24
BA 259F/00/en/07.02 52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement Operating Instructions

prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Embed Size (px)

Citation preview

Page 1: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

BA 259F/00/en/07.0252014981 prosonic T

FMU 230/231Ultrasonic Level Measurement

Operating Instructions

Page 2: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Short Instructions Prosonic T FMU 230/231

2 Endress+Hauser

Short Instructions

Quick and easywithout display

More functions with plugged-in display

– V

– +

V H

0%

100%

BD

BD

– H

V+

2. Reset:

4. Adjust level to 100%,wait 35 s, confirm(s. lower figure):

3. Adjust level to 0%,wait 35 s, confirm(s. upper figure):

or

or

1. Unlock device:

5. Lock device:

V H

1.660 02

E

F

100%

0%

+

V

H

V0V1V2V3V4

H0 H1 H2 H3 H4V

VV H

BD

1. Reset instrument V9H5– Input:

2. Length unit V8H2– Input: m

ft

333

0:1:

3. Empty calibration V0H1– Input:

4. Full calibration V0H2– Input:

E (m/ft)

F (m/ft)

4: Conveyor belt

3: Bulk solids

2: Dome cover

1: Rapid levelchange

0: Liquid

5. Application V0H3– Input:Parameter

MatrixPosition

: Increases the parameter value

: Decreases the parameter value

or : Confirms the entry

Selection of matrix position:

Operation matrix Basic calibration (Chap. 6.1)

After Basic calibration:Linearization (Chap. 6.2)Set current output (Chap. 6.3)

••

Page 3: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Prosonic T FMU 230/231 Table of Contents

Endress+Hauser 3

Table of Contents

Short Instructions . . . . . . . . . . . . . . . . . . . . . . . 2

1 Safety instructions . . . . . . . . . . . . . . . . . 4

2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . 5

3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

4 Display and operating elements . . . 7

5 Commissioning withoutdisplay module . . . . . . . . . . . . . . . . . . . . 8

6 Commissioning withdisplay module . . . . . . . . . . . . . . . . . . . . 9

6.1 Basic calibration . . . . . . . . . . . . . . . . . . . . . . 106.2 Linearization . . . . . . . . . . . . . . . . . . . . . . . . . . 116.3 Current output . . . . . . . . . . . . . . . . . . . . . . . . 136.4 Additional parameters . . . . . . . . . . . . . . . . . . 146.5 Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . 156.6 Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

7 Trouble shooting . . . . . . . . . . . . . . . . . 16

8 Accessories . . . . . . . . . . . . . . . . . . . . . . . 18

9 Technical Data . . . . . . . . . . . . . . . . . . . 20

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Operating Matrix FMU 230/231 . . . . . . . . 22

Page 4: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

1 Safety instructions Prosonic T FMU 230/231

4 Endress+Hauser

1 Safety instructionsThe compact transmitters Prosonic T FMU have been designed to operate safely in accordance with current technical and safety standards and must be installed by qualified personnel according to the instructions in this manual. The manufacturer accepts no responsibility for any damage arising from incorrect use, insatallation or operation of the equipment. Changes or modifications to the equipment not expressly approved in the operating instructions or by the bodies responsible for compliance may make the user‘s authority to use the equipment null and void. Damaged instruments which may be a safety hazard must not be operated and are to be marked as defective.

Use in hazardous areas When used in explosion hazardous areas, the equipment must be installed in accordance with local regulations as well as with technical and safety requirements on the measuring point as specified in the accompanying certificates.

Installation andCommissioning

Installation, electrical connection, commissioning, operation and maintenance may only be carried out by trained and authorized personnel. The personnel must read and understand these operating instructions before carrying them out.

Operation The instruments may only be operated by trained personnel authorized by the plant operator. The instructions given in this manual are to be followed exactly.

Safety conventions and symbols

In this operating instructions, safety-relevant information is indicated by the following symbols:

Symbol Meaning

!Note!"Note" indicates activities which - if improperly executed - could have an indirect impact on operation or trigger unexpected device actions.

"Caution!"Caution" indicates activities or processes which - if improperly executed - could lead to personal injury or to incorrect functioning of the device.

#Warning!"Warning" indicates activities or processes which - if improperly executed - could lead to serious injury to persons, to a safety risk or to destruction of the device.

% DC voltageA terminal at which DC voltage is applied or through which DC flows.

& Alternating currentA terminal at which (sinusoidal) alternating voltage is applied or through which AC flows.

)Ground connectionA grounded terminal, which, from the user's point of view, is already grounded by a grounding system.

* Protective earth connectionA terminal which must be grounded before other connections may be made.

+Equipotential terminalA connection which must be connected to the grounding system of the equipment: this can, for example, be a potential matching line of a star-shaped grounding system, depending on national or company code of practice.

Page 5: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Prosonic T FMU 230/231 2 Installation

Endress+Hauser 5

2 InstallationInstallation variants

Blocking distance

Level echos from the blocking distance (BD) cannot be evaluated due to the transient characteristics of the sensor. Install the Prosonic T at a height so that the blocking distance BD is not undershot, even at maximum fill level. Use a pipe nozzle if you cannot maintain the blocking distance in any other way. The interior of the nozzle must be smooth and may not contain any edges or welded joints. In particular, there should be no burr on the inside of the tank side nozzle end. Note the specified limits for nozzle diameter and length.

