52
OpenAir Damper Actuators Range overview Building Technologies s

OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

OpenAirDamper ActuatorsRange overview

Building Technologies s

Page 2: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

For a comfortable working and living environmentConsultants, wholesalers, system houses, craftsmen, building owners, operators and the environment take advantage of the technology and reliability offered by the OpenAir™ damper actuators from Siemens, which have been leading the way for over 20 years. Building automation can only function correctly if each component in the system operates reliably and accurately. The damper actuators are of modular design and excel not only in low power consumption. They increase the flexibility of the application areas and enable fast implementation of customer requirements, thus ensuring secure and sustained added value of HVAC plant.

2

Page 3: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Motors with low noise levelThe sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus, the OpenAir damper actuators are suited for use in commercial buildings, hotels, hospi tals, office buildings, schools and public buildings.

Certified production for high quality

Siemens meets the stringent ISO 9001 and ISO 14001 standards, thus satisfying the requirements of a closed quality and ecological cycle. High quality and simple design are of prime concern from devel-opment all the way through to disposal. The actuators are produced based on the subassembly principle and undergo integr al testing. Each actuator is sub-jected to extensive final testing after assembly is completed. The OpenAir damper actuators conform to the CE, C-Tick and UL standards and are there-fore suited for worldwide use.

Fast deliverySiemens’ global sales network ensures fast and uncomplicated delivery.

Excellent price/performance ratio OpenAir damper actuators provide the best price/performance ratio due to their compact dimensions, exactly calculable size, precise functioning and good price.

Complete product range for all types of application

OpenAir damper actuators are reliable, powerful solutions for recirculated air, outside air, shutoff, smoke extraction and fire protection dampers, blinds as well as VAV devices, central and compact air conditioning units.

Faster installation – lower overall costs

With standardized dimensions, wiring and mounting concepts, OpenAir damper actuators are designed for direct connection and straightforward commis-sioning. This results in savings when it comes to installation expenses. All actuator models are secured with a single fixing screw. The high-torque actuators are equipped with a self-center-ing shaft adapter, which can be fitted from both sides. This offers the advan-tage that the actuator can also be easily fitted to short shafts. This patented design does not allow the actuator to move in the longitudinal holder, thus preventing friction and cracking noises.

Rugged housing for added durability and longevity

First-class engineering has made it pos-sible to design the OpenAir damper actuators with very compact dimensions. They are easy to handle and very resist-ant to the rough conditions encountered during transportation, storage and on the construction site.

Highlights

Complete product range for any type of application

Quick installation – low overall costs

Rugged housing for added durability

Motors with low noise level

Certified production for high quality

Fast delivery

Best price/performance ratio

3

Page 4: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

GLB

13

1.1

E G

LB1

32

.1E

G

LB1

36

.1E

GLB

33

1.1

E G

LB3

32

.1E

G

LB3

36

.1E

Mod

ula

tin

g

G

LB1

61

.1E

G

LB1

63

.1E

GLB

16

4.1

E

GLB

16

6.1

E D

C 0

...1

0 V

3

-pos

itio

n

GBB

13

1.1

E

GBB

13

5.1

E G

BB1

36

.1E

GBB

33

1.1

E

GBB

33

5.1

E G

BB3

36

.1E

Mod

ula

tin

g

GBB

16

1.1

E

GBB

16

3.1

E G

BB1

64

.1E

G

BB1

66

.1E

DC

0..

.10

V

3

-pos

itio

n

GIB

13

1.1

E

GIB

13

5.1

E G

IB1

36

.1E

GIB

33

1.1

E

GIB

33

5.1

E G

IB3

36

.1E

Mod

ula

tin

g

GIB

16

1.1

E

GIB

16

3.1

E G

IB1

64

.1E

G

IB1

66

.1E

D

C 0

...1

0 V

A

SK7

1.3

A

SK7

1.4

A

SK7

1.1

A

SK7

1.2

A

SK7

4.1

A

SK7

3.1

A

SK7

3.2

A

SK7

5.1

A

SK7

1.9

A

SC7

7.1

E A

SC7

7.2

E A

SK7

4.7

ASK

75

.4

A

SK7

1.5

A

SK7

1.6

A

SK7

1.6

A

SK7

1.6

A

SK7

1.9

A

SK7

1.5

A

SK7

1.6

A

SK7

1.6

A

SK7

1.6

A

SK7

1.9

A

SK7

1.3

A

SK7

1.4

A

SK7

1.1

A

SK7

1.2

A

SK7

4.1

A

SK7

3.1

A

SK7

3.2

A

SK7

5.1

A

SK7

1.9

A

SC7

7.1

E A

SC7

7.2

E A

SK7

4.7

ASK

75

.4

A

SK7

1.3

A

SK7

1.4

A

SK7

1.1

A

SK7

1.2

A

SK7

4.1

A

SK7

3.1

A

SK7

3.2

A

SK7

5.1

A

SK7

1.9

A

SC7

7.1

E A

SC7

7.2

E A

SK7

4.7

ASK

75

.4

GIB

ser

ies

35

Nm

for

app

rox.

6 m

² da

mpe

r ar

ea

15

0 s

ec. r

un

tim

e(5

0 H

z)

GC

A s

erie

s1

8 N

m f

or a

ppro

x.3

dam

per

area

90

sec

. ru

nti

me

15

sec

. SR

tim

e

GD

B s

erie

s5

Nm

for

app

rox.

0.8

dam

per

area

15

0 s

ec. r

un

tim

e(5

0 H

z)

GB

B s

erie

s2

5 N

m f

or a

ppro

x.

4 m

² da

mpe

r ar

ea

15

0 s

ec. r

un

tim

e(5

0 H

z)

GM

A1

21

.1E

GM

A1

26

.1E

GM

A3

21

.1E

GM

A3

26

.1E

GM

A1

31

.1E

GM

A1

32

.1E

G

MA

13

6.1

E M

odu

lati

ng

GM

A1

61

.1E

G

MA

16

3.1

E G

MA

16

4.1

E

GM

A1

66

.1E

D

C 0

...1

0 V

G

CA

12

1.1

E

G

CA

12

6.1

E

G

CA

32

1.1

E

G

CA

32

6.1

E

GC

A1

31

.1E

G

CA

13

5.1

E

Mod

ula

tin

g

G

CA

16

1.1

E

GC

A1

63

.1E

GC

A1

64

.1E

G

CA

16

6.1

E D

C 0

...1

0 V

3-p

osit

ion

2

4 V

GD

B13

1.1

E G

DB1

32

.1E

G

DB1

36

.1E

GD

B33

1.1

E G

DB3

32

.1E

G

DB3

36

.1E

M

odu

lati

ng

GD

B16

1.1

E

GD

B16

3.1

E G

DB1

64

.1E

G

DB1

66

.1E

DC

0..

.10

V

A

SK7

1.1

3

ASK

71

.14

A

SK7

1.1

1

ASK

71

.11

ASK

73

.3

A

SK7

5.3

A

SK7

1.9

A

SC7

7.1

E A

SC7

7.2

E A

SK7

4.7

A

SK7

1.1

3

ASK

71

.14

A

SK7

1.1

1

ASK

71

.11

ASK

73

.3

A

SK7

5.3

A

SK7

1.9

A

SC7

7.1

E A

SC7

7.2

E A

SK7

4.7

GEB

ser

ies

15

Nm

for

app

rox.

3 m

² da

mpe

r ar

ea

15

0 s

ec. r

un

tim

e(5

0 H

z)

G

EB1

31

.1E

GEB

13

2.1

E

GEB

13

6.1

E

GEB

33

1.1

E G

EB3

32

.1E

G

EB3

36

.1E

Mod

ula

tin

g

G

EB1

61

.1E

G

EB1

63

.1E

GEB

16

4.1

E

GEB

16

6.1

E

DC

0..

