Adding component from DIPPR.doc; June.06 Page 1 of 22 DNV Software Adding a Component from DIPPR This article applies to the following products: SAFETI (Financial/NL/Micro) 6.x PHAST (Financial/Micro) 6.x

Phast - Adding a Component from DIPPR.pdf

Embed Size (px)

Citation preview

Page 1: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 1 of 22

DNV Software

Adding a Component from DIPPR

This article applies to the following products:

SAFETI (Financial/NL/Micro) 6.x

PHAST (Financial/Micro) 6.x

Page 2: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 2 of 22

1. Introduction

The programme, when installed has 60 components available in the normal user mode and

has over 1500 compounds from the Design Institute for Physical Property Database (DIPPR),

available in Administrator mode.

The DIPPR database contains pure component physical property data for commercially

important chemicals. The data included is compiled and evaluated by a project of the

American Institute of Chemical Engineers (AIChE), DIPPR. The data in the DIPPR database

consists of both property constants and temperature dependent properties.

DIPPR components are generally ready to be used in dispersion calculations but may contain

missing flammable and toxic data; this information has to be supplied in order to be able to

calculate effects.

Each component has a unique CAS number assigned to it by the Chemical Abstract Services

(http://www.cas.org/). The CAS number is particularly useful because some compounds are

published under various names depending on the source, and the name known to the user may

not be the same used in the DIPPR list. The CAS number is a unique identifier for each

component.

Useful websites for CAS numbers include the following:

• http://chemfinder.cambridgesoft.com/

• http://www.chrismanual.com/toc.htm

• http://www.msdssearch.com/DBLinksN.htm#Foreign%20Language

Components from DIPPR can only be added in PHAST and SAFETI administrator mode; the

components are added under the System Materials tab. The options below will be available

when adding components to the System Materials tab.

Page 3: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 3 of 22

• Insert a new component - the programme inserts a component with the name

"New Component”. This will not be from DIPPR and all the component

properties will be blank.

• Add an existing component - the programme adds a new component from the

DIPPR database and missing component properties can be added or existing

properties can be edited.

• Copy an existing component – the programme copies an existing component from

the System Materials tab and the properties can then be edited.

Since this document is focused on adding components from the DIPPR database, only the

option of adding existing components will be discussed further.

2. Adding components from DIPPR

2.1 Accessing the DIPPR Database through PHAST

The DIPPR database is installed with PHAST, and can only be accessed through the

Administration mode. The following are instructions on how to access the DIPPR database

from PHAST.

1. Launch PHAST, in administrator mode. Type in the password (default: Technica)

and then select Login as Administrator, as seen in the screen below.

Page 4: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 4 of 22

2. Start a new file (through the menu bar under File -> New). The new file will look

very similar to the user mode PHAST study, except that after the Map tab in the study

tree, there are two new tabs: System Parameters and System Materials tabs.

3. While in the system Material tab, right click on the System Components Folder and

through the menu, select Insert -> Component. This will bring up a dialogue box, as

shown below which presents the contents of the DIPPR component database and give

the user options of adding components.

Page 5: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 5 of 22

2.2 Inserting an Existing Component from DIPPR

The list of components in the DIPPR database are referred to as the DIPPR List, the

following are steps for inserting a component from the DIPPR List onto the System

Materials.

1. Highlight the desired component from the DIPPR List and click OK.

2. The highlighted component will be added to the System Materials. If the added

component has incomplete data, the icon for the component will have a red border.

When the component has complete data, there will be no red border around its icon.

The properties of each component are grouped into various tabs and it is

recommended that each tab be viewed, by double clicking on the component and

browsing the tabs, to check for the missing data that the red border is indicating.

Page 6: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 6 of 22

The components that have complete data compiled in the DIPPR database are Allyl

Alcohol, Bromine, Ethyleneimine, Fluorine, Formaldehyde, Methyl Mercaptaan and

Allyl Chloride.