" Caution!If the blocking distance is undershot, it may cause device malfunction.

counter nut (PA)supplied for G 1 ½"and G 2" instruments

seal

adapter flange

Installation with counter nut Installation with sleeve

Installation with adapter flange Installation with installation bracket

Sensor Blocking distance FMU 230 0,25mFMU 231 0,4m

max.

BD

LD

seal

adapter flange

FMU 230 with Display

50 8080 240

100 300

D [mm] max.L [mm]

FMU 231 with Display

80 240100 300

D [mm] max.L [mm]

FMU 230/231without Display:Dmin = 100 mmLmax = 150 mm

Page 6: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

2 Installation Prosonic T FMU 230/231

6 Endress+Hauser

Installation position

• Do not install the sensor in the middle of the tank (3). We recommend leaving a distance between the sensor and the tank wall (1) measuring 1/3 of the tank radius.

• Use a protective cover (page 18), in order to protect the device from direct sun or rain (2).

• Avoid measurements through the filling curtain (4).• Make sure that equipment (5) such as limit switches, temperature sensors, etc. are not

located within the emitting angle α. In particular, symmetrical equipment (6) such as heating coils, baffles etc. can influence measurement.

• Align the sensor so that it is vertical to the product surface.• Never install two ultrasonic measuring devices in a tank.

! Note!Make use of the echo quality display (page 14) to find the best installation position.

Installation Screw the Prosonic T at the screw-in piece using an 60 AF spanner. In order to facilitate the wiring the housing is rotatable after installation.

1

2 3 4

5

6

α/2 = 5,5°

1/3 R

r

α

Sensor L rFMU 230 5 m 0,38 mFMU 231 7 m 0,67m

60

housingturnable afterinstallation

AF 60

max torque20 Nm

Caution!Use only the hexagonalnut to screw in theProsonic T#

Page 7: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Prosonic T FMU 230/231 3 Wiring

Endress+Hauser 7

3 Wiring

4 Display and operating elementsOperating elements

The operating elements are located under the cover of the housing.

LED Pressing of a key is confirmed by a flash of the green LED.

Display module(optional)

When the display module is used, the Prosonic T is operated via an operating matrix. The current matrix position and the associated parameter (e.g. measured value) are displayed on the module. The bargraph represents the measured value or the echo quality, depending on the matrix position.The basic functions for simple applications (empty and full calibration, locking and unlocking) are accesible without the display module.

1. Open the housing cover.2. Insert cable through gland, make

connection according to the figure.3. Tighten cable gland.

Note!Use screened two-core instrumentation cable.For optimal protection against electromagnetic interference, the screen should be grounded in the control room or the nearest earthing point. A good connection to ground is essential to good screening.

Supply voltage:12 ... 36 VDC

!+4

-5

V+ H

V H

plug-in display

matrix position

parameters

segmented bar diagram

operating keys

green LED:confirm entry

Page 8: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

5 Commissioning without display module Prosonic T FMU 230/231

8 Endress+Hauser

5 Commissioning without display moduleWhen operated without the display module, the empty- and full-distance are detected by the instrument itself and have to be confirmed by a key combination.

Methods of calibration • after installation: The vessel is emptied to 0% and filled to 100% afterwards.• before installation: The respective levels are simulated by directing the Prosonic T at

the appropriate distance to a plain wall.

The procedure

Reset A reset causes most of the instrument settings to return to the factory settings. The following parameters are not affected by a reset:• all linearisation parameters• the m/ft selection (V8H2)The factory settings are included in the operating matrix on page 22.

Locking Locking protects the entries against unwanted and unauthorized changes.

Current output After calibration the Prosonic T outputs a current according to the measured value. The complete measuring range (0% ... 100%) is mapped to the current interval 4 ... 20 mA.

– V

– +

V H

0%

100%

BD

BD

– H

V+

2. Reset:

4. Adjust level to 100%,wait 35 s, confirm(s. lower figure):

3. Adjust level to 0%,wait 35 s, confirm(s. upper figure):

or

or

1. Unlock device:

5. Lock device:

Page 9: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Prosonic T FMU 230/231 6 Commissioning with display module

Endress+Hauser 9

6 Commissioning with display moduleOperating matrix

When the display module is used, the Prosonic T is operated via an operating matrix. Each matrix field represents an operating parameter. The matrix can be accessed via the keys. The meaning of the matrix fields is summarised on page 22.

Key operation withplugged-in display

Selecting the matrix field

Increases the vertical matrix position by 1.

Increases the horizontal matrix position by 1.

and Resets the display to V0H0 (measured value).

Entering parameters

or Activates the selected matrix position. The smallest digit flashes.

or

Increases or decreases the flashing digit.To enter large parameter changes hold the key pressed.When the decimal is exceeded (for the first or second time), the digit retains the value 0 and the next digit begins to change. If you release the key, the smallest digit can be edited again.

and Resets the parameter to its original value, if it has not yet been confirmed.

Confirming the entry

Confirms the entry and selects the next matrix position (vertically).

Confirms the entry and selects the next matrix position (horizontally).

and Confirms the entry and resets the display to V0H0.

Locking/unlocking the matrix

and Locks the matrix.

and Unlocks the matrix.

Page 10: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

6 Commissioning with display module Prosonic T FMU 230/231

10 Endress+Hauser

6.1 Basic calibration

Reset(V9H5)

1. Enter "333" into the matrix position V9H5.This sets all matrix positions back to the factory settings. Only the linearisation para-meters (V2H0 ... V2H3) and the length unit (V8H2) retain their current values.