.10

V

Ro

tary

to

Rota

ry t

o Fl

oor

Fram

e

Ove

rsiz

ed

Tand

em

Tand

em

Wea

ther

U

nive

rsal

Ex

tern

al

Exte

rnal

Sh

aft

lin

ear

kit

linea

r ki

t m

ount

kit

m

ount

kit

sh

aft

brac

ket-

br

acke

t sh

ield

le

ver

auxi

liary

au

xilia

ry

exte

nsio

n

w

/mou

ntin

g

ad

apte

r 2

pt./3

pt.

m

odul

atin

g

sw

itch

sw

itch

bra

cket

co

ntro

l

1x

2x

GLB

ser

ies

10

Nm

for

app

rox.

1.5

dam

per

area

15

0 s

ec. r

un

tim

e(5

0 H

z)

A

C/D

C 2

4 V

G

QD

12

1.1

A

2

30

V G

QD

32

1.1

A

AC

/DC

24

V

GQ

D1

31

.1A

Mod

ula

tin

g

AC

/DC

24

V

GQ

D1

61

.1A

2-p

osit

ion

G

SD1

21

.1A

On

/Off

(1

-wir

e SP

ST)

GSD

32

1.1

A

Spring return actuators and accessories Non-spring return actuators and accessories

GSD

ser

ies

2 N

m f

or a

ppro

x.0

.3 m

² da

mpe

r ar

ea

30

sec

. ru

nti

me

Co

ntro

l

Pow

er

Stan

dard

Fe

edba

ck

Adj

usta

ble

Adj

usta

ble

Feed

back

2

auxi

liary

si

gnal

supp

ly

mod

el

pote

ntio

- st

art/

span

st

art/

span

(1

kΩ)

wit

h sw

itch

es

met

er

w

ith

2 au

xil-

2 au

xilia

ry

(1

kOhm

)

iary

sw

itch

es

swit

ches

GM

A s

erie

s7

Nm

for

app

rox.

1.5

dam

per

area

90

sec

. ru

nti

me

15

sec

. SR

tim

e

GQ

D s

erie

s 2

Nm

for

app

rox.

0.3

dam

per

area

30

sec

. ru

nti

me

15

sec

. SR

tim

e

DC

0..

.10

V

3-p

osit

ion

2-p

osit

ion

(to

26.5

mm

)

3-p

osit

ion

3-p

osit

ion

2-p

osit

ion

2-p

osit

ion

3-p

osit

ion

3-p

osit

ion

AC

AC

/DC

24

V

23

0 V

AC

AC

/DC

24

V

AC

/DC

24

V

23

0 V

AC

AC

/DC

24

V

AC

/DC

24

V

AC

/DC

24

V

AC

/DC

24

V

23

0 V

AC

AC

23

0 V

AC

23

0 V

AC

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

23

0 V

AC

23

0 V

AC 2

30

VA

C2

4 V

AC

24

VA

C

4

Page 5: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

A

SK5

5.2

A

SK5

5.2

A

SK7

2.2

A

SK7

2.1

ASK

75

.2

GD

B s

erie

s1

25

N f

or a

ppro

x.0

.8 m

² da

mpe

r ar

ea

15

0 s

ec. r

un

tim

e(5

0 H

z)

GB

B s

erie

s5

50

N f

or a

ppro

x.

4 m

² da

mpe

r ar

ea

15

0 s

ec. r

un

tim

e(5

0 H

z)

A

SK7

2.3

GEB

ser

ies

40

0 N

for

app

rox.

3 m

² da

mpe

r ar

ea

15

0 s

ec. r

un

tim

e(5

0 H

z)

GLB

ser

ies

25

0 N

for

app

rox.

1.5

dam

per

area

15

0 s

ec. r

un

tim

e(5

0 H

z)

A

ST1

0

AST

11

A

CS9

31

ASK

79

.3/*

*

GD

B 3

00

Pa

VA

V s

tati

c *

5 N

m f

or a

ppro

x.0

.8 m

² da

mpe

r ar

ea

15

0 s

ec. r

un

tim

e(5

0 H

z)

ASV

30

0 P

a V

AV

mo

du

lar

*

GLB

30

0 P

a V

AV

sta

tic

*1

0 N

m f

or a

ppro

x.1

.5 m

² da

mpe

r ar

ea

15

0 s

ec. r

un

tim

e(5

0 H

z)

A

ST1

0

AST

11

A

CS9

31

A

ST1

0

AST

11

A

CS9

31

A

ST1

0

AST

11

A

CS9

31

A

ST1

0

AST

11

A

CS9

31

* O

nly

ava

ilabl

e th

rou

gh O

EM c

han

nel

**

For

for

m f

itte

d sh

aft

fixa

tion

fro

m 8

…1

5 m

m

ro

tary

kit

shie

ld

unit

co

nver

ter

soft

war

e pl

ate

join

t

Co

ntro

l

Pow

er

Stan

dard

Fe

edba

ck

Adj

usta

ble

Adj

usta

ble

Feed

back

2

auxi

liary

2

auxi

liary

si

gnal

supp

ly

mod

el

pote

ntio

- st

art/

span

st

art/

span

(1

kΩ)

wit

h sw

itch

es

swit

ches

+

met

er

ther

mal

(1

kOhm

)

cut-

out

ASK

79

.3/*

*

GN

A F

&S

actu

ator

*7

Nm

for

app

rox.

1 m

² da

mpe

r ar

ea

90

sec

. ru

nti

me

>1

5 s

ec. S

R ti

me

3-p

osit

ion

G

LB18

1.1E

/3

Mod

ula

tin

g

G

LB18

1.1E

/3 D

C 0

...1

0 V

GG

A126

.1E*

* GG

A126

.1E/

T**

GG

A326

.1E*

*

3-p

osit

ion

G

DB18

1.1E

/3

Mod

ula

tin

g

GDB

181.

1E/3

DC

0..

.10

V

3-p

osit

ion

AS

V181

.1E/

3

Mod

ula

tin

g

AS

V181

.1E/

3 D

C 0

...1

0 V

2

-pos

itio

n

GNA1

26.1

E**

GN

A326

.1E*

*

G

LB1

31

.2E

GLB

13

2.2

E

GLB

13

6.2

E

G

LB3

31

.2E

GLB

33

2.2

E

GLB

33

6.2

E

G

LB1

61

.2E

G

LB1

63

.2E

GLB

16

4.2

E

GLB

16

6.2

E

GBB

13

1.2

E

GBB

13

5.2

E G

BB1

36

.2E

GBB

33

1.2

E

GBB

33

5.2

E G

BB3

36

.2E

G

BB1

61

.2E

G

BB1

63

.2E

GBB

16

4.2

E

GBB

16

6.2

E

2

4

V G

DB1

31

.2E

GD

B13

2.2

E

GD

B13

6.2

E

23

0

V G

DB3

31

.2E

GD

B33

2.2

E

GD

B33

6.2

E

GD

B16

1.2

E

GD

B16

3.2

E G

DB1

64

.2E

G

DB1

66

.2E

3

-pos

itio

n

GEB

13

1.2

E G

EB1

32

.2E

G

EB1

36

.2E

G

EB3

31

.2E

GEB

33

2.2

E

GEB

33

6.2

E

Mod

ula

tin

g

G

EB1

61

.2E

G

LB1

63

.2E

GEB

16

4.2

E

GEB

16

6.2

E D

C 0

...1

0 V

A

ST1

0

AST

11

A

CS9

31

Non-spring return actuators and accessories Special OEM actuators

GG

A F

&S

actu

ato

r *

18

Nm

for

app

rox.

