PQM Connection to DCS Using Modbus Interface
Introduction
Presented by:
SARMAD RIAZ
Background
ISTAT transducers replaced by PQM
Why Replace…? Faulty Obsolete (Retrofit not available)
Power Quality Meter
GE Multilin
Continuous Monitoring of a Three Phase System
PQM
Communication With DCS
Previous Scheme Analog (4~20 mA) Signals
Present Scheme Serial Communication using Modbus
Interface
ISTAT Communication with DCS
CT
PT
IST
AT
C
AR
D
Analog Input M
odule
DC
S
Backplane OPS
4~20 mA
Note: DCS Backplane is the same as FLEX Backplane.
PQM Communication with DCS
PT
PQMMVI94
Interface Module
DCSBackplaneRS485
CTModbus
RS485
Standard EIA RS-485
Physical Media Twisted Pair
Network Topology Point-to-point, Multi-dropped, Multi-point
Maximum Devices 32 (32 drivers & 32 receivers)
Maximum Distance 1200 meters (4000 feet)
Maximum Baud Rate 100Kbps - 10Mbps
Voltage Levels -7V to +12V (max), +/-6V (Commonly used)
Modbus MODBUS Protocol
Layer 7 Messaging Protocol MODICON Master Slave Communication Link
Versions Modbus-RTU Modbus-ASCII
OSI Model
Application
Presentation
Session
Transport
Network
Link
Physical
7
6
5
4
3
2
1
Master - SlaveMaster - Slave
Modbus
RS485RS485
System Configuration of MPS
MVI94-MCM The inRAx Modbus Master/Slave
Communication Module is designed to allow FLEX processors to interface easily with Modbus protocol compatible devices and hosts.
MVI94-MCM Module
The MVI94-MCM module acts as an input/output module between the Modbus network and the FLEX backplane.
The data transfer from the FLEX processor is asynchronous from the actions on the Modbus network.
Configuration of MVI94-MCM Module
A terminal program is used to send a configuration file to the MVI94-MCM module. The MVI94-MCM module stores its configuration in a text file, located in the module's flash memory.
When the module starts up, it reads the configuration file and uses the information to control how the MCM protocol interacts with the module's application port(s).
Configuration File [Module]
Basic Module Settings Module Name Register Addresses
[Port] The [PORT] section of the configuration file sets the
Modbus port communication parameters. [Modbus Master]
The [Modbus Master] section of the configuration file defines the command list specifications for the master port.
Configuration File
[Modbus Slave] The [Modbus Slave] section of the
configuration file defines the slave address and the data storage offsets for the slave port.
[Commands] The [COMMANDS] section of the
configuration file sets the Modbus master port command list.
[Commands]
“The command is enabled. Modbus Master will Read the value stored in one register starting at address 644 [0284h] (Voltage Vcn) of the device at Node 1 and place it in internal address 58 of the MVI94 Modbus Master module.”
Daisy Chain Configuration
Node 1 Node 2 Node 3 Node 4
Data Formats
High Word
Low Word
× 65536
< 0
No
YesLow
Word
Low Word
+
+
65536
Actual Value
Reliability
Less Reliability Reliability can be increased by
Staggering Data over two channels Using Redundant Links and Modules