7
ETN-Z500-Zone-Rev1-1-A4 Rev. 1.1 06/01/2009 1 Meitav-tec Ltd (Contel group) Tel: +972-3-9626462 Fax: +972-3-9626620 www.meitavtec.com - [email protected] ETN-Z500 Owner’s Manual – Installation and Operating Instructions Please read this manual carefully before installation and use. Index Installation Instructions 1 Wiring Connections 2 DIP switch Configuration 3 Operating Manual 4 ON button 4.1 OFF button 4.2 FAN button 4.3 Technician settings 5 Set point limits 5.1 Set point limits for economy mode 5.2 Offset settings 5.3 Celsius/Fahrenheit selection 5.4 Damper’s open/close motor time 5.5

Owner’s Manual – Installation and Operating Instructions · Owner’s Manual – Installation and Operating Instructions Please read this manual carefully before installation

Embed Size (px)

Citation preview

Page 1: Owner’s Manual – Installation and Operating Instructions · Owner’s Manual – Installation and Operating Instructions Please read this manual carefully before installation

ETN-Z500-Zone-Rev1-1-A4 Rev. 1.1 06/01/2009 1

Meitav-tec Ltd (Contel group)

Tel: +972-3-9626462 Fax: +972-3-9626620

www.meitavtec.com - [email protected]

ETN-Z500 Owner’s Manual – Installation and Operating Instructions

Please read this manual carefully before installation and use.

Index

Installation Instructions 1

Wiring Connections 2

DIP switch Configuration 3

Operating Manual 4

ON button 4.1

OFF button 4.2

FAN button 4.3

Technician settings 5

Set point limits 5.1

Set point limits for economy mode 5.2

Offset settings 5.3

Celsius/Fahrenheit selection 5.4

Damper’s open/close motor time 5.5

Page 2: Owner’s Manual – Installation and Operating Instructions · Owner’s Manual – Installation and Operating Instructions Please read this manual carefully before installation

2

On/Off Select Prog

CoolHeat

AutoFan

Setting

1. Installation Instructions

Separate the front panel from back panel by depressing the

tongue located in the top of the unit.

Pull the back panel out.

Line the back panel up against the wall or flat surface. Install

three screws as required.

Make electrical connections as shown on enclosed electrical

wiring connections table.

Install the cover to the back panel; first the two tabs on the

bottom and then the top tongue. Push until tight against the

wall.

2. Wiring Connections

2.1 Connections table.

On PCB Sticker Function

R R Supply 24Vac

C C Supply 24Vac

S1 CL Close Damper

S2 OP Open Damper

A A RS485 communication for Master and PS

B B RS485 communication for Master and PS

0 0 Common

T T External temperature sensor (option)

Page 3: Owner’s Manual – Installation and Operating Instructions · Owner’s Manual – Installation and Operating Instructions Please read this manual carefully before installation

3

3. DIP switch Configuration

Do not make any changes to the DIP switch before turning the unit off and disconnecting power.

DIP switch SW1

Switch Function Pos. Def.

Internal Sensor ON X 1

External Sensor OFF

External Sensor ON 2

Internal Sensor OFF X

External Sensor ON 3

Internal Sensor OFF X

4 NOT IN USE OFF X

5 NOT IN USE OFF X

Set dampers open close time ON 6

Normal mode OFF X

DIP switch SW2: Unit’s Address – see MAC address table.

Addr. Switch position Addr. Switch position 0 NOT IN USE 32 6 1 1 33 1+6 2 2 34 2+6 3 1+2 35 1+2+6 4 3 36 3+6 5 1+3 37 1+3+6 6 2+3 38 2+3+6 7 1+2+3 39 1+2+3+6 8 4 40 4+6 9 1+4 41 1+4+6 10 2+4 42 2+4+6 11 1+2+4 43 1+2+4+6 12 3+4 44 3+4+6 13 1+3+4 45 1+3+4+6 14 2+3+4 46 2+3+4+6 15 1+2+3+4 47 1+2+3+4+6 16 5 48 5+6 17 1+5 49 1+5+6 18 2+5 50 2+5+6 19 1+2+5 51 1+2+5+6 20 3+5 52 3+5+6 21 1+3+5 53 1+3+5+6 22 2+3+5 54 2+3+5+6 23 1+2+3+5 55 1+2+3+5+6 24 4+5 56 4+5+6 25 1+4+5 57 1+4+5+6 26 2+4+5 58 2+4+5+6 27 1+2+4+5 59 1+2+4+5+6 28 3+4+5 60 3+4+5+6 29 1+3+4+5 61 1+3+4+5+6 30 2+3+4+5 62 2+3+4+5+6 31 1+2+3+4+5 63 1+2+3+4+5+6

Page 4: Owner’s Manual – Installation and Operating Instructions · Owner’s Manual – Installation and Operating Instructions Please read this manual carefully before installation

4

4. Operating Manual

4.1 On Button

• Press the ON button to turn the zone ON – “ON” appears on display.

