THERMOSYSTEME Cosiness with saving effect PYD ® -THERMOSYSTEME mi -Heiztechnik GmbH Dachlmoosweg 6 D-83483 Bischofswiesen Tel. +49 (0)8652 9466-0 Fax +49 (0)8652 9466-17 info @PYD.de www.PYD.de �������������������������������������������� �������� ��������System Laying Heating power PYD ® - ALUTOP Ceiling heating/cooling system PYD ALUTOP 0710-01 EN

PYD θέρμανση-ψύξη οροφής

Embed Size (px)

DESCRIPTION

PYD θέρμανση-ψύξη οροφής.Γρήγορη και εύκολη εγκατάσταση, σύμφωνα με πρότυπο DIN EN1264 υπόσχεται η PYD για υψηλότερη ποιότητα σε θέρμανση και ψύξη. Ως σύστημα οροφής ξηρό είναι κατάλληλο για εγκατάσταση στην οροφή με γυψοσανίδα.

Citation preview

Page 1: PYD θέρμανση-ψύξη οροφής

T H E R M O S Y S T E M ECosiness

w i t h s a v i n g e f f e c t

PYD®-THERMOSYSTEMEmi-Heiztechnik GmbHDachlmoosweg 6D-83483 Bischofswiesen

Tel. +49 (0)8652 9466-0Fax +49 (0)8652 9466-17

[email protected]

T H E R M O S Y S T E M E

����������������������������������������������������� � � � � �������������������������������������������������������

�������������

�������������

�������������

HeizleistungsberechnungAuslegetabellen bei Rλ,B=0,00 m2K/W

�����������������������������������������������������������������

�����������������������������������������������������������������

5

����

���

����

���

����

��

���������������������������

���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ����

����������������������

���������������

�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ���� ������

���

����

����

���

��������

���

�� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ����� � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ����� � �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ����� � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ���� � � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

����

���

����

���

����

��

���������������������������

���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ���� ����

����������������������

���������������

�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ���� ������

���

����

����

���

��������

���

�� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ����� � �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ����� � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ���� � � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ � �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ����� � � �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ����� � � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ���� � � � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

����

���

����

���

����

��

���������������������������

�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

����������������������

���������������

�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ���� ������

���

����

����

���

��������

���

�� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ��� ��� ����� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ����� � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ���� � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ � �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ��� ��� ����� � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ����� � � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ���� � � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�� ������ � �� �� �� �� �� �� �� �� �� �� �� �� ��� ��� ��� ����� � �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ����� � � �� �� �� �� �� �� �� �� �� �� �� �� �� �� ���� � � �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��

�����

��������

������������������������

���������������������������������������������������������������������������������

�����

����

����

����

����

����

���

��

��

��

��

��

��

��

��

����

������

��������

��

��

�������������������������������������������

��

�����

��������

������������������������

���������������������������������������������������������������������������������

�����

����

����

����

����

����

���

��

��

��

��

��

��

��

��

����

�������

�������

��

��

�������������������������������������������

��

� �������������������������������������������������������������������������

�������������������������������������������

�����

��������

������������������������

���������������������������������������������������������������������������������

�����

����

����

����

����

����

���

��

��

��

��

��

��

��

��

����

�������

�������

��

��

��

�����������������������������������������������������������������

System

Laying

Heating power

PYD®-ALUTOP

Ceiling heating/cooling system

PYD ALUTOP 0710-01 EN

Page 2: PYD θέρμανση-ψύξη οροφής

Subject to change without notice www.PYD.de • [email protected] Su

T H E R M O S Y S T E M E

2 Subject to change without notice www.PYD.de • [email protected]

PYD®-ALUTOP

PYD® aluminium heat conducting PYD®-PE foam foil PYD®-SR system pipe

PYD®-ALUTOP

Holohedral laying of PYD® aluminium heat conducting sheets provides for comfort in living rooms and lounges with the greatest heating power/ cooling capacity

Laying on the entire surface area provides for the best performance. • Best in combinati-on with low energy sources of heat like heat pumps and thermal value equipment. Use of gypsum plaster boards from 15mm as a visible surface to the room.

