1 1 PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario, Canada, L3R 1E1 M. Braunovic MB Interface, 5975 Place de l’Authion, Suite 503 Montreal, Quebec, Canada, H1M 2W3

PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

  • Upload
    hakhanh

  • View
    229

  • Download
    3

Embed Size (px)

Citation preview

Page 1: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

1 1

PERFORMANCE OF UTILITY

POWER CONNECTIONS IN A

SALINE ENVIRONMENT

B. Johnson Tyco Electronics,20 Esna Park Drive

Markham, Ontario, Canada, L3R 1E1

M. Braunovic MB Interface, 5975 Place de l’Authion, Suite 503

Montreal, Quebec, Canada, H1M 2W3

Page 2: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

2 2

BACKGROUND

• Connector is generally a weak link in the distribution

system.

• Some connector designs lack the ability to provide

effective long-term performance.

• Corrosion is considered as one of the most significant

reliability concern.

• Corrosion is particularly severe in some areas when

connections has to be made between dissimilar metals.

Page 3: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

3 3

OBJECTIVES

• To conduct a control field study of examining the long-term effect of a worst-case operating environment on the performance of power connection systems.

• To obtain an even more basic appraisal of the chemical severity of the exposure environment.

• Emphasis was placed on the comparative evaluation of compression, bolted and fired wedge connector systems.

• The program was initiated in 1995.

Page 4: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

4 4

EXPERIMENTAL

• Test Site

• Battelle Florida Marine Research Facility located in

Daytona Beach.

• The location is characterized by a high salt deposition

rate from the Atlantic Ocean and a high humidity in

the range of 55-60% annual average.

• Seasonal temperature vary from approximately 0oC

in winter to max. 40oC in summer.

Page 5: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

5 5

EXPERIMENTAL

• Test Samples

• Compression, bolted and fired wedge overhead power

connectors.

• Sample size was 50 connectors of each type.

• AWG 2/0, 19 strand bare AAC aluminum or copper

conductors.

• All connectors supplied with a corrosion inhibitor in

place.

Page 6: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

6 6

EXPERIMENTAL

Types of overhead power connectors used in this study

COMPRESSION BOLTED FIRED WEDGE

Page 7: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

7 7

EXPERIMENTAL

• Electrical Measurements

• Voltage drop was measured periodically using a custom-designed and computer-controlled data acquisition system.

• The resolution of voltage measurement was 10 µV giving resistance resolution of 2 µΩ.

• Current of 5 A DC was used throughout the entire exposure test.

Page 8: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

8 8

EXPERIMENTAL

• Installation

• Connectors were installed at the site according to the practices recommended by the respective manufactures.

• Prior to the assembly of each connector, the surfaces of all conductors were wire brushed.

• Separate brushes were used for the copper and aluminum conductors.

• After brushing, connections were typically made within 3-5 minutes.

Page 9: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

9 9

EXPERIMENTAL

• Failure Criterion

• Connector was deemed to have failed when the

resistance between the two corresponding

equalizers increased by 1000 µΩ above its initial

value.

• The initial value of each connector was

determined as an average resistance measured

for the first 100 days of exposure.

Page 10: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

10 10

EXPERIMENTAL

• Corrosion Monitoring

• The chemical severity of the exposure environment was monitored using Battelle reactivity monitoring coupons.

• Coupons were specially finished and cleaned pieces of silver, copper, 1010 steel and 7075 and 6061 aluminum.

• Corrosion rate was determined by measuring the weight gain on a microbalance.

Page 11: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

11 11

RESULTS

• Connector Performance

Compression Connector

EXPOSURE TIME (DAYS)

0 200 400 600 800 1000 1200 1400 1600 1800

RE

SIS

TA

NC

E C

HA

NG

E (

µ)

0

200

400

600

800

1000

1200

1400

2 FAILED 19 FAILED 29 FAILED

Page 12: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

12 12

RESULTS

• Connector Performance

Bolted Connector

EXPOSURE TIME (DAYS)

0 200 400 600 800 1000 1200 1400 1600 1800

RE

SIS

TA

NC

E C

HA

NG

E (

µ)

0

200

400

600

800

1000

1200

2 FAILED 18 FAILED 27 FAILED

Page 13: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

13 13

RESULTS

• Connector Performance

Fired Wedge Connector

EXPOSURE TIME (DAYS)

0 200 400 600 800 1000 1200 1400 1600 1800

RE

SIS

TA

NC

E C

HA

NG

E (

µ)

0

200

400

600

800

1000

1200

1400

1FAILED 2 FAILED1FAILED

Page 14: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

14 14

RESULTS

• Connector Performance

Cumulative failures over the entire exposure period

TIME TO

FAILURE

FIRED WEDGE

CONNECTOR

BOLTED

CONNECTOR

COMPRESSION

CONNECTOR

300 DAYS

600 DAYS

900 DAYS

1200 DAYS

1600 DAYS

0

0

1

1

2

0

2

18

27

-

0

2

19

29

-

TOTAL FAILED 4 47 50

Page 15: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

15 15

RESULTS

• Connector Performance

Variations of average connector resistance with exposure time

EXPOSURE TIME (DAYS)