4.2 Off Button

• Press the OFF button to turn the zone OFF – “OFF” appears on display.

4.3 Fan Button

• Press the FAN button to switch between FAN ON and AUTO FAN.

In AUTO FAN, mode the fan works according to demand for cooling or heating.

In FAN ON mode, the fan works continuously.

Attention: If the fan mode was set to AUTO FAN by the Master, it cannot be changed from the zone.

Fan

OC

ON

Auto Fan

Fan

Auto Fan Fan on

Off

OFF

OC

On

ON

OC

Page 5: Owner’s Manual – Installation and Operating Instructions · Owner’s Manual – Installation and Operating Instructions Please read this manual carefully before installation

5

5. Technician Settings

5.1 Set point limits

• Turn the zone ON.

• Set the COOL temperature to 10ºC (51ºF)

• Wait until “Set” stops flashing.

• Press and hold the FAN button (5 seconds) until “COOL” and the temperature limit for

cooling appear on display.

• Using the “+” and “-‘” buttons, adjust the temperature limit for cooling.

(Range: 10ºC÷30ºC, 51ºF÷86ºF).

• Press the FAN button again – “HEAT” and the temperature limit for heating appear on

display.

• Using the “+” and “-‘” buttons, adjust the temperature limit for heating.

(Range: 10ºC÷30ºC, 51ºF÷86ºF).

The set point limits will not affect the display of the zone when the user adjusts the

temperature. The display will show the set temperature adjusted by the user but the

thermostat will perform according to the set temperature limits.

FanOn

Using the buttonAdjust the temperature to 10ºC / 51ºF

+

-

ON

OC Press & Hold

Using the buttonAdjust the set temperature limit for heating

+

-

OC

Cool

Using the buttonAdjust the set temperature limit for cooling

+

-

Fan

Heat

OC

Page 6: Owner’s Manual – Installation and Operating Instructions · Owner’s Manual – Installation and Operating Instructions Please read this manual carefully before installation

6

5.2 Set point limits for economy mode

• Follow the steps described in 5.1.

• Press the FAN button again – “COOL”, “AUX” and the temperature limit for cooling in

economy mode appear on display.

• Using the “+” and “-‘” buttons, adjust the temperature limit for cooling in economy

mode.

(Range: 20ºC÷30ºC, 69ºF÷86ºF).

• Press the FAN button again – “HEAT”, “AUX” and the temperature limit for heating in

economy mode appear on display.

• Using the “+” and “-‘” buttons, adjust the temperature limit for heating in economy

mode.

(Range: 10ºC÷20ºC, 51ºF÷68ºF).

5.3 Offset settings The Offset is used for calibration of the measured temperature if needed.

• Follow the steps described in 5.2.

• Press the FAN button again – “AUX” and the current offset appear on display.

• Using the “+” and “-‘” buttons, adjust the offset for measured temperature.

(Range: -5ºC÷+5ºC, -9ºF÷+9ºF).

• Press the FAN button again to return to normal display mode.

FanFan

+

-

OC OC

Heat

#5.1

Cool

AUX AUX

Set Set

Using the buttonAdjust the temperature limit for cooling in economy mode

+

-Using the buttonAdjust the temperature limit for heating in economy mode

Fan

+

-

OC

#5.2

AUX

Set

Using the buttonAdjust the offset for measured temperature

Page 7: Owner’s Manual – Installation and Operating Instructions · Owner’s Manual – Installation and Operating Instructions Please read this manual carefully before installation

7

5.4 Celsius/Fahrenheit Selection

• Turn the zone ON.

• Set the COOL temperature to 15ºC (65ºF)

• Wait until “Set” stops flashing.

• Press and hold the FAN button (3 seconds) until the scale changes.

5.5 Set the Damper’s open/close motor time

• Move DIP switch SW1 – No. 6 to ON position.

• “AUX” and the current time appear on display.

• Using the “+” and “-“ buttons adjust the damper’s open/close motor time.

The number is multiplied by 10. i.e. 5 5 X 10 50 seconds.

(Range: 2÷40 20÷400 seconds, default 20 seconds)

• Move DIP switch SW1 – No. 6 to OFF position to return to normal mode.

FanOn

Using the buttonAdjust the temperature to 15ºC / 65ºF

+

-

ON

OC Press & Hold OC OF

The scale will change

ON

1 2 3 4 5 6

S1 DIP

AUX

Using the buttonAdjust the damper’s open/close motor time

+

-

ON

1 2 3 4 5 6

S1 DIP