Pumped Storage Speaker 9655 Session 664 1

Embed Size (px)

Citation preview

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    1/12

    1

    HYDROVISION 2011Evaluation of Pumped Storage Operations for Coordination with

    Wind Resources and for Supplying Ancillary Services.

    Authors

    Diana Hurdowar-Castro, Ph.D., P.Eng, Director, Power and Water Optimization, Hatch,

    Ontario, Canada

    Dieter Matzner, MScE, Principal Power Consultant, Hatch Woodmead, South Africa

    Francois Welt, Ph.D., P. Eng., Senior Optimization Specialist and Mechanical Engineer, Hatch,

    Ontario, Canada

    Abstract

    Pumped storage has the capability to support renewable power projects by providing the

    necessary generation required to firm such supplies. Pumped storage capacity can also be

    used to trade between off and on-peak energy and to provide ancillary services especiallyfor systems where conventional hydro is small or nonexistent. Spinning and non-spinning

    reserves can be produced in both the generating and pumping modes of operation,depending on the selected design of the pumping/generating units and control system.

    This paper discusses pump/generation facilities and their interaction in the market by

    describing specific experiences gained with pumped storage plants. Of particular interestis the growing role of wind power in the overall energy mix and the increased variability

    that results from its large scale implementation. To demonstrate the economic and

    operational viability of pumped storage in re-regulating wind energy, an optimizationmodel has been setup for a potential pumped storage plant and wind farm in Lesotho,

    Africa. Results were generated over a full year of operation for various wind scenariosand an associated pumped storage plant.

    With a growing demand for energy storage and rapid expansion of renewable energy, the

    analysis discussed herein is applicable to the evaluation of any future large scale

    renewable project.

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    2/12

    2

    Introduction

    Pumped storage stations are used worldwide as a means to increase on-peak powerdelivery capability by storing energy during low demand periods. This is particularly

    useful in areas that do not have a high percentage of conventional storage hydro power in

    their generation resource mix and which are heavily base loaded with nuclear or coal

    fired plants (e.g. parts of North America, Asia and Europe). With the increasedpenetration of non firm renewable energy such as wind, the issue of energy storage is

    becoming even more significant as wind generation is highly variable and can take placeat any time of the day or night.

    In addition, the use of renewable energy requires a higher amount of regulation andspinning reserves. Pumped storage stations can significantly contribute to the ever

    increasing reserve requirements. In some particular cases, pump storage stations serve a

    dual purpose, i.e. not only do they firm up the on-peak capacity, but they also provide

    water for irrigation purposes.

    Design ConsiderationsPumped storage stations use an upper and one lower reservoir to re-circulate water in a

    close loop cycle. A pumped storage station can have two artificial reservoirs; however,

    many facilities have the lowerreservoir located on an existing

    waterway. There are also

    concepts and preliminary

    designs where the lowerreservoir is an (abandoned)

    underground mine or an

    underground excavation madespecifically for the pumped

    storage project. It is preferable

    that the two storage areas arequite close to each other to minimize losses in the tunnels and conduits, and the cost of

    long penstocks. A typical pump storage station configuration is shown in Figure 1.

    Pumped storage stations operate on a daily, weekly or even seasonal basis, the differencebeing the size of the upper reservoir and inflows. When the upper reservoir is part of the

    watershed and receives natural inflow from upstream, it is considered to be an in-stream

    pump storage station and the operation may be affected by the changes in precipitation.

    Typically, the elevation differential between the upper and lower reservoir is quite large

    to minimize the amount of water that is required to store. Plant heads are usually greaterthan 100 m, and there are many instances where plant heads are in excess of 300 m (e.g.

    Bleinheim Bilboa, NY, USA). Pumped storage stations with 700 or 800 m heads are

    also increasingly common worldwide (e.g., Kazunogawa, Japan, LaCoche, France).

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    3/12

    3

    For a given amount of energy storage, the volume of water in the system is inversely

    proportional to the head. Therefore the physical size and cost of reservoirs, pump-turbineequipment and water conduits is reduced as head increases. For this reason higher head

    pumped storage developments are generally more economic.