Sample laying plan

PYD®-ALUTOP is the easy, ingenious solution to using energy most

effi ciently. It combines perceptible comfort and optimal adjustability.

As a system for dry mortarless consrtuction it is most suitable for

the installation in ceilings below gypsum plaster boards.

With easy and fast laying in accordance with DIN EN 1264, PYD promises the

highest standard of quality and heating power with regard to tempering surface

We offer you the necessary security with a ten-year warranty on the system and its components, guaranteed by an independent insurance fi rm.

Measured performance fi gures in accordance with DIN 4726, production

of our components in accordance with ISO 9001, DIN 4721, CE. Our suppliers’ testing institutes.

HV2

201414

55 2222 101010

28 56

Page 3: PYD θέρμανση-ψύξη οροφής

Subject to change without notice www.PYD.de • [email protected] Subject to change without notice www.PYD.de • [email protected]

T H E R M O S Y S T E M E

Subject to change without notice www.PYD.de • [email protected]

Contents Page

Calculation of performance 4 - 5Cooling of surfaces 6 - 7Views 8 - 9Buil dups 10

PYD®-ALUTOP

Specific heating capacity

∆ΘF difference of temperature between

the surface of the ceiling and the compartment air.

∆ΘF in K q

F in W/m²

1 11,6

2 23,2

3 34,8

4 46,4

5 58

6 69,6

7 81,2

8 92,8

9 104,4

Scheme 3.1

Specific cooling capacity

∆ΘF difference of temperature between

the surface of the ceiling and the compartment air.

∆ΘF in K q

F in W/m²

1 15

2 30

3 45

4 60

5 75

6 90

Scheme 3.2

∆ΘF = Difference of temperature in K

qF = Specifi c heating power/ cooling

capacity in W/m²

PYD®-RHT pipe bracket PYD®-MB assembly bow PYD®-VW laying elbow pipe

Page 4: PYD θέρμανση-ψύξη οροφής

Subject to change without notice www.PYD.de • [email protected] Su

T H E R M O S Y S T E M E

4 Subject to change without notice www.PYD.de • [email protected]

Laying of PYD®-ALUTOP

Example:Type of room: Offi ceArea: 20 m²Heating load: 1160 WHeating load/m²: 58 W/m²Room temp.: + 20° CSpread: 5 Kelvin

3.) Interpretation of fl ow temperaturesaccording to table 5.2.

Result:

System: Q in W/m²: VL in ° C:VHT 58 37° C

Inside temperatures

Kind of room Heating Cooling

Living and bedrooms + 20 + 26

Offi ce, conference, and exhibiti-on rooms, main staircasesand counter areas

+ 20 + 26

Hotel rooms + 20 + 26

Showrooms and shops + 20 + 26

Teaching rooms in general + 20 + 26

Theatre and concert halls + 20 + 26

Bath and shower rooms, baths, changing and examinationrooms (in general every use in unclothed areas)

+ 24 alone

Restrooms + 20 +26

Heated, secondary rooms (hall-ways, staircases)

+ 15 +26

Unheated, secondary rooms(Basements, staircases, storage rooms)

+ 10 +26

Scheme 4.2 extract from DIN12831 Bbl 1:2004-04

PYD®-ALUTOP calculation of heating powerInformation for installation

The following data has to be known in order to calculate the exact heating power of PYD®-ALUTOP:

1.) Heating load from the calculationof heating load

2.) Spread between temperature of fl owand return

Laying of PYD®-ALUTOP

Example:Type of room: Offi ceArea: 20 m²Cooling load: 1160 WCooling load/m²: 58 W/m²Room temp.: + 26° CSpread: 3 KelvinFlow temperature: 16° CReturn temperature: 19° C