3. To edit the properties of the inserted component, double click on the component’s

icon to open the material properties dialogue. On certain tabs there may be missing

data but most of the data necessary for discharge and dispersion calculations are

available for each component. All the fields outlined in red must have content before

the component can be used in any calculations. The next section of this document will

give more information about the missing data and possible sources for them.

3. Missing Component Properties

Generally, there are four component tabs which require further information, these are:

• General Tab

Page 7: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 7 of 22

• Flammable Tab

• Toxic Tab

• Water Tab

3.1 General Tab

Clicking on the General tab gives a dialogue screen similar to the one below.

Guidelines for the missing data in this tab are discussed below.

3.1.1 Is the component flammable/Toxic?

The user must specify whether the component is flammable, toxic, both, or neither. If unsure

of whether the component is flammable or toxic look at the second tab; if the LFL, UFL or

Page 8: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 8 of 22

heat of combustion exists, the component is most likely flammable.

3.1.2 Reactivity with the Atmosphere?

The user needs to choose from the list available (Strongly Reactive, Not strongly Reactive or

HF only). The only type of reaction with the atmosphere currently modelled in the

programme is the association reaction with Hydrogen Fluoride and this is covered in the

Association tab section. Any other option selected is only for the user’s reference and is not

used in the programme.

3.2 Flammable Tab

Clicking on the Flammable tab gives a dialogue screen similar to the one below

If the flammable properties are difficult to find, general guidelines on input data are discussed

below; alternatively, properties from a similar component can be used but are not strongly

Page 9: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 9 of 22

recommended. All missing flammable properties in this tab are only used for pool fire

calculations, with the exception of TNT efficiency which is used only in vapour cloud

explosion calculations.

3.2.1 How to Specify TNT Efficiency?

Sources of Component-Specific TNT Efficiency Values include the following:

• Handbook of Chemical Hazard Analysis Procedures (ARCHIE User’s Manual), Published

by FEMA / DOT / EPA, 1989

• FM Global Property Loss Prevention Data Sheet 7-42, April 1994, pages 13-14.

The table below shows TNT efficiency values for some commonly used compounds and their

respective sources.

Page 10: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 10 of 22

Specific TNT efficiency inputs:

• The value of the component-specific citation should be used if available. When not

available, a typical value of 10% is suggested.

3.2.2 How do I determine what type of pool fire flame occurs?

The type of pool fire flame (luminous or smoky flame) from the combustion of the

component needs to be added.

Pool fire flame inputs:

• ARCHIE Manual Suggests: “components with a normal boiling point (NBP) above 30 °F

typically burn with sooty flames”

• DNV Suggests: “light components (molecules up to 4 carbon atoms) produce a luminous

flame; heavier components produce smoky flames”. A conservative approach is to enter

“luminous” for all fuels (for highest thermal radiation). However, it is better to use

number-of-carbon-atoms or NBP correlation.

3.2.3 How do I specify emissive power length scale?

There is very little guidance from literature (8.33 m value cited occasionally).

Emissive Power Length Scale inputs:

• DNV Suggests: 2.75 m for luminous flames, 8.33 m for smoky flames

3.2.4 How do I specify minimum surface emissive power?

Pool fire modelling requires minimum surface emissive power and emissive power length

scale, given by the correlation below:

⎟⎠⎞⎜

⎝⎛ −+⎟

⎠⎞⎜

⎝⎛= −− L

D

smokeL

D

a eEeEE 1max

Page 11: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 11 of 22

Where,

Ea = average emissive power of hydrocarbon pool fire

Emax = maximum surface emissive power of fuel, kW/m2

D = pool diameter, m

L = emissive power length scale, m

Esmoke = emissive power of smoke, 20 kW/m2

The Maximum Surface Emissive Power sets an upper limit to the surface emissive power

used in the radiation modelling, and the Scale Length is used for calculating the emissive

power for a fire with a given diameter. Values of the Scale Length for a number of materials

are given in Mudan, K. S. and Croce, P. A., 1988, Handbook of fire protection engineering,

Society of Fire Protection Engineers, 1988, ch 2-4.