Length unit(V8H2)

2. In V8H2, select the length unit for all subsequent inputs:

" Caution!Change the unit only immediately after a reset. If you change the length unit at a later point, all subsequent entries have to be repeated in the new unit.

Empty distance (V0H1)Span (V0H2)

3. Enter the empty distance E into V0H1 and the span F into V0H2. Use the units, which have been selected in V8H2.

Application parameter(V0H3)

4. In V0H3 enter the application parameter according to the following table:

Measured value display 5. Now the instrument is measuring. You can read out the following values:

Check, if the displayed values match the actual level.– If the displayed distance D (V0H8) is too small: Perform an interference echo sup-

pression (page 14).– If al false level is displayed: Adjust empty distance and span.

Current output(V9H8)

6. After the basic calibration the Prosonic T outputs the level in the form of a current sig-nal. The complete measuring range (0% ... 100%) is mapped to the current interval 4 ... 20 mA. The current value (mA) is displayed in matrix position V9H8.

V8H2 Unit0 (Default) m1 ft

• The Empty distance E is the distance from the sensor diaphragm to the 0% level.

• The Span F is the distance from the 0% to the 100% level.

E

F

100%

0%

BDE: Empty distanceF: Measuring range

(span)

V0H3 Application0 Liquid1 Liquid with rapid level change2 Liquid in vessels with dome ceiling3 Coarse bulk solids4 Conveyor belt

Matrixfeld DisplayV0H0 Level in %V0H8 Distance D from sensor diaphragm to product

surface (m or ft)V0H9 Level in m or ft

Page 11: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Prosonic T FMU 230/231 6 Commissioning with display module

Endress+Hauser 11

6.2 Linearization

After the basic calibration, the measured value is displayed in V0H0 as a percentage of the span. The value can be converted into any other unit by the linearization function. Four different modes of linearization can be selcted in V2H0.

Linearization mode"Level" (V2H0=0)

Use this mode, if you want to display the level in the length unit, which has been selected in V8H2 (m or ft).

Linearization mode"linear"(V2H0=5, Default)

! Note!The factory setting is V2H5=100. That means, the level is expressed in % by default.

Linearization mode"manual" (V2H0=2)

Use this mode, if you want to measure:• the level in any unit other than m, ft or

%.• the volume or weight, if the volume-to-

level relationship of your vessel is linear.

Step Matrix position

Entry / Meaning

1 V2H0 "4": Deletes a linearization table that might be present2 V2H0 "5": Linearization mode "linear"3 V2H5 Maximum level F (or appropriate volume or weight, respectively) in the desired unit.

Use this mode, if you want to measure the volume or weight, and if a sufficient number of value pairs level/volume or level/weight are known. You can enter up to 11 value pairs into the linearization table. The table must be monotonically increasing.

Step Matrix position

Entry / Meaning

1 V2H0 "4": Deletes a linearization table that might be present2 V2H0 "2": Linearization mode "manual"3 V2H1 number of the value pair (1 ... 11)4 V2H2 Level of the value pair (unit according to V8H2, m or ft)5 V2H3 Volume or weight of the value pair (in the desired unit)Repeat steps 3 to 5 for all value pairs6 V2H0 "1": Activates the table

Page 12: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

6 Commissioning with display module Prosonic T FMU 230/231

12 Endress+Hauser

Linearization mode"semi-automatic" (V2H0=3)

Use this linearization mode, if you want to measure the volume or weight, while the value pairs level/volume or level weight are not yet known.The vessel is emptied in steps. At each step, the Prosonic T automatically registers the level. The associated volume or weight must be entered manually.

Exception: cylincrical horizontal tank

Error message As long as a linearization table is being entered, the current output indicates an error message. The error disappears as soon as the table is complete and activated.

Measured value display When the table has been activated, the following measured values can be read out:

Current output The current output always follows the measured value V0H0. Therefore, the 4 mA value (V0H5) and the 20 mA value (V0H6) must be adapted to the new units (see chapter 6.3).

Step Matrix position

Entry / Meaning

Fill the vessel to a level of 100%1 V2H0 "4": Deletes a linearization table that might be present2 V2H0 "3": Linearisation mode "semi-automatic"3 V2H1 number of the value pair (1 ... 11)4 V2H2 Check the displayed level and confirm by pressing .5 V2H3 Enter the associated volume or weight (in the desired unit)Empty the vessel stepwise and repeat steps 3 ... 5 for each point6 V2H0 "1": Activates the table

The linearization for a cylindrical horizontal tank is performed in the following way:1. Determine the diameter D and the total

volume Vtot of the tank.2. Multiply this value by the factors given

in the table below.3. Enter these values into the instrument

as described above (Linearization mode "manual").

V2H1 V2H2 (m or ft) V2H3 (desired unit)1 0 02 D x 0,1 = Vtot x 0,052 =3 D x 0,2 = Vtot x 0,1424 =4 D x 0,3 = Vtot x 0,2523 =5 D x 0,4 = Vtot x 0,3735 =6 D x 0,5 = Vtot x 0,5 =7 D x 0,6 = Vtot x 0,6164 =8 D x 0,7 = Vtot x 0,7477 =9 D x 0,8 = Vtot x 0,8576 =

10 D x 0,9 = Vtot x 0,9479 =11 D = Vtot =

Matrix posi-tion

Display

V0H0 Volume or weight in the unit of the linearizationV0H8 Distance D from sensor diaphragm to product surface (m or ft)V0H9 Level in m or ft

Page 13: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Prosonic T FMU 230/231 6 Commissioning with display module

Endress+Hauser 13

6.3 Current output

In V8H1 you can define the mode of the current output. You have got the following options:

Continuous output(V8H1=0, Default)

Continuous output with 4 mA threshold(V8H1=1)

In addition to the linear scaling the 4 mA threshold becomes effective in this option. It makes sure, that the current output does not fall below 4 mA even if the measured value is less than V0H5. Use this option, if your control system can not handle currents below 4 mA.