Maximal cooling capacity: 90 W/m²

In order to determine the exact cooling capacity of PYD®-ALUTOP, the following data has to be known:

1.) Cooling load from the calculation ofcooling load

2.) Minimal Room temp. = 26° C3.) Minimal surface temperature = 20° C4.) Flow temperature = 16° C5.) Return temperature = 19° C6.) Relative humidity = 50 %

25° C

20° C

heating

20° C

26° C

cooling

Page 5: PYD θέρμανση-ψύξη οροφής

Subject to change without notice www.PYD.de • [email protected] Subject to change without notice www.PYD.de • [email protected]

T H E R M O S Y S T E M E

Subject to change without notice www.PYD.de • [email protected]

Spread 5 K

Spread 3 K

Spread 8 K

Scheme 5.3 Table for determination of the heating load in W/m² bei 8 K Spread

Scheme 5.2 Table for determination of the heating load in W/m² bei 5 K Spread

Room

tem

p.

Syst

em

Median heating temperature in ° C

31,5 32,5 33,5 34,5 35,5 36,5 37,5 38,5 39,5 40,5 41,5 42,5 43,5 44,5 45,5 46,5 47,5 48,5 49,5 50,5

Flow temperature ΘVL

in ° C; bei 3 K

33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52

15 VHT

Heat

ing

pow

er

Q spez in

W/m

²

64 68 72 75 79 83 86 90 94 97 101 105 108 112 116 119 123 127 130 134

18 VHT 53 57 61 64 68 72 75 79 83 86 90 94 97 101 105 108 112 116 119 123

20 VHT 46 50 53 57 61 64 68 72 75 79 83 86 90 94 97 101 105 108 112 116

22 VHT 39 42 46 50 53 57 61 64 68 72 75 79 83 86 90 94 97 101 105 108

24 VHT 31 35 39 42 46 50 53 57 61 64 68 72 75 79 83 86 90 94 97 101

Chart 5.3.1 Characteristic line at Θint = 20° C

qspez

in W/m2

Flow temperature in ° C

33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53

150

140

130

120

110

100

90

80

70

60

50

40

30

20

10

VHT

Chart 5.2.1 Characteristic line at Θint = 20° C

qspez

in W/m2

Flow temperature in ° C

30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

150

140

130

120

110

100

90

80

70

60

50

40

30

20

10

VHT

qspez

in W/m2

Flow temperature in ° C

33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53

150

140

130

120

110

100

90

80

70

60

50

40

30

20

10

VHT

Chart 5.1.1 Characteristic line at Θint = 20° C

Room

tem

p.

Syst

em

Median heating temperature in ° C

27,5 28,5 29,5 30,5 31,5 32,5 33,5 34,5 35,5 36,5 37,5 38,5 39,5 40,5 41,5 42,5 43,5 44,5 45,5 46,5

Flow temperature ΘVL

in ° C; bei 5 K

30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49

15 VHT

Heat

ing

pow

er

Q spez in

W/m

²

50 53 57 61 64 68 72 75 79 83 86 90 94 97 101 105 108 112 116 119

18 VHT 39 42 46 50 53 57 61 64 68 72 75 79 83 86 90 94 97 101 105 108

20 VHT 31 35 39 42 46 50 53 57 61 64 68 72 75 79 83 86 90 94 97 101

22 VHT 24 28 31 35 39 42 46 50 53 57 61 64 68 72 75 79 83 86 90 94

24 VHT 17 20 24 28 31 35 39 42 46 50 53 57 61 64 68 72 75 79 83 86

Room

tem

p.

