Upload
malik-sameeullah
View
215
Download
0
Embed Size (px)
Citation preview
8/6/2019 PLC Quick Working Explain
1/8
1
1
UGC scholar ship based research program:
PLC Based Substation Control And Its Linking
WithThe New Automation Ssheme
REPORT 3
By: Malik Sameeullah (08EES31) B.Tech electrical
Date :27:02:2011
PLC: working in substation with help of illustration.
Much attention given to the use of PLC (Programmable Logic Controller) insubstation and distribution automation application in recent years. Day to day
new application based on plc and SCADA is found. PLC is very cost competitive in
compression of traditional RTU and have many benefits in substation automation.
So need to understand PLC is much essential to develop new system which leads
PLC.
PLC parts:
y Input and output port: input device such as switches, pushbutton andother sensors like RTD (Resistance Temperature Detector) are connected to
the terminal strip under the bottom cover of PLC. Input is required so that
PLC work on input and generate logic. Generally input is either 1 or 0, which
is a case when we have to work on only two conditions (logic). But
8/6/2019 PLC Quick Working Explain
2/8
2
2
sometimes analog input is present which is need to sense as it is so we
need converter to convert it into equivalent digital signal. For this type of
input we need specific PLC module to serve this condition. Similarly output
port is provided to implement the result in field circuits.
y Main part (Processor):The processor is an self contained unit is generallyspecified according to memory required for the program to be
implemented. The processor is consist of microprocessor, system memory,
serial communication port for printer, PLC LAN link, supply port and
external port for I/O. Mounting rack is usually a metal framework with a
printed circuit board backplane which provides meanly for mounting the
PLC I/O modules and processor. There is a provision of adding a extra I/O by
adding a rack.
y Program loader/monitor section:Remote control unit known asworkstation from where a technical expert monitor substation and do
appropriate change in logic to control in better way. Program is written in
specific software packages and loaded in PLC. So, there is a gateway
between PC and PLC.
Ladder Logic: Programming of PLC:A ladder logic program is exactly similar to an electrical ladder diagram. It is
readily understood and maintained by skill workers familiar with relay logic. It
simplifies training ladder language, however, it generally lack good flow control.
Modern PLC is user friendly a graphical type programming with a help menu to
easily use any instruction.
The program symbols for a PLC input will look like a normally open or normally
closed contact used in typically electrical diagrams. Two types of switches areused:
(1)Normally Open (NO) signal state of contact is 1 then power can flowotherwise power cannot flow.
8/6/2019 PLC Quick Working Explain
3/8
3
3
(2)Normally Closed (NC) signal state of contact is 1 then power cannot flowotherwise power is flow.
The output instruction is OE ( )- i.e. Output energies. This is used to turn on bit
when circuit condition is satisfied. The real world switches are connected to theinput terminal and the outputs relays are connected to the output terminal of the
PLC. The I/O terminals are grouped together and placed in modules. There
arehundred of modules, it is important to have some kind of numbering system to
identify each module and all its input and output terminals. The generalized
numbering of I/O is following pattern:
Input/output Module number Rack number Slot number Word number
Terminal number
i.e. - I:0.0/1
AND gate using ladder logic: For two input C1(I:0/1),C2(I:0/1) and output
Y(O:0/1)
In this case output is high only when both inputsare high. Therefore, the AND gate
is equivalent to a series combination of normally open switches in a ladder as
shown in fig. Similarly different logic is made using different combination of
switch. For the digital circuit, if we want to develop equivalent ladder logic three
steps is follow: (1) Design description by truth table (2) Logic minimization (3)
Logic realization. There is also a provision of timers and counter which help to
provide delay on output. Timers have a great industrial application for
automation.
The contacts on the left side of the timer function block are the timer enable
contacts. When they are closed, power passes to the left terminal of the timer, it
clock is enabled and it starts timing. When they open power stop flowing through
8/6/2019 PLC Quick Working Explain
4/8
4
4
the terminal, and timer stop functioning. A timer function blocks has three output
contacts. When the timer is timed out, DN is set. The enable bit follow the input
enable status. If the enable contact is true then output EN is true. TT is set when
the timer is operating.