2

.5 m

² da

mpe

r ar

ea

90

sec

. ru

nti

me

>1

5 s

ec. S

R ti

me

2

-pos

itio

n

wit

h 2

auxi

l-ia

ry s

wit

ches

2 au

xilia

ry

sw

itch

es

Line

ar to

Clam

pW

eath

erSe

ttin

gIn

terf

ace

Calib

rati

onLo

ckin

gLi

near

to

w/m

ount

ing

w

ith

ro

tary

kit

ca

rdan

plat

e

GGA3

26.1

E/T*

*

GNA1

26.1

E/T*

*GN

A326

.1E/

T**

Mod

ula

tin

g

DC

0..

.10

V

3-p

osit

ion

Mod

ula

tin

g

DC

0..

.10

V

Mod

ula

tin

g

DC

0..

.10

V

3-p

osit

ion

3-p

osit

ion

AC

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

24

VA

C

AC

23

0V

AC

23

0V

AC

23

0V

AC

23

0V

AC

23

0V

AC

AC

/DC

24

V

AC

/DC

24

V

5

Page 6: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Rotary actuators with spring return

Self-centering shaft coupling with patented design relieves strain on the actuator for longer motor life and increased reliability

Position indicators are uni ver-sally located for at-a-glance verification

Manual override allows to check:- Mounting of actuator

on damper shaft- Mechanical functionality

of damper blade- End position of damper

blade

Optional built-in adjustable start/span factory-installed for faster installation

Single-bolt fastening for easy installation and reduced installed cost

AC/DC operation for added flexibility

Direct-coupled connection for on-the-go installation.Position measured continuou sly with no need to power up at startup, saving time.Full-stroke overload protection kicks in automatically to protect motor and components.

Precabled options are factory-installed for faster, easier installation in the field.Consistent wiring detail across product family for faster installation and lower in stalled cost.Motor technology for quiet, low-noise operation.

Rugged housing on all models for added durability and longevity

Other SR models: GQD, GCA

More benefits

GMA model shown

Auxiliary end switches adjustment on both sides of the actuator

Compact footprint for ease of installation

6

Page 7: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Rotary actuators non-spring return

Position indicators are universally located for at-a-glance verification

Auxiliary end switches adjustment on both sides of the actuator

Self-centering, shaft coupling with patented design relieves strain on the actuator for longer motor life and increased reliability

Manual override allows to check:- Mounting of actuator

on damper shaft- Mechanical functionality

of damper blade- End position of damper blade

Direct-coupled connection snap on for on-the-go, fast installation.Full-stroke protection kicks in automa-tically to protect motor and components.Precabled options are factory-installed for faster, easier installation in the field.

Small footprint provides powerful performance.Consistent wiring detail across product family for faster installation and lower in stalled cost.Motor technology for quiet, low-noise operation.

GEB model shown

Other NSR models: GSD, GDB, GLB, GBB, GIB

Moreperformance

Rugged housing on all models for added durability and longevity

Optional built-in adjustable start/span available factory-installed for faster instal-lation

Single-bolt fastening for easy installation and reduced installed cost

7

Page 8: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Rugged housing on all models for added durability and longevity

Optional built-in adjustable start/span factory-installed for faster installa-tion

Auxiliary end switches adjustment on both sides of the actuator

Manual override allows to check:- Mounting of actuator on damper shaft- Mechanical functionality of damper blade- End position of damper blade

Full-stroke protection kicks in automa-tically to protect motor and components.Precabled options are factory-installed for faster, easier installation in the field.Small footprint provides powerful performance.

Consistent wiring detail across product family for faster installation and lower installed cost.Motor technology for quiet, low-noise operation.

GEB model shown

Other NSR models: GDB, GLB, GBB

Linear actuators non-spring return

Morealternatives

8

Page 9: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Short shaft mounting option

For easy mounting on short shafts without special accessories, the self-centering shaft adapter can be mounted on the backside of the actuator.Each actuator includes an adapter so that the position indicator is still easily viewed.

Frame mounting

The frame mounting kit is used when actuator cannot be directly mounted on damper shaft due to space limitations.

Foot mounting

Easily replace existing modulating motors using the foot mounting kit. The foot mounting kit can also be used for placing the actuator in the air stream and linking to the damper blades.

OpenAir actuators can be mounted in tandem to effectively double the torque of a single actuator. This unique feature allows OpenAir actuators to operate in a wider range of applications.

Unit fan applications

Excellent when space is limited, the GMA and GEB have a small footprint for easy mounting.High torque, full features, and a small footprint make the GMA and GEB actuators a perfect choice for unit fan applications.

More mountingalternatives

Actuators mounted in tandem

9

Page 10: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

OpenAiraccessories

DescriptionGDB/

GLB

GEB/

GMA

GCA/GIB

GBB

Part no. /

type reference

Hex key

Hex key

Adjustment key 1 ea.

••

74 109 0017 04 109 2111 074 109 0013 0

Rotary to linear set with lever Allows a direct-coupled actuator to provide a linear drive; can be used to simultaneously drive a set of opposing or adjacent dampers with a single actuator.

• ASK71.5

Rotary to linear set with lever Allows a direct-coupled actuator to provide an auxiliary linear drive; can be used to simultaneously drive a set of opposing or adjacent dampers with a single actuator.

••

ASK71.13ASK71.3

Rotary to linear set with lever and angle bracket For use in applications where the actuator can be rigidly surface-mounted and a linear stroke output is required.

• ASK71.6

Rotary to linear set with lever and mounting plateFor use in applications where the actuator can be rigidly surface-mounted and a linear stroke output is required.

••

ASK71.14ASK71.4

Universal leverFor use with all OpenAir rotary to linear kits for linear applications requiring connection to damper louver shaft when joint connection is not possible.For 8 to 25.6 mm round.

• • • ASK71.9

10

Page 11: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

DescriptionGDB/

GLB

GEB/

GMA

GCA/GIB

GBB

Part no. /

type reference

Tandem mounting bracket

Tandem mounting bracket for 2-position and 3-positionGCA/GIB models

Tandem mounting bracket for modulating GCA/GIB models

ASK73.3

ASK73.1

ASK73.2

Rotary to linear set for duct mountingFor airstream applications and where a foot-mounted actuator can be used. Includes crank arm, Teflon support-bearing ring, and mounting fasteners. Rotary to linear set for duct and frame mounting

•ASK71.6ASK71.1

ASK71.11

Rotary to linear set for frame mountingFor direct mounting to damper frame. Includes a crank arm to generate a linear stroke, a Teflon support-bearing ring to minimize side-loading on the actuator’s output bearing, and other mounting fasteners.