0 200 400 600 800 1000 1200 1400 1600 1800

AV

ER

AG

E R

ES

IST

AN

CE

)

0

400

800

1200

1600

2000

COMPRESSION

BOLTED

FIRED WEDGE

Page 16: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

16 16

RESULTS

• Connector Performance

Compression Connector Bolted Connector Fired Wedge Connector

Photos of compression, bolted and fired wedge connectors after 3 years of

exposure at the test site

Page 17: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

17 17

RESULTS • Connector Performance Compression Connector

Cross section of failed compression connector with close-up view of Al and Cu conductor-connector interface regions affected by corrosion

Page 18: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

18 18

RESULTS • Connector Performance

Bolted Connector

Cross section of failed bolted connector with close-up view of Al and Cu conductor-connector interface regions affected by corrosion

Page 19: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

19 19

RESULTS • Connector Performance

Fired Wedge Connector

Cross section of failed fired wedge connector with close-up view of Al and Cu conductor-connector interface regions affected by corrosion

Page 20: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

20 20

RESULTS

• Connector Performance

Corrosion rates of different metals at exposure site

EXPOSURE TIME (DAYS)

10 100 1000

CU

MU

LA

TIV

E W

EIG

HT

GA

IN (

µg

/ c

m2 )

101

102

103

104

105

106

STEEL

SILVER

AL 6061

AL7075

COPPER

Page 21: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

21 21

DISCUSSION

• The results show that there is a considerable difference in

the performance of the three connector populations used.

• Difference is manifested not only by the number of failed

connectors but also by the onsets of connector failure.

• First failures occurred in compression and bolted

connectors after 600 days and after 1000 days in fired

wedge connectors.

• By the end of field exposure test all of the compression

connectors failed, only three from bolted survived

whereas only four fired wedge connectors failed.

Page 22: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

22 22

DISCUSSION

• Plausible Failure Mechanisms

• Loss of mechanical contact force due to metal loss at

the contact interfaces.

• Compression and bolted connectors are prone to

this degradation since their design does not provide

an elastic-energy storing capability.

• The spring action of the C-member design of fired

wedge connector maintains not only steady contact

load but also uniform stress distribution and large

metal-to-metal contact

Page 23: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

23 23

DISCUSSION

• Plausible Failure Mechanisms

• Growth and accumulation of corrosion products in the interspaces between conductor and connector can provoke separation of conductor from the connector.

• Compression connectors are particularly prone to this type of degradation due to the action of mechanical forces generated by the build-up of corrosion products, that pry open the connector.

• Bolted and fired wedge connectors showed no such susceptibility to deformation by the corrosion product build-up.

Page 24: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

24 24

DISCUSSION

• Plausible Failure Mechanisms

• Differential thermal expansion between copper and

aluminum caused by seasonal temperature variations.

• Differential thermal expansion results in large lateral

movement of the contact interface (fretting).

• Direct result of fretting is rupture of metallic

conducting bridges, significant loss of contact area

and formation of an insulated layer of debris at the

contact interface.

Page 25: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

25 25

DISCUSSION

• Economical Consequences

• The result of this study show that exposure to a harsh environment resulted in sharp increase in the connector resistance.

• Increase in contact resistance affects not only connector performance but creates serious economical consequence on the network as a whole.

Page 26: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

26 26

DISCUSSION

• Economical Consequences

Calculation of cost of energy loss due to increase

in connector resistance

C = ( R/ t) * I2 * f * t2 * (8760/2000)*G

R/ t – increase in resistance per year (x10-6)

I – operating current=400A f – load factor (40%)

t – time (years) G – generation cost/kWh = $ 0.05

Page 27: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

27 27

DISCUSSION

• Economical Consequences

TIME (YEARS)

0 5 10 15 20 25 30

CO

ST

OF

EN

ER

GY

LO

SS

(U

S$

)

0

500

1000

1500

2000

2500

3000

3500

FIRED WEDGE CONNECTOR

BOLTED CONNECTOR

COMRESSION CONNECTOR

Page 28: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

28 28

CONCLUSIONS

• Differences in design, installation procedure and inhibitors exert major effect on the connector performance in a saline environment.

• Galvanic corrosion was the main cause for the connector failure.

• Build-up of corrosion products at the conductor-connector interface was the major factor controlling connector life.

• Connector life is largely determined by the connector design and the loss of mechanical contact load.

Page 29: PERFORMANCE OF UTILITY POWER CONNECTIONS … · PERFORMANCE OF UTILITY POWER CONNECTIONS IN A SALINE ENVIRONMENT B. Johnson Tyco Electronics,20 Esna Park Drive Markham, Ontario,

29 29

CONCLUSIONS

• Ever increasing load on the network will accelerate connector degradation and accentuate the importance of connector design in mitigating deleterious effects resulting from increasing connector temperature.

• The superior performance of fired-wedge connector is due to the “spring action” of the connector C-member.

• The C-member design resists loss of contact load, maintains uniform stress distribution over contact interface and assures large metal-to-metal contact area.