Syst

em

Median heating temperature in ° C

29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

Flow temperature ΘVL

in ° C; bei 8 K

33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52

15 VHT

Heat

ing

pow

er

Q spez in

W/m

²

55 59 63 66 70 74 77 81 85 88 92 96 99 103 107 110 114 118 121 125

18 VHT 44 48 51 55 59 63 66 70 74 77 81 85 88 92 96 99 103 107 110 114

20 VHT 37 40 44 48 51 55 59 63 66 70 74 77 81 85 88 92 96 99 103 107

22 VHT 29 33 37 40 44 48 51 55 59 63 66 70 74 77 81 85 88 92 96 99

24 VHT 22 26 29 33 37 40 44 48 51 55 59 63 66 70 74 77 81 85 88 92

PYD®-ALUTOP calculation of heating powerTables for interpretation for Rλ,B=0,07 m2 K/Wwith a gypsum plaster board ceiling (15 mm)

Scheme 5.1 Table for determination of the heating load in W/m² bei 3 K Spread

Page 6: PYD θέρμανση-ψύξη οροφής

Subject to change without notice www.PYD.de • [email protected] Su

T H E R M O S Y S T E M E

6 Subject to change without notice www.PYD.de • [email protected]

PYD®-ALUTOPCeiling heating

• Prerequisites for laying and comfort

Some things have to be taken into consideration:

1. Rooms with a height below 3m are suitable for the installation of a ceiling heating system only to a limited extent.

2. In accordance with DIN 1946 part 2, comfortable conditions have to be provided for the occupant. These conditions are defi ned as such:

- Distance to the exterior wall 1,0 m- Distance to the interior wall 0,5 m- Height above the fl oor of up to 2 m- The air temperature between the heights of 0,1m and 1,1m from the ground must not have a greater difference than 2 K/m, in

accordance with DIN 1946 part 2.- The fall of cold air in lounging areas must not cause a speed of the air that is >0,15 m/s.

3. The Room temp. has to be set out about 1-2 K higher than in fl oor heating systems, according to the profi le of temperature!

PYD®-ALUTOP warms up the surfaces that encompass the room fi rst. The median surface temperature of PYD-ALUTOP should not be above 30° C at a Room temp. of 22° C. An increase of the surface temperature is not recommended due to the asymmetrical nature of radiation that may arise then.

• Temperatureprofi le • Criteria of comfort

Field of comfort for the pair of variatesTemperature of room air temperature t

L - Temperature of ceiling t

D( Wurzel & Müller )

36

34

32

30

28

26

24

22

14 16 18 20 22 24 26 2812

Deck

ente

mpe

ratu

r in

°C

38

20

40

Uncomfortably warm

Uncomfortably cold

Still comfortable

comfortable

fl oor heating ceiling heating

16 18 20 22 24 26 28 30° C16 18 20 22 24° C

Temperature of compartment air in ° C

Page 7: PYD θέρμανση-ψύξη οροφής

Subject to change without notice www.PYD.de • [email protected] Subject to change without notice www.PYD.de • [email protected]

T H E R M O S Y S T E M E

Subject to change without notice www.PYD.de • [email protected]

PYD®-ALUTOPCooling of surfaces

• The dual usage heating/cooling

PYD®-THERMOSYSTEME cannot only be used for heating, but also for cooling in the summer. This yields a dual usage and another fi eld of application. With a relatively small additional effort, a heat pump can be run in a way so the ceiling heating system can be used for cooling in the summer. Doing so, a cooling capacity of up to 90 W/m² is possible, relating to the high heat transition fi gure α of 15 W/m²K of our systems. Yet, the performances achieved depend upon a variety of factors.A consideration of individual cases is necessary, since nowadays the heating loads and respectively cooling loads adductable, are signifi cantly greater in most cases. The dimensioning of the system is conducted with respect to the case of cooling, yet without neglecting the aspect of comfort.

• Health and comfort

Conventional air conditioning systems use cool air to remove the thermal load. Air in subtemperatures is blown into the rooms in great amounts.In some cases this can lead not only to a reduction of comfort, but also to impairments to health, as well. Besides the risk of draught and exposure to noise, defi cient hygienic conditions of the air channel system, in many cases caused by insuffi cient maintenance, often contribute to an impairment of health. Maintenance of our systems’ heating/ cooling surfaces is not necessary.