Rotary to linear set for duct and frame mounting

• ASK71.2

ASK71.11

Anti-rotation bracket ••

4 190 7152 074 190 0013 04 190 6599 0

Replacement standard shaft adapter

••

74 718 0008 04 718 1402 0

11

Page 12: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

OpenAiraccessories

DescriptionGDB/

GLB

GEB/

GMA

GCA/GIB

GBB

Part no. /

type reference

Special shaft adapter • Up to 27 mm shaft diameter

Note: When used with a GIB,

accepts shaft diameters from 19 to 27 mm

• ASK74.1

Actuator shaft insertfor small shaft diameters • Up to 10 mm diameter

• ASK78.3

Replacement position indicators/packs of 10

••

4 304 1349 074 304 0000 04 304 1348 0

Weathershield Includes cover, gasket and screws.• IP65 • UV-resistant

•••

ASK75.3ASK75.1ASK75.4

Shaft extension • • ASK74.7

Setting unitHandheld programming tool for VAV static GDB/GLB/ASV181.1E/3

• AST10

12

Page 13: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

DescriptionGDB/

GLB

GEB/

GMA

GCA/GIB

GBB

Part no. /

type reference

Interface converterPPS2 to RS232 interface converter for use with GDB/GLB/ASV181.1E/3

Service case

AST11

AST21

External auxiliary switches External auxiliary switch kit, attachable to GCA, GMA, GEB, GBB und GIB rotary actuators- 1 external auxiliary switch - 2 external auxiliary switches

••

••

ASC77.1EASC77.2E

Shaft inserts for GDB/GLB…1 - D-profile - Round ½ ” - Square 8 x 8 mm - Square 8 x 8 mm fix- Square 10 x 10 mm- Round 8 mm - Round 10 mm - Round 12 mm- Round ⅜ ” - D-profile fix

••••••••••

ASK78.4ASK78.5 ASK78.6 ASK78.14ASK78.7ASK78.8ASK78.9ASK78.10ASK78.11ASK78.12

Shaft adapter square - 15 x 15 mm - 12 x 12 mm - 10 x 10 mm - 8 x 8 mm

- 15 x 15 mm - 12 x 12 mm - 10 x 10 mm - 8 x 8 mm

••••

••••

74 718 0019 074 718 0020 074 718 0021 074 718 0022 0

74 718 0027 074 718 0028 074 718 0029 0 74 718 0030 0

13

Page 14: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

DC 0…10 V actuators wired in parallel with one transformer

OpenAir DC 0…10 V actuators can be wired in parallel with one signal driving up to ten actuators. Feedback should not be wired together and can be picked up at one of the actuators.

DC 0…10 V actuators wired in parallel with multiple transformers

OpenAir DC 0…10 V actuators can be wired in parallel with one signal driving a bank of up to ten actuators. Multiple transformers can power multiple actuators. Feedback should not be wired together and can be picked up at one of the actuators.

Sequencing of DC 0…10 V actuators

With the settings shown, two DC 0…10 V actuators can be sequenced such that the first one will operate at DC 0…2 V and the second at DC 2…10 V.This feature is perfect for specialized applications, such as staging or minimum required airflow.

More wiringoptions

EARTH GROUNDISOLATING EN 61558TRANSFORMER FOR

AC 24 V POWER

AC 24 VNEUTRAL

MAXIMAL 10 ACTUATORS

EARTH GROUND ISOLATING EN 61558 TRANSFORMER FOR AC 24 V POWER

AC 24 VNEUTRAL AC 24 VNEUTRAL AC 24 VNEUTRAL

EARTH GROUNDISOLATING EN 61558TRANSFORMER FOR

AC 24 V POWER

AC 24 VNEUTRAL

14

Page 15: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

2-position AC 24 V actuators wired in parallel

Two actuators can be wired in parallel to double the torque or may be mounted separately and operated in parallel.

2-position AC 230 V actuators wired in parallel

Two actuators can be wired in parallel to double the torque or may be mounted separately and operated in parallel.

3-position actuators wired in parallel

Two actuators of the same type can be wired in parallel to double the torque or may be mounted separately and operated in parallel.

GQD/GMA/GCA series*Note: GBB/GIB index A GBB/GIB index B

GDB/GLB/GEB/GBB/GIB series

NEUTRAL AC 24 V

EARTH GROUNDISOLATING EN 61558TRANSFORMER FOR

AC 24 V POWER

AC 24 V NEUTRAL

EARTH GROUNDISOLATING EN 61558TRANSFORMER FOR

AC 24 V POWER

EARTH GROUNDISOLATING EN 61558TRANSFORMER FOR

AC 24 V POWER

NEUTRALAC 24 V

15

Page 16: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

2 NmAC/DC 24 V and AC 230 VModulating2-position/3-position

N474

Submittalsummary

Dimensions shown in mm

OpenAir GQD series –spring return, rotary movement

Technical data

Torque 2 Nm running and

2 Nm spring return

Runtime for 90° 30 sec. operating

15 sec. typical closing

Frequency 50 / 60 Hz

Power consumption AC/DC 24 V

Running 6.5 VA / 4.5 W

Holding 4 VA / 2.5 W

Power consumption AC 230 V

Running 10 VA / 4.5 W

Holding 7 VA / 3 W

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 8 to 15 mm round

6 to 11 mm square

20 mm min. length

Operating temperature -32…+55 °C

Storage temperature -32…+50 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protecion IP40

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material durable plastic

Gear lubrication silicon-free

Dimensions 70 (W) x 121.4 (H) x

62.5 mm (D)

Weight 0.50 kg

16

Page 17: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Connection diagrams

2-position, AC/DC 24 V 2-position, AC 230 V 3-position, AC 24 V / DC 24…48 V

Modulating (DC 0…10 V), AC 24 V / DC 24…48 V

Type reference

Operating voltage Control

AC

24

V ±

20

%D

C 2

4 V

± 1

5%

AC

24

V ±

20

%D

C 2

4…4

8 V

±

20

%

AC

23

0 V

± 1

5%

DC

0…

10 V

3-p

osi

tio

n

2-p

osi

tio

n

GQD121.1A

GQD321.1A

GQD131.1A

GQD161.1A

17

Page 18: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

7 NmAC 24 V / DC 24…48 V and AC 230 V Modulating 2-position/3-position

N474

Technical data

Torque 7 Nm running and

7 Nm spring return

Runtime for 90° 90 sec. operating

15 sec. typical closing

Frequency 50 / 60 Hz

Power consumption AC/DC 24 V

Running 5 VA / 3.5 W

Holding 2.5 W

Power consumption AC 230 V

Running 7 VA / 4.5 W

Holding 3.5 W

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 6.4 to 20.5 mm round

6.4 to 13 mm square

20 mm min. length

Operating temperature -32…+55 °C

Storage temperature -32…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material die-cast aluminum alloy

Gear lubrication silicone-free

Dimensions 192 mm (H) x 81 mm (W)

x 63 mm (D)

Weight 1.3 kg

Submittalsummary

Dimensions shown in mm

OpenAir GMA series –spring return, rotary movement

18

Page 19: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

2-position, AC 24 V / DC 24…48 V

2-position, AC 230 V 3-position, AC 24 V / DC 24…48 V Modulating (DC 0…10 V), AC 24 V / DC 24…48 V

Connection diagrams

Type reference

Operating voltage Control Built-in control options

AC

24

V ±

20

%D

C 2

4...4

8 V

±

20

%

AC

23

0 V

±

10

%

DC

0…

10 V

3-p

osi

tio

n

2-p

osi

tio

n

Posi

tio

nfe

edb

ack

Du

al a

uxi

liary

swit

ches

Off

set

and

span

GMA121.1E

GMA126.1E

GMA321.1E

GMA326.1E

GMA131.1E

GMA132.1E

GMA136.1E

GMA161.1E

GMA163.1E

GMA164.1E

GMA166.1E

19

Page 20: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

30

0

73

85,8

90

0

100

27

,6

19

7

Ø 8

... 2

5,6

mm

6..

. 18

mm

max.17,5

P1..

.P3

1..

.9

S1..