    Large pumped storage stations are more cost effective and plant capacities tend to bequite large. Most plants have a capacity that is at least a few hundred MW, and a

    significant number of pump storage stations have a capacity in excess of a 1000 MW(e.g., Ludington with 1800 MW, Michigan, USA) especially for the newer plants constructed

    in the 1960s and beyond.

    The (cycle) efficiency of a pumped storage station is the ratio of energy output to energy

    input. Efficiency for plants constructed from the 1960s to mid 1980s is usually 68% to

    74%. More modern plants have an overall cycle efficiency in the 72% to 78% range,

    with some designs approaching 80%. Traditionally, very large motors and generators inthe power industry (and other industry) have been single speed synchronous types. This

    means pump-turbines will operate at a single point of operation in the pump mode, e.g.,the flow and MW range reduces to a single point at any given head. However, over thepast 20 years, variable speed technology has advanced to large hydro units. This is an

    increasingly popular design for pumped storage station as the variable speed permits a

    wide range of operation in both pumping and generating modes. This allows foradditional reserve capability, especially in the pumping mode of operation, as well as

    modest increases in efficiencies. However, the cost of such units can be as much as 30%

    higher than the fixed speed type. Such units have been installed in Europe (e.g.,

    Goldisthal, Germany) and Asia (e.g., Kazunogawa, Japan).

    Plant Operation

    In most cases, units are used in pumping mode during off-peak periods, typically at night,and in generating mode during the day. For the vast majority of units, there is a minimum

    amount of time required to switch from the pumping to generating mode, or vice versa.

    For newer units the minimum time for the changeover is fairly short (e.g., of the order of10 minutes), but it can be of the order of 1 hour and can be even two hours for certain

    operations.

    In older plants, it may also be required that no more than one pump cycle per day beused, and some restriction may also exist on the generating side. These rules of operation

    are imposed to prevent excessive wear and tear on the units, but also to facilitate

    scheduling of the operation in a smooth and predictable fashion. Newer plants have beendesigned for a much more flexible operation and may not exhibit such restrictions (e.g.,

    Dinorwig, UK, with up to 35 mode changes per day).

    Operation in a Coordinated Hydro-Thermal Environment

    In this regulated environment, the use of available resources is well coordinated and

    planned ahead of time according to the best available load forecast. The utilization of apump storage station is then heavily dictated by the difference between on-peak and off-

    peak load demand.

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    4/12

    4

    The cost savings comes from the ability to displace more expensive non hydro peaking

    units required to meet load,such as diesel or natural gas

    fired units, during on-peak

    hours. The savings in

    production costs has to begreater than the sum of lost

    revenue from the 20%-30%loss in cycle efficiency,

    amortized debt payment and

    expected equity cost for theplant operation to be

    profitable. As a result, pump

    storage stations have usually

    a fairly low utilization factor(0.08 to 0.18). A typical

    schedule of operation isshown in Figure 2, where theplant is operated in pumping mode for a few hours at night, and similarly for a few hours

    in generation mode during the day.

    Operation in an Open Energy Market Environment

    In this environment, the utilization of a pump storage station is heavily dictated by the

    difference between on-peak and off-peak market prices. Similar to the hydro-thermal

    environment, the price differential has to be greater than the sum of losses in pumpgenerating efficiency (e.g., 20-30%), amortized debt payment and expected equity cost

    for the plant operation to be profitable. As a result, there is a strong incentive to pump at

    low price hours and generate during high price hours. Because of price variability, theeconomic operation of a pump storage station may lead to a more dynamic schedule with

    an increased number of starts and stops or mode changes, as compared to the operation

    within a regulated environment such as described previously.

    Operation to Provide Ancillary Services

    Conventional hydro power plants are very effective at providing regulation and spinning

    reserves, as compared to other non hydro resources. The same characteristics apply topump storage units when operated in generating mode. In general, pump storage units can

    provide the following ancillary services:

    Operating Reserve Load Following. Regulation Reserve (up and down regulation). Black Start. Supply or Absorb Reactive Power.Newer units have been designed to be able to start very quickly, which means that they

    have excellent capability to respond to reserve requests.

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    5/12

    5

    When operating in pumping mode, fixed speed pump storage units cannot provideancillary services. This is where variable speed units can be very useful, as they can

    provide the same amount of operating, load following or regulation reserve as compared

    to the generating mode.