Binary output4/20mA (V8H1=2) or8/16mA (V8H1=3)

Current on Fault(V0H7)

In V0H7 specify the behaviour of the current output for the case of an error.

Display of the current output (V9H8)

The current output (mA) is displayed in matrix positon V9H8.

• In the continuous mode, the output directly follows the measured value V0H0.

• V0H5 and V0H6 define the interval of the measuring range which is mapped to the current interval 4 ... 20 mA. The factory settings (V0H5=0, V0H6=100) can only be used if no linearization is present. In any other case these values must be specified in the unit of the linerization.

• If V0H5 is larger than V0H6, then the current output is inverted. That means the current decreases if the level increases and vice versa.

20 mA4 mA

V0H6

V0H5

F

100%

0%

V0H0

Measuredvalue

Current

If binary output is selected, the current only assumes two possible values:• It jumps to 20mA (or 16mA), as soon as

the measured value exceeds V0H6.• It jumps to 4mA (or 8mA), as soon as the

measured value falls below V0H5.

20 mA4 mA

V0H6

V0H5

F

100%

0%

8 mA 16 mA

Measuredvalue

Current

V0H7 Output on error0 3,8mA1 22 mA (Default)2 hold last value

Page 14: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

6 Commissioning with display module Prosonic T FMU 230/231

14 Endress+Hauser

6.4 Additional parameters

Echo Quality(V3H2)

The echo quality of the ultrasonic signal is displayed in V3H3 in steps from 1 to 10. Additionally it is indicated by the bargraph in the matrix positions V0H8 and V0H9. Use this display in order to find the best installation position. For a sound measurement, the echo quality should be at least 5.

Interference echosuppression (V3H0)

Temperature(V3H5)

The actual temperature at the sensor is shown in V3H5. If the limit of 80°C has been exceeded once, the highest value ever reached remains stored (drag indicator).

Lost echo delay time(V8H3)

The lost echo delay time makes sure that no alarm will be output if the echo becomes lost for a short period of time (for example due to foam). Values between 0 and 255 s can be entered. The dafault setting is 60 s. For standard applications the lost echo delay time should be not less than 30 s.

Actual level(V3H1)

Falsifications in height in V0H9 (e.g. by temperature effects) can be corrected by entering the correct height - the actual height - in V3H1. Entering the actual height then automatically corrects the empty calibration.

First Echo Factor(V3H4)

Vessels with tightly rounded roofs (dome covers) can cause double echos giving rise to a display showing a level which is too low. Double echos can be excluded by increasing the first echo factor to "maximum".

Output damping(V0H4)

The effect of the output damping is to attenuate the analogue output and the measurand indication on the display of the Prosonic T. When the liquid surface is not steady, a steady reading can be obtained with the aid of the output damping. Values from 0 to 255 s can be entered. The default setting is 3 s. Please note, that the Prosonic T can not resolve level changes faster than the output damping.

The interference echo suppression is used when the level echo is not detected because a fitting is generating a stronger interference echo. Up to three interfernece echos can be suppressed. The suppression should be activated with the tank as empty as possible.

Step Matrix position

Entry / Meaning

1 V0H8 Check the displayed distance between sensor diaphragm and product surface. An interference echo suppression is necessary, if the displayed value is too low.

2 V3H0 Enter the actual distance between sensor diaphragm and product surface. Confirm by pressing . Wait approx. 40 s. The interference echo is suppressed.

3 V0H8 Check the displayed distance between sensor diaphragm and product surface. If the displayed value is still to low, a furhter interference echo must be suppressed. Therefore, repeat Step 2.

V3H4 First Echo Factor

0 off

1 medium

2 maximum

Page 15: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Prosonic T FMU 230/231 6 Commissioning with display module

Endress+Hauser 15

6.5 Simulation

The measured value is processed by the Prosonic T in two steps and subsequently output to external instruments. With the simulation function the correct operation of each of these steps can be checked.

Level simulation(V9H6=1)

Use the level simulation to check the linearisation:1. Set V9H6=12. In V9H7, enter a level. Use the unit, which has been selected in V8H2 (m or ft).3. Check if V0H0 assumes the correct value.4. Set V9H6=0 to return to the ordinary operation mode.

Volume simulation(V9H6=2)

Use the volume simulation, to check the scaling of the output value:1. Set V9H6=22. In V9H7, enter a main value (level, volume or weight).3. Check if the output current (V9H8) assumes the correct value.4. Set V9H6=0 to return to the ordinary operation mode.

Current simulation(V9H6=3)

Use the current simulation to check correct operation of the external instruments:1. Set V9H6=32. In V9H7, enter a current (in mA).3. Now, the specified current is present at the output. Check, if the external instruments

respond correctly to this current.4. Set V9H6=0 to return to the ordinary operation mode.

6.6 Locking

Locking via the keyboard

Locking via the matrix (V9H9)

! Note!If the instrument has been locked via the keyboard, it can only be unlocked again via the keyboard. Unlocking via the matrix is not possible in this case.