.S6

24

,8

61,5

min

. 10

0

N474

18 Nm AC 24 V / DC 24…48 V and AC 230 V Modulating 2-position/3-position

Submittalsummary

Dimensions shown in mm

OpenAir GCA series –spring return, rotary movement

Technical data

Torque 18 Nm running and

18 Nm spring return

Runtime for 90° 90 sec. operating

15 sec. typical closing

Frequency 50 / 60 Hz

Power consumption AC/DC 24 V

Running 7 VA / 5 W

Holding 3 W

Power consumption AC 230 V

Running 8 VA / 6 W

Holding 4 W

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 8 to 25.6 mm round

6 to 18 mm square

20 mm min. length

Operating temperature -32…+55 °C

Storage temperature -32…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material die-cast aluminum alloy

Gear lubrication silicone-free

Dimensions 300 mm (H) x 100 mm

(W) x 70.5 mm (D)

Weight 2.1 kg

20

Page 21: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Connection diagrams

Type reference

Operating voltage Control Built-in control options

AC

24

V ±

20

%D

C 2

4...4

8 V

±

20

%

AC

23

0 V

±

10

%

DC

0…

10 V

3-p

osi

tio

n

2-p

osi

tio

n

Posi

tio

nfe

edb

ack

Du

al a

uxi

liary

swit

ches

Off

set

and

span

GCA121.1E

GCA126.1E

GCA321.1E

GCA326.1E

GCA131.1E

GCA135.1E

GCA161.1E

GCA163.1E

GCA164.1E

GCA166.1E

Modulating (DC 0…10 V),AC 24 V / DC 24…48 V

2-position, AC 24 V / DC 24…48 V

3-position, AC 24 V / DC 24…48 V

2-position, AC 230 V

21

Page 22: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

2 NmAC/DC 24 V and AC 230 VOn/Off (1-wire SPST)

N474

Submittalsummary

Dimensions shown in mm

OpenAir GSD series –non-spring return, rotary movement

Technical data

Torque 2 Nm

Runtime for 90° 30 sec.

Frequency 50 / 60 Hz

Power consumption AC/DC 24 V

Running 2 VA / 1.5 W

Holding 1 VA / 0.5 W

Power consumption AC 230 V

Running 12 VA / 2 W

Holding 12 VA / 2 W

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 8 to 15 mm round

6 to 11 mm square

20 mm min. length

Operating temperature -32…+55 °C

Storage temperature -32…+50 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP40

CE Conformity

Electromagnetic

Compatibility (EMC) 2004/108/EG

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material durable plastic

Gear lubrication silicon-free

Dimensions 121.4 (W) x 70 (H) x

62.5 mm (D)

Weight 0.44 kg

22

Page 23: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Connection diagrams

On/Off (1-wire SPST), AC/DC 24 V

On/Off (1-wire SPST),AC 230 V

Type reference

Operating voltage Control

AC

24

V ±

20

%D

C 2

4 V

± 1

5%

AC

23

0 V

±

15

%

On

/Off

(1

-wir

e SP

ST)

GSD121.1A

GSD321.1A

23

Page 24: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Dimensions shown in mm Technical data

Torque 5 Nm

Runtime for 90° 150 sec. (50 Hz)

opening and closing

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 3 VA (modulating)

Running 2 VA (3-position)

Holding 1 W (modulating)

Power consumption AC 230 V

Running 2 VA

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 8 to 16 mm round

6 to 12.8 mm square

30 mm min. length

Operating temperature -32…+55 °C

Storage temperature -32…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material durable plastic

Gear lubrication silicone-free

Dimensions 137 mm (H) x 68 mm

(W) x 59.5 mm (D )

Weight 0.48 kg

5 NmAC 24 V and AC 230 V Modulating 3-position

N474

Submittalsummary OpenAir GDB series –

non-spring return, rotary movement

24

Page 25: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Note:GSF161.1E, 2 Nm, 20 s runtime for 90° also available

Connection diagrams

46

34

G0

1

100%

0%

(Y2

)

AC 0 V 0...1000

(a)

(G)

1

7 P3

(Y1

)

(b)

(c)

6 P1 P2

AC 24 V

MA

AC 24 V...230 V / 6 (2) A

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

S2 S3 S5 S6

S1 S4

(Q1

1)

(Q2

1)

B

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V 3-position, AC 230 V

46

34

G0

2

A100%

0%

(Y2

)

AC 230 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(N)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

4 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

M

46

34

G0

3

A100%

0%

DC 0...10 V

(G)

DC 0...10 V

(Y)

(G0

)

(U)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

2 9 S2 S3 S5 S6

1 8 S1 S4

(Q1

1)

(Q2

1)

B

AC 24 V...230 V / 6 (2) AAC 24 V

M

Type reference

Operating voltage Control Built-in control options

AC

24

V

± 2

0%

AC

23

0 V

±

10

%

DC

0…

10 V

3-p

osi

tio

n

Posi

tio

nfe

edb

ack

Du

al a

uxi

liary

swit

ches

Off

set

and

span

GDB131.1E

GDB132.1E

GDB136.1E

GDB331.1E

GDB332.1E

GDB336.1E

GDB161.1E

GDB163.1E

GDB164.1E

GDB166.1E

25

Page 26: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Dimensions shown in mm Technical data

Torque 10 Nm

Runtime for 90° 150 sec. (50 Hz)

opening and closing

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 3 VA (modulating)

Running 2 VA (3-position)

Holding 1 W (modulating)

Power consumption AC 230 V

Running 2 VA

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 8 to 16 mm round

6 to 12.8 mm square

30 mm min. length

Operating temperature -32…+55 °C

Storage temperature -32…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material durable plastic

Gear lubrication silicone-free

Dimensions 137 mm (H) x 68 mm

(W) x 59.5 mm (D)

Weight 0.48 kg

Submittalsummary OpenAir GLB series –

non-spring return, rotary movement

10 NmAC 24 V and AC 230 V Modulating 3-position

N474

26

Page 27: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Type reference

Operating voltage Control Built-in control options

AC

24

V

± 2

0%

AC

23

0 V

±

10

%

DC

0…

10 V

3-p

osi

tio

n

Posi

tio

nfe

edb

ack

Du

al a

uxi

liary

swit

ches

Off

set

and

span

GLB131.1E

GLB132.1E

GLB136.1E

GLB331.1E

GLB332.1E

GLB336.1E

GLB161.1E

GLB163.1E

GLB164.1E

GLB166.1E

Connection diagrams4

63

4G

01

100%

0%

(Y2

)

AC 0 V 0...1000

(a)

(G)

1

7 P3

(Y1

)

(b)

(c)

6 P1 P2

AC 24 V

MA

AC 24 V...230 V / 6 (2) A

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

S2 S3 S5 S6

S1 S4

(Q1

1)

(Q2

1)

B

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V 3-position, AC 230 V

46

34

G0

2

A100%

0%

(Y2

)

AC 230 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(N)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

4 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

M

46

34

G0

3

A100%

0%

DC 0...10 V

(G)

DC 0...10 V

(Y)

(G0

)

(U)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

2 9 S2 S3 S5 S6

1 8 S1 S4

(Q1

1)

(Q2

1)

B

AC 24 V...230 V / 6 (2) AAC 24 V

M

27

Page 28: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Dimensions shown in mm Technical data

Torque 15 Nm

Runtime for 90° 150 sec. (50 Hz)

opening and closing

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 4 VA (3-position)

Running 6 VA (modulating)

Holding 1.5 W (modulating)

Power consumption AC 230 V

Running 3 VA

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 6 to 20.5 mm round

6.4 to 13 mm square

20 mm min. length

Operating temperature -32…+55 °C

Storage temperature -32…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material die-cast aluminum alloy

Gear lubrication silicone-free

Dimensions 192 mm (H) x 81 mm

(W) x 63 mm (D)

Weight 1.1 kg

Submittalsummary OpenAir GEB series –

non-spring return, rotary movement

15 NmAC 24 V and AC 230 VModulating 3-position

N474

28

Page 29: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Type reference

Operating voltage Control Built-in control options

AC

24

V

± 2

0%

AC

23

0 V

±

10

%

DC

0…

10 V

3-p

osi

tio

n

Posi

tio

nfe

edb

ack

Du

al a

uxi

liary

swit

ches

Off

set

and

span

Inp

ut

sig

nal

se

lect

able

*)

