Capacitance Switches Compact Operating Instructions 03/2013 Pointek CLS500

Pointek CLS500 Compact Operating Instructions 03/2013 · PDF fileCompact Operating Instructions 03/2013 Pointek CLS500. ... • Flat-faced flange ASME, EN 1092-1 ... apparatus group

Embed Size (px)

Text of Pointek CLS500 Compact Operating Instructions 03/2013 · PDF fileCompact Operating...

  • Capacitance Switches

    Compact Operating Instructions 03/2013

    Pointek CLS500

  • mm

    mm

    m

    English

    Pointek CLS500 Quick Start Manual

    This manual outlines the essential features and functions of the Pointek CLS500. We strongly advise you to acquire the detailed version of the manual so you can use your instrument to its fullest potential. The complete manual is available at: www.siemens.com/level. The printed manual is available from your Siemens Milltronics representative.

    Questions about the contents of this manual can be directed to:Siemens Milltronics Process Instruments1954 Technology Drive, P.O. Box 4225Peterborough, Ontario, Canada, K9J 7B1Email: [email protected]

    MILLTRONICS is a registered trademark of Siemens Milltronics Process Instruments.

    Safety GuidelinesWarning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed:

    1

    Copyright Siemens Milltronics Process Instruments 2013.

    All Rights ReservedDisclaimer of Liability

    We encourage users to purchase authorized bound manuals, or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments. Siemens Milltronics Process Instruments will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions.

    While we have verified the contents of this manual for agreement with the instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welcome all suggestions for improvement.

    Technical data subject to change.

    WARNING: relates to a caution symbol on the product, and means that failure to observe the necessary precautions can result in death, serious injury, and/or considerable material damage.

    WARNING1: means that failure to observe the necessary precautions can result in death, serious injury, and/or considerable material damage.

    CAUTION: means that failure to observe the necessary precautions can result in considerable material damage.

    Note: means important information about the product or that part of the operating manual.

    1. This symbol is used when there is no corresponding caution symbol on the product.

    A5E32243995 Pointek CLS500 QUICK START MANUAL Page EN-1

  • mm

    mm

    m

    Engl

    ish

    Pointek CLS500

    Pointek CLS500 is a 2-wire capacitance point level switch for detecting interfaces, solids, liquids, slurries and viscous materials in critical conditions of extreme temperature and extreme pressure.

    Approvals (verify against device nameplate) CE, C-TICK CSA, FM, ATEX, INMETRO Bureau Veritas, Lloyds Register of Shipping, categories ENV1, ENV2, ENV3, and ENV5

    Process connections Threaded NPT [(Taper), ANSI/ASME B1.20.1], R[(BSPT), EN 10226/PT (JIS-T),

    JIS B 0203], G [(BSPP), EN ISO 228-1/PF (JIS-P), JIS B 0202]

    Flat-faced flange ASME, EN 1092-1

    Ambient conditions general applications -40 to +85 C (-40 to +185 F)

    Process conditions

    relative dielectric constant (r1.5 minimum

    Temperature rating

    Standard (PFA) -50 to +200 C (-58 to +392 F)

    High temperature stainless steel version with enamel insulation and thermal insulator-60 to +400 C (-76 to +752 F)

    High temperature stainless steel version with thermal isolator-60 to +400 C (-76 to +752 F)

    Pressure rating

    Standard (PFA) -1 to +150 bar g (-14.6 to +2175 psi g)

    High temperature version (enamel)-1 to +345 bar g (-14.6 to +5004 psi g)

    High temperature version (stainless steel)-1 to +35 bar g (-14.6 to 507.6 psi g)

    Note: Pointek CLS500 is to be used only in the manner outlined in this manual, otherwise protection provided by the equipment may be impaired.

    This product is intended for use in industrial areas. Operation of this equipment in a residential area may cause interference to several frequency based communications.

    Note: The use of approved watertight conduit hubs/glands is required for Type 4X / NEMA 4X, Type 6 / NEMA 6, IP65, IP68 (outdoor applications).

    Note: Please see full Operating Instructions for Process Pressure/Temperature De-rating Curves.