PYD®-THERMOSYSTEME work completely silently and without draught. This is why it’s sometimes called “silent cooling“. The exchange of energy by means of radiation corresponds to natural conditions and is perceived as very comfortable. The user perceives the room ambient to be comfortable due to the cooled surfaces, even though the Room temp. may be relatively high. The chart below shows this.Additionally, the surfaces have a homogeneous profi le of temperature without great differences or a wave-like pattern due to the ideal distribution of temperature.This means that every occupant is provided with the exact same conditions and the „traditional“ discussion about better or worse work places, when it comes to terms of room ambient, has become obsolete.

28

26

24

22

20

18

16

14

14 16 18 20 22 24 26 28 3012

Infl uence of cooled surfaces that encompass rooms= mantle surfaces(fl oor, walls, ceiling)

Range oftemperature thatis perceived ascomfortable

Conception ofcomfort: too warm

Conception ofcomfort: too cold

Example: without surface heating systemRoom temperature: 26 °CMedian temperature of mantle surfaces: 20 °CIs perceived as too warm.

Example: with surface heating systemRoom temperature: 26 °CMedian temperature of mantle surfaces 16 °CComfortable indoor climate.

1

1

2

2

Thermischer Behaglichkeitsbereich nach P.O. Fanger

Temperature of compartment air in ° C

Med

ian

tem

pera

ture

of m

antle

sur

face

s in

° C

Page 8: PYD θέρμανση-ψύξη οροφής

Subject to change without notice www.PYD.de • [email protected] Su

T H E R M O S Y S T E M E

8 Subject to change without notice www.PYD.de • [email protected]

PYD®-ALUTOPCooling of surfaces

Flow temperature : 16° C

Rücklauftemperatur: 19° C

rel. Luftfeuchtigkeit: 50 %

W/m²

Room temp. in ° C

160

105

90

75

60

45

30

15

21 22 23 24 25 26 27 28

• Setting the direction for climatisation of buildings

Nowadays, the occupant and operator have high demands on air-conditioning and heating buildings. When it comes to comfort, conventional heating systems such as static heating surfaces, climate and ventilation systems are depleted soon and only suitable with restrictions. In our times it’s important to use all the space provided ideally and at the same time conserve as much energy as possible. This should all be achieved while providing for an optimum of cosiness, comfort, and user-friendliness.Alternative sources of energy like terrestial heat exchangers or convertible heat pumps can serve as chiller units to produce chillness.

The technology of PYD®-THERMOSYSTEME opens up new, almost unlimited possibilities in this fi eld. Aluminium heat conducting sheets moulded in the shape of pyramids are integrated close to the areas of the room that encompass surfaces and adjusted to the required temperatures by means of heating or cooling water. Due to the unique moulding, an utmost of effectiveness can be achieved, redundant mass that saves energy can be conserved, and little space is used for pipes that bear water.The occupant still has the chance to adjust the room temperature himself and suit it to his request. Regulating temperature by means of heat radiation is in correspondence to the natural circumstance within most living creatures that regulate their body temperature the same way. Due to the background in nature this is perceived to be highly comfortable. Due to the great surface for transfering heat actively of PYD®-THERMOSYSTEME, small differences of temperature between the activated mantle surfaces of a room and the temperature of the air of a room suffi ce to transfer great amounts of energy noise and draught free.

• Laying and planning

We would like to assist you specifi cally in planning and laying, with regard to the individual needs of your project. Please don’t hesitate to contact us about it.