V0H0: main value(level, volume, weight)

V9H8Current output

V0H9Level Linearization

Output

scaling

externalinstruments

Key combination Meaning

and Locking of the instrument against parameter changes

and Unlocking of the instrument

V9H9 Meaning

≠ 333 Locking of the instrument against parameter changes

333 Unlocking of the instrument

Page 16: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

7 Trouble shooting Prosonic T FMU 230/231

16 Endress+Hauser

7 Trouble shootingTypes of error messages The self monitoring system of the Prosonic T distinguishes beween alarms and

warnings.

Alarm• The bargraph flashes (if the display is plugged in)• The current output adopts a preselected value (page 13)• An error code is output in V9H0.

Warning• The instrument continues to measure.• An error code is output in V9H0.

Error codes V9H0 Type Cause Removal

E101 ...E103

Alarm/Warning

Initialisation Appears after switching on. If error remains, contact Endress-Hauser service.

E106 Alarm Download in progress Wait until completed.

E110 ...E121

Alarm Electronics error Reset instrument (V9H5 = 333). If error remains, contact Endress+Hauser service.

E125 Alarm Defective sensor Check sensor connection, contact End-ress+Hauser service if error remains

E261 Alarm Error in temperature sensor Contact Endress+Hauser service

E501 Alarm Sensor electronics not recog-nised

Contact Endress+Hauser service

E602 Warning Linearisation curve is not rising continuously

Check manual linearisation curve. Does the volume increase with height?

E604 Warning Linearisation curve has less than 2 points

Enter more points

E605 Alarm Linearisation table not available Activate the linearisation curve after entering all points.

E613 Warning Simulation activated Switch to normal operation after simulation is completed (V9H6=0).

E620 Warning Current outside range Check calibration and setting of the current output.

E641 Alarm No usable echo Check, if a better position of the sensor is pos-sible.

E661 Warning High temperature (greater than 80°C/176°F)

Check measuring conditions.

Page 17: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Prosonic T FMU 230/231 7 Trouble shooting

Endress+Hauser 17

Fault analysis

Output currenttoo large ortoo small

yesCheck V0H0:Is the displayed measuredvalue correct?

Adjust outputscaling(s. chap. 6.3)

no

V0H0 to large orV0H0 to small, see below.

Main value V0H0too small orjumps occasion-ally to smallvalues

Check V0H8 :Is the displayed distancebetween sensor diaphragmand product surfacetoo large?

Gas layering? Contactservice

Adjust linearisation(s. chap. 6.2)

Multiple echos- V0H3: Select "2" (dome cover)- V3H4: increase first echo factor

Main value V0H0too large

Check V0H8:Is the displayed distancebetween sensor diaphragmand product surfacetoo small?

Interference echos- fittings in vessel removable?- nozzle too long?- V0H3: Select "0" (liquid) or "2" (domecover)

- Perform Interference echo suppression

Adjust linearisation(s. chap. 6.2)

Main value V0H0vacillates

Turbulent surface? - Agitator blades in measuring range?- Increase output damping- V0H3: Select "0" (liquid) or "2" (domecover)

no

no

yesyes

no

yes

yes

Matrix can notbe edited

Unlock matrix(s. chap. 6.6)

Page 18: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

8 Accessories Prosonic T FMU 230/231

18 Endress+Hauser

8 AccessoriesProtective cover

Adapter flange

Mounting bracket

Order Code: 942665-0000

FAU70E Process connection12 DN50 PN 1614 DN80 PN1615 DN100 PN16

Sensor connection3 G 1 1/2" ISO 2284 G 2" ISO 228

Material2 1.44357 Polypropylene,

PPS

FAU70E- Order Code

FAU70A Process connection22 ANSI 2" 150 psi44 ANSI 3" 150 psi25 ANSI 4" 150 psi

Sensor connection5 NPT 1 1/2 - 11,56 NPT 2 - 11,5

Material2 1.44357 Polypropylene,

PPS

FAU70A- Order Code

adapter flangesealing ringEPDM(supplied)

sensor nozzle

– for FMU 230:G 1 1/2, A=55 mmOrder code: 942669-0000

– for FMU 231G2, A=66 mmOrder code: 942669-0001

– Material: 14301 (SS 304)– suited for NPT 1 1/2" and

2" as well

Page 19: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Prosonic T FMU 230/231 8 Accessories

Endress+Hauser 19

Cantilever

Mounting Frame orWall Bracketfor Cantilever

A

D M8

35 50

20

2010

5

50/

62 22

C

C

6.5 15

100

25

351007575 B

• The 50 mm or 62 mm orifices serve for the mounting of the FMU 40 or FMU 41 sensor, respecitvely.

• The 22 mm orifice may be used for an additional sensor.

A B C D for Sensor Material Order Code585 250 2 200 FMU 40 1.4301 (AISI 304) 52014132

galv. steel 52014131FMU 41 1.4301 (AISI 304) 52014136

galv. steel 520141351085 750 3 300 FMU 40 1.4301 (AISI 304) 52014134

galv. steel 52014133FMU 41 1.4301 (AISI 304) 52014138

galv. steel 52014137

3.2

20

55

100

2570

0/14

00

45

7610

0 200

6.5

13

Ø 33.7

130 150100

604

Height Material Order Code700 mm galv. steel 919791-0000700 mm 1.4301 (AISI

304)919791-0001

1400 mm galv. steel 919791-00021400 mm 1.4301 (AISI

304)919791-0003

Material Order Codegalv. steel 919792-00001.4301 (AISI 304)

