”)42U

#0553

1.8m(71”)36U

#0551

1.3m(49”)25U

#0555

0.6m (24”)11U

#0554

This chart applies to the POWER5 and to the POWER6 non-unified servers

(9406, 9407, 9408 and 9409). It changes somewhat with the unified

POWER6 servers (8203, 8204, 8234, 9117, 9119)

Withdrawn

From

marketing

© 2009 IBM Corporation58

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

0.6 Meter Rack (11U)

• 11 EIA or 11U • 28-inch depth between vertical supports• EIA 310-D mounting hole pattern

• But square holes, unlike 1.8m or 2m rack

• Same basic rack (i, p, x), ordered differently• 7014-S11 System p (also being withdrawn)

• 9306-110 System x

• No accessories - base includes: • Front lockable doors (No rear door)

• Front filler panels if empty from plant

• Narrower than 1.8 or 2 meter rack• PDU placement impacted

• Model 570 processor drawer not supported873 mm (34.4 in)Front door, no rear door

36 kg (80 lb)

611 mm (24 in)

No rear door

28 in

N/A

518 mm (20.4 in)

DEPTH – interior (rail to rail)

WEIGHT empty

HEIGHT

Front & rear doors

DEPTH - exterior

Without side panels

With side panels

WIDTH - exterior

WithdrawnFrom

marketing

Page 30: Racking Your System

30

© 2009 IBM Corporation59

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

Ordering IBM Manufacturing Placement

Without ordering guidance, IBM Manufacturing applies general guidelines to place equipment in rack

� System CECs, I/O drawers, HMC & monitor, UPS, PDU

� Doesn’t apply to I/O not shipped from the same IBM Plant

Guidance you can give IBM Manufacturing with proper ordering

a) Reserve rack space leaves open space in the rack for inserting an HMC, HMC monitor or UPS at the customer site (no charge)

b) Factory integration directs IBM to find a separately ordered HMC, HMC monitor or UPS and insert in the 9406 rack before shipping (no charge)

c) Custom rack placement tells IBM Manufacturing exactly where to place the components in the rack (520/550 - modest charge & 570/595 – no charge)

© 2009 IBM Corporation60

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

This document was developed for IBM offerings in the United States as of the date of publication. IBM may not make these offerings available in other countries, and the information is subject to change without notice. Consult your local IBM business contact for information on the IBM offerings available in your area.

Information in this document concerning non-IBM products was obtained from the suppliers of these products or other public sources. Questions on the capabilities of non-IBM products should be addressed to the suppliers of those products.

IBM may have patents or pending patent applications covering subject matter in this document. The furnishing of this document does not give you any license to these patents. Send license inquires, in writing, to IBM Director of Licensing, IBM Corporation, New Castle Drive, Armonk, NY 10504-1785 USA.

All statements regarding IBM future direction and intent are subject to change or withdrawal without notice, and represent goals and objectives

only.

The information contained in this document has not been submitted to any formal IBM test and is provided "AS IS" with no warranties or guarantees either expressed or implied.

All examples cited or described in this document are presented as illustrations of the manner in which some IBM products can be used and the results that may be achieved. Actual environmental costs and performance characteristics will vary depending on individual client configurations and conditions.

IBM Global Financing offerings are provided through IBM Credit Corporation in the United States and other IBM subsidiaries and divisions worldwide to qualified commercial and government clients. Rates are based on a client's credit rating, financing terms, offering type, equipment type and options, and may vary by country. Other restrictions may apply. Rates and offerings are subject to change, extension or withdrawal without notice.

IBM is not responsible for printing errors in this document that result in pricing or information inaccuracies.

All prices shown are IBM's United States suggested list prices and are subject to change without notice; reseller prices may vary.

IBM hardware products are manufactured from new parts, or new and serviceable used parts. Regardless, our warranty terms apply.

Any performance data contained in this document was determined in a controlled environment. Actual results may vary significantly and are dependent on many factors including system hardware configuration and software design and configuration. Some measurements quoted in this document may have been made on development-level systems. There is no guarantee these measurements will be the same on generally-available systems. Some measurements quoted in this document may have been estimated through extrapolation. Users of this document should verify the applicable data for their specific environment.

Revised September 26, 2006

Special notices

Page 31: Racking Your System

31

© 2009 IBM Corporation61

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin

IBM, the IBM logo, ibm.com AIX, AIX (logo), AIX 6 (logo), AS/400, BladeCenter, Blue Gene, ClusterProven, DB2, ESCON, i5/OS, i5/OS (logo), IBM Business Partner (logo), IntelliStation, LoadLeveler, Lotus, Lotus Notes, Notes, Operating System/400, OS/400, PartnerLink, PartnerWorld, PowerPC, pSeries, Rational, RISC

System/6000, RS/6000, THINK, Tivoli, Tivoli (logo), Tivoli Management Environment, WebSphere, xSeries, z/OS, zSeries, AIX 5L, Chiphopper, Chipkill, Cloudscape, DB2 Universal Database, DS4000, DS6000, DS8000, EnergyScale, Enterprise Workload Manager, General Purpose File System, , GPFS, HACMP, HACMP/6000, HASM, IBM Systems Director Active Energy Manager, iSeries, Micro-Partitioning, POWER, PowerExecutive, PowerVM, PowerVM (logo), PowerHA, Power Architecture, Power

Everywhere, Power Family, POWER Hypervisor, Power Systems, Power Systems (logo), Power Systems Software, Power Systems Software (logo), POWER2, POWER3, POWER4, POWER4+, POWER5, POWER5+, POWER6, System i, System p, System p5, System Storage, System z, Tivoli Enterprise, TME 10, Workload

Partitions Manager and X-Architecture are trademarks or registered trademarks of International Business Machines Corporation in the United States, other countries, or both. If these and other IBM trademarked terms are marked on their first occurrence in this information with a trademark symbol (® or ™), these symbols indicate U.S. registered or common law trademarks owned by IBM at the time this information was published. Such trademarks may also be registered or common law trademarks in

other countries. A current list of IBM trademarks is available on the Web at "Copyright and trademark information" at www.ibm.com/legal/copytrade.shtml

The Power Architecture and Power.org wordmarks and the Power and Power.org logos and related marks are trademarks and service marks licensed by Power.org.UNIX is a registered trademark of The Open Group in the United States, other countries or both.