Communication:
For the communication between various PLC and PC station in substation. These
is a need of communication system. Different vendor use different protocol.
IEEE -488 bus: To connect and control programmable instruction and to provide a
standard interface for communication b/w instrument from difference sources.It
consists of 16 signal lines and 8 ground line. The 16 signal lines are divided into 3
group, namely 8 data lines, 3 handshake lines, 5 interface, management lines.
Serial interface RS-232C:
8/6/2019 PLC Quick Working Explain
5/8
5
5
RS for recommended standard and C for third version. RS 232C is a standard
interface approved by the electronic industries. All once for connecting serial
device. The Rs 232 interface standard specification of connecting two device, the
data terminal equipment (DTE) & Data Communication Equipment (DCE).
Ethernet:
This has become least expensive most popular way of communication. Speed LAN
alternative use standard Ethernet, twisted pair Ethernet. Ethernet refer to the
cable.Four type of cabling are commonly used. These are:10Base5, 10Base2,
10Base-T, 10Base-F. The electromagnetic type ray which contain message may
propagate through some medium like coaxial cable cause the development of
Ethernet. One of the problems in earlier day is that computer listening before
transmitting. So other wait until the current transmission complete then all start
at once. The solution is that each computer listen during its own transmission and
if it detects interface, jam the ether to alert all senders. And after random time
resend data. If data again collide than waiting time go double and so on and give
competing transmission and give one of them a chance to go first.
Profibus: Root of PLC Communication
General features of Profibus
y Straight per topologyy Token passing between up to three mastery Length from 960m/9.6kbps with 7 repeaters. With fibre optic cable the
length can over 80 km.
The Profibus familiar consist of three compatible version: DP, FMS, PA
PA:
Use layer 1,2 and user interface of the OSI model and layer 3 to 7 are not define.
Direct data link mapper allows access between the user interface and layer 2. The
user interface specified both application function and device behavior. RS-485
and fibre optic are available physical media for Profibus DP.
8/6/2019 PLC Quick Working Explain
6/8
6
6
FMS:
Layer 1,2,and 7 are defined. The application layer consist of fieldbus message
specification (FMS) and lower layer interface (LLI). FMS contain the application
protocol and provides the user with a wide selection of communication services.Application layer provides with a user communication services, mate it possible to
access variable, transmit program and control programmable execution.
PA:
Designed for process control and automation, using the international fieldbus
standard physical layer, IEC 1158-2 for bus powered sensor and actuator to be
operated intrinsically safe area. This is a hybrid communication system use a
function of master slave system.
PLC working in substation with the help of example
At a generation station, generator is the main part as without it no power is
available. So need to regulate properly, so that reliable flow of power is maintain.
PLC is easily utilized for this purpose. Generator connected to the turbine which is
rotate by steam so alternator also rotates. For regulating the speed of alternator
and stopping in case of renovation or in any emergency, we need to have a
control over a entry of steam. For control the over current, we need to trip some
line. In case of fault on main line, we need to activate the main circuit breaker.
Temp control of generator is also necessary. Temperature regulation of generator
by sensing the temp of coil using RTD and convert it to specify signal to produce
input at PLC. If the signal crosses the safe limit then we immediate stop the entry
of steam and so generator is stop. Relays are connected from PLC so that it
reliability increase because know we able to control relay in wide range.
8/6/2019 PLC Quick Working Explain
7/8
7
7
For the control we have input and output connected with a PLC. They are as
follow:
Input
y I0:1, start bottom for start generator.y I0:2, stop bottom for shutdown generator.y I0:3, temp sensor device to sense temperaturey I0:4, CT for sense overload and trip line 1y
I0:5, CT for sense overload and also trip line 2
Output
y O0:1, motor supply who stem entryy O0:2, input for a relay to trip line 1y O0:3, input for a relay to trip line 2y O0:4, for closing main ckt after generator starty O0:5, for activating relay in cause of ground fault due to which
overcurrent is flow
8/6/2019 PLC Quick Working Explain
8/8
8
8
END