919792-0001

110

25

5

6.5

150

ø 33.7

3.2

110

13

150

180

213

88

Page 20: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

9 Technical Data Prosonic T FMU 230/231

20 Endress+Hauser

9 Technical DataInput variables

Output variables

Measuring accuracy

Application conditions

Mechanical construction

Display and operating elements

Power supply

Measuring range Type in liquids in solids

FMU 230 0,25 ... 4 m 0,25 ... 2 m

FMU 231 0,4 ... 7 m 0,4 ... 3,5 m

Blocking distance FMU 230: 0,25m; FMU 231: 0,4m

Operating frequency FMU 230: approx. 70 kHz; FMU 231: approx. 55 kHz

Pulse frequency 0,5 ... 1 Hz depending on sensor and electronic version

Current output 4 ... 20 mA

Output damping 0 ... 255 s

Load max. 600 Ω

Reference conditions Ideal reflection from a calm surface at 20 °C

Measuring uncertainty 0,25 % for max. measuring span(includes linearity, reproducibility and hysteresis)

Resolution 3 mm

Process temperature –40…+80 °C (built-in temperature sensor)

Operating temperature –20…+60 °C

Storage temperature –40…+80 °C

Operating pressure pabs 3 bar

Climatic class IEC 68 T2-30Db

Type of protection IP 67 (NEMA 6), with housing cover open: IP 20

Vibration resistance IEC 68 T2-6 Tab. 2.C (10...55 Hz)

Electromagnetic compati-bility

Interference emmission according to EN 61326 ; apparatus of class B;Interference immunity according to EN 61326 ; Appendix A (industrial are) and NAMUR recommendation EMV (NE 21)Use screened cable for wiring. Installation hints for screened cables and gene-ral notes on EMC test conditions: see TI 241F

Material Housing: PBT (glass reinforced, flame-retended)Threaded boss and sensor: PVDF

Seals between threaded boss and sensor, internal: EPDM sealon threaded boss, external: EPDM seal

Process connection FMU 230: G 1 ½ or NPT 1 ½, FMU 231: G 2 or NPT 2

Dimensions(The housing dimensions are the same for both vari-ants)

Display LCD (optional) 4 character display with segment display of current

LED for entry acknowledgement

Operation via four keys: –, +, V, H

Supply voltage 12 ... 36 VDC

Power consumption < 2,5 W

Page 21: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Prosonic T FMU 230/231 Index

Endress+Hauser 21

Index

AActual level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Adapter flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Application parameter . . . . . . . . . . . . . . . . . . . . . . . 10

BBinary output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Blocking distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

CCantilever . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Continuous output. . . . . . . . . . . . . . . . . . . . . . . . . . . 13Current on Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Current output . . . . . . . . . . . . . . . . . . . . . . . . . 8, 10, 12Current simulation. . . . . . . . . . . . . . . . . . . . . . . . . . . 15cylincrical horizontal tank . . . . . . . . . . . . . . . . . . . . . 12

DDisplay module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

EEcho Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Empty distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Error message. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

FFault analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17First Echo Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

IInstallation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Installation position . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Installation variants . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Interference echo suppression. . . . . . . . . . . . . . . . . 14

KKey operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

LLED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Length unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Level simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Linearization mode. . . . . . . . . . . . . . . . . . . . . . . . . . . 11Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Lost echo delay time . . . . . . . . . . . . . . . . . . . . . . . . . 14

MMeasured value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Measured value display. . . . . . . . . . . . . . . . . . . . . . . 12Methods of calibration . . . . . . . . . . . . . . . . . . . . . . . . . 8Mounting bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Mounting Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

OOperating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Operating matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Output damping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

PProtective cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

RReset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 10

SSpan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

TTemperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Threshold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

VVolume simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

WWall Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Page 22: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Operating Matrix FMU 230/231 Prosonic T FMU 230/231

22 Endress+Hauser

Operating Matrix FMU 230/231

H0 H1 H2 H3 H4 H5 H6 H7 H8 H9

V0BasicCalibration

Measured value

User unit

Emptycalibration

m/ft

Fullcalibration

m/ft

Application0: liquid.1: fast2: dome cov..3: solids4: conveyor

OutputdampingDefault: 3 s

seconds

4mA valueDefault: 0%switch point for4 mA (8mA)

User unit

20mA value Default: 100%switch point for 20mA(16mA)

unser unit

Output onAlarm0: 3,8mA1: 22mA2: hold

Measureddiestance(Bargraph:Echo Quality

m/ft

Level(Bargraph:Echo Quality)

m/ft

V2Linearisa-tion

Linearisation0: height1. activate2: manual3: automatic.4. cancel5: linear

TableLine-No.

TableLevel

Table:Volume/Weight

Volume max.Default: 100

V3Ext. para-meter

Range auto-matic sup-pressionDefault: 0,0

Actual levelDefault: 0,0

Echo Quality0 ... 10

First echo factor0: none1: medium2: max.

Temperature

°C

V8Operating parameter

Current outp.0: 4 ... 20mA1: 4 ... 20mA

+threshold2: 4/20mA3: 8/16mA

Select unit0: m1: ft

Lost echo delay time0 ... 255 sDefault: 60 s

V9Service/Simulat.

diagnostic code

last diag-nostic code

Type of sen-sor/electro-nics

Instrument & Software No.