    Operation with Water Management

    A few pump storage stations are part of a more complex hydro system and as suchrequire more elaborate water management. This is the case when there is significant

    upstream inflow in one of the reservoirs. Plants with significant storage can also be used

    for flood control. In other cases, pump cycles may be interrupted during the high flowperiods, as the water must be carried downstream while generating at all hours of the day.

    Other plants may not always be free to pump and generate according to market

    incentives, e.g., when they must follow a very well defined irrigation schedule withpumping required over extended periods of time.

    Although not all pumped storage stations can be used to provide ancillary services,

    especially when considering older plants, many other plants in various parts of the world

    do contribute significantly to the ancillary service requirements (e.g., Ludington in theUSA, Dinorwig in the UK, etc.)

    Operation with Wind EnergyStorage of wind energy (as is for the case study described below) has been the focus of

    considerable attention over the last few years. A number of options have been considered

    such as the use of batteries, compressed air energy storage technology, fly wheel inertia,

    only to mention a few. Pumped storage is the most established technology, particularlywhen considering large amounts of energy storage. However, pumped storage may also

    incur the highest initial capital costs and investment requirement.

    The design of pump storage stations for storing wind energy requires some special

    consideration due to the random nature of the wind energy resource, as follows:

    Sufficient reservoir storage capacity to handle extended periods of high or lowwinds.

    Flexible range of operation as wind can fluctuate rapidly over time, with the use ofmultiple units so that high efficiencies can be maintained over a wide range bychanging the unit allocation. Variable speed designs are generally considered

    necessary to accommodate varying pumping power that is available from wind

    energy generation.

    Good ancillary service capability to contribute to the higher reserve requirementsthat the use of renewable energy imposes on the system. The ability to provide

    ancillary services can be a key factor in the profitability of the plant operation.

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    6/12

    6

    Case Study Lesotho HighlandsLesotho is a country land locked by South Africa as shown in Figure 3. The landscape is

    characterized by hill (almost cliff-like) type terrain and characteristically high winds.

    Apart from the logistics associated with installing wind in this geographic area, theseregional characteristics provide for an ideal opportunity for wind power production.

    The opportunity to export wind energy to South Africa appeared economically viable

    with the introduction

    of the South AfricanFeed in Tariff

    program in 2009

    which provides for

    attractive tariffs forrenewable resources

    such as wind.However, exportingof large scale wind,

    produced within

    Lesotho, wouldrequire firming for

    delivery to South

    Africa.

    The basis of the study

    was to gain insight into the operations that a pumped storage station (PSS) could provide

    to improve the delivery reliability and firming of renewable energy to the South Africanelectricity market. Specifically the study included a preliminary evaluation of operations

    of a wind-PSS hybrid system and the wind power capacity required to support an on-peak

    firm delivery of energy over a specified period of time each week. Various peakdeliveries were evaluated along with a staged PSS development of 1,000, 2,000, 3,000

    and 4,000 MW.

    Simulation of the wind-PSS system was carried out using the Vista DSSTM

    model. Thismodel optimizes the hourly operations of all reservoirs, units, and spillways in view of

    external energy sources like wind and other factors like market prices, load, inflow, and

    operational constraints. For the study herein, the model was used to produce anoperations pattern of pumping and generating on an hourly basis over a year-long period.

    The Model

    The Vista model simulates the hourly operation of the hydraulic system using detailed

    operational procedures analogous to those used in actual practice. The model uses

    detailed physical system and operational constraints to schedule plant dispatch, by unit, in

    a manner which optimizes revenue but which abides by defined system constraints:

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    7/12

    7

    Reservoir physical and operational limits Unit characteristics and operational limits Historical inflow sequences Channel lag and route characteristics River flow constraints

    Market price forecasts Transaction opportunities Firm contracts Transmission constraints tie lines Maintenance

    The model uses a series of arcs, which link plants, power canals, spill channels and river

    reaches as shown in Figure 4. Generating facilities are connected to buses and

    interconnected to the system via transmission lines which are tied to load centers and

    available markets as shown in Figure 5

    PSS Setup

    The features of the PSS system configuration aredescribed below and shown in Figure 6:

    Two storage reservoirs were defined, with theupper reservoir located 800 m above the

    lower reservoir to provide the desired head.