• Lower deviation of the dew point

In order to avoid the danger of a lower deviation of the dew point and the formation of condensate that comes with it, dew point detectors are installed in the individual zones of regulation. In case the dew point detector detects condensate, either the supply of cooling water to the activated surfaces will be discontinued or, optionally, the fl ow temperature of the cooling medium will be raised slowly, until the formation of condensate is no longer possible.The case of lower deviation of the dew point can be almost excluded in offi ce buildings since there often is an additional ventilation system installed in those buildings, in order to secure the minimal turnover of air and keep the relative air moisture at comfortable 50%. This means that a range that is free from dew points is maintained.

Since the eduction of cooling loads in the construction concept mentioned is undertaken by one of the PYD THERMOSYSTEME, the use of the air ventilation system can be reduced to a minimum. Thus, the space requirement for the air ventilation system is reduced and as a matter of that fact the cost of the system, as well.

• Laying tables cooling capacity Rλ,B=0,01 m2 K/W Parquet (20 mm)

Flow temperature : 16° C

Return temperature: 19° C

Relative humidity: 50 %

W/m²

Room temperature in °C

90

75

60

45

30

15

21 22 23 24 25 26 27 28

Page 9: PYD θέρμανση-ψύξη οροφής

Subject to change without notice www.PYD.de • [email protected] Subject to change without notice www.PYD.de • [email protected]

T H E R M O S Y S T E M E

Subject to change without notice www.PYD.de • [email protected]

Ceiling heating /-cooling

• Typ A

1) Rough ceiling

2) Distance bearings

3) Supporting profi le

4) Ripple- free mineral rock wool 30 - 50 mm

5) OSB board 12 mm

6) PYD®-PE foam foil 3 mm

7) PYD® mounting wood bar width B 50 mm x H 23 mm

8) PYD® aluminium heat conducting sheets

and PYD®-system pipe

9) Gypsum plaster board 15 mm

• Typ B

1) Rough ceiling

2) PYD®-PE foam foil 3 mm

3) PYD® mounting wood bar width B 50 mm x H 23 mm

4) PYD® aluminium heat conducting sheets

and PYD®-system pipe

5) Gypsum plaster board 15 mm

The weight of PYD®-ALUTOP can be estimated at 11,4 kg/m². It includes the weight of the mounting wood, PE foam, assembly bows, fi xing materials, and the PYD® aluminium heat conducting sheets with the PYD® system pipe that is fi lled with the heating medium.When a gypsum plaster board with a thickness of 15mm is affi xed, the entire weight can be estimated to be 13,1 kg.

2

67

8

1

43

9

5

center - center mounting wood bar 56 cm

1

23

4

5

center - center mounting wood bar 56 cm

PYD®-ALUTOPCeiling buildup

Page 10: PYD θέρμανση-ψύξη οροφής

Subject to change without notice www.PYD.de • [email protected] Su

T H E R M O S Y S T E M E

10 Subject to change without notice www.PYD.de • [email protected]

PYD®-ALUTOPInstructions for installation

5) Installation of PYD® assembly bows

PYD® assembly bows are affi xed to the OSB panel by means of the provided PYD®-SXM wooden screws. Where necessary, the feeding tubes are also attached to the pipe holders that are deli-vered as additional equipment

Prerequisites for installation:

1. The existing ceiling construction has to be even, clean, dry, and stable..

2. The structural condition and the laying plan match.3. The insulation for additional heat, respectively the

compensation insulation, has been inserted in accordance with EnEV and laid out accordingly.

4. The OSB panels have been affi xed to the ceilingconstruction on the entire surface area.

Needed tools/documents:1. Scissors for cutting PE-RT pipes2. Sharp knive3. Possibly PYD®-RVH decoiler for laying the pipe4. Ring wrench NW 30 mm5. Hand-held screwdriver with bit and torx6. Hand-held saw or fret saw7. Electronic tacker8. Prepackaging of pipe rings9. Laying plan

1) Installation of the mounting wood

After the OSB panels have been installed on the entire surface of the ceiling and the optional notches for the cables have been created, we start measuring, cutting, and affi xing the mounting wood bars