Reset333

Simulation0: off1: level2: volume3: current

Simualtion value

Currentoutput

Locking333:unlocked≠ 333:

locked

Entry fieldbold: factory settingsitalic: units

Display field

Page 23: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Allgemeine Informationen zu Service und Reparaturen:www.services.endress.com

Lieber Kunde,Aufgrund der gesetzlichen Bestimmungen und zum Schutz unserer Mitarbeiter und Betriebseinrichtungenbenötigen wir die unterschriebene »Erklärung zur Kontamination«, bevor Ihr Auftrag bearbeitet werden kann.Legen Sie diese vollständig ausgefüllte Erklärung unbedingt den Versandpapieren bei. Dies gilt auch fürzusätzliche Sicherheitsdatenblätter und/oder spezielle Handhabungsvorschriften.

Geräte- / Sensortyp: __________________________________ Seriennummer: _____________________________

Medium / Konzentr.: __________________________________ Temperatur: ________ Druck: _______

Gereinigt mit: __________________________________ Leitfähigkeit: ________ Viskosität: _______

radioaktiv

explosiv

ätzend

giftig

gesundheits-

schädlich

bio-

gefährlich

brand-

fördernd

unbedenklich

Kreuzen Sie bitte zutreffende Warnhinweise an.

________________________________________________________________________

________________________________________________________________________

Firma: _________________________ Ansprechpartner: _______________________

_________________________ _______________________

_________________________ Abteilung: _______________________

Adresse: _________________________ Telefon-Nummer: _______________________

_________________________ Fax / E-Mail: _______________________

_________________________ Ihre Auftrags-Nr.: _______________________

Hiermit bestätigen wir, dass die zurückgesandten Teile gereinigt wurden und frei sind von jeglichen Gefahr- oderGiftstoffen entsprechend den Gefahren-Schutzvorschriften.

(Ort, Datum) (Firmenstempel und rechtsverbindliche Unterschrift)

SAFE

Page 24: prosonic T FMU 230/231 Ultrasonic Level · PDF file52014981 prosonic T FMU 230/231 Ultrasonic Level Measurement ... – H + V 2. Reset: 4. ... Install the Prosonic T at a height so

Unternehmen der Endress+Hauser-Gruppe

BA 259F/00/de/07.0252014980FM+SGML 6.0

Europe

Austria Endress+Hauser Ges.m.b.H.WienTel. (01) 88056-0, Fax (01) 88056-35

Belarus BelorgsintezMinskTel. (0172) 263166, Fax (0172) 263111

Belgium / Luxembourg Endress+Hauser N.V.BrusselsTel. (02) 2480600, Fax (02) 2480553

BulgariaINTERTECH-AUTOMATIONSofiaTel. (02) 664869, Fax (02) 9631389

Croatia Endress+Hauser GmbH+Co.ZagrebTel. (01) 6637785, Fax (01) 6637823

CyprusI+G Electrical Services Co. Ltd.NicosiaTel. (02) 484788, Fax (02) 484690

Czech Republic Endress+Hauser GmbH+Co.PrahaTel. (026) 6784200, Fax (026) 6784179

Denmark Endress+Hauser A/SSøborgTel. (70) 131132, Fax (70) 132133

EstoniaELVI-AquaTartuTel. (7) 441638, Fax (7) 441582

Finland Endress+Hauser OyEspooTel. (09) 8676740, Fax (09) 86767440

France Endress+Hauser S.A.HuningueTel. (389) 696768, Fax (389) 694802

Germany Endress+HauserMesstechnik GmbH+Co.Weil am RheinTel. (07621) 975-01, Fax (07621) 975-555

Great Britain Endress+Hauser Ltd.ManchesterTel. (0161) 2865000, Fax (0161) 9981841

GreeceI & G Building Services Automation S.A.AthensTel. (01) 9241500, Fax (01) 9221714

HungaryMile Ipari-ElektroBudapestTel. (01) 2615535, Fax (01) 2615535

IcelandBIL ehfReykjavikTel. (05) 619616, Fax (05) 619617

IrelandFlomeaco Company Ltd.KildareTel. (045) 868615, Fax (045) 868182

Italy Endress+Hauser S.p.A.Cernusco s/N MilanoTel. (02) 921921, Fax (02) 92107153

LatviaRino TKRigaTel. (07) 312897, Fax (07) 312894

LithuaniaUAB "Agava"KaunasTel. (07) 202410, Fax (07) 207414

Netherland Endress+Hauser B.V.NaardenTel. (035) 6958611, Fax (035) 6958825

Norway Endress+Hauser A/STranbyTel. (032) 859850, Fax (032) 859851

Poland Endress+Hauser Polska Sp. z o.o.WarszawyTel. (022) 7201090, Fax (022) 7201085

PortugalTecnisis - Tecnica de Sistemas IndustriaisLinda-a-VelhaTel. (21) 4267290, Fax (21) 4267299

RomaniaRomconseng S.R.L.BucharestTel. (01) 4101634, Fax (01) 4101634

Russia Endress+Hauser Moscow OfficeMoscowTel. (095) 1587564, Fax (095) 1589871

SlovakiaTranscom Technik s.r.o.BratislavaTel. (7) 44888684, Fax (7) 44887112

Slovenia Endress+Hauser D.O.O.LjubljanaTel. (061) 1592217, Fax (061) 1592298

Spain Endress+Hauser S.A.Sant Just DesvernTel. (93) 4803366, Fax (93) 4733839

Sweden Endress+Hauser ABSollentunaTel. (08) 55511600, Fax (08) 55511655

Switzerland Endress+Hauser AGReinach/BL 1Tel. (061) 7157575, Fax (061) 7111650

TurkeyIntek Endüstriyel Ölcü ve Kontrol SistemleriIs-tanbulTel. (0212) 2751355, Fax (0212) 2662775