    Page EN-2 Pointek CLS500 QUICK START MANUAL A5E32243995

  • mm

    mm

    m

    English

    PowerSupply voltage 12 to 33 V DC

    Loop current 3.6 to 22 mA / 22 to 3.6 mA (2-wire current loop)

    Conforms to Namur NE 43

    Installation

    Mounting Location

    Do: protect the transmitter from direct heat radiation. Do not: exceed the permissible ambient temperature limits Do not: mount Pointek CLS500 in locations subject to strong vibrations (if it can

    be avoided).

    Standard mounting locations

    High level alarm normally mounted into the vessel top, or through the tank wall at the detection level

    Notes: Installation shall only be performed by qualified personnel and in accordance with local

    governing regulations. This product is susceptible to electrostatic shock. Follow proper grounding procedures. This housing may only be opened for maintenance, local operation, or electrical

    installation. Before installing the instrument, verify that the environment complies with any restrictions

    specified on the device nameplate.

    WARNINGS:

    Disconnect the device before any welding is carried out in the vicinity of the instrument.

    Provide protection diodes when the solid state switch is activating an external relay to prevent possible switch/relay damage resulting from inductive spikes generated by the relay coil.

    Notes: Keep the probe or probe tip at least 50 mm (2") away from any nozzle or tank wall. If multiple units are used, allow at least 500 mm (20") between them, to prevent

    interference (mount diagonally if space is restricted).

    Angle Horizontal Vertical

    A5E32243995 Pointek CLS500 QUICK START MANUAL Page EN-3

  • mm

    mm

    m

    Engl

    ish

    Low level alarm mounted through the tank wall at the detection level

    Standard configuration with extensions: top mounting

    Designed for top mounting, for high or low level alarm. Mount the probe vertically so that it reaches into the process at the desired detection level.

    Process Cautions The maximum allowable torque on a horizontally installed rod is 30 Nm. Keep unit out of path of falling material, or protect probe from falling material. Avoid areas where material build up occurs. Take into account material surface configuration when installing unit. Ensure tensile load does not exceed probe or vessel ratings

    Mounting InstructionsPointek CLS500 is available in three thread types: NPT, or R (BSPT), or G (BSPP). Make sure the mounting connection threads are of the same type, then simply screw the device into the process connection, and hand tighten.

    CAUTION: Consider material surface configuration when installing unit

    Page EN-4 Pointek CLS500 QUICK START MANUAL A5E32243995

  • mm

    mm

    m

    English

    Wiring

    1. Loosen the retaining set-screw and remove the enclosure cover.

    2. Loosen the cable gland and thread the cable through it.

    3. Connect the power / signal conductor wires to the current loop terminal block (any polarity). For effective electromagnetic compatibility performance, ensure that the filter assembly remains installed. When wiring the current loop, ensure that each terminal block entry houses a power wire, and one line of the filter assembly.

    4. Ground the enclosure.

    5. Check to ensure all connections are good.

    6. Tighten the cable gland to form a good seal.

    WARNINGS:

    All field wiring must have insulation suitable for voltage to be applied. Turn off power before servicing any device. Please check the ambient and operating temperatures in the Operating

    Instructions for the specific configuration you are about to use or install. In potentially explosive atmospheres, open the enclosure only when Pointek

    CLS500 is not energized.Notes: The transmitter is in operation when the power supply is switched on. Only qualified personnel are authorized to install and operate this equipment in

    accordance with established safety practices and standards. The Protective Earth Terminal must be connected to reliable ground. A circuit breaker or switch in the building installation, marked as a disconnect

    switch, shall be in close proximity to the equipment and within easy reach of the operator.

    WARNING: Damage or removal of the protective label voids the warranty for the Pointek CLS500.

    A5E32243995 Pointek CLS500 QUICK START MANUAL Page EN-5

  • mm

    mm

    m

    Engl

    ish

    7. Replace the enclosure cover and tighten the retaining set-screw.

    Handling electrodes

    WARNINGS: Do not scratch or gouge the electrode insulation since this could

    reduce the integrity of the insulation and the useful life of the electrode.

    Do not damage the insulating sleeve on the electrode during shipping, packing, and installation. Any damage to the electrode can prevent proper performance.

    (ATEX 95): Precautions MUST be taken to avoid ignition due to hazardous electrostatic discharges:

    a. where an isolated probe is used in gas, vapor, or a non-conductive liquid that is potentially explosive, requiring apparatus group IIC equipment

    b. where the probe is used in a potentially explosive dusty atmosphere

    ground lug

    instrument system ground

    measuring s