Linux is a registered trademark of Linus Torvalds in the United States, other countries or both.

Microsoft, Windows and the Windows logo are registered trademarks of Microsoft Corporation in the United States, other countries or both.

Intel, Itanium, Pentium are registered trademarks and Xeon is a trademark of Intel Corporation or its subsidiaries in the United States, other countries or both.

AMD Opteron is a trademark of Advanced Micro Devices, Inc.

Java and all Java-based trademarks and logos are trademarks of Sun Microsystems, Inc. in the United States, other countries or both.

TPC-C and TPC-H are trademarks of the Transaction Performance Processing Council (TPPC).

SPECint, SPECfp, SPECjbb, SPECweb, SPECjAppServer, SPEC OMP, SPECviewperf, SPECapc, SPEChpc, SPECjvm, SPECmail, SPECimap and SPECsfs are trademarks of the Standard Performance Evaluation Corp (SPEC).

NetBench is a registered trademark of Ziff Davis Media in the United States, other countries or both.

AltiVec is a trademark of Freescale Semiconductor, Inc.

Cell Broadband Engine is a trademark of Sony Computer Entertainment Inc.

InfiniBand, InfiniBand Trade Association and the InfiniBand design marks are trademarks and/or service marks of the InfiniBand Trade Association. Other company, product and service names may be trademarks or service marks of others.

Revised April 24, 2008

Special notices (cont.)

© 2009 IBM Corporation62

STG Technical Conferences 2009

Racking Your Power System … Without Aspirin62

Trademarks

The following are trademarks of the International Business Machines Corporation in the United States, other countries, or both.

The following are trademarks or registered trademarks of other companies.

* All other products may be trademarks or registered trademarks of their respective companies.

Notes: Performance is in Internal Throughput Rate (ITR) ratio based on measurements and projections using standard IBM benchmarks in a controlled environment. The actual throughput that any user will experience will vary depending upon considerations such as the amount of multiprogramming in the user's job stream, the I/O configuration, the storage configuration, and the workload processed. Therefore, no assurance can be given that an individual user will achieve throughput improvements equivalent to the performance ratios stated here.

IBM hardware products are manufactured from new parts, or new and serviceable used parts. Regardless, our warranty terms apply.

All customer examples cited or described in this presentation are presented as illustrations of the manner in which some customers have used IBM products and the results they may have achieved. Actual environmental costs and performance characteristics will vary depending on individual customer configurations and conditions.

This publication was produced in the United States. IBM may not offer the products, services or features discussed in this document in other countries, and the information may be subject to change without notice. Consult your local IBM business contact for information on the product or services available in your area.

All statements regarding IBM's future direction and intent are subject to change or withdrawal without notice, and represent goals and objectives only.Information about non-IBM products is obtained from the manufacturers of those products or their published announcements. IBM has not tested those products and cannot confirm the performance, compatibility, or any other claims related to non-IBM products. Questions on the capabilities of non-IBM products should be addressed to the suppliers of those products.

Prices subject to change without notice. Contact your IBM representative or Business Partner for the most current pricing in your geography.

Adobe, the Adobe logo, PostScript, and the PostScript logo are either registered trademarks or trademarks of Adobe Systems Incorporated in the United States, and/or other countries.Cell Broadband Engine is a trademark of Sony Computer Entertainment, Inc. in the United States, other countries, or both and is used under license therefrom. Java and all Java-based trademarks are trademarks of Sun Microsystems, Inc. in the United States, other countries, or both. Microsoft, Windows, Windows NT, and the Windows logo are trademarks of Microsoft Corporation in the United States, other countries, or both.

Intel, Intel logo, Intel Inside, Intel Inside logo, Intel Centrino, Intel Centrino logo, Celeron, Intel Xeon, Intel SpeedStep, Itanium, and Pentium are trademarks or registered trademarks of Intel Corporation or its subsidiaries in the United States and other countries.UNIX is a registered trademark of The Open Group in the United States and other countries. Linux is a registered trademark of Linus Torvalds in the United States, other countries, or both. ITIL is a registered trademark, and a registered community trademark of the Office of Government Commerce, and is registered in the U.S. Patent and Trademark Office.IT Infrastructure Library is a registered trademark of the Central Computer and Telecommunications Agency, which is now part of the Office of Government Commerce.

For a complete list of IBM Trademarks, see www.ibm.com/legal/copytrade.shtml:

*, AS/400®, e business(logo)®, DBE, ESCO, eServer, FICON, IBM®, IBM (logo)®, iSeries®, MVS, OS/390®, pSeries®, RS/6000®, S/30, VM/ESA®, VSE/ESA, WebSphere®, xSeries®, z/OS®, zSeries®, z/VM®, System i, System i5, System p, System p5, System x, System z, System z9®, BladeCenter®

Not all common law marks used by IBM are listed on this page. Failure of a mark to appear does not mean that IBM does not use the mark nor does it mean that the product is not actively marketed or is not significant within its relevant market.

Those trademarks followed by ® are registered trademarks of IBM in the United States; all others are trademarks or common law marks of IBM in the United States.