• ARCHIE Manual cites work by Alger and Huggland, given by the correlation below:

)313.0(117max NBPTE −=

Where,

TNBP = normal boiling point in °F

The table below gives the comparisons between the Alger and Huggland

correlation and known values.

TNBP Alger/Huggland Observed

LNG -258 198 220

LPG -44 131 160

Page 12: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 12 of 22

The Alger and Huggland estimated values are lower than those observed by

about 16%. Therefore, modifications can be made to establish a modified

Alger and Huggland correlation; if both Parameters are increased for the

revised correlation it gives:

)364.0(136max NBPTE −=

Maximum Surface Emissive Power Inputs:

• The modified Alger and Huggland values are a good choice as they are component

specific. However, the DNV recommended values can also be used.

• DNV Suggests: 140 kW/m2 for smoky flames, 170 kW/m2 for luminous flames

3.2.5 How do I determine the maximum burn rate?

Maximum burn rate is the equivalent of the maximum mass loss rate from a pool fire. The

program uses the correlation by Burgess and Hertzberg to estimate maximum mass burning

rate, given by the correlations below:

*

)(001.0

V

C

HH

MBR∆

∆=

)(*ambNBPPLVV TTcHH −+∆=∆

Where,

∆Hc = heat of combustion

∆Hv = heat of vaporization

cPL = specific heat capacity of the liquid

TNBP = normal boiling point temperature

Tamb = ambient temperature

Page 13: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 13 of 22

The burn rates of some commonly used components are as follows:

The graph below shows the relationship between mass burning rate on land and

thermochemical property of the fuel.

Page 14: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 14 of 22

Maximum Burn rate inputs:

• DNV Suggests: It is recommended that component specific values are used if

available but the correlation can also be used. To use the correlation, enter value of

“0”.

3.2.6 How do I estimate pool fire burn rate length?

Actual burning rate (ABR) is less than or equal to maximum burning rate (MBR), according

to Babrauskas Correlation:

⎟⎠⎞⎜

⎝⎛ −= − L

DeMBRABR 1

Where,

ABR = actual burn rate, kg/(m2*s)

MBR = maximum burn rate, kg/(m2*s)

D = pool diameter, m

L = characteristic pool scale length, m

The burn rates, length (m), of some commonly used components are in the table below.

Page 15: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 15 of 22

Pool-fire burn rate length inputs:

• DNV Suggests: specific values are used where possible. A zero value is not accepted.

If no data is available, then 0.1 m (“conservative” default value) With L = 0.1 m,

ABR ≈ MBR for any pool with diameter > 0.3 m (1 foot).

3.3 Toxic Tab

Clicking on the toxic tab will give a dialogue screen similar to the one below.

Page 16: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 16 of 22

Toxic properties are not compulsory for toxic only components. If no data is entered here,

users will not obtain any toxicity data and an additional input to stop the dispersion

calculations will be required in the case input. The additional input is specified as either a

concentration of interest or a distance of interest.

Guidelines for filling the missing data in this tab are as follows:

3.3.1 How do I find ERPsG value?

ERPG values are established for about 100 compounds, current values can be found at

http://www.aiha.org/Committees/documents/erpglevels.pdf

For the remaining components you can use Temporary Emergency Exposure Limit ( TEEL-1,

Page 17: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 17 of 22

-2 and-3) values. They are an “unofficial” but invaluable supplement to ERPG values. TEEL

values have been developed by Westinghouse (under Contract to the US Department of

Energy) for 2200+ components. Current values can be found at

http://www.eh.doe.gov/chem_safety//teel.html

ERPG inputs:

DNV Suggests: use specific ERPG values where available, if no ERPG values exist then

TEEL values may be used. Otherwise these inputs can be left blank as they are not required

for dispersion calculations.

