transient system Circulating water Circulating water Circulating water Up to 20℃〕 2060℃〕 6090℃〕 pH 25.0℃) 6.58.2 6.08.0 6.88.0 6.88.0 6.88.0 7.08.0 7.08.0 7.08.0 7.08.0 electric conductivity mS/mup to 80 up to 30 up to 40 up to 40 up to 30 up to 30 up to 30 up to 30 up to 30 chloride ion mg/ℓ) up to 200 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 30 up to 30 sulfate ion mg/ℓ) up to 200 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 30 up to 30 M alkali level mg/ℓ) up to 100 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 total hardness mg/ℓ) up to 200 up to 70 up to 70 up to 70 up to 70 up to 70 up to 70 up to 70 up to 70 calcium hardness mg/ℓ) up to 150 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 ionized silica mg/ℓ) up to 50 up to 30 up to 30 up to 30 up to 30 up to 30 up to 30 up to 30 up to 30 iron mg/ℓ) up to 1.0 up to 0.3 up to 1.0 up to 1.0 up to 0.3 up to 1.0 up to 0.3 up to 1.0 up to 0.3 copper mg/ℓ) up to 0.3 up to 1.0 up to 1.0 up to 1.0 up to 1.0 up to 1.0 up to 0.1 up to 1.0 up to 0.1 sulfide ion mg/ℓ) Not to be detected Not to be detected Not to be detected Not to be detected Not to be detected Not to be detected Not to be detected Not to be detected Not to be detected ammonium ion mg/ℓ) up to 1.0 up to 0.1 up to 1.0 up to 1.0 up to 0.1 up to 0.3 up to 0.1 up to 0.1 up to 0.1 residual chlorine mg/ℓ) up to 0.3 up to 0.3 up to 0.3 up to 0.3 up to 0.3 up to 0.25 up to 0.3 up to 0.1 up to 0.3 free carbon dioxide mg/ℓ) up to 4.0 up to 4.0 up to 4.0 up to 4.0 up to 4.0 up to 0.4 up to 4.0 up to 0.4 up to 4.0 stability index 6.07.0 (1) The item appellation and its difinition and the unit belong to JIS K 0101. (2) The "" marks in the chart show the factor relevant to corrosion or scale genesis. (3) When high temperature (over 40) ; generally, using corrosive steel, materials which have no protective coating against water, anticorrosive measure shall be done such as adding corrosion prevention material, degasser and etc. (4) Under the Cooling water system with hermetically-closed cooling tower; the closed-circuit circulating water and its Makeup water are based on Hot water standard, spreading water and its Makeup water are based on circulating Cooling water system. (5) Supplied / replenished water needs to be tap water or industrial water or groundwater. Deionized water, regeneration treated water and softening treated water are excluded. (6) Upper 15 items are shown as a typical factor for corrosion and/or scale genesis. S t a n d a r d V a l u e R e f e r e n c e Makeup water transient water Makeup water Water Quality Standard for Cooling water, Cold water, Hot water, Makeup water (JRA GL02-1994) Item Cooling water Cold water Hot water Tendency Circulating water system Lower Hot water system Higher Hot water system Circulating water Scale genesis Makeup water Makeup water Corrosion

Water Quality Standard for Cooling water, Cold water, … Quality Standard for Cooling water, Cold water, Hot water, Makeup water (JRA GL02-1994) Item Cooling water Cold water Hot

Embed Size (px)

Citation preview

Page 1: Water Quality Standard for Cooling water, Cold water, … Quality Standard for Cooling water, Cold water, Hot water, Makeup water (JRA GL02-1994) Item Cooling water Cold water Hot

transient system

Circulating water Circulating water Circulating water

〔Up to 20℃〕 〔20~60℃〕 〔60~90℃〕

pH (25.0℃) 6.5~8.2 6.0~8.0 6.8~8.0 6.8~8.0 6.8~8.0 7.0~8.0 7.0~8.0 7.0~8.0 7.0~8.0 ○ ○

electric conductivity (mS/m) up to 80 up to 30 up to 40 up to 40 up to 30 up to 30 up to 30 up to 30 up to 30 ○ ○

chloride ion (mg/ℓ) up to 200 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 30 up to 30 ○

sulfate ion (mg/ℓ) up to 200 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 30 up to 30 ○

M alkali level (mg/ℓ) up to 100 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 ○

total hardness (mg/ℓ) up to 200 up to 70 up to 70 up to 70 up to 70 up to 70 up to 70 up to 70 up to 70 ○

calcium hardness (mg/ℓ) up to 150 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 up to 50 ○

ionized silica (mg/ℓ) up to 50 up to 30 up to 30 up to 30 up to 30 up to 30 up to 30 up to 30 up to 30 ○

iron (mg/ℓ) up to 1.0 up to 0.3 up to 1.0 up to 1.0 up to 0.3 up to 1.0 up to 0.3 up to 1.0 up to 0.3 ○ ○

copper (mg/ℓ) up to 0.3 up to 1.0 up to 1.0 up to 1.0 up to 1.0 up to 1.0 up to 0.1 up to 1.0 up to 0.1 ○

sulfide ion (mg/ℓ) Not to be detected Not to be detected Not to be detected Not to be detected Not to be detected Not to be detected Not to be detected Not to be detected Not to be detected ○

ammonium ion (mg/ℓ) up to 1.0 up to 0.1 up to 1.0 up to 1.0 up to 0.1 up to 0.3 up to 0.1 up to 0.1 up to 0.1 ○

residual chlorine (mg/ℓ) up to 0.3 up to 0.3 up to 0.3 up to 0.3 up to 0.3 up to 0.25 up to 0.3 up to 0.1 up to 0.3 ○

free carbon dioxide (mg/ℓ) up to 4.0 up to 4.0 up to 4.0 up to 4.0 up to 4.0 up to 0.4 up to 4.0 up to 0.4 up to 4.0 ○

stability index 6.0~7.0 - - - - - - - - ○ ○

(1) The item appellation and its difinition and the unit belong to JIS K 0101.

(2) The "○" marks in the chart show the factor relevant to corrosion or scale genesis.

(3) When high temperature (over 40℃) ; generally, using corrosive steel, materials which have no protective coating against water, anticorrosive measure shall be done such as adding

corrosion prevention material, degasser and etc.

(4) Under the Cooling water system with hermetically-closed cooling tower; the closed-circuit circulating water and its Makeup water are based on Hot water standard,

spreading water and its Makeup water are based on circulating Cooling water system.

(5) Supplied / replenished water needs to be tap water or industrial water or groundwater.

Deionized water, regeneration treated water and softening treated water are excluded.

(6) Upper 15 items are shown as a typical factor for corrosion and/or scale genesis.

S

t

a

n

d

a

r

d

V

a

l

u

e

R

e

f

e

r

e

n

c

e

Makeup water transient water Makeup water

Water Quality Standard for Cooling water, Cold water, Hot water, Makeup water (JRA GL02-1994)

Item

Cooling waterCold water

Hot waterTendency

Circulating water system Lower Hot water system Higher Hot water system

Circulating waterScale

genesisMakeup water Makeup water Corrosion