GEB131.1E

GEB132.1E

GEB136.1E

GEB331.1E

GEB332.1E

GEB336.1E

GEB161.1E*

GEB163.1E

GEB164.1E

GEB166.1E*

*) DC 0…10 V or DC 2…10 V

Connection diagrams

46

21

G0

1

A100%

0%

(Y2

)

AC 0 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(G)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

1 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

AC 24 V

M

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V 3-position, AC 230 V

46

21

G0

2

A100%

0%

(Y2

)

AC 230 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(N)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

4 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

M

46

21

G0

3

A100%

0%

DC 0...10 V

(G)

DC 0...10 V

(Y)

(G0

)

(U)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

2 9 S2 S3 S5 S6

1 8 S1 S4

(Q1

1)

(Q2

1)

B

AC 24 V...230 V / 6 (2) AAC 24 V

M

29

Page 30: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Technical data

Torque 25 Nm

Runtime for 90° 150 sec. (50 Hz)

opening and closing

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 7 VA (3-position)

Running 8 VA (modulating)

Holding 1 W (modulating)

Power consumption AC 230 V

Running 5 VA

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 8 to 25.6 mm round

6 to 18 mm square

20 mm min. length

Operating temperature -32…+55 °C

Storage temperature -32…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material die-cast aluminum alloy

Gear lubrication silicone-free

Dimensions 300 mm (H) x 100 mm

(W) x 70.5 mm (D)

Weight 2.0 kg

Submittalsummary OpenAir GBB series –

non-spring return, rotary movement

25 NmAC 24 V and AC 230 VModulating 3-position

N474

30

0

73

85,8

90

0

100

27

,6

19

7

Ø 8

... 2

5,6

mm

6..

. 18

mm

max.17,5

P1..

.P3

1..

.9

S1..

.S6

24

,8

61,5

min

. 10

0

Dimensions shown in mm

30

Page 31: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Type reference

Operating voltage Control Built-in control options

AC

24

V

± 2

0%

AC

23

0 V

±

10

%

DC

0…

10 V

3-p

osi

tio

n

Posi

tio

nfe

edb

ack

Du

al a

uxi

liary

swit

ches

Off

set

and

span

GBB131.1E

GBB135.1E

GBB136.1E

GBB331.1E

GBB335.1E

GBB336.1E

GBB161.1E

GBB163.1E

GBB164.1E

GBB166.1E

Connection diagrams

46

21

G0

1

A100%

0%

(Y2

)

AC 0 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(G)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

1 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

AC 24 V

M

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V 3-position, AC 230 V

46

21

G0

2

A100%

0%

(Y2

)

AC 230 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(N)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

4 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

M

46

21

G0

3

A100%

0%

DC 0...10 V

(G)

DC 0...10 V

(Y)

(G0

)

(U)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

2 9 S2 S3 S5 S6

1 8 S1 S4

(Q1

1)

(Q2

1)

B

AC 24 V...230 V / 6 (2) AAC 24 V

M

31

Page 32: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Technical data

Torque 35 Nm

Runtime for 90° 150 sec. (50 Hz)

opening and closing

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 7 VA (3-position)

Running 8 VA (modulating)

Holding 1 W (modulating)

Power consumption AC 230 V

Running 5 VA

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 8 to 25.6 mm round

6 to 18 mm square

20 mm min. length

Operating temperature -32…+55 °C

Storage temperature -32…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material die-cast aluminum alloy

Gear lubrication silicone-free

Dimensions 300 mm (H) x 100 mm

(W) x 70.5 mm (D)

Weight 2.0 kg

Submittalsummary OpenAir GIB series –

non-spring return, rotary movement

Dimensions shown in mm

35 NmAC 24 V and AC 230 V Modulating 3-position

N474

30

0

73

85,8

90

0

100

27

,6

19

7

Ø 8

... 2

5,6

mm

6..

. 18

mm

max.17,5

P1..

.P3

1..

.9

S1..

.S6

24

,8

61,5

min

. 10

0

32

Page 33: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Type reference

Operating voltage Control Built-in control options

AC

24

V

± 2

0%

AC

23

0 V

±

10

%

DC

0…

10 V

3-p

osi

tio

n

Posi

tio

nfe

edb

ack

Du

al a

uxi

liary

swit

ches

Off

set

and

span

GIB131.1E

GIB135.1E

GIB136.1E

GIB331.1E

GIB335.1E

GIB336.1E

GIB161.1E

GIB163.1E

GIB164.1E

GIB166.1E

Connection diagrams

46

21

G0

1

A100%

0%

(Y2

)

AC 0 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(G)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

1 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

AC 24 V

M

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V 3-position, AC 230 V

46

21

G0

2

A100%

0%

(Y2

)

AC 230 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(N)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

4 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

M

46

21

G0

3

A100%

0%

DC 0...10 V

(G)

DC 0...10 V

(Y)

(G0

)

(U)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

2 9 S2 S3 S5 S6

1 8 S1 S4

(Q1

1)

(Q2

1)

B

AC 24 V...230 V / 6 (2) AAC 24 V

M

33

Page 34: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

125 NAC 24 V and AC 230 V Modulating 3-position

N474

Technical data

Force 125 N

Runtime for 60 mm 150 sec. (50 Hz)

opening and closing

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 3 VA (modulating)

Running 2 VA (3-position)

Holding 1 W (modulating)

Power consumption AC 230 V

Running 2 VA

Stroke 60 mm

Operating temperature -32…+55 °C

Storage temperature -32…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP40

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material durable plastic

Gear lubrication silicone-free

Dimensions 152 mm (H) x 68 mm

(W) x 59 mm (D)

Weight 0.48 kg

Submittalsummary OpenAir GDB series –

non-spring return, linear movement

Dimensions shown in mm

34

Page 35: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Type reference

Operating voltage Control Built-in control options

AC

24

V

± 2

0%

AC

23

0 V

±

10

%

DC

0…

10 V

3-p

osi

tio

n

Posi

tio

nfe

edb

ack

Du

al a

uxi

liary

swit

ches

Off

set

and

span

GDB131.2E

GDB132.2E

GDB136.2E

GDB331.2E

GDB332.2E

GDB336.2E

GDB161.2E

GDB163.2E

GDB164.2E

GDB166.2E

Connection diagrams

46

34

G0

1

100%

0%

(Y2

)

AC 0 V 0...1000

(a)

(G)

1

7 P3

(Y1

)

(b)

(c)

6 P1 P2

AC 24 V

MA

AC 24 V...230 V / 6 (2) A

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

S2 S3 S5 S6

S1 S4

(Q1

1)

(Q2

1)

B

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V 3-position, AC 230 V

46

34

G0

2

A100%

0%

(Y2

)

AC 230 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(N)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

4 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

M

46

34

G0

3

A100%

0%

DC 0...10 V

(G)

DC 0...10 V

(Y)

(G0

)

(U)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

2 9 S2 S3 S5 S6

1 8 S1 S4

(Q1

1)

(Q2

1)

B

AC 24 V...230 V / 6 (2) AAC 24 V

M

35

Page 36: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Technical data

Force 250 N

Runtime for 60 mm 150 sec. (50 Hz)

opening and closing

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 3 VA (modulating)

Running 2 VA (3-position)

Holding 1 W (modulating)

Power consumption AC 230 V

Running 2 VA

Stroke 60 mm

Operating temperature -32…+55 °C

Storage temperature -32…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP40

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material durable plastic

Gear lubrication silicone-free

Dimensions 152 mm (H) x 68 mm

(W) x 59 mm (D)