UkrainePhotonika GmbHKievTel. (44) 26881, Fax (44) 26908

Yugoslavia Rep.Meris d.o.o.BeogradTel.(11) 4441966, Fax (11) 4441966

Africa

EgyptAnasiaHeliopolis/CairoTel. (02) 4179007, Fax (02) 4179008

MoroccoOussama S.A.CasablancaTel. (02) 241338, Fax (02) 402657

South Africa Endress+Hauser Pty. Ltd.SandtonTel. (011) 4441386, Fax (011) 4441977

TunisiaControle, Maintenance et RegulationTunisTel. (01) 793077, Fax (01) 788595

America

Argentina Endress+Hauser Argentina S.A.Buenos AiresTel. (01) 145227970, Fax (01) 145227909

BoliviaTritec S.R.L.CochabambaTel. (042) 56993, Fax (042) 50981

Brazil Samson Endress+Hauser Ltda.Sao PauloTel. (011) 50313455, Fax (011) 50313067

Canada Endress+Hauser Ltd.Burlington, OntarioTel. (905) 6819292, Fax (905) 6819444

Chile Endress+Hauser Chile Ltd.SantiagoTel. (02) 3213009, Fax (02) 3213025

ColombiaColsein Ltda.Bogota D.C.Tel. (01) 2367659, Fax (01) 6104186

Costa RicaEURO-TEC S.A.San JoseTel. (02) 961542, Fax (02) 961542

EcuadorInsetec Cia. Ltda.QuitoTel. (02) 269148, Fax (02) 461833

GuatemalaACISAAutomatizacionYControlIndustrial S.A.Ciudad de Guatemala, C.A.Tel. (03) 345985, Fax (03) 327431

Mexico Endress+Hauser S.A. de C.V.Mexico CityTel. (5) 5682405, Fax (5) 5687459

ParaguayIncoel S.R.L.AsuncionTel. (021) 213989, Fax (021) 226583

UruguayCircular S.A.MontevideoTel. (02) 925785, Fax (02) 929151

USA Endress+Hauser Inc.Greenwood, IndianaTel. (317) 535-7138, Fax (317) 535-8498

VenezuelaControval C.A.CaracasTel. (02) 9440966, Fax (02) 9444554

Asia

China Endress+Hauser Shanghai

Instrumentation Co. Ltd.ShanghaiTel. (021) 54902300, Fax (021) 54902303

Endress+Hauser Beijing OfficeBeijingTel. (010) 68344058, Fax: (010) 68344068

Hong Kong Endress+Hauser HK Ltd.Hong KongTel. 25283120, Fax 28654171

India Endress+Hauser (India) Pvt Ltd.MumbaiTel. (022) 8521458, Fax (022) 8521927

IndonesiaPT Grama BazitaJakartaTel. (21) 7975083, Fax (21) 7975089

Japan Sakura Endress Co. Ltd.TokyoTel. (0422) 540613, Fax (0422) 550275

Malaysia Endress+Hauser (M) Sdn. Bhd.Petaling Jaya, Selangor Darul EhsanTel. (03) 7334848, Fax (03) 7338800

PakistanSpeedy AutomationKarachiTel. (021) 7722953, Fax (021) 7736884

Papua-NeuguineaSBS Electrical Pty LimitedPort MoresbyTel. 3251188, Fax 3259556

Philippines Endress+Hauser Philippines Inc.Metro ManilaTel. (2) 3723601-05, Fax (2) 4121944

Singapore Endress+Hauser (S.E.A.) Pte., Ltd.SingaporeTel. 5668222, Fax 5666848

South Korea Endress+Hauser (Korea) Co., Ltd.SeoulTel. (02) 6587200, Fax (02) 6592838

TaiwanKingjarl CorporationTaipei R.O.C.Tel. (02) 27183938, Fax (02) 27134190

Thailand Endress+Hauser Ltd.BangkokTel. (2) 9967811-20, Fax (2) 9967810

VietnamTan Viet Bao Co. Ltd.Ho Chi Minh CityTel. (08) 8335225, Fax (08) 8335227

IranPATSA Co.TehranTel. (021) 8754748, Fax(021) 8747761

IsraelInstrumetrics Industrial Control Ltd.Tel-AvivTel. (03) 6480205, Fax (03) 6471992

JordanA.P. Parpas Engineering S.A.AmmanTel. (06) 4643246, Fax (06) 4645707

Kingdom of Saudi ArabiaAnasia Ind. AgenciesJeddahTel. (02) 6710014, Fax (02) 6725929

LebanonNetwork EngineeringJbeilTel. (3) 944080, Fax (9) 548038

Sultanate of OmanMustafa & Jawad Sience & Industry Co. L.L.C.RuwiTel. 602009, Fax 607066

United Arab EmiratesDescon Trading EST.DubaiTel. (04) 2653651, Fax (04) 2653264

YemenYemenCompany for Ghee andSoapIndustryTaizTel. (04) 230664, Fax (04) 212338

Australia + New Zealand

AustraliaALSTOM Australia LimitedMilperraTel. (02) 97747444, Fax (02) 97744667

New ZealandEMC Industrial Group LimitedAucklandTel. (09) 4155110, Fax (09) 4155115

All other countries Endress+Hauser GmbH+Co.

Instruments InternationalD-Weil am RheinGermanyTel. (07621) 975-02, Fax (07621) 975345