6) Installation of PYD® foam foil

After removing the carrier material, PYD®-PE foam foil is installed between the mounting wood bars and the assembly bows with the adhesive side facing upwards. PYD®-PE foam foil is now in-stalled in the area of the heat conducting sheets

4) Notches for PYD® assembly bows

…and dislocate the cut wooden bars by 28cm. The bars are af-fi xed to the OSB panel at the grid measurement of 56cm, not before. But now the notches for the feeding tubes are cut out

3) Labelling of the PYD® assembly bows

At only one feeding tube, at a distance of about 25 cm (+10cm for every additional feeding tube) we mark the cut through the mounting wood bar, as well as the notches for the feeding tubes. We cut the mounting wood bars at the position designated by the assembly bow…

PYD®MBassembly bow

PYD®-PYD-ETKR brackets

PYD®-PEfoam foil

PYD®-RHTpipe bracket

2) Affixing of the mounting wood bars

When installing the PYD® mounting wood bars, the grid measurement of 56 cm has to be checked. The measurement is taken from one middle to the other middle of the mounting wood bars. Every 30cm the bars are affi xed to the OSB panel with screws

Page 11: PYD θέρμανση-ψύξη οροφής

Subject to change without notice www.PYD.de • [email protected] Subject to change without notice www.PYD.de • [email protected]

T H E R M O S Y S T E M E

Subject to change without notice www.PYD.de • [email protected]

PYD®-ALUTOPInstructions for installation

Duration of assembly

PYD® ceiling system and its components for installation are designed very simply. You can estimate about 20-22 group minutes to be the required period of time for laying (basically, this depends upon the condition and preparation of the subground).This time specifi cation includes installation of the mounting wood bars, PYD foam foil, PYD assembly bows, as well as their alignment, cut and assembly. Furthermore, installation of PYD system pipe with a connection to the heating circuit distributor as well as the set-up and fi xing of PYD aluminium heat conducting sheets are included in this time specifi cation

9) Installation of PYD® system pipe

PYD® system pipe is pulled over the arch of the assembly bow and hooked in. In order to retighten the PYD® system pipe, it is compressed about 20 cm in front of the bow and pushed/ pulled as far above the PYD® assembly bow until the pipe is straight

7) Connection of the flow to the PYD® heating circuit distributor

In order to feed the PYD® system pipe to the heating circuit dis-tributor without tension, the boiler tube is pushed through PYD® laying angle. Afterwards, PYD® system pipe is connected to the fl ow of the heating circuit distributor with the PYD® adaptor and conducted to the correspondent room indicated in the laying plan

10) Connection of the return to the PYD® heating circuit distributor

After the ceiling has been covered with PYD® system pipe as indicated in the laying plan, the pipe is guided back to the PYD® heating circuit distributor. It is cut fi ttingly, pushed through the laying angle pipe, and connected to the return of the PYD® heating circuit distributor with an adaptor

PYD®-SR20system pipe

PYD®-ALUaluminium heat conducting

PYD®-VWR20laying elbow pipe

PYD®-RVHdecoiler for laying the pipel

12) Fixation of PYD® aluminium heat conducting sheets

The sheets are laid out in a row at a distance of about 10mm. The distance to the mouting wood bars has to be about 0,5 mm, in order to create a pre-tension for installing the ceiling cover

11) Installation of PYD® aluminium heat conducting sheets

PYD® aluminium heat conducting sheets are put onto the PYD sys-tem pipe from below and affi xed to the OSB panels in the middle of both sides next to the pipe by means of a tacker tool

8) Usage of PYD® laying angle

In order to ensure PYD® system pipe is installed without tension, laying angles are positioned in between two pipe holders at the points of redirection of the feed pipe and deduction

Page 12: PYD θέρμανση-ψύξη οροφής

Subject to change without notice www.PYD.de • [email protected] Su

T H E R M O S Y S T E M E

12

PYD®-ALUTOPNotice