3.3.2 How do I find IDLH and STEL values?

The Immediately Dangerous to Life and Health (IDLH) and Short Term Exposure Limit

(STEL) can usually be found on the internet.

Download “NIOSH Pocket Guide” for IDLH, STEL, and other values at

http://www.cdc.gov/niosh/npg/.

Another good source for IDLH/Odour data is the “3M Respirator Selection Guide” at

http://www.occupationalhazards.com/safety_zones/50/article.php?id=11631

DNV Suggests: this is an optional input and should only be used if suitable data is available

3.3.3 How do I find Probit coefficients ?

Probit coefficients are used to predict the probability of fatality from exposure to a toxic

component. Generally accepted values have been established for only 20 - 30 components.

A crude technique does exist for estimating values for other toxic components in “Methods

for the Determination of Possible Damage “(Green Book), CPR 16E, Section 5.2.2

For this method LC50 data (preferably for humans) is necessary. A good internet resource for

LC50 data is http://www.cdc.gov/niosh/idlh/intridl4.html

Given the LC50 data its value must then be translated from the cited exposure length, t, to a 30

minutes exposure basis, this is given by the correlation below:

Page 18: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 18 of 22

5.0

5050 30min)(min)30( ⎟

⎠⎞

⎜⎝⎛×=

ttLCLC

If LC50 (30 min) is for non-human species, it must be translated into human, by the

correlation below:

)()( 5050 animalLCfhumanLC ×=

Where,

ƒ < 1 (as listed in Green Book)

Then the Probit coefficients can be estimated as follows

( )1

)(30ln5

2

250

=

×−=

=

B

humanLCA

N

Profit coefficient inputs:

• DNV recommends: established probit coefficients be used where possible. Otherwise

they can be estimated using the “Green Book” method as described above or left

blank as they are not compulsory fields.

3.4 Water Tab

Clicking on the water tab gives a dialogue screen similar to the one below

Page 19: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 19 of 22

The component will be missing information about interaction with water. The first four

inputs are only used if the release forms a pool on water:

• Liquid-Water Surface Tension

• Solubility in Water

• Heat of Solution

• Water Heat Transfer Coefficient

Page 20: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 20 of 22

Input values for the fields in the water tab:

• It is suggested to perform a good literature search to find these values. If the release is

over land, the inputs can be set to zero; otherwise examine the values for the standard

60 components then reverse-engineer values for the new component.

• Reaction with Water: there are two choices, None or Raj and Reid

Raj and Reid Model is only valid for ammonia spills onto water. If the component is not

ammonia then it should always be set to “None”.

4. Saving the New System Components List

The component has now been added in the system materials and it now must be saved. If it is

not saved, then when the program is started in normal mode the component will no longer be

there.

1. In order to save the information, through the menu bar, click on Options ->

Administration -> Update System Materials. See dialogue screen below.

Page 21: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 21 of 22

The program will prompt the user for a description of the changes made. It is

useful to note what components have been added or what values have been

changed. The program will keep a log of all the changes made to the system

materials.

2. The program will then save a copy of the old system materials. It will make a

backup copy of the old system materials file every time the list is updated.

3. The program will then update the system materials.

4. The new component will now be available for every file opened in PHAST.

Page 22: Phast - Adding a Component from DIPPR.pdf

Adding component from DIPPR.doc; June.06

Page 22 of 22

5. Contact DIPPR

For further information on DIPPR, contact AIChE at:

Design Institute for Physical Property Data

Karen Elizabeth Person

Sponsor Relations, ITA

American Institute of Chemical Engineers

3 Park Avenue, 19th Floor

New York, NY 10016

USA

phone: 212-591-7319

fax: 212-591-8883

email: [email protected]

web: http://www.aiche.org