Weight 0.48 kg

Submittalsummary OpenAir GLB series –

non-spring return, linear movement

Dimensions shown in mm

250 NAC 24 V and AC 230 V Modulating 3-position

N474

36

Page 37: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Type reference

Operating voltage Control Built-in control options

AC

24

V

± 2

0%

AC

23

0 V

±

10

%

DC

0…

10 V

3-p

osi

tio

n

Posi

tio

nfe

edb

ack

Du

al a

uxi

liary

swit

ches

Off

set

and

span

GLB131.2E

GLB132.2E

GLB136.2E

GLB331.2E

GLB332.2E

GLB336.2E

GLB161.2E

GLB163.2E

GLB164.2E

GLB166.2E

Connection diagrams

46

34

G0

1

100%

0%

(Y2

)

AC 0 V 0...1000

(a)

(G)

1

7 P3

(Y1

)

(b)

(c)

6 P1 P2

AC 24 V

MA

AC 24 V...230 V / 6 (2) A

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

S2 S3 S5 S6

S1 S4

(Q1

1)

(Q2

1)

B

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V 3-position, AC 230 V

46

34

G0

2

A100%

0%

(Y2

)

AC 230 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(N)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

4 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

M

46

34

G0

3

A100%

0%

DC 0...10 V

(G)

DC 0...10 V

(Y)

(G0

)

(U)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

2 9 S2 S3 S5 S6

1 8 S1 S4

(Q1

1)

(Q2

1)

B

AC 24 V...230 V / 6 (2) AAC 24 V

M

37

Page 38: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Technical data

Force 400 N

Runtime for 57 mm 150 sec. (50 Hz)

opening and closing

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 4 VA (3-position)

Running 6 VA (modulating)

Holding 1.5 W (modulating)

Power consumption AC 230 V

Running 3 VA

Stroke 60 mm

Operating temperature -32…+55 °C

Storage temperature -32…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP40

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emissions standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material die-cast aluminum alloy

Gear lubrication silicone-free

Dimensions 212 mm (H) x 81 mm

(W) x 60 mm (D)

Weight 0.9 kg

Submittalsummary OpenAir GEB series –

non-spring return, linear movement

Dimensions shown in mm

400 NAC 24 V and AC 230 V Modulating 3-position

N474

38

Page 39: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Connection diagrams

46

21

G0

1

A100%

0%

(Y2

)

AC 0 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(G)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

1 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

AC 24 V

M

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V 3-position, AC 230 V

46

21

G0

2

A100%

0%

(Y2

)

AC 230 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(N)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

4 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

M

46

21

G0

3

A100%

0%

DC 0...10 V

(G)

DC 0...10 V

(Y)

(G0

)

(U)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

2 9 S2 S3 S5 S6

1 8 S1 S4

(Q1

1)

(Q2

1)

B

AC 24 V...230 V / 6 (2) AAC 24 V

M

Type reference

Operating voltage Control Built-in control options

AC

24

V

± 2

0%

AC

23

0 V

±

10

%

DC

0…

10 V

3-p

osi

tio

n

Posi

tio

nfe

edb

ack

Du

al a

uxi

liary

swit

ches

Off

set

and

span

Inp

ut

sig

nal

se

lect

able

*)

GEB131.2E

GEB132.2E

GEB136.2E

GEB331.2E

GEB332.2E

GEB336.2E

GEB161.2E*

GEB163.2E

GEB164.2E

GEB166.2E*

*) DC 0…10 V or DC 2…10 V

39

Page 40: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Technical data

Force 550 N

Runtime for 75 mm 150 sec. (50 Hz)

opening and closing

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 7 VA (3-position)

Running 8 VA (modulating)

Holding 1 W (modulating)

Power consumption AC 230 V

Running 5 VA

Stroke 75 mm

Operating temperature -32…+55°C

Storage temperature -32…+70°C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material die-cast aluminum alloy

Gear lubrication silicone-free

Dimensions 298 mm (H) x 100 mm

(W) x 67.5 mm (D)

Weight 2.0 kg

Submittalsummary OpenAir GBB series –

non-spring return, linear movement

Dimensions shown in mm

550 NAC 24 V and AC 230 VModulating 3-position

N474

40

Page 41: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Type reference

Operating voltage Control Built-in control options

AC

24

V

± 2

0%

AC

23

0 V

±

10

%

DC

0…

10 V

3-p

osi

tio

n

Posi

tio

nfe

edb

ack

Du

al a

uxi

liary

swit

ches

Off

set

and

span

GBB131.2E

GBB135.2E

GBB136.2E

GBB331.2E

GBB335.2E

GBB336.2E

GBB161.2E

GBB163.2E

GBB164.2E

GBB166.2E

Connection diagrams

46

21

G0

1

A100%

0%

(Y2

)

AC 0 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(G)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

1 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

AC 24 V

M

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V 3-position, AC 230 V

46

21

G0

2

A100%

0%

(Y2

)

AC 230 V 0...1000 AC 24 V...230 V / 6 (2) A

(a)

(N)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

4 S2 S3 S5 S6

7 P3 S1 S4

(Q1

1)

(Q2

1)

B

(Y1

)

(b)

(c)

6 P1 P2

M

46

21

G0

3

A100%

0%

DC 0...10 V

(G)

DC 0...10 V

(Y)

(G0

)

(U)

(Q1

2)

(Q1

4)

(Q2

4)

(Q2

2)

2 9 S2 S3 S5 S6

1 8 S1 S4

(Q1

1)

(Q2

1)

B

AC 24 V...230 V / 6 (2) AAC 24 V

M

41

Page 42: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Technical data

Torque 5 Nm

Runtime for 90° 150 sec. (50 Hz)

opening and closing

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 3 VA

Running + calibration 7.5 VA

Holding 1 W

Vnom range 1.00…2.55

Vmin range -20%…100%

Vmax range 20%…120%

Measuring range 0…400 Pa

Operating range 4…300 Pa

Accuracy (T = 25 °C, 990 mbar,

Vn = 1) ± 2.5%

Time constant 1 sec.

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 8 to 16 mm round

6 to 12.8 mm square

30 mm min. length

Operating temperature 0…+50 °C

Storage temperature -25…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material durable plastic

Gear lubrication silicone-free

Dimensions 137 mm (H) x 68 mm

(W) x 59.5 mm (D)

Weight 0.54 kg

Submittalsummary OpenAir GDB – VAV static air volume

compact controller, non-spring return

Dimensions shown in mm

5 NmAC 24 VModulating 3-position

N474

42

Page 43: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Type reference

Operating voltage

Control Built-in control options

AC

24

V

± 2

0%

DC

0…

10 V

3-p

osi

tio

n

30

0 P

a st

atic

d

iffe

ren

tial

p

ress

ure

se

nso

r

Y1 a

nd

Y2

o

pen

/clo

se

sig

nal

GDB181.1E/3

Connection diagrams

(YC

)

AC 24 V AC 0 V

(G0

)

2

8

(G)

1

M dP

(Y2

)

7

(Y1

)

6

AC 0 V

0..300Pa

NC

(U)

9

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V

(YC

)

AC 24 V AC 0 V

(G0

)

2

8

(G)

1

M dP

(Y2

)

7

(Y1

)

6

AC 0 V

0..300Pa

DC 0..10 V

(U)

9

43

Page 44: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Submittalsummary OpenAir GLB – VAV static air volume

compact controller, non-spring return

10 NmAC 24 VModulating 3-position

N474

Dimensions shown in mm Technical data

Torque 10 Nm

Runtime for 90° 150 sec. (50 Hz)

opening and closing

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 3 VA

Running + calibration 7.5 VA

Holding 1 W

Vnom range 1.00…2.55

Vmin range -20%…100%

Vmax range 20%…120%

Measuring range 0…400 Pa

Operating range 4…300 Pa

Accuracy (T = 25 °C, 990 mbar,

Vn = 1) ± 2.5%

Time constant 1 sec.