    Four units (250 MW each) were specified atthe PSS capable of pumping and/or

    generating up to a maximum capacity of

    1,000 MW, depending on the net head andwater volume moving between the tworeservoirs.

    A controlled spillway was placed at eachreservoir to handle extreme flow conditions. The plant tailrace was defined to provide a

    water level that is equal to the downstream

    reservoir elevation.

    No natural inflows at the upper or lowerreservoirs were considered in the analysis.

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    8/12

    8

    Characteristics of the PSS

    In order to perform the analysis several assumptions on the characteristics of the PSSwere required. The pumping and generating capability of the plant was modeled as four

    reversible units with a rated head of 800 m. The units were assumed to be able to operate

    in a continuous manner in both pumping and generating modes, so that it can continue to

    operate even under erratic wind conditions.

    Typical generating and pumping characteristics were adopted. In the generation mode apeak efficiency of 89% is achieved at rated head and a flow of 32 m3 /s. In the pumping

    mode, 92% efficiency is achieved at a flow of 30 m3/s. The variation of efficiency versus

    flow for both generating and pumping modes are shown in Figure 7.

    Pumps are typically available as single speed types, however variable speeds are

    available but tend to be more expensive. For the purposes of this preliminary level study,

    the continuous mode was employed to ensure maximum use of incoming wind power.

    The system was modeled to include up to four pumped storage stations each comprising aset of two reservoirs and corresponding pumped storage facilities.

    Storage Characteristics

    The upper and lower reservoirs were assumed to have a storage capability of up to 13

    Million Cubic Meters (MCM), which would permit accumulation of energy over asustained period even under a continuous pumping mode of operation. The elevation to

    volume curve has been assumed to be linear, with both reservoirs sharing the same

    characteristics.

    Plant Tailwater Characteristics

    The plant tailwater elevation was assumed to be the same as the downstream reservoirelevation. As a result, the plant head is simply,

    Plant Head = upper reservoir elevation lower reservoir elevation.

    Wind Data

    Mesoscale data indicating the general spatial wind speed patterns over the terrain was

    available. For modeling purposes however an hourly wind time series was required to

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    9/12

    9

    analyse wind coordination with the proposed PSS. Procurement of general hourly time

    series data (satellite derived) for each of three wind farm locations was obtained. In orderto perform the analysis the Goldwind 77 1.5MW wind turbine with an 85m hub height

    was assumed. The power curve from the manufacturer was adjusted to the site conditions

    and used to develop an hourly power delivery pattern over the designated yearlong period

    for each site.

    TransmissionThe wind energy was modeled as a set of external energy sources. Three buses,

    representing the three different wind farms were defined to incorporate the wind spatial

    diversity. A bus collecting generation from the various sources (wind and PSS) waslinked to the South African power market. The various buses were all connected via

    transmission lines of unlimited capacity. The wind energy can be transmitted to the main

    collecting bus where it can be sold directly to the South African power market under the

    preferential tariffs (e.g., REFIT), or it can be used to power the pumping units.

    Simulation MethodologyThe operations simulated were formulated on the basis that the Lesotho wind andpumped storage system would be isolated with only the ability to export energy i.e.,

    South African off-peak energy was not available for pumping. Consequently pumping

    for reservoir refill could occur using wind energy resources only during the off-peakhours.

    In the off-peako wind energy is used to pump water to the upper reservoirs.o once the reservoirs are full, excess wind energy is sold as secondary

    energy into the S.A. market.

    In the on-peak

    o wind energy is sold directly to the market as part of the firm delivery.o shortfalls in meeting the firm are supplied by the generation cycle of the

    PSS.

    o if the reservoirs are empty and firm can not be met the model records themagnitude of the shortfall.

    Shortfalls in meeting the on-peak firm requirement were recorded and subsequently used

    to determine system reliability for the level of wind and PSS installed.

    A number of runs were performed which simulated operations for delivering 25, 30 or 35

    hours of on-peak energy to a firm value of 1000, 2000, 3000 and 4000 MWcorresponding to a PSS staged development of equivalent scale. The reliability

    associated with meeting the firm commitments were assessed as a function of the wind

    capacity installed.