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 8 to 16 mm round

6 to 12.8 mm square

30 mm min. length

Operating temperature 0…+50 °C

Storage temperature -25…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material durable plastic

Gear lubrication silicone-free

Dimensions 137 mm (H) x 68 mm

(W) x 59.5 mm (D)

Weight 0.54 kg

44

Page 45: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Type reference

Operating voltage

Control Built-in control options

AC

24

V

± 2

0%

DC

0…

10 V

3-p

osi

tio

n

30

0 P

a st

atic

d

iffe

ren

tial

p

ress

ure

se

nso

r

Y1 a

nd

Y2

o

pen

/clo

se

sig

nal

GLB181.1E/3

Connection diagrams

(YC

)

AC 24 V AC 0 V

(G0

)

2

8

(G)

1

M dP

(Y2

)

7

(Y1

)

6

AC 0 V

0..300Pa

NC

(U)

9

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V

(YC

)

AC 24 V AC 0 V

(G0

)

2

8

(G)

1

M dP

(Y2

)

7

(Y1

)

6

AC 0 V

0..300Pa

DC 0..10 V

(U)

9

45

Page 46: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Submittalsummary OpenAir ASV –

VAV static air volume modular controller

Dimensions shown in mm Technical data

Frequency 50 / 60 Hz

Power consumption AC 24 V

Running 3 VA

Running + calibration 7.5 VA

Holding 1 W

Vnom range 1.00…2.55

Vmin range -20%…100%

Vmax range 20%…120%

Measuring range 0…400 Pa

Operating range 4…300 Pa

Accuracy (T = 25 °C, 990 mbar,

Vn = 1) ± 2.5%

Time constant 1 sec.

Operating temperature 0…+50 °C

Storage temperature -25…+70 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material durable plastic

Dimensions 135 mm (H) x 68 mm

(W) x 45 mm (D)

Weight 0.28 kg

AC 24 VModulating 3-position

N474

46

Page 47: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Type reference

Operating voltage

Control Built-in control options

AC

24

V

± 2

0%

DC

0…

10 V

3-p

osi

tio

n

30

0 P

a st

atic

d

iffe

ren

tial

p

ress

ure

se

nso

r

Y1 a

nd

Y2

o

pen

/clo

se

sig

nal

ASV181.1E/3

Connection diagrams

(YC

)

AC 24 V AC 0 V

(G)

1

8

(G)

1

dP

(Y2

)

7

(Y1

)

6

AC 0 V

0..300Pa

NC

(U)

9

AC 0 V

(G0

)

2

(Y1

1)

6

(Y2

2)

7

(G0

)

2

Modulating (DC 0…10 V),AC 24 V

3-position, AC 24 V

(YC

)

AC 24 V AC 0 V

(G)

1

8

(G)

1

dP

(Y2

)

7

(Y1

)

6

AC 0 V

0..300Pa

DC 0..10 V

(U)

9

AC 0 V

(G0

)

2

(Y1

1)

6

(Y2

2)

7

(G0

)

2

47

Page 48: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Submittalsummary OpenAir GGA actuators for fire protection

dampers – spring return, rotary movement

Technical data

Torque 18 Nm running and

18 Nm spring return

Runtime for 90° 90 sec. operating

15 sec. typical closing

Frequency 50 / 60 Hz

Power consumption AC/DC 24 V

Running 7 VA / 5 W

Holding 3 W

Power consumption AC 230 V

Running 8 VA / 6 W

Holding 4 W

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 8 x 8, 10 x 10,

12 x 12, 15 x 15 mm

Operating temperature -32…+50 °C

Storage temperature -32…+50 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material die-cast aluminum alloy

Gear lubrication silicone-free

Dimensions 264 mm (H) x 100 mm

(W) x 71 mm (D)

Weight 2.6 kg

Thermal cut-out

Connecting cable 0.9 m long

Switching temp. Tf1: outside the duct 72 °C

For sizing Tf2: inside the duct 72 °C

Degree of protection IP30

18 NmAC 24 V / DC 24…48 V and AC 230 V2-position

N474

Dimensions shown in mm

48

Page 49: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Connection diagrams

2-position, AC 24 V / DC 24…48 V

2-position, AC 230 V

** = 08 or 10 or 12 or 15 for form-fitted shaft adapters from 8 x 8 to 15 x 15 mm square

Type reference

Operating voltage Control Built-in control options

AC

24

V ±

20

%

DC

24…

48

V ±

20%

AC

23

0 V

±

10

%

2-p

osi

tio

n

Du

al a

uxi

liary

swit

ches

Ther

mal

cu

t-o

ut

GGA126.1E/**

GGA126.1E/T**

GGA326.1E/**

GGA326.1E/T**

49

Page 50: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Submittalsummary OpenAir GNA actuators for fire protection

dampers – spring return, rotary movement

Technical data

Torque 7 Nm running and

7 Nm spring return

Runtime for 90° 90 sec. operating

15 sec. typical closing

Frequency 50 / 60 Hz

Power consumption AC/DC 24 V

Running 5 VA / 3.5 W

Holding 2.5 W

Power consumption AC 230 V

Running 7 VA / 4.5 W

Holding 3.5 W

Angle of rotation 90° nominal

95° maximal

Shaft dimensions 8 x 8, 10 x 10, 12 x 12,

15 x 15 mm square

Operating temperature -32…+50 °C

Storage temperature -32…+50 °C

Ambient humidity <95% r.h.

(non-condensing)

Precabled connection 0.75 mm², 0.9 m long

Degree of protection IP54

CE conformity

Electromagnetic

Compatibility (EMC) 2004/108/EEC

Emission standards IEC/EN 61000-6-3

Immunity standards IEC/EN 61000-6-2

Material die-cast aluminum alloy

Gear lubrication silicone-free

Dimensions 178 mm (H) x 81 mm

(W) x 63 mm (D)

Weight 1.3 kg

Thermal cut-out

Connecting cable 0.9 m long

Switching temp. Tf1: outside the duct 72 °C

For sizing Tf2: inside the duct 72 °C

Degree of protection IP30

7 NmAC 24 V / DC 24…48 V and AC 230 V2-position

N474

Dimensions shown in mm

50

Page 51: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

Connection diagrams

2-position,AC 24 V / DC 24…48 V

2-position, AC 230 V

Type reference

Operating voltage Control Built-in control options

AC

24

V ±

20

%

DC

24…

48

V ±

20%

AC

23

0 V

±

10

%

2-p

osi

tio

n

Du

al a

uxi

liary

swit

ches

Ther

mal

cu

t-o

ut

GNA126.1E/**

GNA126.1E/T**

GNA326.1E/**

GNA326.1E/T**

** = 08 or 10 or 12 or 15 for form-fitted shaft adapters from 8 x 8 to 15 x 15 mm square

51

Page 52: OpenAir Damper Actuators - Siemens...Motors with low noise level The sturdy design, brushless motors and gear-trains that have already been run in ensure low-noise operation. Thus,

www.siemens.com/openair

Siemens Switzerland LtdBuilding Technologies DivisionInternational HeadquartersGubelstrasse 22CH-6301 ZugTel +41 41 724 24 24Fax +41 41 724 35 22

Siemens Building TechnologiesBrunel HouseSir William Siemens Square, FrimleyCamberleySurrey, GU16 8QDUnited KingdomTel +44 1276 696000Fax +44 1276 696133

Siemens LtdBuilding TechnologiesUnits 1006-1010/F, China Resources Building26 Harbour RoadWanchai, Hong KongTel +852 2870 7888Fax +852 2870 7880

The information in this document contains general descriptions of technical options available,

which do not always have to be present in individual cases. The required features should therefore

be specified in each individual case at the time of closing the contract.

Subject to change • Order no. Z-C00610402EN •

© Siemens Switzerland Ltd • Printed in Switzerland • 10802 Ni/Ah