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    10/12

    10

    Simulation Results

    As the model simulateshourly operations over an

    entire year the interaction

    between the incoming wind,

    pumping, generating,reservoir usage and energy

    export delivery was closelymonitored and preliminary

    conclusions formulated on

    the reliability of supply.Simulations provided an

    opportunity to specifically

    determine the reliability of

    meeting firm commitment,the average shortfall, the unit operations and usage of the reservoirs.

    Figure 8 shows the reliability results for a 25 hour per week on-peak delivery of 1000,2000, 3000 and 4000 MW and the associated wind farm capacity required to achieve

    various reliability levels. For example, results indicated that to achieve a 95% reliability

    level, in terms of delivering 1000 MW for a 25-hour on-peak weekly commitment,approximately 600 MW of wind would be required.

    The reliabilities curve asymptotically at higher reliability levels due to the magnitude of

    wind required to meet firmdemand at that level. This

    trend can be attributed to

    specific weeks during theyear when the wind is

    unusually low and the

    reservoirs are completelydepleted. These specific

    periods of time are seen to

    require significant

    additional wind capacity toincrease firm reliability.

    The number of shortfalls

    encountered during on-peakhours over the duration of

    the yearlong simulation and their associated magnitude, were sorted and categorized into

    a plot as presented in Figure 9 showing probability of occurrence and average shortfall

    for the various wind farm capacities modeled. With increasing wind supply the average

    shortfall and likelihood of occurrence decreases.

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    11/12

    11

    For all simulations, the

    operation of the pump

    storage plant was

    essentially optimized to

    minimize the number of

    shortfalls, given the windinput energy and the firm

    delivery requirement. A

    typical operation, in terms

    of generation and pumping

    operations over a week

    long period for the 25-

    hour 1000 MW firm

    requirement is shown in

    Figure 10.

    The capability of the pumped storage plant to firm wind energy is further illustrated in

    Figure 11, which shows the wind energy input over a week long period along with the net

    energy output. The on-off shaping is visibly present on the output side, while being

    totally absent in the raw wind input energy.

    Upper and Lowerreservoir utilization is

    recorded throughout the

    yearlong simulationperiod. Figure 12 shows

    the upper reservoir usage

    for a 2-week period for the25-hour 1000 MW case.In the cases modeled

    herein the storage of the

    reservoirs was set and theoperations limited by the

    storage capability defined.

    Conclusions

    Storage of wind energy has been the focus of considerable attention over the last few

    years. A number of options have been considered such as the use of batteries, compressedair energy storage technology, fly wheel inertia etc. Storage can be an important

    component of any generation system when export of the wind energy, as part of a firm

    commitment, is required. Pumped storage is the most established technology,particularly when considering large amounts of energy storage. However, pumped

    storage may also incur the highest initial capital costs and investment requirement.

  • 8/3/2019 Pumped Storage Speaker 9655 Session 664 1

    12/12

    12

    As part of a study to assess the coordination of operations, between proposed wind farms

    and PSS facilities inLesotho, an analysis was

    performed to determine the

    likely operations, reservoir

    usage, reliability of firmdelivery and average

    shortfall for severalproposed systems. In the

    analysis, a review of the

    coordinated operations of alarge scale wind resource

    combined with a pump

    storage facility ranging

    from 1000 to 4000 MW waspresented using an optimization model to project the level of coordination. Estimates on

    the size of wind farm, for specific pumped storage facility sizes, was determined forseveral reliability levels.

    This information was subsequently used to assess the economic viability of the proposed

    works.

    Dr. Hurdowar is Director of Power and Water Optimization, Hatch, Canada, with over 20 years of

    engineering experience. Her most recent emphasis has been on hydro operations which includes

    optimization analyses for power generation, power system planning, energy deregulation, relicensing, and

    most notably coordination between renewable power sources and hydro-thermal coordination.

    Mr. Matzner is principal power consultant, Hatch, South Africa. Dieter leads the renewable power team of

    Hatch in Africa with its' main focus of developing wind, solar (PV, CPV and CSP) and hydro-electric

    projects for clients.

    Dr. Welt is a Mechanical Engineer specialized in the development of software solutions for the hydro

    industry. He has held lead technical positions in the design and implementation of water management

    systems for electricity producers.